Attach 12. Plans Section E Electrical 2Feb2026.pdf
PDF 5 MB Posted
- Attached to
- Pactola Loop B Campground Reconstruction Project
- Solicitation number
- 1240LT26Q0010
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a set of electrical construction plans and specifications for the Pactola Campground Loop B Reconstruction project located in the Black Hills National Forest, Mystic Ranger District, managed by the U.S. Department of Agriculture Forest Service, Region 2 (Rocky Mountain Region).
The electrical work encompasses installation of underground service distribution, three pad-mounted transformers (T-1, T-2, T-3), three electrical panels (L-1, L-2, L-3), and multiple 100-amp RV pedestals serving host/volunteer sites #1, #2, #34, #36, #37, and #38. The project includes a new pump house equipped with electrical provisions for well pump control, chemical metering pump, receptacles, lighting, and a 3,000-watt heater. All work must comply with the National Electrical Code (NFPA 70), U.S. Forest Service Engineering Manual, local utility requirements, and NEMA standards. The contractor is responsible for locating existing underground utilities, coordinating with the local utility provider for service upgrades and meter installation, boring under paved surfaces, and restoring all disturbed areas upon completion. Grounding installations require 3/4-inch diameter copper-clad steel ground rods with supplemental grounding rods located at least six feet from primary rods. Panel schedules specify demand loads ranging from 5,431 VA for Panel L-3 (pump building) to 36,000 VA for Panel L-1 (host/volunteer sites #34-38). The project includes a bid option for two additional host/volunteer sites (#1 and #2) with corresponding pedestals and storage tank alarm systems.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATENO. REVISION / ISSUE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
GENERAL NOTES,
ABBREVIATIONS
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E0.1 43 52
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
1. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE (NFPA 70), U.S. FOREST SERVICE ENGINEERING MANUAL AND STANDARD SPECIFICATIONS AS WELL AS LOCAL ELECTRICAL UTILITY REQUIREMENTS AND ORDINANCES.
2. OBTAIN ALL NECESSARY PERMITS BEFORE COMMENCING WORK.
3. COORDINATE INSPECTIONS WITH THE AUTHORITY HAVING JURISDICTION (AHJ) AND THE CONTRACTING OFFICER.
4. INSTALL ELECTRICAL PROVISIONS FOR RV PEDESTALS AND CAMPGROUND FACILITIES AS INDICATED ON THE DRAWINGS.
5. ALL NEW ELECTRICAL EQUIPMENT, COMPONENTS, AND WIRING SHALL BE UL-LISTED, AND INSTALLED PER MANUFACTURER
RECOMMENDATIONS.
6. PROVIDE NEMA 3R WEATHERPROOF ENCLOSURES AND CONNECTIONS FOR ALL OUTDOOR EQUIPMENT.
7. TEST ALL ELECTRICAL CIRCUITS AND EQUIPMENT FOR PROPER OPERATION AND GROUNDING BEFORE FINAL ACCEPTANCE. SUBMIT
TEST RESULTS TO THE U.S. FOREST SERVICE FOR REVIEW.
8. COORDINATE ALL UTILITY CONNECTIONS AND SERVICE UPGRADES WITH THE LOCAL UTILITY PROVIDER.
9. VERIFY EXACT LOCATIONS OF EXISTING UTILITIES IN THE FIELD PRIOR TO EXCAVATION.
10. PRIOR TO EXCAVATION, VERIFY THE LOCATION OF ALL EXISTING UNDERGROUND UTILITIES, INCLUDING WATER, SEWER, AND GAS
LINES, THROUGH THE APPROPRIATE UTILITY LOCATING SERVICE.
11. ELECTRICAL CONTRACTOR SHALL BORE UNDER ANY EXISTING PAVED SURFACES.
12. WHERE UNDERGROUND ELECTRICAL LINES INTERSECT WITH SIGNIFICANT TREE ROOTS, USE TRENCHLESS METHODS (E.G., BORING) OR HAND-DIGGING TO PRESERVE TREE HEALTH. REPORT ANY UNAVOIDABLE ROOT DAMAGE TO THE CONTRACTING OFFICER.
13. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR RECALCULATING VOLTAGE-DROP FOR ALTERNATE CIRCUIT ROUTES AND SUBMITTING REVISED CALCULATIONS FOR APPROVAL IF ADDITIONAL CONDUCTOR LENGTHS ARE REQUIRED.
14. RESTORE ALL DISTURBED AREAS, INCLUDING VEGETATION AND PAVING, TO THEIR ORIGINAL CONDITION UPON COMPLETION OF WORK. EXCAVATIONS SHALL BE BACKFILLED WITH CLEAN, COMPACTED SOIL FREE OF DEBRIS AND SHARP OBJECTS.
GENERAL NOTESABBREVIATIONS
A AMPERE
AC ANALYSIS CONTROL SWITCH
AFF ABOVE FINISHED FLOOR
AIC AMPERE INTERRUPTING CAPACITY
AIT ANALYIS INDICATION TEMPERATURE
AIP ANALYSIS INDICATION PH
AL ALUMINUM
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
A/C ABOVE COUNTER
C CONDUIT
C/W COMPLETE WITH
CIR CIRCUIT
CU COPPER
DIV DIVISION
EC ELECTRICAL CONTRACTOR
EGC EQUIPMENT GROUNDING CONDUCTOR
EMT ELECTRIC METALLIC TUBING
EA VOLTAGE ALARM
ES VOLTAGE SWITCH
ER EXISTING TO REMAIN
FFC FLOW RATION CONTROL
FI FLOW INDICATION SWITCH
FS FLOW SWITCH
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GND GROUND
HC HAND CONTROL
HP HORSEPOWER
HZ HERTZ
IECC INTERNAL ENERGY CONSERVATION CODE
IMC INTERMEDIATE METALLIC CONDUIT
IN INCHES
KC TIME INDICATION SWITCH
KV KILOVOLT
KVA KILOVOLT-AMPS
KW KILOWATT
LA LEVEL ALARM
LB POUND
LED LIGHT EMITTING DIODE
LI LEVEL INDICATION SWITCH
LIC LEVEL INDICATION CONTROL
LPS LIGHTNING PROTECTION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MFR MANUFACTURER
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NUM NUMBER
NTS NOT TO SCALE
OEM ORIGINAL EQUIPMENT MANUFACTURER
OHD OVERHEAD (ROLLUP) DOOR
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTATION
P POLE
PC PRESSURE CONTROL
PH PHASE
PI PRESSURE INDICATION SWITCH
PRI PRIMARY
PVC POLYVINYL CHLORIDE
QI QUALITY INDICATION SWITCH
QTY QUANTITY
RL RELOCATE
RLD RELOCATED
RS RIGID STEEL
RMC RIGID METAL CONDUIT
RTU ROOFTOP UNIT
SC SPEED CONTROL
SCH SCHEDULE
SEC SECONDARY
SPD SURGE PROTECTIVE DEVICE
SQFT SQUARE FEET
TBD TO BE DETERMINED
TI TEMPERATURE INDICATION
TMP TEMPORARY
TYP TYPICAL
TSTAT THERMOSTAT
UG UNDERGROUND
UL UNDERWRITER LABORATORIES
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UH UNIT HEATER
V VOLTS
VAC VOLTS ALTERNATING CURRENT
VC VIBRATION CONTROL
VDC VOLTS DIRECT CURRENT
VS VIBRATION SWITCH
W WATTS
W/ WITH
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION PROOF
UFC UNITED FACILITIES CRITERIA
MV MEDIUM VOLTAGE
W
S
O
W
S O
W
S
O W S
O
E
M
W
S O
W
S O
W
S
O
W
M
E
D
.4
F.
F.
E.
E E
SD
SD
SD
.5
F.
F.
E.
T
T
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W
W
P-UGP-UGP-UG
P-UG
P-UG
P-UG
P-UG
P-UGP-UGP-UGP-UG
P- U
G
CP
-1
CP
-2
W
S
O
W
S O
W
S
O W S
O
E
M
.28 F.
F.E
W
S O
W
S O
W
S
O
W
M
E
.2
F.
F.
E.
D
.4
F.
F.
E.
E E
SD
SD
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
WW
W
S
O
W
S O
W
S
O W S
O
E
M
W
S O
W
S O
W
S
O
W
M
E
D
E E
SD
SD
T
W
W
W
P-UG
P-UG
P-UG
P-UG
P-UG
P-UG
P-UG
P-UGP-UGP-UGP-UG
P-
U G
P-U G
P-UG
P-UG
P-
UG
P- U
G
P-
UG
P- U
G
P-
UG
P-UG
P-UG
P-U G
W
W
W
W W
W
W
W
W
T
" 15
DATENO. REVISION / ISSUE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL SITE PLAN
DEMOLITION PLAN
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
ED1.0
44 52SCALE IN FEET
40' 80'20'0'
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
EXISTING UG ELECTRIC SERVICE TO REMAIN AS IS FOR REUSE WITH NEW PUMP HOUSE AND HOST/VOLUNTEER SITES.
CONTRACTOR TO CONFIRM EXISTING UG FEEDER CABLE ROUTING AND EITHER DEMO OR DISCONNECT FROM SERVICE LINE
AND ABANDON IN PLACE.
CONTRACTOR TO PROTECT AND REUSE CAMPSITE PEDESTAL WITH NEW ELECTRIC SERVICE.
EXISTING PUMP HOUSE TO REMAIN IN SERVICE UNTIL NEW PUMP HOUSE IS COMMISSIONED. ONCE NEW PUMP HOUSE IS IN SERVICE. EXISTING PUMP HOUSE TO REMAIN IN SERVICE UNTIL NEW PUMP HOUSE IS COMMISSIONED. ONCE NEW PUMP HOUSE IS IN SERVICE DEMO ALL ELECTRICAL EQUIPMENT INSIDE OF PUMP HOUSE (I.E. RECEPTACLES, CABLES, LIGHTS, SWITCHES, ETC.).
CONTRACTOR TO LOCATE AND CONFIRM FEEDER LOCATION TO EXISTING PUMP HOUSE AND HOST SITE. CONTRACTOR TO
PROTECT SERVICE CONDUCTORS FOR REUSE IN NEW PUMP HOUSE AND HOST SITE.
UTILITY TO CONFIRM EXISTING M.V. CABLE IS SUFFICIENTLY SIZED FOR NEW TRANSFORMER.
EXISTING TRANSFORMER TO BE REPLACED WITH NEW TRANSFORMER (BY UTILITY).
DEMOLITION KEYNOTES:DEMOLITION NOTES:
1. DEMO OR ABANDON IN PLACE.
DEMOLITION LEGEND
1. ALL DEMOLITION IS TO BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE CITY, COUNTY, STATE AND/OR GOVERNING BODY'S STANDARDS.
2. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL PERMITS ASSOCIATED WITH THE DEMOLITION WORK AS DESCRIBED & SHOWN ON THESE PLANS.
3. THE EXISTING UTILITY LOCATIONS SHOWN ON THE PLANS ARE APPROXIMATE AND MAY NOT INCLUDE ALL LINES PRESENT. THE CONTRACTOR SHALL BE RESPONSIBLE TO CALL "811", AND COORDINATE FIELD LOCATION OF EXISTING UNDERGROUND UTILITIES PRIOR TO BEGINNING DEMOLITION ACTIVITIES. !!KNOW WHAT'S BELOW. CALL BEFORE YOU DIG!!
4. CONTRACTOR SHALL COORD. WITH ELECTRIC, TELEPHONE/FIBER, AND CABLE PROVIDERS TO TERMINATE ALL EXISTING SERVICES TO BUILDINGS MARKED FOR DEMOLITION ON THESE PLANS. CONTRACTOR SHALL VERIFY WITH UTILITY PROVIDERS THAT SERVICES ARE DISCONNECTED PRIOR TO ANY REMOVAL OF INTERNAL SERVICE LINES.
5. THE DEMOLITION PLAN AND EXISTING CONDITIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL INSPECT AND FIELD VERIFY THE EXISTING SITE CONDITIONS TO BECOME ACQUAINTED WITH ALL EXISTING CONDITIONS WHICH EFFECT ANY AND ALL WORK ASSOCIATED WITH THE DEMOLITION PLANS.
6. ALL EXISTING BUILDING RELATED FEATURES NOT SHOWN ON THIS PLAN SHALL BE COORD. WITH ALL OTHER PLANS ASSOCIATED WITH THIS PROJECT. ALL CONCRETE OR ASPHALT PAVEMENT, CURB & GUTTER, RETAINING WALLS AND MISCELLANEOUS STRUCTURES INCLUDING BUT NOT LIMITED TO WATER HYDRANTS, FIRE RINGS, PICNIC TABLES, SITE NUMBERING POSTS, WHEELSTOPS, KIOSKS, INFO BOARDS, AND MISCELLANEOUS DEBRIS SHALL BE DEMOLISHED AND REMOVED FROM THE SITE AND SHALL BE DISPOSED OF OFF-SITE AT
CONTRACTORS EXPENSE TO AN APPROVED LANDFILL, UNLESS OTHERWISE NOTED.
7. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL, CONTRACTOR SHALL IMMEDIATELY NOTIFY THE CONTRACTING OFFICER
8. DEBRIS SHALL NOT BE BURIED ON SITE. ALL UNSUITABLE MATERIAL AND DEBRIS SHALL BE REMOVED FROM THE SITE AND PROPERLY DISPOSED OFF-SITE IN ACCORDANCE WITH ALL CITY, STATE, COUNTY & FEDERAL LAWS AND ORDINANCES. NO ON-SITE BURNING WILL BE PERMITTED.
9. IF EXISTING UN-CAPPED WATER WELLS ARE DISCOVERED ON-SITE, CONTRACTOR SHALL IMMEDIATELY NOTIFY THE CONTRACTING OFFICER.
10. CONTRACTOR SHALL COORDINATE WITH FOREST SERVICE TO PUMP SEPTIC VAULTS OF ALL WASTEWATER AND SLUDGE. CONTRACTOR SHALL REMOVE EXISTING VAULTS AND ANY ASSOCIATED APPURTENANCES IN ACCORDANCE WITH CITY, COUNTY, STATE, AND FEDERAL LAWS AND ORDINANCES.
11. ANY AREA DISTURBED BY DEMOLITION THAT WILL NOT BE DISTURBED IN PROPOSED GRADING ACTIVITIES SHOWN ON THESE PLANS SHALL HAVE TOPSOIL PLACED, SEEDED AND
MULCHED ACCORDING TO THE CONTRACT SPECIFICATIONS.
12. OWNER HAS FIRST RIGHT OF REFUSAL OF ALL MATERIALS REMOVED FROM THE SITE.
DUMPSTER
DUMPSTER
DUMPSTER
D U
M
PSTER
W
S
O W
S
O
W
S
O W
S
O
8"
M
"16
6"
"16
6"
6"
6"
6"
8"
W
M
6" 9"
6"
9"
6" 6"
9"
6"
" 15
6"
9"
6"
6"
6"
9"
9"
6"
9"
9"
9"
9"
9"
" 12 "6"
9"
9"
" 12
9"
6"
9"
9"
9"
9"
9"
6"
6"
9"
9"
9"
9"
6"
9"
6"
6"
6"
6"
9"
9"
6"
6"
"9"
9"
9"
"12
6"
6"
9"
9"
9"
"15
9"
6"
9"
9"
9"
9"
6"
6"
9"
9"
9"
9"
9"
6"
9"
9"
9"
6"
" 18
9"
9"
9"
9"
" 18
9"
6"
"12
9"
6"
9"
9"
9"
9"
6"
9"
9"
9"
9"9"
9"
9" 9"
9"12
6"
9"
9" 18
9"
6"
9"
D
.4
F.
F.
E.
E E
SD
SD
SD
.5
F.
F.
E.
T
T
W
W
W
W
W
W
W
W
W
P-UGP-UGP-UG
P-UG
P-UG
P-UG
P-UG
P-UGP-UGP-UGP-UG
P- U
G
CP
-1
CP
-2
W
S
O W
S
O
W
S
O W
S
O
8"
4"
"20
" 12
"16
" 14
8"
M
8"
" 12
6"
8"
8"
6"
8"
8"
6"
8"
" 8"
" 6"
6"
6" 6"
6"
6"
8"
8"
6"
.28 F.
F.E
W
M
9"
6"
9"
6"
6"
9"
6"
6"
9"
9"
9"
9"
9"
6" 9"
6"
6"
6"
9"
6"
6"
" 24
" 21
6"
6"
9"
9"
9"
6"
6"
9"
9"
9"
6"
6"
9"
6"
9"
9"
6"
9"
6"
9"
9"
6"
9"
9"
9"
9"
6"
6"
9"
9"
6"
6"
9"
9"
9"
9"
9"
6"
9"
6"
9"
9"
9"
9"
9"
9"
9"
6"
6"
9"
6"
"15
6"
9"
6"
6"
6"
9"
6"
6"
9" 9"
9"
9"
9"
6"
9"
6"
6"
9"
9"
9"
6"
6"
9"
9"
9"
9"
9"
9"
"15
9"
9"
9"
9"
9"
9"
9"
9"
6"
.2
F.
F.
E.
D
.4
F.
F.
E.
E E
SD
SD
W
W
W W
S
O W
S
O
W
S
O W
S
O
M
W
M
D
E E
SD
SD
T
W
W
W
P-UG
P-UG
P-UG
P-UG
P-UG
P-UG
P-UG
P-UGP-UGP-UGP-UG
P- U
G
P-U G
P-UG
P-UG
P-
UG
P- U
G
P-
UG
P- U
G
P-
UG
P-UG
P-UG
T
" 15
NEW TRANSFORMER
PANEL L1
SEE DETAIL F ON SHEET E5.2
FOR MORE INFORMATION
PANEL L-2
SEE SEE DETAIL F ON SHEET
E5.2 FOR MORE INFORMATION
HOST/VOLUNTEER SITE # 1
HANDHOLE FOR FUTURE PEDESTAL
SEE DETAIL G ON SHEET E5.2
FOR MORE INFORMATION
HOST/VOLUNTEER SITE # 2
HANDHOLE FOR FUTURE PEDESTAL
SEE DETAIL G ON SHEET E5.2
FOR MORE INFORMATION PROPOSED
UNDERGROUND
M.V. FEED
FEEDERS TO PEDESTALS
REUSE EXISTING CABLE FOR FLOATS
AND FEEDERS FOR NEW PUMP HOUSE
P- U
G P-
UG
P-UGP-UG
P- U
G
FEEDER TO
FUTURE PEDESTALS
PANEL L3
SEE DETAIL H ON SHEET E5.2
FOR MORE INFORMATION
EXTEND EXISTING PUMP
HOUSE FEEDER TO NEW PUMP
HOUSE
PUMP HOUSE TO BE EQUIPPED WITH
RECEPTACLES, PUMP CONTROL PANEL,
LIGHTING AND HEATER. SEE PUMP
BUILDING ELECTRICAL PLAN ON SHEET
E5.1 FOR MORE INFORMATION.
EXISTING TRANSFORMER AND METER
UTILITY TO CONFIRM
EXISTING M.V. CABLE IS
SUFFICIENTLY SIZED FOR
NEW TRANSFORMER
#25
#26
#27 #28
#24
#31 #30
#29
#32
#33
#23
#21
#22
#44
#20
#19
#18
#17
#16
#15
#14
#13
#12
#10
#9
#8
#7
#6
#5
#4
#3
#39
#41
#40
#42
#43
#35
#3
HO
ST
/V
OL
UN
TE
ER
S
IT
E
#3
HO
ST
/V
OL
UN
TE
ER
S
IT
E
#3
HO
ST
/V
OL
UN
TE
ER
S
IT
E #3
HO
ST
/V O
LU
NT
EE
R
SI
TE
#1 H
O
ST
/V O
LU
N
TE
ER
S
IT
E
#2 H
O
ST
/V O
LU
N
TE
ER
S
IT
E
HOST/VOLUNTEER SITE #34 PEDESTAL
SEE DETAIL E ON SHEET E5.2
FOR MORE INFORMATION
HOST/VOLUNTEER SITE #36 PEDESTAL
SEE DETAIL E ON SHEET E5.2
FOR MORE INFORMATION
HOST/VOLUNTEER SITE #37 PEDESTAL
SEE DETAIL E ON SHEET E5.2
FOR MORE INFORMATION
EXISTING UG FEEDER
ABANDON IN PLACE
HOST/VOLUNTEER SITE #38 PEDESTAL
SEE DETAIL E ON SHEET E5.2 FOR
MORE INFORMATION
NEW TRANSFORMER
T-2
DATENO. REVISION / ISSUE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL SITE PLAN
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E1.1
45 52SCALE IN FEET
40' 80'20'0'
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
GENERAL NOTES:
1. CONTRACTOR SHALL BORE UNDER ALL GRAVEL ROADS.
2. CONTRACTOR SHALL LOCATE AND PROTECT ALL EXISTING UTILITIES DURING TRENCHING/BORING
ACTIVITIES.
3. ANY EXISTING ABANDONED DIRECT BURY CONDUCTORS SHALL BE REMOVED IF LOCATED IN SAME LOCATION
AS NEW CONDUIT PATH. REMOVE AND DISPOSE OFF-SITE.
4. CONTRACTOR SHALL INSTALL NEW UG SERVICE CABLE PARALLEL TO EXISTING UG SERVICE CABLE.
CONTRACTOR TO LOCATE AND CONFIRM LOCATION OF EXISTING UG SERVICE CABLE TO AVOID CONFLICT
WITH NEW UG SERVICE CABLE.
5. CONTRACTOR TO COORDINATE ELECTRIC SERVICE REQUIREMENTS AND ROUTING TO TRANSFORMER WITH
UTILITY.
NEW
T-2
SECONDARY:120/240
(BY UTILITY)
PANEL L-2
200 AMP-120/240 1P
20-CIR 3R
22K AIC SERVICE RATED
PANEL BOARD
N G
200A
GROUND ROD
50A-2P
GROUND ROD
50A-2P
NEW
HOST/VOLUNTEER
SITE #1
N G
NEW
100A
RV
PEDESTAL
N G
NEW
100A
RV
PEDESTAL
GROUND ROD GROUND ROD
NEW
T-1
SECONDARY:120/240
(BY UTILITY)
N G
GROUND ROD
GROUND ROD
HOST/VOLUNTEER SITE #38
STORAGE
TANK
ALARM
50/2P
30/1P
20/1P
20/1P
50/2P
30/1P
20/1P
20/1P
N G
NEW
100A
RV
PEDESTAL
GROUND ROD
50/2P
30/1P
20/1P
20/1P
STORAGE
TANK
ALARM
STORAGE
TANK
ALARM
EXISTING
PRIMARY FEEDER
NEW
PRIMARY FEEDER
(BY UTILITY)
NEW
HOST/VOLUNTEER
SITE #2
HOST/VOLUNTEER SITE #37 HOST/VOLUNTEER SITE #36
EXISTING
HOST/VOLUNTEER
SITE METER
M-1
50A-2P
50A-2P
100A-2P
200A
PANEL L-1
200 AMP-120/240 1P
20-CIR 3R
22K AIC SERVICE RATED
PANEL BOARD
STORAGE TANK
FLOAT SWITCHES
JUNCTION BOX
2-#14 FLOAT SWITCH
CABLES IN 1"
(TYP. OF ALL)
HIGH HIGH LEVEL 90%
VISUAL/AUDIBLE ALARM
HIGH LEVEL 80%
VISUAL ALARM
STORAGE TANK
FLOAT SWITCHES
HIGH HIGH LEVEL 90%
VISUAL/AUDIBLE ALARM
HIGH LEVEL 80%
VISUAL ALARM
STORAGE TANK
FLOAT SWITCHES
HIGH HIGH LEVEL 90%
VISUAL/AUDIBLE ALARM
HIGH LEVEL 80%
VISUAL ALARM
X1
X2
X3
X4
X5
N G
NEW
100A
RV
PEDESTAL
GROUND ROD
50/2P
30/1P
20/1P
20/1P
STORAGE
TANK
ALARM
HOST/VOLUNTEER SITE #34
STORAGE TANK
FLOAT SWITCHES
HIGH HIGH LEVEL 90%
VISUAL/AUDIBLE ALARM
HIGH LEVEL 80%
VISUAL ALARM
X6
X7
X8
X9
X10
M-2
HANDHOLE HANDHOLE
N G 40A
PANEL L-3
FOR PUMP HOUSE BUILDING
100 AMP-120/240 1P
20-CIR 3R
10K AIC PANELBOARD
20A-2P
PUMP HOUSE 3000
WATT HEATER
20A-2P
PUMP HOUSE
DUPLEX
PUMP HOUSE
LIGHTING
PUMP HOUSE
SURGE
SUPPRESSION
20A-2P
20A-1P
20A-1P
BUILDING STEEL
METAL PIPEING
LT SWITCH
GROUND
ROD
TO WELL PUMP CONTROL PANEL (SEE DWG. E5.1)
EXISTING
T-3
SECONDARY:120/240
EXISTING
PRIMARY FEEDER
M-2
X11
X12
DATENO. REVISION / ISSUE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL DETAIL
ONE-LINE DIAGRAM
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E5.0 46 52
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
PAD MOUNTED TRANSFORMER BY UTILITY COMPANY.
METER BY UTILITY COMPANY.
SECONDARY CONDUCTORS, DIRECT BURIAL CABLE, COPPER, 3-#4/0 MCM FROM TRANSFORMER TO PANEL L2, MOUNT PANEL L2 ON METER STUB PROVIDED BY UTILITY COMPANY.
DIRECT BURIAL CABLE, ALUMINUM, 3-#1 WITH #1 GROUND.
COPPER, 3-#3/0 WITH #6 GROUND IN 2" CONDUIT.
COPPER, 3-#1 WITH #6 GROUND IN 1-1/2" CONDUIT.
DIRECT BURIAL CABLE, ALUMINUM, 2-4/0 WITH #2/0 GROUND.
RV POWER PEDESTAL, TYP.
8'-0" GROUND ROD WITH #6 COPPER CONDUCTOR CONNECTED BACK TO GROUND LUG OF RV POWER PEDESTAL, WHERE ROCK IS ENCOUNTERED BURY ROD IN A TRENCH THAT IS AT LEAST 30 INCHES DEEP, TYP.
BOND GROUND BUS AND NEUTRAL BUS TO PANEL.
GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD, SIZE IN ACCORDANCE WITH NEC.
SUPPLEMENTAL GROUND ROD, LOCATE AT LEAST 6 FEET FROM GROUND ROD, SIZE IN ACCORDANCE WITH NEC.
DIRECT BURIAL CABLE, COPPER, 2-#12 WITH #12 GROUND TO SEWAGE TANK ALARM.
PURCHASE EXTRA BREAKER FOR SUMP TANK ALARM, ALARM PANEL, ADD CONDUIT AND WIRING TO TANK FLOATS.
REUSE EXISTING HOST/VOLUNTEER SITE IF APPLICABLE.
UPGRADE SERVICE EQUIPMENT TO ACCOMMODATE EXTRA LOADS.
HANDHOLE, TYP.
EXTEND EXISTING FEED FROM EXISTING PUMP HOUSE TO NEW PUMP HOUSE. SEE DRAWING E1.1 FOR LOCATION.
KEYED NOTES:
1. PROVIDE FULL AMPACITY SERVICE RATED BREAKERS FOR CIRCUIT BREAKERS PROTECTING RV POWER
PEDESTAL.
2. FOR PANEL L1, L2 AND L3 PANEL SCHEDULES SEE SHEET E6.0.
3. FOR PACTOLA SERVICE SHORT CIRCUIT SCHEDULE SEE SHEET E6.1.
GENERAL NOTES:
12 11
131313 13
17 17
NEUTRALGRD.
WELL PUMP "OFF"
WELL PUMP "ON"
PRESSURE SWITCH "PS-1"
JUNCTION BOX ON
STORAGE TANK RISER
TERMINAL STRIP NUMBERS
WILL BE INCLUDED WITH
CONTROL PANEL
CHEMICAL METERING PUMP
RECEPTACLE (SINGLE,
SWITCHED)
NOTE: CONTRACTOR RESPONSIBLE FOR ALL WIRING
SHOWN.
SUPPLY PUMP
MOTOR CONTROL
BOX
WELL PUMP MOTOR
CONTROL BOX JUNCTION BOX AT
WELL HEAD
SUPPLY PUMP
POWER FROM LOAD CENTER 230/115 VAC 3-WIRE
W/GRD.
40 AMP. DISCONNECT
SWITCH
WELL PUMP CONTROL
PANEL
TEI CONTROLS OR EQUAL
GROUND
FROM PANEL L3
9,11
1,3
PANEL L3
5,7
4GFI
GFI
GFI
SPD
A
DATENO. REVISION / ISSUE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL
DETAIL
PUMP HOUSE
ELECTRICAL LAYOUT
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E5.1 47 52
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
PACTOLA WELL PUMP CONTROL WIRING DETAIL
WELL PUMP CONTROL PANEL,
ROUTE 2-#10 WITH #10 GROUND IN 3/4"
CONDUIT TO ELECTRICAL PANEL, ROUTE
12-#12 CONTROL CONDUCTORS IN 1"
CONDUIT TO FLOATS
CHLORINE PUMP RECEPTACLE, CONNECT
TO CONTROL PANEL
MOUNT EXISTING PUMP MOTOR MINDER
ADJACENT TO WELL PUMP CONTROL PANEL,
CONNECT 2-#12 WITH #12 GROUND IN 1/2"
CONDUIT TO CONTROL PANEL
ELECTRICAL PANEL L3, RECONNECT
EXISTING SERVICE CONDUCTORS TO PANEL
(NOT ALL SYMBOLS SHOWN IN LEGEND ARE USED ON PROJECT)
# INDICATES PANEL AND CIRCUIT BREAKER
CIRCUIT, MINIMUM SIZE #12 AWG,
120 VOLT DUPLEX RECEPTACLE
1-WAY SWITCH
LEGEND
LETTER INDICATES FIXTURE
CEILING MOUNTED FIXTURE
VOLTS
LAMPS/MODELTYPE MANUFACTURER
LUMINAIRE SCHEDULE
LUMENS NOMINAL SIZE REMARKS
MODULES
PLAN
CODE W X D X L
LED
COLOR
TEMP
WATTS
A 120 UL LISTED FOR DAMP LOCATIONS
1WALL PACK 13 X 7.5 X 9TWR1 LED 1 40K MVOLT PE 1202161
MOUNT SURGE PROTECTION DEVICE BELOW
PANEL, ROUTE 3-#10 IN 3/4" CONDUIT TO
CIRCUIT BREAKER
ROUTE 2-#10 WITH #10 GROUND IN 1"
CONDUIT TO WELL PUMP CONTROL PANEL
AND WELL PUMP
INSTALL METER CAN, COORDINATE METER
INSTALLATION WITH UTILITY COMPANY
UNIT HEATER, MOUNT
7 FEET ABOVE FINISHED
FLOOR, ROUTE 2-#12 AND
#12 GROUND IN 1/2" CONDUIT
4000K 33 PROVIDE WITH PHOTOCELL
32W T8LITHONIAROUGH SERVICE 9 X 3 X 49VSL 2 32 MVOLT GEB10IS DL -- 64
B LITHONIA
CEILING MOUNTED FIXTURE
LETTER INDICATES FIXTURE
DUPLEX, GROUND FAULT CIRCUIT RECEPTACLE
ELECTRICAL PANEL OR
TRANSIENT VOLTAGE SURGE SUPPRESSOR
WALL MOUNTED FIXTURE
LETTER INDICATES FIXTURE
JUNCTION BOX
A
E5.1
PUMP BUILDING ELECTRICAL LAYOUT
NOT TO SCALE
1. COORDINATE ELECTRICAL INSTALLATION AND ROUTING WITH EQUIPMENT AND PIPING IN PUMP BUILDING.
2. ROUTE POWER THROUGH OPENINGS IN CONCRETE FLOOR WITH 1" HDPE PIPE, FILL FLOOR OPENING ANNULAR SPACE WITH HIGH DENSITY POLYURETHANE FOAM AFTER INSTALLING CONDUIT. SEE M5.1 FOR FLOOR
OPENINGS.
3. SURFACE MOUNT CONDUITS IN PUMP BUILDING.
GENERAL NOTES:
GFI
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL DETAILS
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRCUTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E5.2 48 52
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
HEX HEAD BOLT WITH WASHER
BASE
COVER
4" X 4" MOUSEHOLES
1" DEEP (MIN.)
GRAVEL BASE
LOGO
1/2" X 4" PULL SLOT
3/8" STAINLESS STEEL
SKID RESISTANT
SURFACE
NOTES:
1. PROVIDE STANDARD HANDHOLE. COVER COLOR
SHALL BE AS SPECIFIED BY THE U.S. FOREST SERVICE.
2. COVER, RING AND BOX SHALL BE MADE OF SAME
MATERIAL.
HAND HOLE DETAILG
E5.2 NOT TO SCALE
FINISHED GRADE
MIN.
6"
OR
30" 9
MIN.
COPPER GROUND WIRE
CONNECT TO GROUND ROD.
(SIZE PER PLAN)
BILL OF MATERIAL
ITEM
GROUND WIRE, STRANDED DIRECT-BURRIED COPPER
FOR EACH ADDITIONAL CABLE CONNECTION ADD 1 CONNECTOR.
CONNECTOR, #8 SOLID THRU #4 STR. CABLE TO GND. ROD, BURNDY #GAR-644C
CONNECTOR, #2/0 SOLID THRU 250KCMIL STR. CABLE TO GND. ROD, BURNDY #GAR-6429
CONNECTOR, #4 SOLID THRU #2/0 STR. CABLE TO GND. ROD, BURNDY #GAR-6426
GROUND ROD, 3/4" DIA. x 10' LONG, COPPER CLAD STEEL
6"
MIN.
LEAVE RAKE FINISH FOR
EXPOSED EARTH AREAS.
2' -0
BACKFILL SHALL BE WITH CLEAN, DEBRIS
FREE EARTH (ABSOLUTELY NO ROCKS)
COMPACTED TO 90% OF UNDISTURBED
EARTH IN MAXIMUM 6" LIFTS.
SCHEDULE 40 PVC CONDUIT
PROVIDE UNDERGROUND
WARNING TAPE WITH TRACER TAPE
M
IN
EXPANSION COUPLING
2' -0
" M
IN
PVC CONDUIT
(SCHEDULE 40)
GRADE LINE
GALVANIZED RIGID
STEEL CONDUIT
GALVANIZED RIGID
STEEL CONDUIT ABOVE
GRADE
ELECTRICAL DEVICE/
PANEL/DISCONNECT
M
IN
1'
-0
A A
SECTION A-A
10" 15" 12"
A B C
APPROXIMATE DIMENSIONS
4"MIN.
A
C
B
" M
IN
. G
R
AV
EL
O
R C
R U
SH
ED
R O
C K
6" M
IN
NOTES
9. PULL BOX COVERS SHALL BE OF HEAVY-DUTY
CONSTRUCTION TO WITHSTAND THE STRUCTURAL
REQUIREMENTS OF THE SPECIFICATIONS. COVERS SHALL
FIT SUFFICIENTLY TIGHT TO PREVENT THE ENTRANCE OF
RUN-OFF WATER. COVERS SHALL BE EMBOSSED WITH AN
ANTI-SLIP SURFACE, THE MANUFACTURER'S NAME AND THE
LOGO "ELECTRIC". COVERS SHALL BE HELD SECURELY IN
PLACE BY TWO OR MORE 3/8" (MIN. DIA.) STAINLESS STEEL
HEX HEAD BOLTS WITH FLAT WASHER. BOLTS SHALL BE
HELD CAPTIVE TO THE COVER. ALL COVERS SHALL BE
EQUIPPED WITH A RECESSED "LIFT PIN" AND HAVE A
MINIMUM 0.50 COEFFICIENT OF FRICTION SKID RESISTANT
SURFACE.
10.EACH PULL BOX ASSEMBLY (BOX WITH HEAVY-DUTY COVER
SECURELY ATTACHED) SHALL CONFORM TO ALL TEST
PROVISIONS AND REQUIREMENTS FOR TIER 15
APPLICATIONS AS OUTLINED IN THE LATEST ISSUE OF THE
ANSI/SCTE 77 2002 STANDARD TITLED "SPECIFICATION FOR
UNDER GROUND ENCLOSURE INTEGRITY". INDEPENDENT
THIRD-PARTY TEST REPORTS TOGETHER WITH
CERTIFICATION THAT ALL TEST PROVISIONS OF THE
ANSI/SCTE 77 2002 STANDARD HAVE BEEN MET WILL BE
REQUIRED FOR EACH TYPE OF PULL BOX BEING FURNISHED.
ALL TESTS SHALL BE DATED AND SIGNED BY A REGISTERED
PROFESSIONAL ENGINEER AND SHALL BEAR THE
LETTERHEAD OF THE TESTING AGENCY.
1. ACCESS DUCTS, BENDS AND/OR SWEEPS, ARE SUBSIDIARY
TO THE ITEM "PULL BOX, TYPE PB".
2. FILL MATERIAL SHALL BE GRAVEL OR CRUSHED ROCK
COMPOSED OF CLEAN, HARD, DURABLE AND UNCOATED
3. PROLONGED EXPOSURE OF THE PULL BOX AND COVER TO
SUNLIGHT, COMMON ICE MELTING CHEMICALS OR
FERTILIZERS SHALL NOT CAUSE SIGNIFICANT DAMAGE TO
THE PULL BOX OR COVER, OR IMPAIR ITS FUNCTION.
4. CONDUIT TERMINATIONS IN PULL BOX SHALL BE FITTED WITH
BELL OR FLARED END.
5. CONCRETE SHALL BE CLASS 47B-3000.
6. PULL BOXES ARE IN GROUND, GRADE LEVEL ENCLOSURES
INTENDED TO BE INSTALLED WHERE NON-DELIBERATE
VEHICULAR TRAFFIC IS ANTICIPATED.
7. PULL BOX ILLUSTRATIONS ARE TYPICAL AND ARE NOT
INTENDED TO LIMIT DESIGN. BOXES OF SQUARE OR
CIRCULAR PLAN-SECTION AND OF EQUAL OR GREATER
VOLUME ARE ACCEPTABLE. A MINIMUM DEPTH OF 18 INCHES,
MUST BE MAINTAINED.
8. THE PULL BOX ENCLOSURES (BOX AND COVER) SHALL BE
NON-METALLIC AND GREEN OR GRAY IN COLOR.
GROUND ROD INSTALLATIONA
E5.2 NOT TO SCALE
GRADE PULL BOX DETAILB
E5.2 NOT TO SCALE
TRENCH DETAILC
E5.2 NOT TO SCALE
EXPOSED CONDUIT DETAILD
E5.2 NOT TO SCALE
2' -4
GRADE PULL BOX DETAILE
E5.2 NOT TO SCALE
EQUIPMENT RACK MOUNT DETAILF
E5.2 NOT TO SCALE
PEDESTAL, MOUNT TOP
NO HIGHER THAN 6'-0" AFG
2" DIA GALVANIZED STEEL
PIPE WITH END CAP
ROUTE FEEDER CIRCUITS IN RGS
CONDUIT, TERMINATE CONDUIT WITH
ELBOW 24" BELOW GRADE
METER AND METER
SOCKET
TO MAIN SERVICE
GRADE
12"Ø - 3'-0" MEN DEEP
CONCRETE PIER, TYP.
12"
3' -0
" M
IN
U-BOLTS, TYPICAL
1-1/2"x1-1/2" STRUT, TYPICAL.
AS REQUIRED FOR EQUIPMENT AND
CONDUIT SUPPORT.
MOUNTING RACK AND PIPE SHALL
BE PAINTED WITH TWO COATS OF
RUST INHIBITING ENAMEL.
COLOR SHALL BE FOREST SERVICE
BROWN.
ELECTRICAL EQUIPMENT
(PANEL, DISCONNECT, UTILITY METER)
2" DIA. GALVANIZED STEEL
PIPE WITH END CAP.
SIZE OF RACK TO BE AS
REQUIRED FOR EQUIPMENT SIZE.
PIPE STRAP, SIZE AS
REQUIRED, TYPICAL.
CONDUITS
CONCRETE, TYPICAL.
MIN 3" FROM EDGE OF STEEL PIPE
TO EDGE OF PANEL (TYP)
SEE DETAIL F ON SHEET
S2.0 FOR RACK AND
CONCRETE DETAILS
ELECTRICAL EQUIPMENT
TO BE PAINTED FOREST
SERVICE BROWN.
SEE DETAIL F ON SHEET S2.0 FOR
RACK AND CONCRETE DETAILS
EQUIPMENT BUILDING MOUNTH
E5.2 NOT TO SCALE
WALL OF PRE-FAB
CONCRETE BUILDING
SECURE CABINET TO WALL USING (6) .25” DIA. X
1.875” KH-EZ SCREW ANCHORS (1 SCREW AT
EACH CORNER OF CABINET, AND (1) AT
MID-HEIGHT ON EACH SIDE )
5' -0
GRADE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL SCHEDULES
PANEL SCHEDULES
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E6.0 49 52
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
PANEL SCHEDULES
FED
FROM: UTILITY PANEL SCHEDULE L1 PANEL LOCATION:
MOUNTING METHOD: SURFACE VOLTS: 240/120 BUS RATING: 200
ENCLOSURE: NEMA 3R PHASE: 1 MAIN BREAKER: 200
FEED FROM: BOTTOM WIRE: 3 AIC RATING: 22,000
C od e LOAD Brkr PHASE Brkr LOAD
C od e
# DESCRIPTION VA Size A B Size VA DESCRIPTION #
1 6 HOST/VOLUNTEER SITE #38 6000
50/2
12000 50/2
6000 HOST/VOLUNTEER SITE #37 6 2
3 6 HOST/VOLUNTEER SITE #38 6000 12000 6000 HOST/VOLUNTEER SITE #37 6 4
5 6 HOST/VOLUNTEER SITES #36 & 34 12000
100/2
12000 6
7 6 HOST/VOLUNTEER SITES #36 & 34 12000 12000 8
9 0 10
11 0 12
13 0 14
15 0 16
17 ` 0 18
19 0 20
CODE DESCRIPTION Load VA DEM TOTAL
1 LIGHTING 0 1.25 0 TOTAL PHASE A: 24,000 VA
2 REC. TO 10,000 VA 0 1 0 TOTAL PHASE B: 24,000 VA
2.1 REC. OVER 10,000 VA 0 0.5 0
3 MOTOR 0 1 0
3.1 LARGEST MOTOR 0 1.25 0 1 f CONNECTED: 48,000 VA
4 HEATER 0 1.25 0 1 f CODE DEMAND: 36,000 VA
5 KITCHEN 0 1 0 Per f Code Demand: 150.0 AMPS
6 MISCELLANEOUS 48,000 0.75 36,000
7 SUB PANEL 0 1 0
FED
FROM: UTILITY PANEL SCHEDULE L2 PANEL LOCATION: TBD
MOUNTING METHOD: SURFACE VOLTS: 240/120 BUS RATING: 200 Amp
ENCLOSURE: NEMA 3R PHASE: 1 MAIN BREAKER: 200
FEED FROM: BOTTOM WIRE: 3 AIC RATING: 22,000
C od e LOAD Brkr PHASE Brkr LOAD
C od e
# DESCRIPTION VA Size A B Size VA DESCRIPTION #
1 6 HOST/VOLUNTEER SITE #1 6000
50/2
12000 50/2
6000 HOST/VOLUNTEER SITE #2 6 2
3 6 HOST/VOLUNTEER SITE #1 6000 12000 6000 HOST/VOLUNTEER SITE #2 6 4
5 0 6
7 0 8
9 0 10
11 0 12
13 0 14
15 0 16
17 0 18
19 0 20
CODE DESCRIPTION Load VA DEM TOTAL
1 LIGHTING 0 1.25 0 TOTAL PHASE A: 12,000 VA
2 REC. TO 10,000 VA 0 1 0 TOTAL PHASE B: 12,000 VA
2.1 REC. OVER 10,000 VA 0 0.5 0
3 MOTOR 0 1 0
3.1 LARGEST MOTOR 0 1.25 0 1 f CONNECTED: 24,000 VA
4 HEATER 0 1.25 0 1 f CODE DEMAND: 19,200 VA
5 KITCHEN 0 1 0 Per f Code Demand: 80.0 AMPS
6 MISCELLANEOUS 24,000 0.8 19,200
7 SUB PANEL 0 1 0
FED
FROM: UTILITY PANEL SCHEDULE L3 PANEL LOCATION: PUMP BUILDING
MOUNTING METHOD: SURFACE VOLTS: 240/120 BUS RATING: 100 Amp
ENCLOSURE: NEMA 3R PHASE: 1 MAIN BREAKER: 40
FEED FROM: BOTTOM WIRE: 3 AIC RATING: 10,000
C od e LOAD Brkr PHASE Brkr LOAD
C od e
# DESCRIPTION VA Size A B Size VA DESCRIPTION #
1 6 WELL PUMP CONTROL PANEL 600
20/2
960 20/1 360 RECEPTACLES 2 2
3 6 WELL PUMP CONTROL PANEL 600 697 20/2 97 LIGHTING 1 4
5 6 SURGE PROTECTION 0
20/2
0 6
7 6 SURGE PROTECTION 0 0 8
9 4 ELECTRIC HEAT 1500
20/2
1500 10
11 4 ELECTRIC HEAT 1500 1500 12
13 0 14
15 0 16
17 0 18
19 0 20
CODE DESCRIPTION Load VA DEM TOTAL
1 LIGHTING 97 1.25 121 TOTAL PHASE A: 2,460 VA
2 REC. TO 10,000 VA 360 1 360 TOTAL PHASE B: 2,197 VA
2.1 REC. OVER 10,000 VA 0 0.5 0
3 MOTOR 0 1 0
3.1 LARGEST MOTOR 0 1.25 0 1 f CONNECTED: 4,657 VA
4 HEATER 3,000 1.25 3,750 1 f CODE DEMAND: 5,431 VA
5 KITCHEN 0 1 0 Per f Code Demand: 22.6 AMPS
6 MISCELLANEOUS 1,200 1 1,200
7 SUB PANEL 0 1 0
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL SCHEDULES
SHORT CIRCUIT
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E6.1 50 52
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
1. FOR SHORT CIRCUIT POINT LOCATIONS SEE SHEET E5.0 FOR ONE-LINE DIAGRAM.
GENERAL NOTES:PACTOLA LOOP B SERVICE TO PANEL L-1 AND SITES #34, 36, 36, AND 38
SHORT CIRCUIT SCHEDULE
POINT DESCRIPTION WIRE SIZE
LENGTH OF RUN
(FT)
RATED SHORT
CIRCUIT BRACING
SHORT CIRCUIT
(Isc SYM RMS)
LINE-LINE
VOLTAGE
T1 UTILITY TRANSFORMER 50KVA 1.4% Z 14,800 240
X1 T-1 TO UTILITY METER M-1 250 MCM-ALU 30 12,451 240
X2 UTILITY METER TO PANEL L-1 250 MCM-ALU 6 22,000 12,008 240
X3 PANEL L-1 TO SITE #38 PEDESTAL #1 AWG-ALU 120 10,000 3,486 240
X4 PANEL L-1 TO SITE #37 PEDESTAL #1 AWG-ALU 200 10,000 2,277 240
X5 PANEL L-1 TO SITE #36 PEDESTAL #4/0 AWG-ALU 260 10,000 3,634 240
X6 SITE #36 PEDESTAL TO SITE #34 PEDESTAL #1 AWG-ALU 120 10,000 2,006 240
PACTOLA LOOP B SERVICE TO PANEL L-2 AND FUTURE SITES #1 AND 2
SHORT CIRCUIT SCHEDULE
POINT DESCRIPTION WIRE SIZE
LENGTH OF RUN
(FT)
RATED SHORT
CIRCUIT BRACING
SHORT CIRCUIT
(Isc SYM RMS)
LINE-LINE
VOLTAGE
T2 UTILITY TRANSFORMER 50KVA 1.4% Z 14,800 240
X7 T-2 TO UTILITY METER M-2 250 MCM-ALU 30 12,451 240
X8 UTILITY METER TO PANEL L-2 250 MCM-ALU 6 22,000 12,008 240
X9 PANEL L-2 TO FUTURE SITE #1 PEDESTAL #1 AWG-ALU 250 10,000 1,868 240
X10 PANEL L-2 TO FUTURE SITE #2 PEDESTAL #1 AWG-ALU 180 10,000 2,494 240
PACTOLA LOOP B SERVICE TO PUMP HOUSE PANEL L-3
SHORT CIRCUIT SCHEDULE
POINT DESCRIPTION WIRE SIZE
LENGTH OF RUN
(FT)
RATED SHORT
CIRCUIT BRACING
SHORT CIRCUIT
(Isc SYM RMS)
LINE-LINE
VOLTAGE
T3 UTILITY TRANSFORMER 25KVA 1.4% Z 7,400 240
X11 T-3 TO UTILITY METER M-3 250 MCM-ALU 20 6,856 240
X12 UTILITY METER TO PANEL L-3 250 MCM-ALU 160 10,000 3,339 240
DUMPSTER
DUMPSTER
D U
M
PSTER
W
S
O W
S
O
W
S
O W
S
O
8"
M
"16
6"
"16
6"
6"
6"
6"
8"
W
M
6" 9"
6"
9"
6" 6"
9"
6"
" 15
6"
9"
6"
6"
6"
9"
9"
6"
9"
9"
9"
9"
9"
" 12 "6"
9"
9"
" 12
9"
6"
9"
9"
9"
9"
9"
6"
6"
9"
9"
9"
9"
6"
9"
6"
6"
6"
6"
9"
9"
6"
6"
"9"
9"
9"
"12
6"
6"
9"
9"
9"
"15
9"
6"
9"
9"
9"
9"
6"
6"
9"
9"
9"
9"
9"
6"
9"
9"
9"
6"
" 18
9"
9"
9"
9"
" 18
9"
6"
"12
9"
6"
9"
9"
9"
9"
6"
9"
9"
9"
9"9"
9"
9" 9"
9"12
6"
9"
9" 18
9"
6"
9"
D
.4
F.
F.
E.
E E
SD
SD
SD
.5
F.
F.
E.
T
T
W
W
W
W
W
W
W
W
W
P-UGP-UGP-UG
P-UG
P-UG
P-UG
P-UG
P-UGP-UGP-UGP-UG
P- U
G
CP
-1
CP
-2
W
S
O W
S
O
W
S
O W
S
O
8"
4"
"20
" 12
"16
" 14
8"
M
8"
" 12
6"
8"
8"
6"
8"
8"
6"
8"
" 8"
" 6"
6"
6" 6"
6"
6"
8"
8"
6"
.28 F.
F.E
W
M
9"
6"
9"
6"
6"
9"
6"
6"
9"
9"
9"
9"
9"
6" 9"
6"
6"
6"
9"
6"
6"
" 24
" 21
6"
6"
9"
9"
9"
6"
6"
9"
9"
9"
6"
6"
9"
6"
9"
9"
6"
9"
6"
9"
9"
6"
9"
9"
9"
9"
6"
6"
9"
9"
6"
6"
9"
9"
9"
9"
9"
6"
9"
6"
9"
9"
9"
9"
9"
9"
9"
6"
6"
9"
6"
"15
6"
9"
6"
6"
6"
9"
6"
6"
9" 9"
9"
9"
9"
6"
9"
6"
6"
9"
9"
9"
6"
6"
9"
9"
9"
9"
9"
9"
"15
9"
9"
9"
9"
9"
9"
9"
9"
6"
.2
F.
F.
E.
D
.4
F.
F.
E.
E E
SD
SD
W
W
W W
S
O W
S
O
W
S
O W
S
O
M
W
M
D
E E
SD
SD
T
W
W
W
P-UG
P-UG
P-UG
P-UG
P-UG
P-UG
P-UG
P-UGP-UGP-UGP-UG
P- U
G
P-U G
P-UG
P-UG
P-
UG
P- U
G
P-
UG
P- U
G
P-
UG
P-UG
P-UG
T
" 15
HOST/VOLUNTEER SITE # 1 PEDESTAL
SEE DETAIL E ON SHEET E5.2
FOR MORE INFORMATION
HOST/VOLUNTEER SITE # 2 PEDESTAL
SEE DETAIL E ON SHEET E5.2
FOR MORE INFORMATION P-
U
G P-
UG
P-UGP-UG
P- U
G
DATENO. REVISION / ISSUE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL SITE PLAN
BID OPTION
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E7.0
51 52SCALE IN FEET
40' 80'20'0'
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
GENERAL NOTES:
PACTOLA ELECTRICAL BID OPTIONS
OPTION # DESCRIPTION
1 ADDITIONAL HOST/VOLUNTEER
SITE IMPROVEMENTS
OPTION 1
OPTIONS LISTED ABOVE SHALL BE COORDINATED WITH ALL OTHER DISCIPLINE
SHEETS. REFERENCE DWG. C7.0, M6.0, AND S6.0.
1. CONTRACTOR SHALL BORE UNDER ALL GRAVEL ROADS.
2. CONTRACTOR SHALL LOCATE AND PROTECT ALL EXISTING UTILITIES DURING TRENCHING/BORING
ACTIVITIES.
3. ANY EXISTING ABANDONED DIRECT BURY CONDUCTORS SHALL BE REMOVED IF LOCATED IN SAME LOCATION
AS NEW CONDUIT PATH. REMOVE AND DISPOSE OFF-SITE.
4. CONTRACTOR SHALL INSTALL NEW UG SERVICE CABLE PARALLEL TO EXISTING UG SERVICE CABLE.
CONTRACTOR TO LOCATE AND CONFIRM LOCATION OF EXISTING UG SERVICE CABLE TO AVOID CONFLICT
WITH NEW UG SERVICE CABLE.
5. CONTRACTOR TO COORDINATE ELECTRIC SERVICE REQUIREMENTS AND ROUTING TO TRANSFORMER WITH
UTILITY.
N G
100A
RV
PEDESTAL
N G
100A
RV
PEDESTAL
GROUND ROD GROUND ROD
NEW
HOST/VOLUNTEER
SITE #1
STORAGE
TANK
ALARM
50/2P
30/1P
20/1P
20/1P
50/2P
30/1P
20/1P
20/1P
STORAGE
TANK
ALARM
NEW
HOST/VOLUNTEER
SITE #2
STORAGE TANK
FLOAT SWITCHES
JUNCTION BOX
2-#14 FLOAT SWITCH
CABLES IN 1"
HIGH HIGH LEVEL 90%
VISUAL/AUDIBLE ALARM
HIGH LEVEL 80%
VISUAL ALARM
STORAGE TANK
FLOAT SWITCHES
HIGH HIGH LEVEL 90%
VISUAL/AUDIBLE ALARM
HIGH LEVEL 80%
VISUAL ALARM
X9
X10
FROM PANEL L3
FROM PANEL L3
DATENO. REVISION / ISSUE
UNITED STATES
DEPARTMENT OF AGRICULTURE
FOREST SERVICE
ELECTRICAL
BID OPTION
ONE-LINE DIAGRAM
R2
ROCKY MOUNTAIN REGION
PACTOLA
CAMPGROUND
LOOP B
RECONSTRUCTION
BLACK HILLS
NATIONAL FOREST
MYSTIC RANGER DISTRICT
DGK
DGK
05.28.2025
E7.1 52 52
550 East St. Louis Street Springfield, MO 65806 Olsson - Engineering South Dakota COA #C-159 olsson.com
TEL 417.890.8802
1343 SOUTH 75TH STREET
OMAHA NE 68124
744 Horizon Court, #135 Grand Junction, CO 81506 Citrine - Engineering South Dakota COA #FL269825 citrinellc.com
TEL 303.325.3460
METER BY UTILITY COMPANY
SECONDARY CONDUCTORS, DIRECT BURIAL CABLE, COPPER, 3-#4/0 MCM FROM TRANSFORMER TO PANEL L2, MOUNT PANEL L2 ON METER STUB PROVIDED BY UTILITY COMPANY
DIRECT BURIAL CABLE, ALUMINUM, 3-#1 WITH #1 GROUND
COPPER, 3-#1 WITH #6 GROUND IN 1-1/2" CONDUIT
RV POWER PEDESTAL, TYP.
8'-0" GROUND ROD WITH #6 COPPER CONDUCTOR CONNECTED BACK TO GROUND LUG OF RV POWER PEDESTAL, WHERE ROCK IS ENCOUNTERED BURY ROD IN A TRENCH THAT IS AT LEAST 30 INCHES DEEP, TYP
BOND GROUND BUS AND NEUTRAL BUS TO PANEL
GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD, SIZE IN ACCORDANCE WITH NEC
SUPPLEMENTAL GROUND ROD, LOCATE AT LEAST 6 FEET FROM GROUND ROD, SIZE IN ACCORDANCE WITH NEC
DIRECT BURIAL CABLE, COPPER, 2-#12 WITH #12 GROUND TO SEWAGE TANK ALARM
PURCHASE EXTRA BREAKER FOR SUMP TANK ALARM, ALARM PANEL, ADD CONDUIT AND WIRING TO TANK FLOATS
KEYED NOTES: XX
1. PROVIDE FULL AMPACITY SERVICE RATED BREAKERS FOR CIRCUIT BREAKERS PROTECTING RV POWER
PEDESTAL.
2. FOR PANEL L1 AND L2 PANEL SCHEDULES SEE SHEET E6.0.
3. FOR PACTOLA SERVICE SHORT CIRCUIT SCHEDULE SEE SHEET E6.1.
GENERAL NOTES:
5 5
10 10
OPTION 1
| Part 11_PACTOLA CAMPGROUND_M6 & E1 2.pdf |
| Part 11_PACTOLA CAMPGROUND_M6 & E1 3.pdf |
| Part 11_PACTOLA CAMPGROUND_M6 & E1 4.pdf |
| Part 12_PACTOLA CAMPGROUND_E5.pdf |
| Part 13 _PACTOLA CAMPGROUND_E6 & E7.pdf |
File details come from the government source that posted it. Updated .