ADD 1 - 03 Architectural - A-701.pdf
PDF 265 KB Posted
- Solicitation number
- 36C77623B0002
About this file
This document package includes architectural drawings and door/frame schedules for a federal construction project. The drawings provide details for door types, frames, wall sections and finishes for the EHRM Infrastructure Upgrades project at the Grand Island VAMC, identified as project number 636-21-701. The solicitation is for construction services to upgrade infrastructure at the medical center campus. The Department of Veterans Affairs Technology Acquisition Center in Austin is the contracting agency. Services include installation of new doors, frames and wall sections according to the specifications and materials schedule provided in the architectural drawings. The projected is valued at an undisclosed amount with an anticipated award date in 2023.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCHEDULE
SEE DOOR
S C
H E
D U
LE
S
E E
D O
O R
DOOR FRAME TYPES
SCALE: 1/4" = 1'-0"
HM
2"
2" 2"
SCHEDULE
SEE DOOR
HM
4"
2" 2"
S C
H E
D U
LE
S
E E
D O
O R
REFER TO WALL SECTIONS AND DETAILS FOR EXTERIOR FRAME DETAILS
A-701
A-701
A-701
F
DOOR TYPES
SCALE: 1/4" = 1'-0"
FLUSH
2'-0"
3' -0
A-701
TELLER WINDOW
DEAL TRAY
WALL - SEE PLAN
WALL - SEE PLAN
HEADER - SEE SCHEDULE
VARIES
SEE PLAN
1/2"1/2"
WALL - SEE
PLAN FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND, TYP.
HOLLOW METAL
FRAME
V A
R
IE
S
S E
E P
LA
N
1/ 2"
1/ 2"
2"4"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA. SIDE
& ALL AROUND, TYP.
HOLLOW METAL FRAME
WALL - SEE
PLAN FOR TYPE
CORRIDOR
ROOM
EXISTING CLAY TILE
SAW-CUT CLAY TILE
5/8" F.R. GWB BOTH SIDES
ADDITIONAL GWB AS REQUIRED
TO MATCH THICKNESS
3 5/8" NON-LOAD BEARING WALL
FRAMING SYSTEM
TYP. AT CLAY TILE
1'-0"
1/ 2"
1/ 2"
HOLLOW METAL FRAME
SEALANT - EA. SIDE & ALL AROUND,
TYP.
REMOVE CLAY TILE
TO STRUCTURE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
636A-21-701
09/01/2022
EHRM INFRASTRUCTURE
UPGRADES
CONSTRUCTION
DOCUMENTS
GRAND ISLAND, NE
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer Stevens & Schaap P.C.
1070 Howard Street Omaha, NE 68102 Phone: (402) 455-7698
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
IMEG Corp.
2882 106th Street Des Moines, IA 50322 Phone (515) 334-4324
Thompson, Dreessen & Dorner, Inc.
10836 Old Mill Rd Omaha, NE 68154 Phone: (402) 330-8860
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
B
IM
/2
-1 a -2
-7
V A
G ra n d I s la n d
E H
R M
/6
B ld g
.r v t
/5
/2
:0
:4
P M
A-701
DOOR AND FRAME TYPES AND SCHEDULE
JHH R
DOOR SCHEDULE
DOOR NUMBER ROOM NAME DOOR SIZE HARDWARE DOOR MATERIAL DOOR TYPE DOOR FINISH FRAME TYPE FRAME MATERIAL FRAME FINISH FIRE RATING REMARKS
1-C01 MCR PR 3'-0" x 7'-0" HW-SH-3D WD F ST-1 1 HM MCR P-20/CORR P-8 45 MIN
1-C06 TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-8 90 MIN
1-N02 UPS 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM UPS P-20/CORR P-8
1-NE0 CANTEEN OFFICE 3'-0" x 7'-0" HW-SH-3D WD F ST-1 1 HM OFF P-9/CORR P-8 1 Door Viewer, L03221 – 190° (VIEW INTO CORRIDOR)
1-NE1 OFFICE 3'-0" x 7'-0" HW-3G WD F ST-1 1 HM OFF P-9/CORR P-8
1-N116 CASHIER 3'-0" x 7'-0" HW-SH-3D WD F ST-1 1 HM CASHIER P-9/CORR P-9 1 Door Viewer, L03221 – 190° (VIEW INTO CORRIDOR)
1-N118 TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-9
1-S202 TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-9
1-S208 OFFICE 3'-0" x 7'-0" HW-3G WD F ST-1 1 HM OFF P-9/CORR P-9
1-S302 TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-9
1-C404A TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-9
1-C404C EMS OFFICE 3'-0" x 7'-0" HW-3G WD F ST-1 1 HM EMS P-9/CORR P-9
1-S502 TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-9
1-S517 CONF ROOM 3'-6" x 7'-0" HW-SH-4 WD F ST-1 1 HM CONF P-9/CORR P-9
3-2C TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-16
4-2C TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-18
5-1 TR 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM TR P-20/CORR P-20
5-B4 STORAGE 3'-0" x 7'-0" HW-5 WD F ST-1 1 HM STOR P-20/CORR P-20
6-1 PASSAGE 3'-8" x 7'-0" HW-SH-3D WD F ST-1 1 HM PASS P-20/CORR P-20
19-G01 GENERATOR ROOM 4'-0" x 7'-0" HW-SH-12 HM F P-19 2 HM P-19 BLAST RESISTANT
19-G02 SWITCHGEAR ROOM 3'-0" x 7'-0" HW-SH-12 HM F P-19 2 HM P-19 BLAST RESISTANT
19-G02A SWITCHGEAR ROOM 4'-0" x 7'-0" HW-4F HM F P-20 2 HM P-20 45 MIN
1 1/2" = 1'-0"6
TELLER WINDOW
3" = 1'-0"1
HEAD
3" = 1'-0"2
JAMB
3" = 1'-0"3
JAMB
Mark Revisions: Date:
1 ADDENDUM 1 03JAN23
| Sheets |
| A-701 - DOOR AND FRAME TYPES AND SCHEDULE |
File details come from the government source that posted it. Updated .