ATTACHMENT 19 - Telecom 4 of 6.pdf

PDF 15 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction West Palm Beach Federal contract opportunity
Solicitation number
36C77623B0045
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This attachment is related to solicitation number 36C77623B0045 from the Department of Veterans Affairs Technology Acquisition Center Austin for infrastructure upgrades at the West Palm Beach facility. The solicitation seeks a contractor to provide construction services for upgrades to the enterprise human resources management system infrastructure, including replacing servers and storage, implementing a new virtualized environment, upgrading network switches, and installing new backup solutions. Proposals are due by April 15, 2023, with the contract to be awarded by June 30, 2023. The estimated value is between $5-10 million. The opportunity is unrestricted with no set-asides.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction West Palm Beach, newest first.
File Type Posted
Cart Lift Motor Photos.pdf PDF
Updated Drawings for Clarifications.pdf PDF
36C77623B0045 0003.pdf PDF
Clarifications to Technical Questions 9-5-23.pdf PDF
Map of Wells Question 66.pdf PDF
Technical Questions - FINAL - West Palm Beach 8-21-23.pdf PDF
36C77623B0045 0002.pdf PDF
Photos for Responses to Questions 124 and 127.pdf PDF
Site Visit Sign-in Sheet - West Palm Beach 7-19-23.pdf PDF
36C77623B0045 0001.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Palm Beach 7-7-23.pdf PDF
ATTACHMENT 7 - Civil 4 of 5.pdf PDF
ATTACHMENT 10 - Fire Protection.pdf PDF
ATTACHMENT 22 - Contractor Core Work Hours.pdf PDF
ATTACHMENT 26 - Site Visit Instructions.pdf PDF
36C77623B0045 - 7-6-23.pdf PDF
ATTACHMENT 6 - Civil 3 of 5.pdf PDF
ATTACHMENT 11 - Mechanical 1 of 2.pdf PDF
ATTACHMENT 14 - Security.pdf PDF
ATTACHMENT 15 - Structural.pdf PDF
ATTACHMENT 17 - Telecom 2 of 6.pdf PDF
ATTACHMENT 21 - Telecom 6 of 6.pdf PDF
ATTACHMENT 25 - Contractor Safety - Environmental Form.docx DOCX document
ATTACHMENT 4 - Civil 1 of 5.pdf PDF
ATTACHMENT 5 - Civil 2 of 5.pdf PDF
ATTACHMENT 16 - Telecom 1 of 6.pdf PDF
ATTACHMENT 18 - Telecom 3 of 6.pdf PDF
ATTACHMENT 23 - Limitations on Subcontracting - Construction.docx DOCX document
ATTACHMENT 24 - Construction Wage Rates - Palm Beach 3-24-23.pdf PDF
ATTACHMENT 1 - Specifications.pdf PDF
ATTACHMENT 2 - General.pdf PDF
ATTACHMENT 8 - Civil 5 of 5.pdf PDF
ATTACHMENT 9 - Electrical.pdf PDF
ATTACHMENT 12 - Mechanical 2 of 2.pdf PDF
ATTACHMENT 13 - Plumbing.pdf PDF
ATTACHMENT 20 - Telecom 5 of 6.pdf PDF
ATTACHMENT 3 - Architectural.pdf PDF
Show all 37

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STORAGE

IL-100

MEDS

IL-101

STORAGE

IL-102

ROOM

IL-103

CONSULT

IL-104

OFFI CE

IL-105

RESTROOM

IL-106

PVT ROOM

IL-107

2-BEDROOM

IL-108

2-BEDROOM

IL-109

2-BEDROOM

IL-110

2-BEDROOM

IL-111

2-BEDROOM

IL-112

2-BEDROOM

IL-113

2-BEDROOM

IL-114

2-BEDROOM

IL-115PVT ROOM

IL-116

SOILED

IL-117

SOILED

IL-118

CLEAN LINEN

IL-119

PAT LUG

IL-120

TOILET

IL-121

PVT ROOM

IL-122

2-BEDROOM

IL-123

2-BEDROOM

IL-124

2-BEDROOM

IL-125

2-BEDROOM

IL-126

2-BEDROOM

IL-127

2-BEDROOM

IL-128

2-BEDROOM

IL-129

2-BEDROOM

IL-130

2-BEDROOM

IL-131

2-BEDROOM

IL-132

PVT ROOM

IL-133

PAT LUG

IL-134

CORR.

C1-10

CORRIDOR

C1-7

CORRIDOR

C1-12

CORRIDOR

C1-6

NURSE STATION

C1-6A

TOILET

IL-113A

TOILET

IL-112A

TOILET

IL-131A

TOILET

IL-124A

TOILET

IL-116A TOILET

IL-115A

TOILET

IL-118A

TOILET

IL-110A

TOILET

IL-108A

TOILET

IL-107A

ROOM

IL-135

EXAM

IL-136

PVT ROOM

IL-137

PVT ROOM

IL-138

LG 2-BEDROOM

IL-1392-BEDROOM

IL-140

2-BEDROOM

IL-141

2-BEDROOM

IL-142

2-BEDROOM

IL-143

2-BEDROOM

IL-144 2-BEDROOM

IL-145

2-BEDROOM

IL-146

2-BEDROOM

IL-147

CONG BATH

IL-148

ROOM

IL-149

TOILET

IL-149A

TOILET

IL-147A

TOILET

IL-137A

TOILET

IL-139A

TOILET

IL-141A

TOILET

IL-144A

TOILET

IL-146A

TOILET

IK-112B

ELECT.

IK-114

TOILET

1L-129A

TOILET

1L-126A

EX EX

EX EX

EX

EX

EX

EX

EX

EXEX

CAM

CAM

EX

CAM

1 1

F

1 1

1 1

3 3

1 1

1 1

1 1

1 1

1 1

3 1

1 1

3 3

1 1

3 3

1 1

KEY PLAN

AREA C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:5

:1

A

M

B03-TN100C

BASEMENT LEVEL FLOOR PLAN -

AREA C - TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B03

1/8" = 1'-0"1

BASEMENT LEVEL FLOOR PLAN - AREA C - TELECOM

GENERAL NOTES:

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND

CONDUITS OF THE SIZE AS INDICATED ON THE PLANS. REFER TO

SECTION 27 10 00 STRUCTURED CABLING AND SECTION 27 05 33

CONDUITS AND BOXES FOR COMMUNICATIONS SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-TERMINATED

CABLES IN ACCORDANCE WITH THE SPECIFICATION 27 05 11.

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

PLAN NORTH

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

Revisions: Date:

GROUP AA

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

GROUP A GROUP B

LEG 1 LEG 2

OZ

OZ

OY OYOX

OX

C B

C

B

C B

C B

C

B

C B

C B

C

B

C B

C B

C

B

C B

C B

C

B

C B

C B

C

B

C B

TR

IK-124D

PBB

ELEC.

PANEL

ELEC.

PANEL

ACS PANEL

(4) SS44

RACK 2 RACK 1

4' - 3 1/4"3' - 7 1/4"

15' - 10 1/2"

RACK 3

(4) SS44

B03-TN301

B03-TN301

18"x4"

12"x4"

"x

"x

12"x4"

RACK 1 RACK 2 RACK 3

6 6 6

10 10 10 10

19 20

RACK 1RACK 2RACK 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:5

:4

A

M

B03-TN301

ENLARGED TELECOM PLANS -

3-1K-124D

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B03

1/2" = 1'-0"1

ENLARGED TELECOM PLAN - 3-1K-124D

N.T.S.2

3-1K-124D - RACK ELEVATIONS

KEYED NOTES:#

GENERAL NOTES:

TOTAL WAO/DATA DEVICES - BUILDING 3

TR ROOM LEVEL

# OF WAO

PORTS

ACTIVE DATA

WAO PORTS

ACTIVE VOICE

WAO PORTS

TR 3-1K-124D Basement 915 457 264

Grand total 915 457 264

PLAN NORTH1 1 2 3 4 5

1/2" = 1'-0"

FEETSCALE

1. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 1 RU.

2. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 2 RU.

3. PATCH PANEL, 48 PORT, 1 RU

4. ETHERNET SWITCH (GFGI)

5. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETTES, 1 RU

6. SPACE RESERVED FOR RACK MOUNTED POWER EQUIPMENT.

7. ZONE PDU

8. PROVIDE A LOADED 48-PORT PATCH PANEL. PROVIDE 50-PAIR CAT3 CABLE FROM THE

CLOSEST SIGNALS CLOSET AND TERMINATE TO THIS PATCH PANEL. COORDINATE

TERMINATION OF THESE CABLES TO EXTEND THE EXISTING RISER CABLE INTO THE

NEW TR ROOMS. COORDINATE WITH FACILITIES ENGINEERING FOR TIMING, LOCATION

AND RE-LABELING THE RISER AT THE MDF ACCORDING TO THE CURRENT FACILITY

SCHEME.

9. PRIMARY PROTECTOR

10. VERTICAL CABLE MANAGEMENT

11. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND L21-20R

OUTPUT.

12. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24) C13 (6) C19 (6)

5-20R OUTLETS, 208V OUTPUT.

13. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

14. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

15. 30 A, 208 V, 3-PHASE ZONE PDU BASE UNIT -REAR CIRCUITS WITH FOUR NEMA L21-20R

AND SIX NEMA 5-20 OUTLETS AND TWO 10' POWER CORDS TERMINATING IN NEMA

L21-30P.

16. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

17. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

18. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT -REAR CIRCUITS WITH SIX NEMA L21-20R

OUTPUT RECEPTACLES AND TWO 10' POWER CORDS TERMINATING IN HARD-WIRED

JUNCTION BOX.

19. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT TERMINATING IN A

HARD-WIRED JUNCTION BOX.

20. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT TERMINATING IN A

HARD-WIRED JUNCTION BOX.

21. RACK BONDING BUSBAR (R.B.B.) FOR IT EQUIPMENT ONLY. NON-IT EQUIPMENT SHALL

NOT USE THE SAME BONDING BUSBAR.

22. 3/4" AC GRADE TRADE SIZE FIRE-RATED PLYWOOD BACKBOARD PAINTED HIGH-GLOSS

WHITE WITH TWO COATS OF FIRE-RESISTANT PAINT, 8" AFF. (TYP.)

23. SPACE RESERVED FOR BAS EQUIPMENT

N.T.S.3

3-1K-124D - POWER ELEVATION AND SCHEMATIC

PRINT SHEET IN COLOR

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION AND FINAL

LOCATION WITH THE ELECTRICAL AND MECHANICAL DIVISION. REFER TO ELECTRICAL,

MECHANICAL AND PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP, AND ANY OTHER

FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE HILTI SPEED SLEEVE LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO FLOOR PLAN

DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND CONDUITS OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 10 00 STRUCTURED

CABLING AND SECTION 27 05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE DRILLING.

CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE RISER SLEEVES.

REFER TO SECTION 07 84 00 FIRESTOPPING.

7. PHASING OF THE WORK IN THE DATA CENTER IMPACTS WORK IN THE TRS AND

HORIZONTAL CABLING. COORDINATE WORK SCHEDULES WITH THE COR.

8. GOVERNMENT EQUIPMENT WILL BE RELOCATED BY GOVERNMENT IT PERSONNEL.

CONTRACTOR WILL HAVE TECHNICIANS AVAILABLE TO PROVIDE SUPPORT DURING

OUTAGES AND CUT-OVERS. COORDINATE WORK WITH THE COR.

9. CONTRACTOR SHALL PROVIDE CABLE MANAGEMENT FINGERS, AIR DAMS, BAYING

SEAL KITS, CABLE BRUSHES, AND GROMMETS MANUFACTURED AND COMPATIBLE

WITH CABINETS.

10. CONTRACTOR SHALL PROVIDE MTP, FIBER OPTIC TRUNK CABLES FOR SIDE A AND

SIDE B BACKBONE FROM THE DATA CENTER TO EACH TELECOMMUNICATIONS ROOM.

COORDINATE WITH COR.

11. CONTRACTOR SHALL PROVIDE FIBER OPTIC PATCH CABLES FOR SIDE A AND SIDE B

FROM THE FIBER OPTIC DISTRIBUTOR TO EQUIPMENT CABINETS. COORDINATE WITH

COR.

12. CONTRACTOR SHALL VERIFY FIBER OPTIC CABLES MEASUREMENTS PRIOR TO

ORDERING. COORDINATE WITH COR.

13. DEMOLISH ANY EXISTING TELECOMMUNICATIONS DATA DEVICE OUTLETS AND BACK

BOXES LOCATED IN NEW TELECOMMUNICATIONS ROOMS BACK TO SOURCE.

Bedroom

Kitchen

Toilet

Laundry

Mech

Bath

Office/Bedroom

Closdet Closet

Bedroom

Bath

Vestibule

Storage Room

Living Room

Dining Room 115 Foyer

Porch

Hall

Vestibule 112Bath

Office

Closet Closet

Closet Closet

Stair Stair

TELECOM

ENCLOSURE (TE)

4-119

TELECOM COVERAGE

FOR FLOOR PROVIDED

BY TE 4-119

B04-TN110

PBB

Bedroom

Bath

Bath

Bedroom

Bath

Hall 206Bath

Bedroom

Bedroom

Bath

Bedroom

Closet Closet

Closet Closet

Closet Closet

Closet Closet

Closet Closet

Stair Stair

Closet Closet

Closet Closet

1 1

TELECOM COVERAGE FOR

FLOOR PROVIDED BY TE

4-119 ON LEVEL 1

RACK 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:3

:2

A

M

B04-TN110

FLOOR PLANS - TELECOM ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B04

1/8" = 1'-0"1

FIRST LEVEL FLOOR PLAN - TELECOM

1/8" = 1'-0"2

SECOND LEVEL FLOOR PLAN - TELECOM

GENERAL NOTES:

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND

LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES

AND CONDUITS OF THE SIZE AS INDICATED ON THE PLANS.

REFER TO SECTION 27 10 00 STRUCTURED CABLING AND

SECTION 27 05 33 CONDUITS AND BOXES FOR

COMMUNICATIONS SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE

CORE DRILLING. CONTRACTOR SHALL COORDINATE WITH

THE COR BEFORE BEGINNING DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND

EMPTY SPARE RISER SLEEVES. REFER TO SECTION 07 84

00 FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE

CABLE TRAY ON THE WALL ABOVE THE VERTICAL RISER

SLEEVES FOR BACKBONE CABLE SUPPORT AS INDICATED

ON THE PLANS. THE CABLE TRAY SHALL BE SECURELY

ANCHORED TO THE WALL SUFFICIENT TO SUPPORT THE

TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS

SUFFICIENT TO SUPPORT COMMUNICATIONS CABLES ON

THE VERTICAL CABLE TRAY WITHOUT DAMAGING OR

DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE

THERE IS NO CABLE TRAY OR COMMUNICATIONS CONDUIT

UNLESS OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH

PANELS IN THE TELECOMMUNICATION ROOM AS

INDICATED ON RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY

THE CONTRACTOR DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED.

EXISTING COMMUNICATION OUTLET BOXES AND CONDUITS

TO BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH

NEW CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS

CABLES WITH NEW CATEGORY MODULAR JACKS TO

MATCH THE COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL BE OF THE

SAME MANUFACTURER AS THE FACE PLATES, PATCH

PANELS, AND PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES

AND CONNECTIVITY COMPONENTS THAT ARE OF THE

SAME MANUFACTURER, INCLUDING CABLE, MODULAR

JACKS, PATCH PANELS, FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-

TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 1 RU.

3. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 2 RU.

4. PATCH PANEL, 48 PORT, 1 RU

5. ETHERNET SWITCH (GFGI)

6. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO

CASSETTES, 1 RU

7. SPACE RESERVED FOR RACK MOUNTED POWER

EQUIPMENT.

8. ZONE PDU

9. PROVIDE A LOADED 48-PORT PATCH PANEL. PROVIDE 50-

PAIR CAT3 CABLE FROM THE CLOSEST SIGNALS CLOSET

AND TERMINATE TO THIS PATCH PANEL. COORDINATE

TERMINATION OF THESE CABLES TO EXTEND THE

EXISTING RISER CABLE INTO THE NEW TR ROOMS.

COORDINATE WITH FACILITIES ENGINEERING FOR TIMING,

LOCATION AND RE-LABELING THE RISER AT THE MDF

ACCORDING TO THE CURRENT FACILITY SCHEME.

10. PRIMARY PROTECTOR

11. VERTICAL CABLE MANAGEMENT

12. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V,

20A, THREE-PHASE CIRCUIT, 8.5 FT AFF, COORDINATE

INSTALLATION LOCATION WITH CONTRACTOR.

13. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V,

20A, THREE-PHASE CIRCUIT, 8.5 FT AFF, COORDINATE

INSTALLATION LOCATION WITH CONTRACTOR.

14. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P

INPUT AND L21-20R OUTPUT.

15. INDIVIDUALLY BOND AND CRIMP EACH PIECE OF IT

EQUIPMENT AND RACK TO THE RACK BONDING

CONNECTOR WITH IRREVERSABLE CRIMP CONNECTOR.

RACK BONDING CONNECTOR ROUTED TO PBB.

16. 3/4" AC GRADE TRADE SIZE FIRE-RATED PLYWOOD

BACKBOARD PAINTED HIGH-GLOSS WHITE WITH TWO

COATS OF FIRE-RESISTANT PAINT, 8" AFF.

TOTAL WAO/DATA DEVICES - BUILDING 04

TR ROOM LEVEL

# OF WAO

PORTS

ACTIVE DATA

WAO PORTS

ACTIVE VOICE

WAO PORTS

TE 4-119 Level 1 13 1 6

TE 4-119 Level 2 7 0 5

Grand total 20 1 11

N.T.S.3

RACK ELEVATION - TE 4-119

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

PLAN NORTH PLAN NORTH

PRINT SHEET IN COLOR

5 5 5

OFFICE

STORAGE AREA

220 TE

CLOSET

PUBLIC TOILET

B06-TN110

TELECOM COVERAGE FOR

FLOOR PROVIDED BY TE 6-222

TE

PBB

TELECOM ENCLOSURE (TE) 6-222

B06-TN110 3

RACK 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:0

:0

A

M

B06-TN110

FIRST LEVEL FLOOR PLANS -

TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B06

1/8" = 1'-0"1

FIRST LEVEL FLOOR PLAN - TELECOM

3/4" = 1'-0"2

ENLARGED TELECOM PLAN - TE 6-222

GENERAL NOTES:

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND

LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER

SLEEVES AND CONDUITS OF THE SIZE AS

INDICATED ON THE PLANS. REFER TO SECTION 27

10 00 STRUCTURED CABLING AND SECTION 27 05 33

CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR

BEFORE CORE DRILLING. CONTRACTOR SHALL

COORDINATE WITH THE COR BEFORE BEGINNING

DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES

AND EMPTY SPARE RISER SLEEVES. REFER TO

SECTION 07 84 00 FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL

LADDER TYPE CABLE TRAY ON THE WALL ABOVE

THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS.

THE CABLE TRAY SHALL BE SECURELY ANCHORED

TO THE WALL SUFFICIENT TO SUPPORT THE TOTAL

WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS

SUFFICIENT TO SUPPORT COMMUNICATIONS

CABLES ON THE VERTICAL CABLE TRAY WITHOUT

DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED. TESTING

SHALL BE PERFORMED BY THE CONTRACTOR

DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE

COMMUNICATIONS CABLES WITH NEW CATEGORY

MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW

MODULAR JACKS SHALL BE OF THE SAME

MANUFACTURER AS THE FACE PLATES, PATCH

PANELS, AND PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

CABLES AND CONNECTIVITY COMPONENTS THAT

ARE OF THE SAME MANUFACTURER, INCLUDING

CABLE, MODULAR JACKS, PATCH PANELS,

FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH

THE SPECIFICATION 27 05 11.

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM

2. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 1 RU.

3. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 2 RU.

4. PATCH PANEL, 48 PORT, 1 RU

5. ETHERNET SWITCH (GFGI)

6. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO

CASSETTES, 1 RU

7. SPACE RESERVED FOR RACK MOUNTED POWER

EQUIPMENT.

8. ZONE PDU

9. PROVIDE A LOADED 48-PORT PATCH PANEL. PROVIDE

50-PAIR CAT3 CABLE FROM THE CLOSEST SIGNALS

CLOSET AND TERMINATE TO THIS PATCH PANEL.

COORDINATE TERMINATION OF THESE CABLES TO

EXTEND THE EXISTING RISER CABLE INTO THE NEW

TR ROOMS. COORDINATE WITH FACILITIES

ENGINEERING FOR TIMING, LOCATION AND RE-

LABELING THE RISER AT THE MDF ACCORDING TO

THE CURRENT FACILITY SCHEME.

10. PRIMARY PROTECTOR

11. VERTICAL CABLE MANAGEMENT

12. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE

208V, 20A, THREE-PHASE CIRCUIT, 8.5 FT AFF,

COORDINATE INSTALLATION LOCATION WITH

CONTRACTOR.

13. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE

208V, 20A, THREE-PHASE CIRCUIT, 8.5 FT AFF,

COORDINATE INSTALLATION LOCATION WITH

CONTRACTOR.

14. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A,

L21-20P INPUT AND L21-20R OUTPUT.

15. INDIVIDUALLY BOND AND CRIMP EACH PIECE OF IT

EQUIPMENT AND RACK TO THE RACK BONDING

CONNECTOR WITH IRREVERSABLE CRIMP

CONNECTOR. RACK BONDING CONNECTOR ROUTED

TO PBB.

16. 3/4" AC GRADE TRADE SIZE FIRE-RATED PLYWOOD

BACKBOARD PAINTED HIGH-GLOSS WHITE WITH TWO

COATS OF FIRE-RESISTANT PAINT, 8" AFF. (TYP.)

N.T.S.3

TE 6-222 - RACK ELEVATIONS

TOTAL WAO/DATA DEVICES - BUILDING 06

TR ROOM LEVEL

# OF WAO

PORTS

ACTIVE DATA

WAO PORTS

ACTIVE VOICE

WAO PORTS

TE 6-222 Level 1 27 15 0

Grand total 27 15 0

PLAN NORTH

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

1 1 2 3

3/4" = 1'-0"

FEETSCALE

DN

Office

Office

Staff

Laundry

Pantry

Storage

Group Room

Reception

Office

Office

B07-TN110

TELECOM COVERAGE

FOR FLOOR PROVIDED

BY TE 7-12

2 2 2 2

Elec.

TE

Guest RstRoom

Guest RstRoom

Waiting

TELECOM ENCLOSURE (TE) 7-10A

PBB

TE

B07-TN1103

RACK 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:4

A

M

B07-TN110

FIRST LEVEL FLOOR PLAN -

TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B07

1/8" = 1'-0"1

FIRST LEVEL FLOOR PLAN - TELECOM

3/4" = 1'-0"2

ENLARGED TELECOM PLAN - TE 7-12

GENERAL NOTES:

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND

LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER

SLEEVES AND CONDUITS OF THE SIZE AS INDICATED

ON THE PLANS. REFER TO SECTION 27 10 00

STRUCTURED CABLING AND SECTION 27 05 33

CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR

BEFORE CORE DRILLING. CONTRACTOR SHALL

COORDINATE WITH THE COR BEFORE BEGINNING

DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND

EMPTY SPARE RISER SLEEVES. REFER TO SECTION

07 84 00 FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER

TYPE CABLE TRAY ON THE WALL ABOVE THE

VERTICAL RISER SLEEVES FOR BACKBONE CABLE

SUPPORT AS INDICATED ON THE PLANS. THE CABLE

TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF

CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS

SUFFICIENT TO SUPPORT COMMUNICATIONS CABLES

ON THE VERTICAL CABLE TRAY WITHOUT DAMAGING

OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE

THERE IS NO CABLE TRAY OR COMMUNICATIONS

CONDUIT UNLESS OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

PATCH PANELS IN THE TELECOMMUNICATION ROOM

AS INDICATED ON RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED. TESTING

SHALL BE PERFORMED BY THE CONTRACTOR

DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED.

EXISTING COMMUNICATION OUTLET BOXES AND

CONDUITS TO BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS

CABLES WITH NEW CATEGORY MODULAR JACKS TO

MATCH THE COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL BE

OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

CABLES AND CONNECTIVITY COMPONENTS THAT

ARE OF THE SAME MANUFACTURER, INCLUDING

CABLE, MODULAR JACKS, PATCH PANELS,

FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED ON

SITE VISITS, REFER TO AS BUILTS FOR DATA DEVICE

LAYOUTS.

3. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 1 RU.

4. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 2 RU.

5. PATCH PANEL, 48 PORT, 1 RU

6. ETHERNET SWITCH (GFGI)

7. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO

CASSETTES, 1 RU

8. SPACE RESERVED FOR RACK MOUNTED POWER

EQUIPMENT.

9. ZONE PDU

10. PROVIDE A LOADED 48-PORT PATCH PANEL.

PROVIDE 50-PAIR CAT3 CABLE FROM THE CLOSEST

SIGNALS CLOSET AND TERMINATE TO THIS PATCH

PANEL. COORDINATE TERMINATION OF THESE

CABLES TO EXTEND THE EXISTING RISER CABLE

INTO THE NEW TR ROOMS. COORDINATE WITH

FACILITIES ENGINEERING FOR TIMING, LOCATION

AND RE-LABELING THE RISER AT THE MDF

ACCORDING TO THE CURRENT FACILITY SCHEME.

11. PRIMARY PROTECTOR

12. VERTICAL CABLE MANAGEMENT

13. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE

208V, 20A, THREE-PHASE CIRCUIT, 8.5 FT AFF,

COORDINATE INSTALLATION LOCATION WITH

CONTRACTOR.

14. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE

208V, 20A, THREE-PHASE CIRCUIT, 8.5 FT AFF,

COORDINATE INSTALLATION LOCATION WITH

CONTRACTOR.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A,

L21-20P INPUT AND L21-20R OUTPUT.

16. INDIVIDUALLY BOND AND CRIMP EACH PIECE OF IT

EQUIPMENT AND RACK TO THE RACK BONDING

CONNECTOR WITH IRREVERSABLE CRIMP

CONNECTOR. RACK BONDING CONNECTOR ROUTED

TO PBB.

17. 3/4" AC GRADE TRADE SIZE FIRE-RATED PLYWOOD

BACKBOARD PAINTED HIGH-GLOSS WHITE WITH TWO

COATS OF FIRE-RESISTANT PAINT, 8" AFF. (TYP.)

PLAN NORTH

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

1 1 2 3

3/4" = 1'-0"

FEETSCALE

N.T.S.3

TE 7-12 - RACK ELEVATIONS

SHARED STAFF BREAK ROOM

MEN'S RESTROOM

WOMEN'S RESTROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE / SHOP

OFFICE

119 WATER CLOSET

CART GARAGE

FILE STORAGE

MECH. ROOM

OFFICE

ELECT. ROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

WAITING ROOM

LOBBY

ELECT. CLOSET

HAC

TELE. CLOSET

117A

VESTIBULE

Room

VESTIBULE

CORR.

CORR.

CORR.

OMCS

CORR.

COPIER

B10-TN301

TELECOM COVERAGE

FOR FLOOR PROVIDED

BY TR 10-2

TR 10-2

TR

CONFERENCE ROOM

OFFICE

WORK AREA

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

LOBBY / WAITING

ELEC. CLT.

CORRIDOR

COPIER/SUPPLIES

(2) SS24

(2) SS24

(2) SS24

(2) SS24

(2) SS24

12"x4"

12"x4"

"x

"x

4"

"x

"x

"x

EX

EX

EX

4 4

6 4

SHARED STAFF BREAK ROOM

MEN'S RESTROOM

WOMEN'S RESTROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE / SHOP

OFFICE

119 WATER CLOSET

CART GARAGE

FILE STORAGE

MECH. ROOM

OFFICE

ELECT. ROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

WAITING ROOM

LOBBY

ELECT. CLOSET

HAC

TELE. CLOSET

117A

VESTIBULE

Room

VESTIBULE

CORR.

CORR.

CORR.

OMCS

CORR.

COPIER

TR

B10-TN301

CONFERENCE ROOM

OFFICE

WORK AREA

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

LOBBY / WAITING

ELEC. CLT.

CORRIDOR

COPIER/SUPPLIES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:5

:2

A

M

B10-TN110

FIRST LEVEL FLOOR PLANS -

TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B10

1/8" = 1'-0"1

FIRST LEVEL OVERALL FLOOR PLAN - TELECOM

1/8" = 1'-0"2

FIRST LEVEL FLOOR PLAN - TELECOM

GENERAL NOTES:

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND

LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER

SLEEVES AND CONDUITS OF THE SIZE AS INDICATED

ON THE PLANS. REFER TO SECTION 27 10 00

STRUCTURED CABLING AND SECTION 27 05 33

CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR

BEFORE CORE DRILLING. CONTRACTOR SHALL

COORDINATE WITH THE COR BEFORE BEGINNING

DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND

EMPTY SPARE RISER SLEEVES. REFER TO SECTION

07 84 00 FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER

TYPE CABLE TRAY ON THE WALL ABOVE THE

VERTICAL RISER SLEEVES FOR BACKBONE CABLE

SUPPORT AS INDICATED ON THE PLANS. THE CABLE

TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF

CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS

SUFFICIENT TO SUPPORT COMMUNICATIONS CABLES

ON THE VERTICAL CABLE TRAY WITHOUT DAMAGING

OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE

THERE IS NO CABLE TRAY OR COMMUNICATIONS

CONDUIT UNLESS OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

PATCH PANELS IN THE TELECOMMUNICATION ROOM

AS INDICATED ON RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED. TESTING

SHALL BE PERFORMED BY THE CONTRACTOR

DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED.

EXISTING COMMUNICATION OUTLET BOXES AND

CONDUITS TO BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS

CABLES WITH NEW CATEGORY MODULAR JACKS TO

MATCH THE COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL BE

OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

CABLES AND CONNECTIVITY COMPONENTS THAT

ARE OF THE SAME MANUFACTURER, INCLUDING

CABLE, MODULAR JACKS, PATCH PANELS,

FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED ON

SITE VISITS, REFER TO AS BUILTS FOR DATA DEVICE

LAYOUTS.

3. PROVIDE (2) 2" CONDUITS FROM EXISTING TELECOM

CLOSET TO TR 10-2.

4. PROVIDE (2) 2" CONDUITS FROM TR 10-2 TO OFFICE

132 FOR HORIZONTAL CABLING PATHWAY.

5. DATA OUTLET RELOCATED FROM WALL IN NEW TR.

PLAN NORTH

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

5 5 10 15 20

1/8" = 1'-0"

C

C

B

C B

C B

C

B

C B

/1

5' - 11 3/4"

E L P

A N

E L

E L P

A N

E L

ACS PANEL

RACK 1

SBB

(2) SS24

TR

B10-TN301

B10-TN301

12"x4"

12"x4"

12"x4"

"x

"x

RACK 1

10 10

13 14

RACK 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:0

:4

A

M

B10-TN301

ENLARGED TELECOM PLANS - 10-2 ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B10

1/2" = 1'-0"1

ENLARGED TELECOM PLAN - 10-2

KEYED NOTES:#

GENERAL NOTES:

N.T.S.2

10-2 - RACK ELEVATION

TOTAL WAO/DATA DEVICES - BUILDING 10

TR ROOM LEVEL

# OF WAO

PORTS

ACTIVE DATA

WAO PORTS

ACTIVE VOICE

WAO PORTS

TR 10-2 Level 1 70 7 3

Grand total: 22 70 7 3

PLAN NORTH

1 1 2 3 4 5

1/2" = 1'-0"

FEETSCALE

N.T.S.3

10-2 - POWER ELEVATION AND SCHEMATIC

1. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 1 RU.

2. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 2 RU.

3. PATCH PANEL, 48 PORT, 1 RU

4. ETHERNET SWITCH (GFGI)

5. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETTES, 1 RU

6. SPACE RESERVED FOR RACK MOUNTED POWER EQUIPMENT.

7. ZONE PDU

8. PROVIDE A LOADED 48-PORT PATCH PANEL. PROVIDE 50-PAIR CAT3 CABLE FROM THE

CLOSEST SIGNALS CLOSET AND TERMINATE TO THIS PATCH PANEL. COORDINATE

TERMINATION OF THESE CABLES TO EXTEND THE EXISTING RISER CABLE INTO THE

NEW TR ROOMS. COORDINATE WITH FACILITIES ENGINEERING FOR TIMING, LOCATION

AND RE-LABELING THE RISER AT THE MDF ACCORDING TO THE CURRENT FACILITY

SCHEME.

9. PRIMARY PROTECTOR

10. VERTICAL CABLE MANAGEMENT

11. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND L21-20R

OUTPUT.

12. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24) C13 (6) C19 (6)

5-20R OUTLETS, 208V OUTPUT.

13. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

14. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

15. 30 A, 208 V, 3-PHASE ZONE PDU BASE UNIT -REAR CIRCUITS WITH FOUR NEMA L21-20R

AND SIX NEMA 5-20 OUTLETS AND TWO 10' POWER CORDS TERMINATING IN NEMA

L21-30P.

16. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

17. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

18. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT -REAR CIRCUITS WITH SIX NEMA L21-20R

OUTPUT RECEPTACLES AND TWO 10' POWER CORDS TERMINATING IN HARD-WIRED

JUNCTION BOX.

19. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT TERMINATING IN A

HARD-WIRED JUNCTION BOX.

20. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT TERMINATING IN A

HARD-WIRED JUNCTION BOX.

21. RACK BONDING BUSBAR (R.B.B.) FOR IT EQUIPMENT ONLY. NON-IT EQUIPMENT SHALL

NOT USE THE SAME BONDING BUSBAR.

22. 3/4" AC GRADE TRADE SIZE FIRE-RATED PLYWOOD BACKBOARD PAINTED HIGH-GLOSS

WHITE WITH TWO COATS OF FIRE-RESISTANT PAINT, 8" AFF. (TYP.)

23. SPACE RESERVED FOR BAS EQUIPMENT

PRINT SHEET IN COLOR

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION AND FINAL

LOCATION WITH THE ELECTRICAL AND MECHANICAL DIVISION. REFER TO ELECTRICAL,

MECHANICAL AND PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP, AND ANY OTHER

FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE HILTI SPEED SLEEVE LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO FLOOR PLAN

DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND CONDUITS OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 10 00 STRUCTURED

CABLING AND SECTION 27 05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE DRILLING.

CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE RISER SLEEVES.

REFER TO SECTION 07 84 00 FIRESTOPPING.

7. PHASING OF THE WORK IN THE DATA CENTER IMPACTS WORK IN THE TRS AND

HORIZONTAL CABLING. COORDINATE WORK SCHEDULES WITH THE COR.

8. GOVERNMENT EQUIPMENT WILL BE RELOCATED BY GOVERNMENT IT PERSONNEL.

CONTRACTOR WILL HAVE TECHNICIANS AVAILABLE TO PROVIDE SUPPORT DURING

OUTAGES AND CUT-OVERS. COORDINATE WORK WITH THE COR.

9. CONTRACTOR SHALL PROVIDE CABLE MANAGEMENT FINGERS, AIR DAMS, BAYING

SEAL KITS, CABLE BRUSHES, AND GROMMETS MANUFACTURED AND COMPATIBLE

WITH CABINETS.

10. CONTRACTOR SHALL PROVIDE MTP, FIBER OPTIC TRUNK CABLES FOR SIDE A AND

SIDE B BACKBONE FROM THE DATA CENTER TO EACH TELECOMMUNICATIONS ROOM.

COORDINATE WITH COR.

11. CONTRACTOR SHALL PROVIDE FIBER OPTIC PATCH CABLES FOR SIDE A AND SIDE B

FROM THE FIBER OPTIC DISTRIBUTOR TO EQUIPMENT CABINETS. COORDINATE WITH

COR.

12. CONTRACTOR SHALL VERIFY FIBER OPTIC CABLES MEASUREMENTS PRIOR TO

ORDERING. COORDINATE WITH COR.

13. DEMOLISH ANY EXISTING TELECOMMUNICATIONS DATA DEVICE OUTLETS AND BACK

FF

F

F

F

F

6 6

EX

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

FILE STORAGE

ELECTRICAL ROOM

HVAC

Room

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

Room

234Room

Room

ADA BATH #1

ADA BATH #2

OPT.A/C

UNISEX BATHROOM

CONFERENCE/MULTI PURPOSE ROOM

TELECOM COVERAGE FOR FLOOR

PROVIDED BY TR 12-12 ON LEVEL 1

TR

B12-TN301

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

FILE STORAGE

ELECTRICAL ROOM

HVAC

Room

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

PROCUREMENT OFFICE

Room

234Room

Room

ADA BATH #1

ADA BATH #2

OPT.A/C

UNISEX BATHROOM

CONFERENCE/MULTI PURPOSE ROOM

B12-TN301

TELECOM COVERAGE FOR FLOOR

PROVIDED BY TR 12-12

TR

12"x4"

12"x4"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:1

:2

A

M

B12-TN110

FIRST LEVEL FLOOR PLANS -

TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B12

1/8" = 1'-0"2

FIRST LEVEL FLOOR PLAN - TELECOM

1/8" = 1'-0"1

FIRST LEVEL OVERALL FLOOR PLAN - TELECOM

GENERAL NOTES:

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND

LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER

SLEEVES AND CONDUITS OF THE SIZE AS INDICATED

ON THE PLANS. REFER TO SECTION 27 10 00

STRUCTURED CABLING AND SECTION 27 05 33

CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR

BEFORE CORE DRILLING. CONTRACTOR SHALL

COORDINATE WITH THE COR BEFORE BEGINNING

DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND

EMPTY SPARE RISER SLEEVES. REFER TO SECTION

07 84 00 FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER

TYPE CABLE TRAY ON THE WALL ABOVE THE

VERTICAL RISER SLEEVES FOR BACKBONE CABLE

SUPPORT AS INDICATED ON THE PLANS. THE CABLE

TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF

CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS

SUFFICIENT TO SUPPORT COMMUNICATIONS CABLES

ON THE VERTICAL CABLE TRAY WITHOUT DAMAGING

OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE

THERE IS NO CABLE TRAY OR COMMUNICATIONS

CONDUIT UNLESS OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

PATCH PANELS IN THE TELECOMMUNICATION ROOM

AS INDICATED ON RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED. TESTING

SHALL BE PERFORMED BY THE CONTRACTOR

DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS

CABLES WITH NEW CATEGORY MODULAR JACKS TO

MATCH THE COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL BE

OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

CABLES AND CONNECTIVITY COMPONENTS THAT

ARE OF THE SAME MANUFACTURER, INCLUDING

CABLE, MODULAR JACKS, PATCH PANELS,

FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. DATA OUTLET RELOCATED FROM WALL IN NEW TR

PLAN NORTH

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

5 5 10 15 20

1/8" = 1'-0"

C

B

C B

C B

C

B

C B

ACS PANEL

ELEC.

PANEL

ELEC.

PANEL

PBB

(2) SS24

TR

/2

/2

(2) SS24

B12-TN3012B12-TN301 3

"x

12"x4"

12"x4"

"x

"x

RACK 1

9 9

13 14

RACK 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:2

:0

A

M

B12-TN301

ENLARGED TELECOM PLANS -

12-12

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B12

1/2" = 1'-0"1

ENLARGED TELECOM PLAN - 12-12

N.T.S.2

TR 12-12 RACK ELEVATION

KEYED NOTES:#

GENERAL NOTES:

TOTAL WAO/DATA DEVICES - BUILDING 12

TR ROOM LEVEL

# OF WAO

PORTS

ACTIVE DATA

WAO PORTS

ACTIVE VOICE

WAO PORTS

TR 12-12 184 19 34

Grand total: 35 184 19 34

PLAN NORTH

1 1 2 3 4 5

1/2" = 1'-0"

FEETSCALE

N.T.S.3

12-12 - POWER ELEVATION AND SCHEMATIC

1. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 1 RU.

2. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 2 RU.

3. PATCH PANEL, 48 PORT, 1 RU

4. ETHERNET SWITCH (GFGI)

5. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETTES, 1 RU

6. SPACE RESERVED FOR RACK MOUNTED POWER EQUIPMENT.

7. ZONE PDU

8. PROVIDE A LOADED 48-PORT PATCH PANEL. PROVIDE 50-PAIR CAT3 CABLE FROM THE

CLOSEST SIGNALS CLOSET AND TERMINATE TO THIS PATCH PANEL. COORDINATE

TERMINATION OF THESE CABLES TO EXTEND THE EXISTING RISER CABLE INTO THE

NEW TR ROOMS. COORDINATE WITH FACILITIES ENGINEERING FOR TIMING, LOCATION

AND RE-LABELING THE RISER AT THE MDF ACCORDING TO THE CURRENT FACILITY

SCHEME.

9. PRIMARY PROTECTOR

10. VERTICAL CABLE MANAGEMENT

11. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND L21-20R

OUTPUT.

12. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24) C13 (6) C19 (6)

5-20R OUTLETS, 208V OUTPUT.

13. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

14. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

15. 30 A, 208 V, 3-PHASE ZONE PDU BASE UNIT -REAR CIRCUITS WITH FOUR NEMA L21-20R

AND SIX NEMA 5-20 OUTLETS AND TWO 10' POWER CORDS TERMINATING IN NEMA

L21-30P.

16. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

17. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

18. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT -REAR CIRCUITS WITH SIX NEMA L21-20R

OUTPUT RECEPTACLES AND TWO 10' POWER CORDS TERMINATING IN HARD-WIRED

JUNCTION BOX.

19. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT TERMINATING IN A

HARD-WIRED JUNCTION BOX.

20. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT TERMINATING IN A

HARD-WIRED JUNCTION BOX.

21. RACK BONDING BUSBAR (R.B.B.) FOR IT EQUIPMENT ONLY. NON-IT EQUIPMENT SHALL

NOT USE THE SAME BONDING BUSBAR.

22. 3/4" AC GRADE TRADE SIZE FIRE-RATED PLYWOOD BACKBOARD PAINTED HIGH-GLOSS

WHITE WITH TWO COATS OF FIRE-RESISTANT PAINT, 8" AFF. (TYP.)

23. SPACE RESERVED FOR BAS EQUIPMENT

PRINT SHEET IN COLOR

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION AND FINAL

LOCATION WITH THE ELECTRICAL AND MECHANICAL DIVISION. REFER TO ELECTRICAL,

MECHANICAL AND PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP, AND ANY OTHER

FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE HILTI SPEED SLEEVE LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO FLOOR PLAN

DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES AND CONDUITS OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 10 00 STRUCTURED

CABLING AND SECTION 27 05 33 CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE DRILLING.

CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE RISER SLEEVES.

REFER TO SECTION 07 84 00 FIRESTOPPING.

7. PHASING OF THE WORK IN THE DATA CENTER IMPACTS WORK IN THE TRS AND

HORIZONTAL CABLING. COORDINATE WORK SCHEDULES WITH THE COR.

8. GOVERNMENT EQUIPMENT WILL BE RELOCATED BY GOVERNMENT IT PERSONNEL.

CONTRACTOR WILL HAVE TECHNICIANS AVAILABLE TO PROVIDE SUPPORT DURING

OUTAGES AND CUT-OVERS. COORDINATE WORK WITH THE COR.

9. CONTRACTOR SHALL PROVIDE CABLE MANAGEMENT FINGERS, AIR DAMS, BAYING

SEAL KITS, CABLE BRUSHES, AND GROMMETS MANUFACTURED AND COMPATIBLE

WITH CABINETS.

10. CONTRACTOR SHALL PROVIDE MTP, FIBER OPTIC TRUNK CABLES FOR SIDE A AND

SIDE B BACKBONE FROM THE DATA CENTER TO EACH TELECOMMUNICATIONS ROOM.

COORDINATE WITH COR.

11. CONTRACTOR SHALL PROVIDE FIBER OPTIC PATCH CABLES FOR SIDE A AND SIDE B

FROM THE FIBER OPTIC DISTRIBUTOR TO EQUIPMENT CABINETS. COORDINATE WITH

COR.

12. CONTRACTOR SHALL VERIFY FIBER OPTIC CABLES MEASUREMENTS PRIOR TO

ORDERING. COORDINATE WITH COR.

13. DEMOLISH ANY EXISTING TELECOMMUNICATIONS DATA DEVICE OUTLETS AND BACK

OFFICE #6

OFFICE #5

OFFICE #4

OFFICE #3

OFFICE #2

OFFICE #1

Room

MED ROOM

TR

ADMIN. OFFICE

H.A.C 110A

STAFF

DATA

ELEC

PAPER SUPPLIES

GROUP ROOM #2

CONFERENCE ROOM

OFFICE

116A TOLILET

HAC

TOLILET

A/C #2

RECEPTION

116C

WAITING AREA

116B

TR 14-122

TELECOM COVERAGE FOR FLOOR

PROVIDED BY TR 14-122

B14-TN301

12"x4"

12"x4"

EX

EX

EX

4 4 4 4 4 4

4 4

4 4

4 4

4 4

OFFICE #6

OFFICE #5

OFFICE #4

OFFICE #3

OFFICE #2

OFFICE #1

Room

MED ROOM

TR

ADMIN. OFFICE

H.A.C 110A

STAFF

DATA

ELEC

PAPER SUPPLIES

GROUP ROOM #2

CONFERENCE ROOM

101 OFFICE

116A TOLILET

HAC

TOLILET

A/C #2

RECEPTION

116C

WAITING AREA

116B

B14-TN301

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:3

:1

A

M

B14-TN110

FIRST LEVEL FLOOR PLANS -

TELECOM

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B14

1/8" = 1'-0"1

FIRST LEVEL OVERALL FLOOR PLAN - TELECOM

1/8" = 1'-0"2

FIRST LEVEL FLOOR PLAN - TELECOM

GENERAL NOTES:

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND

LEGENDS.

2. CONTRACTOR SHALL INSTALL BACKBONE RISER

SLEEVES AND CONDUITS OF THE SIZE AS INDICATED

ON THE PLANS. REFER TO SECTION 27 10 00

STRUCTURED CABLING AND SECTION 27 05 33

CONDUITS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

3. CONTRACTOR SHALL X-RAY CONCRETE FLOOR

BEFORE CORE DRILLING. CONTRACTOR SHALL

COORDINATE WITH THE COR BEFORE BEGINNING

DRILLING.

4. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND

EMPTY SPARE RISER SLEEVES. REFER TO SECTION

07 84 00 FIRESTOPPING.

5. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER

TYPE CABLE TRAY ON THE WALL ABOVE THE

VERTICAL RISER SLEEVES FOR BACKBONE CABLE

SUPPORT AS INDICATED ON THE PLANS. THE CABLE

TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF

CABLES AND CABLE TRAY PLUS 50%.

6. CONTRACTOR SHALL INSTALL CABLE SUPPORTS

SUFFICIENT TO SUPPORT COMMUNICATIONS

CABLES ON THE VERTICAL CABLE TRAY WITHOUT

DAMAGING OR DEFORMING THE CABLE.

7. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE

THERE IS NO CABLE TRAY OR COMMUNICATIONS

CONDUIT UNLESS OTHERWISE NOTED.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

PATCH PANELS IN THE TELECOMMUNICATION ROOM

AS INDICATED ON RACK ELEVATIONS.

9. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED. TESTING

SHALL BE PERFORMED BY THE CONTRACTOR

DURING COMMISSIONING.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

11. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

12. CONTRACTOR SHALL TERMINATE COMMUNICATIONS

CABLES WITH NEW CATEGORY MODULAR JACKS TO

MATCH THE COMMUNICATION CABLE

PERFORMANCE SPECIFICATIONS. NEW MODULAR

JACKS SHALL BE OF THE SAME MANUFACTURER AS

THE FACE PLATES, PATCH PANELS, AND PATCH

CABLES.

13. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

CABLES AND CONNECTIVITY COMPONENTS THAT

ARE OF THE SAME MANUFACTURER, INCLUDING

CABLE, MODULAR JACKS, PATCH PANELS,

FACEPLATES, AND PATCH CABLES.

14. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 05 11.

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

PLAN NORTH

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

5 5 10 15 20

1/8" = 1'-0"

C

B

C B

C B

C

B

C B

SBB

TR

RACK 1

ELEC.

PANEL

ELEC.

PANELACS PANEL

(2) SS24

(2) SS24

4' - 5 3/8" 4' - 5 3/8"

B14-TN301

B14-TN301

12"x4"

18"x4"

"x

"x

12"x4"

RACK 1

9 9

13 14

RACK 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

6 South Old Orchard Ave, Saint Louis, MO 63119 T: 800.404.7677 www.introba.com

B

IM

/2

V

A W e s t P a lm

B e a c h

E H

R M

I n fr a s tr u c tu re U p g ra d e s D e s ig n /5

-7

.B

.T

R

.r v t

/2

/2

:3

:2

A

M

B14-TN301

ENLARGED TELECOM PLANS -

14-122

ELECTRONIC HEALTH RECORD

MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES

WEST PALM BEACH, FL

548-22-700

03/31/23 PR TL

B14

3/4" = 1'-0"1

ENLARGED TELECOM PLAN - 14-122

KEYED NOTES:#

GENERAL NOTES:

N.T.S.2

14-122 - RACK ELEVATIONS

TOTAL WAO/DATA DEVICES - BUILDING 14

TR ROOM LEVEL

# OF WAOs

PORTS

ACTIVE DATA

WAO PORTS

ACTIVE VOICE

WAO PORTS

TR 14-122 Level 1 110 9 3

Grand total: 30 110 9 3

PLAN NORTH

1 1 2 3

3/4" = 1'-0"

FEETSCALE

N.T.S.3

14-122 - POWER ELEVATION AND SCHEMATIC

1. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 1 RU.

2. HORIZONTAL CABLE MANAGER, SINGLE SIDED, 2 RU.

3. PATCH PANEL, 48 PORT, 1 RU

4. ETHERNET SWITCH (GFGI)

5. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETTES, 1 RU

6. SPACE RESERVED FOR RACK MOUNTED POWER EQUIPMENT.

7. ZONE PDU

8. PROVIDE A LOADED 48-PORT PATCH PANEL. PROVIDE 50-PAIR CAT3 CABLE FROM THE

CLOSEST SIGNALS CLOSET AND TERMINATE TO THIS PATCH PANEL. COORDINATE

TERMINATION OF THESE CABLES TO EXTEND THE EXISTING RISER CABLE INTO THE

NEW TR ROOMS. COORDINATE WITH FACILITIES ENGINEERING FOR TIMING, LOCATION

AND RE-LABELING THE RISER AT THE MDF ACCORDING TO THE CURRENT FACILITY

SCHEME.

9. PRIMARY PROTECTOR

10. VERTICAL CABLE MANAGEMENT

11. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND L21-20R

OUTPUT.

12. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24) C13 (6) C19 (6)

5-20R OUTLETS, 208V OUTPUT.

13. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

14. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, THREE-PHASE CIRCUIT,

8.5 FT AFF, COORDINATE INSTALLATION LOCATION WITH CONTRACTOR.

15. 30 A, 208 V, 3-PHASE ZONE PDU BASE UNIT -REAR CIRCUITS WITH FOUR NEMA L21-20R

AND SIX NEMA 5-20 OUTLETS AND TWO 10' POWER CORDS TERMINATING IN NEMA

L21-30P.

16. SIDE-A POWER, L21-30R…