ATTACHMENT 20 - Telecom 5 of 6.pdf

PDF 4 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction West Palm Beach Federal contract opportunity
Solicitation number
36C77623B0045
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation is for an electronic health record modernization infrastructure upgrades construction project at the Department of Veterans Affairs facility in West Palm Beach, Florida. Key requirements include upgrading telecommunications infrastructure through installation of new fiber optic cabling and pathways, structured cabling, grounding systems, and telecommunications rooms. The project involves construction of new underground duct banks and manholes, as well as relocation of existing cabling and demolition of outdated infrastructure. Response due date is not provided. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction West Palm Beach, newest first.
File Type Posted
36C77623B0045 0003.pdf PDF
Clarifications to Technical Questions 9-5-23.pdf PDF
Updated Drawings for Clarifications.pdf PDF
Cart Lift Motor Photos.pdf PDF
36C77623B0045 0002.pdf PDF
Technical Questions - FINAL - West Palm Beach 8-21-23.pdf PDF
Photos for Responses to Questions 124 and 127.pdf PDF
Map of Wells Question 66.pdf PDF
36C77623B0045 0001.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Palm Beach 7-7-23.pdf PDF
Site Visit Sign-in Sheet - West Palm Beach 7-19-23.pdf PDF
ATTACHMENT 4 - Civil 1 of 5.pdf PDF
ATTACHMENT 5 - Civil 2 of 5.pdf PDF
ATTACHMENT 16 - Telecom 1 of 6.pdf PDF
ATTACHMENT 18 - Telecom 3 of 6.pdf PDF
ATTACHMENT 19 - Telecom 4 of 6.pdf PDF
ATTACHMENT 23 - Limitations on Subcontracting - Construction.docx DOCX document
ATTACHMENT 24 - Construction Wage Rates - Palm Beach 3-24-23.pdf PDF
36C77623B0045 - 7-6-23.pdf PDF
ATTACHMENT 6 - Civil 3 of 5.pdf PDF
ATTACHMENT 11 - Mechanical 1 of 2.pdf PDF
ATTACHMENT 14 - Security.pdf PDF
ATTACHMENT 15 - Structural.pdf PDF
ATTACHMENT 17 - Telecom 2 of 6.pdf PDF
ATTACHMENT 21 - Telecom 6 of 6.pdf PDF
ATTACHMENT 25 - Contractor Safety - Environmental Form.docx DOCX document
ATTACHMENT 1 - Specifications.pdf PDF
ATTACHMENT 2 - General.pdf PDF
ATTACHMENT 8 - Civil 5 of 5.pdf PDF
ATTACHMENT 9 - Electrical.pdf PDF
ATTACHMENT 12 - Mechanical 2 of 2.pdf PDF
ATTACHMENT 13 - Plumbing.pdf PDF
ATTACHMENT 3 - Architectural.pdf PDF
ATTACHMENT 7 - Civil 4 of 5.pdf PDF
ATTACHMENT 10 - Fire Protection.pdf PDF
ATTACHMENT 22 - Contractor Core Work Hours.pdf PDF
ATTACHMENT 26 - Site Visit Instructions.pdf PDF
Show all 37

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C B

C

B

C B

C B

C

B

C B

C B

C

B

C B

C B

C

B

C B

(2) SS24

RACK 1

RACK 2

ELEC.

PANEL

ELEC.

PANEL

(2) SS24

ENTRANCE RM 2

B23-TN3052B23-TN305 3

"x

12"x4"

"x

" 1 "x

12"x4"

RACK 1 RACK 2RACK 1 RACK 2

4 4 4

8 9

RACK 1RACK 2

8 9

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t

P a lm B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.D

C .T

R

.r v t

/2

/2

:1

:4

A

M

B23-TN305

ENLARGED TELECOM PLANS -

SERVICE ENTRANCE B 23-104

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B23

1/2" = 1'-0"1

ENLARGED TELECOM PLAN - SEB 23-104

KEYED NOTES:#

GENERAL NOTES:

N.T.S.2

23-104 - RACK ELEVATIONS

1. ANGLED FIBER PANEL, 12 HDX CASSETTE 144 FIBER, 1 RU

2. SPACE RESERVED FOR RACK MOUNTED POWER EQUIPMENT.

3. ZONE PDU

4. VERTICAL CABLE MANAGEMENT

5. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND L21-20R

OUTPUT.

6. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24) C13 (6) C19 (6)

5-20R OUTLETS, 208V OUTPUT.

7. 30 A, 208 V, 3-PHASE ZONE PDU BASE UNIT -REAR CIRCUITS WITH FOUR NEMA L21-20R

AND SIX NEMA 5-20 OUTLETS AND TWO 10' POWER CORDS TERMINATING IN NEMA

L21-30P.

8. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

9. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

10. RACK BONDING BUSBAR (R.B.B.) FOR IT EQUIPMENT ONLY. NON-IT EQUIPMENT SHALL

NOT USE THE SAME BONDING BUSBAR.

11. 3/4" AC GRADE TRADE SIZE FIRE-RATED PLYWOOD BACKBOARD PAINTED HIGH-GLOSS

WHITE WITH TWO COATS OF FIRE-RESISTANT PAINT, 8" AFF. (TYP.)

N.T.S.3

23-104 - POWER ELEVATION AND SCHEMATIC

PLAN NORTH1 1 2 3 4 5

1/2" = 1'-0"

FEETSCALE

PRINT SHEET IN COLOR

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION AND FINAL

LOCATION WITH THE ELECTRICAL AND MECHANICAL DIVISION. REFER TO ELECTRICAL,

MECHANICAL AND PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP, AND ANY OTHER

FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE HILTI SPEED SLEEVE LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO FLOOR PLAN

DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND CONDUITS OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 10 00 STRUCTURED

CABLING AND SECTION 27 05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE DRILLING.

CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE RISER SLEEVES.

REFER TO SECTION 07 84 00 FIRESTOPPING.

7. PHASING OF THE WORK IN THE DATA CENTER IMPACTS WORK IN THE TRS AND

HORIZONTAL CABLING. COORDINATE WORK SCHEDULES WITH THE COR.

8. GOVERNMENT EQUIPMENT WILL BE RELOCATED BY GOVERNMENT IT PERSONNEL.

CONTRACTOR WILL HAVE TECHNICIANS AVAILABLE TO PROVIDE SUPPORT DURING

OUTAGES AND CUT-OVERS. COORDINATE WORK WITH THE COR.

9. CONTRACTOR SHALL PROVIDE CABLE MANAGEMENT FINGERS, AIR DAMS, BAYING

SEAL KITS, CABLE BRUSHES, AND GROMMETS MANUFACTURED AND COMPATIBLE

WITH CABINETS.

10. CONTRACTOR SHALL PROVIDE MTP, FIBER OPTIC TRUNK CABLES FOR SIDE A AND

SIDE B BACKBONE FROM THE DATA CENTER TO EACH TELECOMMUNICATIONS ROOM.

COORDINATE WITH COR.

11. CONTRACTOR SHALL PROVIDE FIBER OPTIC PATCH CABLES FOR SIDE A AND SIDE B

FROM THE FIBER OPTIC DISTRIBUTOR TO EQUIPMENT CABINETS. COORDINATE WITH

COR.

12. CONTRACTOR SHALL VERIFY FIBER OPTIC CABLES MEASUREMENTS PRIOR TO

ORDERING. COORDINATE WITH COR.

Revisions: Date:

IRR

C overed Patio

DIESEL TANK

DIESEL TANK

METAL STEPS

S

IG

N SIGN

SI

G

N

SI

G

N

C A N

O P Y

C O V E

R

ALUMINUM TRAILOR WITH ALUMINUM HANDI-CAP RAMP & STEPS

GAT E

GATE

GATE

G

ATE

W P B

W P B

WPB

TR

A

N S

T R A N S

WPB

WPB

WPB

W P B

E C B

W P B

W P B

W P BW P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W P B

W

PB

W P B

W P B

W P B

W P B

W P B

WPB

WPB

W P B

W P B W P B

W P B W P B

W P B

W P B

W P B

W P B

WPB

WPB

WPB

WPB

WPB

TRANS

W P B

W P B

WPB

H R

H R

HR

H R

H R

H R

H R

HR

HR

B U

S

BUS

B U

S

Gate

Gate

G at e

Gate

Gate

Gate

GATE

G A

T E

DUMPSTER

PAD

CONTROL BOXS

CONTROL BOXS

CONTROL BOXS

CONTROL BOXS

KEY PAD

KEY PAD

KEY PAD

KEY PAD

VAULT

KEY PAD

EXISTING

WETLANDS AREA

B-3

P ar ki n g G ar ag e

Parking Garage

B-15

B-13 B-14

B-22

B-1

B-12

B-7

B-4

B-19

B-10

B-20

Parking Deck

B -6

Gate

Gate

G at e

Gate

Gate

Gate

GATE

G A

T E

X

M H

MH

DUCT BANK - (D)

DUCT BANK - (D)

DUCT BANK - (B)

DUCT BANK - (gg)

DUCT BANK - (hh)

DUCT BANK - (aa)

DUCT BANK - (bb)

DUCT BANK - (dd)

DUCT BANK - (cc)

DUCT BANK - (ee)

DUCT BANK - (ff)

DUCT BANK - (ii)

DUCT BANK - (jj)

DUCT BANK - (kk)

DUCT BANK - (ll)

DUCT BANK - (mm)

DUCT BANK - (oo)

DUCT BANK - (pp)

DUCT BANK - (NN)

DUCT BANK - (A)

DUCT BANK - (A)

2 5

2 11

4 9

4 10

6 11

2 11

11 242

11 252

11 242

2 11 24

2 11

2 23

11 6

11 6 11

11 6

26 26

27 27

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/3

/2

:5

:0

P

M

TN400

SITE PLAN - TELECOM ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

1. EXISTING (A-SIDE) SERVICE PROVIDER SITE ENTRANCE

2. PATHWAY FOR A-SIDE SERVICE PROVIDER

3. NEW (B-SIDE) SERVICE PROVIDER SITE ENTRANCE

4. PATHWAY FOR B-SIDE SERVICE PROVIDER

5. A-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 1 - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 3 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 4 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 6 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 7 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

F. BUILDING 10 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

G. BUILDING 12 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

H. BUILDING 14 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

I. BUILDING 16 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

J. BUILDING 19 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

K. BUILDING 22 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

6. A-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 14 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 22 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

7. A-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 14 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

8. A-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 1 - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 3 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 4 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 6 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 7 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

F. BUILDING 10 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

G. BUILDING 12 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

H. BUILDING 16 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

I. BUILDING 19 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

9. B-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 1 - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 3 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 4 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 6 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 7 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

F. BUILDING 10 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

G. BUILDING 12 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

H. BUILDING 14 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

I. BUILDING 16 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

J. BUILDING 19 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

K. BUILDING 22 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

10. B-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 1 - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 3 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 4 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 6 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 7 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

F. BUILDING 10 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

G. BUILDING 12 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

H. BUILDING 16 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

I. BUILDING 19 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

J. BUILDING 22 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

11. B-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 1 - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 3 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 4 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 6 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 7 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

F. BUILDING 10 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

G. BUILDING 12 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

H. BUILDING 16 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

I. BUILDING 19 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

12. A-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 1 - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 4 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 6 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 7 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 12 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

13. A-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 3 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 10 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 16 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 19 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

14. A-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 3 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 16 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 19 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

15. BACKBONE PATHWAY FOR:

A. BUILDING 3 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 16 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 19 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 10 B-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

16. A-SIDE BACKBONE PATHWAY FOR:

A. BUILDING 1 - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 6 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 7 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 12 - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

17. BACKBONE PATHWAY FOR:

A. BUILDING 1 A-SIDE - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 6 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 7 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 12 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 4 B-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

18. BACKBONE PATHWAY FOR:

A. BUILDING 1 A-SIDE - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 6 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 12 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 4 B-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 7 B-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

19. BACKBONE PATHWAY FOR:

A. BUILDING 1 A-SIDE - (27) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 6 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

C. BUILDING 4 B-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

D. BUILDING 7 B-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

E. BUILDING 12 B-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

20. BACKBONE PATHWAY FOR:

A. BUILDING 6 A-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

B. BUILDING 6 B-SIDE - (1) 24-STRAND SINGLE MODE INDOOR/OUTDOOR RATED OS2 FOC

21. PROVIDE (4) 4" CONDUITS FROM SITE FOR A-SIDE BACKBONE PATHWAY. ROUTE CONDUITS

TIGHT TO PARKING STRUCTURE ABOVE AND INTO BASEMENT INTERSTITIAL LEVEL.

22. PROVIDE (2) 4" CONCRETE ENCASED CONDUIT DUCT BANK REFER TO DETAIL 1 ON SHEET

TN505 FOR DUCTBANK DETAIL.

23. PROVIDE (4) 4" CONCRETE ENCASED CONDUIT DUCT BANK REFER TO DETAIL 2 ON SHEET

TN505 FOR DUCTBANK DETAIL.

24. PROVIDE (6) 4" CONCRETE ENCASED CONDUIT DUCT BANK REFER TO DETAIL 3 ON SHEET

TN505 FOR DUCTBANK DETAIL.

25. PROVIDE (6) 4" CONCRETE ENCASED CONDUIT DUCT BANK OVER CULVERT REFER TO

DETAIL 4 ON SHEET TN505 FOR DUCTBANK DETAIL.

26. NEW TELECOMMUNICATIONS HAND HOLE. REFER TO DETAIL 5 ON SHEET TN505.

27. NEW TELECOMMUNICATIONS MANHOLE. REFER TO DETAIL 1 ON SHEET TN506.

KEYED NOTES:#

GENERAL NOTES:

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION AND FINAL LOCATION

WITH THE ELECTRICAL AND MECHANICAL DIVISION. REFER TO ELECTRICAL, MECHANICAL

AND PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND CONDUITS OF THE SIZE AS

INDICATED ON THE PLANS. REFER TO SECTION 27 10 00 STRUCTURED CABLING AND

SECTION 27 05 33 CONDUITS AND BOXES FOR COMMUNICATIONS SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE DRILLING. CONTRACTOR

SHALL COORDINATE WITH THE COR BEFORE BEGINNING DRILLING.

4. PHASING OF THE WORK IN THE DATA CENTER IMPACTS WORK IN THE TRS AND HORIZONTAL

CABLING. COORDINATE WORK SCHEDULES WITH THE COR.

5. GOVERNMENT EQUIPMENT WILL BE RELOCATED BY GOVERNMENT IT PERSONNEL.

CONTRACTOR WILL HAVE TECHNICIANS AVAILABLE TO PROVIDE SUPPORT DURING

OUTAGES AND CUT-OVERS. COORDINATE WORK WITH THE COR.

6. CONTRACTOR SHALL PROVIDE , MTP, FIBER OPTIC TRUNK CABLES FOR SIDE A AND SIDE B

BACKBONE FROM THE DATA CENTER TO EACH TELECOMMUNICATIONS ROOM.

COORDINATE WITH COR.

7. CONTRACTOR SHALL PROVIDE , FIBER OPTIC PATCH CABLES FOR SIDE A AND SIDE B FROM

THE FIBER OPTIC DISTRIBUTOR TO EQUIPMENT CABINETS. COORDINATE WITH COR.

8. CONTRACTOR SHALL VERIFY FACTORY, PRE-TERMINATED, FIBER OPTIC CABLES

MEASUREMENTS PRIOR TO ORDERING. COORDINATE WITH COR.

9. REFER TO SHEET B01-TN600 LOGICAL FIBER RISER DIAGRAM FOR CABLE QUANTITIES.

10. REFER TO TN505 AND TN506 FOR PATHWAY DETAILS AND DUCT SIZING.

11. PROVIDE CONCRETE ENCASEMENT FOR ALL NEW SITE TELECOMMUNICATIONS PATHWAY.

1" = 100'-0"1

TELECOMMUNICATIONS SITE PATHWAYS

SHEET LEGEND:

A-SIDE BACKBONE PATHWAY

B-SIDE BACKBONE PATHWAY

A-SIDE SERVICE PROVIDER ENTRANCE PATHWAY

B-SIDE SERVICE PROVIDER ENTRANCE PATHWAY

PRINT SHEET IN COLOR

CONDUIT PATHWAY FROM SITE MANHOLE ROUTED ALONG CEILING

STRUCTURE OF PARKING AREA INTO BUILDING 1.

E

AC

IRR

ACACAC

HYD

WPB

WPB

WPB

WPB

WPB

WPB

WPB

WPB

T R

A N

S

TRANS

WPB

WPB

WPB

DUMPSTER

PAD

X

MH

MH

M H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:5

P

M

TN401

SITE PLAN - TELECOM PHASE 1 ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

05/24/23 PR TL

B01

1" = 30'-0"1

SITE PLAN - TELECOM PHASE 1

1. DEMO EXISTING TELECOM DUCT BANK AND INFRASTRUCTURE BETWEEN THE TWO EXISTING

MANHOLES NOTED. NEW DUCT BANK AND RELOCATED CABLING SHALL BE IN PLACE PRIOR

TO DEMO WORK COMMENCING. SEE CIVIL PHASING NOTES ON SHEET C-003.

2. NEW TELECOMMUNICATIONS DUCT BANK. REFER TO CU100 CIVIL PLANS FOR QUANTITY OF

CONDUITS. REFER TO SHEET TN505 AND TN506 FOR SITE TELECOM DUCTBANK DETAILS.

3. PROVIDE TEMPORARY PATHWAY BETWEEN EXISTING TELECOMMUNICATIONS DUCT BANK

AND NEW TELECOMMUNICATIONS HAND HOLE.

4. ROUTE NEW FIBER OPTIC CABLING FROM EXISTING TELECOMMUNICATION MANHOLE TO

EXISTING TELECOMMUNICATIONS HAND HOLE/MANHOLE THROUGH NEW

TELECOMMUNICATIONS DUCT BANK. INTERCEPT AND SPLICE EXISTING FIBER OPTIC

CABLING IN EXISTING HAND HOLE/MANHOLES.

5. NEW TELECOMMUNICATIONS HAND HOLE/MANHOLE

6. EXISTING TELECOMMUNICATIONS HAND HOLE

7. EXISTING TELECOMMUNICATIONS HAND HOLE TO BE RELOCATED

8. RELOCATE EXISTING TELECOMMUNICATIONS HAND HOLE TO THIS LOCATION

KEYED NOTES:#

GENERAL NOTES:

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION AND FINAL

LOCATION WITH THE ELECTRICAL AND MECHANICAL DIVISION. REFER TO ELECTRICAL,

MECHANICAL AND PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP, AND ANY OTHER

FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND CONDUITS OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 10 00 STRUCTURED

CABLING AND SECTION 27 05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE DRILLING.

CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE RISER SLEEVES.

REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH FLOOR.

REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED CABLING.

7. PHASING OF THE WORK IN THE DATA CENTER IMPACTS WORK IN THE TRS AND

HORIZONTAL CABLING. COORDINATE WORK SCHEDULES WITH THE COR.

8. GOVERNMENT EQUIPMENT WILL BE RELOCATED BY GOVERNMENT IT PERSONNEL.

CONTRACTOR WILL HAVE TECHNICIANS AVAILABLE TO PROVIDE SUPPORT DURING

OUTAGES AND CUT-OVERS. COORDINATE WORK WITH THE COR.

9. CONTRACTOR SHALL PROVIDE CABLE MANAGEMENT FINGERS, AIR DAMS, BAYING

SEAL KITS, CABLE BRUSHES, AND GROMMETS MANUFACTURED AND COMPATIBLE

WITH CABINETS.

10. CONTRACTOR SHALL PROVIDE , MTP, FIBER OPTIC TRUNK CABLES FOR SIDE A AND

SIDE B BACKBONE FROM THE DATA CENTER TO EACH TELECOMMUNICATIONS ROOM.

COORDINATE WITH COR.

11. CONTRACTOR SHALL PROVIDE , FIBER OPTIC PATCH CABLES FOR SIDE A AND SIDE B

FROM THE FIBER OPTIC DISTRIBUTOR TO EQUIPMENT CABINETS. COORDINATE WITH

COR.

12. CONTRACTOR SHALL VERIFY FACTORY, PRE-TERMINATED, FIBER OPTIC CABLES

MEASUREMENTS PRIOR TO ORDERING. COORDINATE WITH COR.

13. REFER TO SHEET B01-TN600 LOGICAL FIBER RISER DIAGRAM FOR CABLE QUANTITIES.

14. REFER TO TN505 AND TN506 FOR PATHWAY DETAILS AND DUCT SIZING.

15. PROVIDE CONCRETE ENCASEMENT FOR ALL NEW SITE TELECOMMUNICATIONS

PATHWAY.

16. COORDINATE WITH LOCAL VA OIT FOR THE IDENTIFICATION OF ALL CABLES LOCATED

WITHIN EXISTING TELECOMMUNICATIONS DUCT BANK TO BE RELOCATED. SCOPE

SHALL INCLUDE THE IDENTIFICATION OF THE CABLE OWNER/USERS, STRAND/PAIR

COUNTS, CABLE TYPES, ENDPOINTS, PATHWAYS TO ENDPOINTS, AND ANY ALLOWED

DOWNTIME.

17. COORDINATE WITH CABLE OWNER/USER IF SPLICING OF CABLING IS PERMITTED OR IF

CABLE IS TO BE REPLACED IN ITS ENTIRETY FROM THE END POINTS OF TERMINATION.

18. FULLY INSTALL AND COMMISSION THE NEW DUCT BANK FROM HAND HOLE/MANHOLE

TO HAND HOLE/MANHOLE PRIOR TO ANY DEMO WORK.

19. COORDINATE SCHEDULING WITH VA OIT FOR RELOCATION OF CABLING

INFRASTRUCTURE. THIS INCLUDES REPLACEMENT OF CABLING WITHIN NEW DUCT

BANK, EXTENDING NEW CABLING AS REQUIRED TO NEAREST POINT OF TERMINATION

IN BOTH DIRECTIONS, TERMINATION OF NEW CABLING, TESTING OF NEW CABLING,

AND CUT-OVER TO NEW CABLING.

20. ONCE NEW CABLING IS 100% INSTALLED AND OPERATIONAL, CONTRACTOR SHALL

REMOVE ABANDONED CABLING IN EXISTING DUCT BANK TO BE DEMOLISHED.

21. ONCE CABLING IS CONFIRMED TO BE FULLY REMOVED, EXISTING DUCT BANK CAN BE

REMOVED AS INDICATED.

SHEET LEGEND:

DEMO FIBER PATHWAY

PHASE 1 FIBER PATHWAY

TYPE NOTES

WPH

PORT 1 TYPE

A

NOTES:

1-PORT FACEPLATE

TYPE NOTES

1 2

PORT 1 TYPE PORT 2 TYPE

2-PORT FACEPLATE

NOTES:

1. IF NUMBER OF CABLES IS DIFFERENT FROM STANDARD QUANTITY (SEE STRUCTURED CABLING LEGEND). USE NEXT AVAILABLE OPEN PORT IN

FACEPLATE.

SURFACE MOUNTED OUTLET

TC A

DEVICE MOUNT.

DETAIL TYPE

ROUGH-IN DETAIL

TYPE

DEVICE MOUNT.

DETAIL TYPE

ROUGH-IN

DETAIL TYPE

TYPE NOTES

FURN

PORT 1 TYPE

A--

DEVICE MOUNT.

DETAIL TYPE

FURN-1.1

ROUGH-IN

DETAIL TYPE

PORT 2 TYPE PORT 3 TYPE PORT 4 TYPE

A

X X

TYPE NOTES

COMM-2 1

1 2

PORT 1 TYPE

A

PORT 2 TYPE

A

PORT 3 TYPE

X

PORT 4 TYPE

X4-PORT FACEPLATE

PM-CEN 1A A A A

PM 1A A X X

PM-RM 1A A X X

DEVICE MOUNT.

DETAIL TYPE

ROUGH-IN

DETAIL TYPE

J1

NOTES:

NOTES:

1. IF NUMBER OF CABLES IS DIFFERENT FROM STANDARD QUANTITY (SEE STRUCTURED CABLING LEGEND). USE NEXT AVAILABLE OPEN PORT IN FACEPLATE.

1. PROVIDE SPACE ON EITHER SIDE OF FACEPLATE FOR MOUNTING DEVICE. REFER TO DETAILS FOR ADDITIONAL INFORMATION.

J1

J1

J1

1. IF NUMBER OF CABLES IS DIFFERENT FROM STANDARD QUANTITY (SEE STRUCTURED CABLING LEGEND). PROVIDE ADDITIONAL CABLING, JACKS, AND SURFACE

MOUNTED BOX.

WPC 1A A X XWPC-1.1J1

TYPE PORT 1 TYPE PORT 2 TYPE NOTES

BISC-1 A X

BISC-2 A A

ROUGH-IN

DETAIL TYPE

DEVICE MOUNT.

DETAIL TYPE

BISC-1.1

-- BISC-2.1

NOTES:

1. CONNECT FIELD MOUNT PLUG TO SURGE PROTECTOR MOUNTED IN DEVICE BOX.

DIRECT ATTACHED FIELD MOUNT PLUG

FACEPLATE TYPE DETAILS

TYPE PORT 1 TYPE PORT 2 TYPE NOTES

ROUGH-IN

DETAIL TYPE

DEVICE MOUNT.

DETAIL TYPE

A X

NOTES:

1. IF NUMBER OF CABLES IS DIFFERENT FROM STANDARD QUANTITY (SEE STRUCTURED CABLING LEGEND). USE NEXT AVAILABLE OPEN PORT IN FACEPLATE.

2. COORDINATE MOUNTING HEIGHT AND LOCATION WITH FINAL LOCATION OF ELECTRICAL OUTLETS.

3. REFER TO AUDIO VISUAL DISPLAY DETAILS FOR ADDITIONAL ROUGH-IN REQUIREMENTS, BASED ON DISPLAY TYPE.

4. REFER TO AUDIO VISUAL POKE-THRU AND FLOORBOX DETAILS FOR ADDITIONAL ROUGH-IN REQUIREMENTS, BASED ON PENETRATION TYPE.

TYPE NOTES

1 2

PORT 2 TYPE PORT 3 TYPE PORT 4 TYPE6-PORT FACEPLATE

PORT 5 TYPE PORT 6 TYPE

DEVICE MOUNT.

DETAIL TYPE

ROUGH-IN

DETAIL TYPE

DIS 1, 3A X X X--

TV 1, 3A X X B--

TV-NC 1, 3A X B C--

FB 1A A X X--

FB-AV 1, 4A A--

PT 1A A--

PT-AV 1, 4A A--

X X

X X

X X

PORT TYPE DESCRIPTION

APPEARANCE DESIGNATOR MODULAR JACK DESCRIPTION CABLING

B

RJ-45, 8-POSITION 8-CONTACT, NON-KEYED 4-PAIR UTP

A

APPEARANCE DESIGNATOR MODULAR JACK DESCRIPTION CABLING

D

SINGLE MODE DUPLEX LC JACK SINGLE MODE FIBER

X

BLANK INSERT NOT APPLICABLEF-CONNECTOR COAXIAL CABLE

C

1/4" JACK REFER TO SPECIFICATIONS

NOTES:

1. IF NUMBER OF CABLES IS DIFFERENT FROM STANDARD QUANTITY (SEE STRUCTURED CABLING LEGEND). USE NEXT AVAILABLE OPEN PORT IN

FACEPLATE.

2. COORDINATE MOUNTING HEIGHT AND LOCATION WITH FINAL LOCATION OF ELECTRICAL OUTLETS.

3. REFER TO AUDIO VISUAL DISPLAY DETAILS FOR ADDITIONAL ROUGH-IN REQUIREMENTS, BASED ON DISPLAY TYPE.

4. REFER TO AUDIO VISUAL POKE-THRU AND FLOORBOX DETAILS FOR ADDITIONAL ROUGH-IN REQUIREMENTS, BASED ON PENETRATION TYPE.

J1

J1

RW 1A A X X--RW-1.1

TO NEAREST

ACCESSIBLE CEILING

DETAIL NOTES:

1. ROUTE CABLE(S) IN CONDUIT CONCEALED WITHIN WALL. STUB CONDUIT UP INTO NEAREST

ACCESSIBLE CEILING. REFER TO STRUCTURE CABLING LEGEND FOR CONDUIT SIZE AND

QUANTITY.

2. PROVIDE BACKBOX SIZE AS INDICATED ON STRUCTURED CABLING LEGEND PER DEVICE

TYPE. PROVIDE RAISED MUD RING FOR DEVICES THAT REQUIRE ADDITIONAL DEPTH.

3. REFER TO FACEPLATE MATRIX FOR PORT CONFIGURATION.

4. DASHED LINES INDICATE ALTERNATE CONDUIT/CABLE ROUTING PATH.

5. FINISHED WALL OR CASEWORK SURFACE.

TO TR

DETAIL NOTES:

1. ROUTE CABLE(S) IN CONDUIT CONCEALED WITHIN WALL. STUB CONDUIT UP INTO NEAREST

ACCESSIBLE CEILING. REFER TO STRUCTURE CABLING LEGEND FOR CONDUIT SIZE AND

QUANTITY.

2. PROVIDE BACKBOX SIZE AS INDICATED ON STRUCTURED CABLING LEGEND PER DEVICE

TYPE. PROVIDE RAISED MUD RING FOR DEVICES THAT REQUIRE ADDITIONAL DEPTH.

3. REFER TO FACEPLATE MATRIX FOR PORT CONFIGURATION.

4. DASHED LINES INDICATE ALTERNATE CONDUIT/CABLE ROUTING PATH.

5. WALL, COLUMN, OR CASEWORK SURFACE.

LABEL EXAMPLE INDICATES

COMM. OUTLET SERVER BY

TELECOMMUNICATIONS ROOM

TDR-8A, RACK 1, PATCH PANEL

"A", PORT 01.

RACK NUM

IDENTIFIER

TWO (2) UTP CABLES

PATCH PANEL PORT

NUMBER FACTORY

LABELED 1-48

1 2

A

ENGRAVED LABEL:

PATCH PANELS "A", "B", ETC

PORTS A01 THRU A48

TDR-8A

1A021A01

PATCH PANEL ID

PORT NUMBER OF

DESIGNATED PATCH PANEL

TDR-XX

1 A01

TELECOMMUNICATIONS RM

NUMBER DESIGNATOR

CO IDENTIFICATION NOMENCLATURE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:5

A

M

TN501

STRUCTURED CABLING DETAILS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

NTS1

TYPE J1 - DEVICE BOX FLUSH MOUNT

NTS2

DEVICE BOX TYPE J2 SURFACE MOUNT

NTS3

TIA / EIA 606A OUTLET LABELING

PROVIDE TEMPORARY COLORED LOCATER

PUSH PIN IN CEILING TILE UNDER OUTLET

TO HELP LOCATE THE OUTLET AFTER

CEILING HAS BEEN INSTALLED

LAY-IN CEILING

12"

UTP CABLES ROUTED

THROUGH CEILING SPACE TO

NEAREST TELECOM ROOM

LEAVE 20' SLACK CABLE FOR

EACH OUTLET

SINGLE UTP JACK(S) MOUNTED INTO

SURFACE MOUNTED BOX. PROVIDE

ADHESIVE LABEL ON EACH OUTLET

LABEL

VELCRO WRAP

CABLE TO J-HOOK

THREADED ROD TO

SLAB ABOVE

PROVIDE TEMPORARY COLORED LOCATED

PUSH PIN IN CEILING UNDER OUTLET

TO HELP LOCATE THE OUTLET AFTER

CEILING HAS BEEN INSTALLED

12"

LAY-IN CEILING

VELCRO WRAP

CABLE TO J-HOOK

UTP CABLES ROUTED

THROUGH CEILING SPACE TO

NEAREST TELECOM ROOM

LEAVE 20' OF SLACK CABLE

FOR EACH OUTLET

SINGLE UTP JACK(S) MOUNTED INTO SURFACE

MOUNTED BOX. PROVIDE

ADHESIVE LABEL ON EACH OUTLET

LABELPROVIDE TEMPORARY COLORED LOCATER

PUSH PIN IN CEILING TILE UNDER OUTLET

TO HELP LOCATE THE OUTLET AFTER

CEILING HAS BEEN INSTALLED

LAY-IN CEILING

UTP CABLES ROUTED

THROUGH CEILING SPACE TO

NEAREST TELECOM ROOM

LEAVE SLACK CABLE FOR

EACH OUTLET

SINGLE UTP JACK(S) MOUNTED INTO

SURFACE MOUNTED BOX. PROVIDE

ADHESIVE LABEL ON EACH OUTLETLABEL

THREADED ROD TO

SLAB ABOVE

12"

VELCRO WRAP

CABLE TO J-HOOK

EXTENDED J-HOOK

ANGLE BRACKET

SECURE OUTLETS TO

BRACKET WITH SCREWS

PROVIDE TEMPORARY COLORED LOCATED

PUSH PIN IN CEILING UNDER OUTLET

TO HELP LOCATE THE OUTLET AFTER

CEILING HAS BEEN INSTALLED

12"

VELCRO WRAP

CABLE TO J-HOOK

UTP CABLES ROUTED

THROUGH CEILING SPACE TO

NEAREST TELECOM ROOM

LEAVE 20' OF SLACK CABLE

FOR EACH OUTLET

SINGLE UTP JACK(S) MOUNTED INTO SURFACE

MOUNTED BOX. PROVIDE

ADHESIVE LABEL ON EACH OUTLET

LAY-IN CEILING

LABEL

THREADED ROD TO

SLAB ABOVE

EXTENDED J-HOOK

ANGLE BRACKET

SECURE OUTLETS TO

BRACKET WITH SCREWS

FLOOR

1-1/4" CONDUITS

2 GANGS BACK BOX

2 GANGS FACEPLATE

COORDINATE EXACT

LOCATION WITH SYSTEM

FURNITURE INSTALLER

SYSTEM FURNITURE

CABLING CONTRACTOR SHALL

PROVIDE BLACK SPLIT TUBING WITH

CABLING INSIDE, ROUTE INTO

SYSTEMS FURNITURE

6"

FROM FURNITURE, ALIGN

WITH ELECTRICAL FEED TO

SYSTEM FURNITURE

ROUTE CABLES IN ONE CONDUIT.

LEAVE ONE FOR FUTURE USE

STUB CONDUIT ABOVE

ACCESSIBLE CEILING. PROVIDE

NYLON BUSHING ON ENDS.

PROVIDE PULL STRINGS

CEILING TILE

ROUTE CABLING CONCEALED

WITHIN SYSTEM FURNITURE

RACEWAYS AND PANELS

COMMUNICATIONS OUTLETS,

MOUNTED IN SYSTEM

FURNITURE RACEWAY. ROUTE

CABLES DOWN WALL

TYPICAL

SYSTEM

FURNITURE

WALL

(2) 1-1/4" CONDUITS IN WALL

SYSTEM FURNITURE WALL

FEED, 4" x 4" x 2-1/8" DEEP BACK

BOX WITH COVER PLATE WITH 2"

GROMMETED OPENING. SPIRAL

WRAP CABLES FROM

FACEPLATE TO FURNITURE

+18" AFF

SYSTEM FURNITURE RACEWAY

SYSTEM FURNITURE MOUNTED

COMMUNICATION OUTLET

RACEWAY COVER

CONDUITS BY ELECTRICAL

CONTRACTOR

UTP JACK "A" TERMINATE TO

UTP CABLE OF SAME COLOR

UTP JACK "B" TERMINATE TO

UTP CABLE OF SAME COLOR

UTP JACK "F" TERMINATE TO

UTP CABLE OF SAME COLOR

UTP JACK "C" TERMINATE TO

UTP CABLE OF SAME COLOR

PROVIDE LABEL

DIVIDER PANEL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:0

A

M

TN502

STRUCTURED CABLING DETAILS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

NTS3

TYPE BISC-1.2 - ABOVE CEILING OUTLET - (1) JACK

NTS4

TYPE BISC-2.2 ABOVE CEILING OUTLET - (2) JACKS

NTS1

TYPE BISC-1.1 - ABOVE CEILING OUTLET - (1) JACK

NTS2

TYPE BISC-2.1 ABOVE CEILING OUTLET - (2) JACKS

12" = 1'-0"6

WALL FURNITURE FEED

NTS5

FURN-1.1 - FURNITURE SYSTEM CABLE ROUTING

NTS7

RW-1.1 - SURFACE MOUTED RACEWAY

DATA / VOICE / COAXIAL CABLES

PROVIDE QUANTITY AS REQUIRED.

ALWAYS LEAVE AT LEAST 50%

SPARE CAPACITY.

FRONT VIEW

TYPICAL CABLE TRAY

SIDEVIEW

FULL HEIGHT PARTITION

TYPICAL CABLE TRAY

CABLES

NOTE:

INSTALL WHENEVER MORE THAN 16 CABLES MUST PASS

THROUGH FULL HEIGHT PARTITION.

THREE WAY HORIZONTAL CABLE

TRAY - WIRE BASKET FITTING

WITH 6" RADIUS

HORIZONTAL TEE FITTING

CABLE TRAY

WIRE BASKET

PROVIDE TAPERED INTERSECTION

CABLE TRAY WIRE BASKET

PROVIDE TAPERED INTERSECTION

CABLE TRAY WIRE BASKET

CORNER JUNCTIONTRAPEZE MOUNT

TRAPEZE TYPE CABLE TRAY WIRE BASKET

SUPPORT ACROSS BOTTOM SIDE OF TRAY

EVERY 5' MAX.

3/8" THREADED ROD

PROVIDE 6" SLEEVE OVER

THREADED

ROD FOR CABLE PROTECTION

NOTES:

1. TRAPEZE MOUNT TRAY.

2. PROVIDE CORNER JUNCTIONS TO WRAP TRAY AROUND CORRIDORS CORNERS.

3. PROVIDE TEE FITTING WHERE TRAYS JOIN TOGETHER.

4. PROVIDE #6 AWG INSULATED GROUND CONTINUOUS. BOND TO EACH SECTION OF

CABLE TRAY - WIRE BASKET.

5. ALIGN CABLE TRAY - WIRE BASKET WITH CONDUITS AND HILTI SPEED SLEEVES THAT

PASS THROUGH FIRE OR SMOKE RATED WALLS.

6. MAINTAIN PROPER CLEARANCES AROUND TRAY AS NOTED IN THE SPECIFICATIONS.

0'-8" MIN.

CLEARANCE

REQUIRED

CLEARANCE

REQUIRED

MOUNTING HEIGHTS

PER DRAWINGS

TYPICAL WIRE

MESH CABLE

TRAY

DETAIL NOTES:

1. APPROVED SUPPORT AND MOUNTING

STRUCTURE AS REQUIRED BY

MANUFACTURER, ARCHITECTURAL

CONFIGURATION, AND WEIGHT SUPPORTED.

1'-0" MIN.

CLEARANCE

REQUIRED

0'-8" MIN.

TYPICAL FIBER PATCH

CORD CONTAINMENT

FINISHED FLOOR

APPROX.

7'-6"

AFF

APPROX.

7'-0"

AFF

DETAIL NOTES:

1. TYPICAL WIRE MESH CABLE TRAY (REFER TO PLANS

FOR SIZES AND LAYOUTS).

2. PROVIDE DROPOUT OR "WATERFALL" ACCESSORIES

AS REQUIRED TO PROPERLY MANAGE BEND RADII.

COORDINATE LOCATION AND STYLE WITH FIELD

CONDITIONS AND EQUIPMENT SELECTIONS.

WATERFALL SHALL EXTEND TO 50mm ABOVE

CABINET. ALL CABLES SHALL BE SECURED WITH

HOOK & LOOP FASTENERS AND SHALL BE PROPERLY

SUPPORTED AND ROUTED INTO VERTICAL WIRE

MANAGEMENT WITHIN THE CABINET.

3. TYPICAL OPTICAL FIBER PATCH CORD CONTAINMENT

ALIGNED WITH VERTICAL WIRE MANAGEMENT ON

FRONT OF CABINET.

4. OPTICAL FIBER PATCH CORD CONTAINMENT BEND

RADIUS SPILLWAY.

5. CORRUGATED LOOM TUBING.

6. TELECOMMUNICATIONS ENCLOSURE - REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

7. TYPICAL CLEAR HEIGHT DIMENSION. REFER TO

PLANS AND LAYOUTS FOR ADDITIONAL INFORMATION.

EXISTING CONDUITS STUBBED ABOVE

ACCESSIBLE CEILING. PROVIDE

NYLON BUSHING ON ENDS.

PROVIDE PULL STRINGS. DEMO

EXISTING FACEPLATE/CABLING.

CEILING TILE

WALL

EXISTING CONDUIT(S)

EXISTING BACKBOX

+18" AFF

EXISTING CATEGORY CABLE RUN

LOOSE IN WALL TO ABOVE CEILING.

USE EXISTING CABLE AS PULL

STRING. PROVIDE PULL STRINGS.

DEMO EXISTING FACEPLATE/CABLING.

CEILING TILE

WALL

EXISTING CATEGORY

CABLING

EXISTING BACKBOX

+18" AFF

NOTES:

1. ONLY ACCEPTABLE LOCATIONS TO RUN LOOSE

CABLING IN WALL SPACE ARE LOCATIONS THAT DO NOT

ALREADY HAVE CONDUITS TO BACKBOX.

WATER-TIGHT JUNCTION

BOX OPENING TO TR ON

LEVEL BELOW.

EXISTING INTERSTITIAL

CABLE TRAY

INTERSTITIAL

LEVEL FLOOR

2" FLEX CONDUIT FROM

INTERSTITIAL CABLE

TRAY TO JUNCTION BOX.

FIRE STOPPING

SYSTEM MATERIAL

CONCRETE FLOOR

CABLING NOT TO EXCEED

THE CROSS SECTIONAL AREA AS

THE UL LISTED FIRESTOPPING

SYSTEM ALLOWS

DRILLED CORE THROUGH FLOOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:0

A

M

TN503

STRUCTURED CABLING DETAILS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

NTS5

SCN - WALL PENETRATION SINGLE

N.T.S.1

SCN - CABLE TRAY WIRE BASKET

N.T.S.2

SCN - CABLE TRAY CLEARANCE

N.T.S.3

SCN - CABLE TRAY WATERFALL

NTS6

CABLING SCENARIOS - IN-WALL CONDUITS

NTS7

CABLING SCENARIOS - LOOSE CABLING

NTS8

CABLING SCENARIOS - INTERSTITIAL PENETRATIONS

NTS4

SCN - FLOOR CORE

ISOMETRIC ELEVATION

SBB FRONT ELEVATION

GROUND BUSBAR

HEAVY DUTY 2-HOLE

COMPRESSION LUGS

GROUND BAR

PBB

CONNECT TO SECURITY PANEL

CONNECT TO ALL SECTIONS OF CABLE

RACK TRAY AND CABLE TRAY

CONNECT TO ALL DATA RACKS

CONNECT TO RISER CABLE SHEATHS

CONNECT TO DAS CABINET

#6 A

W G

1. ALL GROUND CONNECTIONS SHALL BE MADE WITH HEAVY DUTY 2 HOLES COMPRESSION LUGS WITH STAINLESS STEEL HEX HEAD CAP SCREWS WITH SS LOCKING NUTS (TWO SCREWS AND NUTS PER 2

HOLES LUG).

2. RUN TBC IN EMT CONDUIT. PROVIDE INSULATED GROUNDING BUSHING - MALLEABLE IRON STEEL

CITY #BG-807 AT CONDUIT ENDS AND GROUND PER NEC GROUNDING TO BUILDING STRUCTURE,

CONDUITS, UTILITY PIPING, OR ELECTRICAL SUBPANELS IN LIEU OF BONDING TO BUILDING MAIN

ELECTRICAL SERVICE GROUND IS NOT ACCEPTABLE.

3. GROUND ALL COMMUNICATIONS RACKS WITH #6 AWG INSULATED STRANDED COPPER GROUNDING

CONDUCTOR TO MAIN GROUNDING BUSBAR. GROUND RACKS INDIVIDUALLY TO BUSBAR (DO NOT

LOOP GROUNDS). ROUTE CONDUCTOR ALONG RACK REAR AND CABLE RUNWAY TO GROUNDING

BUSBAR.

4. GROUND EACH CONDUIT AND CONDUIT SUPPORTS STRUTS IN ALL COMMUNICATION ROOMS WITH

#6 AWG INSULATED STRANDED COPPER GROUNDING CONDUCTOR TO GROUNDING BUSBAR. ROUTE

CONDUCTOR IN CABLE RUNWAY TO GROUNDING BUSBAR.

5. GROUND CABLE RUNWAY WITH #6 AWG SOLID BARE COPPER GROUNDING CONDUCTOR TO

GROUNDING BUSBAR. ROUTE CONDUCTOR IN CABLE RUNWAY TO GROUNDING BUSBAR.

6. MARK CONDUCTOR 6" FROM TERMINATION WITH GREEN TAPE.

7. ELECTRICAL CONTRACTOR TO PROVIDE #3/0 COPPER CABLE FROM BUILDING GROUND AND OTHER

TELECOM ROOMS TO GROUND BAR LOCATION AND PROVIDE GROUNDING BAR IN EACH TELECOM

ROOM. CABLING CONTRACTOR TO PROVIDE GROUNDING CABLING FROM EACH PEACE OF EQUIPMENT

WITHIN THE TELECOM ROOM, UNLESS OTHERWISE NOTED.

INSULATOR

MOUNTING BRACKET (TYP.)

GROUND BUSBAR. REFER TO

SPECIFICATIONS FOR SIZING

MOUNTING BRACKET (TYP.)

BBC (WHERE USED)

#6 INSULATED COPPER GROUND CABLE TO

TYPICAL COMM. EQUIPMENT:

• CONNECT TO SECURITY PANEL

• CONNECT TO ALL SECTIONS OF CABLE

RACK TRAY AND CABLE TRAY

• CONNECT TO ALL NETWORK RACKS

• CONNECT TO RISER CABLE SHEATHS

• CONNECT TO DAS CABINET

HEAVY DUTY 2-HOLE

COMPRESSION LUGS

TBB

TBB TO EACH TELECOM ROOM

SBB

GROUNDING NOTES:

PBB

LIGHTNING

PROTECTION

COPPER

CABLE

BOND

SHEATH

RACKS (TYP.)

ELECTRICAL MAIN

GROUND BUS

ELECTRICAL SERVICE GROUNDING

ELECTRODE CONDUCTOR

ELECTRICAL MAIN

NEUTRAL BUS

TELECOMMUNICATIONS

BONDING CONDUCTOR

(TBC)

BUILDING STEEL

ELECTRICAL SERVICE ENTRANCE

TBB

SBB

EQUIPMENT / TELECOM ROOM

(TELECOMMUNICATIONS

ENTRANCE FACILITY)

BUILDING STEEL

BUILDING CEILINGCABLE TRAY

LADDER RACK

RACK BONDING BUSBAR

(TYP. OF EACH RACK)

NOTE: GROUNDING DETAILS ILLUSTRATE GENERAL REQUIREMENTS AND MAY

NOT COVER ALL REQUIREMENTS OF ANSI/TIA-607-D AT A MINIMUM.

LEGEND

TBB - MUST BE CONTINUOUS WITH EXOTHERMIC WELD TAPS OR INDIVIDUAL

HOME RUNS, NOT DAISY CHAINED SIZING BASED ON LENGTH, SEE ANSI/TIA-607-D.

6 AWG STRANDED, GREEN INSULATED GROUND WIRE

OSP COPPER CABLE

PBB - PRIMARY BONDING BUSBAR

SBB - SECONDARY BONDING BUSBAR

TBC- TELECOMMUNICATIONS BONDING CONDUCTOR - SAME SIZE AS LARGEST

BBC- BACKBONE BONDING CONDUCTOR - SAME SIZE AS LARGEST SBB

TELECOM ROOM

(DISTRIBUTOR ROOM)

TBB

TBB

TBB

TBB

TBB

TBB

SBB

SBB SBB

SBB

SBB

BBC

TBB

TELECOM ROOM

(DISTRIBUTOR ROOM)

TELECOM ROOM

(DISTRIBUTOR ROOM)

TELECOM ROOM

BBC (DISTRIBUTOR ROOM)

EQUIPMENT / TELECOM ROOM

(TELECOMMUNICATIONS

ENTRANCE FACILITY)

PBB

LIGHTNING

PROTECTION

COPPER

CABLE

BOND

SHEATH

RACKS (TYP.)

ELECTRICAL MAIN

GROUND BUS

ELECTRICAL SERVICE GROUNDING

ELECTRODE CONDUCTOR

ELECTRICAL MAIN

NEUTRAL BUS

TELECOMMUNICATIONS

BONDING CONDUCTOR

(TBC)

BUILDING STEEL

ELECTRICAL SERVICE ENTRANCE

BUILDING STEEL

BUILDING CEILINGCABLE TRAY

BUILDING CEILINGCABLE TRAY

BUILDING CEILINGCABLE TRAY

LADDER RACK

RACK BONDING BUSBAR

(TYP. OF EACH RACK)

NOTE: GROUNDING DETAILS ILLUSTRATE GENERAL REQUIREMENTS AND MAY

NOT COVER ALL REQUIREMENTS OF ANSI/TIA-607-D AT A MINIMUM.

LEGEND

TBB - MUST BE CONTINUOUS WITH EXOTHERMIC WELD TAPS OR INDIVIDUAL

HOME RUNS, NOT DAISY CHAINED SIZING BASED ON LENGTH, SEE ANSI/TIA-607-D.

6 AWG STRANDED, GREEN INSULATED GROUND WIRE

OSP COPPER CABLE

PBB - PRIMARY BONDING BUSBAR

SBB - SECONDARY BONDING BUSBAR

TBC- TELECOMMUNICATIONS BONDING CONDUCTOR - SAME SIZE AS LARGEST

BBC- BACKBONE BONDING CONDUCTOR - SAME SIZE AS LARGEST SBB

TELECOM ROOM

(DISTRIBUTOR ROOM)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:1

A

M

TN504

GROUNDING DETAILS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

NTS1

GRD - GROUND BAR DETAIL

NTS2

GRD - GROUNDING SYSTEM

NTS3

GRD - TYPICAL GROUNDING SYSTEM

OPENING

CABLE RACK

CABLE PULL RING

DUCT TERMINATOR

SIDE WALL DUCT

ENTRANCE

DUCT WINDOW

REINFORCED CONCRETESUMP

1" PVC SLEEVE

FOR GROUND ROD

3/4" x 10' LONG COPPER

CLAD STEEL GROUND ROD

SLOPE SLOPE

SLOPE

S L O

P E

S L O

P E

SLOPE

OPENING

GROUND ROD

4'-0"

WIDTH

L E

N G

T H

NOTES:

1. HAND HOLE OVERALL DIMENSION MUST BE A MINIMUM 4' X 4' X 4'

(WxLxD), FULLY ENCLOSED EXCEPT FOR DRAINAGE AND

CONSTRUCTED OF CONCRETE. HAND HOLE COVER MUST BE

LABELED "COMMUNICATIONS" AND MUST BE LOCKABLE WITH A

GSA APPROVE PADLOCK.

EARTH

LABELED

"COMMUNICATIONS"

L O

G O

L O

G O

1/2"x4" PULL SLOT

1/2"-13 UNC STAINLESS

STEEL HEX BOLT W/ WASHER

.5 COF SKID RESISTANT SURFACE

(1) 4" CONDUIT (TYP.)

FIBER SERVICE LOOP.

RUN (2) LOOPS ALONG

OUTSIDE OF HAND HOLE

4" SCHEDULE 40

PVC UON (TYPICAL)

BASE AND INTERMEDIATE

SPACERS HORIZONTALLY

ALONG LENGTH OF DUCTBANK

#4 HOOP REBAR

(STIRRUPS) 18" ON CENTER

#4 LONGITUDINAL REBAR

(TYPICAL, EACH CORNER)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

6" SEPARATION

MINIMUM (TYPICAL)

CRUSHED STONE AS

NEEDED FOR LEVELING

6" SEPARATION

MINIMUM (TYPICAL)

3500 PSI CONCRETE

MAGNETIC WARNING

TAPE (TYPICAL)

4000 PSI CONCRETE6"x6" WIRE MESH

2" ABOVE BOTTOM

FINISHED SURFACE OF SIDEWALK

NOTE:

• THIS DETAIL IS TO BE USED BETWEEN MAN HOLE (5) STA 8 + 83.4 AND MAN HOLE (5A) STA 9+45.1 AND BETWEEN MAN HOLE (5C) STA 16 + 01.1.9 AND MAN HOLE (5D) STA 16+48.6, SEE CIVIL SHEET CU201.

• REFER TO CIVIL SHEET CS501, DETAIL 2 FOR REINFORCED SIDEWALK DETAIL.

16" SEPARATION

MINIMUM (TYPICAL)

51" SEPARATION MINIMUM

4" SCHEDULE 40

PVC UON (TYPICAL)

BASE AND INTERMEDIATE

SPACERS HORIZONTALLY

ALONG LENGTH OF DUCTBANK

#4 HOOP REBAR

(STIRRUPS) 18" ON CENTER

#4 LONGITUDINAL REBAR

(TYPICAL, EACH CORNER)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

6" SEPARATION

MINIMUM (TYPICAL)

CRUSHED STONE AS

NEEDED FOR LEVELING

6" SEPARATION

MINIMUM (TYPICAL)

3500 PSI CONCRETE

MAGNETIC WARNING

TAPE (TYPICAL)

12"

24" MINIMUM DEPTH NON-DRIVE SURFACE,

30" MINIMUM DEPTH DRIVE SURFACE

3" SEPARATION

MINIMUM (TYPICAL)

FINISHED SURFACE OR GRADE

4" SCHEDULE 40

PVC UON (TYPICAL)

BASE AND INTERMEDIATE

SPACERS HORIZONTALLY

ALONG LENGTH OF DUCTBANK

#4 HOOP REBAR

(STIRRUPS) 18" ON CENTER

#4 LONGITUDINAL REBAR

(TYPICAL, EACH CORNER)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

6" SEPARATION

MINIMUM (TYPICAL)

CRUSHED STONE AS

NEEDED FOR LEVELING

6" SEPARATION

MINIMUM (TYPICAL)

3500 PSI CONCRETE

MAGNETIC WARNING

TAPE (TYPICAL)

12"

24" MINIMUM DEPTH NON-DRIVE SURFACE,

30" MINIMUM DEPTH DRIVE SURFACE

3" SEPARATION

MINIMUM (TYPICAL)

FINISHED SURFACE OR GRADE

4" SCHEDULE 40

PVC UON (TYPICAL)

BASE AND INTERMEDIATE

SPACERS HORIZONTALLY

ALONG LENGTH OF DUCTBANK

#4 HOOP REBAR

(STIRRUPS) 18" ON CENTER

#4 LONGITUDINAL REBAR

(TYPICAL, EACH CORNER)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

6" SEPARATION

MINIMUM (TYPICAL)

CRUSHED STONE AS

NEEDED FOR LEVELING

6" SEPARATION

MINIMUM (TYPICAL)

3500 PSI CONCRETE

MAGNETIC WARNING

TAPE (TYPICAL)

12"

24" MINIMUM DEPTH NON-DRIVE SURFACE,

30" MINIMUM DEPTH DRIVE SURFACE

FINISHED SURFACE OR GRADE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:5

P

M

TN505

SITE DETAILS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

05/24/23 PR TL

B01

N.T.S.5

SITE - HAND HOLE

N.T.S.6

SITE - HAND HOLE COVER

N.T.S.7

SITE - HAND HOLE WITH SERVICE LOOP

N.T.S.4

SITE - (6) 4" CONCRETE ENCASED CONDUIT DUCT BANK

(SPECIAL)

N.T.S.3

SITE - (6) 4" CONCRETE ENCASED CONDUIT DUCT BANK

N.T.S.2

SITE - (4) 4" CONCRETE ENCASED CONDUIT DUCT BANK

N.T.S.1

SITE - (2) 4" CONCRETE ENCASED CONDUIT DUCT BANK

OPENING

CABLE TRAY (TYP)

CABLE PULL RING

DUCT TERMINATOR

SIDE WALL DUCT

ENTRANCE

DUCT WINDOW

REINFORCED CONCRETESUMP

1" PVC SLEEVE

FOR GROUND ROD

3/4" x 10' LONG COPPER

CLAD STEEL GROUND ROD

SLOPE SLOPE

SLOPE

S L O

P E

S L O

P E

SLOPE

OPENING

GROUND ROD

OPENING

WIDTH

L E

N G

T H

EARTH

6'-0"

RATED CONCRETE

COLLAR (AS REQUIRED

TO BRING COVER TO

GRADE LEVEL)

FRAME AND COVER

MANHOLE

NOTE:

1. ALL SCHEDULE 40 PVC DUCTS MUST BE ENCASED IN CONCRETE.

2. ALL DUCTS STUBBED THROUGH MANHOLE / HAND HOLE WALLS MUST BE

TERMINATED AND SEALED VIA DUCT TERMINATORS.

3. UNUSED DUCTS MUST BE STUBBED OUT AND CAPPED VIA A SOLVENT

WELDED CONDUIT CAP.

4. ORIENTATION OF MANHOLES / HAND HOLES MUST BE COORDINATED WITH

THE DUCT BANK APPROACH.

5. DEPTH OF DUCT BANKS ARE PROVIDED AS A MINIMUM FOR GENERAL

INFORMATION. REFER TO CIVIL PLANS FOR PROFILES AND ACTUAL DUCT

DEPTH.

6. DUCT ARRANGEMENTS IN THESE DETAILS ARE PROVIDED FOR GENERAL

INFORMATION. REFER TO DUCT BANK SECTIONS FOR ACTUAL QUANTITIES

AND ARRANGEMENTS.

7. MANHOLE / HAND HOLE COVERS MUST BE H-20 RATED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:5

:2

A

M

TN506

SITE DETAILS ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

N.T.S.1

SITE - MAN HOLE

1-1B-2381-1A-148 1-1C-140

1-BA-216 1-BB-221 1-BC-218 1-BC-250

1-2A-281 1-2B-205 1-2C-112

1-3A-320 1-3B-139A

1-4A-322 1-4B-252 1-4C-234

1-5A-235 1-5B-232

1-6A-233 1-6B-232

1-7A-233 1-7B-232

1-8A-233 1-8B-232

1-9A-225 1-9B-227

3-1K-124D

MCR

23-107 23-110

BUILDING 23

BUILDING 03

BUILDING 01

4-119

BUILDING 04

6-222

BUILDING 06

7-12

BUILDING 07

10-2

BUILDING 10

12-13

BUILDING 12

14-122

BUILDING 14

BUILDING 16

19-1H-103

BUILDING 19

16-M-100

22-154

BUILDING 22

1-BC-263 1-BC-202

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:0

:5

A

M

TN600

LOGICAL FIBER RISER ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

N.T.S.1

LOGICAL FIBER RISER DIAGRAM

1. (37) A-SIDE 24-STRAND SINGLE MODE

INDOOR/OUTDOOR RATED OS2 FIBER OPTIC CABLE

2. (37) B-SIDE 24-STRAND SINGLE MODE

INDOOR/OUTDOOR RATED OS2 FIBER OPTIC CABLE

KEYED NOTES:#

GENERAL NOTES:

1. DIAGRAM DEPICTS TYPICAL REDUNDANT AND

DIVERSE CABLE ROUTING. A-SIDE AND B-SIDE

CABLING TO BE DIVERSELY ROUTED FOLLOWING OIT

ISTS CABLE SEPARATION GUIDELINES.

SHEET LEGEND:

A-SIDE BACKBONE 24-STRAND SINGLE

MODE INDOOR/OUTDOOR RATED OS2 FIBER

OPTIC CABLE

B-SIDE BACKBONE 24-STRAND SINGLE

MODE INDOOR/OUTDOOR RATED OS2 FIBER

OPTIC CABLE

A-SIDE SERVICE PROVIDER ENTRANCE

CABLES

B-SIDE SERVICE PROVIDER ENTRANCE

CABLES

PRINT SHEET IN COLOR

B23-TN305 - ENLARGED TELECOM PLANS -SERVICE ENTRANCE B 23-104
TN400 - SITE PLAN -TELECOM
TN401 - SITE PLAN -TELECOM PHASE 1
TN501 - STRUCTURED CABLING DETAILS
TN502 - STRUCTURED CABLING DETAILS
TN503 - STRUCTURED CABLING DETAILS
TN504 - GROUNDING DETAILS
TN505 - SITE DETAILS
TN506 - SITE DETAILS
TN600 - LOGICAL FIBER RISER

File details come from the government source that posted it. Updated .