This document provides construction drawings for infrastructure upgrades at the Department of Veterans Affairs West Palm Beach facility in support of an electronic health record modernization project. The drawings cover mechanical, electrical, plumbing, and telecommunications aspects of the project, depicting existing conditions, demolition plans, and new construction work. Key project components include upgrading mechanical systems and air handling units, installing new electrical switchgear and panelboards, and expanding telecommunications rooms to support additional IT equipment. Completion of the work will enhance the facility's capacity for modern healthcare technologies as part of the VA's broader electronic health record modernization initiative.
View the file
Other files for this federal contract opportunity
Show all 37
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EE
DD
C8C8
18 18.2
18.2
E
D
C8
17 18 18.2
W14X68
W14X68
W14X68
W14X68
W14X68
W14X68
W14X68
W14X68
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
R C
8" x4
8"
R C
8" x3
6"
R C
8" x4
8"
R C
8" x3
6"
27' - 0"
9' - 0" 12' - 0" 6' - 0"
4'
3'
3'
3'
3'
3'
6'
0"
B01-S101
NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL EXISTING DIMENSIONS
2. T/STEEL = 3'-2" ABOVE STRCTURAL SLAB ELEVATION
3. SEE B23-S100 FOR STRUCTURAL GENERAL NOTES
4. REFER TO EXISTING BUILDING 1 DRAWINGS TITLED "NEW GENERAL MEDICAL, SURGICAL, INTERMEDIATE CARE, AND PSYCHIATRIC
HOSPITAL" FOR MORE INFORMATION ON EXISTING CONDITIONS
5. CONTRACTOR TO ENSURE COORDINATION OF STRUCTURAL STEEL WITH MECHANICAL DRAWINGS AND CHILLER MANUFACTURER PRIOR
TO SUBMITTAL OF STEEL SHOP DRAWINGS
6. ALL STEEL TO BE HOT DIPPED GALVANIZED
7. RC COLUMNS SHALL HAVE A 28 DAY COMPRESSIVE STRENGTH OF 5,000 PSI. SEE GENERAL NOTES SHEET FOR ADDITIONAL INFORMATION
NEW CHILLER UNITS. CONTRACTOR TO
COORDINATE ADDITIONAL CHILLER
SUPPORT BEAMS WITH CHILLER
MANUFACTURER AS REQUIRED
CROSSHATCH INDICATES
GALVANIZED METAL GRATING
DESIGNED FOR 20 PSF LIVE LOAD
B01-S101
W 14X68
W
X68
W 14X68
B01-S101
B01-S101
B01-S101
B01-S101
4'
4' - 0"
WP
WP
4' - 0"
WP
4' - 0"
WP
W
X68
WP
WP
4' - 0"
4'
STANDARD AISC SHEAR CONNECTION.
CONTRACTOR OPTION FOR SHEAR TAB
OR ANGLE CONNECTION. DESIGN FOR
MINIMUM OF 30 KIPS ASD
BEAM PER PLAN
EE
E
EMBED PLATE BELOW. SEE DETAIL 3 THIS
SHEET FOR MORE INFORMATION
2' - 0" 2' - 0"
4' - 0"
2'
2'
4'
5/16"
EMBED
PLATE
5/16"
CAP PLATE
PROVIDE 12"X12"X1"
PLATE, TOP OF
BEAMS
NEW CONCRETE COLUMN, PER PLAN
BEAM PER PLAN, TYP
MITERED BEAM CONNECTION
1" THICK EMBED PLATE W/ (5) 3/4" D1.1
GR B HEADED STUDS. MIN EMBED 9"
INTO NEW CONCRETE
(6) #5 BARS @ 3" OC EDGE
ANCHOR REINFORCEMENT
CENTERED ON EMBED PLATE
NEW
CONCRETE
COLUMN
1' - 0"
2' - 0" 2' - 0"
6" 6"
3" 3"
1'
" 6"
6"
3" 3"
4' - 0"
4'
2'
2'
BEAM PER PLAN
12"X12"X1" PLATE
NEW COLUMN PER PLAN
EXISTING STRUCTURAL SLAB
M
IN
2'
12"X12"X1" EMBED PLATE. SEE
DETAILS 3 AND 7 THIS SHEET
EXISTING CONCRETE COLUMN.
CONTRACTOR TO X-RAY FOR
REBAR PRIOR TO INSTALLING
EPOXY DOWELED REBAR FROM
NEW COLUMN
E M
B E
D
IN
E X
IS
T
IN
G
1'
0"DRILL AND EPOXY (12) #9
BARS IN A 4X4 PATTERN.
EPOXY TO BE HILTI-RE 500
V3 OR APPROVED EQUAL.
PROVIDE 90 DEGREE
HOOKED ENDS IN NEW
CONCRETE
(6) #5 BARS PER DETAILS 3 AND 7 THIS SHEET.
PROVIDE 90 DEGREE HOOKS BOTH ENDS
#5 TIES @ 4" OC. PROVIDE 4 LEGS EACH DIRECTION
#5 U-BARS @ 12" OC
EE
E
EMBED PLATE BELOW. SEE DETAIL XXX
FOR MORE INFORMATION
5/16"
EMBED PLATE
5/16"
CAP PLATE
PROVIDE 12"X12"X1" PLATE,
TOP OF BEAMS
NEW CONCRETE COLUMN, PER PLAN
BEAM PER PLAN, TYP
MITER BEAM CONNECTION
2' - 0" 1' - 0"
3' - 0"
2'
2'
4'
1" THICK EMBED PLATE W/ (5) 3/4" D1.1
GR B HEADED STUDS. MIN EMBED 9"
INTO NEW CONCRETE
(6) #5 BARS @ 3" OC EDGE
ANCHOR REINFORCEMENT
NEW
CONCRETE
COLUMN
1' - 0"
2' - 0" 1' - 0"
6" 6"
3" 3"
1'
" 6"
6"
3" 3"
3' - 0"
4'
2'
2'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
B
IM
/2
V
A W e s t P a lm
B e a c h
E H
R M
I n fr a s tr u c tu re U p g ra d e s D e s ig n /5
-7
.B
.S .2
.r v t
/1
/2
:1
:1
P M
B01-S101
CHILLER DUNNAGE
10360 ellison Circle
Omaha, NE 68134
402.991.5520 specializedeng.com
1221 N. Pennsylvania St.
Indianapolis, IN 46202
317.800.6388 guidondesign.com
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
WEST PALM BEACH, FL
548-22-700
B01
03/31/2023 LKB ADK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
BID ADDENDUM 1 09/01/2023
SCALE: 1/4" = 1'-0"B01-S101
1 CHILLER DUNNAGE FRAMING PLAN
SCALE: 3/4" = 1'-0"B01-S101
2 FRAMING SECTION
SCALE: 3/4" = 1'-0"B01-S101
4 ENLARGED PLAN
SCALE: 3/4" = 1'-0"B01-S101
3 EMBED PLATE PLAN
SCALE: 3/4" = 1'-0"B01-S101
5 FRAMING SECTION
SCALE: 3/4" = 1'-0"B01-S101
6 ENLARGED PLAN
SCALE: 3/4" = 1'-0"B01-S101
7 EMBED PLATE PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
B
IM
/2
V
A W e s t P a lm
B e a c h
E H
R M
I n fr a s tr u c tu re U p g ra d e s D e s ig n /5
-7
.B
.S .2
.r v t
/1
/2
:0
:5
P M
SI002
STRUCTURAL GENERAL NOTES
10360 Ellison Circle
Omaha, NE 68134
402.991.5520 specializedeng.com
1221 N. Pennsylvania St.
Indianapolis, IN 46202
317.800.6388 guidondesign.com
ELETRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
WEST PALM BEACH, FL
548-22-700
03/31/2023 LKL ADK
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF
NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING
DRAWINGS AND SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL SPECIFICATIONS FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE WITHOUT
THE APPROVAL OF THE STRUCTURAL ENGINEER.
CONTRACTOR TO COORDINATE ALL EQUIPMENT, ROOF DRAINS, CHASES, AND OTHER ITEMS CONNECTED TO THE STRUCTURE BEFORE
FABRICATION BEGINS.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETEOTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION, AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN ACCORDANCE WITH "STANDARD DEVIATION"
DETERMINATION OUTLINED IN ACI 318.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS
SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT ELECTRONIC VERSIONS OF SHOP DRAWINGS. SUBMIT SHOP DRAWINGS IN PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE
WHERE THE PROJECT IS CONSTRUCTED FOR ALL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS)
3. STEEL DECK
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL
SAMPLES, AND UPON APPROVAL IN WRITING BY CONTRACTING OFFICER.
SUBMIT ELECTRONIC VERSIONS OF PRODUCT DATA IN PDF FORMAT TO THE STRUCTURAL ENGINEER AND COR FOR REVIEW.
1. FIBER REINFORCEMENT FOR CONCRETE
2. CONCRETE REINFORCEMENT
3. DIAMOND PLATE DOWELS FOR SLABS ON GRADE
4. CONCRETE CURING COMPOUND
5. CONCRETE JOINT SEALANT
6. WATER STOPS
7. EXPANSION ANCHORS
8. ADHESIVE ANCHORS
9. NON-SHRINK GROUT
FOUNDATIONS
FOUNDATION EXCAVATIONS AND SOIL RELATED WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE GEOTECHNICAL REPORT
NUMBER 2073502 PREPARED BY TTL ASSOCIATES DATED AUGUST 15 2022.
FOUNDATIONS HAVE BEEN DESIGNED BASED ON ASSUMED ALLOWABLE NET BEARING PRESSURE OF 3,000 PSF. CONTRACTOR SHALL ENGAGE A LICENSED GEOTECHNICAL ENGINEER TO REVIEW THE SOIL CONDITIONS AT THE SITE AS NECESSARY TO CONFIRM THE ALLOWABLE CAPACITIES PRIOR TO PLACEMENT OF THE FOUNDATIONS. CONFIRMATION OF THE ACCEPTABILITY OF THE SOILS SHALL
BE REPORTED IN WRITING TO THE STRUCTURAL ENGINEER.
IF ACTUAL ALLOWABLE CAPACITIES ARE FOUND TO BE LESS THAN THE ASSUMED VALUES, THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL NOT PROCEED WITH FOUNDATION CONSTRUCTION WITHOUT REVIEW BY THE
STRUCTURAL ENGINEER.
FOUNDATIONS AND SOILS RELATED WORK SHALL BE INSPECTED BY A LICENSED GEOTECHNICAL ENGINEER. WRITTEN FIELD REPORTS
SHALL BE FORWARDED TO THE STRUCTURAL ENGINEER AS SOON AS THEY BECOME AVAILABLE.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM THOSE DESCRIBED IN THE GEOTECHNICAL REPORT, SHALL BE REPORTED TO THE STRUCTURAL ENGINEER AND GEOTECHNICAL ENGINEER BEFORE FURTHER CONSTRUCTION IS
ATTEMPTED.
EXCAVATIONS FOR SHALLOW FOUNDATIONS SHALL BE CLEANED AND HAND TAMPED TO UNIFORM SURFACE AND SHALL BE PROTECTED
AND MAINTAINED UNIFORM UNTIL CONCRETE IS PLACED.
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318) AND COMMENTARY (ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301). READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94. IN CASE OF A
DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I, UNO.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT (BY WEIGHT) OF FLY ASH TO TOTAL
CEMENTITIOUS MATERIALS IN THE MIX SHALL NOT EXCEED 25 PERCENT.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE
WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN 0.1 PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN
ACCORDANCE WITH THE LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON THE DRAWINGS SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL BE USED IN THE FOLLOWING AREAS AND SHALL
HAVE THE PROPERTIES AS SHOWN BELOW:
FOUNDATIONS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 1/2 INCHES
7. AIR CONTENT: N/A
FOUNDATION WALLS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: N/A
RETAINING WALLS AND CURBS/SIDEWALKS/SLABS EXPOSED TO DE-ICERS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 517 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.45
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: 6.0% +/- 1%
SLABS ON GRADE
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: 6% +/- 1%
8. HIGH RANGE WATER REDUCING ADMIXTURE AND FIBER REINFORCING REQUIRED
SLABS ON STEEL DECK
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: N/A
COLUMNS
1. COMPRESSIVE STRENGTH (28 DAYS): 6000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 661 LB./CU. YD. (USE TYPE II SULFATE RESISTANT CEMENT FOR LEVEL 1
COLUMNS)
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS
ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.45
6. MAXIMUM COARSE AGGREGATE SIZE: 3/4 INCH
7. AIR CONTENT: N/A
CONCRETE SLABS ON GRADE
SLABS ON GRADE SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST EDITION OF THE GUIDE FOR CONCRETE FLOOR AND
SLAB CONSTRUCTION (ACI 302.1R).
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO ASTM C309, UNLESS NOTED OTHERWISE. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE RECOATED DAILY. OTHER CURING METHODS MAY BE USED WITH APPROVAL BY THE STRUCTURAL ENGINEER.
SLABS ON GRADE SHALL BE PLACED TO ACHIEVE THE FOLLOWING MINIMUM TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
THE MINIMUM LOCAL AREA SHALL BE ANY BAY DEFINED BY COLUMN LINES.
UNLESS SHOWN OR NOTED OTHERWISE, PROVIDE CONTROL OR CONSTRUCTION JOINTS IN SLABS-ON-GRADE AT A MAXIMUM SPACING OF 36 TIMES THE SLAB THICKNESS. PROVIDE JOINTS AT ALL COLUMN LOCATIONS. LOCATE JOINTS TO ELIMINATE RE-ENTRANT CORNERS AND TO CREATE SQUARE OR RECTANGULAR SECTIONS WITH MAXIMUM LONG SIDE TO SHORT SIDE RATIO OF 1.5 TO 1.
CONTROL JOINTS IN SLABS ON GRADE SHALL NOT RECEIVE JOINT FILLER MATERIAL UNLESS NOTED OTHERWISE.
CONCRETE SLABS ON METAL DECK
UNLESS INDICATED OTHERWISE ON THE DRAWINGS, CONCRETE SLABS ON METAL DECK SHALL BE PLACED AS REQUIRED TO MAINTAIN
A CONSTANT SLAB [THICKNESS].
CONTRACTOR SHALL ALLOW FOR THE DEFLECTION OF THE FLOOR ASSEMBLY DUE TO THE WET WEIGHT OF THE CONCRETE WHEN CALCULATING CONCRETE QUANTITIES AND SHALL INCLUDE THE COST OF ALL REQUIRED SLAB-ON-DECK CONCRETE IN THE BID PRICE.
PRIOR TO PLACEMENT OF CONCRETE SLABS ON METAL DECK, THE CONTRACTOR SHALL CAREFULLY REVIEW THE ELEVATIONS OF THE STRUCTURAL STEEL FRAMING, INCLUDING CAMBERED MEMBERS, FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES (SUCH AS IMPROPER CAMBER, IMPROPER STEEL ELEVATIONS, ETC.) IMMEDIATELY AND SHALL NOT BEGIN CONCRETE PLACEMENT WITHOUT PRIOR REVIEW BY THE STRUCTURAL
ENGINEER.
ACTUAL CONCRETE SLAB THICKNESS SHALL NOT BE LESS THAN THE INDICATED NOMINAL THICKNESS AT ANY LOCATION. IF ANY CONDITION IS DISCOVERED THAT WOULD PREVENT PLACEMENT OF CONCRETE TO THE NOMINAL THICKNESS; CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL NOT PROCEED WITH CONCRETE PLACEMENT WITHOUT PRIOR REVIEW
BY THE STRUCTURAL ENGINEER.
SLABS ON METAL DECK SHALL RECEIVE A SMOOTH TROWEL FINISH, AND BE PLACED TO ACHIEVE THE FOLLOWING MINIMUM
TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO ASTM C309. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE RECOATED DAILY. OTHER
CURING METHODS MAY BE USED WITH APPROVAL BY THE STRUCTURAL ENGINEER.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000
PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING STANDARDS:
ACI 301, ACI 315, ACI 318 AND ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE THE FOLLOWING MINIMUM CONCRETE COVER
OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 INCHES
#6 BARS AND LARGER EXPOSED TO EARTH OR WEATHER: 2 INCHES
#5 BARS AND SMALLER EXPOSED TO EARTH OR WEATHER: 1-1/2 INCHES
BEAM AND COLUMN TIES, STIRRUPS AND SPIRALS: 1-1/2 INCHES
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 3/4 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR
APPROVED BY THE STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT CORNERS OF ALL WALLS AND GRADE BEAMS. LAP
SPLICE CORNER BARS WITH STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#6 BARS (ONE EACH FACE) AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM A185. FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND
LAPPED A MINIMUM OF ONE SPACE PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED AS FOLLOWS, UNLESS NOTED OTHERWISE:
SLABS ON METAL DECK: 3/4 INCH DOWN FROM TOP OF SLAB.
FIBER REINFORCEMENT
FIBER REINFORCEMENT SHALL BE 3/4" LONG, VIRGIN (NON-RECYCLED) NYLON OR POLYPROPYLENE FIBERS, INTRODUCED INTO THE CONCRETE MIX AT THE BATCH PLANT, IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. DOSAGE SHALL BE 1.5
POUNDS PER CUBIC YARD OF CONCRETE.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH DAY'S POUR AND FOR EACH 100 CUBIC YARDS. EACH SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT 28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION OF THE STRUCTURAL ENGINEER. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER CASTING
UNLESS
DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST CYLINDERS SHALL BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED. THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL
CURING BOXES ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER, READY-MIX SUPPLIER AND CONTRACTOR WITHIN 24
HOURS AFTER TESTING.
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE CARBON STEEL ANCHORS AS MANUFACTURED BY HILTI FASTENING SYSTEMS OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER AND SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
EXPANSION ANCHORS SHALL NOT BE INSTALLED IN CONCRETE UNTIL IT HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE
STRENGTH.
ADHESIVE ANCHORS
ADHESIVE ANCHORS SHALL BE HILTI "HIT HY200" FOR SOLID SUBSTRATE AND HILTI "HIT HY270" FOR HOLLOW SUBSTRATE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNLESS NOTED OTHERWISE ON PLANS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS BY INSTALLERS TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED, NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF
5,000 PSI IN 28 DAYS.
WATERSTOPS
SELF-EXPANDING STRIP WATER STOPS SHALL BE VOLCLAY WATERSTOP-RX 101 UNLESS NOTED OTHERWISE. INSTALL IN ACCORDANCE
WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
PVC WATERSTOPS
PROVIDE FACTORY MADE WATERSTOP FABRICATIONS FOR ALL CHANGES OF DIRECTION, INTERSECTIONS, AND TRANSITIONS LEAVING
ONLY STRAIGHT BUTT JOINT SPLICES FOR THE FIELD.
PROVIDE HOG RINGS OR GROMMETS SPACED AT 12 INCHES ON CENTER ALONG LENGTH OF WATERSTOP.
PROVIDE TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRONS FOR FIELD BUTT SPLICES.
FIELD BUTT SPLICES SHALL BE HEAT FUSED WELDED USING A TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRON AT APPROXIMATELY 380 DEGREES F. FOLLOW APPROVED MANUFACTURER RECOMMENDATIONS.
LAPPING OF WATERSTOP, USE OF ADHESIVES, OR SOLVENTS SHALL NOT BE ALLOWED.
CENTER WATERSTOP IN JOINT AND SECURE WATERSTOP IN CORRECT POSITION USING HOG RINGS OR GROMMETS SPACED AT 12 INCHES ON CENTER ALONG THE LENGTH OF THE WATERSTOP AND WIRE TIE TO ADJACENT REINFORCING STEEL.
MASTIC COATING
MASTIC COATING FOR PROTECTION OF INDICATED ITEMS SHALL BE BITUMASTIC 50 COAL TAR MASTIC BY CARBOLINE OR EQUIVALENT SUBSTITUTE APPROVED BY THESTRUCTURAL ENGINEER. INSTALL AT LOCATIONS INDICATED ON DRAWINGS.
UNLESS NOTED OTHERWISE, APPLY MASTIC TO A COATING THICKNESS OF 18 MILS. PROVIDE FULL COVERAGE OVER ITEMS INDICATED
TO RECEIVE COATING.
STRUCTURAL STEEL
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, 50 KSI.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE SHAPES SHALL CONFORM TO ASTM A36, UNLESS NOTED
OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED OTHERWISE.
STEEL STUDS SHALL CONFORM TO ASTM A108.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED CONNECTIONS FOR STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4" DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE.
BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN BRACE ELEMENTS
ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY'S STRUCTURAL WELDING
CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.
UNLESS OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD E70XX
ELECTRODES.
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A RUST-INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS. CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM SPECIFIED BY THE
ARCHITECT. COORDINATE FINISH PAINTING REQUIREMENTS WITH THE ARCHITECT.
STRUCTURAL STEEL THAT IS NOT EXPOSED IN THE FINISHED CONSTRUCTION AND DOES NOT RECEIVE FINISH PAINT SHALL NOT BE
SHOP-PRIMED, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE. FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT. FOR GALVANIZED STEEL, USE
A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION AND MANUAL OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE ON THE DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM OF A 10 KIP SHEAR REACTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
PROVIDE C8X13.7 FRAMED OPENINGS FOR ALL ROOF PENETRATIONS 12 INCHES OR LARGER ALONG ANY SIDE, UNLESS LARGER FRAMING IS INDICATED. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR PENETRATIONS. COORDINATE FRAMED OPENING SIZES
AND LOCATIONS WITH THE MECHANICAL AND PLUMBING CONTRACTORS.
GALVANIZE ALL EXPOSED STEEL.
COMPOSITE STEEL BEAMS
COMPOSITE BEAM SHEAR CONNECTORS SHALL BE NELSON STUD TYPE S3L AS MANUFACTURED BY THE NELSON STUD WELDING
COMPANY, OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER.
STUDS SHALL BE MANUFACTURED OF COLD-DRAWN STEEL CONFORMING TO ASTM A108. STUDS SHALL BE 3/4" DIAMETER X 3" INCHES LONG @ 24" OC, UNLESS NOTED OTHERWISE. STUD DESIGN HAS BEEN BASED ON AN ULTIMATE SHEAR CAPACITY OF 17.7 KIPS PER
STUD.
COMPOSITE STEEL BEAMS HAVE BEEN DESIGNED TO ALLOW INSTALLATION OF THE SLAB CONCRETE IN AN UNSHORED CONDITION
UNLESS NOTED OTHERWISE.
STEEL ROOF DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S SPECIFICATIONS AND
CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL ROOF DECK ACCESSORIES, INCLUDING CLOSURES, SUPPLEMENTARY FRAMING, AND SUMP
PANS, WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN ROOF DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS. PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
ROOF DECK SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION.
PROVIDE STEEL ROOF DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
Revisions: Date:
BID ADDENDUM 1 09/01/2023
NEW EMERGENCY
GENERATOR #1
1000KW
1250KVA @
0.8PF
TO FPL SWITCHING
VAULT FOR INCOMING
13.2KV 3P SERVICE
15KV CLASS
PRIMARY
SWITCHGEAR
L.A.
51N
VS
KW
AS A A
V V VS
KW
AS
51N
100% RATED
BREAKER
L.A. 1600
3P
GF
3P
GF
DFT 1600
3P
GF
1600 GF
5000A, 277/480V, 3P, 4W
C4-5000
3P
2000A
100 % RATED
GF
GF
NEW PARALLELING
SWITCHGEAR
277/480V
5000A
C4-2000 C4-5000
EXISTING EMERGENCY SWITCHBOARD ESWBD-1 5000A, 277/480V, 3P, 4W
51N
SPACE 52
SPARE
52 50 51 52
51N
N.O.
1200A
51N
51N
51 52
SPARE
PQS400 - 277/480
C4-600
C4-1200
ATS-11
600A 3P
N E
C4-300 C4-600 C4-300
ATS-1
400A 4P
N E
ATS-2
800A 4P
N E
C4-800
ATS-3
600A 4P
N E N E N E N E N E N E N E N E N E
SPARE
FIRE PUMP
480V, 3P
O2
CDP2A
ATS-4
1200A 3P
ATS-5
300A 4P 225A
SPARE
E SPARE 3 NORMAL
SOURCE
NORMAL
SOURCE
NORMAL
SOURCE
ATS-13
150A 4P N
400A
1200A 300A 600A 125A 800A 400A
SPACE SPACE
VS V
KW
SUBSTATION "F"
1500KVA AS A
GF
2000A
EXISTING
TRANSFER
DEVICE
SPARE
SUBSTATION "G"
2000KVA
AS
VS V
KW
A
GF
2500A
EXISTING
TRANSFER
DEVICE
300A 1000A 700A 600A 600A 800A 125A
NORMAL
SOURCE
NORMAL
SOURCE
NORMAL
SOURCE
SPARE NURSING
HOME
NURSING
HOME
NURSING
HOME
400A
SPARE
225A
E
ATS-14
400A 4P N E
ATS-18
150A 4P N E
400A
CHILLERS
100A
G6 G5 G4 G3 QMCC EXISTING
LOAD
EXISTING
LOAD
EXISTING
LOAD
C4-400
ATS-6
800A 3P
C4-400
ATS-7
600A 3P
C4-350
ATS-8
600A 4P
C4-500
ATS-9
600A 4P
C4-600
ATS-10
800A 4P
C4-800 C4-600
ATS-15
600A 4P
ATS-7A
600A 4P
C4-400
ATS-6A
600A 4P
C4-400 C4-250 C4-60
EXTERIOR MOUNTED
DOCKING STATION
SPACE
600A 1200A 300A 600A 300A 800A 400A 400A 350A 500A 600A 800A 600A 400A 400A 250A 60A
PQS400 - 277/480
480V, 3P, 4W
(TYPICAL)
GEN #1
G
GEN #2
G
GEN #3
G
GEN #4
G
C4-1600 C4-1600 C4-1600 C4-1600
SUBSTATION "A"
2000KVA
VS V
KW
AS
GF
2500A
A
GF
1200A
AS
VS V
KW
A
GF
2500A
AS
SUBSTATION "C"
2000KVA
VS V
KW
A
GF
2500A
AS
SUBSTATION "D"
2000KVA VS V
KW
A
GF
2000A
AS
SUBSTATION "E"
2000KVA
VS V
KW
A
SUBSTATION "B"
750KVA
300A 1200A 800A 800A 125A 600A 700A 125A
SPACE SPACE
500A 800A 1200A 600A 125A
SPACE SPACE
1200A 1200A 125A 1000A
SPACE SPACE
1200A 800A 125A 600A
SPACE SPACE
NDPGK EAST BUS
DUCT
RISER
(5,7&9 FL.)
EAST BUS
DUCT
RISER
(6&8 FL.)
SPARE
WEST BUS
DUCT
RISER
(B,2&4 FL.)
ATS-12
600A 4P
E N XDPIE SPARE
NDPGI EAST BUS
DUCT
RISER
(B,2&4 FL.)
EAST BUS
DUCT
RISER
(1&3 FL.)
WEST BUS
DUCT
RISER
(1&3 FL.)
SPARE
CHILLER
#1
CHILLER
#2
SPARE NMCCA CHILLER
#3
NMCCB SPARE HDPGH
XDPIQ
NE
N
SPD
S P
D
400A
LSIG
01-UPS-BB-312-DP-B
01-UPS-ATS-A
400A
LSIG
400A
01-UPS-ATS-A
4#600, 1#1/0 GROUND
IN 3-1/2 INCH C.
4#600, 1#1/0 GROUND
IN 3-1/2 INCH C.
400A
LSIG
01-NHP-M-4C-326
4#600, 1#1/0 GROUND
IN 3-1/2 INCH C.
4#600, 1#1/0 GROUND
IN 3-1/2 INCH C.
NOTE: THIS ONE-LINE IS BASED UPON A PLANNED EMERGENCY
POWER UPGRADE PROJECT AND DOES NOT REFLECT CURRENTLY
INSTALLED CONDITIONS. THE DESIGN REFERENCES HAVE BEEN
CHANGED TO REFLECT CONNECTION TO EXISTING EQUIPMENT. 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com
B
IM
/2
V
A W e s t P a lm
B e a c h
E H
R M
I n fr a s tr u c tu re U p g ra d e s D e s ig n /5
-7
.B
.E
R
.r v t
/1
/2
:1
:5
P
M
B01-E500
PARTIAL ELECTRICAL ONE-LINE
DIAGRAM
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
WEST PALM BEACH, FL
548-22-700
03/31/23 MG BM
B01
NTS1
PARTIAL ELECTRICAL ONE-LINE DIAGRAM
1. PROVIDE NEW CIRCUIT BREAKERS IN EXISTING SPACE
WITHIN SUBSTATION A. COORDINATE RELOCATION OF
EXISTING COMPONENTS AND INTERRUPTION IN POWER TO
SUBSTATION A LOADS TO MINIMIZE OUTAGE AND COMPLY
WITH ALL VA SAFETY AND OUTAGE REQUIREMENTS.
2. PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE
WITHIN SUBSTATION G. COORDINATE RELOCATION OF
EXISTING COMPONENTS AND INTERRUPTION IN POWER TO
SUBSTATION A LOADS TO MINIMIZE OUTAGE AND COMPLY
WITH ALL VA SAFETY AND OUTAGE REQUIREMENTS.
3. PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE
WITHIN EMERGENCY SWITCHBOARD. COORDINATE
INTERRUPTION IN AVAILABILITY OF EMERGENCY POWER TO
MINIMIZE OUTAGE AND COMPLY WITH ALL VA SAFETY AND
OUTAGE REQUIREMENTS.
4. REMOVE EXISTING 125A SPARE CIRCUIT BREAKER WITHIN
SUBSTATION A TO PROVIDE SPACE FOR NEW CIRCUIT
BREAKER SERVING NEW CHILLER AND PUMPS
PANELBOARD. COORDINATE RELOCATION OF EXISTING
COMPONENTS AND INTERRUPTION IN POWER TO
SUBSTATION A LOADS TO MINIMIZE OUTAGE AND COMPLY
WITH ALL VA SAFETY AND OUTAGE REQUIREMENTS.
KEYED NOTES:#
Revisions: Date:
09/01/2023
BASEMENT LEVEL
1ST FLOOR
2ND FLOOR
30A 100A 60A 150A I
400A
LSI
SPD
60A 60A 60A 150A I
150A I
150A I
01-USP-PNLBD-
2A-TR-HVAC
4#1, 1#6 GRD, 1-1/2" C.
80KW UPS CABINET
WITH FOUR
BREAKER BYPASS
CABINET
UPS ACCESSORY CABINET
WITH K-13 OUTPUT
TRANSFORMER AND
OUTPUT CIRCUIT BREAKER
INTEGRATED BATTERY
CABINET, DC CIRCUIT
BREAKER, AND
MONITORING SYSTEM
01-UPS-BA-250A-PNLBD-A
400A MCB
208Y/120V
3PH, 4W
30A 100A I
100A I
100A I
100A I
100A I
100A I
100A I
100A I
3#2/0, 1#6 GRD, 1-1/2" C. 3#3/0, 1#6 GRD, 2" C.
400A I
3#500, 2#500 NEUTRAL,
1#3 GRD, 3" C.
2#1/0, 1#4 GRD, 1-1/2" C.
SPD
REMOTE
EPO
UPS ACCESSORY CABINET
WITH K-13 OUTPUT
TRANSFORMER AND
OUTPUT CIRCUIT BREAKER
INTEGRATED BATTERY
CABINET, DC CIRCUIT
BREAKER, AND MONITORING
SYSTEM
01-UPS-1B-312A-PNLBD-A
400A MCB
208Y/120V
3PH, 4W
30A 100A I
100A I
100A I
100A I
100A I
100A I
100A I
100A I
3#2/0, 1#6 GRD, 1-1/2" C.
400A I
SPD
REMOTE
EPO
3#3/0, 1#6 GRD, 2" C.
3#500, 2#500 NEUTRAL,
1#3 GRD, 3" C.
2#1/0, 1#4 GRD, 1-1/2" C.
3RD FLOOR
4TH FLOOR
80KW UPS CABINET
WITH FOUR
BREAKER BYPASS
CABINET
UPS ACCESSORY CABINET
WITH K-13 OUTPUT
TRANSFORMER AND
OUTPUT CIRCUIT BREAKER
INTEGRATED BATTERY
CABINET, DC CIRCUIT
BREAKER, AND MONITORING
SYSTEM
01-UPS-3B-304B-PNLBD-A
250A MCB
208Y/120V
3PH, 4W
30A 100A I
100A I
100A I
100A I
100A I
100A I
100A I
100A I
250A I
SPD
REMOTE
EPO
3#6, 1#10 GRD, 3/4" C.
3#1/0, 2#1/0 NEUTRAL,
1#6 GRD, 2" C.
2#2/0, 1#4 GRD, 1-1/2" C.
40KW UPS CABINET
WITH FOUR
BREAKER BYPASS
CABINET
01-ULP-
BA-216A
01-ULP-
BB-221A
01-ULP-
BC-216A
01-ULP-
BC-250A
01-ULP-
1A-148A
01-ULP-
1B-238A
01-ULP-
1C-140A
01-ULP-
2A-281A
01-ULP-
2B-205A
01-ULP-
2C-112A
01-ULP-
3A-320A
01-ULP-
3B-139AA
01-ULP-
4A-322A
01-ULP-
4B-252A
01-ULP-
4C-234A
SEE DRAWING B01-E502
FOR CONTINUATION
5TH FLOOR
01-UPS-BB-312B-DP-A
400A
480Y/277V
3PH, 4W
3#3, 1#3/0 NEUTRAL, 1#8 GROUND, 1-1/2" C.
3#3, 1#3/0 NEUTRAL, 1#8 GROUND, 1-1/2" C.
01-UPS-ATS-A
TO SUBSTATION G
TO EMERGENCY SWITCHGEAR
3#3, 1#3/0 NEUTRAL, 1#8 GROUND, 1-1/2" C.
PROVIDE ONE 1 INCH CONDUIT WITH ENGINE-
GENERATOR START CIRCUITS FROM ATS TO THE
EMERGENCY SYSTEM GENERATOR PARALLELING
SWITCHGEAR IN ELECTRICAL ROOM. PROVIDE
CONNECTION AND PROGRAMMING AS REQUIRED TO
SIGNAL ENGINE-GENERATOR EMERGENCY
OPERATION UPON LOSS OF NORMAL POWER TO ATS.
100A I
3#4, 1#8 GRD, 1" C.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com
B
IM
/2
V
A W e s t P a lm
B e a c h
E H
R M
I n fr a s tr u c tu re U p g ra d e s D e s ig n /5
-7
.B
.E
R
.r v t
/1
/2
:1
:5
P
M
B01-E501
PARTIAL ELECTRICAL ONE-LINE
DIAGRAM A-SIDE
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
WEST PALM BEACH, FL
548-22-700
03/31/23 MG BM
B01
NTS1
PARTIAL ELECTRICAL ONE-LINE DIAGRAM
Revisions: Date:
5TH FLOOR
6TH FLOOR
7TH FLOOR
UPS ACCESSORY CABINET
WITH K-13 OUTPUT
TRANSFORMER AND
OUTPUT CIRCUIT BREAKER
INTEGRATED BATTERY
CABINET, DC CIRCUIT
BREAKER, AND
MONITORING SYSTEM
01-UPS-7B-304B-PNLBD-A
250A MCB
208Y/120V
3PH, 4W
30A 100A I
100A I
100A I
100A I
100A I
100A I
100A I
100A I
250A I
SPD
REMOTE
EPO
3#6, 1#10 GRD, 3/4" C.
3#1/0, 2#1/0 NEUTRAL,
1#6 GRD, 2" C.
2#2/0, 1#4 GRD, 1-1/2" C.
40KW UPS CABINET
WITH FOUR
BREAKER BYPASS
CABINET
60AS/60AF BUSWAY
FUSIBLE SWITCHES
01-USP-PNLBD-
7A-TR-HVAC
100AS/100AF BUSWAY
FUSIBLE SWITCHES
01-ULP-
5A-235A
01-ULP-
5B-232A
01-ULP-
6A-233A
01-ULP-
6B-232A
01-ULP-
7A-233A
01-ULP-
7B-232A
8TH FLOOR
9TH FLOOR
01-ULP-
8A-222A
01-ULP-
8B-245A
01-ULP-
9A-225A
01-ULP-
9B-227A
SEE DRAWING B01-E501
FOR CONTINUATION
3#3, 1#3/0 NEUTRAL, 1#8 GROUND, 1-1/2" C.
PROVIDE BUSWAY SWITCH IN EXISTING
AVAILABLE BUSWAY IN ELECTRICAL
ROOM 7B-302B. EXISTING BUSWAY IS
WESTINGHOUSE POW-R-WAY.
3#3, 1#3/0 NEUTRAL, 1#8 GRD, 1-1/2" C.
3#6, 1#8 GRD, 1" C.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com
B
IM
/2
V
A W e s t P a lm
B e a c h
E H
R M
I n fr a s tr u c tu re U p g ra d e s D e s ig n /5
-7
.B
.E
R
.r v t
/1
/2
:1
:5
P
M
B01-E502
PARTIAL ELECTRICAL ONE-LINE
DIAGRAM A-SIDE
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
WEST PALM BEACH, FL
548-22-700
03/31/23 MG BM
B01
NTS1
PARTIAL ELECTRICAL ONE-LINE DIAGRAM
BASEMENT LEVEL
1ST FLOOR
2ND FLOOR
30A 60A 150A I
400A
LSI
SPD
60A 60A 60A 150A I
150A I
150A I
80KW UPS CABINET
WITH FOUR
BREAKER BYPASS
CABINET
UPS ACCESSORY CABINET
WITH K-13 OUTPUT
TRANSFORMER AND
OUTPUT CIRCUIT BREAKER
INTEGRATED BATTERY
CABINET, DC CIRCUIT
BREAKER, AND
MONITORING SYSTEM
01-UPS-2B-304C-PNLBD-B
400A MCB
208Y/120V
3PH, 4W
30A 100A I
100A I
100A I
100A I
100A I
100A I
100A I
100A I
3#2/0, 1#6 GRD, 1-1/2" C. 3#3/0, 1#6 GRD, 2" C.
400A I
3#500, 2#500 NEUTRAL
1#3 GRD, 3" C.
2#1/0, 1#4 GRD, 1-1/2" C.
SPD
REMOTE
EPO
UPS ACCESSORY CABINET
WITH K-13 OUTPUT
TRANSFORMER AND
OUTPUT CIRCUIT BREAKER
INTEGRATED BATTERY
CABINET, DC CIRCUIT
BREAKER, AND MONITORING
SYSTEM
01-UPS-1C-136-PNLBD-B
400A MCB
208Y/120V
3PH, 4W
30A 100A I
100A I
100A I
100A I
100A I
100A I
100A I
100A I
3#2/0, 1#6 GRD, 1-1/2" C.
400A I
SPD
REMOTE
EPO
3#3/0, 1#6 GRD, 2" C.
3#500, 2#500 NEUTRAL,
1#3 GRD, 3" C.
2#1/0, 1#4 GRD, 1-1/2" C.
3RD FLOOR
4TH FLOOR
80KW UPS CABINET
WITH FOUR
BREAKER BYPASS
CABINET
5TH FLOOR
UPS ACCESSORY CABINET
WITH K-13 OUTPUT
TRANSFORMER AND
OUTPUT CIRCUIT BREAKER
INTEGRATED BATTERY
CABINET, DC CIRCUIT
BREAKER, AND MONITORING
SYSTEM
01-UPS-4B-304C-PNLBD-B
250A MCB
208Y/120V
3PH, 4W
30A 100A I
100A I
100A I
100A I
100A I
100A I
100A I
100A I
250A I
SPD
REMOTE
EPO
3#6, 1#10 GRD, 3/4" C.
3#1/0, 2#1/0 NEUTRAL
1#6 GRD, 2" C.
2#2/0, 1#4 GRD, 1-1/2" C.
40KW UPS CABINET
WITH FOUR
BREAKER BYPASS
CABINET
01-ULP-
BA-216B
01-ULP-
BB-221B
01-ULP-
BC-216B
01-ULP-
BC-250B
01-ULP-
1A-148B
01-ULP-
1B-238B
01-ULP-
1C-140B
01-ULP-
2A-281B
01-ULP-
2B-205B
01-ULP-
2C-112B
01-ULP-
3A-320B
01-ULP-
3B-139AB
01-ULP-
4A-322B
01-ULP-
4C-234B
01-UPS-BB-312B-DP-B
400A
480Y/277V
3PH, 4W
SEE DRAWING B01-E504
FOR CONTINUATION
SEE DRAWING B01-E504
FOR CONTINUATION
01-ULP-
4B-252B
TO SUBSTATION A
3#3, 1#3/0 NEUTRAL, 1#8 GROUND, 1-1/2" C.
3#3, 1#3/0 NEUTRAL, 1#8 GROUND, 1-1/2" C.
3#3, 1#3/0 NEUTRAL, 1#8 GROUND, 1-1/2" C.
3#4, 1#8 GRD, 1" C.
100A I
60A 60A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com
B
IM
/2
V
A W e s t P a lm
B e a c h
E H
R M
I n fr a s tr u c tu re U p g ra d e s D e s ig n /5
-7
.B
.E
R
.r v t
/1
/2
:1
:5
P
M
B01-E503
PARTIAL ELECTRICAL ONE-LINE
DIAGRAM B-SIDE
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
WEST PALM BEACH, FL
548-22-700
03/31/23 MG BM
B01
NTS1
PARTIAL ELECTRICAL ONE-LINE DIAGRAM
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com
B
IM
/2
V
A W e s t P a lm
B e a c h
E H
R M
I n fr a s tr u c tu re U p g ra d e s D e s ig n /5
-7
.B
.E
R
.r v t
/1
/2
:1
:5
P
M
B01-E600
ELECTRICAL LIGHTING
SCHEDULES
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
WEST PALM BEACH, FL
548-22-700
03/31/23 MG BM
B01
17 LEDS SHALL HAVE A MINIMUM COLOR RENDERING INDEX (CRI) OF 90 AND SHALL HAVE COLOR TEMPERATURE OF 4000K, U.O.N.
16. VERIFY COMPATIBILITY OF ALL DIMMING BALLASTS WITH SPECIFIED DIMMING CONTROLS PRIOR TO ORDERING AND PROVIDE APPROPRIATE COMPONENTS TO CREATE A COMPLETE AND FULLY FUNCTIONAL INSTALLATION.
15. WHEN VARYING FROM BASIS-OF-DESIGN LUMINAIRE, PROVIDE A LUMINAIRE UTILIZING ±10% OF THE LED LUMENS INDICATED IN LUMINAIRE SCHEDULE.
14. COMPLETE CATALOG NUMBER MAY NOT BE LISTED. ORDER LUMINAIRE BASED ON DESCRIPTION, PARTIAL CATALOG NUMBER AND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS-OF-DESIGN.
13. REFER TO SPECIFICATION SECTION 265100 LIGHTING FOR ADDITIONAL INFORMATION CONCERNING LUMINAIRES, FINISHES, ETC.
12. WHEN LUMINAIRES ARE INSTALLED IN CONTINUOUS ROWS TWO (2) OR MORE, LUMINAIRES SHALL BE APPROVED FOR USE AS WIREWAY.
11. ALL LUMINAIRES SHALL OPERATE AT 120 OR 277 VOLTS OR OTHER VOLTAGE AS REQUIRED BY THE CIRCUITS AND/OR PANELS TO WHICH THEY ARE CONNECTED.
10. FOR LUMINAIRES TYPES WITH PARABOLIC LOUVERS: FOR LUMINAIRES WITH BALLAST COMPARTMENTS PROTRUDING INTO LUMINAIRE, MOUNT COMPARTMENT OVER LOUVERS.
9. IN ALL MECHANICAL ELECTRICAL EQUIPMENT AREAS, CONTRACTOR TO COORDINATE LUMINAIRE LOCATIONS SUCH THAT LIGHT LUMINAIRES RUN PARALLEL TO THE FACE OF THE EQUIPMENT AND OVER AISLES BETWEEN EQUIPMENT.
INSTALL AT EXACT LOCATIONS AND AT EXACT HEIGHT TO ILLUMINATE ALL GAGES, PANELS, CONTROLS, VALVES, ETC. CHAIN HANGING, STEM HANGING, UNISTRUT HANGING, ETC. ARE ACCEPTABLE METHODS.
6. ALL LUMINAIRES SHALL HAVE A U.L. LABEL.
3. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS OF LUMINAIRES AND CEILING TYPES.
2. CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE, CLIPS, ANGLES, FRAMES, ETC. AS REQUIRED TO MOUNT THE LUMINAIRES IN OR ON THE SURFACES THEY ARE TO BE INSTALLED.
1. ALL LUMINAIRES SHOWN ON THIS SCHEDULE MAY NOT BE USED ON THE VARIOUS PLANS. ALSO, THE USE OF ONLY CERTAIN NUMERICAL SUBSCRIPTS FOR LUMINAIRE TYPES (e.g. H2, H3, A2, A3, etc.) ON THIS PROJECT DOES NOT
NECESSARILY MEAN THAT ON H1 OR A1 IS USED OR MISSING.
LUMINAIRE SCHEDULE GENERAL NOTES:
LUMINAIRE SCHEDULE
PLAN MARK DESCRIPTION MANUFACTURER REMARKS LAMP TYPE LED LUMENS WATTAGE VOLTAGE
A 2'X4' DIRECT/INDIRECT, 90CRI, 4000K LITHONIA 2BLT4 SERIES
2BLT4-60L-ADP-EZ1
LED 6000 48 W
AE SAME AS TYPE A WITH 14W, 90 MINUTE EMERGENCY BATTERY BACKUP LITHONIA 2BLT4 SERIES
2BLT4-60L-ADP-EZ1-EL14L
LED 6000 48 W UNIVERSAL
B 4' STRIP WITH WIREGUARD, 90CRI, 4000K LITHONIA CLX SERIES
CLX-L48-SEF-WDL-MVOLT-GZ10-40K-90CRI-WGCLX48
LED 7000 49 W UNIVERSAL
BE SAME AS TYPE B WITH 10W, 90 MINUTE EMERGENCY BATTERY BACKUP LITHONIA CLX SERIES
CLX-L48-SEF-WDL-MVOLT-GZ10-40K-90CRI-PS1050-WGCLX48
LED 7000 49 W UNIVERSAL
D 2' WALLBRACKET, 90 CRI, 4000K LITHONIA FMVTSL SERIES LED 1400 18 W UNIVERSAL
FE EXTERIOR WALL SCONCE, 70 CRI, 4000K LITHONIA WPX LED SERIES LED 6000 47 W
G1 25' CONCRETE POLE, PAINTED BLACK WITH TWIN HEAD AREA LIGHT AT 180
DEGREES, TYPE III DISTRIBUTION, 70 CRI, 4000K
COOPER GALN GALLEON II SERIES LED 7000 PER
HEAD
250 W 120 V
G2 25' CONCRETE POLE, PAINTED BLACK WITH TWIN HEAD AREA LIGHT AT 180
DEGREES, TYPE IV FORWARD THROW DISTRIBUTION
COOPER GALN GALLEON II SERIES LED 7000 PER
HEAD
250 W 120 V
G3 25' CONCRETE POLE, PAINTED BLACK WITH TWIN HEAD AREA LIGHT AT 90
DEGREES, TYPE III DISTRIBUTION
COOPER GALN GALLEON II SERIES LED 7000 PER
HEAD
250 W 120 V
X UNIVERSAL MOUNT EXIT SIGN WITH 90 MINUTE BATTERY BACKUP AND SELF
DIAGNOSTICS
LITHONIA LQM SERIES LED -- 1 W UNIVERSAL
Y TWIN HEAD EMERGENCY LIGHT WITH 90 MINUTE BATTERY BACKUP AND SELF
DIAGNOSTICS
LITHONIA ELM6L SERIES LED 1100 6 W 120 V
LIGHTING CONTROL SEQUENCE
S - "INDIVIDUAL ZONE WALL CONTROLLER". REFER TO FLOOR PLAN FOR QUANTITY OF ZONES SHOWN IN THE AREA. EACH ZONE SHALL HAVE A ITS OWN INDEPENDENT CONTROLLER WITHIN THE WALL CONTROLLER.
D - "INDIVIDUAL DIMMING ZONE WALL CONTROLLER". EACH ZONE SHALL ITS OWN INDEPENDENT CONTROLLER CAPABLE OF ON, OFF AND DIMMING WITIN THE WALL CONTROLLER. REFER TO FLOOR PLAN FOR QUANTITY OF ZONES SHOWN IN THE AREA.
P -"PRESET SCENE CONTROLLER". NUMBER INDICATES QUATITY OF PRESET SCENE CONTROLS. EACH PRESET SCENE SHALL EACH BE CAPABLE OF TURNING SCENE ON, OFF AND DIM.
DL Ft. Cd. - "DAY LIGHT PHOTO SENSOR". MUST AUTOMATICALLY DIM INDICATED LUMNINAIRES SHOWN ON FLOOR PLANS WITH DAY LIGHT ZONES. MAINTAIN MAXIMUM FOOT CANDLE RATING INDICATED AS MEASURED FROM +30" AFF.
MAN - MANUAL CONTROL. OCC - OCCUPANCY ON AND / OR VACANCY OFF. TC - TIME CLOCK. ETD - EMERGENCY TRANSFER DEVICE.
SEQUENCE ID AREA DESCRIPTION
WALL AUTOMATIC CONTROLS
DL
Ft. Cd. ETD REMARKS
CONTROLLER ON (X=100%) OFF (X=0%)
S D P MAN OCC TC MAN OCC TC
LC01 TELECOM/SERVER - X - - 100% - X - - - -
LC02 ELECTRICAL/MECHANICAL/FIRE X - - X - - X - - - -
LC03 CORRIDORS X - - - 100% - - 50% - - -
LC04 RESTROOMS X - - - X - - X - - -
LC05 STORAGE/JANITOR - X - X X - - X - - -
LC06 OFFICES - X - X 50% - - X - - -
LC07 EXTERIOR LIGHTING - PHOTOCELL/ TIME SWITCH - - - - - X - - X - - ON WITH PHOTOCELL
UNIVERSAL
UNIVERSAL
UNIVERSAL
LIGHTING CONTROL NOTES:
1. LIGHT FIXTURE SHOP DRAWING AND LIGHTING CONTROL SHOP DRAWING SUBMITTAL SHALL BE SUBMITTED AT THE SAME TIME. APPROVAL WILL NOT BE
GRANTED UNTIL BOTH ARE REVIEWED.
2. THE LIGHTING CONTROL SYSTEM SCHEDULE SHALL BE CONSIDERED A PERFORMANCE CRITERIA. PROVIDE ALL CONTROL DEVICES, WIRING, RACEWAY, PROGRAMMING, AND LABOR AS REQUIRED TO OBTAIN THE SEQUENCES IDENTIFIED FOR EACH SPACE.
3. PROVIDE CONTROL DRAWINGS, SEQUENCE DESCRIPTIONS, PUSHBUTTON CONFIGURATIONS (WITH LIGHITNG LOADS IDENTIFIED) AND WIRING DIAGRAMS INDICATING THE PROPOSED LIGHTING CONTROLS WITHIN THE SHOP DRAWING SUBMITTAL FOR APPROVAL.
4. COORDINATE ALL BUTTON ENGRAVING WITH OWNER PRIOR TO ORDERING.
5. MOUNT AREA CONTROLLERS AND POWER PACKS ABOVE CEILING, NEAR WALL CONTROLLERS IN THE INTERIOR SIDE OF THE SPACE SERVED. ROOM
CONTROLLERS SERVING CORRIDORS MAY BE LOCATED IN ELECTRICAL ROOMS.
6. PRIOR TO CONSTRUCTION CLOSEOUT, DEMONSTRATE LIGHTING CONTROLS TO OWNER FOR FINAL APPROVAL. MODIFY PROGRAMMING AND ILLUMINATION
AS REQUIRED TO MEET OWNERS FINAL REQUIREMENTS.
7. EACH SWITCH LEG SHOWN ON LIGHTING DRAWINGS IS A ZONE, PROVIDE A TOGGLE/DIMMER SWITCH FOR EACH SWITCH LEG/ZONE SHOWN ON LIGHTING
FLOOR PLANS.
LUMINAIRE SCHEDULE GENERAL NOTES:
1. LUMINAIRE SCHEDULE APPLIES TO ALL BUILDINGS.
2. UNLESS OTHERWISE STATED IN REMARKS. ALL FIXTURES ARE LED.
3. LIGHT FIXTURE SHOP DRAWING AND LIGHTING CONTROL SHOP DRAWING SUBMITTAL SHALL BE SUBMITTED AT THE SAME TIME. APPROVAL WILL NOT BE GRANTED UNTIL BOTH ARE REVIEWED.
4. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS OF LUMINAIRES AND CEILING TYPES.
5. ALL RECESSED DOWNLIGHTS SHALL HAVE SELF-FLANGED REFLECTORS U.O.N. AND SHALL BE INSTALLED SO THAT THE BOTTOM OF THE THROAT IS EVEN WITH THE FINISHED CEILING PLANE. THE OVERLAPPING FLANGE MUST THEN FIT FLUSH TO THE CEILING PLANE/THROAT. NO LIGHT LEAK MUST BE VISIBLE. ALL MISCELLANEOUS HARDWARE ABOVE THE CEILING PLANE TO ACCOMPLISH THE ABOVE SHALL BE INCLUDED IN THE BASE BID.
6. ALL LUMINAIRES SHALL HAVE A U.L. LABEL.
7. IN ALL MECHANICAL ELECTRICAL EQUIPMENT AREAS, CONTRACTOR TO COORDINATE LUMINAIRE LOCATIONS SUCH THAT LIGHT LUMINAIRES RUN PARALLEL TO THE FACE OF THE EQUIPMENT AND OVER AISLES BETWEEN EQUIPMENT. INSTALL AT EXACT LOCATIONS AND AT EXACT HEIGHT TO ILLUMINATE ALL GAGES, PANELS, CONTROLS, VALVES, ETC. CHAIN HANGING, STEM HANGING, UNISTRUT HANGING, ETC. ARE ACCEPTABLE METHODS.
8. WHEN LUMINAIRES ARE INSTALLED IN CONTINUOUS ROWS OF TWO (2) OR MORE, LUMINAIRES SHALL BE APPROVED FOR USE AS WIREWAY.
9. COMPLETE CATALOG NUMBER IN THIS LIGHT FIXTURE SCHEDULE ARE NOT BE LISTED. ORDER LUMINAIRE BASED ON DESCRIPTION, PARTIAL CATALOG NUMBER AND SPECIFICATIONS. THE MANUFACTURER LISTED IS THE
BASIS-OF-DESIGN.
10. VERIFY COMPATIBILITY OF ALL DIMMING DRIVERS WITH SPECIFIED DIMMING CONTROLS PRIOR TO ORDERING AND PROVIDE APPROPRIATE COMPONENTS TO CREATE A COMPLETE AND FULLY FUNCTIONAL INSTALLATION.
11. ALL LUMINAIRES SHOWN ON THIS SCHEDULE MAY NOT BE USED ON THE VARIOUS PLANS. ALSO, THE USE OF ONLY CERTAIN NUMERICAL SUBSCRIPTS FOR LUMINAIRE TYPES (e.g. H2, H3, A2, A3, etc.) ON THIS PROJECT DOES
NOT NECESSARILY MEAN THAT ON H1 OR A1 IS USED OR MISSING.
12. CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE, CLIPS, ANGLES, FRAMES, ETC. AS REQUIRED TO MOUNT THE LUMINAIRES IN OR ON THE SURFACES THEY ARE TO BE INSTALLED.
13. WHEN VARYING FROM BASIS-OF-DESIGN LUMINAIRE, PROVIDE A LUMINAIRE UTILIZING ±10% OF THE LED LUMENS INDICATED IN LUMINAIRE SCHEDULE.
14. REFER TO SPECIFICATION SECTION 265100 LIGHTING FOR ADDITIONAL INFORMATION CONCERNING LUMINAIRES, FINISHES, DRIVERS, ETC.
15. ALL LUMINAIRES SHALL OPERATE AT 120 OR 277 VOLTS OR OTHER VOLTAGE AS REQUIRED BY THE CIRCUITS AND/OR PANELS TO WHICH THEY ARE CONNECTED.
16. WHEN INSTALLING LUMINAIRES, THE CONTRACTOR SHALL USE THE LUMINAIRE MANUFACTURER'S MOUNTING HARDWARE AND FOLLOW ALL MANUFACTURER'S INSTALLATION DIRECTIONS.
Revisions: Date:
09/01/2023
UNIVERSAL
UNIVERSAL
UNIVERSAL
UNIT
SUB
'G'
UNIT
SUB
'A'
EMERGENCY
PARALLELING
SWITCHGEAR
EXISTING
ESWBD-1
1600A, 480Y/277V
WESTINGHOUSE
POWER LINE C
SWITCHBOARD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com
B
IM
/2
V
A W e s t P a lm
B e a c h
E H
R M
I n fr a s tr u c tu re U p g ra d e s D e s ig n /5
-7
.B
.E
R
.r v t
/1
/2
:1
:5
P
M
B01-EN332
ENLARGED ELECTRICAL ROOM
PLANS - ELECTRICAL
ELECTRONIC HEALTH RECORD
MODERNIZATION (EHRM)
INFRASTRUCTURE UPGRADES
WEST PALM BEACH, FL
548-22-700
03/31/23 MG…