This document package includes construction drawings and specifications for an infrastructure upgrade project at the Grand Island VA Medical Center in Grand Island, Nebraska. The project involves upgrades to mechanical, electrical, and plumbing systems across multiple buildings, including replacement of ductwork, piping, lighting fixtures, and installation of new generators and switchgear. The construction work includes upgrades to HVAC, plumbing, fire protection and electrical systems. The related federal contract opportunity is solicitation number 36C77623B0002 for the EHRM Infrastructure Construction Grand Island Project #636-21-701, issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The solicitation seeks construction services for the infrastructure upgrades depicted in the drawings and specifications provided.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1/8" = 1'-0"
ENLARGED PIPE BASEMENT FLOOR PLAN - MECHANICAL
Revisions: Date:
ADDENDUM 1 01/03/2023
A
2 3
B
B
C
2 3
BUILDING 6
BUILDING 8
UNDERGROUND
FUEL STORAGE
CDCD
CDCD
72x60 UP
CDCD
CDCD
CDCD
CDCD
UH-3
UH-1 UH-2
UH-4
UH-5
P-1
SSIU-19
SSOU-19
F-1
20x20 EA
4" ST
4" SO
4" UP
4" UP
A B C
GENERATOR
ROOM
19-G01
SWITCHGEAR
ROOM
19-G02
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/6
/2
:1
:4
A
M
19-M101
GROUND FLOOR PLAN - MECHANICAL -
BLDG 19
JMM PHV
1/8" = 1'-0"1
GROUND FLOOR PLAN - MECHANICAL
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
SHEET NOTES:
1. PROVIDE ONE 8' x 10' INTAKE DAMPER IN LOUVERED OPENING.
2. 8' x 10' x 1'-4" DOUBLE WALL, INSULATED SHEET METAL PLENUM.
3. PROVIDE 10’ X 10’ WIDE EXHAUST LOUVER. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
4. PROVIDE 10’ X 10’ WIDE X 1’-4” DEEP DOUBLE WALL, INSULATED SHEET METAL PLENUM. PROVIDE 4’ x 2’ WIDE
BYPASS LOW LEAKAGE DAMPER ON FACE OF 10’ X 10’ PLENUM. REFER TO CONTROL SEQUENCE FOR
ADDITIONAL INFORMATION ON OPERATION.
5. EMERGENCY GENERATOR EXHAUST MUFFLER, DISK TYPE WITH 10 INCH BOTTOM INLET AND 10 INCH SIDE OUTLET. ROUTE 10 INCH PIPE INLET TO GENERATOR AND REDUCE AT GENERATOR AS NECESSARY TO CONNECT TO GENERATOR FLEX CONNECTION. ROUTE 10 INCH DISCHARGE AS SHOWN AND REDUCE TO 8 INCH FOR DISCHARGE THROUGH WALL THIMBLE AS INDICATED. REFER TO SPECIFICATION 26 32 13 FOR
PERFORMANCE AND CONSTRUCTION REQUIREMENTS.
6. PROVIDE 6’ X 5’ SHEET METAL DUCT CONNECTION INTO LOUVERED PENTHOUSE INTAKE WITH LOW LEAKAGE OPPPOSED BLADE MOTORIZED DAMPERS. PLAN NORTH DAMPER SHALL BE 56" x 60" AND SOUTH DAMPER SHALL BE 16" x 60". REFER TO CONTROL SEQUENCE FOR ADDITIONAL INFORMATION ON OPERATION.
7. PROVIDE 5,000 GALLON, 8’ DIAMETER, DOUBLE WALL FUEL OIL STORAGE TANK WITH CONCRETE BALAST, FILL, VENT AND DIPTUBE CONNECTIONS. 4 FOOT DEPTH OF COVER. REFER TO DETAIL 4 ON SHEET M500 FOR
MORE DETAILS.
8. PROVIDE 1 INCH DOUBLE WALL FUEL OIL SUPPLY AND RETURN PIPE WITH DOUBLE WALL CONTAINMENT, LEAK DETECTION AND CATHODIC PROTECTION.
9. PROVIDE DUPLEX POSITIVE DISPLACEMENT FUEL OIL PUMPS. MINIMUM CAPACITY 2 GPM.
10. ROUTE 2 INCH VENT LINE FROM FUEL OIL TANK UNDERGROUND TO EXTERIOR OR BUILDING. ROUTE PIPE UP
SIDE OF BUILDING AND END WITH GOOSENECK A MINIMUM OF 12 FEET ABOVE GRADE.
11. FILL CONNECTION WITH SPILL CONTAINMENT AND CONCRETE CURB. PROVIDE 4 INCH, UNDERGROUND
DOUBLE WALL FILL LINE. BURY A MINIMUM OF 24 INCHES.
12. PROVIDE 4" DOWNSPOUT NOZZLE, JR SMITH 1770 OR EQUAL FOR STORM AND OVERFLOW DRAINAGE.
13. PROVIDE 4" ROOF DRAIN AND OVERFLOW DRAIN ON ROOF ABOVE.
GENERAL NOTES:
Revisions: Date:
ADDENDUM 01 01/03/2023
M500
NO SCALE
NO SCALENO SCALE NO SCALE
Revisions: Date:
1/4" = 1'-0"
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
COLOR TEMP CONTROL
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM
CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
J. ALL GENERATORS AND ESS TO BE SECURED PER VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL.
K. PROVIDE PERMANENT NAMEPLATE LABEL FOR PANELBOARDS IDENTIFYING COLOR CODING FOR BRANCH
CIRCUITS IN ACCORDANCE WITH NEC 210.5(c)(1).
L. COORDINATE WITH VA AND SPECIFICATIONS FOR REQUIREMENTS IN SUPPLYING AN ARC FLASH STUDY AND
PROVIDING LABELS FOR ALL NEW EQUIPMENT.
M. FUEL STORAGE TO BE PROVIDED IN COMPLIANCE WITH VA PHYSICAL SECURITY AND RESILIENCY DESIGN
MANUAL.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
LEGEND: (LOW VOLTAGE COORDINATION LEGEND)
CF: CONTRACTOR FURNISHED
CI: CONTRACTOR INSTALLED
OF: OWNER FURNISHED
OI: OWNER INSTALLED
REMARKS: (LOW VOLTAGE COORDINATION LEGEND)
1. FIRE ALARM IS AN EXTENSION OF AN EXISTING SIMPLEXGRINNELL SYSTEM. NEW DEVICES SHALL FUNCTION AS AN
EXTENSION OF THE EXISTING SYSTEM.
GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)
A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.
C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.
D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS
OTHERWISE INDICATED.
E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL CABLING PER
SPECIFICATION.
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/5
/2
:3
:0
A M
E000
ELECTRICAL SYMBOLS, ABBREVIATIONS
AND NOTES
NMT CTB
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
RECEPTACLE - DOUBLE DUPLEX
- CONV
RECEPTACLE - DOUBLE DUPLEX
- EMERGENCY (RED) - CONV
RECEPTACLE - DUPLEX - CONV
RECEPTACLE - DUPLEX - CONV -
GFCI
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - CONV
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - KNOWN
LOAD
RECEPTACLE - DUPLEX - KNOWN
LOAD
ELECTRICAL FIXTURE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
ELECTRICAL GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
EMERGENCY POWER OFF
SWITCH
GENERAL:
PROVIDE STI (SAFETY TECHNOLOGY INTERNATIONAL, INC) MODEL SS2-271PO-EN SURFACE MOUNT EPO SWITCH AND PROTECTIVE COVER, OR PRIOR APPROVED EQUIVALENT, AT APPROXIMATE LOCATIONS INDICATED ON PLANS.
PROVIDE ELECTRICAL COMPONENTS FOR A COMPLETE SYSTEM, INCLUDING ALL NECESSARY RELAYS, TRANSFORMERS, AND SHUNTING DEVICES. COORDINATE BACK BOX AND CONDUIT REQUIREMENTS WITH
MANUFACTURER.
TYPE ‘GEN’, GENERATOR EMERGENCY POWER OFF
PROVIDE 3"x5" OR 4"x4" MINIMUM PLAQUE AT EPO SWITCH WITH ENGRAVED LABEL. COORDINATE LABEL WITH
OWNER. PROVIDE EPO SWITCH TO DISCONNECT PRIME MOVER OF GENERATOR.
POKE THROUGH - POWER GENERAL:
PROVIDE POKE THROUGH AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH POKE THROUGH TYPE. REFER TO PLANS FOR POKE THROUGH DESIGNATION. COORDINATE REQUIREMENTS WITH POKE THROUGH MANUFACTURER. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: BRACKETS, BLANK COVER ASSEMBLIES, MOUNTING FRAMES, ADAPTERS, AND CONCRETE FLOOR ACCESSORIES/OPTIONS. COORDINATE EXACT FINAL LOCATION WITH ARCHITECT, OWNER, OWNER'S FINAL FURNITURE SELECTIONS AND LOCATIONS, AND FINAL FLOOR FINISH SELECTIONS PRIOR TO INSTALLATION. CORE DRILL FLOOR AS REQUIRED TO ACCOMMODATE FLUSH INSTALLATION AND CONCEALMENT OF CONDUITS. CONCEAL ALL CONDUITS ABOVE CEILING AT LEVEL BELOW POKE THROUGH LOCATION AND IN ADJACENT WALL. SUBMIT PRODUCT DATA FOR APPROVAL. COORDINATE INSTALLATION WITH OWNER. COORDINATE DISRUPTION TO EXISTING
SPACE LOCATED BELOW POKE THROUGH LOCATION.
TYPE 'PT1', 4 INCH POWER REACH-IN POKE THROUGH:
PROVIDE WIREMOLD EVOLUTION SERIES MODEL 4ATCP4R POKE THROUGH (OR PRIOR APPROVED EQUIVALENT).
PROVIDE COVER AND FLANGE WITH BRUSHED ALUMINUM FINISH. PROVIDE TWO (2) DUPLEX RECEPTACLES, MOUNTED WITHIN POKE THROUGH. PROVIDE ONE (1) 3/4" CONDUIT TO ELECTRICAL SOURCE FOR ONE (1) 20A 120V
BRANCH CIRCUIT. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION.
RECEPTACLE - NEMA PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA
DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:
•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER
MOUNT TO SIDE OF CABLE TRAY ABOVE TELECOMMUNICATIONS RACK.
FIRE ALARM SYMBOLS
PLAN SYMBOL NAME
DETECTOR - SYSTEM SMOKE -
CEILING
HORN AND STROBE
COMBINATION - WALL
MANUAL PULL STATION
STROBE - CEILING
STROBE - WALL
VOICE/TONE SPEAKER AND
STROBE COMBINATION - CEILING
VOICE/TONE SPEAKER AND
STROBE COMBINATION - WALL
LIGHTING DEVICE SYMBOLS
PLAN SYMBOL NAME
LIGHT SWITCH
LIGHTING DEVICE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
PUSH BUTTON DEVICE SHALL PROVIDE ON/OFF CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA. PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. WHERE NO ZONES ARE INDICATED, PROVIDE CONTROL OF SINGLE ZONE. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM
ADDITIONAL DEVICES.
TYPE ‘D’ – DEVICE SHALL PROVIDE ON/OFF AND MIN/MAX DIMMING CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA, PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM ADDITIONAL DEVICES.
TYPE ‘SC#’ – DEVICE SHALL PROVIDE SCENE CONTROL CAPABLE OF CONTROLLING ALL ZONES IN ROOM BY PRESET SCENES. NUMBER INDICATES QUANTITY OF SCENES TO BE SELECTED AT THIS LOCATION. SEE LIGHTING SCENE
SCHEDULE FOR DESCRIPTION OF DESIRED SCENES.
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
SWITCHED RECEPTACLE
ELECTRICAL MISC SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
LIGHTING CONTROL TAG REFER TO LIGHTING CONTROL SCHEDULE FOR ADDITIONAL INFORMATION.
LIGHTING FIXTURE
SYMBOLS
PLAN SYMBOL NAME
EMERGENCY HATCH
EMERGENCY LIGHTING - WALL
EXIT SIGN - WALL
INDUSTRIAL STRIP LIGHT
TROFFER - RECESSED - 2X2
TROFFER - RECESSED - 2X4
WALL SCONCE FIXTURE
LOW VOLTAGE COORDINATION LEGEND
SYSTEMS
ROUGH-INS &
PATHWAYS
CABLING &
TERMINATIONS
DEVICES &
EQUIPMENT REMARKS
FIRE ALARM CF / CI CF / CI CF / CI 1
ONE LINE SYMBOL
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
DIGITAL METER
DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
GENERATOR
GENERATOR CONNECTION BOX
GROUND BAR
GROUNDING ELECTRODE
KEY INTERLOCK
MOTOR STARTER
PANEL BOARD
SURGE PROTECTIVE DEVICE
SWITCHBOARD/SWITCHGEAR
SWITCHBOARD/SWITCHGEAR -
DOUBLE TUB
TRANSFORMER
UPS PANEL
UTILITY METER
ELECTRICAL EQUIPMENT SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
GENERATOR DOCKING STATION PROVIDE TRYSTAR, INC. DUAL-PURPOSE GENERATOR/LOADBANK DOCKING STATION (OR PRIOR APPROVED EQUIVALENT) WITH VOLTAGE AND CURRENT RATINGS TO MATCH GENERATOR OUTPUT CIRCUIT BREAKER. PROVIDE ENCLOSURE WITH NEMA 3R CONSTRUCTION. PROVIDE WITH INTEGRAL CIRCUIT BREAKER SERVED FROM PERMANENT GENERATOR SOURCE KIRK KEY INTERLOCKED WITH ACCESS DOOR PROTECTING PORTABLE GENERATOR MALE 16 SERIES PANEL MOUNTS (CAM-LOKS). PROVIDE LOAD BANK FEMALE 16 SERIES PANEL MOUNTS (CAM-LOKS). PROVIDE WITH THE FOLLOWING OPTIONS: 2 WIRE AUTO START, BATTERY CHARGER NEMA 5-20 GFCI RECEPTACLE, AND BLOCK HEATER NEMA L5-30 RECEPTACLE. PROVIDE SEPARATE ELECTRICAL CONNECTIONS FROM PANEL GEN-L1, CIRCUITS 2,4 TO SERVE BATTERY CHARGER AND BLOCK HEATER RECEPTACLES.
PROVIDE SIGN ON FRONT OF CABINET STATING THE FOLLOWING:
MAXIMUM GENERATOR CIRCUIT BREAKER SIZE: 1200 AMPS LSIG AND ERMS
GENERATOR SYSTEM IS A SEPARATELY DERIVED SYSTEM. BOND GENERATOR NEUTRAL AND GROUND
ELECTRICAL EQUIPMENT
SYMBOLS
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
BUS DUCT
DISTRIBUTION PANEL
GENERATOR
LOAD CENTER - RECESSED
PANELBOARD - RECESSED
PANELBOARD - SURFACE
SWITCHBOARD
TRANSFORMER - DRY TYPE
UPS CABINET
Revisions: Date:
A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.
CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH
ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.
B. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH
ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE
ARCHITECTURAL DRAWINGS. ROUTE ALL ELECTRICAL BRANCH CIRCUITS AND CONDUITS SPECIFIED, TO COORDINATE WITH OTHER TRADES AND TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, ARRANGE WORK TO INSTALL
PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.
C. REDUNDANT GROUNDING METHODS REQUIRED FOR PATIENT CARE AREAS. REFER TO NEC FOR
REQUIREMENTS AND TO PROJECT SPECIFICATIONS FOR ACCEPTABLE METHODS/APPLICATIONS.
D. GFCI TYPE RECEPTACLES ARE NOTED AS SUCH ON THE PLANS FOR PRICING PURPOSES. HOWEVER, CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE ALL RECEPTACLES INSTALLED WHERE A 6' CORD
LENGTH COULD REACH THE EDGE OF A SINK HAVE GFCI PROTECTION.
E. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.
F. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT
HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
(ELECTRICAL GENERAL NOTES SHALL APPLY TO ALL SHEETS)
POWER GENERAL NOTES:
1-E400
1-E400
1-E400
B-SIDE DIST.A-SIDE DIST.
C R
A C
-1
C R
A C
-2
C R
A C
-3
CSC-UPS-A
CSC-UPS-B
1-E402
TR-1-C6B
TR-1-C6A
1-E402
AC7
CSC-A
CSC-B
AC7A
AC8
L11
48"
SSOU-0GA
SSIU-0GA
SSIU-N02B
SSIU-N02A
E
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
ENTRANCE
ROOM
1-N09A
OFFICE
1-NE1
MCR
1-C01
UPS
1-N02
CORR
1-NEGCOR.2
CANTEEN
OFFICE
1-NE0
CORR
1-CGCOR.2
CORR
1-CGCOR.3
CORR
1-CGCOR.1CORR
1-NEGCOR.1
CORR
1-NEGCOR.3
CORR
1-CGCOR.4
CORR
1-CGCOR.5
TR
1-C6
LAUNDRY
1-NE3
FCU-1
SSOU-0GB
SSIU-0GB
SSOU-01A
SSOU-01B
WR
A. LIGHTING CONTROL DEVICES ARE INDICATED WITHOUT CONNECTION TO FIXTURE(S) BEING CONTROLLED.
WITHIN EACH AREA, CONNECT CONTROL DEVICE TO SERVE LIGHT FIXTURE(S) LOCATED WITHIN SAME AREA. WHERE LIGHT FIXTURES ARE INDICATED WITH A SUBSCRIPT LETTER IDENTIFYING INDIVIDUAL LIGHTING CONTROL ZONES, CONTROL DEVICE SERVING AREA WITH MATCHING SUBSCRIPT SHALL
CONTROL CORRESPONDING LIGHT FIXTURES.
B. LIGHTING CONTROL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.
CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH
ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.
C. CONTRACTOR SHALL COORDINATE ALL LIGHTING CONTROL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE ARCHITECTURAL DRAWINGS. COORDINATE ROUTING OF ALL ELECTRICAL BRANCH CIRCUITS AND CONDUIT WITH OTHER TRADES TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, WORK TO INSTALL PANELS IN LOCATIONS
ACCEPTABLE TO ARCHITECT.
D. FIXTURES DESIGNATED 'LS' AND EXIT LIGHTS SHALL BE SERVED FROM A COMMON 20A 120V LIFE SAFETY BRANCH CIRCUIT. EXIT LIGHTS SHALL BE ILLUMINATED 24 HOURS. FIXTURES DESIGNATED 'LS' SHALL BE
SWITCHED BY CONTROLS INDICATED. PROVIDE EMERGENCY LIGHTING CONTROL RELAYS PER
SPECIFICATIONS FOR EMERGENCY LIGHTING OVERRIDE. REFER TO MANUFACTURER'S WIRING DIAGRAMS
FOR INSTALLATION INSTRUCTIONS.
E. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.
(LIGHTING GENERAL NOTES SHALL APPLY TO ALL SHEETS)
LIGHTING GENERAL NOTES:
CRAWL
SPACE
NO.9
STORAGE
C22
SOILED
LINEN
S7
CHILLER
RM
G03
CRAWL
SPACE
NO.8
OFFICE
N03
IT
C25
OFFICE
C24
CORR
SGCOR.1
OFFICE
S2
STAIR
NO 4
SPS
LOCKER
RM
C28CORR
SEGCOR.1
SOILED
LINEN
CHUTE
N04
LOCKER
N17
IT
OPERATORS
N08
CORR
NGCOR.1
STAIR
NO-3G
TR
C5
STORAGE
C20
SUPPLY
WAREHOUSE
C18
WAREHOUSE
STORAGE
C12A
CORR
CGCOR.7
STORAGE
C17E
STAIR
NO-6G
MECH-1
C17B-1
LOCKER
RM
N05
IT
STORAGE
N15A
PAHTOLOGY
N06
EQUIR
RM
NE3B
IT
SERVICES
N11
IT
OFFICE
N12
UNISEX
TOILET
N13
WOMENS
LOCKER
N14A
WAREHOUSE
SUPPLY
RM
C8
BIO
MED
SHOP/OFFICE
C9
WAREHOUSE
STORAGE
C12
CANTEEN
STORAGE
C13
STORAGE
C14
STORAGE
C15
ER
SUPPLY
C16
PROSTHETICS
C17A
FITNESS
CENTER
S6
POLICE
OFFICE
S4
RM
S9
OFFICE
N07
STORAGE
N18
MENS
TOILET
C29
WOMENS
TOILET
C30
RESTROOM
C31
EEMS
STORAGE
C10
ARMORY
C23
RM
OFFICE
S8
SPS
DISPATCH
S1
WAREHOUSE
STORAGE
C11A
WAREHOUSE
STORAGE
C11
CRAWL
SPACE
NO.7
MCR
C01
CORR
CGCOR.6
MENS
TOILET
C7
CORR
NGCOR.2
EQUIP
RM
NE3A
MECH-2
C17B-2
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/5
/2
:2
:5
A M
1-EP100
GROUND FLOOR PLAN - OVERALL -
ELECTRICAL - BLDG 1
NMT CTB
1/16" = 1'-0"1
GROUND FLOOR PLAN - OVERALL - ELECTRICAL
SHEET NOTES:
1. CONFIRM FINAL OUTLET LOCATION WITH OWNER PRIOR TO ROUGH-IN FOR KEYBOX CONTROLLER POWER.
UTILIZE SPARE 20/1 ESSENTIAL BRANCH CIRCUIT WITHIN PANEL L11.
2. FACILITY PERSONNEL TO PROVIDE AN APPROVED PROCEDURE TO THE STAFF SUPERVISING THE BUILDING THAT UNDERSTAND WHERE TO DE-ENERGIZE THE BREAKERS THAT FEED THE IT EQUIPMENT WITHIN THE
MCR AND CAN RELAY THIS INFORMATION TO EMERGENCY PERSONNEL WHEN REQUIRED. SOURCE
BREAKERS TO ELECTRICAL PANELS WITHIN THE MCR ORIGINATE AT BUILDING 17.
1-E401
SSIU-01A TR-1N118B
TR-1N118A
60"
SSOU-N02B
SSOU-N02A
L11
AC8
WR
AC2
E
1-E402
SSIU-01B
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
OFFICE
1-N115 TR
1-N118
OFFICE
1-N117
CASHIER
1-N116
CORR
1-N1COR.1
VOLUNTEER
AREA
1-N121
CORR
1-C1COR.1
LOBBY
1-001
CLEAN
UTILITY
SE130
SOILED
UTILITY
SE131
CLEAN
UTILITY
NW109
SOILED
UTILITY
NW110
CLEAN
LINEN
NW112
CORR
NW1C0R.1
STAIR-1
NO-1-1
MALE
TOILET
N105
STAIR
NO-3
LAB
NE109
SOILED
NE105
IMAGING
NE110
OFFICE
N103
CANTEEN
N102
STAIR-6
C34
TR
C100
OFFFICE
C101E
CONFERENCE
RM
C101D
HAC
C109
STORAGE
C111
FREEZER
C102
FREEZER
C102A
FREEZER
C103
STORAGE
C106
LINEN
CLOSET
C105
FREEZER
C112
FREEZER
C113A
IV
DISPENSING
SE103
CONFERENCE
RM
SE106
STAIR-1
NO-4-1
VACANT
SE117
PRESCRIPTIONS
SE115
MD
EXAM
SE118
EXAM
RM
SE119
MD
EXAM
SE120
EXAM
RM
SE121
ELECTRICAL
SE138
TOILET
SE139
EXAM
RM
SE140
OFFICE
SE141
TELEMEDICINE
SE145
EXAM
RM
SE142
EXAM
RM
SE127
VACANT
SE108
EXAM
RM
SE124
CONTROL
SUBSTANCE
SE112
REST
RM
SE111
REST
RM
SE110
ELIGIBILTY
SE133
OFFICE
SE148
NUTRITION
CLINIC
SE134
SOCIAL
WORK
SE147
TOILET
SE147A
EXAM
RM
SE135
OFFICE
SE136
OFFICE
SE137
CORR
SW1C0R.2
FEMALE
TOILET
N104
RECEPTION
NE113
TELEHEALTH
SE144
STAIR
NO-5
CLINICAL
PHARMACIST
NW101
EXAM
RM
NW102
EXAM
RM
NW103
STORAGE
NW105
EXAM
RM
NW106
EXAM
RM
NW107
TOILET
NW107A
EXAM
RM
NW108
TOILET
NW108A
EXAM
RM
NW111
TOILET
NW111A
EXAM
RM
NW113
NURSE
STATION
NW114
EXAM
RM
NW115
EXAM
RM
NW116
CLINICAL
PHARMACIST
NW117
PATIENT
EDUCATION
N107
SUPPLY
NE104
OFFICE
NE106
HAC
NE108
OFFICE
N114
WOMENS
TOILET
C104
MALE
TOILET
C107
WASH
RM/HAC
C110
VEG
RM
C101E
CHIEF
PHARMACY
SE107
OFFICE
SE109
MD
EXAM
SE125
MD
EXAM
SE126
MD
EXAM
SE143
AMBULANCE
ENTRANCE
SE156
CONFERENCE
RM
SE155
TOILET
SE153A
MINOR
TREATMENT
SE153
SOCIAL
WORKER
SE152
TOILET
SE152A
TRIAGE
SE151
HAC
SE150
RECEPTION
SW102A
TREATMENT
SW102B
NURSE
STATION
SW103
PROVIDER
STATION
SW104
EXAM
RM
SW105
EXAM
RM
SW106
EXAM
RM
SW107
EXAM
RM
SW109
EXAM
RM
SW113
EXAM
RM
SW114
TOILET
SW115A
CLINICAL
PHARMACIST
SW116
TOILET
SW117
TOILET
SW118
ADVOCATE
OFFICE
S109
FOOD
STORAGE
C115
INPATIENT
PHARMACY
SE102
OUTPATIENT
PHARMACY
SE114
ACTIVE
STORAGE
SE113
PASSAGE
SE105
WOMENS
TOILET
S110
WAITING
N112
TREATMENT
NE103
TREATMENT
NE112
CORR
NE1COR.1
TREATMENT
NE111
NURSE
SE128
CORR
C1C0R.2
CORR
C1C0R.4
CORR
C1C0R.3 PATIENT
RECIEVING
SE116
CORR
SE1COR.1
CORR
SW1C0R.1
LOBBY
S1C0R.3
OFFICE
NE107
CORR
S1C0R.2
CORR
S1COR.1
MALE
TOILET
S111
EXAM
RM
NW104
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/5
/2
:3
:0
A M
1-EP101
FIRST FLOOR PLAN - OVERALL -
ELECTRICAL - BLDG 1
NMT CTB
SHEET NOTES:
1. TIE INTO EXISTING EXTERIOR NORMAL BRANCH 20/1 CONVENIENCE CIRCUIT CURRENTLY SERVING THIS AREA. IF THERE IS AN EXISTING WEATHER-RATED GFCI IN THIS AREA, THIS RECEPTACLE WOULD NOT BE
REQUIRED.
2. TIE INTO EXISTING CIRCUIT SERVING EQUIPMENT PRIOR TO IT'S RELOCATION FROM PANEL "K" LOCATED IN THE KITCHEN. CIRCUITS K-3,5,7,9,11, AND 13 PREVIOUSLY SERVED THE VENDING ROOM WHICH IS CONVERTED TO THE NEW IT ROOM. BREAKERS NOT RE-USED, SHOULD BE DE-ENERGIZED AND SCHEDULE
UPDATED TO SPARE.
3. PROVIDE NEW 20/1 CIRCUIT BREAKER IN AVAILABLE SPACE WITHIN EXISTING NORMAL BRANCH PANEL 'AC2'
UNLESS A SPARE 20/1 CIRCUIT BREAKER IS AVAILABLE.
1/16" = 1'-0"1
FIRST FLOOR PLAN - OVERALL - ELECTRICAL
1-E401
SSIU-02A
TR-1-S202B
TR-1-S202A
SSOU-02A
1-E402
ACCU-1ACCU-2ACCU-3
WR
WR
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
DD
CC
BB
AA
A
B
C
D
E
F
G
H
IJ
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
TREATMENT
1-S203
TR
1-S202
OFFICE
1-S208
CORR
1-C2CO2.2
CORR
1-C2COR.1
CORR
1-C2CO2.3
CORR
1-C2CO2.4
CORR
1-C2CO2.5
CORR
1-C2CO2.7CORR
1-C2CO2.6
CORR
1-SE2COR.1
CORR
1-S2COR.1
SSOU-02B
SSOU-03A
SSIU-02B
SSOU-03B
EXAM
NE207
EXAM
NE208
EXAM
NE203
STORAGE
NE209
STAFF
NE210
SUPPLY
NE211
TOILET
NE212A
STORAGE
NW211
PROCED
NE212
HAC
N209
STORAGE
N213
STORAGE
S209
WOMENS
TOILET
SE206
RESTROOM
C221
CLEAN
LINEN
C217
STORAGE
C213
OFFICE
C208
VOL
SVS
KITCHEN
C203B
STORAGE
C202A
TR
C201
HVAC
S205
ELECTRICAL
SE202
MENS
TOILET
SE203
TOILET
SW206
CORR
NW2COR.1
TOILET
SW201A
ULTRASOUND
SW201
SOILED
UTILITY
S210
AUDIOLOGY
N203
MENS
RESTROOM
N215
AUDIIOLOGY
OFFICE
NW201
AUDIOLOGY
EXAM
NW202
AUDIOLOGY
NW203
STAIR-2
NO-1-2
TREATMENT
RM
NW205B
TREATMENT
RM
NW206
TOILET
NW207A
TREATMENT
RM
NW207
EXAM
NW208
EXAM
NW209
EXAM
NW210
EXAM
N204
EXAM
N205
EXAM
N206
EXAM
N207
STAIR
SE157
SOILED
HOLD
NE201
PROCED
NE202
EXAM
NE204
EXAM
NE205
LINEN
NE206
EXAM
N210
EXAM
N211
WOMENS
RESTROOM
N214
CHAPLAIN
C201
CHAPEL
C202
CHAPLIN
C202B
OFFICE
C210
OFFICE
C211
STAIR
NO-7
MECH
C220
RECREATIONAL
HALL
C203
STAIR
NO-62
THERAPY
S204
LAB
STORAGE
SE201A
OFFICE
SE207
STAIR-2
NO-4-2
LAB
STORAGE
S207
MECH
SW202
TOILET
SW203
X-RAY
SW204
X-RAY
SW207
BREAK
RM
SW210
STAIR-1
NO-2-1
X-RAY
SW211
VASCULAR
PROCEDURE
RM
SW212
CHECKING
SW213
EQUIPMENT
SOTRAGE
S211A
OFFICE
S211
GAIT
RM
S212
OFFICE
SE208
CONFERENCE
RM
S206A
LOCKER
S206
OFFICE
NW205
KITCHEN
S203A
CORRIDOR
N2COR.2
CORR
NE2COR.1
CORR
N2COR.1
CORR
SW2COR.1
WAITING
SW213A
CORR
SE2COR.1
LAB
SE201
CORR
SE2COR.2
OFFICE
C212
STORAGE
C222
PT
RM
C214
DW
S201
TRUE
NORTH
PLAN
NORTH
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
636A-21-701
09/02/2022
EHRM INFRASTRUCTURE
UPGRADES
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
CONSTRUCTION
DOCUMENTS
3 4
10 11
6 191
KEYPLAN
09/02/2022
B
IM
/2
-1 a
-2
-7
V
A G ra n d I s la n d
E H
R M
/6
A
.7
.B
.M E
P T
R
.r v t
/5
/2
:3
:0
A M
1-EP102
SECOND FLOOR PLAN - OVERALL -
ELECTRICAL - BLDG 1
NMT CTB
1/16" = 1'-0"1
SECOND FLOOR PLAN - OVERALL - ELECTRICAL
SHEET NOTES:
1. TIE INTO EXISTING EXTERIOR NORMAL BRANCH 20/1 CONVENIENCE CIRCUIT CURRENTLY SERVING THIS AREA. IF THERE IS AN EXISTING WEATHER-RATED GFCI IN THIS AREA, THIS RECEPTACLE WOULD NOT BE
REQUIRED.
| 1-M100 - GROUND FLOOR PLAN - OVERALL - MECHANICAL - BLDG 1 |
| 1-M101 - FIRST FLOOR PLAN - OVERALL - MECHANICAL - BLDG 1 |
| 1-M102 - SECOND FLOOR PLAN - OVERALL - MECHANICAL - BLDG 1 |
| 19-M101 - GROUND FLOOR PLAN - MECHANICAL - BLDG 19 |
| M500 - MECHANICAL DETAILS AND CONTROLS |
| E000 - ELECTRICAL SYMBOLS, ABBREVIATIONS AND NOTES |
| 1-EP100 - GROUND FLOOR PLAN -OVERALL -ELECTRICAL -BLDG 1 |
| 1-EP101 - FIRST FLOOR PLAN -OVERALL -ELECTRICAL -BLDG 1 |
| 1-EP102 - SECOND FLOOR PLAN -OVERALL -ELECTRICAL -BLDG 1 |