This solicitation is for the construction of a Visitor's Center building at the Herbert R. Temple Jr. Army National Guard Readiness Center in Arlington, Virginia. The National Guard Bureau plans to construct the Visitors Center within the installation fence line. Work will involve civil, architectural, security, structural, plumbing, mechanical, and electrical disciplines. The period of performance is 425 calendar days from notice to proceed to complete the project, with an estimated value between $1-5 million. The primary NAICS code is 236220 for commercial and institutional building construction. Attached are the written solicitation, specifications, and drawings.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: REFER TO 'TYPICAL COMMUNICATION OUTLET DETAIL' FOR BOX & CONDUIT REQUIREMENTS. REFER TO
TELECOMMUNICATION DEVICE DETAILS FOR CABLING AND TERMINAL JACK REQUIREMENTS.
SYMBOL DESCRIPTION
X
COMMUNICATIONS LEGEND
E
TELECOMMUNICATIONS OUTLET, SUBSCRIPT NUMBER INDICATES OUTLET TYPE. MOUNT AT +3'-10"AFF.
TELECOMMUNICATIONS OUTLET, SUBSCRIPT NUMBER INDICATES OUTLET TYPE. MOUNT AT +1'-6"AFF.
X
[MISC COMMUNICATIONS OUTLET] , MOUNT AT +1'-6"AFF.
RECESSED FLOOR MOUNT DEVICE COMPLETE WITH FITTINGS FOR FLOOR COVERING.
INTERCOM STATION WITH PUSHBUTTON, MOUNT AT +4'-6"AFF.
[MISC COMMUNICATIONS OUTLET] , MOUNT AT +4'-6"AFF.
PUSHBUTTON SWITCH, MOUNT AT +4'-6"AFF. SUBSCRIPT "E" INDICATES EMERGENCY FUNCTIONS.
CATV OUTLET, MOUNT AT +1'-6"AFF.
WALL CLOCK, MOUNT AT +7'-6"AFF. SUBSCRIPT "D" INDICATES DOUBLE FACE CLOCK.
MICROPHONE OUTLET, WALL MOUNT AT +1'-6"AFF, FLUSH FLOOR MOUNT. SUBSCRIPT NUMBER
INDICATES NUMBER OF JACKS TO PROVIDE IN OUTLET.
SOUND SYSTEM SPEAKER, RECESS WALL MOUNT AT +7'-6"AFF. 'WG' WHERE PRESENT INDICATES
PROVIDE PROTECTIVE WIRE GUARD.
POWER/COMMUNICATIONS RECESSED FLOOR BOX. SUBSCRIPT LETTER INDICATES OUTLET TYPE.
REFER TO "TYPICAL COMMUNICATION OUTLET DETAIL" FOR BOX AND CONDUIT REQUIREMENTS.
POWER/COMMUNICATIONS RECESSED FLOOR BOX ON EMERGENCY POWER. SUBSCRIPT LETTER
INDICATES OUTLET TYPE. REFER TO "TYPICAL COMMUNICATION OUTLET DETAIL" FOR BOX AND
CONDUIT REQUIREMENTS.
TELECOMMUNICATIONS EQUIPMENT RACK.
2” EMT CONDUIT SLEEVE WITH NYLON BUSHING EACH END UNO, THRU WALL AT +6” ABOVE FINISHED
CEILING.
TELECOMMUNICATIONS GROUND BUS BAR, MOUNT AT +1'-6"AFF.
TELECOMMUNICATIONS MAIN GROUND BUS BAR, MOUNT AT +1'-6"AFF.
CABLE TRAY, MOUNT AT +6" ABOVE FINISHED CEILING.
SOUND SYSTEM SPEAKER, RECESS CEILING MOUNT. 'WG' WHERE PRESENT INDICATES PROVIDE
PROTECTIVE WIRE GUARD.
M M
S
S
TGB
TMGB
WALL CLOCK, CEILING MOUNT. SUBSCRIPT "D" INDICATES DOUBLE FACE CLOCK. ARROWS INDICATE
FACE DIRECTION.
WIRELESS ACCESS POINTWA
SYMBOL DESCRIPTION
DEMOLITION LEGEND
REMOVE DEVICES, EQUIPMENT, IN ACCORDANCE
WITH THE GENERAL DEMOLITION NOTES.
DEVICES ARE EXISTING TO REMAIN.
WITHIN HATCHED AREAS, DISCONNECT AND REMOVE ALL ELECTRICAL MATERIALS
INCLUDING BUT NOT LIMITED TO LIGHTS, DEVICES, EQUIPMENT, SPEAKERS, FIRE ALARM,
COMMUNICATIONS, AND CIRCUITRY.
A. PROVIDE ALL ELECTRICAL DEMOLITION WORK REQUIRED TO INSTALL THE WORK INDICATED. REMOVE, REROUTE, AND RECONNECT ALL BRANCH CIRCUITS THAT WILL REMAIN IN USE BUT INTERFERES WITH THE
WORK.
B. REMOVE ALL EXISTING CONDUITS THAT WILL NOT BE REUSED AND WHERE THEY WILL BE EXPOSED AFTER COMPLETION. ABANDON ALL OTHERS IN THE WALLS ONLY. DISCONNECT ALL WIRING INDICATED AND/OR
REQUIRED TO BE REMOVED FROM ALL POWER SOURCES. REMOVE ALL WIRING FROM ABANDONED
CONDUITS AND PROVIDE BLANK COVER PLATES FOR BOXES NOT UTILIZED FOR THE WORK.
C. MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN OR PORTIONS THEREOF AFFECTED BY THE
WORK.
D. BEFORE DEMOLITION, VERIFY WITH THE OWNER ALL EQUIPMENT TO BE SALVAGED TO OWNER AND NOT REMOVED FROM THE SITE. FOR ALL REMAINING EQUIPMENT INDICATED FOR REMOVAL (AND NOT
RELOCATED), REMOVE AND DISPOSE IN A LEGAL MANNER.
E. EXERCISE CARE IN REMOVING DEMOLITION ITEMS. REPAIR OR REPLACE ALL DAMAGE CAUSED TO EXISTING
CONSTRUCTION AND EQUIPMENT TO REMAIN.
F. DRAWINGS ARE BASED UPON EXISTING PLANS AND FIELD INVESTIGATION WITHOUT DEMOLITION. VISIT THE EXISTING BUILDING AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS AND EXAMINE ALL DRAWINGS
TO AVOID CONFLICTS.
G. WHERE DEMOLITION OF TELECOMMUNICATIONS DEVICES OCCUR, REMOVE CABLING NOT INDICATED TO
REMAIN BACK TO POINT OF ORIGIN.
H. DEMOLITION FLOOR PLANS ARE PROVIDED FOR REFERENCE ONLY TO AID IN DEFINING THE SCOPE OF
DEMOLITION WORK.
GENERAL DEMOLITION NOTES
A. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING
AS IF REQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER
QUALITY. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY
OF WORK.
B. FOLLOW MOUNTING HEIGHTS INDICATED IN THE ELECTRICAL LEGEND UNLESS OTHERWISE INDICATED.
MEASURE ALL MOUNTING HEIGHTS FROM THE DEVICE CENTER LINE UNLESS OTHERWISE INDICATED.
C. FIELD VERIFY EXACT FEEDER LOCATIONS FOR MECHANICAL EQUIPMENT PRIOR TO ROUGH-IN.
D. EQUIPMENT CONNECTIONS ARE INDICATED IN THEIR APPROXIMATE LOCATIONS. VERIFY EXACT LOCATIONS
OF ALL CONNECTIONS WITH OTHER TRADES SUPPLYING EQUIPMENT TO AVOID CONFLICTS AT INSTALLATION.
E. LOCATED ALL SWITCHES FOR LOCAL CONTROL OF LIGHTING ON STRIKE SIDE OF SINGLE DOORS UNLESS
OTHERWISE INDICATED.
F. PROVIDE SPECIFIC BREAKER ARRANGEMENT FOR THE PANEL BOARDS WHEREVER PHYSICALLY POSSIBLE.
PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPE
WRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT.
G. PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE
TYPEWRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. HAND
WRITTEN SCHEDULES ARE NOT ACCEPTABLE.
H. ALL CONDUIT RUNS INDICATED ARE DIAGRAMMATIC, COORDINATE ROUTING IN ALL SPACES WITH OTHER
TRADES.
I. ALL PANELBOARDS INDICATED ARE HOUSED IN A SINGLE WIDTH ENCLOSURE, UNO. THE CONTRACTOR SHALL
FIELD VERIFY ROOM LAYOUT AND ADJUST ACCORDINGLY, AT NO COST TO THE OWNER, IF PROVIDING ANY
PANELBOARD ENCLOSURES.
J. WHERE POWER AND COMMUNICATION OUTLETS ARE INDICATED IN CLOSE PROXIMITY ON THE DRAWINGS, FIELD COORDINATE THE LOCATIONS TO PLACE THE OUTLETS ADJACENT TO EACH OTHER.
K. ALL EXTERIOR RECEPTACLES SHALL BE LABELED "WR" - WEATHER RESISTANT.
L. WHEN GROUPING MULTIPLE LINE TO NEUTRAL BRANCH CIRCUITS IN A CONDUIT, PROVIDE DEDICATED
COLOR CODED NEUTRAL CONDUCTORS FOR EACH CIRCUIT. DO NOT USE BREAKER TIES AND SHARED
NEUTRALS EVEN THOUGH PERMITTED BY NEC.
M. PROVIDE A 2” WIDE YELLOW LINE PAINTED ON THE FLOOR INDICATING THE ELECTRICAL WORKING SPACE. IN
FRONT OF ALL ELECTRICAL PANELS IN ELECTRICAL ROOMS. REFER TO PLANS FOR ELECTRICAL WORKING
SPACE DETAILS. STENCIL “NO STORAGE” IN 2” HIGH, YELLOW LETTERS CENTERED IN THE OUTLINED AREA.
GENERAL NOTES
A123
SPACE NUMBER
BUILDING AREA (WHEN USED)
SPACE IDENTIFICATION TAG
GRAPHICS SYMBOLS LEGEND
E4.1
E3.1
E5.1
DETAIL TITLE
1/4"=1'-0"
E5.1E2.2
SECTION TITLE
1/4"=1'-0"
E4.1
SECTION NUMBER
DRAWING WHERE SECTION IS INDICATED
SECTION WHERE CUT
ENLARGED PLAN NUMBER
DRAWING WHERE ENLARGED PLAN IS INDICATED
ENLARGED PLAN WHERE CUT
DETAIL NUMBER
DRAWING WHERE DETAIL IS INDICATED
DETAIL TAG
DETAIL NUMBER
DRAWING WHERE DETAIL IS INDICATED
DRAWING WHERE DETAIL IS CUT
ADDITIONAL DRAWING REFERENCES
E2.3
E2.4
SECTION NUMBER
DRAWING WHERE SECTION IS INDICATED
DRAWING WHERE SECTION IS CUT
ADDITIONAL DRAWING REFERENCES
E2.2
E2.3
E2.4
SYMBOL DESCRIPTION
LIGHTING LEGEND
LIGHT SWITCH, RATED 120/277 VOLTS, 20-AMPS, MOUNT AT +3'-10"AFF. SUBSCRIPT/SUPERSCRIPT
LETTERS, NUMBERS, AND SYMBOLS INDICATES SWITCH TYPE AS FOLLOWS:
3 INDICATES 3-WAY LIGHT SWITCH
4 INDICATES 4-WAY LIGHT SWITCH
D INDICATES DIMMER SWITCH
P INDICATES PILOT LIGHT, ON WHEN SWITCH IS ON
K INDICATES KEY OPERATED LIGHT SWITCH
OS INDICATES SWITCH WITH INTEGRAL OCCUPANCY SENSOR
OD INDICATES DIMMER SWITCH WITH INTEGRAL OCCUPANCY SENSOR
OS INDICATES DUAL RELAY INTEGRAL OCCUPANCY SENSOR, WIRED
FOR MULTI-LEVEL SWITCHING
LOWER CASE LETTER INDICATES LIGHT FIXTURE CONTROL DESIGNATION
OMNI-DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, CEILING MOUNT.
PHOTOELECTRIC CELL FOR LIGHTING CONTROL. WALL MOUNT AT +10-0"AFF. AIM NORTH.PE
LIGHT FIXTURE, CEILING MOUNT.
LIGHT FIXTURE ON EMERGENCY POWER, CEILING MOUNT.
LIGHTING FIXTURE.
LIGHTING FIXTURE ON EMERGENCY POWER.
LIGHT FIXTURE, WALL MOUNT, HEIGHT AS INDICATED.
EXIT SIGN, CEILING MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.
EXIT SIGN, WALL MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.
SYMBOL DESCRIPTION
ONE LINE DIAGRAM LEGEND
CIRCUIT BREAKER
FUSED SWITCH
TRANSFORMER
TRANSFER SWITCH
FEEDER DESIGNATIONXXX
CURRENT TRANSFORMERCT
PT POTENTIAL TRANSFORMER
SYMBOL DESCRIPTION
POWER LEGEND
APPLIANCE RECEPTACLE, MOUNT AT +1'-6" AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOR
EQUIPMENT SERVED.
APPLIANCE RECEPTACLE, MOUNT AT +1'-6"AFF. PROVIDE NEMA CONFIGURATION TO MATCH PLUG FOR
EQUIPMENT SERVED. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE
RED DEVICE.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER,
PROVIDE RED DEVICE.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +7'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE
RED DEVICE.
DUPLEX RECEPTACLE, NEMA 5-20R, RECESS FLOOR MOUNT.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. PROVIDE NEMA 3R "WHILE IN USE"
ENCLOSURE.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +1'-6"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT AT +3'-10"AFF. CONNECT TO EMERGENCY POWER, PROVIDE RED DEVICE.
POWER/COMMUNICATIONS RECESSED FLOOR BOX. SUBSCRIPT NUMBER INDICATES OUTLET TYPE.
REFER TO DETAIL ON E4 SERIES DRAWINGS.
POWER/COMMUNICATIONS RECESSED FLOOR BOX. CONNECT TO EMERGENCY POWER, PROVIDE RED
DEVICES. SUBSCRIPT NUMBER INDICATES OUTLET TYPE. REFER TO DETAIL ON E4 SERIES DRAWINGS.
[NON-] METALLIC SURFACE RACEWAY, DEVICES AS INDICATED, MOUNT AT +1'-6"AFF, UNO.
JUNCTION BOX, CONCEALED ABOVE CEILING, UNO.
ENCLOSED CIRCUIT BREAKER, CHARACTERISTICS AS INDICATED.
MUSHROOM SWITCH, HEAVY DUTY WITH LEGEND PLATE. MOUNT W/HANDLE AT +3'-10" AFF, UNO.
MANUAL MOTOR STARTER, OVERLOAD PROTECTION AS REQUIRED PER NAME PLATE RATINGS, WITH
'ON' INDICATOR PILOT LIGHT. FLUSH MOUNT W/HANDLE AT +3'-10"AFF, UNO.
DISCONNECT SWITCH, FUSIBLE OR NON-FUSIBLE AS INDICATED. MOUNT W/HANDLE AT +4'-6"AFF, UNO.
MAGNETIC MOTOR STARTER, WITH OVERLOAD RELAYS AS REQUIRED TO SERVE MANUFACTURER
REQUIREMENTS OF EQUIPMENT SERVED. PROVIDE WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH
AND INDICATOR LIGHTS.. MOUNT W/HANDLE AT +4'-6"AFF, UNO.
COMBINATION MAGNETIC STARTER AND DISCONNECT SWITCH. WITH OVERLOAD ELEMENTS AND
FUSING AS REQUIRED TO SERVE MANUFACTURER REQUIREMENTS OF EQUIPMENT SERVED. PROVIDE
WITH HAND-OFF-AUTOMATIC SELECTOR SWITCH AND INDICATOR LIGHTS.. MOUNT W/HANDLE AT +
4'-6"AFF, UNO.
EQUIPMENT POWER CONNECTION.
CONNECTION TO DIV 23 MOTORIZED DAMPER, VERIFY LOCATION.
POWER FOR ELECTRIC DOOR LOCK CONNECTION.
BRANCH CIRCUIT RUN CONCEALED, UNO. DASHED INDICATES CIRCUITRY REQUIRED TO BE RUN BELOW
SLAB.
STRAIGHT LINEWORK FOR CIRCUITRY INDICATES ON EMERGENCY POWER CIRCUIT. INDICATED FOR
CLARITY ONLY, ACTUAL HOMERUN DESIGNATION OVERRIDES THIS SYMBOLOGY.
BRANCH CIRCUIT HOME RUN TO PANELBOARD AND CIRCUIT INDICATED.
PANELBOARD.
TRANSFORMER, PROVIDE CONCRETE HOUSEKEEPING PAD UNLESS NOTED OTHERWISE.
RELAY, N/O OR N/C AS INDICATED.
RELAY, NORMALLY OPEN.
RELAY, NORMALLY CLOSED.
J
CB
E
M
EL
T
R
POWER FOR ELECTRIC DOOR STRIKE CONNECTION.ES
FEEDER TAG. REFER TO FEEDER SCHEDULE ON DWG E5.1.XXX
SYMBOL DESCRIPTION
FIRE ALARM LEGEND
FIRE ALARM AUDIO/VISUAL (SPEAKER STROBE) NOTIFICATION DEVICE, MOUNT AT 80” AFF AND NOT
MORE THAN 96”. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.
FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, 80” AFF AND NOT MORE THAN 96”. SUBSCRIPT
NUMBER INDICATES STROBE CANDELA RATING.
FIRE ALARM MANUAL PULL STATION, MOUNT AT +3'-10"AFF.
FIRE ALARM SLAVE CONTROL PANEL (FASP)
F
FIRE ALARM DUCT SMOKE DETECTOR, FURNISH AND CONNECT UNDER DIVISION 28. INSTALL UNDER
DIVISION 23. VERIFY LOCATION WITH DIVISION 23 PRIOR TO ROUGH-IN. PROVIDE ACCESSIBLE KEY
OPERATED REMOTE TEST SWITCH FOR EACH DETECTOR.
SMOKE DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.
HEAT DETECTOR, CEILING MOUNT. SUBSCRIPT 'G' WHEN PRESENT INDICATES PROVIDE DEVICE GUARD.
S
H
FIRE ALARM TAMPER SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.TS
FIRE ALARM FLOW SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.FS
POST INDICATOR VALVE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.PV
FIRE ALARM PRESSURE SWITCH, PROVIDE UNDER DIVISION 23, MONITOR UNDER DIVISION 28.PS
FIRE ALARM REMOTE INDICATOR, CEILING MOUNT.RI
FIRE ALARM MONITOR MODULE. NOT ALL MONITOR MODULES ARE INDICATED ON DRAWINGS. PROVIDE
QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED MONITORING FUNCTIONS.
M
C
FIRE ALARM CONTROL MODULE. NOT ALL CONTROL MODULES ARE INDICATED ON DRAWINGS.
PROVIDE QUANTITY AND IN LOCATIONS REQUIRED TO ACCOMPLISH SPECIFIED CONTROL FUNCTIONS.
FIRE ALARM SPRINKLER BELL, MOUNT AT +10'-0"AFF.B
FIRE ALARM MAGNETIC DOOR HOLDER, WALL MOUNT DEVICE AT 6" BELOW TOP OF DOOR. PROVIDE
HINGED MAGNETIC CATCH PLATE ON DOOR TO MATE WITH DEVICE, COORDINATE LOCATION AND
LENGTH WITH DIVISION 08. PROVIDE CONCEALED 120-VOLT POWER CONNECTION AND FIRE ALARM
CONTROL MODULE IF REQUIRED FOR PROPER OPERATION.
FIRE ALARM DOOR HOLDER/CLOSER HARDWARE UNDER DIVISION 08, MONITOR AND CONTROL
INTERFACE WITH FIRE ALARM UNDER DIVISION 28.
FIRE ALARM/POWER CONNECTION TO DIVISION 23 SMOKE OR FIRE/SMOKE DAMPER. COORDINATE
WITH DIVISION 23. REFER TO TYPICAL FIRE/SMOKE DAMPER DIAGRAM.
SD
M
M
FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE WITH DEVICE GUARD, 80” AFF AND NOT MORE THAN
96”. SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING. # / # INDICATES STROBE SETTING AND
REDUCED EFFECTIVE OUTPUT WHEN DEVICE GUARD IS PRESENT.
FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, 80” AFF AND NOT MORE THAN 96”. SUBSCRIPT
NUMBER INDICATES STROBE CANDELA RATING. # / # INDICATES STROVE SETTING AND REDUCED
EFFECTIVE OUTPUT WHEN DEVICE GUARD IS PRESENT.
FIRE ALARM AUDIO/VISUAL (SPEAKER STROBE) NOTIFICATION DEVICE, CEILING MOUNTED.
SUBSCRIPT NUMBER INDICATES STROBE CANDELA RATING.
FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, CEILING MOUNTED. SUBSCRIPT NUMBER
INDICATES STROBE CANDELA RATING.
FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE WITH DEVICE GUARD, CEILING MOUNTED. SUBSCRIPT
NUMBER INDICATES STROBE CANDELA RATING. # / # INDICATES STROBE SETTING AND REDUCED
EFFECTIVE OUTPUT WHEN DEVICE GUARD IS PRESENT.
FIRE ALARM VISUAL STROBE NOTIFICATION DEVICE, CEILING MOUNTED. SUBSCRIPT NUMBER
INDICATES STROBE CANDELA RATING. # / # INDICATES STROVE SETTING AND REDUCED EFFECTIVE
OUTPUT WHEN DEVICE GUARD IS PRESENT.
xx xx xx xx xx xx xx xx
C
AO
M
M O N
W E
A LTH OF
V
I R G I N I
P
O
R O F
E
SS I
N
N
AL ENG
I
R E E
M O S E L E Y A R C H
IT
E C T S .C O M
BRIAN C. WELLS
Lic. No. 046269
PROJECT NO:
DATE:
N
O R
F O
L K
S T
R E
E T
R
IC
H
M O
N D
V
A
P H
O N
E
-7
F
A X
-5
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
/2
/2
:0
:3
A
M LEGENDS,
ABBREVIATIONS AND
GENERAL NOTES
H .R
.T . J
R . A
R N
G R
EA
D
IN
ES
S C
EN
TE
R (T
A R
C ) V
IS
IT
O R
S C
EN
TE
R
S . G
E O
R G
E M
A S
O N
D R
A
R L
IN
G
T O
N
V A
E0.1
V A
F M
P N
-0
594303
MAY 27, 2020
ABBREVIATIONS
1P SINGLE PHASE
3P THREE PHASE
3R WEATHERPROOF (NEMA 3R)
A AMPS
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
ATS AUTOMATIC TRANSFER SWITCH
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BKR BREAKER
C CONDUIT
CATV COMMUNITY ANTENNA TELEVISION (CABLE)
CB CIRCUIT BREAKER
CBL CABLE
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CLR CLEAR
CO. COMPANY
COMB COMBINATION
COMM COMMUNICATIONS
CU COPPER
DIA DIAMETER
DISC DISCONNECT
DIV DIVISION
DWG DRAWING
EBH ELECTRIC BASEBOARD HEATER
EC EMPTY CONDUIT
ECS EMERGENCY COMMUNICATIONS STATION
ELEC ELECTRICAL
ELEV ELEVATOR
EPO EMERGENCY POWER OFF
EQ EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EX EXISTING
EXT EXTERIOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAGP FIRE ALARM GRAPHIC PANEL
FASP FIRE ALARM SLAVE CONTROL PANEL
FAXP FIRE ALARM EXTENDER PANEL
FLA FULL LOAD AMPS
FPMR FUSE PER MANUFACTURERS REQUIREMENTS/RECOMMENDATIONS
FPND FUSE PER NAMEPLATE DATA
G GROUND
GE GROUND FAULT PROTECTION FOR EQUIPMENT, 6-50mA PER NEC 427.22 (PROVIDE ACCESSORY FOR
INDICATED BREAKER)
GFCI GROUND FAULT CIRCUIT INTERRUPT
GFP GROUND FAULT PROTECTION FOR PERSONNEL, 4-6mA (PROVIDE ACCESSORY FOR INDICATED
BREAKER)
HKP HOUSEKEEPING PAD
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
Hz HERTZ
IAW IN ACCORDANCE WITH
IG ISOLATED GROUND
J-BOX JUNCTION BOX
KHFSS KITCHEN HOOD FIRE SUPPRESSION SYSTEM
KHz KILOHERTZ
KVA KILOVOLT AMPS
KW KILOWATTS
KWH KILOWATT HOURS
L LOCKOUT TO PREVENT UNAUTHORIZED SWITCHING (PROVIDE ACCESSORY FOR INDICATED BREAKER)
LC ROUTE CIRCUIT TO LOAD VIA LIGHTING CONTACTOR, REFER TO LC SCHEDULE
LED LIGHT EMITTING DIODE
LTG LIGHTING
LTS LIGHTS
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MH METAL HALIDE
MHz MEGAHERTZ
MIN MINIMUM
ML MAINTENANCE LOCK (PROVIDE ACCESSORY FOR INDICATED BREAKER)
MLO MAIN LUG ONLY
MNS MASS NOTIFICATION SYSTEM
MOCP MAXIMUM OVER CURRENT PROTECTION.
MTD MOUNTED
N NEUTRAL
N/C NORMALLY CLOSED
N/O NORMALLY OPEN
NO. NUMBER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
P PILOT LIGHT (AT THE SWITCH HANDLE)
PBD PANELBOARD
PD PROTECTIVE DEVICE
RCPT RECEPTACLE
REC RECEPTACLE
SEC SECURITY
SPD SURGE PROTECTIVE DEVICE
SPEC. SPECIFICATION(S)
ST SHUNT TRIP, 120V COIL (PROVIDE ACCESSORY FOR INDICATED BREAKER)
SW SWITCH
SWBD SWITCHBOARD
TBB TELECOMMUNICATIONS BONDING BACKBONE
TC TELECOMMUNICATIONS CLOSET
TELECOM TELECOMMUNICATIONS
TGB TELECOMMUNICATIONS GROUNDING BUS BAR
TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR
TYP TYPICAL
UNO UNLESS NOTED (INDICATED) OTHERWISE
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WATTS
W/ WITH
WG WIRE GUARD
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
REVISIONS
DATE DESCRIPTION
HC
HCE
IT
ROOM/14
ELEC/MECH
ROOM / 16
SECURITY ROOM
EAST WING AREA "B"
GROUND FLOOR
EXISTING FACP
MECH ROOM
WEST WING AREA "C"
LOWER FLOOR
EXISTING DISTRIBUTION PANEL "EMDPW
EXISTING DISTRIBUTION PANEL "MDPWD"
CLASSFIED PROCESSING ROOM
WEST WING AREA "D"
LOWER FLOOR
IT
bufpqfkd=_rfiafkd=lkb
TELE CLOSET
WEST WING AREA "C"
LOWER FLOOR
TRANSFORMER ROOM
WEST WING AREA "C"
LOWER FLOOR
SECTION B-B
SECTION A-A
SECTION B-B
FASP
SECTION B-B
FINISHED GRADE
1'-6"
6"UNDERGROUND WARNING
TAPE
UNDER ROADWAYS/DRIVES WITH VEHICULAR TRAFFIC:
PROVIDE 4000 PSI CONCRETE UNDER ROADWAYS AND DRIVEWAYS WITH VEHICULAR TRAFFIC.
PROVIDE CONDUIT SPACERS EVERY 6'-0"
ELSEWHERE:
VDOT #10 SCREENINGS OR APPROVED ENGINEERED FILL THROUGHOUT
PROVIDE CONDUIT SPACERS EVERY 6'-0"
SCH 80 PVC CONDUIT
(TYP OF 2)
5" 7" 5"
6"
6"
FINISHED GRADE
1'-6"
6"UNDERGROUND WARNING
TAPE
UNDER ROADWAYS/DRIVES WITH VEHICULAR TRAFFIC:
PROVIDE 4000 PSI CONCRETE UNDER ROADWAYS AND DRIVEWAYS WITH VEHICULAR TRAFFIC.
PROVIDE CONDUIT SPACERS EVERY 6'-0"
ELSEWHERE:
VDOT #10 SCREENINGS OR APPROVED ENGINEERED FILL THROUGHOUT
PROVIDE CONDUIT SPACERS EVERY 6'-0"
SCH 80 PVC CONDUIT
5" 5"
6"
6"
C
AO
M
M O N
W E
A LTH OF
V
I R G I N I
P
O
R O F
E
SS I
N
N
AL ENG
I
R E E
M O S E L E Y A R C H
IT
E C T S .C O M
BRIAN C. WELLS
Lic. No. 046269
PROJECT NO:
DATE:
N
O R
F O
L K
S T
R E
E T
R
IC
H
M O
N D
V
A
P H
O N
E
-7
F
A X
-5
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
/2
/2
:0
:3
A
M ELECTRICAL SITE PLAN
H .R
.T . J
R . A
R N
G R
EA
D
IN
ES
S C
EN
TE
R (T
A R
C ) V
IS
IT
O R
S C
EN
TE
R
S . G
E O
R G
E M
A S
O N
D R
A
R L
IN
G
T O
N
V A
E1.0
V A
F M
P N
-0
594303
MAY 27, 2020
1" = 20'-0"
FLOOR PLAN - ELECTRICAL SITE PLAN
GENERAL NOTES
REPRESENTED BY n
APPLIES TO DRAWINGS E1.0
KEYNOTES
A. REFER TO CIVIL PLANS FOR EXACT CONDUIT ROUTES.
1. DUCTBANK SHALL BE USED OUTDOOR.
2. PROVIDE CONDUITS/WIRES AS INDICATED ON E5.1 FROM "HC" TO EXISTING PANEL "MDPWD".
3. PROVIDE CONDUITS/WIRES AS INDICATED ON E5.1 FROM "HCE" TO EXISTING PANEL
"EMDPW" .
4. PROVIDE (1) 4" CONDUITS FROM SECURITY ROOM TO EXISTING FIRE ALARM CONTROL
PANEL "FACP".
5. PROVIDE (1) 4" CONDUITS FROM IT ROOM TO THE EXISTING SYSTEM LOCTAED IN CLASSIFIED
PROCESSING ROOM .
6. PROVIDE (1) 4" CONDUITS FROM TELE CLOSET TO THE EXISTING SYSTEM LOCTAED IN TELE
CLOSET.
NO SCALE
DUCTBANK SECTION - A-A
NO SCALE
DUCTBANK SECTION - B-B
F E C
FEC
D
3D
D
3D
O D
OS
OD
OS
O S
OS
3 3D
D
3D
O D
D
D
OD
O D
4D
4D
F E C
FEC
E
E
CAC OFFICE
08 SUPERVISOR
OFFICE
IT ROOM
ELEC/MECH
ROOM
VISITOR
CORRIDOR
STAFF TOILET
SECURITY
SCREENING
VESTIBULE
JANITORS
CLOSET
WAITING
ROOM
HELP DESK
CAC
RECEPTIONIST
EXTERIOR
GARDEN
BREAK ROOM
X1
X2C
X1
H
H
WE
WE
WE
ADMIN WORK
AREA
PUBLIC TOILET
ADMIN
WORKSTATION
X1 X1
A
BE
B B
B
BE
BB
B
B
B B
B
A
WE
B
B
BE B
BE B
BEBE
B
A
A
AEA
AE
A
AE
H H
C1
X1
F F
X3
WE
X1
DE DE
C1 C1
B B
B A
P
P
P
D
D
D
D
D D
D D
D D
D
D
A B
B
A
A
A
A
B BEB
A
A A
A
C
CE
C
C C
C
C
CE C
A
B B
B B
STAFF
CORRIDOR
PEDESTRIAN
CHECK
WINDOW
03B
B B
B B B
CE
ELCP-1
(HCE-2)
ELCP-3
(HCE-2)
ELCP-2
(HCE-2)
ELCP-2
(HCE-2)
ELCP-2
(HCE-2)
ELCP-2
(HCE-2)
ELCP-2
(HCE-2)
B A a a a aa a a a a a a a a a a a a a b b b b b b b b c c c c c cc c c d d dd d d d d d d dd dd d d e e e e a d d
X1
CAC OFFICE
SUPERVISOR
OFFICE
ADMIN WORK
AREA
IT ROOM
ELEC/MECH
ROOM
VISITOR
CORRIDOR
PUBLIC TOILET
STAFF TOILET
SECURITY
SCREENING
VESTIBULE
JANITORS
CLOSET
WAITING
ROOM
HELP DESK
CAC
RECEPTIONIST
EXTERIOR
GARDEN
BREAK ROOM
DSS-1A
TU1-1
TU1-2
TU1-5
TU1-3
ECP-1
EWH
TU1-4
EUH-1
EUH-2
DSS-1B
F-1
RTU-1
MOUNT ON
AC UNIT.
LC-22
F-2
C
AO
M
M O N
W E
A LTH OF
V
I R G I N I
P
O
R O F
E
SS I
N
N
AL ENG
I
R E E
M O S E L E Y A R C H
IT
E C T S .C O M
BRIAN C. WELLS
Lic. No. 046269
PROJECT NO:
DATE:
N
O R
F O
L K
S T
R E
E T
R
IC
H
M O
N D
V
A
P H
O N
E
-7
F
A X
-5
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
/2
/2
:0
:4
A
M FLOOR PLAN - LIGHTING
,MECHANICAL POWER, &
ROOF ELECTRICAL
H .R
.T . J
R . A
R N
G R
EA
D
IN
ES
S C
EN
TE
R (T
A R
C ) V
IS
IT
O R
S C
EN
TE
R
S . G
E O
R G
E M
A S
O N
D R
A
R L
IN
G
T O
N
V A
E2.1
V A
F M
P N
-0
594303
MAY 27, 2020
1/8" = 1'-0"
FLOOR PLAN - LIGHTING
1/8" = 1'-0"
FLOOR PLAN - MECHANICAL POWER
1/8" = 1'-0"
ROOF -ELECTRICAL
DIV. 22 & 23 EQUIPMENT ELECTRICAL SCHEDULE - E2.1
NAME VOLTAGE PHASE P/BD CKT DISCONNECTING MEANS FEEDER SIZE NOTES
DSS-1A 208 V 1 NOTE 1 3#10,#10G,3/4"C FED FROM OUTDOOR UNIT ON ROOF
DSS-1B 208 V 1 LC 19,21 NOTE 5 3#10,#10G,3/4"C
ECP-1 120 V 1 LC 18 NOTE 2 2#12,#12G,3/4"C
EUH-1 208 V 1 LC 23,25 NOTE 1 3#10,#10G,3/4"C
EUH-2 208 V 1 LC 24,26 NOTE 1 3#12,#12G,3/4"C
EWH 480 V 3 HC 2,4,6 NOTE 2 4#6,#10G,1"C
F-1 120 V 1 LC 20 NOTE 1 2#12,#12G,3/4"C
F-2 120 V 1 LC 27 NOTE 1 2#12,#12G,3/4"C
RTU-1 480 V 3 HC 20,22,24 NOTE 1 4#6,#10G,1"C
TU1-1 480 V 3 HC 8,10,12 NOTE 3 4#12,#12G,3/4"C
TU1-2 480 V 3 HC 9,11,13 NOTE 3 4#12,#12G,3/4"C
TU1-3 480 V 3 HC 14,16,18 NOTE 3 4#12,#12G,3/4"C
TU1-4 480 V 3 HC 15,17,19 NOTE 3 4#12,#12G,3/4"C
TU1-5 277 V 1 HC 7 NOTE 4 2#12,#12G,3/4"C
GENERAL NOTES
REPRESENTED BY n
APPLIES TO DRAWINGS E2.1
KEYNOTES
A. ALL EXIT SIGNS AND EGRESS LIGHT FIXTURES(TYPE WITH "E") SHALL BE ON UN-SWITCHED
HEC-3 UNLESS NOTED OTHERWISE.
B. ALL NORMAL LIGHT FIXTURES (TYPE WITHOUT "E") SHALL BE ON CIRCUIT HCE-6 UNLESS
NOTED OTHERWISE.
B. COORDINATE LOCATION OF ALL DISCONNECTS, CONTROL PANELS, & ELECTRICAL
CONNECTIONS WITH MECHANICAL AND PLUMBING CONTRACTORS.
NOTES:
1. PROVIDED BY DIVISION 23.
2. PROVIDED BY DIVISION 22.
3. PROVIDE A NEMA 1 ,480V/3P, 30A NON -FUSIBLE DISCONNECT, WALL MOUNT OR UNIT MOUNT ABOVE CEILING. LOCATION SHALL BE FIELD DETERMINED.
4. PROVIDE A NEMA 1, 480V/1P, 30A NON -FUSIBLE DISCONNECT, WALL MOUNT OR UNIT MOUNT ABOVE CEILING. LOCATION SHALL BE FIELD DETERMINED.
5. PROVIDE A NEMA 3R, 208V/2P, 30A NON -FUSIBLE DISCONNECT, WALL MOUNT OR UNIT MOUNT. LOCATION SHALL BE FIELD DETERMINED.
1. REFER TO LIGHTING CONTACTOR DETAIL ON E4.1 FOR ADDITIONAL INFORMATION.
F
C
FEC
E
E
E L
E L
E L
EL
EL
E L
EL
E L
EL
E L
EL
J
J
E L
E
F E C
FEC
F
F
FF
F
F
WA
WA
WA
S S
S
S
S
S
S
S
S
S S
S
S D
CAC OFFICE
SUPERVISOR
OFFICE
ADMIN WORK
AREA
ELEC/MECH
ROOM
VISITOR
CORRIDOR
PUBLIC TOILET
STAFF TOILET
SECURITY
SCREENING
VESTIBULE
JANITORS
CLOSET
WAITING
ROOM
HELP DESK
CAC
RECEPTIONIST
EXTERIOR
GARDEN
BREAK ROOM
METAL
DETECTOR
CONCRETE PAD
LC
HC
TC
HCE
LCE
TCE
X-RAY
ELCP
AUTO
DOOR
AUTO
DOOR
PEDESTRIAN
CHECK
WINDOW
03B
3LC-1
LC-2
LC-3
LC-4
LCE-8
LCE-7
LCE-5
LCE-6
LCE-4
LCE-4
LCE-4
LCE-3
LCE-3
LCE-3
LCE-3
LCE-2
LCE-2 LCE-2
LC-5 LC-5
LC-5
LC-6
LC-6
LC-6
LC-6
LC-6
LC-6
LC-7
LC-7
LC-7
LC-7
LC-7
LC-8
LC-9
LC-9
LC-9
LC-9 LC-9
LC-9
LC-10
LC-10
LC-10
LC-10
LC-11
LC-10
LC-10
LC-12
LC-12
LC-12
LC-12
LC-13
LC-13
LC-13
LC-13
LC-13
LC-17
LC-16
LC-15
LC-14
LC-12 LC-12
60"AFF
FASP
LCE-9
IT ROOM
ADMIN
WORKSTATION
STAFF
CORRIDOR
LC-7
60"AFF
CAC OFFICE
SUPERVISOR
OFFICE
ADMIN WORK
AREA
IT ROOM
ELEC/MECH
ROOM
VISITOR
CORRIDOR
PUBLIC TOILET
STAFF TOILET
SECURITY
SCREENING
VESTIBULE
JANITORS
CLOSET
WAITING
ROOM
04 HELP DESK
CAC
RECEPTIONIST
EXTERIOR
GARDEN
BREAK ROOM
PEDESTRIAN
CHECK
WINDOW
03B
TGB
FASP
LOC
60" AFF
WP
60" AFF
C
AO
M
M O N
W E
A LTH OF
V
I R G I N I
P
O
R O F
E
SS I
N
N
AL ENG
I
R E E
M O S E L E Y A R C H
IT
E C T S .C O M
BRIAN C. WELLS
Lic. No. 046269
PROJECT NO:
DATE:
N
O R
F O
L K
S T
R E
E T
R
IC
H
M O
N D
V
A
P H
O N
E
-7
F
A X
-5
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
/2
/2
:0
:4
A
M FLOOR PLAN - POWER &
LOW VOLTAGE SYSTEMS
H .R
.T . J
R . A
R N
G R
EA
D
IN
ES
S C
EN
TE
R (T
A R
C ) V
IS
IT
O R
S C
EN
TE
R
S . G
E O
R G
E M
A S
O N
D R
A
R L
IN
G
T O
N
V A
E2.2
V A
F M
P N
-0
594303
MAY 27, 2020
1/4" = 1'-0"
FLOOR PLAN - POWER
1/8" = 1'-0"
FLOOR PLAN - LOW VOLTAGE SYSTEMS
GENERAL NOTES
REPRESENTED BY n
APPLIES TO DRAWINGS E2.2
KEYNOTES
A. REFER TO ARCHITECTUAL DRAWINGS FOR EXACT LOCATIONS OF RECEPTACLES AND
JUNCTION BOXES.
1. PROVIDE/INSTALL 4' X 8' X 3/4" FIRE RATED TELECOM PLYWOOD BACK BOARD AT 24" AFF.
2. REFER TO DRAWING E4.1 FOR EXTERIOR LIGHT CONTROL PANEL DETAILS
3. PROVIDE CIRCUIT LCE-1 FOR ELECTRIC LOCKS. REFER TO SECURITY DRAWINGS
FOR ADDITIONAL INFORMATION.
4. REFER TO FIRE ALARM RISER DIAGRAM ON E4.2 FOR ADDITIONAL INFORMATION.
5. REFER TO E5.1 FOR ADDITIONAL INFORMATION.
3'-6" (480V)
MIN 3' - 0" (208V)
O F E
Q
UIP
M
ENTM
IN
IM
UM
2' -
" T O W
ID
TH
DEDICATED
ELECTRICAL
SPACE
ELECTRICAL
EQUIPMENT
REFER TO NEC ARTICLE 110-26
FOR ADDITIONAL
INFORMATION
RGS CONDUIT ELBOW
PVC CONDUIT
EMT CONDUIT
SLAB
POROUS FILL
EARTH
PVC CONDUIT
EMT CONDUIT
SLAB
POROUS FILL
EARTH
RGS CONDUIT ELBOW
WALL
SLAB
FINISHED FLOOR
(2) 1" CONDUITS
UNLESS OTHERWISE INDICATED
FLOOR BOX
WALL/PARTITION CAVITY
2.5" DEEP 2-GANG OUTLET BOX
WITH SINGLE GANG PLASTER RING
WALL/PARTITION FACE
1.25" CONDUIT MINIMUM
SIZE OR AS INDICATED
TERMINATE CONCEALED 6" ABOVE
ACCESSABLE CEILING WITH
NYLON BUSHING
FINISHED CEILING
6"
PROVIDE FIRESTOP SLEEVE EQUAL TO
HILTI MODEL CP-653-2". INSTALL IN
ACCORDANCE WITH MFR'S
RECOMMENDATIONS.
FINISHED ACCESSIBLE CEILING
W A L L
CORE DRILL HOLE, FIRE
SEAL ANNULAR SPACE
AROUND SLEEVE.
WIREMOLD FS2R-RED AND
FS4R-RED ARE SIMILAR
ACCEPTABLE PRODUCTS
NOTE:
REFER TO LS LIFE SAFETY
DRAWINGS FOR WHICH
WALLS ARE RATED AND UN-
RATED
2" CONDUIT
SLEEVE
6"
2" CONDUIT SLEEVE, UIO.
FINISHED ACCESSIBLE CEILING
W A L L
CORE DRILL HOLE, FIRE
SEAL ANNULAR SPACE
AROUND SLEEVE.
NYLON BUSHING
NOTE:
REFER TO LS LIFE SAFETY
DRAWINGS FOR WHICH
WALLS ARE RATED AND UN-
RATED
3" MIN EACH SIDE
NOTE:
FILL 2" INSIDE EACH END OF
CONDUIT SLEEVES WITH
BATT INSULATION FOR
SOUND TRANSMISSION
REDUCTION
WHITE
(NEUTRAL)
RED
(LINE)
N
WHITE
HOT
BLACK
POWER
PACK
R E D
B L K
B L U
RED (LOAD)
OFF SWITCH
BLU CONTROL OUTPUT
BLK COMMON
RED +24VDC
OCCUPANCY SENSORB
L U
B L K
SLAVE
PACK
RED (LOAD)
RED (LINE) OFF SWITCH
LOAD
HOT
NEUTRAL
LOAD
H
N
COIL
LINE
LOAD
H
A
SPECIFIED
TIME
CLOCK
C
N
LED
PILOT
LIGHT
CTRL CKT
PHOTOCELL LOCATED
ON ROOF REFER TO
SPECIFICATIONS
HCE-2
CONTACTOR#
ELCP-1
EXTERIOR LIGHTING CONTROL PANEL - ELCP
CKT # DESCRIPTION PHOTOCELL
(CTRL CKT : HCE-2)
H- HAND SWITCH
O-OFF SWITCH
A- AUTO SWITCH
LOCATION: ELEC/MECH 16
X
X
X
X
X
X
SPARE
EXTERIOR BUILDING SIGN LIGHTS
EXTERIOR LIGHTS
EXTERIOR LIGHTS
SPARE
SPARE
C K
T
C K
T
C K
T
C K
T
C K
T
C K
T
N
H
L C
P -1
C
-2
C
-3
C
-4
C
-5
C
P -6
ELCP-2
ELCP-3
ELCP-4
ELCP-5
ELCP-6
HCE-2
HCE-2
TOGGLE SWITCH WITH PILOT LIGHT:
OR DISCONNECT SWITCH (REF
COORDINATION SCHEDULE) BY DIV
26. 6" ABOVE ACCESSIBLE CEILING.
RIB COIL CONTROL NEARBY BAS
PANEL ALSO SERVING OTHER
EQUIPMENT. DIV 23 VERIFY
LOCATION.
RIB FURNISHED BY
DIV 15, INSTALLED
AND WIRED BY DIV
26.
EQUIPMENT FURNISHED AND
INSTALLED BY DIV 15. LINE
VOLTAGE CIRCUITRY BY DIV
26.
LINE VOLTAGE WIRING, BY DIV 26 IN
CONDUIT
LOW VOLTAGE WIRING, BY DIV 23
TMGB
TGB
#3/O
EXISTING TMGB IN BUILDING ONE
1-1/8"
3-1/2"
1/4" THICK ELECTROTIN
PLATED COPPER BUSBAR
FIBERGLASS
BUSHING
9/32" DIA
4"
10"
1"
FINISHED FLOOR
WALL/PARTITION CAVITY
2.5" DEEP 2-GANG OUTLET BOX
WITH SINGLE GANG PLASTER RING - 18" AFF
WALL/PARTITION FACE
1.25" CONDUIT MINIMUM
SIZE OR AS INDICATED
TERMINATE CONCEALED 6" ABOVE
ACCESSABLE CEILING WITH
NYLON BUSHING
FINISHED CEILING
2.5" DEEP 2-GANG OUTLET BOX
WITH SINGLE GANG PLASTER RING 5'-6' AFF
PLAN
SYMBOL
PROVIDE A DUPLEX POWER OUTLET
ADJACENT TO COMM OUTLET
SUPPORT TIE WIRE FROM BOTTOM
CHORD OF STRUCTURE. VERIFY
ACTUAL BUILDING STRUCTURE AND
PROVIDE SUPPLEMENTAL FRAMING FOR
ATTACHMENT OF HANGER WIRES.
REFER TO FIREPROOFING NOTE.
JUNCTION BOX WITH COVER
AND IDENTIFICATION, MOUNT
TO STRUCTURE. REFER TO
FIREPROOFING NOTE.
PROVIDE STEEL TIE WIRE AT
ALL 4 SIDES OF
FIXTURE TO STRUCTURE,
INDEPENDENT OF CEILING.
SUPPORT WIRES SHALL BE
IDENTIFIED WITH ORANGE
SPRAY PAINT. REFER TO
FIREPROOFING NOTE.
MAXIMUM 6'-0" LONG MC
CABLE OR FLEXIBLE CONDUIT.
SUPPORT IAW SPECIFICATIONS
FIREPROOFING NOTE:
THIS DETAIL APPLIES TO UNPROTECTED
STRUCTURE ONLY. IF THE BUILDING
STRUCTURE REQUIRES FIREPROOFING,
INSTALL BOXES AND CONDUIT WITH A
METHOD THAT MAINTAINS THE INTEGRITY
OF THE FIREPROOFING METHOD.
COORDINATE METHOD AND SCHEDULING
WITH DIVISION 7.
BRANCH CIRCUIT CONDUIT,
SUPPORT IAW SPECIFICATIONS
RECESSED, LAY-IN TYPE,
LED LIGHT FIXTURE.
SECURE TO GRID W/ 2 SHORT SCREWS
AT EACH END, AVOID CONFLICT WITH
FIXTURE OPERATION AND MAINTENANCE
SUSPENDED CEILING
TILE-TYPICAL
C
AO
M
M O N
W E
A LTH OF
V
I R G I N I
P
O
R O F
E
SS I
N
N
AL ENG
I
R E E
M O S E L E Y A R C H
IT
E C T S .C O M
BRIAN C. WELLS
Lic. No. 046269
PROJECT NO:
DATE:
N
O R
F O
L K
S T
R E
E T
R
IC
H
M O
N D
V
A
P H
O N
E
-7
F
A X
-5
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
/2
/2
:0
:4
A
M ELECTRICAL DETAILS
H .R
.T . J
R . A
R N
G R
EA
D
IN
ES
S C
EN
TE
R (T
A R
C ) V
IS
IT
O R
S C
EN
TE
R
S . G
E O
R G
E M
A S
O N
D R
A
R L
IN
G
T O
N
V A
E4.1
V A
F M
P N
-0
594303
MAY 27, 2020
NO SCALE
EQUIPMENT CLEARANCES
NO SCALE
PVC TO EMT TRANSITION DETAIL
NO SCALE
TELECOMMUNICATIONS
OUTLET CONDUIT DETAIL
NO SCALE
RATED WALL CONDUIT SLEEVE DETAIL
NO SCALE
UN-RATED WALL CONDUIT SLEEVE DETAIL
NO SCALE
OCCUPANCY SENSOR DIAGRAM
AUXILARY RELAY PACK SENSOR
NO SCALE
LIGHTING CONTACTOR DETAIL - TIME CLOCK AND PHOTOCELL
NO SCALE
TYPICAL EXHAUST FAN
CONNECTION DIAGRAM
NO SCALE
TGB GROUNDING SYSTEM DIAGRAM
NO SCALE
TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) DETAIL
NO SCALE
CATV OUTLET CONDUIT DETAIL
NO SCALE
RECESSED, LAY-IN, LED
LIGHT FIXTURE MOUNTING DETAIL
BAS
C
COIL
SYSTEMS WITH MULTIPLE MOTORS REQUIRE ONE SHUTDOWN RELAY FOR EACH STARTER OR VFD. THERE MAY BE MORE THAN ONE DUCT SMOKE DETECTOR PER SYSTEM, BUT ONLY ONE CONTROL MODULE IS REQUIRED PER MOTOR. SHUTDOWN IS VIA
CONTROL MODULE, NOT VIA DUCT DETECTOR AUX CONTACTS. COORDINATE W/ DIV 23.
UNDER NORMAL CONDITIONS, FA SYSTEM POWERS THE NORMALLY OPEN FA CONTROL MODULE CONTACT TO THE CLOSED
POSITION TO ALLOW NORMAL UNIT CONTROL BY BAS.
UPON ALARM SIGNAL FROM THE FIRE ALARM SYSTEM, THE CONTACTS IN THE FA SYSTEM RELEASES CONTROL MODULE TO OPEN POSITION, CAUSING SHUTDOWN OF ASSOCIATED HVAC EQUIPMENT. HVAC EQUIPMENT SHALL NOT BE OPERABLE UNTIL FA
CONTROL MODULE IS RESET TO NORMAL CLOSED POSITION.
DIVISION 23 SHALL PROVIDE WIRING BETWEEN FA AND BAS CONTROL MODULES AND HVAC EQUIPMENT CONTROLLER (STARTER, VFD, OR INTEGRAL CONTROL PANEL).
FIRE ALARM ADDRESSABLE CONTROL
MODULE INSTALLATION AND FA
CONTROL WIRING BY DIV 28.
LINE/24 VOLT TRANSFORMER
INTEGRAL WITH HVAC UNIT,
STARTER, OR VFD (VARIES
BY UNIT).
H
N
UNIT
LINE
VOLTAGE
MECHANICAL CONTROL RELAY FURNISHED AND
INTERLOCK WIRING WITH MECH EQUIPMENT BY DIV
23. INSTALLATION AND POWER WIRING BY DIV 26.
STARTER CONTROL COIL (OR
EQUIVALENT CONTROLLER
FOR EQUIPMENT)
MECHANICAL EQUIPMENT
24V
SD
TV
MOUNT +18" AFF TO
CENTERLINE, UNO.
F-TYPE CONNECTOR FOR
CATV DISTRIBUTION, TO &
FROM LOCAL CATV TYPE 1
DEVICE (IN ROOMS WITH TYPE
1 DEVICE)2-GANG BACKBOX WITH
SINGLE-GANG PLASTER
RING AND COVER
1" CONDUIT WITH BUSHING TO ABOVE ACCESSIBLE
CLG, OR TO LOCAL TYPE 1 CATV WHERE PRESENT
F-TYPE CONNECTOR FOR CATV
DISTRIBUTION (IN ROOMS WITH
NO TYPE 1 CATV DEVICE)
TV
MOUNT +18" AFF TO
CENTERLINE, UNO.
F-TYPE CONNECTOR FOR
CATV DISTRIBUTION, TO &
FROM LOCAL CATV TYPE 1
DEVICE (IN ROOMS WITH TYPE
1 DEVICE)
2-GANG BACKBOX WITH
SINGLE-GANG PLASTER
RING AND COVER
1" CONDUIT WITH BUSHING TO ABOVE ACCESSIBLE
CLG, OR TO LOCAL TYPE 1 CATV WHERE PRESENT
F-TYPE CONNECTOR FOR CATV
DISTRIBUTION (IN ROOMS WITH
NO TYPE 1 CATV DEVICE)
DATA CATEGORY 6, 8-POSITION
MODULAR CONNECTOR FOR
VOICE COMMUNICATIONS
PHONE
CATEGORY 6, 8-POSITION
MODULAR CONNECTOR FOR
VOICE COMMUNICATIONS
2-GANG BACKBOX WITH
SINGLE-GANG PLASTER
RING AND COVER
1" CONDUIT WITH BUSHING TO
ABOVE ACCESSIBLE CLG
+18" AFF TO
CENTERLINE
UNO.
+46" AFF TO
CENTERLINE
UNO.
2 2
DATA
PHONE
+18" AFF TO
CENTERLINE
UNO.
CATEGORY 6, 8-POSITION
MODULAR CONNECTOR FOR
VOICE COMMUNICATIONS
CATEGORY 6, 8-POSITION
MODULAR CONNECTOR FOR
DATA COMMUNICATIONS
2-GANG BACKBOX WITH
SINGLE-GANG PLASTER
RING AND COVER
1" CONDUIT WITH BUSHING TO
ABOVE ACCESSIBLE CLG
+46" AFF TO
CENTERLINE
UNO.
DATA
PHONE
+18" AFF TO
CENTERLINE
UNO.
CATEGORY 6, 8-POSITION
MODULAR CONNECTOR FOR
VOICE COMMUNICATIONSCATEGORY 6, 8-POSITION
MODULAR CONNECTOR FOR
DATA COMMUNICATIONS
2-GANG BACKBOX WITH
SINGLE-GANG PLASTER
RING AND COVER
1" CONDUIT WITH BUSHING TO
ABOVE ACCESSIBLE CLG
+46" AFF TO
CENTERLINE
UNO.
3 3
2 COPPER WIRE CONNECTOR
FOR VOICE COMMUNICATIONS
(EMERGENCY PHONE)
FIRE ALARM
CONTROL
PANEL
(FACP) EOL
PROVIDE QUANTITIES AS REQUIRED
S F SD
EOL
EOL
AUDIBLE NAC
STROBE NAC
EXISTING FIRE ALARM SYSTEM
IN EXISTING BUILDING ONE
NEW IN VISITOR CENTER
2 PHONE LINES
120V
BATTERY
CHARGER
BATTERIES
FIRE ALARM SLAVE CONTROL PANEL (FASP)
(LOC)
(ACU)
C
AO
M
M O N
W E
A LTH OF
V
I R G I N I
P
O
R O F
E
SS I
N
N
AL ENG
I
R E E
M O S E L E Y A R C H
IT
E C T S .C O M
BRIAN C. WELLS
Lic. No. 046269
PROJECT NO:
DATE:
N
O R
F O
L K
S T
R E
E T
R
IC
H
M O
N D
V
A
P H
O N
E
-7
F
A X
-5
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
/2
/2
:0
:4
A
M ELECTRICAL DETAILS
H .R
.T . J
R . A
R N
G R
EA
D
IN
ES
S C
EN
TE
R (T
A R
C ) V
IS
IT
O R
S C
EN
TE
R
S . G
E O
R G
E M
A S
O N
D R
A
R L
IN
G
T O
N
V A
E4.2
V A
F M
P N
-0
594303
MAY 27, 2020
NO SCALE
FIRE ALARM HVAC UNIT SHUTDOWN WIRING DIAGRAM
NO SCALE
CATV OUTLET DETAIL - TYPE 1
NO SCALE
CATV / DATA OUTLET DETAIL - TYPE 2
NO SCALE
TELECOMMUNICATION OUTLET DETAIL - TYPE 2
NO SCALE
TELECOMMUNICATION OUTLET DETAIL - TYPE 1
NO SCALE
TELECOMMUNICATION OUTLET DETAIL - TYPE 3
NO SCALE
FIRE ALARM RISER DIAGRAM
FEEDER
ID
# OF
SETS
BUILDING WIRE
QUANTITY & SIZE TYPE
THHN - DRY
TYPE THWN - WET
MINIMUM
CONDUIT SIZE
COPPER FEEDER SCHEDULE
30 1 3#10,#10 G 3/4"
35 1 3#8,#10 G 3/4"
40 1 3#8,#10 G 3/4"
45 1 3#6,#10 G 1"
50 1 3#6,#10 G 1"
60 1 3#4,#10 G 1"
70 1 3#4,#8 G 1 1/4"
80 1 3#3,#8 G
90 1 3#2,#8 G
100 1 3#1,#8 G
110 1 3#2,#6 G
125 1 3#1,#6 G
150 1 3#1/0,#6 G 2"
175 1 3#2/0,#6 G
200 1 3#3/0,#6 G
225 1 3#4/0,#4 G 2 1/2"
250 1 3-250kCM,#4 G
300 1 3-350kCM,#4 G
350 2 2"
400 2 2"
450 3#4/0,#2 G
600 3"
1000 3
1200 4
1600 5
2000 6
2500 7
1 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
2"
2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
4"
3"
4"
3"
4"
4"
4"
3#2/0,#3 G
3#3/0,#3 G
3-250kCM,#2 G
3-350kCM,#1 G
3-500kCM,#1/0 G
3-350kCM,#1/0 G
3-500kCM,#2/0 G
3-350kCM,#3/0 G
3-500kCM,#4/0 G
3-500kCM,#250 G
3-500kCM,#350 G
NOTES:
1. ELECTRICAL CONTRACTOR TO VERIFY CONDUIT SIZE REQUIRED IF WIRE TYPES OTHER
THAN THOSE LISTED ABOVE ARE USED.
2. FEEDER SIZES BASED ON TABLE 310.15(B)(16), 75º C.
3. SIZES ADJUSTED PER NEC 110.14.
FEEDER
ID
# OF
SETS
BUILDING WIRE
QUANTITY & SIZE TYPE
THHN - DRY
TYPE THWN - WET
MINIMUM
CONDUIT SIZE
30Y 1 4#10,#10 G 3/4"
35Y 1 4#8,#10 G 3/4"
40Y 1 4#8,#10 G 3/4"
45Y 1 4#6,#10 G 1"
50Y 1 4#6,#10 G 1"
60Y 1 4#4,#10 G 1"
70Y 1 4#4,#8 G 1 1/4"
80Y 1 4#3,#8 G
90Y 1 4#2,#8 G
100Y 1 4#1,#8 G
110Y 1 4#2,#6 G
125Y 1 4#1,#6 G
150Y 1 4#1/0,#6 G 2"
175Y 1 4#2/0,#6 G
200Y 1 4#3/0,#6 G
225Y 1 4#4/0,#4 G 2 1/2"
250Y 1 4-250kCM,#4 G
300Y 1 4-350kCM,#4 G
350Y 2 2"
400Y 2 2"
450Y 4#4/0,#2 G
500Y
600Y 3"
700Y
800Y
1000Y 3
1200Y 4
1600Y 5
2000Y 6
2500Y 7
1 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
2"
2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
4"
3"
4"
3"
4"
4"
4"
4#2/0,#3 G
4#3/0,#3 G
4-250kCM,#2 G
4-350kCM,#1 G
4-500kCM,#1/0 G
4-350kCM,#1/0 G
4-500kCM,#2/0 G
4-350kCM,#3/0 G
4-500kCM,#4/0 G
4-500kCM,#250 G
4-500kCM,#350 G qo^kpclojbo=p`ebarib kVA TYPE PRIMARY SECONDARY
COPPER PRIMARY
FEEDER
BONDING
CONDUCTOR
15 kVA
30 kVA
45 kVA
75 kVA
112.5 kVA
150 kVA
225 kVA
300 kVA
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
LINEAR
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
480V-3Ø
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
208Y/120V
3#10, #10 G, 3/4" C. #8
#6
#6
#2
#2
#2/0
#2/0
#3/0
500 kVA LINEAR 480V-3Ø 208Y/120V #3/0
COPPER SECONDARY
FEEDER
3#6, #10 G, 1" C.
3#4, #8 G, 1-1/4" C.
3#1, #6 G, 1-1/2" C.
3#2/0, #6 G, 2" C.
3#4/0, #4 G, 2-1/2" C.
4#4, #8 G, 1-1/4" C.
4#1, #6 G, 1-1/2" C.
4#1/0, #6 G, 2" C.
4-250kCM, #2 G, 2-1/2" C.
(2 SETS) 3#2/0,
#3 G, 2" C.
(2 SETS) 3#4/0,
#2 G, 2-1/2" C.
(3 SETS) 3-350kCM, #1/0 G, 4" C.
(2 SETS) 4-3/0,
#2 G, 2-1/2" C.
(2 SETS) 4-250kCM, #2/0 G, 2-1/2" C.
(3 SETS) 4-350kCM, #2/0 G, 3" C.
(4 SETS) 4-350kCM, #4/0 G, 4" C.
(6 SETS) 4-350kCM, 300kCM G, 4" C.
EXISTING PANEL "MDPWD"
480/277V, 3P, 1600A MLO
IN TRANSFORMER ROOM LOCATED
IN WEST WING AREA "C" ON LOWER
FLOOR OF EXISTING BUILDING ONE
NEW PANEL "HC"
480/277V, 3P, 225A MCB
IN ELEC/MECH ROOM LOCATED
IN VISITORS CENTER
225A/3P
NEW XFMR "TC" 45KVA
IN ELEC/MECH ROOM LOCATED
IN VISITORS CENTER
NEW PANEL "LC"
120/208V, 3P, 150A MCB
IN ELEC/MECH ROOM LOCATED
IN VISITORS CENTER
NORMAL POWER ONE-LINE RISER DIAGRAM
70A/3P
150A/3P
EXISTING PANEL "EMDPW"
480/277V, 3P, 800A MLO
IN MECH ROOM LOCATED
IN WEST WING AREA "C" ON
LOWER FLOOR
OF EXISTING BUILDING ONE
NEW PANEL "HCE"
480/277V, 3P, 60A MCB
IN ELEC/MECH ROOM LOCATED
IN VISITORS CENTER
60A/3P
NEW XFMR "TCE" 15KVA
IN ELEC/MECH ROOM LOCATED
IN VISITORS CENTER
NEW PANEL "LCE"
120/208V, 3P, 50A MCB
IN ELEC/MECH ROOM LOCATED
IN VISITORS CENTER
EMERGENCY POWER ONE-LINE RISER DIAGRAM
25A/3P
50A/3P
225A/3P
PROVIDE A NEW
CB AS INDICATED
PROVIDE A NEW
CB AS INDICATED
60A/3P
60Y
225Y
IN 3" C
IN 2" C
C
AO
M
M O N
W E
A LTH OF
V
I R G I N I
P
O
R O F
E
SS I
N
N
AL ENG
I
R E E
M O S E L E Y A R C H
IT
E C T S .C O M
BRIAN C. WELLS
Lic. No. 046269
PROJECT NO:
DATE:
N
O R
F O
L K
S T
R E
E T
R
IC
H
M O
N D
V
A
P H
O N
E
-7
F
A X
-5
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
/2
/2
:0
:4
A
M POWER ONE-LINE
DIAGRAM & PANEL
SCHEDULES
H .R
.T . J
R . A
R N
G R
EA
D
IN
ES
S C
EN
TE
R (T
A R
C ) V
IS
IT
O R
S C
EN
TE
R
S . G
E O
R G
E M
A S
O N
D R
A
R L
IN
G
T O
N
V A
E5.1
V A
F M
P N
-0
594303
MAY 27, 2020
NO SCALE
ONE LINE DIAGRAM
C
AO
M
M O N
W E
A LTH OF
V
I R G I N I
P
O
R O F
E
SS I
N
N
AL ENG
I
R E E
M O S E L E Y A R C H
IT
E C T S .C O M
BRIAN C. WELLS
Lic. No. 046269
PROJECT NO:
DATE:
N
O R
F O
L K
S T
R E
E T
R
IC
H
M O
N D
V
A
P H
O N
E
-7
F
A X
-5
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
/2
/2
:0
:4
A
M LIGHT FIXTURE
SCHEDULE & PANEL
SCHEDULES
H .R
.T . J
R . A
R N
G R
EA
D
IN
ES
S C
EN
TE
R (T
A R
C ) V
IS
IT
O R
S C
EN
TE
R
S . G
E O
R G
E M
A S
O N
D R
A
R L
IN
G
T O
N
V A
E5.2
V A
F M
P N
-0
594303
MAY 27, 2020
INTERIOR LIGHT FIXTURE SCHEDULE
FIXTURE LAMP
MOUNTING
OPTIONS
REFERENCE
NOTE
COMMENTS
TYPE DESCRIPTION MANUFACTURER SERIES NO. WATTAGE LUMENS COLOR TYPE COLOR TEMP. DIMMING
BATTERY
PACK **
A 4' LSR1 RECESSED LIGHT CORONET LSR1-4-50-LTG3-UNV-DB-W-T15-SD 40 3160 lm LED 5000 K RECESSED X
AE 4' LSR1 RECESSED LIGHT W/ BATTERY PACK CORONET LSR1-4-50-LTG3-UNV-DB-W-T15-SD-EM277 40 3160 lm LED 5000 K RECESSED X X
B 2' LSR1 RECESSED LIGHT CORONET LSR1-2-50-LTG3-UNV-DB-W-T15-SD 20 1580 lm LED 5000 K RECESSED X
BE 2' LSR1 RECESSED LIGHT W/BATTERY PACK CORONET LSR1-2-50-LTG3-UNV-DB-W-T15-SD-EM277V 20 1580 lm LED 5000 K RECESSED X X
C 6" LED DOWNLIGHT LITHONIA LDN6-50-20-L06-AR-LSS-MVOLT-GZ10 23 2000 lm SEMI-SPECULAR LED 5000 K RECESSED X
C1 6" LED DOWNLIGHT LITHONIA LDN6-50-10-L06-AR-LSS-MVOLT-GZ1-WL 13 1000 lm SEMI-SPECULAR LED 5000 K RECESSED X
CE 6" LED DOWNLIGHT W/BATTERY PACK LITHONIA LDN6-50-20-L06-AR-LSS-MVOLT-GZ10-EL 23 2000 lm SEMI-SPECULAR LED 5000 K RECESSED X X
D 6" LED DOWNLIGH (WET LOCATION) LITHONIA LDN6-50-15-L06-AR-LSS-MVOLT-GZ1-WL 21 1500 lm SEMI-SPECULAR LED 5000 K RECESSED X
DE 6" LED DOWNLIGHT W/BATTERY PACK (WET LOCATION) LITHONIA LDN6-50-15-L06-AR-LSS-MVOLT-GZ10-EL-WL 21 1500 lm SEMI-SPECULAR LED 5000 K RECESSED X X
F 2' VANITY LIGHT SUNPARK FL2103D-5000K 23 2200 lm SATIN NICKEL LED 5000 K ABOVE MIRROR 2
H 4' INDUSTRIAL PENDANT LIGHT LITHONIA FEM-L48-4000LM-LPACL-MD-MVOLT-GZ10-50K-80CRI-BSL520 30 4000 lm LED 5000 K PENDANT AT 9' AFF X
P LED Single Head Sign Light for Wall or Ceiling Mount Cooper Lighting 303-S1 CITY SILVER LED WALL MOUNT AT 10'-10" AFF 3 Sign & Ceiling
WE WALL PACK WITH BATTERY PACK COOPER ENT-E01-LED-E1-BL2-DP-7050-BBB(277V) 25 2738 lm DARK PLATINUM LED 5000 K WALL MOUNT AT 8' AFF X 3
X1 WALL MOUNT SINGLE FACE EXIT SIGN LITHONIA LRP-1-RC-120/277-ELN 3 BRUSHED ALUMINUM LED WALL MOUNT ABOVE DOOR X
X2C CEILING MOUNT DOUBLE FACE EXIT SIGN LITHONIA LRP-2-RW-120/277-ELN 3 BRUSHED ALUMINUM LED CEILING RECESSED X 1
X3 WET LOCATION EXIT SIGN LITHONIA WLTE-GY-1-R-EL 3 GRAY LED WALL MOUNT ABOVE DOOR X 3
GENERAL NOTES:
A. ALL FIXTURES SHALL BE CAPABLE OF 120V AND 277V INPUT (MVOLT), UNO.
B. REFER TO LIGHTING PLANS AND SPECIFICATIONS FOR ADDITIONAL FIXTURE INFORMATION.
C. "X" IN THE SCHEDULE INDICATES ITEM IS REQUIRED.
E ALL LENS SHALL BE A MINIMUM 0.125" THICKNESS, UNO.
REFERENCE NOTES:
1. NUMBER OF FACES AND DIRECTIONAL CHEVRONS AS INDICATED ON DWGS.
2. FIXTURE SHALL BE SUITABLE FOR DAMP LOCATIONS.
3. FIXTURE SHALL BE SUITABLE FOR WET LOCATIONS.
HC
LC
HCE
LCE
MISCELLANEOUS 7700 VA 100.00% 7700 VA
KITCHEN 0 VA 0.00% 0 VA
ELECTRIC HEAT 39241 VA 100.00% 39241 VA Total Est. Demand... 147 A
AC / HEAT PUMP 68271 VA 100.00% 68271 VA Total Conn. Current: 147 A
RECEPTACLES 7200 VA 100.00% 7200 VA Total Est. Demand: 122.4 kVA
EXTERIOR LIGHTING 0 VA 0.00% 0 VA Total Conn. Load: 122.4 kVA
INTERIOR LIGHTING 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
156 A 142 A 144 A
43 kVA 39 kVA 40 kVA
41 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 42
39 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 40
37 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 38
35 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 36
33 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 34
31 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 32
29 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 30
27 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 28
25 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 26
23 -- -- SPACE ONLY 0.0 10.4 24
21 -- -- SPACE ONLY 0.0 10.4 22
19 2.5 10.4
RTU-1 3 50 A
17 2.5 2.2 18
15 A 3 TU1-4
2.5 2.2 16
13 3.0 2.2
TU1-3 3 15 A
11 3.0 3.7 12
15 A 3 TU1-2
3.0 3.7 10
7 15 A 1 TU1-5 1.3 3.7
TU1-1 3 20 A
5 7.4 10.7 6
3 7.1 10.7 4
70 A 3 XFMR TC
9.7 10.7
EWH - ELEC/MECH ROOM 16 3 50 A
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
225 AMP MCB 480/277 Wye 3 PH 4 W MOUNT: SURFACE PANEL ASSEMBLY RATED (KAIC): 30 KAIC
PANELBOARD SCHEDULE HC LOCATION:
ELEC/MECH
ROOM 16
FED FROM:
MISCELLANEOUS 7700 VA 100.00% 7700 VA
KITCHEN 0 VA 0.00% 0 VA
ELECTRIC HEAT 7422 VA 100.00% 7422 VA Total Est. Demand... 67 A
AC / HEAT PUMP 2030 VA 100.00% 2030 VA Total Conn. Current: 67 A
RECEPTACLES 7200 VA 100.00% 7200 VA Total Est. Demand: 24.2 kVA
EXTERIOR LIGHTING 0 VA 0.00% 0 VA Total Conn. Load: 24.2 kVA
INTERIOR LIGHTING 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
* PROVIDE A GFI CIRCUIT BREAKER AS INDICATED.
82 A 59 A 62 A
10 kVA 7 kVA 7 kVA
41 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 42
39 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 40
37 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 38
35 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 36
33 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 34
31 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 32
29 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 30
27 15 A 1 F-2 0.1 0.0 SPARE 1 20 A 28
25 2.4 1.5 26
30 A 2 EUH-1
2.4 1.5
EUH-2 2 20 A
21 0.9 0.2 REC - ON ROOF 1 20 A 22
30 A 2 DSS-1B
0.9 0.0 F-1 1 15 A 20
17 20 A 1 REC - RM 15 0.2 0.1 ECP-1 - RM 16 1 20 A 18
15 20 A 1 REC - RM 15 1.5 1.2 REC - RM 15 1 20 A 16
13 20 A 1 RECS - RM 15, 16, 13 0.9 1.4 REFRIG.- RM 15 1 20 A 14
11 20 A 1 PLOTTER - RM 12 0.8 1.1 RECS - RM 10, 12 & EXTERIOR 1 20 A 12
9 20 A 1 RECS - RM 07, 18, 17, 12, 04 1.1 1.1 RECS - RM 09, 08, 06, 12 1 20 A 10
7 20 A 1 RECS - RM 04 & EXTERIOR 1.1 0.8 * WATER FOUNTAIN - RM 04 1 20 A 8
5 20 A 1 EXTERIOR RECS 0.5 1.1 RECS - RM 01, 05, 03 1 20 A 6
3 20 A 1 METAL DETECTOR - RM 03 0.5 0.5 X-RAY - RM 03 1 20 A 4
1 20 A 1 AUTO DOOR 0.5 0.5 AUTO DOOR - RM 03 1 20 A 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
150 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: SURFACE PANEL ASSEMBLY RATED (KAIC): 10 KAIC
PANELBOARD SCHEDULE LC LOCATION:
ELEC/MECH
ROOM 16
FED FROM: TC
MISCELLANEOUS 500 VA 100.00% 500 VA
KITCHEN 0 VA 0.00% 0 VA
ELECTRIC HEAT 0 VA 0.00% 0 VA Total Est. Demand... 11 A
AC / HEAT PUMP 0 VA 0.00% 0 VA Total Conn. Current: 10 A
RECEPTACLES 4500 VA 100.00% 4500 VA Total Est. Demand: 9.3 kVA
EXTERIOR LIGHTING 125 VA 125.00% 156 VA Total Conn. Load: 8.7 kVA
INTERIOR LIGHTING 2347 VA 125.00% 2934 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
13 A 11 A 8 A
3 kVA 3 kVA 2 kVA
23 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 24
21 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 22
19 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 20
17 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 18
15 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 16
13 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 14
11 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 12
9 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 10
7 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 8
5 0.7 1.6 LIGHTS 1 20 A 6
3 2.5 0.5 EGRESS LIGHTS AND EXIT SIGNS 1 20 A 4
25 A 3 XFMR TCE
3.0 0.4 EXTERIOR LIGHTS VIA "ELCP" 1 20 A 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
60 AMP MCB 480/277 Wye 3 PH 4 W MOUNT: SURFACE PANEL ASSEMBLY RATED (KAIC): 30 KAIC
PANELBOARD SCHEDULE HCE LOCATION:
ELEC/MECH
ROOM 16
FED FROM:
MISCELLANEOUS 500 VA 100.00% 500 VA
KITCHEN 0 VA 0.00% 0 VA
ELECTRIC HEAT 0 VA 0.00% 0 VA Total Est. Demand... 17 A
AC / HEAT PUMP 0 VA 0.00% 0 VA Total Conn. Current: 17 A
RECEPTACLES 4500 VA 100.00% 4500 VA Total Est. Demand: 6.2 kVA
EXTERIOR LIGHTING 0 VA 0.00% 0 VA Total Conn. Load: 6.2 kVA
INTERIOR LIGHTING 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
27 A 23 A 6 A
3 kVA 2 kVA 1 kVA
23 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 24
21 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 22
19 -- -- SPACE ONLY 0.0 0.0 SPACE ONLY -- -- 20
17 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 18
15 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 16
13 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 14
11 20 A 1 SPARE 0.0 0.0 SPARE 1 20 A 12
9 20 A 1 FASP- VESTIBULE 01 0.5 0.0 SPARE 1 20 A 10
7 20 A 1 REC - IT ROOM 14 0.4 0.4 REC - IT ROOM 14 1 20 A 8
5 20 A 1 REC - IT ROOM 14 0.4 0.4 REC - IT ROOM 14 1 20 A 6
3 20 A 1 RECS - RM 10, 09 0.9 1.1 RECS - RM 07, 13 1 20 A 4
1 20 A 1 SECURITY SYSTEM 1.2 1.1 RECS - RM 08, 06, 03B 1 20 A 2
CKT BRKR POLE LOAD A B C LOAD POLE BRKR CKT
50 AMP MCB 120/208 Wye 3 PH 4 W MOUNT: SURFACE PANEL ASSEMBLY RATED (KAIC): 10 KAIC
PANELBOARD SCHEDULE LCE LOCATION:
ELEC/MECH
ROOM 16
FED FROM: TCE
WALL MOUNT 24" STEM SINGLE HEAD SIGN LIGHT COOPER LIGHTING 303-S1-LEDB2-4000-UNV-T5X-DIM10-CS-24-EDGE 16 1425 lm 4000K
X
WALL MOUNT SIGN LIGHT
EX "MDPWD" EX "EMDPW"
| Sheets |
| E0.1 - LEGENDS, ABBREVIATIONS AND GENERAL NOTES |
| E1.0 - ELECTRICAL SITE PLAN |
| E2.1 - FLOOR PLAN - LIGHTING ,MECHANICAL POWER, & ROOF ELECTRICAL |
| E2.2 - FLOOR PLAN - POWER & LOW VOLTAGE SYSTEMS |
| E4.1 - ELECTRICAL DETAILS |
| E4.2 - ELECTRICAL DETAILS |
| E5.1 - POWER ONE-LINE DIAGRAM & PANEL SCHEDULES |
| E5.2 - LIGHT FIXTURE SCHEDULE & PANEL SCHEDULES |