ADD 1 - 05 ME - ME Drawings Add 01.pdf

PDF 6 MB Posted

Attached to
EHRM Infrastructure Construction Grand Island Project #636-21-701
Solicitation number
36C77623B0002
Issued by

About this file

This document package includes construction drawings and specifications for an infrastructure upgrade project at the Grand Island VA Medical Center in Grand Island, Nebraska. The project involves upgrades to mechanical, electrical, and plumbing systems across multiple buildings, including replacement of ductwork, piping, lighting fixtures, and installation of new generators and switchgear. The construction work includes upgrades to HVAC, plumbing, fire protection and electrical systems. The related federal contract opportunity is solicitation number 36C77623B0002 for the EHRM Infrastructure Construction Grand Island Project #636-21-701, issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The solicitation seeks construction services for the infrastructure upgrades depicted in the drawings and specifications provided.

View the file

Other files

File Type Posted
36C77623B0002 0004 Amendment - Bid Opening and Wage Rates.pdf PDF
Attachment 15 - Construction Wage Rates - Hall 01-13-2022.pdf PDF
ADD 1 - 01 Reports - 1947 Original Construction A2.pdf PDF
Alesia Addendum 1.pdf PDF
ADD 1 - 02 Project Manual - 07 40 00 - ROOFING AND SIDING PANELS - Addendum 1.pdf PDF
ADD 1 - 03 Architectural - A-701.pdf PDF
ADD 1 - 01 Reports - Geotechnical Report 20220114 TD2.pdf PDF
ADD 1 - 02 Project Manual - 09 06 00 - SCHEDULE FOR FINISHES - Addendum 1.pdf PDF
ADD 1 - 03 Architectural - 19-A-102.pdf PDF
ADD 1 - 02 Project Manual - 26 32 13 - ENGINE GENERATORS - Addendum 1.pdf PDF
36C77623B0002 Amendment 0003 - Addendum 1.pdf PDF
ADD 1 - 02 Project Manual - 00 01 10 - TABLE OF CONTENTS - Addendum 1.pdf PDF
ADD 1 - 03 Architectural - A-601.pdf PDF
ADD 1 - 01 Reports - HAZMAT Report GI VA EHRM 01-10-22.pdf PDF
SES Addendum 1.pdf PDF
ADD 1 - 03 General - GI002.pdf PDF
ADD 1 - 03 Architectural - 19-A-201.pdf PDF
ADD 1 - 04 Civil - C3.0.pdf PDF
ADD 1 - 04 Civil - C2.0.pdf PDF
ADD 1 - 01 Reports - 1947 Original Construction S3.pdf PDF
36C77623B0002 Grand Island EHRM - Technical Questions and Answers.pdf PDF
36C77623B0002 0001 IFB Amendment - Grand Island.pdf PDF
Site Visit Sign-in Sheet - Grand Island.pdf PDF
Questions - 36C77623B0002 Grand Island.pdf PDF
Attachment 9 - Mechanical - Drawings.pdf PDF
Attachment 5 - Hazardous Materials - Drawings.pdf PDF
Attachment 16 - Site Visit Instructions.pdf PDF
Attachment 4 - Life Safety - Drawings.pdf PDF
Attachment 1 - Specifications 1.pdf PDF
Attachment 6 - Civil - Drawings.pdf PDF
Attachment 12 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 13 - Limitations on Subcontracting - Construction.pdf PDF
Attachment 15 - Construction Wage Rates - Hall 09-02-2022.pdf PDF
Attachment 11 - Technology - Drawings.pdf PDF
Attachment 2 - Specifications 2.pdf PDF
Attachment 14 - Contractor Safety - Environmental Form.pdf PDF
36C77623B0002_1.pdf PDF
Attachment 10 - Electrical - Drawings.pdf PDF
Attachment 7 - Structural - Drawings.pdf PDF
Attachment 8 - Architectural - Drawings.pdf PDF
Attachment 3 - Drawings Sheet Index.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/8" = 1'-0"

ENLARGED PIPE BASEMENT FLOOR PLAN - MECHANICAL

Revisions: Date:

ADDENDUM 1 01/03/2023

A

2 3

B

B

C

2 3

BUILDING 6

BUILDING 8

UNDERGROUND

FUEL STORAGE

CDCD

CDCD

72x60 UP

CDCD

CDCD

CDCD

CDCD

UH-3

UH-1 UH-2

UH-4

UH-5

P-1

SSIU-19

SSOU-19

F-1

20x20 EA

4" ST

4" SO

4" UP

4" UP

A B C

GENERATOR

ROOM

19-G01

SWITCHGEAR

ROOM

19-G02

TRUE

NORTH

PLAN

NORTH

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

636A-21-701

09/02/2022

EHRM INFRASTRUCTURE

UPGRADES

GRAND ISLAND, NE

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

IMEG Corp.

2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324

Thompson, Dreessen & Dorner, Inc.

10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

Shaffer Stevens & Schaap P.C.

1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698

CONSTRUCTION

DOCUMENTS

3 4

10 11

6 191

KEYPLAN

09/02/2022

B

IM

/2

-1 a

-2

-7

V

A G ra n d I s la n d

E H

R M

/6

A

.7

.B

.M E

P T

R

.r v t

/6

/2

:1

:4

A

M

19-M101

GROUND FLOOR PLAN - MECHANICAL -

BLDG 19

JMM PHV

1/8" = 1'-0"1

GROUND FLOOR PLAN - MECHANICAL

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

SHEET NOTES:

1. PROVIDE ONE 8' x 10' INTAKE DAMPER IN LOUVERED OPENING.

2. 8' x 10' x 1'-4" DOUBLE WALL, INSULATED SHEET METAL PLENUM.

3. PROVIDE 10’ X 10’ WIDE EXHAUST LOUVER. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

4. PROVIDE 10’ X 10’ WIDE X 1’-4” DEEP DOUBLE WALL, INSULATED SHEET METAL PLENUM. PROVIDE 4’ x 2’ WIDE

BYPASS LOW LEAKAGE DAMPER ON FACE OF 10’ X 10’ PLENUM. REFER TO CONTROL SEQUENCE FOR

ADDITIONAL INFORMATION ON OPERATION.

5. EMERGENCY GENERATOR EXHAUST MUFFLER, DISK TYPE WITH 10 INCH BOTTOM INLET AND 10 INCH SIDE OUTLET. ROUTE 10 INCH PIPE INLET TO GENERATOR AND REDUCE AT GENERATOR AS NECESSARY TO CONNECT TO GENERATOR FLEX CONNECTION. ROUTE 10 INCH DISCHARGE AS SHOWN AND REDUCE TO 8 INCH FOR DISCHARGE THROUGH WALL THIMBLE AS INDICATED. REFER TO SPECIFICATION 26 32 13 FOR

PERFORMANCE AND CONSTRUCTION REQUIREMENTS.

6. PROVIDE 6’ X 5’ SHEET METAL DUCT CONNECTION INTO LOUVERED PENTHOUSE INTAKE WITH LOW LEAKAGE OPPPOSED BLADE MOTORIZED DAMPERS. PLAN NORTH DAMPER SHALL BE 56" x 60" AND SOUTH DAMPER SHALL BE 16" x 60". REFER TO CONTROL SEQUENCE FOR ADDITIONAL INFORMATION ON OPERATION.

7. PROVIDE 5,000 GALLON, 8’ DIAMETER, DOUBLE WALL FUEL OIL STORAGE TANK WITH CONCRETE BALAST, FILL, VENT AND DIPTUBE CONNECTIONS. 4 FOOT DEPTH OF COVER. REFER TO DETAIL 4 ON SHEET M500 FOR

MORE DETAILS.

8. PROVIDE 1 INCH DOUBLE WALL FUEL OIL SUPPLY AND RETURN PIPE WITH DOUBLE WALL CONTAINMENT, LEAK DETECTION AND CATHODIC PROTECTION.

9. PROVIDE DUPLEX POSITIVE DISPLACEMENT FUEL OIL PUMPS. MINIMUM CAPACITY 2 GPM.

10. ROUTE 2 INCH VENT LINE FROM FUEL OIL TANK UNDERGROUND TO EXTERIOR OR BUILDING. ROUTE PIPE UP

SIDE OF BUILDING AND END WITH GOOSENECK A MINIMUM OF 12 FEET ABOVE GRADE.

11. FILL CONNECTION WITH SPILL CONTAINMENT AND CONCRETE CURB. PROVIDE 4 INCH, UNDERGROUND

DOUBLE WALL FILL LINE. BURY A MINIMUM OF 24 INCHES.

12. PROVIDE 4" DOWNSPOUT NOZZLE, JR SMITH 1770 OR EQUAL FOR STORM AND OVERFLOW DRAINAGE.

13. PROVIDE 4" ROOF DRAIN AND OVERFLOW DRAIN ON ROOF ABOVE.

GENERAL NOTES:

Revisions: Date:

ADDENDUM 01 01/03/2023

M500

NO SCALE

NO SCALENO SCALE NO SCALE

Revisions: Date:

1/4" = 1'-0"

ELECTRICAL ABBREVIATIONS

ABBREVIATION DESCRIPTION

REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.

MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)

AMPERE

AMPERE FRAME

ABOVE FINISHED FLOOR

ALUMINUM

AMPERE TRIP

CEILING

CIRCUIT BREAKER

COLOR TEMP CONTROL

COPPER

DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)

DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)

EXISTING

ELECTRICALLY OPERATED

ENERGY REDUCING MAINTENANCE SWITCH

FUSE

FULL LOAD AMPS

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT ALARM

GROUND FAULT PROTECTION

HORSEPOWER

KILOAMPERE INTERRUPTING CAPACITY

KILOVOLT AMPERE

KILOWATT

MAXIMUM

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MINIMUM

MAIN LUGS ONLY

MANUALLY OPERATED

NORMALLY CLOSED

NON-FUSED

NOT IN CONTRACT

NORMALLY OPEN

POLES

PARTIAL

RELOCATE

SHORT CIRCUIT CURRENT RATING

SURGE PROTECTIVE DEVICE

SHUNT TRIP

TYPICAL

UNLESS NOTED OTHERWISE

VOICE

WALL PHONE

WIRE

WEATHER RESISTANT

TRANSFORMER

ZONE SELECTIVE INTERLOCKING

A

AF

AFF

AL

AT

C

CB

CCT

CU

D

D

E

EO

ERMS

F

FLA

G, GFCI

GFA

GFP

HP

KAIC

KVA

KW

MAX

MCA

MCB

MIN

MLO

MO

NC

NF

NIC

NO

P

PART

R

SCCR

SPD

ST

TYP

UNO

V

W

W

WR

XFMR

ZSI

A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.

RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG

CONDUCTORS.

B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE

SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.

C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM

CERTIFICATE.

D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL

COST TO THE OWNER.

E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR

INSTALLED DEVICES.

F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS

ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND

PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.

G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL

NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME

INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.

H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE

ENTIRE CIRCUIT LENGTH.

I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN

CABLING.

J. ALL GENERATORS AND ESS TO BE SECURED PER VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL.

K. PROVIDE PERMANENT NAMEPLATE LABEL FOR PANELBOARDS IDENTIFYING COLOR CODING FOR BRANCH

CIRCUITS IN ACCORDANCE WITH NEC 210.5(c)(1).

L. COORDINATE WITH VA AND SPECIFICATIONS FOR REQUIREMENTS IN SUPPLYING AN ARC FLASH STUDY AND

PROVIDING LABELS FOR ALL NEW EQUIPMENT.

M. FUEL STORAGE TO BE PROVIDED IN COMPLIANCE WITH VA PHYSICAL SECURITY AND RESILIENCY DESIGN

MANUAL.

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

ELECTRICAL GENERAL NOTES:

LEGEND: (LOW VOLTAGE COORDINATION LEGEND)

CF: CONTRACTOR FURNISHED

CI: CONTRACTOR INSTALLED

OF: OWNER FURNISHED

OI: OWNER INSTALLED

REMARKS: (LOW VOLTAGE COORDINATION LEGEND)

1. FIRE ALARM IS AN EXTENSION OF AN EXISTING SIMPLEXGRINNELL SYSTEM. NEW DEVICES SHALL FUNCTION AS AN

EXTENSION OF THE EXISTING SYSTEM.

GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)

A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.

B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.

C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.

D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS

OTHERWISE INDICATED.

E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL CABLING PER

SPECIFICATION.

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

636A-21-701

09/02/2022

EHRM INFRASTRUCTURE

UPGRADES

GRAND ISLAND, NE

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

IMEG Corp.

2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324

Thompson, Dreessen & Dorner, Inc.

10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

Shaffer Stevens & Schaap P.C.

1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698

CONSTRUCTION

DOCUMENTS

09/02/2022

B

IM

/2

-1 a

-2

-7

V

A G ra n d I s la n d

E H

R M

/6

A

.7

.B

.M E

P T

R

.r v t

/5

/2

:3

:0

A M

E000

ELECTRICAL SYMBOLS, ABBREVIATIONS

AND NOTES

NMT CTB

ELECTRICAL FIXTURE

SYMBOLS

PLAN SYMBOL NAME

RECEPTACLE - DOUBLE DUPLEX

- CONV

RECEPTACLE - DOUBLE DUPLEX

- EMERGENCY (RED) - CONV

RECEPTACLE - DUPLEX - CONV

RECEPTACLE - DUPLEX - CONV -

GFCI

RECEPTACLE - DUPLEX -

EMERGENCY (RED) - CONV

RECEPTACLE - DUPLEX -

EMERGENCY (RED) - KNOWN

LOAD

RECEPTACLE - DUPLEX - KNOWN

LOAD

ELECTRICAL FIXTURE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

ELECTRICAL GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

EMERGENCY POWER OFF

SWITCH

GENERAL:

PROVIDE STI (SAFETY TECHNOLOGY INTERNATIONAL, INC) MODEL SS2-271PO-EN SURFACE MOUNT EPO SWITCH AND PROTECTIVE COVER, OR PRIOR APPROVED EQUIVALENT, AT APPROXIMATE LOCATIONS INDICATED ON PLANS.

PROVIDE ELECTRICAL COMPONENTS FOR A COMPLETE SYSTEM, INCLUDING ALL NECESSARY RELAYS, TRANSFORMERS, AND SHUNTING DEVICES. COORDINATE BACK BOX AND CONDUIT REQUIREMENTS WITH

MANUFACTURER.

TYPE ‘GEN’, GENERATOR EMERGENCY POWER OFF

PROVIDE 3"x5" OR 4"x4" MINIMUM PLAQUE AT EPO SWITCH WITH ENGRAVED LABEL. COORDINATE LABEL WITH

OWNER. PROVIDE EPO SWITCH TO DISCONNECT PRIME MOVER OF GENERATOR.

POKE THROUGH - POWER GENERAL:

PROVIDE POKE THROUGH AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH POKE THROUGH TYPE. REFER TO PLANS FOR POKE THROUGH DESIGNATION. COORDINATE REQUIREMENTS WITH POKE THROUGH MANUFACTURER. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: BRACKETS, BLANK COVER ASSEMBLIES, MOUNTING FRAMES, ADAPTERS, AND CONCRETE FLOOR ACCESSORIES/OPTIONS. COORDINATE EXACT FINAL LOCATION WITH ARCHITECT, OWNER, OWNER'S FINAL FURNITURE SELECTIONS AND LOCATIONS, AND FINAL FLOOR FINISH SELECTIONS PRIOR TO INSTALLATION. CORE DRILL FLOOR AS REQUIRED TO ACCOMMODATE FLUSH INSTALLATION AND CONCEALMENT OF CONDUITS. CONCEAL ALL CONDUITS ABOVE CEILING AT LEVEL BELOW POKE THROUGH LOCATION AND IN ADJACENT WALL. SUBMIT PRODUCT DATA FOR APPROVAL. COORDINATE INSTALLATION WITH OWNER. COORDINATE DISRUPTION TO EXISTING

SPACE LOCATED BELOW POKE THROUGH LOCATION.

TYPE 'PT1', 4 INCH POWER REACH-IN POKE THROUGH:

PROVIDE WIREMOLD EVOLUTION SERIES MODEL 4ATCP4R POKE THROUGH (OR PRIOR APPROVED EQUIVALENT).

PROVIDE COVER AND FLANGE WITH BRUSHED ALUMINUM FINISH. PROVIDE TWO (2) DUPLEX RECEPTACLES, MOUNTED WITHIN POKE THROUGH. PROVIDE ONE (1) 3/4" CONDUIT TO ELECTRICAL SOURCE FOR ONE (1) 20A 120V

BRANCH CIRCUIT. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION.

RECEPTACLE - NEMA PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA

DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:

•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER

MOUNT TO SIDE OF CABLE TRAY ABOVE TELECOMMUNICATIONS RACK.

FIRE ALARM SYMBOLS

PLAN SYMBOL NAME

DETECTOR - SYSTEM SMOKE -

CEILING

HORN AND STROBE

COMBINATION - WALL

MANUAL PULL STATION

STROBE - CEILING

STROBE - WALL

VOICE/TONE SPEAKER AND

STROBE COMBINATION - CEILING

VOICE/TONE SPEAKER AND

STROBE COMBINATION - WALL

LIGHTING DEVICE SYMBOLS

PLAN SYMBOL NAME

LIGHT SWITCH

LIGHTING DEVICE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

PUSH BUTTON DEVICE SHALL PROVIDE ON/OFF CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA. PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. WHERE NO ZONES ARE INDICATED, PROVIDE CONTROL OF SINGLE ZONE. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM

ADDITIONAL DEVICES.

TYPE ‘D’ – DEVICE SHALL PROVIDE ON/OFF AND MIN/MAX DIMMING CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA, PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM ADDITIONAL DEVICES.

TYPE ‘SC#’ – DEVICE SHALL PROVIDE SCENE CONTROL CAPABLE OF CONTROLLING ALL ZONES IN ROOM BY PRESET SCENES. NUMBER INDICATES QUANTITY OF SCENES TO BE SELECTED AT THIS LOCATION. SEE LIGHTING SCENE

SCHEDULE FOR DESCRIPTION OF DESIRED SCENES.

ELECTRICAL MISC SYMBOLS

PLAN SYMBOL NAME

BRANCH CIRCUIT CONCEALED IN

CEILING OR WALL

BRANCH CIRCUIT CONCEALED IN

FLOOR OR BELOW GRADE

CLEARANCE SPACE

CONDUIT BREAK

CONDUIT DOWN

CONDUIT STUB-OUT

CONDUIT UP

HOMERUN TO PANEL

G = GFCI CIRCUIT

(PART) = PARTIAL CIRCUIT

SWITCHED RECEPTACLE

ELECTRICAL MISC SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

LIGHTING CONTROL TAG REFER TO LIGHTING CONTROL SCHEDULE FOR ADDITIONAL INFORMATION.

LIGHTING FIXTURE

SYMBOLS

PLAN SYMBOL NAME

EMERGENCY HATCH

EMERGENCY LIGHTING - WALL

EXIT SIGN - WALL

INDUSTRIAL STRIP LIGHT

TROFFER - RECESSED - 2X2

TROFFER - RECESSED - 2X4

WALL SCONCE FIXTURE

LOW VOLTAGE COORDINATION LEGEND

SYSTEMS

ROUGH-INS &

PATHWAYS

CABLING &

TERMINATIONS

DEVICES &

EQUIPMENT REMARKS

FIRE ALARM CF / CI CF / CI CF / CI 1

ONE LINE SYMBOL

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

CONTINUATION

DIGITAL METER

DISCONNECT SWITCH

ENCLOSED CIRCUIT BREAKER

GENERATOR

GENERATOR CONNECTION BOX

GROUND BAR

GROUNDING ELECTRODE

KEY INTERLOCK

MOTOR STARTER

PANEL BOARD

SURGE PROTECTIVE DEVICE

SWITCHBOARD/SWITCHGEAR

SWITCHBOARD/SWITCHGEAR -

DOUBLE TUB

TRANSFORMER

UPS PANEL

UTILITY METER

ELECTRICAL EQUIPMENT SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

GENERATOR DOCKING STATION PROVIDE TRYSTAR, INC. DUAL-PURPOSE GENERATOR/LOADBANK DOCKING STATION (OR PRIOR APPROVED EQUIVALENT) WITH VOLTAGE AND CURRENT RATINGS TO MATCH GENERATOR OUTPUT CIRCUIT BREAKER. PROVIDE ENCLOSURE WITH NEMA 3R CONSTRUCTION. PROVIDE WITH INTEGRAL CIRCUIT BREAKER SERVED FROM PERMANENT GENERATOR SOURCE KIRK KEY INTERLOCKED WITH ACCESS DOOR PROTECTING PORTABLE GENERATOR MALE 16 SERIES PANEL MOUNTS (CAM-LOKS). PROVIDE LOAD BANK FEMALE 16 SERIES PANEL MOUNTS (CAM-LOKS). PROVIDE WITH THE FOLLOWING OPTIONS: 2 WIRE AUTO START, BATTERY CHARGER NEMA 5-20 GFCI RECEPTACLE, AND BLOCK HEATER NEMA L5-30 RECEPTACLE. PROVIDE SEPARATE ELECTRICAL CONNECTIONS FROM PANEL GEN-L1, CIRCUITS 2,4 TO SERVE BATTERY CHARGER AND BLOCK HEATER RECEPTACLES.

PROVIDE SIGN ON FRONT OF CABINET STATING THE FOLLOWING:

MAXIMUM GENERATOR CIRCUIT BREAKER SIZE: 1200 AMPS LSIG AND ERMS

GENERATOR SYSTEM IS A SEPARATELY DERIVED SYSTEM. BOND GENERATOR NEUTRAL AND GROUND

ELECTRICAL EQUIPMENT

SYMBOLS

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

BUS DUCT

DISTRIBUTION PANEL

GENERATOR

LOAD CENTER - RECESSED

PANELBOARD - RECESSED

PANELBOARD - SURFACE

SWITCHBOARD

TRANSFORMER - DRY TYPE

UPS CABINET

Revisions: Date:

A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.

CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH

ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.

B. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH

ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE

ARCHITECTURAL DRAWINGS. ROUTE ALL ELECTRICAL BRANCH CIRCUITS AND CONDUITS SPECIFIED, TO COORDINATE WITH OTHER TRADES AND TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, ARRANGE WORK TO INSTALL

PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.

C. REDUNDANT GROUNDING METHODS REQUIRED FOR PATIENT CARE AREAS. REFER TO NEC FOR

REQUIREMENTS AND TO PROJECT SPECIFICATIONS FOR ACCEPTABLE METHODS/APPLICATIONS.

D. GFCI TYPE RECEPTACLES ARE NOTED AS SUCH ON THE PLANS FOR PRICING PURPOSES. HOWEVER, CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE ALL RECEPTACLES INSTALLED WHERE A 6' CORD

LENGTH COULD REACH THE EDGE OF A SINK HAVE GFCI PROTECTION.

E. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.

F. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT

HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

(ELECTRICAL GENERAL NOTES SHALL APPLY TO ALL SHEETS)

POWER GENERAL NOTES:

1-E400

1-E400

1-E400

B-SIDE DIST.A-SIDE DIST.

C R

A C

-1

C R

A C

-2

C R

A C

-3

CSC-UPS-A

CSC-UPS-B

1-E402

TR-1-C6B

TR-1-C6A

1-E402

AC7

CSC-A

CSC-B

AC7A

AC8

L11

48"

SSOU-0GA

SSIU-0GA

SSIU-N02B

SSIU-N02A

E

1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

DD

CC

BB

AA

A

B

C

D

E

F

G

H

IJ

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

ENTRANCE

ROOM

1-N09A

OFFICE

1-NE1

MCR

1-C01

UPS

1-N02

CORR

1-NEGCOR.2

CANTEEN

OFFICE

1-NE0

CORR

1-CGCOR.2

CORR

1-CGCOR.3

CORR

1-CGCOR.1CORR

1-NEGCOR.1

CORR

1-NEGCOR.3

CORR

1-CGCOR.4

CORR

1-CGCOR.5

TR

1-C6

LAUNDRY

1-NE3

FCU-1

SSOU-0GB

SSIU-0GB

SSOU-01A

SSOU-01B

WR

A. LIGHTING CONTROL DEVICES ARE INDICATED WITHOUT CONNECTION TO FIXTURE(S) BEING CONTROLLED.

WITHIN EACH AREA, CONNECT CONTROL DEVICE TO SERVE LIGHT FIXTURE(S) LOCATED WITHIN SAME AREA. WHERE LIGHT FIXTURES ARE INDICATED WITH A SUBSCRIPT LETTER IDENTIFYING INDIVIDUAL LIGHTING CONTROL ZONES, CONTROL DEVICE SERVING AREA WITH MATCHING SUBSCRIPT SHALL

CONTROL CORRESPONDING LIGHT FIXTURES.

B. LIGHTING CONTROL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.

CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH

ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.

C. CONTRACTOR SHALL COORDINATE ALL LIGHTING CONTROL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE ARCHITECTURAL DRAWINGS. COORDINATE ROUTING OF ALL ELECTRICAL BRANCH CIRCUITS AND CONDUIT WITH OTHER TRADES TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, WORK TO INSTALL PANELS IN LOCATIONS

ACCEPTABLE TO ARCHITECT.

D. FIXTURES DESIGNATED 'LS' AND EXIT LIGHTS SHALL BE SERVED FROM A COMMON 20A 120V LIFE SAFETY BRANCH CIRCUIT. EXIT LIGHTS SHALL BE ILLUMINATED 24 HOURS. FIXTURES DESIGNATED 'LS' SHALL BE

SWITCHED BY CONTROLS INDICATED. PROVIDE EMERGENCY LIGHTING CONTROL RELAYS PER

SPECIFICATIONS FOR EMERGENCY LIGHTING OVERRIDE. REFER TO MANUFACTURER'S WIRING DIAGRAMS

FOR INSTALLATION INSTRUCTIONS.

E. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.

(LIGHTING GENERAL NOTES SHALL APPLY TO ALL SHEETS)

LIGHTING GENERAL NOTES:

CRAWL

SPACE

NO.9

STORAGE

C22

SOILED

LINEN

S7

CHILLER

RM

G03

CRAWL

SPACE

NO.8

OFFICE

N03

IT

C25

OFFICE

C24

CORR

SGCOR.1

OFFICE

S2

STAIR

NO 4

SPS

LOCKER

RM

C28CORR

SEGCOR.1

SOILED

LINEN

CHUTE

N04

LOCKER

N17

IT

OPERATORS

N08

CORR

NGCOR.1

STAIR

NO-3G

TR

C5

STORAGE

C20

SUPPLY

WAREHOUSE

C18

WAREHOUSE

STORAGE

C12A

CORR

CGCOR.7

STORAGE

C17E

STAIR

NO-6G

MECH-1

C17B-1

LOCKER

RM

N05

IT

STORAGE

N15A

PAHTOLOGY

N06

EQUIR

RM

NE3B

IT

SERVICES

N11

IT

OFFICE

N12

UNISEX

TOILET

N13

WOMENS

LOCKER

N14A

WAREHOUSE

SUPPLY

RM

C8

BIO

MED

SHOP/OFFICE

C9

WAREHOUSE

STORAGE

C12

CANTEEN

STORAGE

C13

STORAGE

C14

STORAGE

C15

ER

SUPPLY

C16

PROSTHETICS

C17A

FITNESS

CENTER

S6

POLICE

OFFICE

S4

MAIL

RM

S9

OFFICE

N07

STORAGE

N18

MENS

TOILET

C29

WOMENS

TOILET

C30

RESTROOM

C31

EEMS

STORAGE

C10

ARMORY

C23

MAIL

RM

OFFICE

S8

SPS

DISPATCH

S1

WAREHOUSE

STORAGE

C11A

WAREHOUSE

STORAGE

C11

CRAWL

SPACE

NO.7

MCR

C01

CORR

CGCOR.6

MENS

TOILET

C7

CORR

NGCOR.2

EQUIP

RM

NE3A

MECH-2

C17B-2

TRUE

NORTH

PLAN

NORTH

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

636A-21-701

09/02/2022

EHRM INFRASTRUCTURE

UPGRADES

GRAND ISLAND, NE

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

IMEG Corp.

2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324

Thompson, Dreessen & Dorner, Inc.

10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

Shaffer Stevens & Schaap P.C.

1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698

CONSTRUCTION

DOCUMENTS

3 4

10 11

6 191

KEYPLAN

09/02/2022

B

IM

/2

-1 a

-2

-7

V

A G ra n d I s la n d

E H

R M

/6

A

.7

.B

.M E

P T

R

.r v t

/5

/2

:2

:5

A M

1-EP100

GROUND FLOOR PLAN - OVERALL -

ELECTRICAL - BLDG 1

NMT CTB

1/16" = 1'-0"1

GROUND FLOOR PLAN - OVERALL - ELECTRICAL

SHEET NOTES:

1. CONFIRM FINAL OUTLET LOCATION WITH OWNER PRIOR TO ROUGH-IN FOR KEYBOX CONTROLLER POWER.

UTILIZE SPARE 20/1 ESSENTIAL BRANCH CIRCUIT WITHIN PANEL L11.

2. FACILITY PERSONNEL TO PROVIDE AN APPROVED PROCEDURE TO THE STAFF SUPERVISING THE BUILDING THAT UNDERSTAND WHERE TO DE-ENERGIZE THE BREAKERS THAT FEED THE IT EQUIPMENT WITHIN THE

MCR AND CAN RELAY THIS INFORMATION TO EMERGENCY PERSONNEL WHEN REQUIRED. SOURCE

BREAKERS TO ELECTRICAL PANELS WITHIN THE MCR ORIGINATE AT BUILDING 17.

1-E401

SSIU-01A TR-1N118B

TR-1N118A

60"

SSOU-N02B

SSOU-N02A

L11

AC8

WR

AC2

E

1-E402

SSIU-01B

1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

DD

CC

BB

AA

A

B

C

D

E

F

G

H

IJ

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

OFFICE

1-N115 TR

1-N118

OFFICE

1-N117

CASHIER

1-N116

CORR

1-N1COR.1

VOLUNTEER

AREA

1-N121

CORR

1-C1COR.1

LOBBY

1-001

CLEAN

UTILITY

SE130

SOILED

UTILITY

SE131

CLEAN

UTILITY

NW109

SOILED

UTILITY

NW110

CLEAN

LINEN

NW112

CORR

NW1C0R.1

STAIR-1

NO-1-1

MALE

TOILET

N105

STAIR

NO-3

LAB

NE109

SOILED

NE105

IMAGING

NE110

OFFICE

N103

CANTEEN

N102

STAIR-6

C34

TR

C100

OFFFICE

C101E

CONFERENCE

RM

C101D

HAC

C109

STORAGE

C111

FREEZER

C102

FREEZER

C102A

FREEZER

C103

STORAGE

C106

LINEN

CLOSET

C105

FREEZER

C112

FREEZER

C113A

IV

DISPENSING

SE103

CONFERENCE

RM

SE106

STAIR-1

NO-4-1

VACANT

SE117

PRESCRIPTIONS

SE115

MD

EXAM

SE118

EXAM

RM

SE119

MD

EXAM

SE120

EXAM

RM

SE121

ELECTRICAL

SE138

TOILET

SE139

EXAM

RM

SE140

OFFICE

SE141

TELEMEDICINE

SE145

EXAM

RM

SE142

EXAM

RM

SE127

VACANT

SE108

EXAM

RM

SE124

CONTROL

SUBSTANCE

SE112

REST

RM

SE111

REST

RM

SE110

ELIGIBILTY

SE133

OFFICE

SE148

NUTRITION

CLINIC

SE134

SOCIAL

WORK

SE147

TOILET

SE147A

EXAM

RM

SE135

OFFICE

SE136

OFFICE

SE137

CORR

SW1C0R.2

FEMALE

TOILET

N104

RECEPTION

NE113

TELEHEALTH

SE144

STAIR

NO-5

CLINICAL

PHARMACIST

NW101

EXAM

RM

NW102

EXAM

RM

NW103

STORAGE

NW105

EXAM

RM

NW106

EXAM

RM

NW107

TOILET

NW107A

EXAM

RM

NW108

TOILET

NW108A

EXAM

RM

NW111

TOILET

NW111A

EXAM

RM

NW113

NURSE

STATION

NW114

EXAM

RM

NW115

EXAM

RM

NW116

CLINICAL

PHARMACIST

NW117

PATIENT

EDUCATION

N107

SUPPLY

NE104

OFFICE

NE106

HAC

NE108

OFFICE

N114

WOMENS

TOILET

C104

MALE

TOILET

C107

WASH

RM/HAC

C110

VEG

RM

C101E

CHIEF

PHARMACY

SE107

OFFICE

SE109

MD

EXAM

SE125

MD

EXAM

SE126

MD

EXAM

SE143

AMBULANCE

ENTRANCE

SE156

CONFERENCE

RM

SE155

TOILET

SE153A

MINOR

TREATMENT

SE153

SOCIAL

WORKER

SE152

TOILET

SE152A

TRIAGE

SE151

HAC

SE150

RECEPTION

SW102A

TREATMENT

SW102B

NURSE

STATION

SW103

PROVIDER

STATION

SW104

EXAM

RM

SW105

EXAM

RM

SW106

EXAM

RM

SW107

EXAM

RM

SW109

EXAM

RM

SW113

EXAM

RM

SW114

TOILET

SW115A

CLINICAL

PHARMACIST

SW116

TOILET

SW117

TOILET

SW118

ADVOCATE

OFFICE

S109

FOOD

STORAGE

C115

INPATIENT

PHARMACY

SE102

OUTPATIENT

PHARMACY

SE114

ACTIVE

STORAGE

SE113

PASSAGE

SE105

WOMENS

TOILET

S110

WAITING

N112

TREATMENT

NE103

TREATMENT

NE112

CORR

NE1COR.1

TREATMENT

NE111

NURSE

SE128

CORR

C1C0R.2

CORR

C1C0R.4

CORR

C1C0R.3 PATIENT

RECIEVING

SE116

CORR

SE1COR.1

CORR

SW1C0R.1

LOBBY

S1C0R.3

OFFICE

NE107

CORR

S1C0R.2

CORR

S1COR.1

MALE

TOILET

S111

EXAM

RM

NW104

TRUE

NORTH

PLAN

NORTH

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

636A-21-701

09/02/2022

EHRM INFRASTRUCTURE

UPGRADES

GRAND ISLAND, NE

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

IMEG Corp.

2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324

Thompson, Dreessen & Dorner, Inc.

10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

Shaffer Stevens & Schaap P.C.

1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698

CONSTRUCTION

DOCUMENTS

3 4

10 11

6 191

KEYPLAN

09/02/2022

B

IM

/2

-1 a

-2

-7

V

A G ra n d I s la n d

E H

R M

/6

A

.7

.B

.M E

P T

R

.r v t

/5

/2

:3

:0

A M

1-EP101

FIRST FLOOR PLAN - OVERALL -

ELECTRICAL - BLDG 1

NMT CTB

SHEET NOTES:

1. TIE INTO EXISTING EXTERIOR NORMAL BRANCH 20/1 CONVENIENCE CIRCUIT CURRENTLY SERVING THIS AREA. IF THERE IS AN EXISTING WEATHER-RATED GFCI IN THIS AREA, THIS RECEPTACLE WOULD NOT BE

REQUIRED.

2. TIE INTO EXISTING CIRCUIT SERVING EQUIPMENT PRIOR TO IT'S RELOCATION FROM PANEL "K" LOCATED IN THE KITCHEN. CIRCUITS K-3,5,7,9,11, AND 13 PREVIOUSLY SERVED THE VENDING ROOM WHICH IS CONVERTED TO THE NEW IT ROOM. BREAKERS NOT RE-USED, SHOULD BE DE-ENERGIZED AND SCHEDULE

UPDATED TO SPARE.

3. PROVIDE NEW 20/1 CIRCUIT BREAKER IN AVAILABLE SPACE WITHIN EXISTING NORMAL BRANCH PANEL 'AC2'

UNLESS A SPARE 20/1 CIRCUIT BREAKER IS AVAILABLE.

1/16" = 1'-0"1

FIRST FLOOR PLAN - OVERALL - ELECTRICAL

1-E401

SSIU-02A

TR-1-S202B

TR-1-S202A

SSOU-02A

1-E402

ACCU-1ACCU-2ACCU-3

WR

WR

1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

DD

CC

BB

AA

A

B

C

D

E

F

G

H

IJ

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

TREATMENT

1-S203

TR

1-S202

OFFICE

1-S208

CORR

1-C2CO2.2

CORR

1-C2COR.1

CORR

1-C2CO2.3

CORR

1-C2CO2.4

CORR

1-C2CO2.5

CORR

1-C2CO2.7CORR

1-C2CO2.6

CORR

1-SE2COR.1

CORR

1-S2COR.1

SSOU-02B

SSOU-03A

SSIU-02B

SSOU-03B

EXAM

NE207

EXAM

NE208

EXAM

NE203

STORAGE

NE209

STAFF

NE210

SUPPLY

NE211

TOILET

NE212A

STORAGE

NW211

PROCED

NE212

HAC

N209

STORAGE

N213

STORAGE

S209

WOMENS

TOILET

SE206

RESTROOM

C221

CLEAN

LINEN

C217

STORAGE

C213

OFFICE

C208

VOL

SVS

KITCHEN

C203B

STORAGE

C202A

TR

C201

HVAC

S205

ELECTRICAL

SE202

MENS

TOILET

SE203

TOILET

SW206

CORR

NW2COR.1

TOILET

SW201A

ULTRASOUND

SW201

SOILED

UTILITY

S210

AUDIOLOGY

N203

MENS

RESTROOM

N215

AUDIIOLOGY

OFFICE

NW201

AUDIOLOGY

EXAM

NW202

AUDIOLOGY

NW203

STAIR-2

NO-1-2

TREATMENT

RM

NW205B

TREATMENT

RM

NW206

TOILET

NW207A

TREATMENT

RM

NW207

EXAM

NW208

EXAM

NW209

EXAM

NW210

EXAM

N204

EXAM

N205

EXAM

N206

EXAM

N207

STAIR

SE157

SOILED

HOLD

NE201

PROCED

NE202

EXAM

NE204

EXAM

NE205

LINEN

NE206

EXAM

N210

EXAM

N211

WOMENS

RESTROOM

N214

CHAPLAIN

C201

CHAPEL

C202

CHAPLIN

C202B

OFFICE

C210

OFFICE

C211

STAIR

NO-7

MECH

C220

RECREATIONAL

HALL

C203

STAIR

NO-62

THERAPY

S204

LAB

STORAGE

SE201A

OFFICE

SE207

STAIR-2

NO-4-2

LAB

STORAGE

S207

MECH

SW202

TOILET

SW203

X-RAY

SW204

X-RAY

SW207

BREAK

RM

SW210

STAIR-1

NO-2-1

X-RAY

SW211

VASCULAR

PROCEDURE

RM

SW212

CHECKING

SW213

EQUIPMENT

SOTRAGE

S211A

OFFICE

S211

GAIT

RM

S212

OFFICE

SE208

CONFERENCE

RM

S206A

LOCKER

S206

OFFICE

NW205

KITCHEN

S203A

CORRIDOR

N2COR.2

CORR

NE2COR.1

CORR

N2COR.1

CORR

SW2COR.1

WAITING

SW213A

CORR

SE2COR.1

LAB

SE201

CORR

SE2COR.2

OFFICE

C212

STORAGE

C222

PT

RM

C214

DW

S201

TRUE

NORTH

PLAN

NORTH

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

636A-21-701

09/02/2022

EHRM INFRASTRUCTURE

UPGRADES

GRAND ISLAND, NE

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

IMEG Corp.

2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324

Thompson, Dreessen & Dorner, Inc.

10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

Shaffer Stevens & Schaap P.C.

1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698

CONSTRUCTION

DOCUMENTS

3 4

10 11

6 191

KEYPLAN

09/02/2022

B

IM

/2

-1 a

-2

-7

V

A G ra n d I s la n d

E H

R M

/6

A

.7

.B

.M E

P T

R

.r v t

/5

/2

:3

:0

A M

1-EP102

SECOND FLOOR PLAN - OVERALL -

ELECTRICAL - BLDG 1

NMT CTB

1/16" = 1'-0"1

SECOND FLOOR PLAN - OVERALL - ELECTRICAL

SHEET NOTES:

1. TIE INTO EXISTING EXTERIOR NORMAL BRANCH 20/1 CONVENIENCE CIRCUIT CURRENTLY SERVING THIS AREA. IF THERE IS AN EXISTING WEATHER-RATED GFCI IN THIS AREA, THIS RECEPTACLE WOULD NOT BE

REQUIRED.

1-M100 - GROUND FLOOR PLAN - OVERALL - MECHANICAL - BLDG 1
1-M101 - FIRST FLOOR PLAN - OVERALL - MECHANICAL - BLDG 1
1-M102 - SECOND FLOOR PLAN - OVERALL - MECHANICAL - BLDG 1
19-M101 - GROUND FLOOR PLAN - MECHANICAL - BLDG 19
M500 - MECHANICAL DETAILS AND CONTROLS
E000 - ELECTRICAL SYMBOLS, ABBREVIATIONS AND NOTES
1-EP100 - GROUND FLOOR PLAN -OVERALL -ELECTRICAL -BLDG 1
1-EP101 - FIRST FLOOR PLAN -OVERALL -ELECTRICAL -BLDG 1
1-EP102 - SECOND FLOOR PLAN -OVERALL -ELECTRICAL -BLDG 1

File details come from the government source that posted it. Updated .