Attachment 18 – FA488721R0003
Luke Air Force Base
Fire Alarm/Mass Notification System Installation rwm-12/10/2018
Luke Air Force Base Fire Alarm/Mass Notification System Installations
Basic Standard Installation Criteria:
Standardize Fire Alarms Systems in all base facilities.
Fire Alarm System/MNS must be compatible with Monaco BTX-21, BTX-M
Factory train Alarm Maintenance personal on base standard/selected Fire Alarm System.
Establish bench stock for base standard/selected Fire Alarm System.
System design must meet AFI’s, ETL’s, UFC 3-600-01, UFC 4-021-01 (Design/O&M for Mass
Notification Systems), NFPA 70/72 and IBC 2009.
The Fire Alarm Design/MNS is engineered by qualified FPE or NICET level IV personnel.
Factory trained personnel to perform system installation, testing, training, and maintenance.
Mass Notification System (MNS) will provide a Common Intelligibility Scale (CIS) for indoor sound at 0.08 CIS minimum value. An intelligibility voice signal being broadcast will be determined at a distance of no more than 33 ft within the same area.
Fire Alarm initiation will have pull stations (w/ Lexan covers) at all primary exits; monitor all flow switches; smoke/heat detectors (if installed); duct smoke detectors, flame (UVIR) detectors, and monitoring modules. Install smoke detector within 4’ above Fire Alarm Panel.
Fire Alarm Indication will be by the MNS speaker system (voice) and clear strobes.
The MNS sound system will override any fire signals and provide indication of ALERT through amber strobes.
Voice messages can be obtained by the FPO will be per UFC Air Force requirements and have Local Operators Panel(s) with microphone located within a distance determined by the FPO/AHJ, but no further than 200’.
The MNS sound system w/ BTX-M will have (LVN) Live Voice Notification from Fire
Department (ECC) Emergency Communication Center or Base Command Post.
Monaco Transmitting Zones:
Will include; pull stations, smoke/heat detectors, CO detectors, duct detectors, water flow, tampers switches, AEDs, Emergency infrastructure such as (generators, fuel levels, etc.), flame (UVIR) detectors, remote emergency panic buttons;
Contact Fire Dept ECC for proper zoning…
Size of the FACP panel will incorporate the amplifiers and will be mid-size in height, (may require more panels of same height).
Annunciator panel will be installed in facilities with complex configurations per FPO/AHJ.
FPO/AHJ will have final acceptance of Fire Alarm System Installation
Ronald W. Martin Chief, Fire Prevention 623/856-7421