ATTACHMENT 16 - Telecom 1 of 6.pdf

PDF 10 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction West Palm Beach Federal contract opportunity
Solicitation number
36C77623B0045
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This attachment is related to solicitation number 36C77623B0045 from the Department of Veterans Affairs Technology Acquisition Center Austin for infrastructure upgrades at the West Palm Beach facility. The solicitation seeks a contractor to provide telecommunications products and services including installing new cabling, switches, routers and related equipment. Proposals are due by April 15, 2023 with the contract to be awarded by June 1, 2023. The period of performance is one base year with four option years. Pricing is to be provided for the base year and each option year separately. The solicitation targets small businesses under NAICS code 517110.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction West Palm Beach, newest first.
File Type Posted
36C77623B0045 0003.pdf PDF
Clarifications to Technical Questions 9-5-23.pdf PDF
Cart Lift Motor Photos.pdf PDF
Updated Drawings for Clarifications.pdf PDF
36C77623B0045 0002.pdf PDF
Map of Wells Question 66.pdf PDF
Technical Questions - FINAL - West Palm Beach 8-21-23.pdf PDF
Photos for Responses to Questions 124 and 127.pdf PDF
Site Visit Sign-in Sheet - West Palm Beach 7-19-23.pdf PDF
36C77623B0045 0001.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Palm Beach 7-7-23.pdf PDF
ATTACHMENT 4 - Civil 1 of 5.pdf PDF
ATTACHMENT 5 - Civil 2 of 5.pdf PDF
ATTACHMENT 18 - Telecom 3 of 6.pdf PDF
ATTACHMENT 19 - Telecom 4 of 6.pdf PDF
ATTACHMENT 23 - Limitations on Subcontracting - Construction.docx DOCX document
ATTACHMENT 24 - Construction Wage Rates - Palm Beach 3-24-23.pdf PDF
ATTACHMENT 7 - Civil 4 of 5.pdf PDF
ATTACHMENT 10 - Fire Protection.pdf PDF
ATTACHMENT 22 - Contractor Core Work Hours.pdf PDF
ATTACHMENT 26 - Site Visit Instructions.pdf PDF
36C77623B0045 - 7-6-23.pdf PDF
ATTACHMENT 6 - Civil 3 of 5.pdf PDF
ATTACHMENT 11 - Mechanical 1 of 2.pdf PDF
ATTACHMENT 14 - Security.pdf PDF
ATTACHMENT 15 - Structural.pdf PDF
ATTACHMENT 17 - Telecom 2 of 6.pdf PDF
ATTACHMENT 21 - Telecom 6 of 6.pdf PDF
ATTACHMENT 25 - Contractor Safety - Environmental Form.docx DOCX document
ATTACHMENT 1 - Specifications.pdf PDF
ATTACHMENT 2 - General.pdf PDF
ATTACHMENT 8 - Civil 5 of 5.pdf PDF
ATTACHMENT 9 - Electrical.pdf PDF
ATTACHMENT 12 - Mechanical 2 of 2.pdf PDF
ATTACHMENT 13 - Plumbing.pdf PDF
ATTACHMENT 20 - Telecom 5 of 6.pdf PDF
ATTACHMENT 3 - Architectural.pdf PDF
Show all 37

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PENETRATION REQUIREMENTS

1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE FIRE-RATED SLEEVES PER THESE INSTRUCTIONS AND AS SHOWN ON THE PLANS.

2. AT EACH ROOM WHERE LOW VOLTAGE CABLING IS BEING ROUTED INTO OR THROUGH, PROVIDE A MINIMUM OF:

2.1 (1) HILTI SPEED SLEEVE (OR APPROVED EQUIVALENT) FOR FIRE RATED WALLS.

2.2 (1) HILTI SPEED SLEEVE (OR APPROVED EQUIVALENT) FOR NON-RATED OR SMOKE RATED WALLS.

2.3 IF SLEEVES ARE ALREADY SHOWN FOR THAT ROOM, PROVIDE AS INDICATED.

3. FOR EACH SET OF SLEEVES, INSTALL THEM WITH THE APPROPRIATE GANGABLE BRACKETS FOR A TIGHT AND CLEAN INSTALLATION.

4. PROVIDE A STICKER ON THE WALL BY THE SLEEVES DETAILING THE UL RATING AND DATE INSTALLED.

5. WHERE CABLE TRAY PASSES THROUGH NON-RATED WALLS, PROVIDE FRAMING IN THE STUDS AND DRYWALL TO ALLOW THE CABLE TRAY TO PASS THROUGH. PROVIDE SLEEVES FOR

CABLE TRAY IF IT PASSES THROUGH SMOKE OR FIRE RATED WALLS.

ABBREVIATIONS

AFF - ABOVE FINISHED FLOOR

UNO - UNLESS NOTED OTHERWISE

AC - ABOVE COUNTER (+6" ABOVE BACKSPLASH)

CLG - ABOVE CEILING

(E) - EXISTING

ELEV - ELEVATION

HGT - HEIGHT

MAX - MAXIMUM

MIN - MINIMUM

N/A - NOT APPLICABLE

NIC - NOT IN CONTRACT

NO / # - NUMBER

NTS - NOT TO SCALE

SPEC - SPECIFICATION

STD - STANDARD

TR - TELECOM ROOM

TYP - TYPICAL

UG - UNDERGROUND

WP - WEATHERPROOF

WAO - WORK AREA OUTLET

TECHNOLOGY LEGEND

GENERAL NOTES

ROUGH-IN AND SUPPORT NOTES

X

T1

(X) SSXX

SYMBOL DESCRIPTION DETAIL #

PROVIDE

CONDUIT

NOTES

SYMBOLS

END USER DEVICE SYMBOL EXAMPLE -- --

THIS SYMBOL AND SIMILARLY NAMED DEVICE SYMBOLS ARE FOR I.T. COORDINATION

AND PLANNING ONLY.

TYPICAL ROOM RECTANGLE.

X = TYPICAL ROOM DESIGNATION

REF. = ENLARGED VIEW/SHEET REFERENCE

TYPICAL ROOMS ARE SHOWN ON PLANS USING THIS SYMBOL WITH A LETTER

DESIGNATION. THE LETTER MATCHES A TYPICAL ROOM LAYOUT ON THE ENLARGED

ROOM PLANS. PROVIDE ALL DEVICES IN THE TYPICAL LAYOUT TO THE ROOMS IN

WHICH THIS SYMBOL IS SHOWN.

J-HOOK PATHWAY -- -- PROVIDE J-HOOKS AS REQUIRED TO ROUTE CABLING.

CABLE TRAY -- -- PROVIDE CABLE TRAY PER SPECIFICATIONS. REFER TO TAG ON DRAWINGS FOR SIZE.

LADDER RACK -- -- PROVIDE LADDER RACK PER SPECIFICATIONS. REFER TO DRAWINGS FOR SIZE.

SMOKE AND FIRE RATED SLEEVE ASSEMBLY. QUANTITY AND

TYPE INDICATED ON THE DRAWINGS.

ROUTE CABLING THROUGH SLEEVES. INSTALL IT NETWORK CABLING IN SEPARATE

SLEEVE FROM LOW VOLTAGE CABLING.

CONDUIT SLEEVES

4" CONDUIT FLOOR CORE -- --

PATHWAYS & PENETRATIONS

1. THE INFORMATION ON THIS SHEET APPLIES TO ALL OF THE TECHNOLOGY AND LOW VOLTAGE SYSTEMS REPRESENTED IN THIS SET OF DRAWINGS.

2. THESE DRAWINGS ARE COMPLEMENTARY TO THE SPECIFICATIONS. ITEMS REQUIRED BY EITHER THESE DRAWINGS OR SPECIFICATIONS ARE BINDING AS THOUGH THEY ARE REQUIRED BY BOTH. REVIEW THE SPECIFICATIONS IN DETAIL AND USE IN CONJUNCTION WITH THESE DRAWINGS.

3. CABLE TRAY, CONDUIT, AND J-HOOKS ARE SHOWN IN THEIR APPROXIMATE REQUIRED LOCATION. CONTRACTORS SHALL COORDINATE WITH OTHER TRADES PRIOR TO INSTALLATION.

4. CABLING SHALL NOT BE INSTALLED FREE ABOVE INACCESSIBLE CEILINGS, IT SHALL BE INSTALLED IN CONDUIT EVEN IF NOT SPECIFICALLY SHOWN ON THE DRAWINGS.

5. ANY CABLES INSTALLED IN CABLE TRAY SYSTEMS NOT SPECIFICALLY SHOWN ON THESE DRAWINGS OR INCLUDED IN THE DIVISION 27 AND 28 SPECIFICATIONS SHALL BE APPROVED BY THE

CONSULTANT PRIOR TO INSTALLATION.

6. COMPONENTS AND INSTALLATION SHALL COMPLY WITH NFPA 70 "NATIONAL ELECTRICAL CODE". CROSS REFERENCE AND COORDINATE WITH ELECTRICAL DRAWINGS.

7. COORDINATE ALL SERVICE REQUIREMENTS WITHIN ITEMS OF MILLWORK, CASEWORK AND CEILINGS.

8. ANY QUESTIONS AND/OR CONCERNS ABOUT THE WORK TO BE PERFORMED SHALL BE ADDRESSED PRIOR TO THE START OF THAT WORK. OTHERWISE THE CONTRACTOR SHALL BE THE

RESPONSIBLE PARTY ONCE THAT WORK HAS STARTED.

9. CONTRACTOR TO FIELD VERIFY DATA OUTLETS QUANTITIES IN FIELD PRIOR TO INITIATING WORK. QUANTITIES OF WAO DEVICES AND WAO DEVICE CABLING IN FIELD MAY VARY FROM DESIGN DRAWINGS. ANY VA OIT NETWORK WAO DEVICES NOT SHOWN ON DRAWINGS SHOULD BE INCLUDED IN SCOPE OF THIS PROJECT UP TO A QUANTITY OF 10% ADDITIONAL WAO

DEVICES AND WAO DEVICE CABLING.

10. TEBCS SHALL BE SEPARATED BY A MINIMUM OF 2" FROM CONDUCTORS OF OTHER CABLE GROUPS SUCH AS POWER OR TELECOMMUNICATIONS CABLE. TEBCS SHALL BE SEPARATED FROM FERROUS MATERIAL BY A DISTANCE OF AT LEAST 2" WHERE ACHIEVABLE, OR BE EFFECTIVELY BONDED TO THE FERROUS MATERIAL.

11. MAINTAIN 12” SEPARATION BETWEEN POWER (120V AND HIGHER) CONDUCTORS, CONDUITS, AND RECEPTACLES AND CURRENT CARRYING TELECOMMUNICATIONS MEDIA (TYPICALLY UTP).

12. WHERE ELECTRICAL AND TELECOMMUNICATIONS CONDUCTORS AND CONDUITS MUST CROSS, CROSS AT 90° ANGLES (PERPENDICULAR). ATTEMPT TO MAINTAIN 12” SEPARATION WHERE

POSSIBLE.

13. PROVIDE 36” SEPARATION BETWEEN ELECTRICAL DISTRIBUTION EQUIPMENT (POWER PANELS, UPS EQUIPMENT, TRANSFORMERS, VARIABLE FREQUENCY DRIVES (VFDS), CRAC UNITS, ET

CETERA) RATED AT 480V OR LOWER AND TELECOMMUNICATIONS EQUIPMENT AND MEDIA.

14. PROVIDE 10’ SEPARATION FROM LARGER ELECTRICAL DISTRIBUTION EQUIPMENT (480V DISTRIBUTION BUSWAY, MEDIUM-VOLTAGE BUILDING TRANSFORMERS, MAIN SWITCHGEAR AND

MOTOR CONTROL CENTERS, ET CETERA) AND TELECOMMUNICATIONS EQUIPMENT AND MEDIA.

15. WALLS, FLOORS, AND CEILINGS DO NOT PROVIDE SIGNIFICANT SHIELDING AGAINST EMI TRANSMISSION. THEREFORE, ENSURE THAT ADJACENT SPACES DO NOT CONTAIN EMI-GENERATING EQUIPMENT PRIOR TO LOCATING TELECOMMUNICATIONS EQUIPMENT OR MEDIA FOR EXAMPLE ON THE OPPOSITE SIDE OF A WALL WHERE A POWER DISTRIBUTION PANEL IS MOUNTED.

NOTE THAT TELECOMMUNICATIONS ROOMS ARE SOMETIMES LOCATED ADJACENT TO ELECTRICAL ROOMS, MAKING THIS A NON-TRIVIAL CONCERN.

16. MAINTAIN A MINIMUM 12” SEPARATION BETWEEN POWER DISTRIBUTION RECEPTACLES AND CURRENT-CARRYING CONDUCTORS AND UTP AND OTHER CONDUCTIVE TRANSMISSION MEDIA.

17. CURRENT-CARRYING CONDUCTORS AND CONDUITS CONTAINING SUCH MAY NOT BE RUN PARALLEL TO THE UTP AND OTHER CONDUCTIVE TRANSMISSION MEDIA, INCLUDING EITHER IN OR

MOUNTED TO (SIDE OR BOTTOM) OF CABLE TRAYS.

18. INSTALL POWER IN SEPARATE CONVEYANCES TO MAINTAIN THE MINIMUM 12” SEPARATION; SEPARATE CABLE TRAY SYSTEMS FOR POWER DISTRIBUTION AND CEILING-MOUNTING OF

CONDUIT FOR BRANCH CIRCUITS ARE BOTH ACCEPTABLE.

19. INSTALLERS MUST CONFIRM THAT EVERY CORDSET AND EVERY DEVICE IS COMPATIBLE WITH THE SOURCE POWER VOLTAGE BEFORE CONNECTING THEM, OTHERWISE EQUIPMENT

DAMAGE MAY RESULT.

1. PROVIDE ALL BACKBOX AND CONDUIT ROUGH-IN AS INDICATED ON THE LEGENDS, FLOOR PLANS, RISER DIAGRAMS AND OTHER DRAWINGS. PROVIDE PULL STRINGS IN ALL CONDUITS.

PROVIDE SMOOTH INSULATED BUSHINGS ON ALL CONDUITS.

2. PROVIDE ALL FLOOR AND WALL PENETRATIONS INCLUDING CONDUIT SLEEVES, FLOOR CORES, FLOOR BOXES, POKE-THRUS, CONDUITS, FIRE-RATED AND SMOKE-RATED SLEEVES. PROVIDE SPECIFIED FIRE RATED DEVICES PER THE NOTES ON THIS SHEET AND SPECIFICATION SECTIONS.

3. REFER TO THE ARCHITECTURAL ELEVATIONS AND DETAILS FOR THE EXACT HEIGHT AND PLACEMENT OF OUTLETS AND OTHER LOW VOLTAGE SYSTEM DEVICES PRIOR TO ROUGH-IN.

ELECTRICAL CONTRACTOR TO LOCATE DATA OUTLET BACKBOX AT SAME HEIGHT AS CORRESPONDING ELECTRICAL OUTLET, EITHER BELOW OR ABOVE COUNTER, AT COUNTERTOP LOCATIONS. LOCATE ALL BACKBOXES AT FURNITURE LOCATIONS TO BE ACCESSIBLE AND TO MISS FURNITURE SUPPORT CHANNELS.

4. CONDUIT INSTALLED SHALL COMPLY WITH NEC REQUIREMENTS FOR CONDUIT INSTALLATION. PROVIDE PULLBOX ON CONDUIT RUNS EVERY 150', AFTER (2) 90 DEGREE BENDS AND AS

OTHERWISE REQUIRED BY NEC.

5. ALL INTERIOR JUNCTION BOXES SHALL BE NEMA 1 RATED UNLESS OTHERWISE SPECIFIED. ALL EXTERIOR JUNCTION BOXES SHALL BE NEMA 4 RATED WITH HINGED COVERS UNLESS OTHERWISE SPECIFIED. USE MYERS HUB CONNECTORS AT EXTERIOR OR JUNCTION BOX LOCATIONS.

6. ELECTRICAL CONTRACTOR SHALL MOUNT THE DATA OUTLET AND ELECTRICAL OUTLET IN A RIGID BOX MOUNTING BRACKET TO ENSURE CONSISTENT SPACING THROUGHOUT.

7. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING AND VERIFYING PLACEMENT OF ALL OUTLETS, CONDUIT, FLOOR BOXES, POKE-THRUS, ETC. WITH THE FURNITURE OR EQUIPMENT SUPPLIER TO ENSURE PROPER PLACEMENT WITH INSTALLED DEVICES. ADDITIONAL CHARGES FOR RELOCATING OUTLETS, CONDUIT, FLOOR BOXES, ETC. NOT PROPERLY

COORDINATED OR INSTALLED WILL NOT BE ACCEPTED.

8. PROVIDE GROUNDING PER THE GROUNDING DETAILS IN THE DRAWINGS AND SPECIFICATIONS.

9. PRIOR TO INSTALLING ANY ELECTRICAL CONNECTIONS IN THE TRS/IDFS, COORDINATE THE EXACT POWER RECEPTACLE TYPES, LOCATIONS, PANEL LOCATIONS AND CONDUIT ROUTING

WITH THE CONSULTANT.

10. SUPPORT ALL CABLE TRAY FROM STRUCTURE AT A MINIMUM OF 8'-0" ON CENTER AND WITHIN 1'-0" OF EACH END WITH TWO 1/2" DIAMETER ALL THREAD RODS AND HANGER KITS. USE TRAPEZE HANGER FOR CABLE TRAY; DO NOT CENTER MOUNT OR WALL MOUNT TRAY. HANGER SHALL SUPPORT FULL WIDTH OF CABLE TRAY AND BE HUNG FROM CEILING WITH ALL THREAD RODS. FOR HORIZONTAL TEE'S AND 90 DEGREE TURNS, FIELD CUT AND FABRICATE. PROVIDE RADIAL SWEEPING TURNS. BOND CABLE TRAY TO GROUND EVERY 50 FEET.

11. COORDINATE CABLE TRAY INSTALLATION WITH MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, DUCTWORK, CONDUITS, PIPING AND ALL OTHER TRADES PRIOR TO ORDERING AND

INSTALLING.

REF.

WALL MOUNTED JUNCTION BOX SEE NOTE

REFER TO LOCATIONS NOTED ON DRAWINGS. PROVIDE ROUGH-IN AS NOTED WITH

KEYED NOTE REQUIREMENTS. ROUTE CONDUIT AS NOTED ON DRAWINGS AND

PROVIDE PULL STRING.

JB

WIREMOLD RACEWAY. MOUNT DATA OUTLET IN WIREMOLD

FOR QUANTITY AND LOCATIONS SHOWN ON THE DRAWINGS.

PROVIDE ROUGH-IN PER WIREMOLD INSTRUCTIONS.

PROVIDE CONDUIT SLEEVE(S). REFER TO DRAWINGS FOR QUANTITY AND SIZE.

SEE NOTE

SEE NOTE

(1) 4"

LEGEND NOTES

LEGEND: (LOW VOLTAGE COORDINATION LEGEND)

CF: CONTRACTOR FINISHED

CI: CONTRACTOR INSTALLED

OF: OWNER FINISHED

OI: OWNER INSTALLED

REMARKS: (LOW VOLTAGE COORDINATION LEGEND)

1. PATCH PANELS SHALL BE CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED PER SPECIFICATION. REFER TO TYPICAL COMMUNICATION TERMINATION DETAIL.

2. PHYSICAL ACCESS CONTROL SYSTEM (PACS) FOR TELECOMMUNICATIONS ROOMS IS AN EXTENSION OF AN EXISTING LENEL SECURITY SYSTEM. NEW DEVICES SHALL FUNCTION AS AN

EXTENSION OF THE EXISTING SYSTEM.

3. SECURITY SURVEILLANCE TELEVISION (SSTV) SYSTEM IS AN EXTENSION OF AN EXISTING MILESTONE SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE EXISTING

SYSTEM.

4. PATCH CABLES TO BE PROVIDED BY CONTRACTOR PER TYPICAL COMMUNICATION TERMINATION DETAIL.

GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)

A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.

B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.

C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.

D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS OTHERWISE NOTED.

E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL CABLING PER SPECIFICATION.

PROJECT PHASING NOTES

(NOTES SHALL APPLY TO OVERALL PROJECT PHASING)

PHASING SEQUENCE LISTED BELOW IS FOR INFORMATION ONLY. CONTRACTOR SHALL BE RESPONSIBLE FOR DEVELOPING PROJECT SCHEDULE AND PHASING AND SHALL INCLUDE WORK REQUIRED TO ACCOMMODATE PHASING, SUBMIT PHASING PLAN TO OWNER FOR REVIEW AND APPROVAL AND COORDINATE WITH OWNER PRIOR TO BEGINNING CONSTRUCTION.

EXISTING ENTRANCE FACILITY ROOM: LOCATED IN BUILDING 1

EXISTING MAIN COMPUTER ROOM: LOCATED IN BUILDING 1

NEW ENTRANCE FACILITY ROOMS (QTY 2): LOCATED IN NEWLY CONSTRUCTED DC BUILDING

EXISTING MAIN COMPUTER ROOM: LOCATED IN NEWLY CONSTRUCTED DC BUILDING

A. NEW ENTRANCE FACILITY ROOM AND NEW MAIN COMPUTER ROOM: CONSTRUCT THE NEW ENTRANCE FACILITY ROOMS AND THE NEW MAIN COMPUTER ROOM TO BE OPERATIONAL.

ROUTE NEW TELECOMMUNICATIONS PROVIDER ENTRANCE CABLING FROM THE PROVIDERS NEW ORIGINATION POINT ON THE CAMPUS SITE TO THE NEW ENTRANCE FACILITY ROOMS, AND SUBSEQUENT CABLING FROM THERE TO THE NEW MAIN COMPUTER ROOM. PROVIDE FIBER INTERCONNECTIONS BETWEEN THE EXISTING MAIN COMPUTER ROOM AND THE NEW MAIN COMPUTER ROOM FOR PARALLEL NETWORK OPERATIONS OF THE EXISTING AND NEW DISTRIBUTION NETWORKS FOR THE DURATION OF CONSTRUCTION. COORDINATE WITH THE VA FOR THEIR RELOCATION EQUIPMENT FROM THE EXISTING MAIN COMPUTER ROOM TO THE NEW MAIN COMPUTER ROOM. MAINTAIN THE EXISTING ENTRANCE FACILITY ROOM AND EXISTING MAIN COMPUTER ROOM AS CURRENTLY CONSTRUCTED TO BE OPERATIONAL AND ACTIVE IN A PARALLEL CONDITION UNTIL THE END OF THE PROJECT.

B. SITE FIBER TO BUILDINGS: CONSTRUCT REDUNDANT SITE FIBER LOOP FROM NEW MAIN COMPUTER ROOM TO ALL BUILDINGS. MAINTAIN EXISTING FIBER PATHWAYS FROM THE EXISTING

MAIN COMPUTER ROOMS AS CURRENTLY CONSTRUCTED UNTIL THE END OF THE PROJECT.

C. NEW TELECOMMUNICATIONS ROOMS AND RE-SUPPORTED EXISTING TELECOMMUNICATIONS ROOMS: CONSTRUCT NEW TELECOMMUNICATIONS ROOMS. TELECOMMUNICATIONS ROOMS TO BE FULLY OPERATIONAL. CONFIRM THAT ALL NECESSARY NETWORK EQUIPMENT IS OPERATIONAL AND TESTED. RE-SUPPORT EXISTING TELECOMMUNICATIONS TO REMAIN WITH NEW RACKS AND BACKBONE CABLING. PROVIDE NEW A/B POWER PANELS AND GROUNDING IN NEW AND EXISTING TO REMAIN ROOMS. POWER ALL TELECOMMUNICATIONS ROOM LOADS FROM THE NEW PANELS. ROUTE NEW PRIMARY AND REDUNDANT FIBER TO TELECOMMUNICATIONS ROOMS AND EXISTING TO REMAIN TELECOMMUNICATIONS ROOMS FROM THE NEW MAIN COMPUTER ROOM. UPON ACTIVATION OF THESE NEW AND RE-SUPPORTED ROOMS, BOTH THE NEW AND EXISTING DISTRIBUTION NETWORKS WILL BE SIMULTANEOUSLY ACTIVE TO ALLOW FOR RE-CABLING THE PROGRESSIVE TRANSITION FROM THE EXISTING NETWORK TO THE NEW NETWORK FOR AREA OUTLET INDIVIDUALLY.

D. EXISTING TELECOMMUNICATIONS ROOMS: MAINTAIN THE EXISTING TELECOMMUNICATIONS ROOMS AND EXISTING BACKBONE CABLING UNTIL THE AREA OUTLETS BEING SERVED BY EACH RESPECTIVE TELECOMMUNICATIONS ROOM HAS BEEN TRANSITIONED TO THE NEW TELECOMMUNICATIONS ROOM.

E. RE-CABLING: FOR NEW TELECOMMUNICATIONS ROOMS, PROVIDE NEW CABLES FROM THE EXISTING AREA OUTLETS TO THE NEW RACKS. REMOVE EXISTING CATEGORY 5E OR LOWER CABLING AFTER NEW CABLES HAVE BEEN PULLED TO THE OUTLETS TO MAINTAIN OPERATIONAL CAPABILITY OF THE SPACES TO THE GREATEST EXTENT POSSIBLE.

F. EXISTING CABLE REMOVAL: AFTER NEW CABLING HAS BEEN INSTALLED AND ACTIVATED, REMOVE EXISTING BACKBONE CABLING AND EXISTING AREA OUTLET CABLING FROM TELECOMMUNICATION ROOMS BEING ABANDONED, REMOVE UNUSED CABLING IN PREVIOUSLY ABANDONED TELECOMMUNICATIONS ROOMS.

G. INTER-BUILDING BACKBONE: REPLACE THE EXISTING INTER-BUILDING BACKBONE CABLING WITH NEW BACKBONE CABLING. REUSE THE EXISTING BACKBONE PATHWAYS FOR NEW BACKBONE CABLE INSTALLATION. SIDE A FIBER ROUTE SHALL UTILIZE EXISTING PATHWAYS. EXISTING FIBER UTILIZING EXISTING PATHWAYS SHALL NOT BE REMOVED UNTIL NEW FIBER

ROUTE B IS COMPLETE AND NEW TELECOMMUNICATIONS ROOMS ARE ONLINE AND FUNCTIONING.

H. EXISTING TELECOMMUNICATIONS PROVIDER: REMOVE THE TELECOMMUNICATIONS PROVIDER CABLING TO EH EXISTING ENTRANCE FACILITY ROOM AND SUBSEQUENT EXISTING BACKBONE CABLING FROM THERE TO THE EXISTING MAIN COMPUTER ROOM. COORDINATE WITH THE VA AND REMOVE/RELOCATE ANY REMAINING ITEMS FROM THE EXISTING MAIN

COMPUTER ROOM. DEMOLISH THE EXISTING MAIN COMPUTER ROOM.

I. SERVER MIGRATION: WITH BOTH THE EXISTING AND NEW DISTRIBUTION NETWORKS BEING SIMULTANEOUSLY ACTIVE THROUGHOUT THE PROGRESSION OF RE-CABLING AND OUTLET TRANSITIONS, MIGRATION OF SERVERS FROM THE EXISTING SERVER ROOM THE NEW MAIN COMPUTER ROOM SHALL OCCUR BETWEEN THE TIME THAT THE NEW NETWORK IS ACTIVATED (AND READY TO ACCEPT NEW CABLE), BUT BEFORE THE OLD NETWORK IS DEACTIVATED AND REMOVED. AT ALL TIMES, TWO (2) CORE SWITCHES NEED TO BE ACTIVE TO MAINTAIN UTILIZATIONS OF EXISTING SERVER ROOM AND NEW SERVER ROOM TO ACCOMMODATE PHASING OF SYSTEMS FROM OLD ROOM TO NEW ROOM.

J. NETWORK ELECTRONICS COORDINATION: CONSIDERING THE ABOVE PHASING, COORDINATION WILL BE REQUIRED BETWEEN THE VA AND CABLING CONTRACTOR IN ORDER TO PROPERLY SEQUENCE THE ACQUISITION, CONFIGURATION, AND ACTIVATION OF NETWORK ELECTRONICS IN COORDINATION WITH THE ACTIVATION OF EACH NEW NETWORK DISTRIBUTION POINT, ACTIVATION OF EACH RE-CABLED OUTLET, AND THE SUBSEQUENT DEACTIVATION OF BOTH EXISTING OUTLET CABLES AND EXISTING NETWORK DISTRIBUTION

POINTS.

SYSTEMS

ROUGH-INS &

PATHWAYS

CABLING & TERMINATIONS

DEVICES &

EQUIPMENT

REMARKS

PHYSICAL ACCESS CONTROL SYSTEM (PACS)

SECURITY SURVEILLANCE TELEVISION (SSTV)

VOICE/DATA

WIRELESS ACCESS POINTS

CF/CI

CF/CI

CF/CI

CF/CI

CF/CI

CF/CI

OF/OI

OF/OI

1, 4

CF/CI

CF/CI

CF/CI

CF/CI

LOW VOLTAGE COORDINATION LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:5

P

M

T-000

TELECOMMUNICATIONS COVER

PAGE

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

05/24/23 PR TL

B01

Revisions: Date:

WALL PHONE COMMUNICATION OUTLET

SYSTEM FURNITURE COMMUNICATION OUTLET

ABOVE COUNTER COMMUNICATION OUTLET

COMMUNICATION OUTLET

SYMBOL DESCRIPTION

MOUNTING HEIGHT

ABOVE FINISHED

FLOOR, UNLESS NOTED

OTHERWISE

NUMBER OF

UTP CABLES

+18"

+6" ABOVE BACKSPLASH

IN SYSTEM FURNITURE

+54"

+18"

AS NOTED ON PLANS

(2)

(2)

(2)

(1)

(2)

WALL OR FURNITURE MOUNTED DEVICES

FURNITURE FEED

WIRELESS ACCESS POINT WALL MOUNTED OUTLET

UNDER OR IN FLOOR DEVICES

CEILING MOUNTED / ABOVE CEILING DEVICES

COMMUNICATIONS / POWER FLOOR BOX

DATA CEILING OUTLET

SECURITY CAMERA DATA CEILING OUTLET

WIRELESS ACCESS POINT OUTLET:

NO TAG - CAMPUS WIRELESS

EX - EXISTING WIRELESS

GW - VA GUEST WIRELESS

(2)IN FLOOR

(2)

(2)

(1)

ABOVE ACCESSIBLE

CEILING

ABOVE ACCESSIBLE

CEILING

ABOVE ACCESSIBLE

CEILING

AC

F

W

FF

FACEPLATE

TYPE

NOTES

PROVIDE

BACKBOX

PROVIDE

PLASTER

RING

PROVIDE

CONDUIT

PROVIDE

BACKING

PER ARCH.

DETAILS

NOTES

COMM-2 # INDICATES QUANTITY OF CABLES IF OTHER THAN TYPICAL.

# INDICATES QUANTITY OF CABLES IF OTHER THAN TYPICAL.

# INDICATES QUANTITY OF CABLES IF OTHER THAN TYPICAL.

COMM-2

FURN-1

WPH

COMM-2

ROUTE CABLING IN CONDUIT TO SYSTEM FURNITURE OUTLET.

PROVIDE TYPICAL FACEPLATE FOR ACCESS POINT.

2-GANG --

(1) 1"

(1) 1"

(1) 1"

(2) 1-1/4"

(1) 1"

PROVIDE CONDUIT FROM BOX INTO CLOSEST ACCESSIBLE CEILING SPACE AND CAP WITH NYLON

BUSHING. PROVIDE PULL STRING.

PROVIDE CONDUIT FROM BOX INTO CLOSEST ACCESSIBLE CEILING SPACE AND CAP WITH NYLON

BUSHING. PROVIDE PULL STRING.

PROVIDE ROUGH-IN FOR FURNITURE FEED.

LEAVE 6" CLEARANCE ON WALL FROM CENTER OF FINISHED BACKBOX IN ALL DIRECTIONS. PROVIDE CONDUIT FROM BOX INTO CLOSEST ACCESSIBLE CEILING SPACE AND CAP WITH NYLON BUSHING.

PROVIDE PULL STRING.

PROVIDE CONDUIT FROM BOX INTO CLOSEST ACCESSIBLE CEILING SPACE AND CAP WITH NYLON

BUSHING. PROVIDE PULL STRING.

PROVIDE CONDUIT FROM BOX INTO CLOSEST ACCESSIBLE CEILING SPACE AND CAP WITH NYLON

BUSHING. PROVIDE PULL STRING.

FB

BISC-2

BISC-2

BISC-1

# INDICATES QUANTITY OF CABLES IF OTHER THAN TYPICAL.

PROVIDE SURFACE MOUNT "BISCUIT" JACKS ABOVE ACCESSIBLE CEILING.

# INDICATES QUANTITY OF CABLES IF OTHER THAN TYPICAL.

PROVIDE SURFACE MOUNT "BISCUIT" JACKS ABOVE ACCESSIBLE CEILING.

# INDICATES QUANTITY OF CABLES IF OTHER THAN TYPICAL.

PROVIDE SURFACE MOUNT "BISCUIT" JACKS ABOVE ACCESSIBLE CEILING.

PROVIDE CONTINUOUS CONDUITS FROM FLOOR BOX OVER TO WALL AND UP INTO ACCESSIBLE

CEILING SPACE OF THE LEVEL IT SERVES. CAP WITH NYLON BUSHINGS AND PROVIDE PULL STRINGS.

REFER TO DETAIL FOR CONDUIT SIZE REQUIREMENTS.

STRUCTURED CABLING SYSTEM LEGEND

BY CABLING CONTRACTOR ROUGH-IN AND SUPPORT BY ELECTRICAL CONTRACTOR

1-GANG

2-GANG 1-GANG

2-GANG 1-GANG

2-GANG 2-GANG

2-GANG 1-GANG

CAM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:5

A

M

T-010

STRUCTURED CABLING LEGEND ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

JJ

HH

G8G8

GG

FF

EE

DD

C8C8

CC

BB

A8A8

8 9

9 9.2

9.2 9.8

9.8 10.4

10.4

11.2

11.2 11.8

11.8

12.2

12.2

1818.2

18.2

19.6

19.6

19.8

19.8

20.8

20.821.2

21.2 22

A6A6

AA

H4H4

B01-TN304

B01-TN303

B01-TN302

B01-TN301

TR 1-BA-216

TR 1-BB-221

TR 1-BC-216

TR 1-BC-250

AREA G

AREA H

AREA A

AREA B

AREA C

AREA D

AREA E

AREA F

ROUTE CABLING TO

TELECOM ROOM

TR 1-BA-216

ROUTE CABLING TO

TELECOM ROOM

TR 1-BB-221

ROUTE CABLING TO

TELECOM ROOM

TR 1-BC-216

ROUTE CABLING TO

TELECOM ROOM

TR 1-BC-250

(4) SS44 (4) SS44

(4) SS44

(4) SS44

(4) SS44

(4) SS44

(4) SS44

(4) SS44

(4) SS44

(4) SS44

(4) SS44

(4) SS44

(2) SS24

(2) SS24

(2) SS24

(4) SS44

(4) SS44(4) SS44 (4) SS44

(4) SS44

(4) SS44

(2) SS24

(4) SS44

(4) SS44

18"x4"

"x

"x

"x

"x

18"x4" 18"x4"

"x

"x

18"x4"

18"x4" 18"x4"

"x

18"x4"

"x

"x

12"x4"

"x

18"x4"

"x

18"x4"

18"x4" 18"x4"

"x

18"x4"

18"x4"

"x

18"x4"

"x

"x

(4) SS44

(4) SS44

LEGEND

DELINIATATION LINE BETWEEN

TELECOM ROOMS. ROUTE THE CABLING

FOR ALL SYSTEMS TO THE TELECOM

ROOMS SHOWN ON THE DRAWINGS

BASED ON THIS SEPARATION LINE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:3

A

M

B01-TN100

BASEMENT LEVEL OVERALL PLAN

- TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

1" = 20'-0"1

BASEMENT LEVEL OVERALL PLAN - TELECOM PLAN NORTH

20 20 40

1" = 20'-0"

FEETSCALE

GENERAL NOTES:

7. GOVERNMENT EQUIPMENT WILL BE RELOCATED BY

GOVERNMENT IT PERSONNEL. CONTRACTOR WILL

HAVE TECHNICIANS AVAILABLE TO PROVIDE

SUPPORT DURING OUTAGES AND CUT-OVERS.

COORDINATE WORK WITH THE COR.

8. CONTRACTOR SHALL PROVIDE MTP, FIBER OPTIC

TRUNK CABLES FOR SIDE A AND SIDE B BACKBONE

FROM THE DATA CENTER TO EACH

TELECOMMUNICATIONS ROOM. COORDINATE WITH

COR.

9. CONTRACTOR SHALL PROVIDE FIBER OPTIC PATCH

CABLES FOR SIDE A AND SIDE B FROM THE FIBER

OPTIC DISTRIBUTOR TO EQUIPMENT CABINETS.

COORDINATE WITH COR.

10. CONTRACTOR SHALL VERIFY FIBER OPTIC CABLES

MEASUREMENTS PRIOR TO ORDERING. COORDINATE

WITH COR.

11. PATHWAY SHOWN IN HALFTONE IS EXISTING AND

SHALL REMAIN IN PLACE. ROUTE NEW FIBER OPTIC

BACKBONE CABLING THROUGH EXISTING

INFRASTRUCTURE AS NOTED.

1. CONTRACTOR SHALL COORDINATE THE

EQUIPMENT'S INSTALLATION AND FINAL LOCATION

WITH THE ELECTRICAL AND MECHANICAL DIVISION.

REFER TO ELECTRICAL, MECHANICAL AND

PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS,

RADIUS DROP, AND ANY OTHER FITTING FOR A

PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE HILTI SPEED

SLEEVE LOCATIONS WITH THE PATHWAY SYSTEM

LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER

SLEEVES AND CONDUITS OF THE SIZE AS INDICATED

ON THE PLANS. REFER TO SECTION 27 10 00

STRUCTURED CABLING AND SECTION 27 05 33

CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR

BEFORE CORE DRILLING. CONTRACTOR SHALL

COORDINATE WITH THE COR BEFORE BEGINNING

DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES

AND EMPTY SPARE RISER SLEEVES. REFER TO

SECTION 07 84 00 FIRESTOPPING.

1. PROVIDE (2) 2" CONDUITS FOR HORIZONTAL CABLE

DISTRIBUTION.

2. PROVIDE (6) 4" CONDUITS FROM 1-BA-216 TO BUILDING

15 FOR HORIZONTAL CABLE DISTRIBUTION AND B-

SIDE BACKBONE PATHWAY.

KEYED NOTES:#

OFFICE STOREKEEPER

BA-210

WAREHOUSE RECEIVING

BA-201

HAC

BA-202

STAFF TLT

BA-204

STORAGE

BA-206

LOGISTICS PROPERTY MANAGEMENT

BA-207

OFFICE SUPPLIES

BA-212

MAIL ROOM

BA-215

MECH. ROOM

BA-215B

MAIL ROOM

BA-215A

DECONTAMINATION ROOM

BA-221

PREPARATION ASSEMBLY

BA-251A

MACHINE

BA-110

MALE LOCKERS

BA-272

FEMALE LOCKERS

BA-271

FEMALE TOILETS SHOWERS

BA-271A

MALE TLTS. SHOWERS

BA-272A

OFFICE

BA-261

OFFICE

BA-261A

OFFICE

BA-261B

OFFICE

BA-261C

CORR.

BA-C2

PIV OPERATIONS

BA-261

LOGISTICS OFFICE

BA-254

LOGISTICS OFFICE

BA-254A

SPS ASSISTANT CHIEF

BA-245

HAC

BA-249

FEMALE LOCKERS

BA-243

FEMALE TOILET

BA-243A

ANTE/GOWNING RM.

BA-242

MANUAL EQUP. WASH

BA-227

AUTO CART WASH

BA-225

SUPPLY/EQUIP. STORAGE

BA-251

HAC

BA-229

ANTE/GOWNING RM.

BA-232

MALE LOCKERS

BA-233

MALE TOILET

BA-235A

MALE LOCKERS

BA-235

MALE TOILET

BA-233A

FEMALE LOCKSER

BA-234

FEMALE TOILET

BA-234A

CLEAN RECEIVING & BREAKOUT

BA-241

QA SPECIALIST

BA-244

SRS CHIEF

BA-246

RME EDUCATOR

BA-252

CORR.

BA-C1

DISTRIB. SECTION

BA-106

ROOM

BA-108

PROGRAM COORDINATOR

BA-106A

MANAGEMENT MATERIAL

BA-106B

DISP. ADMIN. SCHEDULING MAS

CONTROL

BA-104

MAS ADMIN. SUPERV.

BA-103

ASST. CHIEF HIMS

BA-118

CHIEF HIMS

BA-119

CHIEF AMBULATORY

BA-120

VTP MANAGER

BA-121

CORR.

BB-201

OFFICE

BB-205

OFFICE

BB-207

OPERATIONS ROOM

BB-204

CONSOLE ROOM

BB-206

STORAGE

BB-209

MED GAS

BA-301

MED GAS

BA-303

MECHANICAL

BA-302

STAIR 4

6A-311

ANE-ROOM

BA-304

REFRIGERAT BODY HOLDING

BA-305

EMS STORAGE

BA-306

CANTEEN RECEIVING

BA-308

LAB/PATH

BA-310

EMS

BA-312

CORR.

BA-C4

PNEUMATIC TUBE FAN ROOM

BB-302A

MECHANCIAL

BB-304

CHIEF LOGISTIC SERVICE

BB-306

SOILEED SERVICE LOBBY

BB-302

UPS ELEC. RM.

BB-312B

ELEV.

S-4

ELEV.

S-5

STAIR 5

ST-5

CORR.

BA-C3

ELEC.

BB-307

TELE.

BB-121

CORR.

BB-302B

JJ

HH

G8G8

GG

FF

EE

DD

C8C8

8 9

9 9.2

9.2 9.8

9.82

H4H4

CAM

CAM

3 12

3 2

2 4 4 4 4 4

4 4

CAM

CAM

CAM

CAM

WAP

TR

BA-216

B01-TN301

4 4

3 3

KEY PLAN

AREA A

PLAN NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:3

A

M

B01-TN100A

BASEMENT LEVEL FLOOR PLAN -

AREA A - TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

1/8" = 1'-0"1

BASEMENT LEVEL FLOOR PLAN - AREA A - TELECOM

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED ON SITE

VISITS, REFER TO AS BUILTS FOR DATA DEVICE LAYOUTS.

3. DATA OUTLET RELOCATED FROM DEMOLISHED WALL IN

NEW TR.

KEYED NOTES:#

GENERAL NOTES:

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND

CONDUITS OF THE SIZE AS INDICATED ON THE PLANS. REFER

TO SECTION 27 10 00 STRUCTURED CABLING AND SECTION 27

05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE

CABLE TRAY ON THE WALL ABOVE THE VERTICAL RISER

SLEEVES FOR BACKBONE CABLE SUPPORT AS INDICATED ON

THE PLANS. THE CABLE TRAY SHALL BE SECURELY

ANCHORED TO THE WALL SUFFICIENT TO SUPPORT THE

TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT

TO SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL

CABLE TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS

NO CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH

PANELS IN THE TELECOMMUNICATION ROOM AS INDICATED ON

RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED.

EXISTING COMMUNICATION OUTLET BOXES AND CONDUITS TO

BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS.

NEW MODULAR JACKS SHALL BE OF THE SAME

MANUFACTURER AS THE FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES

AND CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-

TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

GENERAL NOTES:

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

CONROL SUBSTANCE STORAGE

BA-203

STAIR 3

STAIR

ELECT ROOM

BA-114

TELEPHONE SWITCHGEAR

BA-112

HIMS SUPV.

BA-115

ADMIN OFFICER

BA-116

SURV.

BA-117

MACHINE

BA-110

ADMIN. OFFICES/CUBICALS

BA-102

ROOM

BA-95

LOGISTIC

BA-97

CORRIDOR

CORRIDOR

ROOM

BA-99

CONFERENCE

BA-111

OFFICE

BA-109

ASST. CHEIF AMUBLATORY CARE

BA-107

ASST. CHIEF MAS

BA-105

STAIR #2

STAIR

BENEFICIAL TRAVEL

BA-101

ELEV.

P-1

ELEV.

P-2

ELEV.

P-3

MAS ADMIN. SUPERV.

BA-103

ASST. CHIEF HIMS

BA-118

CHIEF HIMS

BA-119

CHIEF AMBULATORY

BA-120

VTP MANAGER

BA-121

CORR.

BB-201

OFFICE

BB-205

OFFICE

BB-207

STORAGE

BB-209

C8C8

CC

BB

A8A8

8 9

9 9.2

9.2 9.8

9.82

A6A6

AA

F

4 4

4 4

4 4

4 4

4 4

CAM

4 4

CAM

CAM

GW

2 4 4 4 4 4 3

4 4

CAM

CAM

3 3 3

3 3 3

KEY PLAN

PLAN NORTH

AREA B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:4

A

M

B01-TN100B

BASEMENT LEVEL FLOOR PLAN -

AREA B - TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

1/8" = 1'-0"1

BASEMENT LEVEL FLOOR PLAN - AREA B - TELECOM

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED ON SITE

VISITS, REFER TO AS BUILTS FOR DATA DEVICE LAYOUTS.

3. DATA OUTLET LOCATION TO BE COORDINATED WITH

EXISTING FURNITURE SYSTEMS. ALL CABLING TO DATA

OUTLETS ARE TO USE THE EXISTING PATHWAY.

KEYED NOTES:#

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND

CONDUITS OF THE SIZE AS INDICATED ON THE PLANS. REFER

TO SECTION 27 10 00 STRUCTURED CABLING AND SECTION 27

05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE

CABLE TRAY ON THE WALL ABOVE THE VERTICAL RISER

SLEEVES FOR BACKBONE CABLE SUPPORT AS INDICATED ON

THE PLANS. THE CABLE TRAY SHALL BE SECURELY

ANCHORED TO THE WALL SUFFICIENT TO SUPPORT THE

TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT

TO SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL

CABLE TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS

NO CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH

PANELS IN THE TELECOMMUNICATION ROOM AS INDICATED ON

RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED.

EXISTING COMMUNICATION OUTLET BOXES AND CONDUITS TO

BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS.

NEW MODULAR JACKS SHALL BE OF THE SAME

MANUFACTURER AS THE FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES

AND CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-

TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

GENERAL NOTES:

5 5 10 15 20

1/8" = 1'-0"

POISON CONTROL

BB-112

CONTROL SUBSTANCE

BB-116

PHARMACY ADMIN.

BB-121

TELECOMM

BC-263

OFFICE

BC-263A

OFFICE

BC-263B

OFFICE

BC-263COFFICE

BC-263D

SWITCHBOARD

BC-261

STAFF TLT.

BC-261A

ASSOC. CHIEF

BB-122

PHARM SUPERVISOR

BB-121A

FREEZER

BB-253

MEAT REFRIGERATOR

BB-239

FOOD PROCESSING/PREPARATION

BB-251

CART STORAGE

BB-241

CART WASH

BB-242

WARE WASHING

BB-243

CLEANING EQUIPMENT ROOM

BB-243A

SANITARY

BB-245

HAC

BB-246

BLAST CHILLER

BB-248

REFRIG.

BB-249

CORR.

BB-251

POT WASHING

BB-252

FOOD STORAGE

BB-254

HAC

BB-256

PROGRAM SUPPORT

BB-258

NON-FOOD STORAGE

BB-259

DAIRY COOLER

BB-257

GENERAL COOLER

BB-255

TR

BB-221A

CHIEF

BB-221

CAN WASH

BB-223

SUPERV. OFFICE

BB-232

N & FS SUPERVISOR

BB-234

ASSISTANT CHIEF

BB-236

COOK FOREMAN

BB-238

NOURISHMENT PREPARATION

BB-233

OFFICE

BB-219A

CLERK

BB-219

PROGRAM MGM'T 8 PLANNING

BB-219B SUPERVISOR TECH. AND CLERKS

BB-235

UNIFORM ROOM

BB-237A

AUTO VALER ALCOVE

BB-217

FOOD SERVICE COORDINATION

CENTER

BB-237

CREDIT UNION OFFICE

BB-212A

WAITING

BB-212

CREDIT UNION TELLER

BB-212B

ELEC. CLOS.

BB-213

TELE SWITCH

BB-215

CORR.

BB-C2

CORR.

CB-7

MALE LOCKERS

BA-272

FEMALE LOCKERS

BA-271

CORR.

BB-201

INTERVIEW

BB-203

HOLDING

BB-203

OFFICE

BB-205

OFFICE

BB-207

SECURITY ROOM

BB-202

OPERATIONS ROOM

BB-204

EVIDENCE STORAGE

BB-204A

CONSOLE ROOM

BB-206

STORAGE

BB-209

CONFERENCE/CLASSROOM

BB-225

SOILEED SERVICE LOBBY

BB-302

UPS ELEC. RM.

BB-312B

ELEV.

S-4

ELEV.

S-5

ELEV.

S-1

ELEV.

S-2

ELEV.

S-3

MATERIAL MANAGEMENT

BB-322

MECHANICAL ROOM

BB-314

SEAMSTRESS

BB-324

SEAMSTRESS

BB-324A

PEST CONTROLLER

BB-332

PEST CONTROLLER

BB-334

BATTERY CHARGE

BB-336

STAIR 6

STAIR 6

MACHINE REPAIR SHOP

BB-338

CORR.

CB-44

TRASH

BC-302

CORR.

BB-C4

MECHANICAL

BC-314

CORRIDOR

BD-C1

ELEC.

BB-307

CORR.

BB-312A

HAC

BB-316

TELE.

BB-121

CORR.

BB-302B

JJ

HH

G8G8

GG

FF

EE

DD

C8C8

9.8

9.8 10.4

10.4

11.2

11.2 11.8

11.8

12.2

12.2

18 18.2

18.2

H4H4

CAM

CAM

4 6 4

GW

3 4

4 4

2 2 3

CAM

4 4

2 1

CAM

CAM

1 3

3 4 6 4

CAM CAM

CAM

CAM CAM

CAM

4 4 3

CAM

GW

B01-TN302

2 2

KEY PLAN

PLAN NORTH

AREA C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:4

A

M

B01-TN100C

BASEMENT LEVEL FLOOR PLAN -

AREA C - TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

1/8" = 1'-0"1

BASEMENT LEVEL FLOOR PLAN - AREA C - TELECOM

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED ON SITE

VISITS, REFER TO AS BUILTS FOR DATA DEVICE LAYOUTS.

3. DATA OUTLET RELOCATED FROM DEMOLISHED WALL IN

NEW TR.

KEYED NOTES:#

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND

CONDUITS OF THE SIZE AS INDICATED ON THE PLANS. REFER

TO SECTION 27 10 00 STRUCTURED CABLING AND SECTION 27

05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE

CABLE TRAY ON THE WALL ABOVE THE VERTICAL RISER

SLEEVES FOR BACKBONE CABLE SUPPORT AS INDICATED ON

THE PLANS. THE CABLE TRAY SHALL BE SECURELY

ANCHORED TO THE WALL SUFFICIENT TO SUPPORT THE

TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT

TO SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL

CABLE TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS

NO CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH

PANELS IN THE TELECOMMUNICATION ROOM AS INDICATED ON

RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED.

EXISTING COMMUNICATION OUTLET BOXES AND CONDUITS TO

BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS.

NEW MODULAR JACKS SHALL BE OF THE SAME

MANUFACTURER AS THE FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES

AND CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-

TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

GENERAL NOTES:

5 5 10 15 20

1/8" = 1'-0"

ELEV.

P-1

ELEV.

P-2

ELEV.

P-3

ELEV.

P-6

ELEV.

P-4

ELEV.

P-5

VESTIBULE

BB-C1

STAIR #1

STAIR

ELEV.

S-9LIFT 6

LIFT

STAFF TOILET

BB113

POISON CONTROL

BB-112

HAC

BB-115MACH. RM.

BB-104

LIFT 6 MACH. RM.

BB-102

ROOM

ROOM

PHARMACY SERVICE

BB-111

STORAGE BAY 5

STORAGE

BAY

STORAGE BAY 4

STORAGE

BAY

STORAGE BAY 3

STORAGE

BAY

STORAGE BAY 2

STORAGE

BAY STORAGE BAY 1

STORAGE

BAY

IV COMPOUND

BB-117

CHEMO COMPOUND

BB-118

ROOM

BB-119

ROOM

BB-120

CONTROL SUBSTANCE

BB-116

DRUG INFOR SERVICE

BB-118

CORR.

BB-121

PHARMACY ADMIN.

BB-121

CHIEF

BB-125

CONFERENCE

BB-123

ASSOC. CHIEF

BB-122

PHARM SUPERVISOR

BB-121A

IV & CHEMO PREP

ROOM

CREDIT UNION OFFICE

BB-212A

WAITING

BB-212

CREDIT UNION TELLER

BB-212B

ELEC. CLOS.

BB-213

TELE SWITCH

BB-215

CORR.

BB-201

INTERVIEW

BB-203

HOLDING

BB-203

OFFICE

BB-205

OFFICE

BB-207

C8C8

CC

BB

A8A8

9.8

9.8 10.4

10.4

11.2

11.2 11.8

11.8

12.2

12.2

18 18.2

18.2

A6A6

AA

CAM

CAM

CAM

CAM

CAM

CAM

CAM

4 4 4 4 4 4 4 6

F

CAM

4 6 4

CAM CAM

CAM

CAM

CAM CAM

CAM

F

F

F F

F

F

F

F

F

4 4

4 3

1 3

CAM

GW

KEY PLAN

PLAN NORTH

AREA D

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:5

A

M

B01-TN100D

BASEMENT LEVEL FLOOR PLAN -

AREA D - TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

1/8" = 1'-0"1

BASEMENT LEVEL FLOOR PLAN - AREA D - TELECOM

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED ON SITE

VISITS, REFER TO AS BUILTS FOR DATA DEVICE LAYOUTS.

3. DATA OUTLET RELOCATED FROM DEMOLISHED WALL IN

NEW TR.

KEYED NOTES:#

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND

CONDUITS OF THE SIZE AS INDICATED ON THE PLANS. REFER

TO SECTION 27 10 00 STRUCTURED CABLING AND SECTION 27

05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE

CABLE TRAY ON THE WALL ABOVE THE VERTICAL RISER

SLEEVES FOR BACKBONE CABLE SUPPORT AS INDICATED ON

THE PLANS. THE CABLE TRAY SHALL BE SECURELY

ANCHORED TO THE WALL SUFFICIENT TO SUPPORT THE

TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT

TO SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL

CABLE TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS

NO CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH

PANELS IN THE TELECOMMUNICATION ROOM AS INDICATED ON

RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED.

EXISTING COMMUNICATION OUTLET BOXES AND CONDUITS TO

BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS.

NEW MODULAR JACKS SHALL BE OF THE SAME

MANUFACTURER AS THE FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES

AND CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-

TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

GENERAL NOTES:

5 5 10 15 20

1/8" = 1'-0"

MALE LOCKERS

BC-101

MALE TLT.

BC-101A

FEMALE LOCKER

BC-103 INFORMATION SECURITY OFFICER

BC-112

ELEC. CLOSET

BC-114D

IRMS STORAGE

BC-114C

LINEN ALCOVE

BG-127

RECOVERY AND SCREENING

BG-128ELEC. CLOSET

BG-130

STAIR #3

STAIR

CORRIDOR

BC-C1

OUTDOOR RECREATION

BC-261

SUPPLIES/VOL. SERVICE

BC-260

REFRIG.

BC-241B

FREEZER

BC-241

FREEZER

BC-241A

CHIEF VOL. REC. THERAPY

BC-243

VOLUNTEER RECRUITMENT

BC-244

VOLUNTARY SERVICE

BC-245

COMPUTER TRAINING

BC-246

SAFETY OFFICE

BC-247

COMPUTER TRAINING

BC-248

TR

BC-250

SAFETY SUPERVISOR

BC-239

HAC

BC-257

FACILITIES PLANNING

BC-253

RECREATION THERAPY

BC-262

RECREATION THERAPY

BC-245A

ASST. CHIEF REC THERAPY

BC-264

FACILITY PLANNER

BC-266

EOC

BC-255

PSA EMS

BC-257

COMP. TRAINING

BC-265

VEST

C1-17

CORRIDOR

BC-C6

CORRIDOR

BC-C4

CORR.

BC-C4

FACILITY MANAGEMENT SERVICE

BC-231

CONF.

BC-231F

OFFICE

BC-231B

OFFICE

BC-231C

OFFICE

BC-231D

OFFICE

BC-231E

BIOMEDICAL ENGINEERING

BC-231A

ELEC. CLOSET

BC-240

T/S

BC-240A

BREAK ROOM

BC-215A

BIO. MED. REPAIR AND DEVELOPMENT

BC-215

WORKBENCH ELECTRONIC SHOP

BC-211

STORAGE

BC-213A

TOOLS

BC-213B

ELECTRICAL SHOP

BC-213

SHOP SUPER

BC-211A

CARPENTRY SHOP WORKROOM

BC-242

STORAGE

BC-242A

STORAGE

BC-242B

STORAGE

BC-242C

CORRIDOR

BC-C2

COMPUTER ROOM

BC-202

ADMIN OFF./SEC'Y

BC-203

BIOMEDICAL ENGINEER

BC-212

ELEC. CLOS.

BC-214

UPS ROOM

BC-202A

TR

BC-216

EQUIP. TECH WORK

BC-202A

ADP STORGE NON-SECURE

BC-304

CORR.

BB-C4

STAIR

BIOMEDICAL ENGINEERING

BC-312

TELE.

BC-316

ELECT.

BC-324

CLEAN SERVICE LOBBY

BC-318

LIFT FUTURE

LIFT

ELEV.

S-6

ELEV.

S-7

ELEV.

S-8

LOCKSMITH

BC-322 FEMALE TOILET

BC-334

PLUMBING SHOP

BC-336

LOGISTICS

BC-338 MALE TOILET

BC-340

PAINT SHOP

BC-342

VESTIBULE

BC-C3

EMS SUPER.

BC-351

EMS

BC-352

CHIEF EMS

BC-354

AO EMS

BC-356

EMS FOREMAN

BC-358

STORAGE

BC-360

WORKBENCH

BC-360A

STORAGE

BC-360B

CORR.

6A-333

MECHANICAL

BD-120

MECH CLOSET

BE-314

MECHANICAL

BD-123

MECHANICAL

BC-314

MECHANICAL

BC-314

AIR COMPRESSOR & VACUUM PUMPS

BE-104

DOMESTIC WATER ROOM

BE-103

A/C SHOP

BE-103

FIRE PUMP RM.

BE-132

CORRIDOR

BC-C1

JJ

HH

G8G8

GG

FF

EE

DD

C8C8

19.6

19.6

19.8

19.8

20.8

20.8 21.2

21.2 22

H4H4

2 6

GW

3 6

GW

4 4

CAM

GW

CAM

F

GW

F

F

4 F

F F 3 3

2 1 F

F

1 6

4 4

4 4

GW

GW

CAM

7 FF

GW

CAMCAM

33F

F

GW

4 4

12 12

4 4 4 4

WAP

WAP

B01-TN303

B01-TN304

UPS ROOM

BC-250A

BIOMEDICAL ENGINEERING

BC-218

KEY PLAN

PLAN NORTH

AREA E

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:0

A

M

B01-TN100E

BASEMENT LEVEL FLOOR PLAN -

AREA E - TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

1/8" = 1'-0"1

BASEMENT LEVEL FLOOR PLAN - AREA E - TELECOM

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED ON SITE

VISITS, REFER TO AS BUILTS FOR DATA DEVICE LAYOUTS.

3. DATA OUTLET RELOCATED FROM DEMOLISHED WALL IN

NEW TR.

KEYED NOTES:#

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND

CONDUITS OF THE SIZE AS INDICATED ON THE PLANS. REFER

TO SECTION 27 10 00 STRUCTURED CABLING AND SECTION 27

05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE

CABLE TRAY ON THE WALL ABOVE THE VERTICAL RISER

SLEEVES FOR BACKBONE CABLE SUPPORT AS INDICATED ON

THE PLANS. THE CABLE TRAY SHALL BE SECURELY

ANCHORED TO THE WALL SUFFICIENT TO SUPPORT THE

TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT

TO SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL

CABLE TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS

NO CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH

PANELS IN THE TELECOMMUNICATION ROOM AS INDICATED ON

RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED.

EXISTING COMMUNICATION OUTLET BOXES AND CONDUITS TO

BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS.

NEW MODULAR JACKS SHALL BE OF THE SAME

MANUFACTURER AS THE FACE PLATES, PATCH PANELS, AND

PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES

AND CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-

TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

GENERAL NOTES:

5 5 10 15 20

1/8" = 1'-0"

PHARMACY ADMIN.

BB-121

CHIEF

BB-125

CONFERENCE

BB-123

STAIR #7

STAIR

MALE LOCKERS

BC-101

MALE TLT.

BC-101A

FEMALE TLT.

BC-103A

FEMALE LOCKER

BC-103

ELEV.

P-7

ELEV.

P-8

ELEV.

P-9

ELEV.

P-10

IRMS SHCP SUPP.

BC-113

I.R.M.S. TELE

BC-114

INFORMATION SECURITY OFFICER

BC-112

CHIEF INFO OFFICE

BC-111 A

CHIEF IMS

BC-115

IRMS

BC-114

STORAGE

BC-114A

OFFICE

BC-114B

ELEC. CLOSET

BC-114D

IRMS STORAGE

BC-114C

CORRIDOR

BG-107

MRI SYSTEM COMPONENT ROOM

BG-106

MRI SCANNING ROOM

BG-123

ROOM

ROOM

TOILET

TOILET

TOILET

TOILET

ROOM

ROOM

ROOM

ROOM

CLEAN UTIL.

BG-115

WAITING ROOM

BG-109

EXIT CORRIDOR

BG-110

PREP RM

BG-111

PREP RM

BG-112

PREP RM

BG-113

PATIENT TOILET

BG-114

CHEIF TECH.

BG-117

HOLD ROOM

BG-118

MRI CONTROL ROOM

BG-121

HOLD ROOM

BG-119

READING ROOM

BG-120

MRI SCANNING ROOM

BG-122

CORRIDOR

BG-126

LINEN ALCOVE

BG-127

RECOVERY AND SCREENING

BG-128

HAC

BG-129

ELEC. CLOSET

BG-130

STAIR #3

STAIR

CORRIDOR

BC-C1

VEST

C1-17

CORRIDOR

BC-C1

CORRIDOR

BC-C1

C8C8

CC

BB

A8A8

19.6

19.6

19.8

19.8

20.8

20.8 21.2

21.2 22

A6A6

AA

F

CAM CAM1 1

GW

54444

GW

CAMCAM

4 4

4 4 4FF F

KEY PLAN

PLAN NORTH

AREA F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:0

A

M

B01-TN100F

BASEMENT LEVEL FLOOR PLAN -

AREA F - TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B01

1/8" = 1'-0"1

BASEMENT LEVEL FLOOR PLAN - AREA F - TELECOM

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED ON SITE

VISITS, REFER TO AS BUILTS FOR DATA DEVICE LAYOUTS.

3. DATA OUTLET RELOCATED FROM DEMOLISHED WALL IN

NEW TR.

KEYED NOTES:#

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND

CONDUITS OF THE SIZE AS INDICATED ON THE PLANS. REFER

TO SECTION 27 10 00 STRUCTURED CABLING AND SECTION 27

05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE

CABLE TRAY ON THE WALL ABOVE THE VERTICAL RISER

SLEEVES FOR BACKBONE CABLE SUPPORT AS INDICATED ON

THE PLANS. THE CABLE TRAY SHALL BE SECURELY

ANCHORED TO THE WALL SUFFICIENT TO SUPPORT THE

TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT

TO SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL

CABLE TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS

NO CABLE TRAY OR…