This document is the Fire Life Safety (FLS) Standard Design for FAA terminal facilities. It provides requirements and code references for the design of FLS systems, including emergency lighting, fire pumps, elevators, fire alarm systems, and stairwell pressurization. The standard specifies that a dedicated FLS distribution bus must be incorporated into the power distribution system, with separate transfer switches feeding emergency distribution panels, fire pumps, and elevators. It also addresses load shedding considerations for the FLS system. The document includes conceptual drawings for incorporating the FLS bus into various standard FAA power distribution system configurations. This standard must be applied to all new FAA terminal facility design and construction projects, and coordination with the FAA is required when upgrading existing facilities.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Task Order 0025
Terminal Facilities Standard Design
FLS Bus Study
June 2, 2021
Fire Life Safety and Electrical Work Group Final
FLS Standard
TABLE OF CONTENTS PAGE
SECTION 1.0 EXECUTIVE SUMMARY
1.1 General Information
1.2 Purpose
1.3 Goal
1.4 Application
SECTION 2.0 CODE REQUIREMENT
2.1 Applicable Codes and Standards
2.2 General Information per Industry code and standards
2.3 Life Safety Systems Standard Requirements
2.4 FAA-Specific Fire Life Safety Systems Requirements
2.5 FLS Code References Table
SECTION 3.0 FAA FLS SYSTEM REQUIREMENT SUMMARY AND
CONSIDERATION
3.1 Fire Life Safety (FLS) Distribution Bus Design
3.2 Load Shedding Consideration
SECTION 4.0 APPENDICES
APPENDIX – 01
FLS Distribution Bus Concept Drawings
SECTION 1.0 EXECUTIVE SUMMARY
1.1 General Information
This design guideline was developed to ensure the FAA required Fire Life Safety (FLS)
Bus and associated designated load are incorporated into the power distribution systems of the Air Traffic Control Towers (ATCT) and Terminal Radar Approach
Control (TRACON) facilities based upon Technical Operations Services (AJW-24) and the FAA FLS workgroup inputs.
The primary focus of this standard is to illustrate the arrangement of commercial utility and standby power sources for fire pumps, elevators, stair pressurization equipment, egress lighting, and fire detection/alarm systems per standard and code requirements, and FAA Fire Life Safety design requirements.
This document captures the unique FLS design criteria (at a conceptual level) from evaluation and ongoing discussion with power services and the FLS workgroup.
Concept drawings in Appendix 01 include a Fire Life Safety (FLS) Bus added to four standard FAA power distribution system: Critical Power Distribution System (CPDS)
Type Basic, CPDS Type Radial, CPDS Type 1, and CPDS Type 2. The type of CPDS and associated detail standard design single line diagram for each project shall be coordinated with FAA.
Refer to Terminal Facility Design Standard (TFDS) Chapter 14 – Vertical Conveyance for elevator requirement.
Refer to TFDS and standard schematic drawings for power distribution system.
1.2 Purpose
The purpose of this design guideline is to provide the Design Engineer with FAA design requirements and code references to identify building systems that are required to be supplied from the FLS bus. This FLS design guideline also provides references on fire rating requirement of rooms that house and feed the FLS system and equipment.
1.3 Goal
The goal of this FLS guideline is to ensure code compliant and FAA specific fire life safety features/requirements are implemented in a consistent standardized approach.
The fire life safety feature includes:
• Emergency lighting equipment.
• Fire pump electric motors.
• Elevators
• Fire alarm detection system
• Stairwell pressurization system
1.4 Application
FLS standard shall be applied to all new terminal facility design/construction projects.
Where existing facilities require electrical system upgrade, coordination and investigation to existing system and site condition shall be performed. Confirm and verify feasibility of the FLS upgrade for existing facility with FAA.
SECTION 2.0 CODE REQUIREMENT
2.1 Applicable Codes and Standards
International Building Code (IBC), 2021 Edition
International Fire Code (IFC), 2018 Edition
NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2019
Edition
NFPA 25, Standard for the Inspection, Testing and Maintenance of Water-Based Fire
Protection Systems, 2020 Edition
NFPA 70, National Electrical Code, (NEC) 2020 Edition
NFPA 72, National Fire Alarm and Signaling Code, 2019 Edition
NFPA 101, Life Safety Code, (LSC), 2021 Edition
NFPA 110, Standard for Emergency and Standby Power Systems, 2019 Edition
FAA Order 6480.7E, Airport Traffic Control Tower (ATCT) and Terminal Radar Approach
Control (TRACON) Design Policy
FAA Order 6030.20G, Electrical Power Policy
FAA Order 6950.2E (CHG-2), Electrical Power Policy Implementation at National
Airspace System Facilities
Institute of Electrical and Electronics Engineers (IEEE), Standard 446-1995, Recommended Practice for Emergency and Standby Power Systems for Industrial and
Commercial
2.2 General Information per Industry code and standards
Chapter 27 of the IBC establishes the requirements for electrical installations within buildings and structures [IBC 2701.1]. Section 2702.2 identifies where emergency and standby power systems are required to be provided, e.g. elevators and platform lifts
[IBC 2702.2.2]; exit signs [IBC 2702.2.6]; means of egress lighting [IBC 2702.2.14];
smoke control systems [IBC 2702.2.17].
For detailed design and construction requirements for the electrical components, equipment and systems, the IBC references the NEC. The NEC categorizes these systems into three types:
1. Emergency systems (Article 700);
2. Legally required standby systems (Article 701); and
3. Optional standby systems (Article 702).
Emergency Systems: According to the IBC Commentary, emergency power systems are intended to provide electrical power for life safety systems, such as egress illumination, emergency communications, and fire pumps. In other words, emergency power is required when the loss of normal power would endanger occupants. One of the key features of emergency systems is the required response, or transfer time, of
10 seconds or less. Sources of power for emergency power systems [NEC 700.12] include storage batteries, generators, uninterruptible power supplies, separate services, fuel cell systems, DC microgrid systems, and unit equipment.
Standby Systems: According to the IBC Commentary, standby power systems are intended to provide electrical power for loads not as critical as those requiring emergency power. Standby power loads include smoke control systems; certain elevators (fire service access elevator, elevator as means of egress); certain hazardous material operations; smoke-proof enclosures; illumination; heating, ventilating and air-conditioning (HVAC) systems; refrigeration and sewage pumps. Standby power systems must provide power within 60 seconds of failure of primary (utility) power.
Sources of power for standby systems [NEC 701.12] include storage batteries, generators, uninterruptible power supplies, separate services, fuel cell systems, DC microgrid systems, unit equipment and a source that is taken from a point of connection ahead of the normal service disconnecting means. Where acceptable to the authority having jurisdiction, connections located ahead of and not within the same cabinet, enclosure, or vertical switchboard section as the service disconnecting means shall be permitted. The legally required standby service shall be sufficiently separated from the normal main service disconnecting means to prevent simultaneous interruption of supply through an occurrence within the building or groups of buildings served [NEC
701.12(F)].
Optional Standby Systems: Optional standby systems are those systems intended to supply power to public or private facilities or property where life safety does not depend on the performance of the system [NEC 702.2]. Optional standby systems are those in which failure can cause physical discomfort, serious interruption of an industrial process, damage to process equipment, or disruption of business. For example, failure of an optional standby generator at a frozen food processing plant [NEC Handbook].
This FLS design standard focuses on Emergency and Standby systems.
2.3 Life Safety Systems Standard Requirements
Various sections of the IBC establish which building systems and equipment are required to be provided with either a standby power system or an emergency power system.
IBC Requirements:
Per IBC sections 412 and 2702, the following systems and equipment in an ATCT are required to be provided with standby power and/or emergency power:
1. Elevator;
2. Fire pump
3. Lighting for egress illumination
4. Automatic smoke detection systems;
5. Fire command center
6. Smoke removal system
In addition to the code requirements, the fire life safety systems shall also meet the requirements indicated in section 2.4.
2.4 FAA-Specific Fire Life Safety Systems Requirements
A dedicated fire life safety electrical distribution is required with separate transfer switches that feed emergency distribution panel(s), fire pump, and elevator equipment.
The emergency distribution panelboard is originated from the facility dedicated “FLS” distribution bus.
The power pathway is provided to serve classified FLS and emergency loads per
NFPA-70, Article 700, Emergency Systems. FLS and emergency loads include:
• Exit signage, egress lighting;
• Facility emergency task illumination;
• Fire pump;
• Automatic smoke detection systems;
• Fire Command Center
The following system has been elevated to FLS system for FAA mission requirement:
• Stairwell pressurization system,
• Elevator(s).
The FLS and emergency distribution system overcurrent protective scheme must be designed to achieve the selective coordination requirements per article 700. A selectively coordinated overcurrent protection scheme that localizes and minimizes the extent of an interruption of power due to the opening of a protective device is a critical safety element. Selective coordination is to be carried through each level of distribution that supplies power to the emergency system.
Selective Coordination Definition per NFPA70:
Localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the selection and installation of overcurrent protective devices and their ratings or settings for the full range of available overcurrents, from overload to the available fault current, and for the full range of overcurrent protective device opening times associated with those overcurrents.
The table in section 2.5 summarizes the requirements and code references for the fire life safety systems.
2.5 FLS Code References Table
Line
Item
No.
System per IBC
FAA Standby
Power
Systems
Classification1
FAA
Power
Bus2
Code Reference
Code/Stds Version Section
1 a.
Stair
Pressurization
System
Fire/Life
Safety
Standby
Power
Systems
(FLS-SPS)
Fire / Life
Safety
IBC 2021
412.2.3 b.
Automatic
Smoke
Detection
Systems
412.2.3.1 c.
Fire Command
Center 412.2.3.2
412.2.3.3
IBC 2021
909.11
909.20.7.1
909.20.7.2
IBC 2021 911
NFPA 101
(LSC)
2021 7.2.3.12
Item
No.
System per IBC
FAA Standby
Power
Systems
Classification1
FAA
Power
Bus2
Code Reference
Code/Std. Version Section
2 a. Exit signs
Fire/Life
Safety
Standby
Power
Systems
(FLS-SPS)
Fire / Life
Safety
IBC
1008.3 b.
Means of egress illumination
1008.3.1
1008.3.2
1008.3.3
IBC 2021 1013.6.3
NFPA 70 2020 700.17
NFPA 101
(LSC)
7.9.2.1
7.9.2.2
3 a.
Fire Service
Access Elevator
Fire/Life
Safety
Standby
Power
Systems
(FLS-SPS)
Fire / Life
Safety
IBC 2021 412.2.5
IBC 2021 2702.2.2
b.
Elevator
Machine Room
IBC 2021 3003
IBC 2021
3007.4
3007.5.2
3007.7
3007.8
Systems
Classification1
FAA
Power
Bus2
Code Reference
Code/Std. Version Section c.
Elevator as part of Means of
Egress
Fire/Life
Safety
Standby
Power
Systems
(FLS-SPS)
Fire / Life
IBC 2021 1009.4
**Refer to TFDS chapter 14 – Vertical
Conveyance for elevator requirement**
NFPA 101
(LSC)
2021 7.5.4.7
4 a.
Fire Alarm
System Fire/Life
Safety
Standby
Power
Systems
(FLS-SPS)
Fire / Life
IBC 2021 907.2
NFPA 72 2019
10.6.3.2
10.6.4.2
10.6.11.3.
1.1
10.6.11.3.
1.2
5 a. Fire pump
Fire/Life
Safety
Standby
Power
Systems
(FLS-SPS)
Fire / Life
IBC 2021 913.1
b.
Fire pump supply conductors
NFPA 70 2020
695.3 (A)
695.3 (B)
695.6
NFPA 20 2019 9.6.2
Systems
Classification1
FAA
Power
Bus2
Code Reference
Code/Std. Version Section
6 a.
Emergency system feeder conductor
Fire/Life
Safety
Standby
Power
Systems
(FLS-SPS)
Fire / Life
Safety
NFPA 70 2020 700.10
a.
FAA NAS
Equipment
NAS
Standby
Power
Systems
(NAS-SPS).
Critical
FAA
6030.20
G
3-4, 4-2 b.
Facility Normal
Lighting &
Equipment
Essential 3-4, 4-2
1 Classification of FAA Standby Power Systems per FAA Power Policy 6030.20G:
• Fire/Life Safety Standby Power Systems [FLS-SPS] = NEC Art 700 [Emergency System];
• NAS Standby Power System [NAS-SPS] = NEC Art 701 [Legally Required Standby Systems]
2 Power Bus Description per FAA Power Policy 6030.20G:
• Fire/Life Safety Bus – Provide unconditioned AC prime and standby power to approved Fire/Life Safety systems and equipment. [Commercial Utility + Standby E/G power source]
• Essential Bus – Provide unconditioned AC prime and standby power to approved FAA and non-FAA systems and systems. [Commercial Utility + Standby E/G power source]
• Critical Bus - Provide conditioned, uninterruptible AC prime and standby power to approved NAS system and equipment, non-NAS FAA sensitive electronic processing equipment, and non-FAA system for site support. [Essential + Uninterruptible Power Supply (UPS)]
SECTION 3.0 FAA FLS System Requirement Summary and
Consideration
3.1 Fire Life Safety (FLS) Distribution Bus Design
1) The FLS Distribution Bus Concept design included in Appendix 01 shall be utilized as the basis of design for all new FAA Terminal Facilities. System configuration (Standard Radial, CPDS, etc) shall be coordinated and determined with the FAA.
2) Provide dedicated automatic transfer switch (ATS) for all elevators(s), Fire
Pump and Emergency Distribution Panelboard.
3) Battery-powered lighting equipment is used to achieve compliance with NFPA-
70 class emergency systems and to ensure continuity of FAA operational mission within the facility in the event of failure to either commercial power or
E/G supplied standby power systems. Battery powered equipment is the most feasible method to mitigate the potential risk of losing facility safety lighting in the event of total loss of power.
4) Battery lights shall be provided in the exit stairwells, egress path, and where deemed necessary for the facility operation.
5) FAA requires additional battery backup powered lighting in addition to code required safety lighting for following areas:
• E/G room,
• Main electrical room, and
• UPS room
6) The use of generator transfer device (GTD) or other technology may be proposed to the FAA for review and concurrence on a case-by-case basis.
3.2 Load Shedding Consideration
Load shedding should be considered as a last resort and only after fire pump is being right sized for the new facility/design. Load shedding may be employed if the fire pump motor HP rating results in significant increase in E/G size. Load shedding operation shall be initiated by the fire pump ATS/controller’s load shed contact.
The following scenarios shall be considered when load shedding sequence of operation is being developed:
Scenario 1: Loss of commercial utility power -> E/G start while fire pump in off state.
Scenario 2: Loss of commercial utility power -> E/G start while fire pump in run state.
Scenario 3: FAA facility load is connected to E/G while fire pump is connected to utility in run state -> loss of utility -> fire pump in run state to transfer to E/G
Sequence of transfer / operation of facility ATSs, including ATS supplying FLS distribution panelboard, fire pump, and elevators, shall be considered when load shedding is required.
SECTION 4.0 APPENDICES
Appendix – 01: FLS Distribution Bus Concept Drawings
APPENDIX – 01
FLS Distribution Bus Concept Drawings
Appendix – 01: FLS Distribution Bus Concept Drawings
Tab No. Description
Tab-01 FLS Distribution Bus – Basic Power Distribution
Tab-02 FLS Distribution Bus – CPDS Typical Radial Distribution
Tab-03 FLS Distribution Bus – CPDS Type 1 Distribution
Tab-04 FLS Distribution Bus – CPDS Type 2 Distribution
The FLS Bus configuration drawings indicated above depict the FAA standard Basic and CPDS power distribution systems.
Basic Power Distribution / CPDS Typical Radial Distribution – One commercial utility power feed plus a standby engine generator. A single essential automatic transfer switch provides both commercial and standby E/G power to the facility essential main distribution panel. The entire facility is backed up by the E/G power source. FLS bus is originated from the E/G distribution panel.
CPDS Type 1 Distribution – One Commercial utility power feed plus one standby engine generator. Two essential automatic transfer switches provide both commercial and standby
E/G power to two facility main essential distribution panels. Normal power distribution panel without E/G backed up power is available. FLS bus is originated from the E/G distribution panel.
CPDS Type 2 Distribution – Two Commercial utility power feeds plus two standby engine generators and associated distribution panels. Two essential automatic transfer switches provide both commercial and standby E/G power to two facility main essential distribution panels. Normal power distribution panel without E/G backed up power is available. FLS bus is originated from one of the E/G distribution panels.
UTILITY
UTILITY TRANSFORMER
NORMAL
FIRE PUMP
DISCONNECT LOAD BANK
TEMPORARY
GENERATOR
CONNECTION
STANDBY
ENGINE-GENERATOR G
FLS
MUST COMPLY WITH
NFPA-695.3 (B)
COLOR CODE DESCRIPTION:
FP
FIRE PUMP
FACILITY NORMAL
LIGHTING
FAA NAS LOADS
OTHER
FIRE LIFE SAFETY
STAIR
PRESSURIZATION
Emergency Panel(s)
FIRE
SERVICE
FIRE
SERVICE
ELEVATOR
ATS ATS
BUS WITH SHARED POWER LOADS
UTILITY "NORMAL" POWER
EMERGENCY NEC, ARTICLE 700
STANDBY NEC, ARTICLE 701
FIRE PUMP NEC, ARTICLE 695
FAA, ESSENTIAL
NOTES:
Emergency Distribution Panel
ATS FLS
2 2 2
1 1
ESSENTIAL BUS FLS BUS
ATS
Controller
ATS with
Fire Pump
ELEVATOR
FLS DISTRIBUTION BUSFAA ATO
TERMINAL FACILITIES STANDARD DESIGNS SCHEMATIC DIAGRAM TYPE - BASIC
DIST PANEL
Essential Distribution Panel
Generator Panel
Main Service
1 1
FUNCTION’S PRIORITY ELEVATED TO EMERGENCY FOR
FAA PURPOSE.
OPTIONAL DIRECT CONNECTION FROM SEPARATE
UTILITY SERVICE.
CENTRALIZED BATTERY SYSTEM OR UNIT EQUIPMENT
IN STAIRWELLS AND DESIGNATED TASK AREAS.
PROVIDE 1'-0" VERTICAL & 4'-0" HORIZONTAL
SEPARATION BETWEEN FACILITY NORMAL LIGHTING
CIRUITS & EMERGENCY LIGHTING CIRCUITS.
PROVIDE 2-HOUR ROOM CONSTRUCTION.
AND FEEDER PROTECTION.
PROVIDE 2-HOUR FEEDER RATING FOR CONSTRUCTION
FOR BRANCH CIRCUIT LOADS.
CONSTRUCTION PROTECTION IS NOT APPLICABLE
2-HR RATING REQUIREMENT FOR FEEDER AND
5 7
CIRCUITS
LIGHTING
UTILITY
NORMAL
FIRE PUMP
DISCONNECT LOAD BANK
TEMPORARY
GENERATOR
CONNECTION
STANDBY
ENGINE-GENERATOR G
FLS
MUST COMPLY WITH
NFPA-695.3 (B)
COLOR CODE DESCRIPTION:
FP
FIRE PUMP
FACILITY NORMAL
LIGHTING
FAA NAS LOADS
OTHER
FIRE LIFE SAFETY
STAIR
PRESSURIZATION
Emergency Panel(s)
FIRE
SERVICE
FIRE
SERVICE
ELEVATOR
ATS ATS
BUS WITH SHARED POWER LOADS
UTILITY "NORMAL" POWER
EMERGENCY NEC, ARTICLE 700
STANDBY NEC, ARTICLE 701
FIRE PUMP NEC, ARTICLE 695
FAA, ESSENTIAL
NOTES:
Emergency Distribution Panel
ATS FLS
2 2 2
1 1
ESSENTIAL BUS FLS BUS
ATS
Controller
ATS with
Fire Pump
ELEVATOR
FLS DISTRIBUTION BUSFAA ATO
TERMINAL FACILITIES STANDARD DESIGNS SCHEMATIC DIAGRAM TYPE - RADIAL
DIST PANEL
Main Service
Generator Panel
Essential Distribution Panel
1 1
5 7
CIRCUITS
LIGHTING
FUNCTION’S PRIORITY ELEVATED TO EMERGENCY FOR
FAA PURPOSE.
OPTIONAL DIRECT CONNECTION FROM SEPARATE
UTILITY SERVICE.
CENTRALIZED BATTERY SYSTEM OR UNIT EQUIPMENT
IN STAIRWELLS AND DESIGNATED TASK AREAS.
PROVIDE 1'-0" VERTICAL & 4'-0" HORIZONTAL
SEPARATION BETWEEN FACILITY NORMAL LIGHTING
CIRUITS & EMERGENCY LIGHTING CIRCUITS.
PROVIDE 2-HOUR ROOM CONSTRUCTION.
AND FEEDER PROTECTION.
PROVIDE 2-HOUR FEEDER RATING FOR CONSTRUCTION
FOR BRANCH CIRCUIT LOADS.
CONSTRUCTION PROTECTION IS NOT APPLICABLE
2-HR RATING REQUIREMENT FOR FEEDER AND
UTILITY UTILITY
NORMAL
FIRE PUMP
DISCONNECT LOAD BANK
TEMPORARY
GENERATOR
CONNECTION
STANDBY
ENGINE-GENERATOR G
FLS STANDBY FLS
UTILITY TRANSFORMER
Main Service B
NORMAL
ENGINE-GENERATOR G
MUST COMPLY WITH
NFPA-695.3 (B)
COLOR CODE DESCRIPTION:
FP
FIRE PUMP
ATS A ATS B
FACILITY NORMAL
LIGHTING
FAA NAS LOADS
FACILITY NORMAL
LIGHTING
OTHER
FIRE LIFE SAFETY
STAIR
PRESSURIZATION
Emergency Panel(s)
FIRE
SERVICE
ELEVATOR
FIRE
SERVICE
ELEVATOR
ATS ATS
BUS WITH SHARED POWER LOADS
UTILITY "NORMAL" POWER
EMERGENCY NEC, ARTICLE 700
STANDBY NEC, ARTICLE 701
FIRE PUMP NEC, ARTICLE 695
MAINTENANCE
FAA, ESSENTIAL
NOTES:
FUNCTION’S PRIORITY ELEVATED TO EMERGENCY FOR
FAA PURPOSE.
OPTIONAL DIRECT CONNECTION FROM SEPARATE
UTILITY SERVICE.
CENTRALIZED BATTERY SYSTEM OR UNIT EQUIPMENT
IN STAIRWELLS AND DESIGNATED TASK AREAS.
PROVIDE 1'-0" VERTICAL & 4'-0" HORIZONTAL
SEPARATION BETWEEN FACILITY NORMAL LIGHTING
CIRUITS & EMERGENCY LIGHTING CIRCUITS.
Generator Panel A Generator Panel B
TEMPORARY
GENERATOR
CONNECTION
LOAD BANK
Main Service A
DIST PANEL A
DIST PANEL B
Emergency Distribution Panel
Essential Distribution Panel BEssential Distribution Panel A
ATS FLS
2 2
1 1
ESSENTIAL BUS ESSENTIAL BUS
FLS BUS
Controller
ATS with
Fire Pump
FLS DISTRIBUTION BUSFAA ATO
TERMINAL FACILITIES STANDARD DESIGNS SCHEMATIC DIAGRAM TYPE - CPDS 2
1 1
PROVIDE 2 HOUR ROOM CONSTRUCTION.
PROVIDE 2 HOUR FEEDER RATING FOR CONSTRUCTION
SOURCE SWITCHING EVENTS.
IS LEFT WITHOUT NORMAL LIGHTING DURING POWER
MAINTENANCE PROCEDURES AND ENSURE NO SPACE
REQUIRED TO FACILITATE POWER PATH A/B FEEDER
PATHS A/B. CIRCUIT DIVERSITY IN THESE SPACES IS
HAVE LIGHTING LOADS DIVERSIFIED BETWEN POWER
ROOMS WITH POWER SWITCHING EQUIPMENT SHOULD
AND FEEDER PROTECTION.
CIRCUITS
LIGHTING
FOR BRANCH CIRCUIT LOADS.
CONSTRUCTION PROTECTION IS NOT APPLICABLE
2-HR RATING REQUIREMENT FOR FEEDER AND
| Section 1 - Executive Summary |
| Section 2 - Code Requirement |
| 2.1 - Applicable Codes and Standards |
| 2.2 - General Information per Industry Code and Stadnards |
| 2.3 - Life Safety Systems Standard Requirements |
| 2.4 - FAA Specific FLS Requirements |
| 2.5 - FLS Code References Table |
| Section 3 - FAA FLS System Requirement Summary and Consideration |
| 3.1 FLS Dist Bus Design |
| 3.2 Load Shedding Consideration |
| Appendix-01 |
| FLS Diagrams |
| Basic |
| Radial |
| CPDS 1 |
| CPDS 2 |