ATTACHMENT 15 - Fire Alarm.pdf

PDF 6 MB Posted

Attached to
Y1DZ--Expand and Renovate B400 for Urgent and Primary Care (Minor) - Tomah
Solicitation number
36C77621B0009
Issued by

About this file

This solicitation is for a construction project to expand and renovate an existing building (B400) to support urgent and primary care services at the Department of Veterans Affairs Medical Center in Tomah, Wisconsin. The contractor shall complete all demolition and removal of existing structures, and furnish labor, materials, and work required by the attached drawings and specifications. The project includes expanding clinical space on the first floor for urgent care and renovating specialty care areas on the second floor. The contractor must prepare the site for building operations, including demolition. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.

View the file

Other files

File Type Posted
31 23 19 DEWATERING.pdf PDF
36C77621B0009 0003.pdf PDF
Drawings VF100 - VF101.pdf PDF
Technical Questions - FINAL - Tomah 8-2-21.pdf PDF
36C77621B0009 0002.pdf PDF
ATTACHMENT 17 - Construction Wage Rates - Monroe County - 7-9-21.pdf PDF
Site Visit Sign-in Sheet - Tomah - 9 AM - 7-12-21.pdf PDF
36C77621B0009 0001.pdf PDF
Site Visit Sign-in Sheet - Tomah - 10 AM - 7-13-21.pdf PDF
ATTACHMENT 20 - Site Visit Registration - Map.pdf PDF
36C77621B0009 - 6-29-21.pdf PDF
ATTACHMENT 7 - Fire Protection.pdf PDF
ATTACHMENT 16 - Contractor Core Work Hours.pdf PDF
ATTACHMENT 17 - Construction Wage Rates - Monroe County - 5-14-21.pdf PDF
ATTACHMENT 12 - Furniture.pdf PDF
ATTACHMENT 4 - Electrical.pdf PDF
ATTACHMENT 13 - Civil.pdf PDF
ATTACHMENT 11 - Architectual.pdf PDF
ATTACHMENT 8 - Equipment.pdf PDF
ATTACHMENT 1 - Specifications Final 6-21-21.pdf PDF
ATTACHMENT 6 - Plumbing.pdf PDF
ATTACHMENT 2 - General.pdf PDF
ATTACHMENT 19 - Contractor Safety - Environmental Form.docx DOCX document
ATTACHMENT 10 - Signage.pdf PDF
ATTACHMENT 18 - Limitations on Subcontracting - Construction.docx DOCX document
ATTACHMENT 5 - Mechanical.pdf PDF
ATTACHMENT 9 - Interiors.pdf PDF
ATTACHMENT 3 - Structural.pdf PDF
ATTACHMENT 14 - Hazard.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

S

S

SD

F

F

F

SD

SD

SD

SD

SD

SD

SD

S

A

S

SD

SF

SD

S

SD

S

S

S

SD

S

S

SD

S

S

S

S FSD

1 2 3 4 5 6 6.1 7 7.8 8 9 9.1 9.9 10 11 11.2 12 13 14 18171615

M.3

M

L

K.3

K

J.4

J.3

J

I.5

I.2

I

H.1

H

G

F.1

F

E

D

C

B

A

EX CP-6-1EX NP-1-1

EX LS-2-1

EX FA

EXISTING FIRE ALARM

WIRING CABINETS

EX FACU

EX CP 6-1

EX ECB-LS

EX ECB-CR

EX ECB-EQ EX REMOTE

GENERATOR PANEL

EX LOAD CENTER

EX NP-3-1

EX CP-4-1

EX NP-2-1

EX CP-2-1

EX CP-3-1

EX ELEVATOR

PANEL

EX NVP-1EX MDP(480)

EX DP-208-EQ

EX MSB(208)

EX ATS-LS

EX ATS(480)CR

EX DP-LS

EX ATS(208)CR

EX DP-CR(480)

EX DP-LQ

EX DP-CR(208)

EX T-CR

EX T-EQ

EX ATS-EQ

EX LS-1-1

EX CP-1-1

A. EXISTING CONDITION DRAWINGS INDICATE CONDITIONS AS THEY WERE

PLANNED FOR UNDER PREVIOUS PROJECTS, AND ARE INCLUDED FOR

REFERENCE ONLY. NOT ALL EXISTING DEVICES/ITEMS MAY BE SHOWN AND

ACTUAL CONDITIONS MAY VARY FROM THE PLANNED CONDITIONS. PROVIDE

DETAILED EVALUATION OF BUILDING SYSTEMS PRIOR TO CONSTRUCTION

AND REPORT DISCREPANCIES AND DEFICIENCIES TO ENGINEER. SYSTEMS

SHALL BE IN SIMILAR OR BETTER CONDITIONS AFTER COMPLETION OF

WORK.

B. FIELD VERIFY EXACT CONDITIONS PRIOR TO ANY DEMOLITION AND

MAINTAIN CONTINUITY OF ADJACENT CIRCUITS THAT REMAIN. REPORT ANY

DISCREPANCIES TO THE ENGINEER.

C. DISCONNECT AND REMOVE ELECTRICAL DEVICES NOTED AND/OR ON

WALLS THAT ARE BEING DEMOLISHED. REMOVE WIRING, CONDUIT,

SUPPORTS, ACCESSORIES, ETC BACK TO SOURCE. LABEL CIRCUIT

BREAKERS MADE UNUSED DURING DEMOLITION AS SPARE. REFER TO

ARCHITECTURAL PLANS FOR WALLS THAT ARE TO BE DEMOLISHED. WALLS

BEING REMOVED ARE SHOWN DASHED.

D. WHERE CIRCUITS TO REMAIN ARE INTERRUPTED DUE TO DEMOLITION,

CONTINUE THE CIRCUITS BY PROVIDING A J-BOX ABOVE CONCEALED

ACCESSIBLE CEILING, OR RE-FEED FROM AVAILABLE SOURCE.

E. ELECTRICAL DEVICES THAT HAVE BEEN INDICATED TO BE DISCONNECTED

AND REMOVED SHALL BE OFFERED TO THE OWNER AS SALVAGE UNLESS

INDICATED OTHERWISE. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR

DISPOSAL OF UNDESIRED ITEMS.

F. REFEED EXISTING CIRCUITS IN CONSTRUCTION LIMITS THAT CONFLICT

WITH NEW WORK. PROVIDE J-BOXES, CONDUIT, WIRING, AND OTHER

ACCESSORIES TO MAINTAIN INTEGRITY OF ELECTRICAL ITEMS. PROPERLY

SUPPORT ELECTRICAL ITEMS TO REMAIN IN CONSTRUCTION LIMITS.

PROVIDE REQUIRED COMPONENTS FOR PROPER INSTALLATION.

G. COORDINATE DEMOLITION WORK AS TO NOT REMOVE DEVICES/SYSTEMS

THAT ARE TO REMAIN AS EXISTING.

H. COORDINATE SYSTEM OUTAGES WITH OWNER.

I. MAINTAIN FIRE RATINGS WHERE CONDUITS ARE TO BE REMOVED FROM A

FIRE RATED STRUCTURE.

J. WHERE CEILINGS ARE REMOVED AND REPLACED; TEMPORARILY AND

PROPERLY SUPPORT ELECTRICAL DEVICES TO REMAIN.

K. PATCH AND RESTORE FINISHES WHERE DISTURBED OR DAMAGED DUE TO

ELECTRICAL DEMOLITION. REPAINT TO MATCH EXISTING WHERE

ELECTRICAL DEVICES ARE REMOVED.

L. PROVIDE STAINLESS STEEL BLANK COVER PLATES FOR ABANDONED

BOXES IN WALLS TO REMAIN.

M. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

N. FIRE ALARM SCOPE: REMOVE EXISTING FIRE ALARM DEVICES, WIRING, AND

RACEWAYS IN THE PROJECT AREAS IN THEIR ENTIRETY. PROVIDE NEW

DEVICES, WIRING, AND RACEWAYS AS INDICATED. MODIFY/EXPAND

EXISTING SILENT KNIGHT FACU AND ASSOCIATED EQUIPMENT PANELS TO

MEET NEW SYSTEM DESIGN.

EXAM

1027 EXAM

EXAM

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

OFFICE

OFFICE

DIRTY UTILTIY

OFFICE

WAITING

NURSE STATION

OFFICE

EXAM

CONFERENCE

EXAM

EXAM

EXAM

OFFICE

OFFICE

WOMEN

VISITOR

TOILET

TLT

MECH

IT

1005 OFFICE

OFFICE

OFFICE

EXAM

STAIR

WAITING / CIRCULATION

EXAM

EXAM

EXAM

NURSE STATION

1085 EXAM

EXAM

WOMEN TLT

EXAM

EXAM

OFFICE

STORAGE

1096A

STAFF TOILET

STAFF TOILET

AMBULANCE GARAGE

IT

1051B

ELECT

1051A

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

B400 KEY PLAN

AREA B

AREA

A1

AREA C

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:4

A

M

EF101

B400 - LEVEL 1 - FIRE ALARM

DEMOLITION PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B400 LEVEL 1 FLOOR PLAN - FIRE ALARM DEMOLITION

1 EXISTING REMOTE FIRE ALARM ANNUNCIATOR PANEL

SHALL BE DISCONNECTED AND STORED DURING

DEMOLITION TO BE REINSTALLED IN SIMILAR

LOCATION.

2 REMOVE AND RELOCATE EXISTING FIRE ALARM

MODULE PANEL.

3 EXISTING MAIN FIRE ALARM CONTROL UNIT - SILENT

KNIGHT IFP-2000ECS.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

Checked

A.NELSON

H

H

S F

SD

SD

S

1 2 3 4 5 6 6.1 7 7.8 8 9 9.1 9.9 10 11 11.2 12 13 14 18171615

M.3

M

L

K.3

K

J.4

J.3

J

I.5

I.2

I

H.1

H

G

F.1

F

E

D

C

B

A

EX NP-1-2

EX CP-6-2.1

EX CP-6-2

EX 4 CP-2-2

EX CP-2-2 EX CP-1-2

EX LS1-2

TEMPORARY

2007A

SOILED UTILITY

A. EXISTING CONDITION DRAWINGS INDICATE CONDITIONS AS THEY WERE

PLANNED FOR UNDER PREVIOUS PROJECTS, AND ARE INCLUDED FOR

REFERENCE ONLY. NOT ALL EXISTING DEVICES/ITEMS MAY BE SHOWN AND

ACTUAL CONDITIONS MAY VARY FROM THE PLANNED CONDITIONS. PROVIDE

DETAILED EVALUATION OF BUILDING SYSTEMS PRIOR TO CONSTRUCTION

AND REPORT DISCREPANCIES AND DEFICIENCIES TO ENGINEER. SYSTEMS

SHALL BE IN SIMILAR OR BETTER CONDITIONS AFTER COMPLETION OF

WORK.

B. FIELD VERIFY EXACT CONDITIONS PRIOR TO ANY DEMOLITION AND

MAINTAIN CONTINUITY OF ADJACENT CIRCUITS THAT REMAIN. REPORT ANY

DISCREPANCIES TO THE ENGINEER.

C. DISCONNECT AND REMOVE ELECTRICAL DEVICES NOTED AND/OR ON

WALLS THAT ARE BEING DEMOLISHED. REMOVE WIRING, CONDUIT,

SUPPORTS, ACCESSORIES, ETC BACK TO SOURCE. LABEL CIRCUIT

BREAKERS MADE UNUSED DURING DEMOLITION AS SPARE. REFER TO

ARCHITECTURAL PLANS FOR WALLS THAT ARE TO BE DEMOLISHED. WALLS

BEING REMOVED ARE SHOWN DASHED.

D. WHERE CIRCUITS TO REMAIN ARE INTERRUPTED DUE TO DEMOLITION,

CONTINUE THE CIRCUITS BY PROVIDING A J-BOX ABOVE CONCEALED

ACCESSIBLE CEILING, OR RE-FEED FROM AVAILABLE SOURCE.

E. ELECTRICAL DEVICES THAT HAVE BEEN INDICATED TO BE DISCONNECTED

AND REMOVED SHALL BE OFFERED TO THE OWNER AS SALVAGE UNLESS

INDICATED OTHERWISE. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR

DISPOSAL OF UNDESIRED ITEMS.

F. REFEED EXISTING CIRCUITS IN CONSTRUCTION LIMITS THAT CONFLICT

WITH NEW WORK. PROVIDE J-BOXES, CONDUIT, WIRING, AND OTHER

ACCESSORIES TO MAINTAIN INTEGRITY OF ELECTRICAL ITEMS. PROPERLY

SUPPORT ELECTRICAL ITEMS TO REMAIN IN CONSTRUCTION LIMITS.

PROVIDE REQUIRED COMPONENTS FOR PROPER INSTALLATION.

G. COORDINATE DEMOLITION WORK AS TO NOT REMOVE DEVICES/SYSTEMS

THAT ARE TO REMAIN AS EXISTING.

H. COORDINATE SYSTEM OUTAGES WITH OWNER.

I. MAINTAIN FIRE RATINGS WHERE CONDUITS ARE TO BE REMOVED FROM A

FIRE RATED STRUCTURE.

J. WHERE CEILINGS ARE REMOVED AND REPLACED; TEMPORARILY AND

PROPERLY SUPPORT ELECTRICAL DEVICES TO REMAIN.

K. PATCH AND RESTORE FINISHES WHERE DISTURBED OR DAMAGED DUE TO

ELECTRICAL DEMOLITION. REPAINT TO MATCH EXISTING WHERE

ELECTRICAL DEVICES ARE REMOVED.

L. PROVIDE STAINLESS STEEL BLANK COVER PLATES FOR ABANDONED

BOXES IN WALLS TO REMAIN.

M. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

N. FIRE ALARM SCOPE: REMOVE EXISTING FIRE ALARM DEVICES, WIRING, AND

RACEWAYS IN THE PROJECT AREAS IN THEIR ENTIRETY. PROVIDE NEW

DEVICES, WIRING, AND RACEWAYS AS INDICATED. MODIFY/EXPAND

EXISTING SILENT KNIGHT FACU AND ASSOCIATED EQUIPMENT PANELS TO

MEET NEW SYSTEM DESIGN.

OFFICE

UNOCCUPIED

CLEAN UTILITY

ELEC.

LAB

MECHANICAL

OFFICE

2015A

TOILET, STAFF

2030A

UTILITY ROOM, SOILED

TOILET

LOCKER ROOM

LAB

TREATMENT ROOM

EXAM/ TREATMENT ROOM

EXAM/ TREATMENT ROOM

TREATMENT ROOM

EXAM/TREATMENT ROOM

TREATMENT ROOM

STAIR

S9

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

B400 KEY PLAN

AREA B

AREA

A1

AREA C

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:4

A

M

EF102

B400 - LEVEL 2 - FIRE ALARM

DEMOLITION PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B400 LEVEL 2 FLOOR PLAN - FIRE ALARM DEMOLITION

1 EXISTING FIRE ALARM POWER PANELS.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

SD

CO

S

S

J

H

SD SD

SD SD

S

SD

407.A

407.B1

407.C1

407.D1

407.E

407.F

407.G1

407.H

407.I

407.J

407.K

407.L

407.M

407.N

407.14407.11 407.12.1407.12

407.9407.7

407.41407.4407.3407.21

J.39

J.40

J.41

407.H2

407.H1

407.13.1

OPEN OFFICE

RESTROOM

MECH / ELEC

OPEN OFFICE

RESTROOM

EX CP3-3

EX CP1-3

EX LS1-3

EX NP1-3

DEDUCT ALT 1:

REMOVE WORK

ASSOCIATED WITH

B407 NORTH.

DEDUCT ALT 2:

REMOVE WORK

ASSOCIATED WITH

B407 SOUTH.

DEDUCT ALT 2:

REMOVE WORK

ASSOCIATED WITH

B407 SOUTH.

A. EXISTING CONDITION DRAWINGS INDICATE CONDITIONS AS THEY WERE

PLANNED FOR UNDER PREVIOUS PROJECTS, AND ARE INCLUDED FOR

REFERENCE ONLY. NOT ALL EXISTING DEVICES/ITEMS MAY BE SHOWN AND

ACTUAL CONDITIONS MAY VARY FROM THE PLANNED CONDITIONS. PROVIDE

DETAILED EVALUATION OF BUILDING SYSTEMS PRIOR TO CONSTRUCTION

AND REPORT DISCREPANCIES AND DEFICIENCIES TO ENGINEER. SYSTEMS

SHALL BE IN SIMILAR OR BETTER CONDITIONS AFTER COMPLETION OF

WORK.

B. FIELD VERIFY EXACT CONDITIONS PRIOR TO ANY DEMOLITION AND

MAINTAIN CONTINUITY OF ADJACENT CIRCUITS THAT REMAIN. REPORT ANY

DISCREPANCIES TO THE ENGINEER.

C. DISCONNECT AND REMOVE ELECTRICAL DEVICES NOTED AND/OR ON

WALLS THAT ARE BEING DEMOLISHED. REMOVE WIRING, CONDUIT,

SUPPORTS, ACCESSORIES, ETC BACK TO SOURCE. LABEL CIRCUIT

BREAKERS MADE UNUSED DURING DEMOLITION AS SPARE. REFER TO

ARCHITECTURAL PLANS FOR WALLS THAT ARE TO BE DEMOLISHED. WALLS

BEING REMOVED ARE SHOWN DASHED.

D. WHERE CIRCUITS TO REMAIN ARE INTERRUPTED DUE TO DEMOLITION,

CONTINUE THE CIRCUITS BY PROVIDING A J-BOX ABOVE CONCEALED

ACCESSIBLE CEILING, OR RE-FEED FROM AVAILABLE SOURCE.

E. ELECTRICAL DEVICES THAT HAVE BEEN INDICATED TO BE DISCONNECTED

AND REMOVED SHALL BE OFFERED TO THE OWNER AS SALVAGE UNLESS

INDICATED OTHERWISE. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR

DISPOSAL OF UNDESIRED ITEMS.

F. REFEED EXISTING CIRCUITS IN CONSTRUCTION LIMITS THAT CONFLICT

WITH NEW WORK. PROVIDE J-BOXES, CONDUIT, WIRING, AND OTHER

ACCESSORIES TO MAINTAIN INTEGRITY OF ELECTRICAL ITEMS. PROPERLY

SUPPORT ELECTRICAL ITEMS TO REMAIN IN CONSTRUCTION LIMITS.

PROVIDE REQUIRED COMPONENTS FOR PROPER INSTALLATION.

G. COORDINATE DEMOLITION WORK AS TO NOT REMOVE DEVICES/SYSTEMS

THAT ARE TO REMAIN AS EXISTING.

H. COORDINATE SYSTEM OUTAGES WITH OWNER.

I. MAINTAIN FIRE RATINGS WHERE CONDUITS ARE TO BE REMOVED FROM A

FIRE RATED STRUCTURE.

J. WHERE CEILINGS ARE REMOVED AND REPLACED; TEMPORARILY AND

PROPERLY SUPPORT ELECTRICAL DEVICES TO REMAIN.

K. PATCH AND RESTORE FINISHES WHERE DISTURBED OR DAMAGED DUE TO

ELECTRICAL DEMOLITION. REPAINT TO MATCH EXISTING WHERE

ELECTRICAL DEVICES ARE REMOVED.

L. PROVIDE STAINLESS STEEL BLANK COVER PLATES FOR ABANDONED

BOXES IN WALLS TO REMAIN.

M. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

N. FIRE ALARM SCOPE: REMOVE EXISTING FIRE ALARM DEVICES, WIRING, AND

RACEWAYS IN THE PROJECT AREAS IN THEIR ENTIRETY. PROVIDE NEW

DEVICES, WIRING, AND RACEWAYS AS INDICATED. MODIFY/EXPAND

EXISTING SILENT KNIGHT FACU AND ASSOCIATED EQUIPMENT PANELS TO

MEET NEW SYSTEM DESIGN.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

B407 KEY PLAN

AREA A

KEY PLAN

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:5

A

M

EF103-407

B407 - LEVEL 3 - FIRE ALARM

DEMOLITION PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B407 LEVEL 3 FLOOR PLAN - FIRE ALARM DEMOLITION

1 EXISTING FIRE ALARM POWER PANELS.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

F

S

S

SD

S

S

S S

SD

S

S

S

S

S

S

S

SD

SD

S

S S

SD

S

S

S

S

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD SD

SD

SD

SD

SD

F

SD

A

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

SD

S

S

S

S

S

HD

SSSD

SD

SD

S

SD

S

S

F

SD

S

1 2 3 4 5 6 6.1 7 7.8 8 9 9.1 9.9 10 11 11.2 12 13 14 18171615

M.3

M

L

K.3

K

J.4

J.3

J

I.5

I.2

I

H.1

H

G

F.1

F

E

D

C

B

A

CONF

CONSULT ROOM 2

CONSULT ROOM 1

CLEAN UTILITY

EXAM 10

CHAIR EXAM

1085b

EXAM 6

ANTE ROOM

1108A

OFFICE

EXAM 8

ALCOVE

WHEELCHAIR ALCOVE

EQ. ALCOVE

EXAM 13 / CONSULT RM 3

EXAM 2

TEAM

WORK

STATIONS

WAITING

1032B

1101A

TEAM

AREA

1086A

TEAM

AREA

PATIENT TLT

TLT

1022B

STAFF TLT

1019B

MECH

STAFF TOILET

1100B

BARIATRIC/

WOMENS

HEALTH

TLT

1104B

TLT

TLT/SHWR

EXAM 2 - NEGATIVE PRESS

1104A

MEDS

EXAM 4

EXAM 5 BARIATRIC/ WOMENS HEALTH

1100A

1032A

RECEPT

CHECK

IN/OUT

WEIGH AREA

MEDS

CORRIDOR

OC11

EXAM 12

FAMILY TLT

NURSE MANAGER OFFICE

OFFICE

CLEAN SUPPLY

EXAM 7

SOILED UTILITY / SPD

CORRIDOR

OC13

EXAM 1

TLT

1108C

TELEHEALTH

TELEHEALTH

EXAM 9

HALLWAY

OC14

LOGISTICS STORAGE

WAITING

RECEPTION

1080C

EXAM 7

CLEAN UTLITY

SOILED UTILITY

CORRIDOR

OC20

1099A

MENTAL

HEALTH

STAFF LOUNGE

1108B

EXAM

1-

NEGATIVE

PRESS

VESTIBULE

TRIAGE

STOR

EXAM 8

EXAM 11

DPE

DPE

DPE

DPE

RTU-10S

RTU-10R

AHU-1

LACTATION

FA

EXISTING FIRE ALARM

WIRING CABINETS

EXISTING MAIN FIRE ALARM

CONTROL UNIT.

EX FACU

EX CP-6-1 EX NP-1-1

EX LS-2-1

EX CP-5-1

IT

1051B

ELECT

1051A

CLG

CLG

CLG

30,CLG

30,CLG

75,CLG

30,CLG

110,CLG

30,CLG

CLG

CLG

CLG

CLG

CLG

CLG

CLG

CLG

CLG

CLG

CLG

CLG

CLG

CLG

NP-1-1

CP-1-1

CLG

75,CLG

30,CLG

30,CLG

30,CLG

CLG

30,CLG

CLG

30,CLG

CLG

CLG

30,CLG

CLG

CLG

CLG

15,CLG

CLG

CLG

CLG

CP-8-1 NP-5-1

EX ECB-EQ

EX REMOTE

GENERATOR PANEL

EX ATS-LS

EX ATS(480)CR

EX ATS-EQEX DP-LS

EX ATS(208)CR EX DP-LQ

EX DP-CR(480)

EX T-CR

EX DP-CR(208)

EX DP-208-EQ

EX T-EQ

EX ECB-LS

EX ECB-CR

EX LOAD CENTER

EX NP-3-1

EX MSB(208)

EX CP-3-1

EX ELEVATOR

PANEL

EX NVP-1

EX MDP(480)

EX CP-2-1

EX NP-2-1

EX CP-4-1

30,CLG

15,CLG

FSD FSD

CP-1-1-1 CP-1-1-1

2 2

DPE

DPE

FSD

CP-1-1-1

DPE

DPE

CP-8-1-39

FSD

HAC

CLG

30,CLG

30,CLG

75,CLG

EX

EX

LS-1-1

AHU-1

EX NP-4-1

EX CP-7-1

75,CLG

CLG

FSD

CP-8-1-39

DPE2

A. ALIGN DEVICES VERTICALLY WHERE LIGHTING, POWER, SPECIAL SYSTEMS,

AND FIRE ALARM DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE

INDICATED CLOSE TO OTHER DEVICES.

B. REFER TO THE ARCHITECTURAL ELEVATION AND DETAIL DRAWINGS FOR

COORDINATION OF ELECTRICAL DEVICES.

C. CUTTING, DRILLING, AND/OR BORING THROUGH STRUCTURAL MEMBERS IS

NOT ACCEPTABLE.

D. PROVIDE FIRE RATED SEALS ON PENETRATIONS IN FIRE RATED FLOORS

AND WALLS. COORDINATE RATED LOCATIONS WITH LIFE SAFETY CODE

PLAN DRAWINGS.

E. PROVIDE INSULATED BUSHINGS FOR ROUGH-IN AND CONDUIT SLEEVE

LOCATIONS PRIOR TO INSTALLATION OF ANY CABLING.

F. BRANCH CIRCUITS CONDUCTOR LENGTHS FROM PANEL LONGER THAN 100’

FOR 120V AND 200' FOR 277V SHALL BE #10 OR LARGER FOR ENTIRE

LENGTH OF CIRCUIT FOR LINE, NEUTRAL, AND GROUND WIRES.

G. PROVIDE DEDICATED NEUTRAL FOR EACH MULTIWIRE BRANCH CIRCUIT

PHASE CONDUCTOR.

H. FOR DEVICE LOCATIONS SPECIFIED FOR ROUGH-IN, UNLESS NOTED

OTHERWISE, PROVIDE DOUBLE GANG J-BOX WITH SINGLE GANG MUD RING

AND BLANK COVER PLATE. ROUTE 1"C. UP INTO CONCEALED ACCESSIBLE

CEILING SPACE. PROVIDE BUSHINGS AND PULL STRING IN CONDUIT.

I. INSTALL SMOKE DETECTORS AT LEAST 3'-0” FROM ANY HVAC SUPPLY

DIFFUSER.

J. PROVIDE DUCT SMOKE DETECTORS FOR CONTROL OF SMOKE DAMPERS.

PROVIDE ONE CONTROL RELAY AND ONE ALARM INDICATOR FOR EACH

DETECTOR. PROVIDE 120V POWER AT EACH DAMPER LOCATION.

COORDINATE INSTALLATION WITH MECHANICAL CONTRACTOR. INSTALL

DETECTORS A MINIMUM OF 6 DUCT WIDTHS FROM ANY AIR INLET. PROVIDE

SAMPLING TUBE THAT EXTENDS INTO THE AIR STREAM, AND MOUNT

DETECTOR IN CENTER OF VERTICAL DIMENSION OF THE DUCT. DUCT

SMOKE DETECTORS INSTALLED FOR INDIVIDUAL CONTROL OF FIRE/SMOKE

DAMPERS SHALL BE INSTALLED A MAXIMUM OF 5' FROM THE DAMPER, WITH

NO AIR OUTLETS OR INLETS BETWEEN THE DETECTOR AND THE DAMPER.

K. SET EACH FIRE ALARM SYSTEM SPEAKER UNITS TO BEST SUIT INDIVIDUAL

ROOM CHARACTERISTICS AND TO ENSURE ALARM SOUND LEVELS OF 15db

OVER AMBIENT LEVELS. FIRE ALARM SPEAKER/STROBE AND STROBE ONLY

DEVICES SHALL BE WHITE.

L. PROVIDE CIRCUIT BREAKER 'LOCK-ON' FOR FIRE ALARM POWER CIRCUITS.

M. DEVICES INSTALLED IN 2X2 CEILING TILE SHALL BE CENTERED IN THE TILE.

DEVICES INSTALLED IN 2X4 CEILING TILE SHALL BE CENTERED IN 2X2

PORTION OF 2X4 TILE.

N. FIRE ALARM STROBES SHALL BE DUAL 'CLEAR FIRE' AND 'AMBER ALERT'

DEVICES.

O. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

P. FIRE ALARM SCOPE: REMOVE EXISTING FIRE ALARM DEVICES, WIRING, AND

RACEWAYS IN THE PROJECT AREAS IN THEIR ENTIRETY. PROVIDE NEW

DEVICES, WIRING, AND RACEWAYS AS INDICATED. MODIFY/EXPAND

EXISTING SILENT KNIGHT FACU AND ASSOCIATED EQUIPMENT PANELS TO

MEET NEW SYSTEM DESIGN.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

B400 KEY PLAN

AREA B

AREA

A1

AREA C

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:5

A

M

EF201

B400 - LEVEL 1 - FIRE ALARM

PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B400 LEVEL 1 FLOOR PLAN - FIRE ALARM

1 EXISTING REMOTE FIRE ALARM ANNUNCIATOR PANEL

SHALL BE REINSTALLED. EXTEND/REFEED EXISTING

WIRING AS REQUIRED TO NEW LOCATION.

2 PROVIDE DUCT SMOKE DETECTOR - PHOTO ELECTRIC

TYPE AND 120V POWER CONNECTION AT MOTORIZED

DAMPER INSTALLED BY M.C. COORDINATE SMOKE

DETECTOR INSTALLATION AND CONNECTION WITH

M.C.

3 NEW LOCATION OF EXISTING FA POWER MODULE

PANEL. EXTEND CIRCUITS TO NEW LOCATION.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

S

S

SD

S

S

S

SD

SD

SD

SD

S

F

SD

S

SD

SD

S

S

S

S S

1 2 3 4 5 6 6.1 7 7.8 8 9 9.1 9.9 10 11 11.2 12 13 14 18171615

M.3

M

L

K.3

K

J.4

J.3

J

I.5

I.2

I

H.1

H

G

F.1

F

E

D

C

B

A

INFUSION ROOM

MECH

EXAM 1

CLEAN UTILITY - LOGISTICS

TLT

TEAM WORK AREA

MED

EQUIPMENT

STORAGE

EXAM 5

EXAM 3

EXAM 2

EXAM 4

CORRIDOR

OC22

CLEAN LINENS

SOILED UTILITY

75,CLG

75,CLG

15,CLG

15,CLG

30,CLG

EX NP-1-2

EX CP-1-2

EX CP-2-2

EX CP-6-2

CLG

CLG

CLG

CLG

CLG

CLG

CLG

SOILED UTILITY

EX CP-6-2.1

EX 4 CP-2-2

EX LS1-2

A. ALIGN DEVICES VERTICALLY WHERE LIGHTING, POWER, SPECIAL SYSTEMS,

AND FIRE ALARM DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE

INDICATED CLOSE TO OTHER DEVICES.

B. REFER TO THE ARCHITECTURAL ELEVATION AND DETAIL DRAWINGS FOR

COORDINATION OF ELECTRICAL DEVICES.

C. CUTTING, DRILLING, AND/OR BORING THROUGH STRUCTURAL MEMBERS IS

NOT ACCEPTABLE.

D. PROVIDE FIRE RATED SEALS ON PENETRATIONS IN FIRE RATED FLOORS

AND WALLS. COORDINATE RATED LOCATIONS WITH LIFE SAFETY CODE

PLAN DRAWINGS.

E. PROVIDE INSULATED BUSHINGS FOR ROUGH-IN AND CONDUIT SLEEVE

LOCATIONS PRIOR TO INSTALLATION OF ANY CABLING.

F. BRANCH CIRCUITS CONDUCTOR LENGTHS FROM PANEL LONGER THAN 100’

FOR 120V AND 200' FOR 277V SHALL BE #10 OR LARGER FOR ENTIRE

LENGTH OF CIRCUIT FOR LINE, NEUTRAL, AND GROUND WIRES.

G. PROVIDE DEDICATED NEUTRAL FOR EACH MULTIWIRE BRANCH CIRCUIT

PHASE CONDUCTOR.

H. FOR DEVICE LOCATIONS SPECIFIED FOR ROUGH-IN, UNLESS NOTED

OTHERWISE, PROVIDE DOUBLE GANG J-BOX WITH SINGLE GANG MUD RING

AND BLANK COVER PLATE. ROUTE 1"C. UP INTO CONCEALED ACCESSIBLE

CEILING SPACE. PROVIDE BUSHINGS AND PULL STRING IN CONDUIT.

I. INSTALL SMOKE DETECTORS AT LEAST 3'-0” FROM ANY HVAC SUPPLY

DIFFUSER.

J. PROVIDE DUCT SMOKE DETECTORS FOR CONTROL OF SMOKE DAMPERS.

PROVIDE ONE CONTROL RELAY AND ONE ALARM INDICATOR FOR EACH

DETECTOR. PROVIDE 120V POWER AT EACH DAMPER LOCATION.

COORDINATE INSTALLATION WITH MECHANICAL CONTRACTOR. INSTALL

DETECTORS A MINIMUM OF 6 DUCT WIDTHS FROM ANY AIR INLET. PROVIDE

SAMPLING TUBE THAT EXTENDS INTO THE AIR STREAM, AND MOUNT

DETECTOR IN CENTER OF VERTICAL DIMENSION OF THE DUCT. DUCT

SMOKE DETECTORS INSTALLED FOR INDIVIDUAL CONTROL OF FIRE/SMOKE

DAMPERS SHALL BE INSTALLED A MAXIMUM OF 5' FROM THE DAMPER, WITH

NO AIR OUTLETS OR INLETS BETWEEN THE DETECTOR AND THE DAMPER.

K. SET EACH FIRE ALARM SYSTEM SPEAKER UNITS TO BEST SUIT INDIVIDUAL

ROOM CHARACTERISTICS AND TO ENSURE ALARM SOUND LEVELS OF 15db

OVER AMBIENT LEVELS. FIRE ALARM SPEAKER/STROBE AND STROBE ONLY

DEVICES SHALL BE WHITE.

L. PROVIDE CIRCUIT BREAKER 'LOCK-ON' FOR FIRE ALARM POWER CIRCUITS.

M. DEVICES INSTALLED IN 2X2 CEILING TILE SHALL BE CENTERED IN THE TILE.

DEVICES INSTALLED IN 2X4 CEILING TILE SHALL BE CENTERED IN 2X2

PORTION OF 2X4 TILE.

N. FIRE ALARM STROBES SHALL BE DUAL 'CLEAR FIRE' AND 'AMBER ALERT'

DEVICES.

O. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

P. FIRE ALARM SCOPE: REMOVE EXISTING FIRE ALARM DEVICES, WIRING, AND

RACEWAYS IN THE PROJECT AREAS IN THEIR ENTIRETY. PROVIDE NEW

DEVICES, WIRING, AND RACEWAYS AS INDICATED. MODIFY/EXPAND

EXISTING SILENT KNIGHT FACU AND ASSOCIATED EQUIPMENT PANELS TO

MEET NEW SYSTEM DESIGN.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

B400 KEY PLAN

AREA B

AREA

A1

AREA C

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:5

A

M

EF202

B400 - LEVEL 2 - FIRE ALARM

PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B400 LEVEL 2 FLOOR PLAN - FIRE ALARM

1 EXISTING FIRE ALARM POWER PANELS.

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

SD

S

S

SD

J

S

S

S

SD

SD

OFFICE

3790A

MECH / ELECT

3790C

OFFICE

3775B

OPEN OFFICE

OFFICE

3790B

BEDROOM

BEDROOM

MECHANICAL ROOM

3780A

MECH / ELEC

MECHANICAL ROOM

BEDROOM

MEDS

3711A

BEDROOM

STORAGE

DINING

3749A

BREAK

3765 BEDROOM

WARD

READING

BEDROOM

TREATMENT

CT CLINIC

TOILET

3744A

CLOSET

RESTROOM

RESTROOM

SHOWERS

3784A

DRESSING

DRESSING

SHOWERS

3715A

Room

DAY ROOM

TOILET

CLOSET

3750A

CORRIDOR

7C36

CORRIDOR

7C31

DATA CLOSET

3772A

ELECTRICAL

CORRIDOR

7C38

CORRIDOR

7C39

OFFICE

STAIR

S4

CORRIDOR

7C37

CORRIDOR

7C32

HAC

3736A

NURSES

BEDROOM

BEDROOM

READING

UTILITY

WARD

STAIR

S6

DINING

LOCKERS

WARD

BEDROOM

BEDROOM

CLEAN LINENS

Room

CLOSET

ELEVATOR LOBBY

7C35

ELEVATOR

CORRIDOR

CORRIDOR

7C33

BEDROOM

LAUNDRY

OPEN OFFICE

407.A

407.B1

407.C1

407.D1

407.E

407.F

407.G1

407.H

407.I

407.J

407.K

407.L

407.M

407.N

407.14407.11 407.12.1407.12

407.9407.7

407.41407.4407.3407.21

J.39

J.40

J.41

407.H2

407.H1

407.13.1

EX CP3-3

EX CP1-3

EX LS1-3

EX NP1-3

EX FACU

PE

PE

75,CLG

75,CLG

75,CLG

75,CLG

CLG

CLG

CLG

DPE

DPE

DEDUCT ALT 1:

REMOVE WORK

ASSOCIATED WITH

B407 NORTH.

DEDUCT ALT 2:

REMOVE WORK

ASSOCIATED WITH

B407 SOUTH.

DEDUCT ALT 2:

REMOVE WORK

ASSOCIATED WITH

B407 SOUTH.

A. ALIGN DEVICES VERTICALLY WHERE LIGHTING, POWER, SPECIAL SYSTEMS,

AND FIRE ALARM DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE

INDICATED CLOSE TO OTHER DEVICES.

B. REFER TO THE ARCHITECTURAL ELEVATION AND DETAIL DRAWINGS FOR

COORDINATION OF ELECTRICAL DEVICES.

C. CUTTING, DRILLING, AND/OR BORING THROUGH STRUCTURAL MEMBERS IS

NOT ACCEPTABLE.

D. PROVIDE FIRE RATED SEALS ON PENETRATIONS IN FIRE RATED FLOORS

AND WALLS. COORDINATE RATED LOCATIONS WITH LIFE SAFETY CODE

PLAN DRAWINGS.

E. PROVIDE INSULATED BUSHINGS FOR ROUGH-IN AND CONDUIT SLEEVE

LOCATIONS PRIOR TO INSTALLATION OF ANY CABLING.

F. BRANCH CIRCUITS CONDUCTOR LENGTHS FROM PANEL LONGER THAN 100’

FOR 120V AND 200' FOR 277V SHALL BE #10 OR LARGER FOR ENTIRE

LENGTH OF CIRCUIT FOR LINE, NEUTRAL, AND GROUND WIRES.

G. PROVIDE DEDICATED NEUTRAL FOR EACH MULTIWIRE BRANCH CIRCUIT

PHASE CONDUCTOR.

H. FOR DEVICE LOCATIONS SPECIFIED FOR ROUGH-IN, UNLESS NOTED

OTHERWISE, PROVIDE DOUBLE GANG J-BOX WITH SINGLE GANG MUD RING

AND BLANK COVER PLATE. ROUTE 1"C. UP INTO CONCEALED ACCESSIBLE

CEILING SPACE. PROVIDE BUSHINGS AND PULL STRING IN CONDUIT.

I. INSTALL SMOKE DETECTORS AT LEAST 3'-0” FROM ANY HVAC SUPPLY

DIFFUSER.

J. PROVIDE DUCT SMOKE DETECTORS FOR CONTROL OF SMOKE DAMPERS.

PROVIDE ONE CONTROL RELAY AND ONE ALARM INDICATOR FOR EACH

DETECTOR. PROVIDE 120V POWER AT EACH DAMPER LOCATION.

COORDINATE INSTALLATION WITH MECHANICAL CONTRACTOR. INSTALL

DETECTORS A MINIMUM OF 6 DUCT WIDTHS FROM ANY AIR INLET. PROVIDE

SAMPLING TUBE THAT EXTENDS INTO THE AIR STREAM, AND MOUNT

DETECTOR IN CENTER OF VERTICAL DIMENSION OF THE DUCT. DUCT

SMOKE DETECTORS INSTALLED FOR INDIVIDUAL CONTROL OF FIRE/SMOKE

DAMPERS SHALL BE INSTALLED A MAXIMUM OF 5' FROM THE DAMPER, WITH

NO AIR OUTLETS OR INLETS BETWEEN THE DETECTOR AND THE DAMPER.

K. SET EACH FIRE ALARM SYSTEM SPEAKER UNITS TO BEST SUIT INDIVIDUAL

ROOM CHARACTERISTICS AND TO ENSURE ALARM SOUND LEVELS OF 15db

OVER AMBIENT LEVELS. FIRE ALARM SPEAKER/STROBE AND STROBE ONLY

DEVICES SHALL BE WHITE.

L. PROVIDE CIRCUIT BREAKER 'LOCK-ON' FOR FIRE ALARM POWER CIRCUITS.

M. DEVICES INSTALLED IN 2X2 CEILING TILE SHALL BE CENTERED IN THE TILE.

DEVICES INSTALLED IN 2X4 CEILING TILE SHALL BE CENTERED IN 2X2

PORTION OF 2X4 TILE.

N. FIRE ALARM STROBES SHALL BE DUAL 'CLEAR FIRE' AND 'AMBER ALERT'

DEVICES.

O. COORDINATE DEMOLITION AND NEW WORK AS TO NOT REMOVE SYSTEMS,

DEVICES, AND/OR ACCESSORIES NECESSARY FOR AREAS IN LATER

PHASES.

P. FIRE ALARM SCOPE: REMOVE EXISTING FIRE ALARM DEVICES, WIRING, AND

RACEWAYS IN THE PROJECT AREAS IN THEIR ENTIRETY. PROVIDE NEW

DEVICES, WIRING, AND RACEWAYS AS INDICATED. MODIFY/EXPAND

EXISTING SILENT KNIGHT FACU AND ASSOCIATED EQUIPMENT PANELS TO

MEET NEW SYSTEM DESIGN.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES

B407 KEY PLAN

AREA A

KEY PLAN

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

B

IM

/6

-3

B

E x p a n d

R e lo c a te

U rg e n t

C a re A n d

R e n o v a te s t F lo o r P a ti e n t C a re

/6

-3

.4

.M

E P

.r v t

/1

/2

:4

:0

A

M

EF203-407

B407 - LEVEL 3 - FIRE ALARM

PLAN

Expand and Renovate B400 for

Urgent and Primary Care

500 E Veterans St, Tomah, WI 54660

676-19-327

400/407

05/20/2021 A.BARTSCH T.INGLE

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

ISSUED FOR

CONSTRUCTION

SCALE: 1/8" = 1'-0"

B407 LEVEL 3 FLOOR PLAN - FIRE ALARM

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

C&S Engineers, Inc.

2575 E. Camelback Rd, Suite 740 Phoenix, AZ 85016 Phone: 602-997-7536 Fax: 602-997-7592 www.cscos.com

Obernel 1331 Tyler Street NE Suite 201 Minneapolis, MN 55413 Phone: (612) 249-5600 www.obernel.com

Hinman Consulting Engineers 601 California Street Suite 1710 San Francisco, CA 94108 Phone: 415-621-4423 www.hce.com

TRIPLE C - THE A&E GROUP

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

48553 5/20/2021 Anthony R. Nelson

GI000-COVER SHEET
GI001-PROJECT SHEET INDEX
GI050-GENERAL NOTES
GI101-B400 -LEVEL 1 -FIRE AND LIFE SAFETY PLAN & CODE DATA
GI102-B400 -LEVEL 2 -FIRE AND LIFE SAFETY PLAN & CODE DATA
GI104-B407 -LEVEL 3 -FIRE AND LIFE SAFETY PLAN & CODE DATA -DEDUCT ALT #1 & #2
GI201-INFECTION CONTROL PLAN & INTERIM LIFE
GC101-PROJECT PHASING
GC102-PHASING PLANS
H101-B400 -LEVEL 1 -HAZARDOUS MATERIAL ABATEMENT
H102-B400 -LEVEL 2 -HAZARDOUS MATERIAL ABATEMENT
H103-407-B407 -LEVEL 3 -HAZARDOUS MATERIAL ABATEMENT
HC101-B400 -LEVEL 1 -HAZARDOUS MATERIAL ABATEMENT -PIPING
VF100-CONTROL POINT SITE PLAN
VF101-viuvTiiig i iuvCIVIL SURVEY PLAN
CD101-CIVIL DEMOLITION PLAN
CS101-CIVIL SITE PLAN
COo-CIVIL SITE PLAN STAGING AREA
CG101-CIVIL GRADING PLAN
CG501-CIVIL DETAIL SHEET 1
CG502-CIVIL DETAIL SHEET 2
CU101-CIVIL UTILITY PLAN
SJ001-GENERAL STRUCTURAL NOTES
SJ002-GENERAL STRUCTURAL NOTES CONTINUED
SJ003-SPECIAL INSPECTIONS
SB100-B400 -LEVEL 1 -FOUNDATION PLAN -OVERALL
SB101-B400 -LEVEL 1 - FOUNDATION PLAN -AREA A
SF102-B400 -LEVEL 2 - FRAMING PLAN -OVERALL
SF103-B400 -LEVEL 2 -ROOF FRAMING PLAN -AREA A
SF201-FRAMING ELEVATIONS
SF202-FRAMING ELEVATIONS
SF203-FRAMING ELEVATIONS
SF501-TYPICAL DETAILS
SF502-TYPICAL DETAILS
SF503-TYPICAL DETAILS
SF504-TYPICAL DETAILS
SF505-TYPICAL DETAILS
SB510-FOUNDATION DETAILS
SF520-FRAMING DETAILS
SF521-FRAMING DETAILS
SF530-COLD-FORMED STEEL FRAMING
SF601-GRAPHICAL COLUMN SCHEDULE
AE000-SYMBOLS, & GENERAL NOTES
AS101-ARCHITECTURAL SITE PLAN
AG100-FLOOR PLAN -LEVEL 1, URGENT CARE CENTER PROGRAM PLAN
AG103-FLOOR PLAN -LEVEL 1, CLINICAL SPACE PROGRAM PLAN
AG200-FLOOR PLAN -LEVEL 2, SPECIALTY CARE PROGRAM PLAN
AG201A-FLOOR PLAN -LEVEL 3 -SWING SPACE LAYOUT B407-DEDUCT ALT #1 & #2
AD101-B400 -LEVEL 1 -DEMOLITION PLAN
AD102-B400 -LEVEL 2 -DEMOLITION PLAN
AD103-407-B407 -LEVEL 3 -DEMOLITION PLAN -DEDUCT AL #1 & #2
AD121-B400 -LEVEL 1 -DEMOLITION RCP
AD122-B400 -LEVEL 2 -DEMOLITION RCP
AD123-407-B407 -LEVEL 3 -DEMOLITION RCP -DEDUCT ALT #1 & #2
AE101-B400 -LEVEL 1 -FLOOR PLAN -OVERALL
AE102-B400 -LEVEL 2 -FLOOR PLAN -OVERALL
AE103-407-B407 -LEVEL 3 -FLOOR PLAN -DEDUCT ALT #1& #2
AE104-B400 -ROOF PLAN -OVERALL
AC101-B400 -LEVEL 1 -REFLECTED CEILING PLAN
AC102-B400 -LEVEL 2 -REFLECTED CEILING PLAN
AC103-407-B407 -LEVEL 3 -REFLECTED CEILING PLAN -DEDUCT ALT #1 & #2
AE201-B400 EXTERIOR ELEVATIONS
AE201-407-B407 EXTERIOR ELEVATIONS -DEDUCT ALT #1 & #2
AE202-B400 EXTERIOR ELEVATIONS
AE301-BUILDING SECTIONS
AE320-WALL SECTIONS
AE321-WALL SECTIONS
AE322-WALL SECTIONS
AE401-B400 -LEVEL 1 -ENLARGED FLOOR PLANS
AE401A-B400 -LEVEL 1 -ENLARGED FLOOR PLANS
AE401B-B400 -LEVEL 1 -ENLARGED FLOOR PLANS
AE401C-B400 -LEVEL 1 -ENLARGED FLOOR PLANS
AE401D-B400 -LEVEL 1 -ENLARGED FLOOR PLANS
AE402-B400 -LEVEL 2 -ENLARGED FLOOR PLANS
AE500-EXTERIOR WALL AND ROOF ASSEMBLIES
AE520-EXTERIOR SECTION DETAILS
AE521-EXTERIOR SECTION DETAILS
AE551-DETAILS -INTERIOR
AE552-DETAILS -INTERIOR
AE560-DOOR DETAILS
AE561-DOOR AND LOUVER DETAILS
AE601-DOOR WINDOW & LOUVER SCHEDULES
AE710-ARCHITECTURAL DOOR, WINDOW & FRAME TYPES
AE720-STANDARD PARTITION TYPES
AE721-PARTITION HEAD DETAILS
AE722-PARTITION FRAMING DETAILS
AE730-TYPICAL MOUNTING HEIGHTS
AG900-B400 RENDERINGS
AG901-B400 RENDERINGS
AG902-B400/ B407 RENDERINGS
AW001-SIGNAGE ABBREVIATIONS, SYMBOLS, GENERAL NOTES & DETAILS
AW101-B400 -LEVEL 1 -SIGNAGE PLAN
AW102-B400 -LEVEL 2 -SIGNAGE PLAN
AW103-B407 -LEVEL 3 -SIGNAGE PLAN -DEDUCT ALT #1 & #2
IN001-NTERIOR FINISH ABBREVIATIONS, SYMBOLS, GENERAL NOTES & FINISH BOARDS
IN101-B400 -LEVEL 1 -INTERIOR FINISH PLAN -OVERALL
IN101A-B400 -LEVEL 1 -INTERIOR FINISH PLANS -AREA & A1
IN101B-B400 -LEVEL 1 -INTERIOR FINISH PLANS -AREA
IN102C-B400 -LEVEL 2 -INTERIOR FINISH PLANS -AREA C
IN103D-B407 -LEVEL 3 -INTERIOR FINISH PLANS -AREA A, B & C -DEDUCT ALT #1& #2
IN501-INTERIOR FINISH DETAILS
IN601-INTERIOR FINISH LEGEND AND SCHEDULES
IF101AB-B400 -LEVEL 1 -INTERIOR FURNITURE PLAN -FOR REFERENCE ONLY
IF102C-B400 -LEVEL 2 -INTERIOR FURNITURE PLAN -FOR REFERENE ONLY
IF103D-B407 -LEVEL 3 -INTERIOR FURNITURE PLAN -FOR REFERENCE ONLY -DEDUCT ALT #1 & #2
IF104-FURNITURE PLAN -FOR REFERENCE ONLY
IF105-FURNITURE PLAN -FOR REFERENCE ONLY
IF106-FURNITURE PLAN -FOR REFERENCE ONLY
Q001-EQUIPMENT SCHEDULE
Q101AB-B400 -LEVEL 1 -EQUIPMENT PLANS
Q101C-B400 -LEVEL 2 -EQUIPMENT PLAN
F000-FIRE PROTECTION ABBREVIATIONS AND SYMBOLS
FD101-B400 -LEVEL 1 - FIRE PROTECTION DEMOLITION PLAN
FD102-B400 -LEVEL 2 - FIRE PROTECTION DEMOLITION PLAN
FD103-407-B407 -LEVEL 3 - FIRE PROTECTION DEMOLITION PLAN
FP101-B400 -LEVEL 1 - FIRE PROTECTION PLAN
FP102-B400 -LEVEL 2 - FIRE PROTECTION PLAN
FP103-407-B407 -LEVEL 3 - FIRE PROTECTION PLAN
P-000-PLUMBING ABBREVIATIONS AND SYMBOLS
PD100-B400 -FOUNDATION -PLUMBING DEMOLITION PLAN
PD101-B400 -LEVEL 1 -PLUMBING DEMOLITION PLAN
PD102-B400 -LEVEL 2 -PLUMBING DEMOLITION PLAN
PD201-B400 -LEVEL 1 -MED GAS DEMOLITION PLAN
P-100-B400 -FOUNDATION -PLUMBING PLAN
P-101-B400 -LEVEL 1 -PLUMBING PLAN
P-102-B400 -LEVEL 2 -PLUMBING PLAN
P103-407-B407 -LEVEL 3 -PLUMBING PLAN
P-201-B400 -LEVEL 1 -MED GAS PLAN
P-300-B400 -PLUMBING ENLARGED PLANS
P-301-B400 -PLUMBING ENLARGED PLANS
P-302-B400 -PLUMBING ENLARGED PLANS
P-303-B400 -PLUMBING ENLARGED PLANS
P-304-B400 -PLUMBING ENLARGED PLANS
P-305-B400 -PLUMBING ENLARGED PLANS
P-400-PLUMBING RISERS
P-401-PLUMBING RISERS
P-402-PLUMBING RISERS
P-403-PLUMBING RISERS
P-404-PLUMBING RISERS
P-500-PLUMBING DETAILS
P-700-PLUMBING SCHEDULES
M-000-MECHANICAL ABBREVIATIONS AND SYMBOLS
MD101-B400 -LEVEL 1 -HVAC DEMOLITION PLAN
MD101A-B400 -LEVEL 1 -HVAC DEMO PLAN -DEDUCT ALT. #4
MD102-B400 -LEVEL 2 -HVAC DEMOLITION PLAN
MD103-407-B407 -LEVEL 3 -HVAC DEMOLITION PLAN
MD200-B400 -FOUNDATION -HVAC PIPING DEMOLITION PLAN
MD201-B400 -LEVEL 1 -HVAC PIPING DEMOLITION PLAN
MD202-B400 -LEVEL 2 -HVAC PIPING DEMOLITION PLAN
M-100-B400 -LEVEL 1 -HVAC TEMPORARY PLAN
M-101-B400 -LEVEL 1 - HVAC PLAN
M-101A-B400 -LEVEL 1 - HVAC PLAN -DEDUCT ALT. #4
M-102-B400 -LEVEL 2 - HVAC PLAN
M-103-407-B407 -LEVEL 3 - HVAC PLAN
MP200-B400 -FOUNDATION -HVAC PIPING PLAN
MP201-B400 -LEVEL 1 -HVAC PIPING PLAN
MP202-B400 -LEVEL 2 -HVAC PIPING PLAN
MP203-407-B407 -LEVEL 3 -HVAC PIPING PLAN
M-400-ENLARGED MECHANICAL PLANS
M-401-ENLARGED MECHANICAL PLANS
M-402-ENLARGED MECHANICAL PLANS -DEDUCT ALT. #4
M-500-MECHANICAL DETAILS
M-501-MECHANICAL DETAILS
M-502-MECHANICAL DETAILS
M-600-MECHANICAL SECTIONS
M-700-MECHANICAL SCHEDULES
M-800-MECHANICAL CONTROLS
M-801-MECHANICAL CONTROLS
M-802-MECHANICAL CONTROLS
E-000-ELECTRICAL ABBREVIATIONS AND SYMBOLS
ED101-B400 -LEVEL 1 - ELECTRICAL DEMOLITION PLAN
ED102-B400 -LEVEL 2 - ELECTRICAL DEMOLITION PLAN
ED103-407-B407 -LEVEL 3 - ELECTRICAL DEMOLITION PLAN
EL101-B400 -LEVEL 1 - LIGHTING PLAN
EL102-B400 -LEVEL 2 - LIGHTING PLAN
EL103-407-B407 -LEVEL 3 - LIGHTING PLAN
EL111-B400 -LEVEL 1 -LIGHTING CALCS
EL112-B400 -LEVEL 2 -LIGHTING CALCS
EL113-407-B407 -LEVEL 3 -LIGHTING CALCS
EP101-B400 -LEVEL 1 - POWER PLAN
EP102-B400 -LEVEL 2 - POWER PLAN
EP103-407-B407 -LEVEL 3 - POWER PLAN
EY101-B400 -LEVEL 1 - SPECIAL SYSTEMS PLAN
EY102-B400 -LEVEL 2 - SPECIAL SYSTEMS PLAN
EY103-407-B407 -LEVEL 3 - SPECIAL SYSTEMS PLAN
E-501-ELECTRICAL DETAILS
E-601-B400 ELECTRICAL DIAGRAMS
E-602-B400 ELECTRICAL DIAGRAMS
E-700-ELECTRICAL SCHEDULES
EF101-B400 -LEVEL 1 - FIRE ALARM DEMOLITION PLAN
EF102-B400 -LEVEL 2 - FIRE ALARM DEMOLITION PLAN
EF103-407-B407 -LEVEL 3 - FIRE ALARM DEMOLITION PLAN
EF201-B400 -LEVEL 1 - FIRE ALARM PLAN
EF202-B400 -LEVEL 2 - FIRE ALARM PLAN
EF203-407-B407 -LEVEL 3 - FIRE ALARM PLAN

File details come from the government source that posted it. Updated .