Attachment 09 Electrical Drawings.pdf

PDF 3 MB Posted

Attached to
Construction of a Visitor's Center at the Herbert R. Temple Jr. Army National Guard Readiness Center (TARC)
Solicitation number
W9133L-21-B-4000
Issued by

About this file

This solicitation is for the construction of a Visitor's Center building at the Herbert R. Temple Jr. Army National Guard Readiness Center in Arlington, Virginia. The National Guard Bureau plans to construct the Visitors Center within the installation fence line. Work will involve civil, architectural, security, structural, plumbing, mechanical, and electrical disciplines. The period of performance is 425 calendar days from notice to proceed to complete the project, with an estimated value between $1-5 million. The primary NAICS code is 236220 for commercial and institutional building construction. Attached are the written solicitation, specifications, and drawings.

View the file

Other files

File Type Posted
20210820 OF 1419 Abstract of Offers (Signed).pdf PDF
Correction to Zip Code for Bid Package.pdf PDF
20210816 RFIs and Responses.pdf PDF
RFI 62 - Updated Pedestrian Gate Spec 11 14 13.pdf PDF
RFI 60 - Sketch - Door 1a Auto Door Actuator.pdf PDF
20210812 RFIs and Responses.pdf PDF
20210810 RFIs and Responses.pdf PDF
Geotechnical Report TARC.pdf PDF
20210810 W9133L-21-B-4000-0002.pdf PDF
Irrigation drawings from ESPC project.pdf PDF
RFIs and Responses - W9133L-21-B-4000 5 Aug 21.pdf PDF
RFI 001 - Eight Event Liquid Crystal Display Module.pdf PDF
20210803 Pre-Proposal Site Visit Slides.pdf PDF
Existing Conditions Photography (Information Only).pdf PDF
W9133L-21-B-4000 - Amendment 1.pdf PDF
Stamped TARC DRAWINGS Amendment 1.pdf PDF
20210803 Site Visit Attendance Sheet.pdf PDF
Attachment 10 Visitors Center Specs.pdf PDF
Attachment 05 Security Drawings.pdf PDF
W9133L-21-B-4000.pdf PDF
Attachment 02 Life Safety Drawings.pdf PDF
Attachment 08 Mechanical Drawings.pdf PDF
Attachment 07 Plumbing Drawings.pdf PDF
AF 66 Visitors Center.xls XLS spreadsheet
Attachment 01 General Drawings.pdf PDF
Attachment 06 Structural Drawings.pdf PDF
Attachment 03 Civil Drawings.pdf PDF
Attachment 04 Architectural Drawings.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTE: REFER TO 'TYPICAL COMMUNICATION OUTLET DETAIL' FOR BOX & CONDUIT REQUIREMENTS. REFER TO

TELECOMMUNICATION DEVICE DETAILS FOR CABLING AND TERMINAL JACK REQUIREMENTS.

SYMBOL DESCRIPTION

X

COMMUNICATIONS LEGEND

E

TELECOMMUNICATIONS OUTLET, SUBSCRIPT NUMBER INDICATES OUTLET TYPE. MOUNT AT +3'-10"AFF.

TELECOMMUNICATIONS OUTLET, SUBSCRIPT NUMBER INDICATES OUTLET TYPE. MOUNT AT +1'-6"AFF.

X

[MISC COMMUNICATIONS OUTLET] , MOUNT AT +1'-6"AFF.

RECESSED FLOOR MOUNT DEVICE COMPLETE WITH FITTINGS FOR FLOOR COVERING.

INTERCOM STATION WITH PUSHBUTTON, MOUNT AT +4'-6"AFF.

[MISC COMMUNICATIONS OUTLET] , MOUNT AT +4'-6"AFF.

PUSHBUTTON SWITCH, MOUNT AT +4'-6"AFF. SUBSCRIPT "E" INDICATES EMERGENCY FUNCTIONS.

CATV OUTLET, MOUNT AT +1'-6"AFF.

WALL CLOCK, MOUNT AT +7'-6"AFF. SUBSCRIPT "D" INDICATES DOUBLE FACE CLOCK.

MICROPHONE OUTLET, WALL MOUNT AT +1'-6"AFF, FLUSH FLOOR MOUNT. SUBSCRIPT NUMBER

INDICATES NUMBER OF JACKS TO PROVIDE IN OUTLET.

SOUND SYSTEM SPEAKER, RECESS WALL MOUNT AT +7'-6"AFF. 'WG' WHERE PRESENT INDICATES

PROVIDE PROTECTIVE WIRE GUARD.

POWER/COMMUNICATIONS RECESSED FLOOR BOX. SUBSCRIPT LETTER INDICATES OUTLET TYPE.

REFER TO "TYPICAL COMMUNICATION OUTLET DETAIL" FOR BOX AND CONDUIT REQUIREMENTS.

POWER/COMMUNICATIONS RECESSED FLOOR BOX ON EMERGENCY POWER. SUBSCRIPT LETTER

INDICATES OUTLET TYPE. REFER TO "TYPICAL COMMUNICATION OUTLET DETAIL" FOR BOX AND

CONDUIT REQUIREMENTS.

TELECOMMUNICATIONS EQUIPMENT RACK.

2” EMT CONDUIT SLEEVE WITH NYLON BUSHING EACH END UNO, THRU WALL AT +6” ABOVE FINISHED

CEILING.

TELECOMMUNICATIONS GROUND BUS BAR, MOUNT AT +1'-6"AFF.

TELECOMMUNICATIONS MAIN GROUND BUS BAR, MOUNT AT +1'-6"AFF.

CABLE TRAY, MOUNT AT +6" ABOVE FINISHED CEILING.

SOUND SYSTEM SPEAKER, RECESS CEILING MOUNT. 'WG' WHERE PRESENT INDICATES PROVIDE

PROTECTIVE WIRE GUARD.

M M

S

S

TGB

TMGB

WALL CLOCK, CEILING MOUNT. SUBSCRIPT "D" INDICATES DOUBLE FACE CLOCK. ARROWS INDICATE

FACE DIRECTION.

WIRELESS ACCESS POINTWA

SYMBOL DESCRIPTION

DEMOLITION LEGEND

REMOVE DEVICES, EQUIPMENT, IN ACCORDANCE

WITH THE GENERAL DEMOLITION NOTES.

DEVICES ARE EXISTING TO REMAIN.

WITHIN HATCHED AREAS, DISCONNECT AND REMOVE ALL ELECTRICAL MATERIALS

INCLUDING BUT NOT LIMITED TO LIGHTS, DEVICES, EQUIPMENT, SPEAKERS, FIRE ALARM,

COMMUNICATIONS, AND CIRCUITRY.

A. PROVIDE ALL ELECTRICAL DEMOLITION WORK REQUIRED TO INSTALL THE WORK INDICATED. REMOVE, REROUTE, AND RECONNECT ALL BRANCH CIRCUITS THAT WILL REMAIN IN USE BUT INTERFERES WITH THE

WORK.

B. REMOVE ALL EXISTING CONDUITS THAT WILL NOT BE REUSED AND WHERE THEY WILL BE EXPOSED AFTER COMPLETION. ABANDON ALL OTHERS IN THE WALLS ONLY. DISCONNECT ALL WIRING INDICATED AND/OR

REQUIRED TO BE REMOVED FROM ALL POWER SOURCES. REMOVE ALL WIRING FROM ABANDONED

CONDUITS AND PROVIDE BLANK COVER PLATES FOR BOXES NOT UTILIZED FOR THE WORK.

C. MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN OR PORTIONS THEREOF AFFECTED BY THE

WORK.

D. BEFORE DEMOLITION, VERIFY WITH THE OWNER ALL EQUIPMENT TO BE SALVAGED TO OWNER AND NOT REMOVED FROM THE SITE. FOR ALL REMAINING EQUIPMENT INDICATED FOR REMOVAL (AND NOT

RELOCATED), REMOVE AND DISPOSE IN A LEGAL MANNER.

E. EXERCISE CARE IN REMOVING DEMOLITION ITEMS. REPAIR OR REPLACE ALL DAMAGE CAUSED TO EXISTING

CONSTRUCTION AND EQUIPMENT TO REMAIN.

F. DRAWINGS ARE BASED UPON EXISTING PLANS AND FIELD INVESTIGATION WITHOUT DEMOLITION. VISIT THE EXISTING BUILDING AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS AND EXAMINE ALL DRAWINGS

TO AVOID CONFLICTS.

G. WHERE DEMOLITION OF TELECOMMUNICATIONS DEVICES OCCUR, REMOVE CABLING NOT INDICATED TO

REMAIN BACK TO POINT OF ORIGIN.

H. DEMOLITION FLOOR PLANS ARE PROVIDED FOR REFERENCE ONLY TO AID IN DEFINING THE SCOPE OF

DEMOLITION WORK.

GENERAL DEMOLITION NOTES

A. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING

AS IF REQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER

QUALITY. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY

OF WORK.

B. FOLLOW MOUNTING HEIGHTS INDICATED IN THE ELECTRICAL LEGEND UNLESS OTHERWISE INDICATED.

MEASURE ALL MOUNTING HEIGHTS FROM THE DEVICE CENTER LINE UNLESS OTHERWISE INDICATED.

C. FIELD VERIFY EXACT FEEDER LOCATIONS FOR MECHANICAL EQUIPMENT PRIOR TO ROUGH-IN.

D. EQUIPMENT CONNECTIONS ARE INDICATED IN THEIR APPROXIMATE LOCATIONS. VERIFY EXACT LOCATIONS

OF ALL CONNECTIONS WITH OTHER TRADES SUPPLYING EQUIPMENT TO AVOID CONFLICTS AT INSTALLATION.

E. LOCATED ALL SWITCHES FOR LOCAL CONTROL OF LIGHTING ON STRIKE SIDE OF SINGLE DOORS UNLESS

OTHERWISE INDICATED.

F. PROVIDE SPECIFIC BREAKER ARRANGEMENT FOR THE PANEL BOARDS WHEREVER PHYSICALLY POSSIBLE.

PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPE

WRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT.

G. PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE

TYPEWRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. HAND

WRITTEN SCHEDULES ARE NOT ACCEPTABLE.

H. ALL CONDUIT RUNS INDICATED ARE DIAGRAMMATIC, COORDINATE ROUTING IN ALL SPACES WITH OTHER

TRADES.

I. ALL PANELBOARDS INDICATED ARE HOUSED IN A SINGLE WIDTH ENCLOSURE, UNO. THE CONTRACTOR SHALL

FIELD VERIFY ROOM LAYOUT AND ADJUST ACCORDINGLY, AT NO COST TO THE OWNER, IF PROVIDING ANY

PANELBOARD ENCLOSURES.

J. WHERE POWER AND COMMUNICATION OUTLETS ARE INDICATED IN CLOSE PROXIMITY ON THE DRAWINGS, FIELD COORDINATE THE LOCATIONS TO PLACE THE OUTLETS ADJACENT TO EACH OTHER.

K. ALL EXTERIOR RECEPTACLES SHALL BE LABELED "WR" - WEATHER RESISTANT.

L. WHEN GROUPING MULTIPLE LINE TO NEUTRAL BRANCH CIRCUITS IN A CONDUIT, PROVIDE DEDICATED

COLOR CODED NEUTRAL CONDUCTORS FOR EACH CIRCUIT. DO NOT USE BREAKER TIES AND SHARED

NEUTRALS EVEN THOUGH PERMITTED BY NEC.

M. PROVIDE A 2” WIDE YELLOW LINE PAINTED ON THE FLOOR INDICATING THE ELECTRICAL WORKING SPACE. IN

FRONT OF ALL ELECTRICAL PANELS IN ELECTRICAL ROOMS. REFER TO PLANS FOR ELECTRICAL WORKING

SPACE DETAILS. STENCIL “NO STORAGE” IN 2” HIGH, YELLOW LETTERS CENTERED IN THE OUTLINED AREA.

GENERAL NOTES

A123

SPACE NUMBER

BUILDING AREA (WHEN USED)

SPACE IDENTIFICATION TAG

GRAPHICS SYMBOLS LEGEND

E4.1

E3.1

E5.1

DETAIL TITLE

1/4"=1'-0"

E5.1E2.2

SECTION TITLE

1/4"=1'-0"

E4.1

SECTION NUMBER

DRAWING WHERE SECTION IS INDICATED

SECTION WHERE CUT

ENLARGED PLAN NUMBER

DRAWING WHERE ENLARGED PLAN IS INDICATED

ENLARGED PLAN WHERE CUT

DETAIL NUMBER

DRAWING WHERE DETAIL IS INDICATED

DETAIL TAG

DETAIL NUMBER

DRAWING WHERE DETAIL IS INDICATED

DRAWING WHERE DETAIL IS CUT

ADDITIONAL DRAWING REFERENCES

E2.3

E2.4

SECTION NUMBER

DRAWING WHERE SECTION IS INDICATED

DRAWING WHERE SECTION IS CUT

ADDITIONAL DRAWING REFERENCES

E2.2

E2.3

E2.4

SYMBOL DESCRIPTION

LIGHTING LEGEND

LIGHT SWITCH, RATED 120/277 VOLTS, 20-AMPS, MOUNT AT +3'-10"AFF. SUBSCRIPT/SUPERSCRIPT

LETTERS, NUMBERS, AND SYMBOLS INDICATES SWITCH TYPE AS FOLLOWS:

3 INDICATES 3-WAY LIGHT SWITCH

4 INDICATES 4-WAY LIGHT SWITCH

D INDICATES DIMMER SWITCH

P INDICATES PILOT LIGHT, ON WHEN SWITCH IS ON

K INDICATES KEY OPERATED LIGHT SWITCH

OS INDICATES SWITCH WITH INTEGRAL OCCUPANCY SENSOR

OD INDICATES DIMMER SWITCH WITH INTEGRAL OCCUPANCY SENSOR

OS INDICATES DUAL RELAY INTEGRAL OCCUPANCY SENSOR, WIRED

FOR MULTI-LEVEL SWITCHING

LOWER CASE LETTER INDICATES LIGHT FIXTURE CONTROL DESIGNATION

OMNI-DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, CEILING MOUNT.

PHOTOELECTRIC CELL FOR LIGHTING CONTROL. WALL MOUNT AT +10-0"AFF. AIM NORTH.PE

LIGHT FIXTURE, CEILING MOUNT.

LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT.

LIGHTING FIXTURE.

LIGHTING FIXTURE ON EMERGENCY POWER.

LIGHT FIXTURE, WALL MOUNT, HEIGHT AS INDICATED.

EXIT SIGN, CEILING MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.

EXIT SIGN, WALL MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.

SYMBOL DESCRIPTION

ONE LINE DIAGRAM LEGEND

CIRCUIT BREAKER

FUSED SWITCH

TRANSFORMER

TRANSFER SWITCH

FEEDER DESIGNATIONXXX

CURRENT TRANSFORMERCT

PT POTENTIAL TRANSFORMER

SYMBOL DESCRIPTION

POWER LEGEND

APPLIANCE RECEPTACLE, MOUNT AT +1'-6" AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOR

EQUIPMENT SERVED.

APPLIANCE RECEPTACLE, MOUNT AT +1'-6"AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOR

EQUIPMENT SERVED. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE

RED DEVICE.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER,

PROVIDE RED DEVICE.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF.

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE

RED DEVICE.

DUPLEX RECEPTACLE, NEMA 5-20R, RECESS FLOOR MOUNT.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. PROVIDE NEMA 3R "WHILE IN USE"

ENCLOSURE.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.

POWER/COMMUNICATIONS RECESSED FLOOR BOX. SUBSCRIPT NUMBER INDICATES OUTLET TYPE.

REFER TO DETAIL ON E4 SERIES DRAWINGS.

POWER/COMMUNICATIONS RECESSED FLOOR BOX. CONNECT TO EMERGENCY POWER, PROVIDE RED

DEVICES. SUBSCRIPT NUMBER INDICATES OUTLET TYPE. REFER TO DETAIL ON E4 SERIES DRAWINGS.

[NON-] METALLIC SURFACE RACEWAY, DEVICES AS INDICATED, MOUNT AT +1'-6"AFF, UNO.

JUNCTION BOX, CONCEALED ABOVE CEILING, UNO.

ENCLOSED CIRCUIT BREAKER, CHARACTERISTICS AS INDICATED.

MUSHROOM SWITCH, HEAVY DUTY WITH LEGEND PLATE. MOUNT W/HANDLE AT +3'-10" AFF, UNO.

MANUAL MOTOR STARTER, OVERLOAD PROTECTION AS REQUIRED PER NAME PLATE RATINGS, WITH

'ON' INDICATOR PILOT LIGHT. FLUSH MOUNT W/HANDLE AT +3'-10"AFF, UNO.

DISCONNECT SWITCH, FUSIBLE OR NON-FUSIBLE AS INDICATED. MOUNT W/HANDLE AT +4'-6"AFF, UNO.

MAGNETIC MOTOR STARTER, WITH OVERLOAD RELAYS AS REQUIRED TO SERVE MANUFACTURER

REQUIREMENTS OF EQUIPMENT SERVED. PROVIDE WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH

AND INDICATOR LIGHTS.. MOUNT W/HANDLE AT +4'-6"AFF, UNO.

COMBINATION MAGNETIC STARTER AND DISCONNECT SWITCH. WITH OVERLOAD ELEMENTS AND

FUSING AS REQUIRED TO SERVE MANUFACTURER REQUIREMENTS OF EQUIPMENT SERVED. PROVIDE

WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH AND INDICATOR LIGHTS.. MOUNT W/HANDLE AT +

4'-6"AFF, UNO.

EQUIPMENT POWER CONNECTION.

CONNECTION TO DIV 23 MOTORIZED DAMPER, VERIFY LOCATION.

POWER FOR ELECTRIC DOOR LOCK CONNECTION.

BRANCH CIRCUIT RUN CONCEALED, UNO. DASHED INDICATES CIRCUITRY REQUIRED TO BE RUN BELOW

SLAB.

STRAIGHT LINEWORK FOR CIRCUITRY INDICATES ON EMERGENCY POWER CIRCUIT. INDICATED FOR

CLARITY ONLY, ACTUAL HOMERUN DESIGNATION OVERRIDES THIS SYMBOLOGY.

BRANCH CIRCUIT HOME RUN TO PANELBOARD AND CIRCUIT INDICATED.

PANELBOARD.

TRANSFORMER, PROVIDE CONCRETE HOUSEKEEPING PAD UNLESS NOTED OTHERWISE.

RELAY, N/O OR N/C AS INDICATED.

RELAY, NORMALLY OPEN.

RELAY, NORMALLY CLOSED.

J

CB

E

M

EL

T

R

POWER FOR ELECTRIC DOOR STRIKE CONNECTION.ES

FEEDER TAG. REFER TO FEEDER SCHEDULE ON DWG E5.1.XXX

SYMBOL DESCRIPTION

FIRE ALARM LEGEND

FIRE ALARM AUDIO/VISUAL (SPEAKER STROBE) NOTIFICATION DEVICE, MOUNT AT 80” AFF AND NOT

MORE THAN 96”. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, 80” AFF AND NOT MORE THAN 96”. SUBSCRIPT

NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM MANUAL PULL STATION, MOUNT AT +3'-10"AFF.

FIRE ALARM SLAVE CONTROL PANEL (FASP)

F

FIRE ALARM DUCT SMOKE DETECTOR, FURNISH AND CONNECT UNDER DIVISION 28. INSTALL UNDER

DIVISION 23. VERIFY LOCATION WITH DIVISION 23 PRIOR TO ROUGH-IN. PROVIDE ACCESSIBLE KEY

OPERATED REMOTE TEST SWITCH FOR EACH DETECTOR.

SMOKE DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.

HEAT DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.

S

H

FIRE ALARM TAMPER SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.TS

FIRE ALARM FLOW SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.FS

POST INDICATOR VALVE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.PV

FIRE ALARM PRESSURE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.PS

FIRE ALARM REMOTE INDICATOR, CEILING MOUNT.RI

FIRE ALARM MONITOR MODULE. NOT ALL MONITOR MODULES ARE INDICATED ON DRAWINGS. PROVIDE

QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED MONITORING FUNCTIONS.

M

C

FIRE ALARM CONTROL MODULE. NOT ALL CONTROL MODULES ARE INDICATED ON DRAWINGS.

PROVIDE QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED CONTROL FUNCTIONS.

FIRE ALARM SPRINKLER BELL, MOUNT AT +10'-0"AFF.B

FIRE ALARM MAGNETIC DOOR HOLDER, WALL MOUNT DEVICE AT 6" BELOW TOP OF DOOR. PROVIDE

HINGED MAGNETIC CATCH PLATE ON DOOR TO MATE WITH DEVICE, COORDINATE LOCATION AND

LENGTH WITH DIVISION 08. PROVIDE CONCEALED 120-VOLT POWER CONNECTION AND FIRE ALARM

CONTROL MODULE IF REQUIRED FOR PROPER OPERATION.

FIRE ALARM DOOR HOLDER/CLOSER HARDWARE UNDER DIVISION 08, MONITOR AND CONTROL

INTERFACE WITH FIRE ALARM UNDER DIVISION 28.

FIRE ALARM/POWER CONNECTION TO DIVISION 23 SMOKE OR FIRE/SMOKE DAMPER. COORDINATE

WITH DIVISION 23. REFER TO TYPICAL FIRE/SMOKE DAMPER DIAGRAM.

SD

M

M

FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE WITH DEVICE GUARD, 80” AFF AND NOT MORE THAN

96”. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING. # / # INDICATES STROBE SETTING AND

REDUCED EFFECTIVE OUTPUT WHEN DEVICE GUARD IS PRESENT.

FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, 80” AFF AND NOT MORE THAN 96”. SUBSCRIPT

NUMBER INDICATES STROBE CANDELA RATING. # / # INDICATES STROVE SETTING AND REDUCED

EFFECTIVE OUTPUT WHEN DEVICE GUARD IS PRESENT.

FIRE ALARM AUDIO/VISUAL (SPEAKER STROBE) NOTIFICATION DEVICE, CEILING MOUNTED.

SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, CEILING MOUNTED. SUBSCRIPT NUMBER

INDICATES STROBE CANDELA RATING.

FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE WITH DEVICE GUARD, CEILING MOUNTED. SUBSCRIPT

NUMBER INDICATES STROBE CANDELA RATING. # / # INDICATES STROBE SETTING AND REDUCED

EFFECTIVE OUTPUT WHEN DEVICE GUARD IS PRESENT.

FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, CEILING MOUNTED. SUBSCRIPT NUMBER

INDICATES STROBE CANDELA RATING. # / # INDICATES STROVE SETTING AND REDUCED EFFECTIVE

OUTPUT WHEN DEVICE GUARD IS PRESENT.

xx xx xx xx xx xx xx xx

C

AO

M

M O N

W E

A LTH OF

V

I R G I N I

P

O

R O F

E

SS I

N

N

AL ENG

I

R E E

M O S E L E Y A R C H

IT

E C T S .C O M

BRIAN C. WELLS

Lic. No. 046269

PROJECT NO:

DATE:

N

O R

F O

L K

S T

R E

E T

R

IC

H

M O

N D

V

A

P H

O N

E

-7

F

A X

-5

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

/2

/2

:0

:3

A

M LEGENDS,

ABBREVIATIONS AND

GENERAL NOTES

H .R

.T . J

R . A

R N

G R

EA

D

IN

ES

S C

EN

TE

R (T

A R

C ) V

IS

IT

O R

S C

EN

TE

R

S . G

E O

R G

E M

A S

O N

D R

A

R L

IN

G

T O

N

V A

E0.1

V A

F M

P N

-0

594303

MAY 27, 2020

ABBREVIATIONS

1P SINGLE PHASE

3P THREE PHASE

3R WEATHERPROOF (NEMA 3R)

A AMPS

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

ATS AUTOMATIC TRANSFER SWITCH

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BKR BREAKER

C CONDUIT

CATV COMMUNITY ANTENNA TELEVISION (CABLE)

CB CIRCUIT BREAKER

CBL CABLE

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CLR CLEAR

CO. COMPANY

COMB COMBINATION

COMM COMMUNICATIONS

CU COPPER

DIA DIAMETER

DISC DISCONNECT

DIV DIVISION

DWG DRAWING

EBH ELECTRIC BASEBOARD HEATER

EC EMPTY CONDUIT

ECS EMERGENCY COMMUNICATIONS STATION

ELEC ELECTRICAL

ELEV ELEVATOR

EPO EMERGENCY POWER OFF

EQ EQUIPMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EX EXISTING

EXT EXTERIOR

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAGP FIRE ALARM GRAPHIC PANEL

FASP FIRE ALARM SLAVE CONTROL PANEL

FAXP FIRE ALARM EXTENDER PANEL

FLA FULL LOAD AMPS

FPMR FUSE PER MANUFACTURERS REQUIREMENTS/RECOMMENDATIONS

FPND FUSE PER NAMEPLATE DATA

G GROUND

GE GROUND FAULT PROTECTION FOR EQUIPMENT, 6-50mA PER NEC 427.22 (PROVIDE ACCESSORY FOR

INDICATED BREAKER)

GFCI GROUND FAULT CIRCUIT INTERRUPT

GFP GROUND FAULT PROTECTION FOR PERSONNEL, 4-6mA (PROVIDE ACCESSORY FOR INDICATED

BREAKER)

HKP HOUSEKEEPING PAD

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

Hz HERTZ

IAW IN ACCORDANCE WITH

IG ISOLATED GROUND

J-BOX JUNCTION BOX

KHFSS KITCHEN HOOD FIRE SUPPRESSION SYSTEM

KHz KILOHERTZ

KVA KILOVOLT AMPS

KW KILOWATTS

KWH KILOWATT HOURS

L LOCKOUT TO PREVENT UNAUTHORIZED SWITCHING (PROVIDE ACCESSORY FOR INDICATED BREAKER)

LC ROUTE CIRCUIT TO LOAD VIA LIGHTING CONTACTOR, REFER TO LC SCHEDULE

LED LIGHT EMITTING DIODE

LTG LIGHTING

LTS LIGHTS

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MH METAL HALIDE

MHz MEGAHERTZ

MIN MINIMUM

ML MAINTENANCE LOCK (PROVIDE ACCESSORY FOR INDICATED BREAKER)

MLO MAIN LUG ONLY

MNS MASS NOTIFICATION SYSTEM

MOCP MAXIMUM OVER CURRENT PROTECTION.

MTD MOUNTED

N NEUTRAL

N/C NORMALLY CLOSED

N/O NORMALLY OPEN

NO. NUMBER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

P PILOT LIGHT (AT THE SWITCH HANDLE)

PBD PANELBOARD

PD PROTECTIVE DEVICE

RCPT RECEPTACLE

REC RECEPTACLE

SEC SECURITY

SPD SURGE PROTECTIVE DEVICE

SPEC. SPECIFICATION(S)

ST SHUNT TRIP, 120V COIL (PROVIDE ACCESSORY FOR INDICATED BREAKER)

SW SWITCH

SWBD SWITCHBOARD

TBB TELECOMMUNICATIONS BONDING BACKBONE

TC TELECOMMUNICATIONS CLOSET

TELECOM TELECOMMUNICATIONS

TGB TELECOMMUNICATIONS GROUNDING BUS BAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR

TYP TYPICAL

UNO UNLESS NOTED (INDICATED) OTHERWISE

V VOLTS

VFD VARIABLE FREQUENCY DRIVE

W WATTS

W/ WITH

WG WIRE GUARD

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

REVISIONS

DATE DESCRIPTION

HC

HCE

IT

ROOM/14

ELEC/MECH

ROOM / 16

SECURITY ROOM

EAST WING AREA "B"

GROUND FLOOR

EXISTING FACP

MECH ROOM

WEST WING AREA "C"

LOWER FLOOR

EXISTING DISTRIBUTION PANEL "EMDPW

EXISTING DISTRIBUTION PANEL "MDPWD"

CLASSFIED PROCESSING ROOM

WEST WING AREA "D"

LOWER FLOOR

IT

bufpqfkd=_rfiafkd=lkb

TELE CLOSET

WEST WING AREA "C"

LOWER FLOOR

TRANSFORMER ROOM

WEST WING AREA "C"

LOWER FLOOR

SECTION B-B

SECTION A-A

SECTION B-B

FASP

SECTION B-B

FINISHED GRADE

1'-6"

6"UNDERGROUND WARNING

TAPE

UNDER ROADWAYS/DRIVES WITH VEHICULAR TRAFFIC:

PROVIDE 4000 PSI CONCRETE UNDER ROADWAYS AND DRIVEWAYS WITH VEHICULAR TRAFFIC.

PROVIDE CONDUIT SPACERS EVERY 6'-0"

ELSEWHERE:

VDOT #10 SCREENINGS OR APPROVED ENGINEERED FILL THROUGHOUT

PROVIDE CONDUIT SPACERS EVERY 6'-0"

SCH 80 PVC CONDUIT

(TYP OF 2)

5" 7" 5"

6"

6"

FINISHED GRADE

1'-6"

6"UNDERGROUND WARNING

TAPE

UNDER ROADWAYS/DRIVES WITH VEHICULAR TRAFFIC:

PROVIDE 4000 PSI CONCRETE UNDER ROADWAYS AND DRIVEWAYS WITH VEHICULAR TRAFFIC.

PROVIDE CONDUIT SPACERS EVERY 6'-0"

ELSEWHERE:

VDOT #10 SCREENINGS OR APPROVED ENGINEERED FILL THROUGHOUT

PROVIDE CONDUIT SPACERS EVERY 6'-0"

SCH 80 PVC CONDUIT

5" 5"

6"

6"

C

AO

M

M O N

W E

A LTH OF

V

I R G I N I

P

O

R O F

E

SS I

N

N

AL ENG

I

R E E

M O S E L E Y A R C H

IT

E C T S .C O M

BRIAN C. WELLS

Lic. No. 046269

PROJECT NO:

DATE:

N

O R

F O

L K

S T

R E

E T

R

IC

H

M O

N D

V

A

P H

O N

E

-7

F

A X

-5

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

/2

/2

:0

:3

A

M ELECTRICAL SITE PLAN

H .R

.T . J

R . A

R N

G R

EA

D

IN

ES

S C

EN

TE

R (T

A R

C ) V

IS

IT

O R

S C

EN

TE

R

S . G

E O

R G

E M

A S

O N

D R

A

R L

IN

G

T O

N

V A

E1.0

V A

F M

P N

-0

594303

MAY 27, 2020

1" = 20'-0"

FLOOR PLAN - ELECTRICAL SITE PLAN

GENERAL NOTES

REPRESENTED BY n

APPLIES TO DRAWINGS E1.0

KEYNOTES

A. REFER TO CIVIL PLANS FOR EXACT CONDUIT ROUTES.

1. DUCTBANK SHALL BE USED OUTDOOR.

2. PROVIDE CONDUITS/WIRES AS INDICATED ON E5.1 FROM "HC" TO EXISTING PANEL "MDPWD".

3. PROVIDE CONDUITS/WIRES AS INDICATED ON E5.1 FROM "HCE" TO EXISTING PANEL

"EMDPW" .

4. PROVIDE (1) 4" CONDUITS FROM SECURITY ROOM TO EXISTING FIRE ALARM CONTROL

PANEL "FACP".

5. PROVIDE (1) 4" CONDUITS FROM IT ROOM TO THE EXISTING SYSTEM LOCTAED IN CLASSIFIED

PROCESSING ROOM .

6. PROVIDE (1) 4" CONDUITS FROM TELE CLOSET TO THE EXISTING SYSTEM LOCTAED IN TELE

CLOSET.

NO SCALE

DUCTBANK SECTION - A-A

NO SCALE

DUCTBANK SECTION - B-B

F E C

FEC

D

3D

D

3D

O D

OS

OD

OS

O S

OS

3 3D

D

3D

O D

D

D

OD

O D

4D

4D

F E C

FEC

E

E

CAC OFFICE

08 SUPERVISOR

OFFICE

IT ROOM

ELEC/MECH

ROOM

VISITOR

CORRIDOR

STAFF TOILET

SECURITY

SCREENING

VESTIBULE

JANITORS

CLOSET

WAITING

ROOM

HELP DESK

CAC

RECEPTIONIST

EXTERIOR

GARDEN

BREAK ROOM

X1

X2C

X1

H

H

WE

WE

WE

ADMIN WORK

AREA

PUBLIC TOILET

ADMIN

WORKSTATION

X1 X1

A

BE

B B

B

BE

BB

B

B

B B

B

A

WE

B

B

BE B

BE B

BEBE

B

A

A

AEA

AE

A

AE

H H

C1

X1

F F

X3

WE

X1

DE DE

C1 C1

B B

B A

P

P

P

D

D

D

D

D D

D D

D D

D

D

A B

B

A

A

A

A

B BEB

A

A A

A

C

CE

C

C C

C

C

CE C

A

B B

B B

STAFF

CORRIDOR

PEDESTRIAN

CHECK

WINDOW

03B

B B

B B B

CE

ELCP-1

(HCE-2)

ELCP-3

(HCE-2)

ELCP-2

(HCE-2)

ELCP-2

(HCE-2)

ELCP-2

(HCE-2)

ELCP-2

(HCE-2)

ELCP-2

(HCE-2)

B A a a a aa a a a a a a a a a a a a a b b b b b b b b c c c c c cc c c d d dd d d d d d d dd dd d d e e e e a d d

X1

CAC OFFICE

SUPERVISOR

OFFICE

ADMIN WORK

AREA

IT ROOM

ELEC/MECH

ROOM

VISITOR

CORRIDOR

PUBLIC TOILET

STAFF TOILET

SECURITY

SCREENING

VESTIBULE

JANITORS

CLOSET

WAITING

ROOM

HELP DESK

CAC

RECEPTIONIST

EXTERIOR

GARDEN

BREAK ROOM

DSS-1A

TU1-1

TU1-2

TU1-5

TU1-3

ECP-1

EWH

TU1-4

EUH-1

EUH-2

DSS-1B

F-1

RTU-1

MOUNT ON

AC UNIT.

LC-22

F-2

C

AO

M

M O N

W E

A LTH OF

V

I R G I N I

P

O

R O F

E

SS I

N

N

AL ENG

I

R E E

M O S E L E Y A R C H

IT

E C T S .C O M

BRIAN C. WELLS

Lic. No. 046269

PROJECT NO:

DATE:

N

O R

F O

L K

S T

R E

E T

R

IC

H

M O

N D

V

A

P H

O N

E

-7

F

A X

-5

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

/2

/2

:0

:4

A

M FLOOR PLAN - LIGHTING

,MECHANICAL POWER, &

ROOF ELECTRICAL

H .R

.T . J

R . A

R N

G R

EA

D

IN

ES

S C

EN

TE

R (T

A R

C ) V

IS

IT

O R

S C

EN

TE

R

S . G

E O

R G

E M

A S

O N

D R

A

R L

IN

G

T O

N

V A

E2.1

V A

F M

P N

-0

594303

MAY 27, 2020

1/8" = 1'-0"

FLOOR PLAN - LIGHTING

1/8" = 1'-0"

FLOOR PLAN - MECHANICAL POWER

1/8" = 1'-0"

ROOF -ELECTRICAL

DIV. 22 & 23 EQUIPMENT ELECTRICAL SCHEDULE - E2.1

NAME VOLTAGE PHASE P/BD CKT DISCONNECTING MEANS FEEDER SIZE NOTES

DSS-1A 208 V 1 NOTE 1 3#10,#10G,3/4"C FED FROM OUTDOOR UNIT ON ROOF

DSS-1B 208 V 1 LC 19,21 NOTE 5 3#10,#10G,3/4"C

ECP-1 120 V 1 LC 18 NOTE 2 2#12,#12G,3/4"C

EUH-1 208 V 1 LC 23,25 NOTE 1 3#10,#10G,3/4"C

EUH-2 208 V 1 LC 24,26 NOTE 1 3#12,#12G,3/4"C

EWH 480 V 3 HC 2,4,6 NOTE 2 4#6,#10G,1"C

F-1 120 V 1 LC 20 NOTE 1 2#12,#12G,3/4"C

F-2 120 V 1 LC 27 NOTE 1 2#12,#12G,3/4"C

RTU-1 480 V 3 HC 20,22,24 NOTE 1 4#6,#10G,1"C

TU1-1 480 V 3 HC 8,10,12 NOTE 3 4#12,#12G,3/4"C

TU1-2 480 V 3 HC 9,11,13 NOTE 3 4#12,#12G,3/4"C

TU1-3 480 V 3 HC 14,16,18 NOTE 3 4#12,#12G,3/4"C

TU1-4 480 V 3 HC 15,17,19 NOTE 3 4#12,#12G,3/4"C

TU1-5 277 V 1 HC 7 NOTE 4 2#12,#12G,3/4"C

GENERAL NOTES

REPRESENTED BY n

APPLIES TO DRAWINGS E2.1

KEYNOTES

A. ALL EXIT SIGNS AND EGRESS LIGHT FIXTURES(TYPE WITH "E") SHALL BE ON UN-SWITCHED

HEC-3 UNLESS NOTED OTHERWISE.

B. ALL NORMAL LIGHT FIXTURES (TYPE WITHOUT "E") SHALL BE ON CIRCUIT HCE-6 UNLESS

NOTED OTHERWISE.

B. COORDINATE LOCATION OF ALL DISCONNECTS, CONTROL PANELS, & ELECTRICAL

CONNECTIONS WITH MECHANICAL AND PLUMBING CONTRACTORS.

NOTES:

1. PROVIDED BY DIVISION 23.

2. PROVIDED BY DIVISION 22.

3. PROVIDE A NEMA 1 ,480V/3P, 30A NON -FUSIBLE DISCONNECT, WALL MOUNT OR UNIT MOUNT ABOVE CEILING. LOCATION SHALL BE FIELD DETERMINED.

4. PROVIDE A NEMA 1, 480V/1P, 30A NON -FUSIBLE DISCONNECT, WALL MOUNT OR UNIT MOUNT ABOVE CEILING. LOCATION SHALL BE FIELD DETERMINED.

5. PROVIDE A NEMA 3R, 208V/2P, 30A NON -FUSIBLE DISCONNECT, WALL MOUNT OR UNIT MOUNT. LOCATION SHALL BE FIELD DETERMINED.

1. REFER TO LIGHTING CONTACTOR DETAIL ON E4.1 FOR ADDITIONAL INFORMATION.

F

C

FEC

E

E

E L

E L

E L

EL

EL

E L

EL

E L

EL

E L

EL

J

J

E L

E

F E C

FEC

F

F

FF

F

F

WA

WA

WA

S S

S

S

S

S

S

S

S

S S

S

S D

CAC OFFICE

SUPERVISOR

OFFICE

ADMIN WORK

AREA

ELEC/MECH

ROOM

VISITOR

CORRIDOR

PUBLIC TOILET

STAFF TOILET

SECURITY

SCREENING

VESTIBULE

JANITORS

CLOSET

WAITING

ROOM

HELP DESK

CAC

RECEPTIONIST

EXTERIOR

GARDEN

BREAK ROOM

METAL

DETECTOR

CONCRETE PAD

LC

HC

TC

HCE

LCE

TCE

X-RAY

ELCP

AUTO

DOOR

AUTO

DOOR

PEDESTRIAN

CHECK

WINDOW

03B

3LC-1

LC-2

LC-3

LC-4

LCE-8

LCE-7

LCE-5

LCE-6

LCE-4

LCE-4

LCE-4

LCE-3

LCE-3

LCE-3

LCE-3

LCE-2

LCE-2 LCE-2

LC-5 LC-5

LC-5

LC-6

LC-6

LC-6

LC-6

LC-6

LC-6

LC-7

LC-7

LC-7

LC-7

LC-7

LC-8

LC-9

LC-9

LC-9

LC-9 LC-9

LC-9

LC-10

LC-10

LC-10

LC-10

LC-11

LC-10

LC-10

LC-12

LC-12

LC-12

LC-12

LC-13

LC-13

LC-13

LC-13

LC-13

LC-17

LC-16

LC-15

LC-14

LC-12 LC-12

60"AFF

FASP

LCE-9

IT ROOM

ADMIN

WORKSTATION

STAFF

CORRIDOR

LC-7

60"AFF

CAC OFFICE

SUPERVISOR

OFFICE

ADMIN WORK

AREA

IT ROOM

ELEC/MECH

ROOM

VISITOR

CORRIDOR

PUBLIC TOILET

STAFF TOILET

SECURITY

SCREENING

VESTIBULE

JANITORS

CLOSET

WAITING

ROOM

04 HELP DESK

CAC

RECEPTIONIST

EXTERIOR

GARDEN

BREAK ROOM

PEDESTRIAN

CHECK

WINDOW

03B

TGB

FASP

LOC

60" AFF

WP

60" AFF

C

AO

M

M O N

W E

A LTH OF

V

I R G I N I

P

O

R O F

E

SS I

N

N

AL ENG

I

R E E

M O S E L E Y A R C H

IT

E C T S .C O M

BRIAN C. WELLS

Lic. No. 046269

PROJECT NO:

DATE:

N

O R

F O

L K

S T

R E

E T

R

IC

H

M O

N D

V

A

P H

O N

E

-7

F

A X

-5

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

/2

/2

:0

:4

A

M FLOOR PLAN - POWER &

LOW VOLTAGE SYSTEMS

H .R

.T . J

R . A

R N

G R

EA

D

IN

ES

S C

EN

TE

R (T

A R

C ) V

IS

IT

O R

S C

EN

TE

R

S . G

E O

R G

E M

A S

O N

D R

A

R L

IN

G

T O

N

V A

E2.2

V A

F M

P N

-0

594303

MAY 27, 2020

1/4" = 1'-0"

FLOOR PLAN - POWER

1/8" = 1'-0"

FLOOR PLAN - LOW VOLTAGE SYSTEMS

GENERAL NOTES

REPRESENTED BY n

APPLIES TO DRAWINGS E2.2

KEYNOTES

A. REFER TO ARCHITECTUAL DRAWINGS FOR EXACT LOCATIONS OF RECEPTACLES AND

JUNCTION BOXES.

1. PROVIDE/INSTALL 4' X 8' X 3/4" FIRE RATED TELECOM PLYWOOD BACK BOARD AT 24" AFF.

2. REFER TO DRAWING E4.1 FOR EXTERIOR LIGHT CONTROL PANEL DETAILS

3. PROVIDE CIRCUIT LCE-1 FOR ELECTRIC LOCKS. REFER TO SECURITY DRAWINGS

FOR ADDITIONAL INFORMATION.

4. REFER TO FIRE ALARM RISER DIAGRAM ON E4.2 FOR ADDITIONAL INFORMATION.

5. REFER TO E5.1 FOR ADDITIONAL INFORMATION.

3'-6" (480V)

MIN 3' - 0" (208V)

O F E

Q

UIP

M

ENTM

IN

IM

UM

2' -

" T O W

ID

TH

DEDICATED

ELECTRICAL

SPACE

ELECTRICAL

EQUIPMENT

REFER TO NEC ARTICLE 110-26

FOR ADDITIONAL

INFORMATION

RGS CONDUIT ELBOW

PVC CONDUIT

EMT CONDUIT

SLAB

POROUS FILL

EARTH

PVC CONDUIT

EMT CONDUIT

SLAB

POROUS FILL

EARTH

RGS CONDUIT ELBOW

WALL

SLAB

FINISHED FLOOR

(2) 1" CONDUITS

UNLESS OTHERWISE INDICATED

FLOOR BOX

WALL/PARTITION CAVITY

2.5" DEEP 2-GANG OUTLET BOX

WITH SINGLE GANG PLASTER RING

WALL/PARTITION FACE

1.25" CONDUIT MINIMUM

SIZE OR AS INDICATED

TERMINATE CONCEALED 6" ABOVE

ACCESSABLE CEILING WITH

NYLON BUSHING

FINISHED CEILING

6"

PROVIDE FIRESTOP SLEEVE EQUAL TO

HILTI MODEL CP-653-2". INSTALL IN

ACCORDANCE WITH MFR'S

RECOMMENDATIONS.

FINISHED ACCESSIBLE CEILING

W A L L

CORE DRILL HOLE, FIRE

SEAL ANNULAR SPACE

AROUND SLEEVE.

WIREMOLD FS2R-RED AND

FS4R-RED ARE SIMILAR

ACCEPTABLE PRODUCTS

NOTE:

REFER TO LS LIFE SAFETY

DRAWINGS FOR WHICH

WALLS ARE RATED AND UN-

RATED

2" CONDUIT

SLEEVE

6"

2" CONDUIT SLEEVE, UIO.

FINISHED ACCESSIBLE CEILING

W A L L

CORE DRILL HOLE, FIRE

SEAL ANNULAR SPACE

AROUND SLEEVE.

NYLON BUSHING

NOTE:

REFER TO LS LIFE SAFETY

DRAWINGS FOR WHICH

WALLS ARE RATED AND UN-

RATED

3" MIN EACH SIDE

NOTE:

FILL 2" INSIDE EACH END OF

CONDUIT SLEEVES WITH

BATT INSULATION FOR

SOUND TRANSMISSION

REDUCTION

WHITE

(NEUTRAL)

RED

(LINE)

N

WHITE

HOT

BLACK

POWER

PACK

R E D

B L K

B L U

RED (LOAD)

OFF SWITCH

BLU CONTROL OUTPUT

BLK COMMON

RED +24VDC

OCCUPANCY SENSORB

L U

B L K

SLAVE

PACK

RED (LOAD)

RED (LINE) OFF SWITCH

LOAD

HOT

NEUTRAL

LOAD

H

N

COIL

LINE

LOAD

H

A

SPECIFIED

TIME

CLOCK

C

N

LED

PILOT

LIGHT

CTRL CKT

PHOTOCELL LOCATED

ON ROOF REFER TO

SPECIFICATIONS

HCE-2

CONTACTOR#

ELCP-1

EXTERIOR LIGHTING CONTROL PANEL - ELCP

CKT # DESCRIPTION PHOTOCELL

(CTRL CKT : HCE-2)

H- HAND SWITCH

O-OFF SWITCH

A- AUTO SWITCH

LOCATION: ELEC/MECH 16

X

X

X

X

X

X

SPARE

EXTERIOR BUILDING SIGN LIGHTS

EXTERIOR LIGHTS

EXTERIOR LIGHTS

SPARE

SPARE

C K

T

C K

T

C K

T

C K

T

C K

T

C K

T

N

H

L C

P -1

C

-2

C

-3

C

-4

C

-5

C

P -6

ELCP-2

ELCP-3

ELCP-4

ELCP-5

ELCP-6

HCE-2

HCE-2

TOGGLE SWITCH WITH PILOT LIGHT:

OR DISCONNECT SWITCH (REF

COORDINATION SCHEDULE) BY DIV

26. 6" ABOVE ACCESSIBLE CEILING.

RIB COIL CONTROL NEARBY BAS

PANEL ALSO SERVING OTHER

EQUIPMENT. DIV 23 VERIFY

LOCATION.

RIB FURNISHED BY

DIV 15, INSTALLED

AND WIRED BY DIV

26.

EQUIPMENT FURNISHED AND

INSTALLED BY DIV 15. LINE

VOLTAGE CIRCUITRY BY DIV

26.

LINE VOLTAGE WIRING, BY DIV 26 IN

CONDUIT

LOW VOLTAGE WIRING, BY DIV 23

TMGB

TGB

#3/O

EXISTING TMGB IN BUILDING ONE

1-1/8"

3-1/2"

1/4" THICK ELECTROTIN

PLATED COPPER BUSBAR

FIBERGLASS

BUSHING

9/32" DIA

4"

10"

1"

FINISHED FLOOR

WALL/PARTITION CAVITY

2.5" DEEP 2-GANG OUTLET BOX

WITH SINGLE GANG PLASTER RING - 18" AFF

WALL/PARTITION FACE

1.25" CONDUIT MINIMUM

SIZE OR AS INDICATED

TERMINATE CONCEALED 6" ABOVE

ACCESSABLE CEILING WITH

NYLON BUSHING

FINISHED CEILING

2.5" DEEP 2-GANG OUTLET BOX

WITH SINGLE GANG PLASTER RING 5'-6' AFF

PLAN

SYMBOL

PROVIDE A DUPLEX POWER OUTLET

ADJACENT TO COMM OUTLET

SUPPORT TIE WIRE FROM BOTTOM

CHORD OF STRUCTURE. VERIFY

ACTUAL BUILDING STRUCTURE AND

PROVIDE SUPPLEMENTAL FRAMING FOR

ATTACHMENT OF HANGER WIRES.

REFER TO FIREPROOFING NOTE.

JUNCTION BOX WITH COVER

AND IDENTIFICATION, MOUNT

TO STRUCTURE. REFER TO

FIREPROOFING NOTE.

PROVIDE STEEL TIE WIRE AT

ALL 4 SIDES OF

FIXTURE TO STRUCTURE,

INDEPENDENT OF CEILING.

SUPPORT WIRES SHALL BE

IDENTIFIED WITH ORANGE

SPRAY PAINT. REFER TO

FIREPROOFING NOTE.

MAXIMUM 6'-0" LONG MC

CABLE OR FLEXIBLE CONDUIT.

SUPPORT IAW SPECIFICATIONS

FIREPROOFING NOTE:

THIS DETAIL APPLIES TO UNPROTECTED

STRUCTURE ONLY. IF THE BUILDING

STRUCTURE REQUIRES FIREPROOFING,

INSTALL BOXES AND CONDUIT WITH A

METHOD THAT MAINTAINS THE INTEGRITY

OF THE FIREPROOFING METHOD.

COORDINATE METHOD AND SCHEDULING

WITH DIVISION 7.

BRANCH CIRCUIT CONDUIT,

SUPPORT IAW SPECIFICATIONS

RECESSED, LAY-IN TYPE,

LED LIGHT FIXTURE.

SECURE TO GRID W/ 2 SHORT SCREWS

AT EACH END, AVOID CONFLICT WITH

FIXTURE OPERATION AND MAINTENANCE

SUSPENDED CEILING

TILE-TYPICAL

C

AO

M

M O N

W E

A LTH OF

V

I R G I N I

P

O

R O F

E

SS I

N

N

AL ENG

I

R E E

M O S E L E Y A R C H

IT

E C T S .C O M

BRIAN C. WELLS

Lic. No. 046269

PROJECT NO:

DATE:

N

O R

F O

L K

S T

R E

E T

R

IC

H

M O

N D

V

A

P H

O N

E

-7

F

A X

-5

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

/2

/2

:0

:4

A

M ELECTRICAL DETAILS

H .R

.T . J

R . A

R N

G R

EA

D

IN

ES

S C

EN

TE

R (T

A R

C ) V

IS

IT

O R

S C

EN

TE

R

S . G

E O

R G

E M

A S

O N

D R

A

R L

IN

G

T O

N

V A

E4.1

V A

F M

P N

-0

594303

MAY 27, 2020

NO SCALE

EQUIPMENT CLEARANCES

NO SCALE

PVC TO EMT TRANSITION DETAIL

NO SCALE

TELECOMMUNICATIONS

OUTLET CONDUIT DETAIL

NO SCALE

RATED WALL CONDUIT SLEEVE DETAIL

NO SCALE

UN-RATED WALL CONDUIT SLEEVE DETAIL

NO SCALE

OCCUPANCY SENSOR DIAGRAM

AUXILARY RELAY PACK SENSOR

NO SCALE

LIGHTING CONTACTOR DETAIL - TIME CLOCK AND PHOTOCELL

NO SCALE

TYPICAL EXHAUST FAN

CONNECTION DIAGRAM

NO SCALE

TGB GROUNDING SYSTEM DIAGRAM

NO SCALE

TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) DETAIL

NO SCALE

CATV OUTLET CONDUIT DETAIL

NO SCALE

RECESSED, LAY-IN, LED

LIGHT FIXTURE MOUNTING DETAIL

BAS

C

COIL

SYSTEMS WITH MULTIPLE MOTORS REQUIRE ONE SHUTDOWN RELAY FOR EACH STARTER OR VFD. THERE MAY BE MORE THAN ONE DUCT SMOKE DETECTOR PER SYSTEM, BUT ONLY ONE CONTROL MODULE IS REQUIRED PER MOTOR. SHUTDOWN IS VIA

CONTROL MODULE, NOT VIA DUCT DETECTOR AUX CONTACTS. COORDINATE W/ DIV 23.

UNDER NORMAL CONDITIONS, FA SYSTEM POWERS THE NORMALLY OPEN FA CONTROL MODULE CONTACT TO THE CLOSED

POSITION TO ALLOW NORMAL UNIT CONTROL BY BAS.

UPON ALARM SIGNAL FROM THE FIRE ALARM SYSTEM, THE CONTACTS IN THE FA SYSTEM RELEASES CONTROL MODULE TO OPEN POSITION, CAUSING SHUTDOWN OF ASSOCIATED HVAC EQUIPMENT. HVAC EQUIPMENT SHALL NOT BE OPERABLE UNTIL FA

CONTROL MODULE IS RESET TO NORMAL CLOSED POSITION.

DIVISION 23 SHALL PROVIDE WIRING BETWEEN FA AND BAS CONTROL MODULES AND HVAC EQUIPMENT CONTROLLER (STARTER, VFD, OR INTEGRAL CONTROL PANEL).

FIRE ALARM ADDRESSABLE CONTROL

MODULE INSTALLATION AND FA

CONTROL WIRING BY DIV 28.

LINE/24 VOLT TRANSFORMER

INTEGRAL WITH HVAC UNIT,

STARTER, OR VFD (VARIES

BY UNIT).

H

N

UNIT

LINE

VOLTAGE

MECHANICAL CONTROL RELAY FURNISHED AND

INTERLOCK WIRING WITH MECH EQUIPMENT BY DIV

23. INSTALLATION AND POWER WIRING BY DIV 26.

STARTER CONTROL COIL (OR

EQUIVALENT CONTROLLER

FOR EQUIPMENT)

MECHANICAL EQUIPMENT

24V

SD

TV

MOUNT +18" AFF TO

CENTERLINE, UNO.

F-TYPE CONNECTOR FOR

CATV DISTRIBUTION, TO &

FROM LOCAL CATV TYPE 1

DEVICE (IN ROOMS WITH TYPE

1 DEVICE)2-GANG BACKBOX WITH

SINGLE-GANG PLASTER

RING AND COVER

1" CONDUIT WITH BUSHING TO ABOVE ACCESSIBLE

CLG, OR TO LOCAL TYPE 1 CATV WHERE PRESENT

F-TYPE CONNECTOR FOR CATV

DISTRIBUTION (IN ROOMS WITH

NO TYPE 1 CATV DEVICE)

TV

MOUNT +18" AFF TO

CENTERLINE, UNO.

F-TYPE CONNECTOR FOR

CATV DISTRIBUTION, TO &

FROM LOCAL CATV TYPE 1

DEVICE (IN ROOMS WITH TYPE

1 DEVICE)

2-GANG BACKBOX WITH

SINGLE-GANG PLASTER

RING AND COVER

1" CONDUIT WITH BUSHING TO ABOVE ACCESSIBLE

CLG, OR TO LOCAL TYPE 1 CATV WHERE PRESENT

F-TYPE CONNECTOR FOR CATV

DISTRIBUTION (IN ROOMS WITH

NO TYPE 1 CATV DEVICE)

DATA CATEGORY 6, 8-POSITION

MODULAR CONNECTOR FOR

VOICE COMMUNICATIONS

PHONE

CATEGORY 6, 8-POSITION

MODULAR CONNECTOR FOR

VOICE COMMUNICATIONS

2-GANG BACKBOX WITH

SINGLE-GANG PLASTER

RING AND COVER

1" CONDUIT WITH BUSHING TO

ABOVE ACCESSIBLE CLG

+18" AFF TO

CENTERLINE

UNO.

+46" AFF TO

CENTERLINE

UNO.

2 2

DATA

PHONE

+18" AFF TO

CENTERLINE

UNO.

CATEGORY 6, 8-POSITION

MODULAR CONNECTOR FOR

VOICE COMMUNICATIONS

CATEGORY 6, 8-POSITION

MODULAR CONNECTOR FOR

DATA COMMUNICATIONS

2-GANG BACKBOX WITH

SINGLE-GANG PLASTER

RING AND COVER

1" CONDUIT WITH BUSHING TO

ABOVE ACCESSIBLE CLG

+46" AFF TO

CENTERLINE

UNO.

DATA

PHONE

+18" AFF TO

CENTERLINE

UNO.

CATEGORY 6, 8-POSITION

MODULAR CONNECTOR FOR

VOICE COMMUNICATIONSCATEGORY 6, 8-POSITION

MODULAR CONNECTOR FOR

DATA COMMUNICATIONS

2-GANG BACKBOX WITH

SINGLE-GANG PLASTER

RING AND COVER

1" CONDUIT WITH BUSHING TO

ABOVE ACCESSIBLE CLG

+46" AFF TO

CENTERLINE

UNO.

3 3

2 COPPER WIRE CONNECTOR

FOR VOICE COMMUNICATIONS

(EMERGENCY PHONE)

FIRE ALARM

CONTROL

PANEL

(FACP) EOL

PROVIDE QUANTITIES AS REQUIRED

S F SD

EOL

EOL

AUDIBLE NAC

STROBE NAC

EXISTING FIRE ALARM SYSTEM

IN EXISTING BUILDING ONE

NEW IN VISITOR CENTER

2 PHONE LINES

120V

BATTERY

CHARGER

BATTERIES

FIRE ALARM SLAVE CONTROL PANEL (FASP)

(LOC)

(ACU)

C

AO

M

M O N

W E

A LTH OF

V

I R G I N I

P

O

R O F

E

SS I

N

N

AL ENG

I

R E E

M O S E L E Y A R C H

IT

E C T S .C O M

BRIAN C. WELLS

Lic. No. 046269

PROJECT NO:

DATE:

N

O R

F O

L K

S T

R E

E T

R

IC

H

M O

N D

V

A

P H

O N

E

-7

F

A X

-5

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

/2

/2

:0

:4

A

M ELECTRICAL DETAILS

H .R

.T . J

R . A

R N

G R

EA

D

IN

ES

S C

EN

TE

R (T

A R

C ) V

IS

IT

O R

S C

EN

TE

R

S . G

E O

R G

E M

A S

O N

D R

A

R L

IN

G

T O

N

V A

E4.2

V A

F M

P N

-0

594303

MAY 27, 2020

NO SCALE

FIRE ALARM HVAC UNIT SHUTDOWN WIRING DIAGRAM

NO SCALE

CATV OUTLET DETAIL - TYPE 1

NO SCALE

CATV / DATA OUTLET DETAIL - TYPE 2

NO SCALE

TELECOMMUNICATION OUTLET DETAIL - TYPE 2

NO SCALE

TELECOMMUNICATION OUTLET DETAIL - TYPE 1

NO SCALE

TELECOMMUNICATION OUTLET DETAIL - TYPE 3

NO SCALE

FIRE ALARM RISER DIAGRAM

FEEDER

ID

# OF

SETS

BUILDING WIRE

QUANTITY & SIZE TYPE

THHN - DRY

TYPE THWN - WET

MINIMUM

CONDUIT SIZE

COPPER FEEDER SCHEDULE

30 1 3#10,#10 G 3/4"

35 1 3#8,#10 G 3/4"

40 1 3#8,#10 G 3/4"

45 1 3#6,#10 G 1"

50 1 3#6,#10 G 1"

60 1 3#4,#10 G 1"

70 1 3#4,#8 G 1 1/4"

80 1 3#3,#8 G

90 1 3#2,#8 G

100 1 3#1,#8 G

110 1 3#2,#6 G

125 1 3#1,#6 G

150 1 3#1/0,#6 G 2"

175 1 3#2/0,#6 G

200 1 3#3/0,#6 G

225 1 3#4/0,#4 G 2 1/2"

250 1 3-250kCM,#4 G

300 1 3-350kCM,#4 G

350 2 2"

400 2 2"

450 3#4/0,#2 G

600 3"

1000 3

1200 4

1600 5

2000 6

2500 7

1 1/4"

1 1/4"

1 1/4"

1 1/2"

1 1/2"

2"

2"

2 1/2"

2 1/2"

2 1/2"

2 1/2"

4"

3"

4"

3"

4"

4"

4"

3#2/0,#3 G

3#3/0,#3 G

3-250kCM,#2 G

3-350kCM,#1 G

3-500kCM,#1/0 G

3-350kCM,#1/0 G

3-500kCM,#2/0 G

3-350kCM,#3/0 G

3-500kCM,#4/0 G

3-500kCM,#250 G

3-500kCM,#350 G

NOTES:

1. ELECTRICAL CONTRACTOR TO VERIFY CONDUIT SIZE REQUIRED IF WIRE TYPES OTHER

THAN THOSE LISTED ABOVE ARE USED.

2. FEEDER SIZES BASED ON TABLE 310.15(B)(16), 75º C.

3. SIZES ADJUSTED PER NEC 110.14.

FEEDER

ID

# OF

SETS

BUILDING WIRE

QUANTITY & SIZE TYPE

THHN - DRY

TYPE THWN - WET

MINIMUM

CONDUIT SIZE

30Y 1 4#10,#10 G 3/4"

35Y 1 4#8,#10 G 3/4"

40Y 1 4#8,#10 G 3/4"

45Y 1 4#6,#10 G 1"

50Y 1 4#6,#10 G 1"

60Y 1 4#4,#10 G 1"

70Y 1 4#4,#8 G 1 1/4"

80Y 1 4#3,#8 G

90Y 1 4#2,#8 G

100Y 1 4#1,#8 G

110Y 1 4#2,#6 G

125Y 1 4#1,#6 G

150Y 1 4#1/0,#6 G 2"

175Y 1 4#2/0,#6 G

200Y 1 4#3/0,#6 G

225Y 1 4#4/0,#4 G 2 1/2"

250Y 1 4-250kCM,#4 G

300Y 1 4-350kCM,#4 G

350Y 2 2"

400Y 2 2"

450Y 4#4/0,#2 G

500Y

600Y 3"

700Y

800Y

1000Y 3

1200Y 4

1600Y 5

2000Y 6

2500Y 7

1 1/4"

1 1/4"

1 1/4"

1 1/2"

1 1/2"

2"

2"

2 1/2"

2 1/2"

2 1/2"

2 1/2"

4"

3"

4"

3"

4"

4"

4"

4#2/0,#3 G

4#3/0,#3 G

4-250kCM,#2 G

4-350kCM,#1 G

4-500kCM,#1/0 G

4-350kCM,#1/0 G

4-500kCM,#2/0 G

4-350kCM,#3/0 G

4-500kCM,#4/0 G

4-500kCM,#250 G

4-500kCM,#350 G qo^kpclojbo=p`ebarib kVA TYPE PRIMARY SECONDARY

COPPER PRIMARY

FEEDER

BONDING

CONDUCTOR

15 kVA

30 kVA

45 kVA

75 kVA

112.5 kVA

150 kVA

225 kVA

300 kVA

LINEAR

LINEAR

LINEAR

LINEAR

LINEAR

LINEAR

LINEAR

LINEAR

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

480V-3Ø

208Y/120V

208Y/120V

208Y/120V

208Y/120V

208Y/120V

208Y/120V

208Y/120V

208Y/120V

3#10, #10 G, 3/4" C. #8

#6

#6

#2

#2

#2/0

#2/0

#3/0

500 kVA LINEAR 480V-3Ø 208Y/120V #3/0

COPPER SECONDARY

FEEDER

3#6, #10 G, 1" C.

3#4, #8 G, 1-1/4" C.

3#1, #6 G, 1-1/2" C.

3#2/0, #6 G, 2" C.

3#4/0, #4 G, 2-1/2" C.

4#4, #8 G, 1-1/4" C.

4#1, #6 G, 1-1/2" C.

4#1/0, #6 G, 2" C.

4-250kCM, #2 G, 2-1/2" C.

(2 SETS) 3#2/0,

#3 G, 2" C.

(2 SETS) 3#4/0,

#2 G, 2-1/2" C.

(3 SETS) 3-350kCM, #1/0 G, 4" C.

(2 SETS) 4-3/0,

#2 G, 2-1/2" C.

(2 SETS) 4-250kCM, #2/0 G, 2-1/2" C.

(3 SETS) 4-350kCM, #2/0 G, 3" C.

(4 SETS) 4-350kCM, #4/0 G, 4" C.

(6 SETS) 4-350kCM, 300kCM G, 4" C.

EXISTING PANEL "MDPWD"

480/277V, 3P, 1600A MLO

IN TRANSFORMER ROOM LOCATED

IN WEST WING AREA "C" ON LOWER

FLOOR OF EXISTING BUILDING ONE

NEW PANEL "HC"

480/277V, 3P, 225A MCB

IN ELEC/MECH ROOM LOCATED

IN VISITORS CENTER

225A/3P

NEW XFMR "TC" 45KVA

IN ELEC/MECH ROOM LOCATED

IN VISITORS CENTER

NEW PANEL "LC"

120/208V, 3P, 150A MCB

IN ELEC/MECH ROOM LOCATED

IN VISITORS CENTER

NORMAL POWER ONE-LINE RISER DIAGRAM

70A/3P

150A/3P

EXISTING PANEL "EMDPW"

480/277V, 3P, 800A MLO

IN MECH ROOM LOCATED

IN WEST WING AREA "C" ON

LOWER FLOOR

OF EXISTING BUILDING ONE

NEW PANEL "HCE"

480/277V, 3P, 60A MCB

IN ELEC/MECH ROOM LOCATED

IN VISITORS CENTER

60A/3P

NEW XFMR "TCE" 15KVA

IN ELEC/MECH ROOM LOCATED

IN VISITORS CENTER

NEW PANEL "LCE"

120/208V, 3P, 50A MCB

IN ELEC/MECH ROOM LOCATED

IN VISITORS CENTER

EMERGENCY POWER ONE-LINE RISER DIAGRAM

25A/3P

50A/3P

225A/3P

PROVIDE A NEW

CB AS INDICATED

PROVIDE A NEW

CB AS INDICATED

60A/3P

60Y

225Y

IN 3" C

IN 2" C

C

AO

M

M O N

W E

A LTH OF

V

I R G I N I

P

O

R O F

E

SS I

N

N

AL ENG

I

R E E

M O S E L E Y A R C H

IT

E C T S .C O M

BRIAN C. WELLS

Lic. No. 046269

PROJECT NO:

DATE:

N

O R

F O

L K

S T

R E

E T

R

IC

H

M O

N D

V

A

P H

O N

E

-7

F

A X

-5

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

/2

/2

:0

:4

A

M POWER ONE-LINE

DIAGRAM & PANEL

SCHEDULES

H .R

.T . J

R . A

R N

G R

EA

D

IN

ES

S C

EN

TE

R (T

A R

C ) V

IS

IT

O R

S C

EN

TE

R

S . G

E O

R G

E M

A S

O N

D R

A

R L

IN

G

T O

N

V A

E5.1

V A

F M

P N

-0

594303

MAY 27, 2020

NO SCALE

ONE LINE DIAGRAM

C

AO

M

M O N

W E

A LTH OF

V

I R G I N I

P

O

R O F

E

SS I

N

N

AL ENG

I

R E E

M O S E L E Y A R C H

IT

E C T S .C O M

BRIAN C. WELLS

Lic. No. 046269

PROJECT NO:

DATE:

N

O R

F O

L K

S T

R E

E T

R

IC

H

M O

N D

V

A

P H

O N

E

-7

F

A X

-5

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

/2

/2

:0

:4

A

M LIGHT FIXTURE

SCHEDULE & PANEL

SCHEDULES

H .R

.T . J

R . A

R N

G R

EA

D

IN

ES

S C

EN

TE

R (T

A R

C ) V

IS

IT

O R

S C

EN

TE

R

S . G

E O

R G

E M

A S

O N

D R

A

R L

IN

G

T O

N

V A

E5.2

V A

F M

P N

-0

594303

MAY 27, 2020

INTERIOR LIGHT FIXTURE SCHEDULE

FIXTURE LAMP

MOUNTING

OPTIONS

REFERENCE

NOTE

COMMENTS

TYPE DESCRIPTION MANUFACTURER SERIES NO. WATTAGE LUMENS COLOR TYPE COLOR TEMP. DIMMING

BATTERY

PACK **

A 4' LSR1 RECESSED LIGHT CORONET LSR1-4-50-LTG3-UNV-DB-W-T15-SD 40 3160 lm LED 5000 K RECESSED X

AE 4' LSR1 RECESSED LIGHT W/ BATTERY PACK CORONET LSR1-4-50-LTG3-UNV-DB-W-T15-SD-EM277 40 3160 lm LED 5000 K RECESSED X X

B 2' LSR1 RECESSED LIGHT CORONET LSR1-2-50-LTG3-UNV-DB-W-T15-SD 20 1580 lm LED 5000 K RECESSED X

BE 2' LSR1 RECESSED LIGHT W/BATTERY PACK CORONET LSR1-2-50-LTG3-UNV-DB-W-T15-SD-EM277V 20 1580 lm LED 5000 K RECESSED X X

C 6" LED DOWNLIGHT LITHONIA LDN6-50-20-L06-AR-LSS-MVOLT-GZ10 23 2000 lm SEMI-SPECULAR LED 5000 K RECESSED X

C1 6" LED DOWNLIGHT LITHONIA LDN6-50-10-L06-AR-LSS-MVOLT-GZ1-WL 13 1000 lm SEMI-SPECULAR LED 5000 K RECESSED X

CE 6" LED DOWNLIGHT W/BATTERY PACK LITHONIA LDN6-50-20-L06-AR-LSS-MVOLT-GZ10-EL 23 2000 lm SEMI-SPECULAR LED 5000 K RECESSED X X

D 6" LED DOWNLIGH (WET LOCATION) LITHONIA LDN6-50-15-L06-AR-LSS-MVOLT-GZ1-WL 21 1500 lm SEMI-SPECULAR LED 5000 K RECESSED X

DE 6" LED DOWNLIGHT W/BATTERY PACK (WET LOCATION) LITHONIA LDN6-50-15-L06-AR-LSS-MVOLT-GZ10-EL-WL 21 1500 lm SEMI-SPECULAR LED 5000 K RECESSED X X

F 2' VANITY LIGHT SUNPARK FL2103D-5000K 23 2200 lm SATIN NICKEL LED 5000 K ABOVE MIRROR 2

H 4' INDUSTRIAL PENDANT LIGHT LITHONIA FEM-L48-4000LM-LPACL-MD-MVOLT-GZ10-50K-80CRI-BSL520 30 4000 lm LED 5000 K PENDANT AT 9' AFF X

P LED Single Head Sign Light for Wall or Ceiling Mount Cooper Lighting 303-S1 CITY SILVER LED WALL MOUNT AT 10'-10" AFF 3 Sign & Ceiling

WE WALL PACK WITH BATTERY PACK COOPER ENT-E01-LED-E1-BL2-DP-7050-BBB(277V) 25 2738 lm DARK PLATINUM LED 5000 K WALL MOUNT AT 8' AFF X 3

X1 WALL MOUNT SINGLE FACE EXIT SIGN LITHONIA LRP-1-RC-120/277-ELN 3 BRUSHED ALUMINUM LED WALL MOUNT ABOVE DOOR X

X2C CEILING MOUNT DOUBLE FACE EXIT SIGN LITHONIA LRP-2-RW-120/277-ELN 3 BRUSHED ALUMINUM LED CEILING RECESSED X 1

X3 WET LOCATION EXIT SIGN LITHONIA WLTE-GY-1-R-EL 3 GRAY LED WALL MOUNT ABOVE DOOR X 3

GENERAL NOTES:

A. ALL FIXTURES SHALL BE CAPABLE OF 120V AND 277V INPUT (MVOLT), UNO.

B. REFER TO LIGHTING PLANS AND SPECIFICATIONS FOR ADDITIONAL FIXTURE INFORMATION.

C. "X" IN THE SCHEDULE INDICATES ITEM IS REQUIRED.

E ALL LENS SHALL BE A MINIMUM 0.125" THICKNESS, UNO.

REFERENCE NOTES:

1. NUMBER OF FACES AND DIRECTIONAL CHEVRONS AS INDICATED ON DWGS.

2. FIXTURE SHALL BE SUITABLE FOR DAMP LOCATIONS.

3. FIXTURE SHALL BE SUITABLE FOR WET LOCATIONS.

HC

LC

HCE

LCE

MISCELLANEOUS 7700 VA 100.00% 7700 VA

KITCHEN 0 VA 0.00% 0 VA

ELECTRIC HEAT 39241 VA 100.00% 39241 VA Total Est. Demand... 147 A

AC / HEAT PUMP 68271 VA 100.00% 68271 VA Total Conn. Current: 147 A

RECEPTACLES 7200 VA 100.00% 7200 VA Total Est. Demand: 122.4 kVA

EXTERIOR LIGHTING 0 VA 0.00% 0 VA Total Conn. Load: 122.4 kVA

INTERIOR LIGHTING 0 VA 0.00% 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

156 A 142 A 144 A

43 kVA 39 kVA 40 kVA

41 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 42

39 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 40

37 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 38

35 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 36

33 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 34

31 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 32

29 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 30

27 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 28

25 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 26

23 -- -- SPACE ONLY 0.0 10.4 24

21 -- -- SPACE ONLY 0.0 10.4 22

19 2.5 10.4

RTU-1 3 50 A

17 2.5 2.2 18

15 A 3 TU1-4

2.5 2.2 16

13 3.0 2.2

TU1-3 3 15 A

11 3.0 3.7 12

15 A 3 TU1-2

3.0 3.7 10

7 15 A 1 TU1-5 1.3 3.7

TU1-1 3 20 A

5 7.4 10.7 6

3 7.1 10.7 4

70 A 3 XFMR TC

9.7 10.7

EWH - ELEC/MECH ROOM 16 3 50 A

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

225 AMP MCB 480/277 Wye 3 PH 4 W MOUNT: SURFACE PANEL ASSEMBLY RATED (KAIC): 30 KAIC

PANELBOARD SCHEDULE HC LOCATION:

ELEC/MECH

ROOM 16

FED FROM:

MISCELLANEOUS 7700 VA 100.00% 7700 VA

KITCHEN 0 VA 0.00% 0 VA

ELECTRIC HEAT 7422 VA 100.00% 7422 VA Total Est. Demand... 67 A

AC / HEAT PUMP 2030 VA 100.00% 2030 VA Total Conn. Current: 67 A

RECEPTACLES 7200 VA 100.00% 7200 VA Total Est. Demand: 24.2 kVA

EXTERIOR LIGHTING 0 VA 0.00% 0 VA Total Conn. Load: 24.2 kVA

INTERIOR LIGHTING 0 VA 0.00% 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

* PROVIDE A GFI CIRCUIT BREAKER AS INDICATED.

82 A 59 A 62 A

10 kVA 7 kVA 7 kVA

41 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 42

39 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 40

37 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 38

35 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 36

33 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 34

31 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 32

29 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 30

27 15 A 1 F-2 0.1 0.0 SPARE 1 20 A 28

25 2.4 1.5 26

30 A 2 EUH-1

2.4 1.5

EUH-2 2 20 A

21 0.9 0.2 REC - ON ROOF 1 20 A 22

30 A 2 DSS-1B

0.9 0.0 F-1 1 15 A 20

17 20 A 1 REC - RM 15 0.2 0.1 ECP-1 - RM 16 1 20 A 18

15 20 A 1 REC - RM 15 1.5 1.2 REC - RM 15 1 20 A 16

13 20 A 1 RECS - RM 15, 16, 13 0.9 1.4 REFRIG.- RM 15 1 20 A 14

11 20 A 1 PLOTTER - RM 12 0.8 1.1 RECS - RM 10, 12 & EXTERIOR 1 20 A 12

9 20 A 1 RECS - RM 07, 18, 17, 12, 04 1.1 1.1 RECS - RM 09, 08, 06, 12 1 20 A 10

7 20 A 1 RECS - RM 04 & EXTERIOR 1.1 0.8 * WATER FOUNTAIN - RM 04 1 20 A 8

5 20 A 1 EXTERIOR RECS 0.5 1.1 RECS - RM 01, 05, 03 1 20 A 6

3 20 A 1 METAL DETECTOR - RM 03 0.5 0.5 X-RAY - RM 03 1 20 A 4

1 20 A 1 AUTO DOOR 0.5 0.5 AUTO DOOR - RM 03 1 20 A 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

150 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: SURFACE PANEL ASSEMBLY RATED (KAIC): 10 KAIC

PANELBOARD SCHEDULE LC LOCATION:

ELEC/MECH

ROOM 16

FED FROM: TC

MISCELLANEOUS 500 VA 100.00% 500 VA

KITCHEN 0 VA 0.00% 0 VA

ELECTRIC HEAT 0 VA 0.00% 0 VA Total Est. Demand... 11 A

AC / HEAT PUMP 0 VA 0.00% 0 VA Total Conn. Current: 10 A

RECEPTACLES 4500 VA 100.00% 4500 VA Total Est. Demand: 9.3 kVA

EXTERIOR LIGHTING 125 VA 125.00% 156 VA Total Conn. Load: 8.7 kVA

INTERIOR LIGHTING 2347 VA 125.00% 2934 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

13 A 11 A 8 A

3 kVA 3 kVA 2 kVA

23 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 24

21 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 22

19 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 20

17 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 18

15 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 16

13 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 14

11 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 12

9 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 10

7 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 8

5 0.7 1.6 LIGHTS 1 20 A 6

3 2.5 0.5 EGRESS LIGHTS AND EXIT SIGNS 1 20 A 4

25 A 3 XFMR TCE

3.0 0.4 EXTERIOR LIGHTS VIA "ELCP" 1 20 A 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

60 AMP MCB 480/277 Wye 3 PH 4 W MOUNT: SURFACE PANEL ASSEMBLY RATED (KAIC): 30 KAIC

PANELBOARD SCHEDULE HCE LOCATION:

ELEC/MECH

ROOM 16

FED FROM:

MISCELLANEOUS 500 VA 100.00% 500 VA

KITCHEN 0 VA 0.00% 0 VA

ELECTRIC HEAT 0 VA 0.00% 0 VA Total Est. Demand... 17 A

AC / HEAT PUMP 0 VA 0.00% 0 VA Total Conn. Current: 17 A

RECEPTACLES 4500 VA 100.00% 4500 VA Total Est. Demand: 6.2 kVA

EXTERIOR LIGHTING 0 VA 0.00% 0 VA Total Conn. Load: 6.2 kVA

INTERIOR LIGHTING 0 VA 0.00% 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

27 A 23 A 6 A

3 kVA 2 kVA 1 kVA

23 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 24

21 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 22

19 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 20

17 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 18

15 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 16

13 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 14

11 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 12

9 20 A 1 FASP- VESTIBULE 01 0.5 0.0 SPARE 1 20 A 10

7 20 A 1 REC - IT ROOM 14 0.4 0.4 REC - IT ROOM 14 1 20 A 8

5 20 A 1 REC - IT ROOM 14 0.4 0.4 REC - IT ROOM 14 1 20 A 6

3 20 A 1 RECS - RM 10, 09 0.9 1.1 RECS - RM 07, 13 1 20 A 4

1 20 A 1 SECURITY SYSTEM 1.2 1.1 RECS - RM 08, 06, 03B 1 20 A 2

CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT

50 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: SURFACE PANEL ASSEMBLY RATED (KAIC): 10 KAIC

PANELBOARD SCHEDULE LCE LOCATION:

ELEC/MECH

ROOM 16

FED FROM: TCE

WALL MOUNT 24" STEM SINGLE HEAD SIGN LIGHT COOPER LIGHTING 303-S1-LEDB2-4000-UNV-T5X-DIM10-CS-24-EDGE 16 1425 lm 4000K

X

WALL MOUNT SIGN LIGHT

EX "MDPWD" EX "EMDPW"

Sheets
E0.1 - LEGENDS, ABBREVIATIONS AND GENERAL NOTES
E1.0 - ELECTRICAL SITE PLAN
E2.1 - FLOOR PLAN - LIGHTING ,MECHANICAL POWER, & ROOF ELECTRICAL
E2.2 - FLOOR PLAN - POWER & LOW VOLTAGE SYSTEMS
E4.1 - ELECTRICAL DETAILS
E4.2 - ELECTRICAL DETAILS
E5.1 - POWER ONE-LINE DIAGRAM & PANEL SCHEDULES
E5.2 - LIGHT FIXTURE SCHEDULE & PANEL SCHEDULES