Attachment 10 - Electrical - Drawings.pdf
PDF 9 MB Posted
- Solicitation number
- 36C77623B0002
About this file
This solicitation is for construction services for the EHRM Infrastructure Upgrades project at the Grand Island VA Medical Center, project number 636-21-701. The solicitation involves renovating and upgrading infrastructure including electrical, mechanical, plumbing and low voltage systems. The construction work will take place in multiple buildings on the medical center campus. The Department of Veterans Affairs Technology Acquisition Center in Austin, Texas issued the solicitation. Responses are due on an unspecified date, with award anticipated for an unspecified future date. Pricing will be fixed price. No set-asides or incumbent are mentioned. Relevant subcontractors and suppliers are to be identified in responses.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
COLOR TEMP CONTROL
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM
CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
J. ALL GENERATORS AND ESS TO BE SECURED PER VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL.
K. PROVIDE PERMANENT NAMEPLATE LABEL FOR PANELBOARDS IDENTIFYING COLOR CODING FOR BRANCH
CIRCUITS IN ACCORDANCE WITH NEC 210.5(c)(1).
L. COORDINATE WITH VA AND SPECIFICATIONS FOR REQUIREMENTS IN SUPPLYING AN ARC FLASH STUDY AND
PROVIDING LABELS FOR ALL NEW EQUIPMENT.
M. FUEL STORAGE TO BE PROVIDED IN COMPLIANCE WITH VA PHYSICAL SECURITY AND RESILIENCY DESIGN
MANUAL.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
LEGEND: (LOW VOLTAGE COORDINATION LEGEND)
CF: CONTRACTOR FURNISHED
CI: CONTRACTOR INSTALLED
OF: OWNER FURNISHED
OI: OWNER INSTALLED
REMARKS: (LOW VOLTAGE COORDINATION LEGEND)
1. FIRE ALARM IS AN EXTENSION OF AN EXISTING SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE
EXISTING SYSTEM.
GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)
A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.
C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.
D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS
OTHERWISE INDICATED.
E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL CABLING PER
SPECIFICATION.
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:0
:5
A M
E-000
ELECTRICAL SYMBOLS, ABBREVIATIONS
AND NOTES
NMT CTB
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
RECEPTACLE - DOUBLE DUPLEX
- CONV
RECEPTACLE - DOUBLE DUPLEX
- EMERGENCY (RED) - CONV
RECEPTACLE - DUPLEX - CONV
RECEPTACLE - DUPLEX - CONV -
GFCI
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - CONV
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - KNOWN
LOAD
RECEPTACLE - DUPLEX - KNOWN
LOAD
ELECTRICAL FIXTURE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
ELECTRICAL GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
EMERGENCY POWER OFF
SWITCH
GENERAL:
PROVIDE STI (SAFETY TECHNOLOGY INTERNATIONAL, INC) MODEL SS2-271PO-EN SURFACE MOUNT EPO SWITCH AND PROTECTIVE COVER, OR PRIOR APPROVED EQUIVALENT, AT APPROXIMATE LOCATIONS INDICATED ON PLANS.
PROVIDE ELECTRICAL COMPONENTS FOR A COMPLETE SYSTEM, INCLUDING ALL NECESSARY RELAYS, TRANSFORMERS, AND SHUNTING DEVICES. COORDINATE BACK BOX AND CONDUIT REQUIREMENTS WITH
MANUFACTURER.
TYPE ‘GEN’, GENERATOR EMERGENCY POWER OFF
PROVIDE 3"x5" OR 4"x4" MINIMUM PLAQUE AT EPO SWITCH WITH ENGRAVED LABEL. COORDINATE LABEL WITH
OWNER. PROVIDE EPO SWITCH TO DISCONNECT PRIME MOVER OF GENERATOR.
POKE THROUGH - POWER GENERAL:
PROVIDE POKE THROUGH AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH POKE THROUGH TYPE. REFER TO PLANS FOR POKE THROUGH DESIGNATION. COORDINATE REQUIREMENTS WITH POKE THROUGH MANUFACTURER. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: BRACKETS, BLANK COVER ASSEMBLIES, MOUNTING FRAMES, ADAPTERS, AND CONCRETE FLOOR ACCESSORIES/OPTIONS. COORDINATE EXACT FINAL LOCATION WITH ARCHITECT, OWNER, OWNER'S FINAL FURNITURE SELECTIONS AND LOCATIONS, AND FINAL FLOOR FINISH SELECTIONS PRIOR TO INSTALLATION. CORE DRILL FLOOR AS REQUIRED TO ACCOMMODATE FLUSH INSTALLATION AND CONCEALMENT OF CONDUITS. CONCEAL ALL CONDUITS ABOVE CEILING AT LEVEL BELOW POKE THROUGH LOCATION AND IN ADJACENT WALL. SUBMIT PRODUCT DATA FOR APPROVAL. COORDINATE INSTALLATION WITH OWNER. COORDINATE DISRUPTION TO EXISTING
SPACE LOCATED BELOW POKE THROUGH LOCATION.
TYPE 'PT1', 4 INCH POWER REACH-IN POKE THROUGH:
PROVIDE WIREMOLD EVOLUTION SERIES MODEL 4ATCP4R POKE THROUGH (OR PRIOR APPROVED EQUIVALENT).
PROVIDE COVER AND FLANGE WITH BRUSHED ALUMINUM FINISH. PROVIDE TWO (2) DUPLEX RECEPTACLES, MOUNTED WITHIN POKE THROUGH. PROVIDE ONE (1) 3/4" CONDUIT TO ELECTRICAL SOURCE FOR ONE (1) 20A 120V
BRANCH CIRCUIT. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION.
RECEPTACLE - NEMA PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA
DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:
•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER
MOUNT TO SIDE OF CABLE TRAY ABOVE TELECOMMUNICATIONS RACK.
FIRE ALARM SYMBOLS
PLAN SYMBOL NAME
DETECTOR - SYSTEM SMOKE -
CEILING
HORN AND STROBE
COMBINATION - WALL
MANUAL PULL STATION
STROBE - CEILING
STROBE - WALL
VOICE/TONE SPEAKER AND
STROBE COMBINATION - CEILING
VOICE/TONE SPEAKER AND
STROBE COMBINATION - WALL
LIGHTING DEVICE SYMBOLS
PLAN SYMBOL NAME
LIGHT SWITCH
LIGHTING DEVICE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
PUSH BUTTON DEVICE SHALL PROVIDE ON/OFF CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA. PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. WHERE NO ZONES ARE INDICATED, PROVIDE CONTROL OF SINGLE ZONE. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM
ADDITIONAL DEVICES.
TYPE ‘D’ – DEVICE SHALL PROVIDE ON/OFF AND MIN/MAX DIMMING CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA, PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM ADDITIONAL DEVICES.
TYPE ‘SC#’ – DEVICE SHALL PROVIDE SCENE CONTROL CAPABLE OF CONTROLLING ALL ZONES IN ROOM BY PRESET SCENES. NUMBER INDICATES QUANTITY OF SCENES TO BE SELECTED AT THIS LOCATION. SEE LIGHTING SCENE
SCHEDULE FOR DESCRIPTION OF DESIRED SCENES.
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
SWITCHED RECEPTACLE
ELECTRICAL MISC SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
LIGHTING CONTROL TAG REFER TO LIGHTING CONTROL SCHEDULE FOR ADDITIONAL INFORMATION.
LIGHTING FIXTURE
SYMBOLS
PLAN SYMBOL NAME
EMERGENCY HATCH
EMERGENCY LIGHTING - WALL
EXIT SIGN - WALL
INDUSTRIAL STRIP LIGHT
TROFFER - RECESSED - 2X2
TROFFER - RECESSED - 2X4
WALL SCONCE FIXTURE
LOW VOLTAGE COORDINATION LEGEND
SYSTEMS
ROUGH-INS &
PATHWAYS
CABLING &
TERMINATIONS
DEVICES &
EQUIPMENT REMARKS
FIRE ALARM CF / CI CF / CI CF / CI 1
ONE LINE SYMBOL
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
DIGITAL METER
DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
GENERATOR
GENERATOR CONNECTION BOX
GROUND BAR
GROUNDING ELECTRODE
KEY INTERLOCK
MOTOR STARTER
PANEL BOARD
SURGE PROTECTIVE DEVICE
SWITCHBOARD/SWITCHGEAR
SWITCHBOARD/SWITCHGEAR -
DOUBLE TUB
TRANSFORMER
UPS PANEL
UTILITY METER
ELECTRICAL EQUIPMENT SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
GENERATOR DOCKING STATION PROVIDE TRYSTAR, INC. DUAL-PURPOSE GENERATOR/LOADBANK DOCKING STATION (OR PRIOR APPROVED EQUIVALENT) WITH VOLTAGE AND CURRENT RATINGS TO MATCH GENERATOR OUTPUT CIRCUIT BREAKER. PROVIDE ENCLOSURE WITH NEMA 3R CONSTRUCTION. PROVIDE WITH INTEGRAL CIRCUIT BREAKER SERVED FROM PERMANENT GENERATOR SOURCE KIRK KEY INTERLOCKED WITH ACCESS DOOR PROTECTING PORTABLE GENERATOR MALE 16 SERIES PANEL MOUNTS (CAM-LOKS). PROVIDE LOAD BANK FEMALE 16 SERIES PANEL MOUNTS (CAM-LOKS). PROVIDE WITH THE FOLLOWING OPTIONS: 2 WIRE AUTO START, BATTERY CHARGER NEMA 5-20 GFCI RECEPTACLE, AND BLOCK HEATER NEMA L5-30 RECEPTACLE. PROVIDE SEPARATE ELECTRICAL CONNECTIONS FROM PANEL GEN-L1, CIRCUITS 2,4 TO SERVE BATTERY CHARGER AND BLOCK HEATER RECEPTACLES.
PROVIDE SIGN ON FRONT OF CABINET STATING THE FOLLOWING:
MAXIMUM GENERATOR CIRCUIT BREAKER SIZE: 1200 AMPS LSIG AND ERMS
GENERATOR SYSTEM IS A SEPARATELY DERIVED SYSTEM. BOND GENERATOR NEUTRAL AND GROUND
ELECTRICAL EQUIPMENT
SYMBOLS
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
BUS DUCT
DISTRIBUTION PANEL
GENERATOR
LOAD CENTER - RECESSED
PANELBOARD - RECESSED
PANELBOARD - SURFACE
SWITCHBOARD
TRANSFORMER - DRY TYPE
UPS CABINET
Revisions: Date:
P
IV
E
P B
P B
C O
A C
A C
A C
P B
P B
P B
S
A C
PB
G
A C
T
S
P
P
S
S
AC
AC
AC
A C
A C
A C
W
AC
AC
S
U
P B
P B
P B
PB
A C
A C
S S S
U
P
IV
K A C
E V
EP
E E
V P
U
U
U
U
U
U
U
U
E U
U E
S
C P
C P
W
S
IG
N
P L A Y G R O U N D
E Q U I P M E N T
P
IC
N
IC
T A B L E
S
IG
N
S
IG
N
BUILDING 1
BUILDING 17
BUILDING 6
BUILDING 8
BUILDING 7
BUILDING 18
BUILDING 5
BUILDING 4
BUILDING 11
BUILDING 2
BUILDING 3
BUILDING 10
A
B
A
B
A
B
C
A
B
C
A
B
A
B
C
D
A
B
C
A
B
C
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a -2
-7
V
A G ra n d I s la n d E
H R
M /6
A .7
.S it e
P la n .M
E P
T R
.r v t
/1
/2
:4
:3
A
M
0-ES100
ELECTRICAL SITE PLAN
NMT CTB
SITE PLAN
1" = 40'-0"1
SITE PLAN ELECTRICAL
SHEET NOTES:
1. ELECTRICAL CONDUITS SHALL FOLLOW THE LOW VOLTAGE
CONDUIT ROUTING. PROVIDE IN-GRADE PULL BOX AT SAME
LOCATIONS AS LOW VOLTAGE, OFFSET SO THEY DO NOT
INTERFERE AND FOLLOW NEC REQUIREMENTS, VA DETAILS AND
PER SPECIFICATIONS. CONDUITS SHALL BE CONCRETE ENCASED
PER VA REQUIREMENTS AND DESIGNED PER SPECIFICATIONS.
CONDUITS SHALL ENTER BUILDING IN CEILING LEVEL OF GROUND
FLOOR AND CONTINUE TO REQUIRED DESTINATION WITHIN
BUILDING. REFER TO ONE-LINE DIAGRAM FOR CONDUIT SIZES,
QUANTITY AND TERMINATION LOCATIONS.
F
LIMITS OF ELECTRICAL
DEMOLITION
LIMITS OF
ELECTRICAL
DEMOLITION
LIMITS OF
ELECTRICAL
DEMOLITION
LIMITS OF
ELECTRICAL
DEMOLITION
LIMITED ELECTRICAL
DEMOLITION
D D
D D D D D
D D D D D
AC7A
E EPO
D
FCU-1
AC7
E
E
E
D D
E
D
UPSCE
E
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
L11
AC8
E
E
A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK.
EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS) WITHIN LIMITS OF DEMOLITION AND NOT SERVING ADJACENT AREAS, SHALL BE REMOVED UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT
MUST REMAIN.
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION.
SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING
CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE
ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE
WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT.
REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.
F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.
MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO
NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF
INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION.
INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT
BECOME INACCESSIBLE DUE TO NEW WORK.
H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND
LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.
J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE
ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.
K. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH
ADJACENT SURFACE.
L. ALL UNLABELED ELECTRICAL DEVICES WITH CIRCUITRY OR DEVICES MODIFIED DURING CONSTRUCTION THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE SHALL BE CIRCUIT TRACED AS NEEDED
WITH A LABEL PROVIDED.
M. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE.
COMPLETELY REMOVE ALL ABANDONED WIRING.
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND
ALL ELECTRICAL DEMOLITION WORK)
ELECTRICAL DEMOLITION GENERAL NOTES:
CRAWL
SPACE
NO.9
ENTRANCE
ROOM
N09A
STORAGE
C22
SOILED
LINEN
S7
CHILLER
RM
G03
CRAWL
SPACE
NO.8
OFFICE
N03
IT
C25
OFFICE
C24
CORR
SGCOR.1
OFFICE
S2
STAIR
NO 4
SPS
LOCKER
RM
C28CORR
SEGCOR.1
SOILED
LINEN
CHUTE
N04
LOCKER
N17
IT
OPERATORS
N08
CORR
NGCOR.1
STAIR
NO-3G
TR
C5
STORAGE
C20
SUPPLY
WAREHOUSE
C18
WAREHOUSE
STORAGE
C12A
CORR
CGCOR.7
STORAGE
C17E
STAIR
NO-6G
MECH-1
C17B-1
LOCKER
RM
N05
IT
STORAGE
N15A
PAHTOLOGY
N06
EQUIR
RM
NE3B
IT
SERVICES
N11
IT
OFFICE
N12
UNISEX
TOILET
N13
WOMENS
LOCKER
N14A
WAREHOUSE
SUPPLY
RM
C8
BIO
MED
SHOP/OFFICE
C9
WAREHOUSE
STORAGE
C12
CANTEEN
STORAGE
C13
STORAGE
C14
STORAGE
C15
ER
SUPPLY
C16
PROSTHETICS
C17A
FITNESS
CENTER
S6
POLICE
OFFICE
S4
RM
S9
OFFICE
N07
STORAGE
N18
MENS
TOILET
C29
WOMENS
TOILET
C30
RESTROOM
C31
EEMS
STORAGE
C10
ARMORY
C23
RM
OFFICE
S8
SPS
DISPATCH
S1
WAREHOUSE
STORAGE
C11A
WAREHOUSE
STORAGE
C11
CRAWL
SPACE
NO.7
MCR
C01
CORR
CGCOR.2
CORR
CGCOR.3
CORR
CGCOR.6
CORR
NEGCOR.1
CORR
CGCOR.4
OFFICE
N02
CORR
CGCOR.1
MENS
TOILET
C7
CANTEEN
OFFICE
C6
CORR
CGCOR.5
CORR
NGCOR.2
EQUIP
RM
NE3A
LAUNDRY
NE3
CORR
NEGCOR.2
OFFICE
NE1
MECH-2
C17B-2
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:0
:2
A M
1-ED100
GROUND FLOOR PLAN - OVERALL -
DEMOLITION - BLDG 1
NMT CTB
1/16" = 1'-0"1
GROUND FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
SHEET NOTES:
1. REFER TO PLANS FOR EQUIPMENT THAT WILL BE DEMOLISHED WITHIN THIS SPACE. REMOVE ELECTRICAL
ASSOCIATED WITH EXISTING MECHANICAL EQUIPMENT THAT IS BEING REMOVED FROM THIS SPACE. REFER
TO ARCHITECTURAL AND TECHNOLOGY DRAWINGS FOR FURTHER INFORMATION ON CONSTRUCTION
PHASING OF THIS ROOM.
2. EXISTING SERVER ROOM DISTRIBUTION PANEL UPSC SHALL REMAIN DURING CONSTRUCTION TO BE USED AS A TEMPORARY SOURCE SERVING THE SERVERS UNTIL THE NEW DISTRIBUTION PANELS CAN BE SET IN PLACE AND ENERGIZED. UPON TRANSFERRING THE EQUIPMENT OFF THIS PANEL, THE PANEL SHOULD BE REMOVED AND PROVIDED TO THE OWNER IF DESIRED. THE BREAKER PREVIOUSLY SERVING THIS PANEL
SHALL BE LABELED AS SPARE WITHIN THE EXISTING GENERATOR DISTRIBUTION PANEL.
LIMITS OF ELECTRICAL DEMOLITION
AC2
E
L11
AC8
E
E
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
CLEAN
UTILITY
SE130
SOILED
UTILITY
SE131
CLEAN
UTILITY
NW109
SOILED
UTILITY
NW110
CLEAN
LINEN
NW112
CORR
NW1C0R.1
STAIR-1
NO-1-1
MALE
TOILET
N105
STAIR
NO-3
LAB
NE109
SOILED
NE105
IMAGING
NE110
OFFICE
N103
CANTEEN
N102
STAIR-6
C34
TR
C100
OFFFICE
C101E
CONFERENCE
RM
C101D
HAC
C109
STORAGE
C111
FREEZER
C102
FREEZER
C102A
FREEZER
C103
STORAGE
C106
LINEN
CLOSET
C105
FREEZER
C112
FREEZER
C113A
IV
DISPENSING
SE103
CONFERENCE
RM
SE106
STAIR-1
NO-4-1
VACANT
SE117
PRESCRIPTIONS
SE115
MD
EXAM
SE118
EXAM
RM
SE119
MD
EXAM
SE120
EXAM
RM
SE121
ELECTRICAL
SE138
TOILET
SE139
EXAM
RM
SE140
OFFICE
SE141
TELEMEDICINE
SE145
EXAM
RM
SE142
EXAM
RM
SE127
VACANT
SE108
EXAM
RM
SE124
CONTROL
SUBSTANCE
SE112
REST
RM
SE111
REST
RM
SE110
ELIGIBILTY
SE133
OFFICE
SE148
NUTRITION
CLINIC
SE134
SOCIAL
WORK
SE147
TOILET
SE147A
EXAM
RM
SE135
OFFICE
SE136
OFFICE
SE137
CORR
SW1C0R.2
FEMALE
TOILET
N104
RECEPTION
NE113
TELEHEALTH
SE144
STAIR
NO-5
CLINICAL
PHARMACIST
NW101
EXAM
RM
NW102
EXAM
RM
NW103
STORAGE
NW105
EXAM
RM
NW106
EXAM
RM
NW107
TOILET
NW107A
EXAM
RM
NW108
TOILET
NW108A
EXAM
RM
NW111
TOILET
NW111A
EXAM
RM
NW113
NURSE
STATION
NW114
EXAM
RM
NW115
EXAM
RM
NW116
CLINICAL
PHARMACIST
NW117
PATIENT
EDUCATION
N107
SUPPLY
NE104
OFFICE
NE106
HAC
NE108
OFFICE
N114
OFFICE
N115
WOMENS
TOILET
C104
MALE
TOILET
C107
WASH
RM/HAC
C110
VEG
RM
C101E
CHIEF
PHARMACY
SE107
OFFICE
SE109
MD
EXAM
SE125
MD
EXAM
SE126
MD
EXAM
SE143
AMBULANCE
ENTRANCE
SE156
CONFERENCE
RM
SE155
TOILET
SE153A
MINOR
TREATMENT
SE153
SOCIAL
WORKER
SE152
TOILET
SE152A
TRIAGE
SE151
HAC
SE150
RECEPTION
SW102A
TREATMENT
SW102B
NURSE
STATION
SW103
PROVIDER
STATION
SW104
EXAM
RM
SW105
EXAM
RM
SW106
EXAM
RM
SW107
EXAM
RM
SW109
EXAM
RM
SW113
EXAM
RM
SW114
TOILET
SW115A
CLINICAL
PHARMACIST
SW116
TOILET
SW117
TOILET
SW118
ADVOCATE
OFFICE
S109
FOOD
STORAGE
C115
INPATIENT
PHARMACY
SE102
OUTPATIENT
PHARMACY
SE114
ACTIVE
STORAGE
SE113
PASSAGE
SE105
WOMENS
TOILET
S110
WAITING
N112 VENDING
N118
TREATMENT
NE103
TREATMENT
NE112
CORR
NE1COR.1
TREATMENT
NE111
NURSE
SE128
CASHIER
N117
OFFICE
N116
LOBBY
CORR
C1C0R.2
CORR
C1C0R.1
CORR
C1C0R.4
CORR
C1C0R.3 PATIENT
RECIEVING
SE116
CORR
SE1COR.1
CORR
SW1C0R.1
LOBBY
S1C0R.3
OFFICE
NE107
CORR
S1C0R.2
CORR
S1COR.1
MALE
TOILET
S111
EXAM
RM
NW104
OFFICE
N116
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:0
:2
A M
1-ED101
FIRST FLOOR PLAN - OVERALL -
ELECTRICAL - DEMOLITION - BLDG 1
NMT CTB
1/16" = 1'-0"1
FIRST FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
EXAM
NE207
EXAM
NE208
EXAM
NE203
STORAGE
NE209
STAFF
NE210
SUPPLY
NE211
TOILET
NE212A
STORAGE
NW211
PROCED
NE212
HAC
N209
STORAGE
N213
STORAGE
S209
WOMENS
TOILET
SE206
RESTROOM
C221
CLEAN
LINEN
C217
STORAGE
C213
OFFICE
C208
VOL
SVS
KITCHEN
C203B
STORAGE
C202A
TR
C201
HVAC
S205
ELECTRICAL
SE202
MENS
TOILET
SE203
TOILET
SW206
CORR
NW2COR.1
TOILET
SW201A
ULTRASOUND
SW201
SOILED
UTILITY
S210
AUDIOLOGY
N203
MENS
RESTROOM
N215
AUDIIOLOGY
OFFICE
NW201
AUDIOLOGY
EXAM
NW202
AUDIOLOGY
NW203
STAIR-2
NO-1-2
TREATMENT
RM
NW205B
TREATMENT
RM
NW206
TOILET
NW207A
TREATMENT
RM
NW207
EXAM
NW208
EXAM
NW209
EXAM
NW210
EXAM
N204
EXAM
N205
EXAM
N206
EXAM
N207
STAIR
SE157
SOILED
HOLD
NE201
PROCED
NE202
EXAM
NE204
EXAM
NE205
LINEN
NE206
EXAM
N210
EXAM
N211
WOMENS
RESTROOM
N214
CHAPLAIN
C201
CHAPEL
C202
CHAPLIN
C202B
OFFICE
C210
OFFICE
C211
STAIR
NO-7
MECH
C220
RECREATIONAL
HALL
C203
STAIR
NO-62
THERAPY
S204
LAB
STORAGE
SE201A
OFFICE
SE207
STAIR-2
NO-4-2
LAB
STORAGE
S207
MECH
SW202
TOILET
SW203
X-RAY
SW204
X-RAY
SW207
BREAK
RM
SW210
STAIR-1
NO-2-1
X-RAY
SW211
VASCULAR
PROCEDURE
RM
SW212
CHECKING
SW213
EQUIPMENT
SOTRAGE
S211A
OFFICE
S211
GAIT
RM
S212
OFFICE
SE208
CONFERENCE
RM
S206A
LOCKER
S206
OFFICE
NW205
OFFICE
S202
KITCHEN
S203A
TREATMENT
S203
CORR
C2CO2.2
CORR
C2COR.1
WAITING
S208
CORRIDOR
N2COR.2
CORR
NE2COR.1
CORR
N2COR.1
CORR
C2CO2.3
CORR
C2CO2.4
CORR
C2CO2.5
CORR
C2CO2.7
CORR
C2CO2.6
CORR
SW2COR.1
WAITING
SW213A
CORR
SE2COR.1
CORRIDOR
S2COR.1
LAB
SE201
CORR
SE2COR.2
OFFICE
C212
STORAGE
C222
PT
RM
C214
DW
S201
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:0
:3
A M
1-ED102
SECOND FLOOR PLAN - OVERALL -
ELECTRICAL - DEMOLITION - BLDG 1
NMT CTB
1/16" = 1'-0"1
SECOND FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION - BLDG1
FCU-1
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
SUPPLY
RM
SW312
UNISEX
TOILET
S312
CORR
SE3COR.2
DUMB-
WAITER
S301
UNISEX
TOILET
C320
MENS
TOILET
C308
OXYGEN
STORAGE
C305B
OXYGEN
STORAGE
NW312
LAUNDRY
C304
UNISEC
TOILET
N312
TOILET
N307
FAMILY
RM
NE302
2-BED
NE304
2-BED
NE305
MEDS
NE310
CORR
NE3COR.2
SOILED
UTILITY
S314
Room
N314
TR
C306
SUPV
OFFICE
N302
HSKP
C305
SPD
C301
2-BED
N317
2-BED
N316
1-BED
NW311
Room
NW309
STAIR
SE163
2-BED
NW307
2-BED
NW305
2-BED
NW304
2-BED
NW303
2-BED
NW302
2-BED
N311
PATIENT
LOUNGE
N310
STAIR
SE164
2-BED
NE308
2-BED
NE307
STORAGE
NE306
CLEAN
STORAGE
N306
TUB/SHOWER
N305
1-BED
N304
1-BED
N303
WOMENS
TOILET
C307
NURSE
OFFICE
C309
STAFF
LOUNGE
C311
PHYSICIAN/NURSE
OFFICE
C313
SOCIALWORKER
OFFICE
C314
STAIR
NO-
MECH
C315
PHARMACIST
OFFICE
C316
NURSE
MGR
OFFICE
C317
PHYSICIAN
OFFICE
C318
SOCIAL
WORKER
C319
FAMILY
RM
C321
CORR
C3COR.4
NUTRITION
AND
FOOD
C323
ACTIVITIES
RM
C324
REC
THERAPY
C325
CLEAN
LINEN
C326
STAIR
SE161
1-BED
SE302
2-BED
SE304
2-BED
SE305
STORAGE
SE306
2-BED
SE307
1-BED
SE308
MEDS
SE311
STAIR
SE160
PATIENT
LOUNGE
S310
CLC
REHAB
RM
S311
2-BED
SW302
2-BED
SW303
2-BED
SW304
2-BED
SW3052-BED
SW306
2-BED
SW307
STAIR-2
NO-2-2
2-BED
SW309
1-BED
SW311
2-BED
S316
2-BED
S317
2-BED
NW306
1-BED
ISOLATION
S303
1-BED
S304
TUB/SHOWER
S306
CLEAN
STORAGE
S308
CENTRAL
NURSE
C302
1-BED
S302
NURSE
SE310
LIFT
SE309
HAND
WASH
ALCOVE
SE303
CORR
SE3COR.1
NUTRISH
SE301
ALCOVE
S309
HANDWASH
S307
HANDWASH
S315
ALCOVE
S305
OBSERVATION
SW313 NURSE
SW301
LIFT
S313
CORR
SW3COR.1
CORR
C3COR.1
CORR
C3COR.3
CORR
C3COR.2
OBSERVATION
NW313
CORR
CW3COR.1
LIFT
N313
NURSE
NW301
LIFT
NE309
NURSE
SE165
HANDWASH
ALCOVE
NE303
ALCOVE
N309
HANDWASH
N308
CORR
N3COR.1
CORR
NE3COR.1
CORR
S3COR.1
TOILET
C302A
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:0
:3
A M
1-ED103
THIRD FLOOR PLAN - OVERALL -
ELECTRICAL - DEMOLITION - BLDG 1
NMT CTB
1/16" = 1'-0"1
THIRD FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
FCU-1
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
STAIR-3
NO-4-3
STORAGE
SW415
STORAGE
S408
DUMBWAITER
S401
RESTROOM
N415
OFFICE
C404A
BREAK
RM
NE405
OFFICE
NE403
OFFICE
NE401
MEETING
RM
NE400A
MEDICATION
NW401
HOMELESS
CLINIC
C404B
TR
C404C
HOUSEKEEPING
S411
SOILED
LINEN
N404
OFFICE
N416
Room
SE402
Room
SE403
Room
SE404
Room
SE405
Room
SE406
Room
SE407
Room
SE408
GROUP
RM
S409
OFFICE
SW403
THERAPY
RM
SW404
OFFICE
SW405
MH
STORAGE
SW406
PHARMACIST
OFFICE
SW407
OFFICE
SW408
CORR
SW4COR.1
STAIR-1
NO-6-1
EMS
OFFICE
C404
2-BED
N413
LAUNDRY
N412
RECEPTION
OFFICE
N411
TREATMENT
RM
N410
MEETING
RM
NE400B
OFFICE
NE402
SUPPLY
NE404
OFFICE
NE406
STAIR
SE172
DINING
RM
N407
1-BED
NW402
2-BED
NW404
1-BED
NW405
STAIR-3
NO-1-3
1-BED
NW406
1-BED
NW407
CORR
NW4COR.1
1-BED
NW408
1-BED
NW409
1-BED
NW411
1-BED
NW413
1-BED
NW414
HOUSEKEEPING
S412
CONFERENCE
RM
S413
GROUP
RM
S414
WOMENS
TOILET
C401
OFFICE
C402
EXERCISE
RM
C402A
MENS
TOILET
C403
2-BED
N401
2-BED
N402
HOUSEKEEPING
N403
NURSE
OFFICE
SW409
SOCIAL
WORKER
OFFICE
SW410
STAIR-3
NO-2-3
SOCIAL
WORKER
OFFICE
SW411
SOCIAL
WORKER
OFFFICE
SW412
OFFICE
SW413
OFFICE
SW414
OFFICE
SW402
EXAM
S402
OFFICE
S405
RECEPTION
CHECK-IN
S404
WOMAN
RESTROOM
S406
BREAK
RM
S407
OFFICE
N414
Room
SE409
WAITING
N409
CORR
NE4COR.1
CORR
C4COR.1
CORR
C4COR.3
CORR
C4COR.2
CORR
N4COR.1
WOMEN
RESTROOM
S406
Room
SE412
WORK
SE401
CORR
SE4COR.1
CORR
S4COR.1
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:0
:3
A M
1-ED104
FOURTH FLOOR PLAN - OVERALL -
ELECTRICAL - DEMOLITION - BLDG 1
NMT CTB
1/16" = 1'-0"1
FOURTH FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
LIMITS OF ELECTRICAL DEMOLITION
D D
WD
AC6
L21A L21
E
E E
FCU-1
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
BREAK
RM
S502
POLICE
S508
STORAGE
S505A
EMPLOYEE
EDUCATION
STORAGE
SW508
HAC
S511
WOMENS
TOILET
C504
UNION
STORAGE
N503
OFFICE
N504
STAIR
SE175
OFFICE
N513A
HAC
C505A
COMPUTER
TRAINING
RM
AND
CPRS
C505
TR
C506
WOMENS
TOILET
C501
OFFICE
C513B
OFFICE
N513
PIV
RM
S518
STAIR-4
NO-4-4
POLICE
OFFICE
SE501
OFFFICE
SE503
POLICE
OFFICE
SE502
STAIR-2
NO-6-2
CPRS
OFFICE
C505B
OFFICE
N512
SITE-3
CONFERENCE
RM
N511
OFFICE
N508
OFFICE
N507B
STORAGE
N505
UNION
OFFICE
NW505
CORR
NW5COR.1
SITE-5
CONFERENCE
RM
NW504
STORAGE
NW502
EMPLOYEE
HEALTH
EXAM
RM
NW501
PRIMARY
CARE
N502
OFFICE
N501
VACANT
C503A
SITE-2
CONFERENCE
RM
C503
OFFICE
C502 STORAGE
C502A
MENS
TOILET
S516
CLINICAL
DOCUMENTATION
CENTER
S515
OFFICE
S514 STORAGE
S513
OFFICE
SW507
EMPLOYEE
EDUCATION
CLASS
RM
SW505
CORR
SW5COR.1
OFFICE
SW504
OFFICE
SW502
OFFICE
NW507
LACTATION
RM
S501
STORAGE
S503
OFFICE
S505
EXECUTIVE
OFFICE
N510
SITE
MANAGERS
OFFICE
N509
EXTENDED
CARE
S517
CORR
N5COR.1
CORR
NE5COR.1
CORR
C5COR.1
CORR
C5COR.3
CORR
C5COR.2
CORR
SE5COR.1
CORR
S5COR.1
SITE-4
CONFERENCE
RM
S506
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:0
:3
A M
1-ED105
FIFTH FLOOR PLAN - OVERALL - ELECTRICAL
- DEMOLITION - BLDG 1
NMT CTB
1/16" = 1'-0"1
FIFTH FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
1/16" = 1'-0"
Fifth Floor Room Tags - Demo Electrical
A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK.
EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS) WITHIN LIMITS OF DEMOLITION AND NOT SERVING ADJACENT AREAS, SHALL BE REMOVED UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT
MUST REMAIN.
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION.
SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING
CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE
ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE
WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT.
REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.
F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.
MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO
NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF
INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION.
INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT
BECOME INACCESSIBLE DUE TO NEW WORK.
H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND
LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.
J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE
ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND
ALL ELECTRICAL DEMOLITION WORK)
ELECTRICAL DEMOLITION GENERAL NOTES:
A
B
C
1 2
IT PANEL
E
LIMITS OF ELECTRICAL DEMOLITION
D
DD
D
R
E
CRAWL
SPACE
STAIR
3A
BASEMENT
JAN/ELEC
CLOSET
3D
TLT
2B
TLT
3B
STAIR
2A
CRAWL
SPACE
BASEMENT
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:4
:5
A M
3-ED101
BASEMENT FLOOR PLANS - ELECTRICAL -
DEMOLITION - BLDG 3
NMT CTB
SHEET NOTES:
1. PRESERVE EXISTING FIRE ALARM PANEL AND EQUIPMENT ON THIS WALL DURING DEMOLITION. RELOCATE
FIRE ALARM BOX TO NEW WALL ONCE IT HAS BEEN INSTALLED AND ENSURE FIRE ALARM SYSTEM REMAINS OPERATIONAL DURING RENOVATION. COORDINATE REQUIREMENTS WITH EXISTING FIRE ALARM VENDOR
PRIOR TO DEMOLITION IN THIS AREA.
1/4" = 1'-0"1
BASEMENT FLOOR PLAN - ELECTRICAL - DEMOLITION
EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS) WITHIN LIMITS OF DEMOLITION AND NOT SERVING ADJACENT AREAS, SHALL BE REMOVED UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT
MUST REMAIN
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION.
SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING
CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE
ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE
WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT.
REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.
F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.
MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO
NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF
INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION.
INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT
BECOME INACCESSIBLE DUE TO NEW WORK.
H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND
LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.
J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE
ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND
ALL ELECTRICAL DEMOLITION WORK)
ELECTRICAL DEMOLITION GENERAL NOTES:
A
1 2
B
C
LIMITS OF ELECTRICAL DEMOLITION
D
DR
E
E
E
D1
CRAWL
SPACE
TLT
BASEMENT
TR
JAN/ELEC
CLOSET
BASEMENT
TLT
CRAWL
SPACE
A
1 2
B
C
OFFICE
114 115 116
OFFICE
CLOSET
TLT
KITCHEN
CONFERENCE
VEST
SOILED
UTILITY
CLEAN
EQUIPMENT
AND
CLEAN
SUPPLIES
CLOSET
TLT
VEST
OFFICE
OFFICE
CLEAN
EQUIPMENT
STORAGE
EQUIPMENT
REPAIR
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/1
/2
:1
:5
A M
4-ED101
BASEMENT AND GROUND FLOOR PLAN -
ELECTRICAL - DEMOLITION - BLDG 4
NMT CTB
SHEET NOTES:
1. EXISTING ELECTRICAL PANEL SHALL REMAIN UNTIL NEW PANEL IS ENERGIZED AND EXISTING FEEDS CAN BE
MOVED OVER TO NEW PANEL. SEE ONE-LINE FOR ADDITIONAL INFORMATION.
2. REMOVE ALL EXISTING ELECTRICAL DEVICES AND CONDUIT ALONG WALL THAT WILL BE DEMOLISHED.
COORDINATE WITH LOW VOLTAGE DRAWINGS FOR EQUIPMENT TO BE RELOCATED TO NEW WALL OF IT
ROOM.
1/4" = 1'-0"1
BASEMENT FLOOR PLAN - ELECTRICAL - DEMOLITION
1/4" = 1'-0"2
GROUND FLOOR PLAN - ELECTRICAL - DEMOLITION
DATA/COMMUNICATION SYSTEMS) WITHIN LIMITS OF DEMOLITION AND NOT SERVING ADJACENT AREAS, SHALL BE REMOVED UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT
MUST REMAIN
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION.
SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING
CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE
ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE
WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT.
REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.
F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.
MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO
NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF
INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION.
INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES.
This is the start of the file's text. The full file is on GovTribe.