Att 10-Dental Final Support Doc 2 of 8.pdf

PDF 16 MB Posted

Attached to
Y1DA--Project 612-164 - Dental Expansion and Relocation Northern California VAMC Located on Travis AFB, California
Solicitation number
36C77624R0085
Issued by

About this file

This document appears to be Attachment 10, which is part of the supporting documentation for Solicitation No. 36C77624R0085 issued by the Department of Veterans Affairs Technology Acquisition Center Austin.

The solicitation is for the Dental Expansion and Relocation Northern California VAMC Located on Travis AFB, California. The key details are:

  • The scope of work involves dental expansion and relocation at the Northern California VAMC on Travis AFB.
  • The solicitation is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin, a civilian federal agency.
  • The solicitation number is 36C77624R0085.
  • The work is identified as Project 612-164.
  • No specific response or award dates are provided in this attachment.

View the file

Other files

File Type Posted
Dental Expansion and Relocation RFI-Questions 9.27.2024.pdf PDF
36C77624R0085 0005.docx DOCX document
3 Dental Final Spec 2 of 3.pdf PDF
4 Dental Final Spec 3 of 3.pdf PDF
5 Prelim Contractor Construct Fence Area.pdf PDF
RevJA_Brand Name_All Redacted.pdf PDF
2 Dental Final Spec 1 of 3.pdf PDF
6 Prelim Contractor Laydown Area.pdf PDF
1 Dental Expansion and Relocation_Responses to Questions.pdf PDF
36C77624R0085 Amd 04.docx DOCX document
36C77624R0085 Amd 03.docx DOCX document
S04 - Site Visit Agenda.doc DOC document
Dental Pre-Bid Site Walk Attendence 20240829.pdf PDF
Amd 02 Dental Expansion and Relocation RFI-Questions.pdf PDF
36C77624R0085 Amd 02.docx DOCX document
36C77624R0085 Amd 01.docx DOCX document
Amd 01 Dental Expansion and Relocation-Questions.xlsx XLSX spreadsheet
Att 15-Dental Final Support Doc 7 of 8.pdf PDF
Att 02 - Dental Final Drawing 2 of 6.pdf PDF
Att 09-Dental Final Support Doc 1 of 8.pdf PDF
Att 04 - Dental Final Drawing 4 of 6.pdf PDF
Att 05 - Dental Final Drawing 5 of 6.pdf PDF
Att 16-Dental Final Support Doc 8 of 8.pdf PDF
Att 01 - Dental Final Drawing 1 of 6.pdf PDF
Att 19-Limitations on Subcontracting.docx DOCX document
Att 21-Division Cost Breakdown.xlsx XLSX spreadsheet
Att 03 - Dental Final Drawing 3 of 6.pdf PDF
Att 08 - Dental Final Spec 2 of 2.pdf PDF
Att 06 - Dental Final Drawing 6 of 6.pdf PDF
Att 07 - Dental Final Spec 1 of 2.pdf PDF
36C77624R0085_1 FINAL.docx DOCX document
Att 17b-DBIDS Enrollment QR.pdf PDF
Att 14-Dental Final Support Doc 6 of 8.pdf PDF
Att 18-DBA WD CA20240007 0726.pdf PDF
Att 17c-DVES - Slide Deck.pptx PPTX presentation
Att 13-Dental Final Support Doc 5 of 8.pdf PDF
Att 20-PPQ form.docx DOCX document
Att 17a-Site Visit Information.docx DOCX document
Att 11-Dental Final Support Doc 3 of 8.pdf PDF
Att 12-Dental Final Support Doc 4 of 8.pdf PDF
Att 22-JA_Brand Name_redacted.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

General Specifications:

The Alarm Valve Combo Unit shall be an Amico Alert-1 Series.

Each AVC shall consist of the following components: an 18 Gauge steel valve box complete with a baked white enamel finish which can house one to six shut-off ball valves with tube extensions, gas-specific sensor (DISS nut and nipple connection), a hinged gas-specific compact alarm with illuminated LED digital display and an error message for an incorrect connection, an aluminum frame and a pull-out removable window.

Affixed to the opposing sides of the box will be two adjustable steel brackets for the purpose of mounting the box to the structural support. The steel brackets shall accommodate various finished wall thicknesses between 3/8" [9.5 mm] and 1-3/16" [30 mm] and shall be field adjustable. The frame assembly shall be constructed of anodized aluminum and shall be mounted to the back box assembly by standard number #6 x 3/8" tapping screws as provided.

The digital alarm shall read from 0-250 psi [0-1,724 kPa] for pressure and 0-30" Hg [-100-0 HgkPa] for vacuum. The digital read-out shall provide a constant indication of each service being measured. It will indicate a green ”NORMAL” and a red ”HIGH” or ”LOW” alarm condition. If an alarm occurs, the ”RED” alarm light shall flash and the audible alarm (which exceeds 90 decibels) will sound. Pushing the ”ALARM MUTE” button will cancel the audible alarm but the unit will remain in the alarm condition until the problem is rectified. A repeat alarm function shall, when enabled on the compact alarm module, be capable of turning on the buzzer again (after a preset time) if the fault condition has not been rectified.

Each alarm module shall be individually microprocessor based and be field adjustable. The default set point on this alarm shall be +/- 20% variation from normal condition. In the calibration mode the following parameters shall be adjustable: high/low set-points, imperial/metric units, repeat alarm enable/ disable (adjustable from 1 to 60 minutes) as well as psi, kPa or Bar readout (switch selected). Set points shall be adjustable by two on-board push buttons.

Access to the shut-off valves shall be by merely pulling the ring assembly to remove the window from the frame. The window can be reinstalled without the use of tools only after the valve handles have been returned to the open position. The window shall be marked to prohibit unauthorized persons from tampering with the valves with the following silk-screen caution:

”Medical Gas Control Valves with Alarms” ”Close Valves Only in Emergency”

The valve shall be a 3 piece ball-type design with a brass forging body and a chrome-plated brass ball for sizes 1/2" to 2" [1.3 cm to 5.1 cm]. Seats shall be reinforced Teflon (PTFE) and seals Viton for 1/2" to 2" [1.3 cm to 5.1 cm]. A blowout proof stem shall be used and the valve shall have a maximum pressure rating of 600 psi [4,137 kPa].

Valves shall be operated by a lever-type handle requiring only a quarter turn from a fully open position to a fully closed position. All valves shall be equipped with a type ”K” washed and degreased copper pipe stub. Each valve will be identified for gas specification as indicated on the hinged alarm label.

Input power to the Amico Alarm Valve Combo Unit is: 115 VAC to 220 VAC, 50 to 60 Hz.

Amico products comply with NFPA 99 and CSA Z7396.1.

The Amico Alert-1 Alarm complies with the following electromagnetic compatibilty standards: FCC Part 15 Class A and ICES-003 Class A.

Combo Unit Multiple Alarm Valve

Features

• 2 in 1 design combines the Area Alarm and Zone

• Valve Box to compensate for space restrictions

• True digital, illuminated LED display is readable even in poor lighting conditions

• High/low alarm set-points are field adjustable for each gas service

• Repeat alarm is adjustable from 1 to 60 minutes or off

• Gas-specific sensor with DISS nut and nipple

• Alarm buzzer in excess of 90 decibels

• Each module is marked with an approved medical gas identification label

• Pre-mounted pull-out ring allows for ease of maintenance

• Individual microprocessor for each display and sensor module; digital sensor is mounted locally

• Dry contacts for remote monitoring of the high and low alarm

C US LISTED

Technical Specifications

Inch [mm]

TOP VIEW1/2" - 1-1/2" Valve Drawing

2" Valve Drawing

RIGHT SIDE VIEWFRONT VIEW

34 3/4 [883]

4 3/8 [110]

2 1/4 [57]

34 3/4 [883]

28 1/2 [724]

19 1/2 [495]

10 1/2 [267]

2 1/4 [57]

3 7/8 [98]

2 1/8 [54]

30 1/4 [769]

4 1/2 [114]

4 1/2 [114]

28 1/2 [724]

7 1/8 [181]

4 1/8 [105]

1 3/4 [45]

4 1/2 [114]

[381]

[610]

[838]

[305]

3/8 to 1 3/16 [9.50 to 30]

1/2 [12]

30 1/4 [768]

25 3/4 [654]

21 1/4 [540]

16 3/4 [425]

12 1/4 [311]

13 3/4 [350]

4 1/2 [114]

4 1/2 [114]

1/2 [12]

[305]

[533]

3/8 to 1 3/16 [9.50 to 30]

Amico Corporation 85 Fulton Way, Richmond Hill, ON L4B 2N4, Canada | 71 East Industry Court, Deer Park, NY 11729, USA Toll Free Tel: 1.877.462.6426 | Toll Free Fax: 1.866.440.4986 | Tel: 905.764.0800 | Fax: 905.764.0862 www.amico.com 3

AVL-XGXGXGXGXGXGXG

Model Numbers

NOTE:

The power supply will require 1 gang per box.

Example: English, 3 valves, 1/2" [1.3 cm] oxygen, 3/4" [1.9 cm] medical air and 1-1/4" [3.18 cm] medvac. Will be in a 4 gang box.

AVU-1O2A4V

The 1-1/2" [3.8 cm] valve will have an empty space above the valve.

Example: A box with a 1/2" [1.3 cm] oxygen, 3/4" [1.9 cm] medical air and a 1-1/2" [3.8 cm] medvac valves will require a 5 hole box not a 3 hole box.

The 2" [5.1 cm] valve will be assembled in a 3-7/8" [9.84 cm] deep box and shall accommodate up to a maximum of 4 gases. The 2" [5.1 cm] valve shall be positioned on the bottom of the assembly. Refer to 2" [5.1 cm] Valve Drawing provided on page 2.

ACP-SP-MLTPL-ALRM-VLV-COMBO-UNIT 12.10.2018

The Letter “L” Defines the Language:

English (NFPA) = U

Spanish (NFPA) = S

Spanish (CSA/ISO) = H

English (CSA/ISO) = E

French (CSA/ISO) = F

The Letter “G” Defines the Type of Gas:

Oxygen = O

Medical Air = A

MedVac = V

Nitrous Oxide = 2

Nitrogen = N

Carbon Dioxide = C

WAGD (NFPA) = W

AGSS (ISO) = E

Instrument Air = I

The Letter “X” Defines the Valve Size:

1/2" [1.3 cm] 05 = 1

3/4" [1.9 cm] 07 = 2

1" [2.5 cm] 10 = 3

1-1/4" [3.2 cm] 12 = 4

1-1/2" [3.8 cm] 15 = 5

2" Full Port [5.1 cm] 20F = 6

RO Water System ROS-1

AXEON L1-300

Wall Mount

Reverse Osmosis System

AXEON L1-300

Reverse Osmosis System with Optional 20” Stand and 20” Filter Housings

AXEON L1-Series Reverse Osmosis Systems are manufactured for light commercial applications and feature a compact wall mount space-saving design. The L1-Series come pre-assembled and ready for immediate on-line service with minimal set up and simple utility connections.

AXEON L1-Series Reverse Osmosis Systems have been engineered for capacities of 200 and 300 gallons per day and feature a single pump design for enhanced performance.

Standard Features AXEON® 5 Micron Sediment Pre-Filter

AXEON 10 Micron Carbon Block Pre-Filter and Post-Filter

AXEON by Pentek® 10” Slim Line Filter Housings

AXEON HF4 Extra Low Energy Membrane

AXEON FRP-300E Fiberglass Membrane Housing

AXEON 0 – 300 psi Glycerin-Filled Pump Pressure Gauge

AXEON 0 – 100 psi Glycerin-Filled Pre-Filter Pressure Gauge

AXEON 0 – 100 psi Glycerin-Filled Permeate Pressure Gauge

John Guest® Push/Pull Fittings with Locking Safety Clips

Aquatec® High Flow Booster Pump

Aquatec Tank Pressure Switch

Aquatec Feed Solenoid Valve

Aquatec Auto Flush Timer Valve

Options and Upgrades 10” and 20“ Floor Stands

Product Water Storage Tanks

AXEON HF5 Ultra Low Energy Membrane (For Cold Water Applications)

AXEON 2521 SS-250E Stainless Steel Membrane Housing

HM Digital® DM-2 TDS Meter

AXEON by Pentek 20” Slim Line Filter Housings

Engineered Membrane Solutions

L1-Series Reverse Osmosis Systems

Product Specifications L1-200

Single Pass

TDS <1000

40%

98.5%

0.14 / 0.53

0.21 / 0.79

3/8 Tube 3/8 Tube 3/8 Tube

Aquatec 8800

110V, 60Hz, 1Ph, 1.0A 220V, 50Hz, 1Ph, 0.5A

9 x 20 x 19 / 22.9 x 50.8 x 48.3 42 / 19.1

L1-300

Single Pass

TDS <1000

50%

98.5%

0.21 / 0.79

0.21 / 0.79

3/8 Tube 3/8 Tube 3/8 Tube

Aquatec 5800

110V, 60Hz, 1Ph 1.0A 220V, 50Hz, 1Ph, 0.5A

9 x 27 x 19 / 22.9 x 68.6 x 48.3 50 / 22.7

Design Temperature 77°F Max. Turbidity NTU ^ 1

Max. Feed Temperature 85°F Max. Free Chlorine ppm 0

Min. Feed Temperature 40°F Max. TDS ppm 1,000

Max. Ambient Temperature 120°F Max. Hardness GPG ^^ 1

Min. Ambient Temperature 40°F Max. pH (Continuous) 11

Max. Feed Pressure psi 85 Min. pH (Continuous) 3

Min. Feed Pressure psi 45 Max. pH (Cleaning 30 Min.) 12

Max. Operating Pressure psi 120 Min. pH (Cleaning 30 Min.) 2

Max. SDI Rating <3

Operating Limits

Test Parameters: Static pressure tested.

^^ Scale prevention measures must be taken to prolong membrane life.

Appropriate Pre- filtration must be installed in order to prevent premature membrane fouling.

Product �ow and recovery rates are based on feedwater conditions of 550 TDS at 77°F at 100 psi. Treatment ability of the RO system is dependent on feedwater quality. Higher TDS and/or lower temperatures will reduce product �ow. Performance projections should be run for each installation.

Design

Con�guration

Feed Water Source (ppm)

Standard Recovery*

Rejection and Flow Rates

Nominal Salt Rejection

Permeate Flow* (gpm / lpm)

Concentrate Flow (gpm / lpm)

Connections

Feed (in)

Permeate (in)

Concentrate (in)

Membranes

Membrane Per Vessel

Membrane Quantity

Membrane Size

Vessels

Vessel Array

Vessel Quantity

Pumps

Pump Type

Electrical

Standard Voltage

Voltage Options

System Dimensions

L x W x H (in / cm)

Weight (lb / kg)

MKTF-247-C AXEON is a registered trademark of AXEON Water Technologies. 4/15 ©2015 AXEON Water Technologies

P: 800-320-4074 • W: www.axeonwater.com F: 800-609-0829 • E: sales@axeonwater.com 40980 County Center Drive, Suite 100, Temecula, CA 92591

L1-Series Reverse Osmosis Systems

Final CD Submittal, August 10, 2022 Relocate and Expand Dental Clinic

VA Medical Center – Fairfield, California

Final CD Submittal

Section 3:

Mechanical Cut Sheets

Condensing Unit CU-3

FEATURES

Larger capacity single modules ranging up to 14 tons and systems up to 38 tons allow for a more flexible system design Variable Refrigerant Temperature (VRT) control allows the VRV IV to deliver up to 28% of improvement in seasonal cooling efficiency compared to previous Daikin VRV heat pump systems Modular and lightweight enables flexibility in system layout and installation with larger capacity single modules reducing electrical, piping connections Compatible with Daikin DVS series of Dedicated Outdoor Air Systems

(DOAS)

System wide auto-climate adjustment technology to increase the energy efficiency Improved efficiency with IEER values now up to 29.3 Can provide heating down to -13°F WB as standard All inverter compressors to increase the efficiency and avoid starting current inrush Same product structure for 230V and 460V simplifies ordering New configurator software designed to simplify the commissioning and maintenance of the system Factory standard coil guards Assembled in the US to increase flexibility and reduce lead times Standard Limited Warranty: 10-year limited parts warranty

BENEFITS

Can operate up to 12 indoor units on a single piping network Modular and lightweight - enables flexibility in system layout and installation Refrigerant cooled inverted technology to avoid influence from ambient temperatures Integrated inverter technology deliver maximum efficiency during part load conditions and provide precise individual zone control Heat exchanger coil wraps around on all 4 sides of the unit to increase the surface area / efficiency Corrosion resistance 1000hr salt spray tested Daikin PE blue fin heat exchanger Design flexibility with long piping lengths up to 3,280 ft. total and 100 ft.

vertical separation between indoor units Designed with reduced MOP to optimize installation cost Digital display on the unit for improved and faster configuration, commissioning, and trouble shooting

Submittal Data Sheet 6 Ton, 230V, VRV IV HR

REYQ72TATJU

www.daikinac.com www.daikincomfort.comDaikin City Generated Submittal Data

Submittal Date: 9/12/2018 8:59:51 AM Page 1 of 3

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

CONDENSING UNIT 1-CU-3

REYQ72TATJU

PERFORMANCE

Outdoor Unit Model No. REYQ72TATJU Outdoor Unit Name: 6 Ton, 230V, VRV IV HR

Type: Heat Recovery Unit Combination:

Rated Cooling Conditions: Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75 Rated Heating Conditions: Indoor (°F DB/WB): 70 / 60

Ambient (°F DB/WB): 47 / 43

Rated Piping Length(ft):

Rated Height Difference (ft):

Rated Cooling Capacity (Btu/hr): 69,000 Rated Heating Capacity (Btu/hr): 75,000

Nom Cooling Capacity (Btu/hr): 72,000 Nom Heating Capacity (Btu/hr): 81,000

Cooling Input Power (kW): 4.13 Heating Input Power (kW): 5.46

EER (Non-Ducted/Ducted): 15.00 / 12.30 Heating COP (Non-Ducted/Ducted): 4.3 / 3.6

IEER (Non-Ducted/Ducted): 24.90 / 20.90 Heating COP 17F (Non-Ducted/Ducted): 2.7 / 2.4

SCHE (Non-Ducted/Ducted): 25.40 / 21.40

OUTDOOR UNIT DETAILS

Power Supply (V/Hz/Ph): 208-230 / 60 / 3 Compressor Stage: Inverter

Power Supply Connections: L1, L2, L3 Ground Capacity Control Range (%): 15 - 100

Min. Circuit Amps MCA (A): 30.2 Capacity Index Limit: 36.0 - 93.0

Max Overcurrent Protection (MOP) (A): 35 Airflow Rate (H) (CFM): 5544

Max Starting Current MSC(A): Gas Pipe Connection (inch): 3/4

Rated Load Amps RLA(A): 20.7 Liquid Pipe Connection (inch): 3/8

Dimensions (Height) (in): 66-11/16 H/L Pressure Connection (inch) 5/8

Dimensions (Width) (in): 36-11/16 H/L Equalizing Connection (inch)

Dimensions (Depth) (in): 30-3/16 Sound Pressure (H) (dBA): 58

Net Weight (lb): 507 Sound Power Level (dBA): 79

Max. No. of Indoor Units: 12 www.daikinac.com www.daikincomfort.comDaikin City Generated Submittal Data

Submittal Date: 9/12/2018 8:59:51 AM Page 2 of 3

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without

REYQ72TATJU

SYSTEM DETAILS

Refrigerant Type: R-410A Cooling Operation Range (°F DB): 23 - 122

Holding Refrigerant Charge (lbs): 21.9 Heating Operation Range (°F WB): -13 - 60

Additional Charge (lb/ft): Max. Pipe Length (Vertical) (ft): 295

Pre-charge Piping (Length) (ft): Cooling Range w/Baffle (°F DB): -

Max. Pipe Length (Total) (ft): 540 Heating Range w/Baffle (°F WB): -

Max Height Separation (Ind to Ind ft):

DIMENSIONAL DRAWING

www.daikinac.com www.daikincomfort.comDaikin City Generated Submittal Data

Submittal Date: 9/12/2018 8:59:51 AM Page 3 of 3

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without

Exhaust Fan EF-1

JobName:G-143-VGCutSheet
Tag:MK-1
Quantity:1
PrintedDate:September5,2019
Model:G-143-VG
DirectDriveCentrifugalRoofExhaustFan
StandardConstructionFeatures:Aluminumhousing.Centrifugalbackwardinclinedaluminumwheel.
Directdrivenmotormountedonvibrationisolation.

Fan Configuration

Drive type Direct

Performance

RequestedVolume(CFM) 1,290
ActualVolume(CFM) 1,290
TotalExternalSP(in.wg) 0.5
FanRPM 1,006
OperatingPower(bhp) 0.21
StartupPower(bhp) 0.21
AirStreamTemp(F) 70
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.075
StaticEfficiency(%) 48

Outlet Velocity (ft/min) 977

Motor

Enclosure ODP Size (hp) 1/2

V/C/P 115/60/1 NEC FLA (Amps) 6.7

Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

1,006 FRPM

Do no t o pe ra te

in
s

ha de d ar ea

Sy ste m

Volume (CFM) x 100 0 2 4 6 8 10 12 14 16 18 20

St at ic P re ss ur e (in

. w g)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Br ak e Ho rs ep ow er (B

HP

0.04

0.08

0.12

0.16

0.2

0.24

0.28

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 72 75 70 63 57 54 49 42 66 55 7.5

GreenheckFanCorporationcertifiesthatthemodelshownhereinislicensedtobear
theAMCASeal.Theratingsshownarebasedontestsandproceduresperformedin
accordancewithAMCAPublication211andAMCAPublication311andcomplywith
therequirementsoftheAMCACertifiedRatingsProgram.Performancecertifiedisfor
installationtypeA:Freeinlet,Freeoutlet.Powerrating(BHP/kW)doesnotinclude
transmissionlosses.Performanceratingsincludetheeffectsofbirdscreen.Thesound
ratingsshownareloudnessvaluesinfansonesat5ft.(1.5m)inahemispherical
freefieldcalculatedperAMCAStandard301.Valuesshownareforinstallationtype
A:freeinlethemisphericalsonelevels.dBAlevelsarenotlicensedbyAMCA
International.TheAMCACertifiedRatingsSealforSoundappliestoinletsone
ratingsonly.
FLA-basedontables150or148ofNationalElectricCode2002.Actual
motorFLAmayvary,forsizingthermaloverload,consultfactory.

Page 1 of 2 Version 2.3.2, July 2019

EXHAUST FAN 1-EF-1

JobName:G-143-VGCutSheet
Tag:MK-1
Quantity:1
PrintedDate:September5,2019

Dimensions and Weights

Label Value Description

- 50 Weightw/oaccessories(lbs)
A 36 OverallHeight(in)
D 28 OverallWidth(in)
B 22 CurbCapWidth(in)
C 22 CurbCapLength(in)
- 16 Duct/DamperWidth(in)
- 16 Duct/DamperLength(in)
- 18.5 RoofOpeningWidth(in)
- 18.5 RoofOpeningLength(in)
*Alldimensionsareininches.
Page2of2 Version2.3.2,July2019

Exhaust Fan EF-2

JobName:CSW-13-BICutSheet
Tag:MK-1
Quantity:1
PrintedDate:September4,2019
Model:CSW-13-BI
BackwardInclinedSingleWidthBlower
StandardConstructionFeatures:Steelscroll(optionalaluminumorstainlesssteel),PermaLockseam
(optionalwelded).Centrifugalbackwardinclinedsteelwheel(optionalaluminumorstainlesssteel).Steel
inletcone(optionalaluminumorstainlesssteel).Beltdrivenmotormountedoutoftheairstream.

Fan Configuration

Arrangement 10 Discharge position TH

Wheelrotation CW
Fanmaterial Steel

Drive type Belt

Performance

RequestedVolume(CFM) 1,230
ActualVolume(CFM) 1,230
TotalExternalSP(in.wg) 0.5
FanRPM 1,158
DriveLoss(%) 17
OperatingPower(bhp) 0.24
StartupPower(bhp) 0.24
AirStreamTemp(F) 70
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.075
StaticEfficiency(%) 50

Outlet Velocity (ft/min) 1,171

Motor

Enclosure ODP Size (hp) 1/4

V/C/P 115/60/1 NEC FLA (Amps) 5.8

Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

Do no t o pe ra te

in
s

ha de d ar ea

System

Volume (CFM) x 100 0 2 4 6 8 10 12 14 16 18

St at ic P re ss ur e

(in . w g)

0.2

0.4

0.6

0.8

Br ak e Ho rs ep ow er

(B

HP

0.05

0.1

0.15

0.2

0.25

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 76 76 72 66 64 58 52 44 69 58 8.8

GreenheckFanCorporationcertifiesthatthemodelshownhereinislicensedtobear
theAMCASeal.Theratingsshownarebasedontestsandproceduresperformedin
accordancewithAMCAPublication211andAMCAPublication311andcomplywith
therequirementsoftheAMCACertifiedRatingsProgram.Performancecertifiedisfor
installationtypeB:Freeinlet,Ductedoutlet.Powerrating(BHP/kW)includes
transmissionlosses.Performanceratingsdonotincludetheeffectsof
appurtenances(accessories).Thesoundpowerlevelratingsshownareindecibels,
referredto10^-12wattscalculatedperAMCAStandard301.TheA-weightedsound
ratingsshownhavebeencalculatedperAMCAInternationalStandard301.Values
shownareforinletLwi,LwiA,andoutletLwo,LwoAsoundpowerlevelsfor
installationtypeB:freeinlet,ductedoutlet.Outletratingsincludetheeffectsof
ductendcorrection.dBAlevelsarenotlicensedbyAMCAInternational.TheAMCA
CertifiedRatingsSealforSoundappliestoinletLwi,LwiAandoutletLwo,LwoA
ratingsonly.FLA-basedontables150or148ofNationalElectricCode2002.Actual

motor FLA may vary, for sizing thermal overload, consult factory.

Page 1 of 2 Version 2.3.2, July 2019

EXHAUST FAN 1-EF-2

JobName:CSW-13-BICutSheet
Tag:MK-1
Quantity:1
PrintedDate:September4,2019

Dimensions and Weights

Label Value Description

- 204 Weightw/oaccessories(lbs)
A 34 OverallHeight(in)
B 26 OverallWidth(in)
C 39 OverallLength(in)
- 17 InletDiameter(in)
- 11x14 OutletSize(WxH)(in)

Wheel rotation is defined as being viewed from the drive side.

*Alldimensionsareininches.
Page2of2 Version2.3.2,July2019

Exhaust Fan EF-3

JobName:CSW-9-BICutSheet
Tag:MK-1
Quantity:1
PrintedDate:September5,2019
Model:CSW-9-BI
BackwardInclinedSingleWidthBlower
StandardConstructionFeatures:Steelscroll(optionalaluminumorstainlesssteel),PermaLockseam
(optionalwelded).Centrifugalbackwardinclinedsteelwheel(optionalaluminumorstainlesssteel).Steel
inletcone(optionalaluminumorstainlesssteel).Beltdrivenmotormountedoutoftheairstream.

Fan Configuration

Arrangement 10 Discharge position TH

Wheelrotation CW
Fanmaterial Steel
Drivetype Belt

Performance

RequestedVolume(CFM) 200
ActualVolume(CFM) 200
TotalExternalSP(in.wg) 0.5
FanRPM 1,131
DriveLoss(%) 40
OperatingPower(bhp) 0.06
StartupPower(bhp) 0.06
AirStreamTemp(F) 70
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.075
StaticEfficiency(%) 42

Outlet Velocity (ft/min) 310

Motor

Enclosure ODP Size (hp) 1/4

V/C/P 115/60/1 NEC FLA (Amps) 5.8

Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

1,131 FRPM

Sy ste m

Volume (CFM) x 100 0 1 2 3 4 5 6

St at ic P re ss ur e (in

. w g)

0.1

0.2

0.3

0.4

0.5

0.6

Br ak e Ho rs ep ow er (B

HP

0.02

0.04

0.06

0.08

0.1

0.12

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 76 67 63 59 53 49 46 37 61 50 5.5

GreenheckFanCorporationcertifiesthatthemodelshownhereinislicensedtobear
theAMCASeal.Theratingsshownarebasedontestsandproceduresperformedin
accordancewithAMCAPublication211andAMCAPublication311andcomplywith
therequirementsoftheAMCACertifiedRatingsProgram.Performancecertifiedisfor
installationtypeB:Freeinlet,Ductedoutlet.Powerrating(BHP/kW)includes
transmissionlosses.Performanceratingsdonotincludetheeffectsof
appurtenances(accessories).Thesoundpowerlevelratingsshownareindecibels,
referredto10^-12wattscalculatedperAMCAStandard301.TheA-weightedsound
ratingsshownhavebeencalculatedperAMCAInternationalStandard301.Values
shownareforinletLwi,LwiA,andoutletLwo,LwoAsoundpowerlevelsfor
installationtypeB:freeinlet,ductedoutlet.Outletratingsincludetheeffectsof
ductendcorrection.dBAlevelsarenotlicensedbyAMCAInternational.TheAMCA
CertifiedRatingsSealforSoundappliestoinletLwi,LwiAandoutletLwo,LwoA
ratingsonly.FLA-basedontables150or148ofNationalElectricCode2002.Actual

motor FLA may vary, for sizing thermal overload, consult factory.

Page 1 of 2 Version 2.3.2, July 2019

EXHAUST FAN 1-EF-3

JobName:CSW-9-BICutSheet
Tag:MK-1
Quantity:1
PrintedDate:September5,2019

Dimensions and Weights

Label Value Description

- 174 Weightw/oaccessories(lbs)
A 30 OverallHeight(in)
B 21 OverallWidth(in)
C 35 OverallLength(in)
- 13 InletDiameter(in)
- 8x11 OutletSize(WxH)(in)

Wheel rotation is defined as being viewed from the drive side.

*Alldimensionsareininches.
Page2of2 Version2.3.2,July2019

Fancoil Unit FCU-3

FEATURES

Increased capacity range for increased flexibility Improved efficiency with DC fan motor Ease of installation with auto adjusting airflow at commissioning based on external static pressure Easy maintenance with service access from below Installation flexibility with a low profile, compact design at less than 12'' in height Standard Limited Warranty: 10-year warranty on compressor and all parts

BENEFITS

Enhanced indoor air quality and LEED ready with MERV 13 filter options Flexible ductwork design with ESP capabilities up to 0.54'' W.G.

New economizer control logic New configurable auxiliary heater control logic Design allows it to be completely concealed - perfect for retail, classrooms, offices, banks, restaurants, and hotels.

3.0-Ton DC Ducted Concealed Ceiling

FXMQ36PBVJU

www.daikinac.com www.daikincomfort.comDaikin City Generated Submittal Data

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without

HORIZONTAL FAN-COIL UNIT 1-FCU-3

FXMQ36PBVJU

PERFORMANCE

Indoor Unit Model No. FXMQ36PBVJU Indoor Unit Name: 3.0-Ton DC Ducted Concealed Ceiling

Type: Ducted Rated Cooling Conditions: Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

Rated Cooling Capacity (Btu/hr): 36,000 Rated Heating Conditions: Indoor (°F DB/WB): 70 / 70 Ambient (°F DB/WB): 47 / 43

Sensible Capacity (Btu/hr): 28,800 Rated Piping Length(ft):

Cooling Input Power (kW): 0.380 Rated Height Separation (ft):

Rated Heating Capacity (Btu/hr): 40,000

Heating Input Power (kW): 0.36

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph): 208-230 / 60 / 1 Airflow Rate (HH/H/M/L) (CFM): 1,130/1,130/953/812

Power Supply Connections: L1, L2, Ground Moisture Removal (Gal/hr):

Min. Circuit Amps MCA (A): 2.90 Gas Pipe Connection (inch): 5/8

Max Overcurrent Protection (MOP) (A): 15.00 Liquid Pipe Connection (inch): 3/8

Dimensions (HxWxD) (in): 11-13/16 x 55-1/8 x 27-9/16 Condensate Connection (inch): 1-1/4

Panel (HxWxD) (in): Sound Pressure (H/M/L) (dBA): 43/41/39

Net Weight (lb): 102 Sound Power Level (dBA):

Panel Weight (lb): Ext. Static Pressure (Rated/Max) (inWg): 0.40 / 0.80 www.daikinac.com www.daikincomfort.comDaikin City Generated Submittal Data

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without

FXMQ36PBVJU

DIMENSIONAL DRAWING

www.daikinac.com www.daikincomfort.comDaikin City Generated Submittal Data

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without

Rooftop Unit RTU-1

Split Systems for IT Rooms

2.0-Ton Wall Mounted Cooling Only

FAQ24TAVJURZR24TAVJU

INDOOR UNIT OUTDOOR UNIT

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056 Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

Submittal Date: 6/3/2019 8:10:22 AM Page 1 of 4

SPLIT SYSTEM FOR IT ROOMS

FAQ24TAVJURZR24TAVJU

SYSTEM PERFORMANCE

Indoor Unit Model No. FAQ24TAVJU Indoor Unit Name: Sky-Air Wall Mounted

Outdoor Unit Model No. RZR24TAVJU Outdoor Unit Name: Sky-Air Cooling Only ODU

Rated Cooling Capacity (Btu/hr): 24,000 Rated Cooling Conditions:

Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

Sensible Capacity (Btu/hr): 18,000 Rated Piping Length(ft): 25

Max/Min Cooling Capacity (Btu/hr): / Rated Height Difference (ft): 0.00

Cooling Input Power (kW):

SEER (Non-Ducted/Ducted): 17.60 /

EER (Non-Ducted/Ducted): 10.20 /

SYSTEM DETAILS

Refrigerant Type: R-410A Cooling Operation Range (°F DB): 23 - 122

Holding Refrigerant Charge (lbs): 6.4 Heating Operation Range (°F WB): -

Additional Charge (lb/ft): 0.04 Max. Pipe Length (Vertical) (ft): 98

Pre-charge Piping (Length) (ft): 15 Cooling Range w/Baffle (°F DB): 0 - 122

Max. Pipe Length (Total) (ft): 164 Heating Range w/Baffle (°F WB): -

Max Height Separation (Ind to Ind ft): 0

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056 Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without

Submittal Date: 6/3/2019 8:10:22 AM Page 2 of 4

FAQ24TAVJURZR24TAVJU

INDOOR UNIT DETAILS

Power Supply (V/Hz/Ph): 208-230 / 60 / 1 Airflow Rate (H/L) (CFM): 635/470

Power Supply Connections: L1, L2, Ground Moisture Removal (Gal/hr):

Min. Circuit Amps MCA (A): 0.6 Gas Pipe Connection (inch): 5/8

Max Overcurrent Protection (MOP) (A): 15 Liquid Pipe Connection (inch): 3/8

Dimensions (HxWxD) (in): 11-3/8 x 41-3/8 x 9-1/4 Condensate Connection (inch): 1/2

Net Weight (lb): 31 Sound Pressure (H/L) (dBA): 43/37

Ext. Static Pressure (Rated/Max) (inWg): / Sound Power Level (dBA):

DIMENSIONAL DRAWING - INDOOR UNIT

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056 Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without

Submittal Date: 6/3/2019 8:10:22 AM Page 3 of 4

FAQ24TAVJURZR24TAVJU

OUTDOOR UNIT DETAILS

Power Supply (V/Hz/Ph): 208-230 / 60 / 1 Compressor Stage:

Power Supply Connections: L1, L2, Ground Capacity Control Range (%): 14 - 100

Min. Circuit Amps MCA (A): 16.5 Airflow Rate (H) (CFM): 2682

Max Overcurrent Protection (MOP) (A): 25 Gas Pipe Connection (inch): 5/8

Max Starting Current MSC(A): Liquid Pipe Connection (inch): 3/8

Rated Load Amps RLA(A): 15.3 Sound Pressure (H) (dBA): 58

Dimensions (HxWxD) (in): 39 x 37 x 12-5/8 Sound Power Level (dBA):

Net Weight (lb): 172

DIMENSIONAL DRAWING - OUTDOOR UNIT

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056 Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without

Submittal Date: 6/3/2019 8:10:22 AM Page 4 of 4

Terminal Unit with Electrical Heat single / dual duct terminals

Redefine your com fort zone. ™

| w w w .titus-hvac.com

M21

M

SELECTION AND CAPACITIES

Recommended Coil Selection Data The table at the right describes the maximum recommended kW capacities and number of stages available for Titus single duct terminals.

To make a coil selection:

1. Check the desired kW is available in desired unit size and number of stages. (Required to prevent excessive watt density and current draw, while taking into account unit size limitations.)

2. Check the desired minimum airflow limit is within recommended operating range. (Ensures velocity pressure will be sufficient to close airflow sensing switch.)

3. Multiply desired minimum airflow limit by a factor of 0.0142 and check the result is equal to or greater than desired kW. (Limits temperature rise across the coil to 45°F.)

These requirements established to prevent excessive temperature rise caused by low airflow and/or oversized coils. Minimum airflow limits must be within recommended ranges to ensure proper operation and long service life. For optimum diffuser performance and maximum thermal comfort, coil discharge temperatures should not be more than 15°F above desired room temperatures. For proper coil operation it is recommended that coil discharge temperatures do not to exceed 100°F.

Inlet Size

Heating cfm Range

Number of

Steps Available

120V 1 Phase kW Range

208V 1 Phase kW Range

240V 1 Phase kW Range

277V 1 Phase kW Range

208V 3 Phase kW Range

480V 3 Phase kW Range

Min Max Min Max Min Max Min Max Min Max Min Max

4 55-225 1 0.5

5.0 0.5

3.0 1.0

3.0 1.0

3.0 1.5 3.0 2.5 3.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

5 85-350 1 0.5

5.0 0.5

5.0 1.0

5.0 1.0

5.0 1.5 5.0 2.5 5.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

6 105-500 1 0.5

5.0 0.5

7.5 1.0

7.5 1.0

7.5 1.5 7.5 2.5 7.52 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

7 135-650 1 0.5

5.0 0.5

9.5 1.0

9.5 1.0

9.5 1.5 9.5 2.5 9.52 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

8 190-900 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 13.0 2.5 13.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

9 225-1050 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 16.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

10 300-1400 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 21.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

12 425-2000 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 30.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

14 575-3000 1 0.5

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 3.0 36.02 1.0 2.0 2.0 2.0 2.0 3 1.5 3.0 3.0 3.0 3.0

16 750-4000 1 0.5

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 3.0 36.02 1.0 2.0 2.0 2.0 2.0 3 1.5 3.0 3.0 3.0 3.0

24x16 1800-8000 1 1.0

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 4.0 36.02 2.0 2.0 2.0 3.0 2.0 3 3.0 3.0 3.0 4.5 3.0

Useful formulas:

kW= cfm x ∆T or ∆T= kW x 3160 or cfm = kW x 3160

3160 cfm ∆T Where ∆T = air temperature rise.

PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT)

Titus electric heating coils are specifically designed for use with VAV terminal units. They include an extended plenum section and diffuser plate to minimize stratification. The heating elements are designed to minimize hot spots and nuisance tripping of the thermal cutouts.

Note: The Titus 480V, 3-phase electric heat configuration is 4-wire wye. 3-wire configuration is available.

kW ≤ cfm x 0.0142

ELECTRIC CO

ILS

ELECTRIC COILS

VAV TERMINAL UNITS WITH ELEC. HEAT

single / dual duct terminals

Re de fin e yo ur c om fo rt zo ne w w w .ti tu s-hv ac

.c om

M22

M

Inlet Size

Heating cfm Range

120V 1 Phase kW Range

208V 1 Phase kW Range

240V 1 Phase kW Range

277V 1 Phase kW Range

208V 3 Phase kW Range

480V 3 Phase kW Range

Min Max Min Max Min Max Min Max Min Max Min Max

4 55-225 0.5 2.5 0.5 3.0 1.0 3.0 1.0 3.0 1.5 3.0 2.5 3.0

5 85-350 0.5 4.5 0.5 5.0 1.0 5.0 1.0 5.0 1.5 5.0 2.5 5.0

6 105-500 0.5 5.0 0.5 7.5 1.0 7.5 1.0 7.5 1.5 7.5 2.5 7.5

7 135-650 0.5 5.0 0.5 9.5 1.0 9.5 1.0 9.5 1.5 9.5 2.5 9.5

8 190-900 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 13.0

9 225-1050 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 16.0

10 300-1400 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 21.0

12 425-2000 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 25.0

14 575-3000 0.5 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

16 750-4000 0.5 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

24x16 1800-8000 2.0 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 4.0 25.0

PESV, AESV, DESV / APPLICATION DATA (LYNERGY HEAT)

EL

EC

TR

IC

C O

IL

S

ELECTRIC COILS

Final CD Submittal, August 10, 2022 Relocate and Expand Dental Clinic

VA Medical Center – Fairfield, California

Final CD Submittal

Section 4:

Electrical Cut Sheets

Corelite JAYLUM – JS Frosted Lens

LED

DESCRIPTION

Catalog #

Project

Comments

Prepared by

Type

Date

SPECIFICATION FEATURES

Corelite

08/21/2015

PS524006EN

ORDERING INFORMATION

Series Front Optics Back Optics Light Level

(3500K) (1) Color

Temperature Circuiting/

Wiring Input Voltage Mounting Driver Options (3) Finish

JS= Jaylum Sconce

L = Frosted Lens

L = Frosted Lens

N = None (No Backlight)

1 = Light Level 1 (8 W, 564 Lms) 2 = Light Level 2 (18 W, 1175 Lms) 3 = Light Level 3 (23 W, 1376 Lms)

L30 = LED 3000K

L35 = LED 3500K

L40 = LED 4000K

1D = 1 Dimming Circuit (2)

120 = 120V 277 = 277V UNV = Universal

(120V-277V)

SU-WA = Wall Mount, J-Box

STD = Standard 0-10V

5LT = Fifth Light

DALI (4)

W = White S = Silver CC = Custom

Color

Sample Number: JS-LL-1L35-1D-UNV-SU-WA-STD-W

TECHNICAL NOTES

1. Lumen values vary depending on color temperature and lens option. Refer to photometric data for specific lumen values.

2. Dimming wires come standard in all LED fixtures but can be capped in the field for standard switched operation.

3. Maximum one driver per fixture.

4. Must be used in conjunction with a DALI control system. For a complete listing of Fifth Light Technology products and other solutions from Cooper

Lighting Solutions, visit www.cooperlighting.com.

Construction Low profile housing and integral gear tray constructed from die-formed 20 gauge cold rolled steel forming a 8” x 1-1/2” ADA compliant profile.

Reflectors Reflector pan is painted with a high reflectance white powder coat finish.

End Caps Standard endcaps are rounded die cast aluminum and mechanically attached flush to end of fixture without exposed fasteners.

Shielding Lens is high light transmission 0.08” thick frosted acrylic material.

Electrical Long-Life LED system coupled with electronic driver to deliver optimal performance. LEDs are available in 3000K, 3500K or 4000K with a typical CRI ≥ 85. Standard drivers are 0-10 volt continuous dimming that work with any 0-10V control/dimmer. Or, specify the Digital Addressable Lighting Interface (DALI) drivers; for use with Fifth Light controls. See ordering information for details.

Mounting Fixture mounts directly to structure over a 4 x 4 inch standard electrical box. Fixture can be mounted horizontally or vertically. Please refer to installation instructions for details.

Finish Fixture housings are high reflectance white (standard) using electrostatically applied polyester powder coat paint. Silver and custom colors are available.

Compliance Components are UL recognized and luminaires are cULus listed for 25ºC ambient environments, damp location listed, and RoHS compliant.

Life and Warranty Greater than 70% lumen maintenance expected at 60,000 hours, based off LM-80 test data and TM-21 standards. Five-year warranty.

The perfect complement to the Jaylum pendant luminaire, the Jaylum Sconce LED features crisp modern lines in a small non-obtrusive form factor. This highly efficient LED luminaire will accompany almost any décor while meeting today’s increasingly stringent energy requirements.

The Jaylum Series may be mounted horizontally or vertically and is ideal for corridors, lobbies, restrooms, and open offices. The Jaylum sconce can be mounted over a standard 4x4 inch J-Box while maintaining ADA compliance.

8.5” [216mm]

24.75” [629mm]

2.5” [64mm]

8.5” [216mm]

JAYLUM - JS

Frosted Lens

Wall Mounted Direct/Indirect

LED

Disconnect Switch

© 2019 Schneider Electric All Rights Reserved 3-1

Light Duty

General Duty

Heavy Duty

Stainless Steel Heavy Duty

Table of Contents

Section 3 Safety Switches

EZ Selector - Selection Assistance 3-2

Safety Switches EZ Selector - Selection Assistance 3-2 Safety Switches EZ Selector - Selection Assistance 3-2

Light Duty Safety Switches 3-3

Light Duty—Visible Blades 10 kA Short Circuit Current Rating 3-3

General Duty Safety Switches 3-4

General Duty—Up to 100 kA Short Circuit Current Rating 3-4 240 Volt—Single Throw Fusible Switches 3-4 240 Volt—Single Throw Non-Fusible Switches 3-5 UL Listed Maximum Short Circuit Current Ratings — AC Only 3-5

Accessories and Lug Data 3-6 Field-Installed Fuse Puller Kits 3-6 Field-Installed Electrical Interlock Kits 3-6 Equipment Grounding Kits 3-6 Field-Installed Lug Kit 400 A – 600 A 3-6 Terminal Lug Data 3-6

Dimensions for General Duty Safety Switches 3-7

Heavy Duty Safety Switches 3-8

240 Volt—Single Throw Fusible Switches 3-8 600 Volt—Single Throw Fusible Switches 3-9 600 Volt—Single Throw Non-Fusible Switches 3-10 UL Listed Maximum Short Circuit Current Ratings—AC only 3-11 Special Applications 3-12 Receptacle Switches 3-14 Accessories and Special Features 3-15 Dimensions for Heavy Duty Safety Switches 3-22

NEMAType 1 and 3R 3-22 NEMAType 4, 4X, 5, 7, 9, and 12 3-23

Double Throw Safety Switches 3-25

Fusible and Non-Fusible Overview 3-25 240 Volt — Double Throw Safety Switches 3-26 600 Volt — Double Throw Safety Switches 3-27 Accessories and Lug Data 3-28 Application Data 3-30 Terminal Lug Data 3-31 Dimensions for Double Throw Safety Switches 3-32

Series F Devices 30–100 A 3-32 Series A, E, and T4 Devices 3-33

Photovoltaic Disconnect Switches 3-34

1000 Vdc Photovoltaic Heavy Duty Disconnect Switch 3-34

S A

FE

T Y S W

IT

C H E S

9/13/2019

© 2019 Schneider Electric All Rights Reserved

3-5 www.se.com/us

General Duty—Up to 100 kA Short Circuit Current Rating

General Duty Safety Switches

Class 3130 / Refer to Catalog 3100CT1602 240 Volt—Single Throw Non-Fusible Switches Table 3.3: Non-Fusible

System Amperes NEMAType 1 Indoor NEMAType 3R Rainproof [8]

Horsepower Ratings (Max.)

Cat. No. Cat. No. 1Ø 3Ø 2 Wire (2 Blades)—240 Vac Maximum

30 — DU221RB 3 —

60 — DU222RB 10 —

60 QO260NATS [9] [10] QO200TR [9] [10] [11] 10 —

100 QO2000NS [9] [10] QO2000NRB [9] [11] 20 —

200 Use 3P Switch Use 3P Switch — — 400 Use 3P Switch Use 3P Switch — — 600 Use 3P Switch Use 3P Switch — —

3 Wire (3 Blades)—240 Vac Maximum

30 DU321 DU321RB 3 7-1/2

60 DU322 DU322RB 10 15

100 DU323 [12] DU323RB [12] 15 40

200 DU324 [13] DU324RB [13] 15 60

400 DU325 — — 125

600 DU326 [14] — — 150

UL Listed Maximum Short Circuit Current Ratings — AC Only Table 3.4: Fusible Safety Switch Short Circuit Current Rating

Fuse Class UL Listed Short Circuit Rating Plug 10 kA H, K 10 kA

J [15], R 100 kA T [16] 100 kA

Non-Fusible Safety Switches Systems equal or less than 10 kAIR SCCR—Any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used in conjunction with a non-fusible safety switch.

Systems above 10 kAIR SCCR—The UL Listed short circuit current rating for Square D non-fusible switches is based upon the switch being used in conjunction with fuses or Square D circuit breakers or Mag-Gard motor circuit protectors.

Table 3.5: Non-Fusible Safety Switch Short Circuit Current Rating Fuse Class or Circuit Breaker Type [17] UL Listed Short Circuit Rating

Any Brand Circuit Breaker 10 kA H or J PowerPact Circuit Breaker Up to 65 kA [18]

H, K 10 kA J, R 100 kA [19] T 100 kA [20]

S A

FE

T Y S W

IT

C H E S

[8] Bolt-on hubs—Refer to Hubs, page 3-15.

[9] Enclosed molded case switch—Refer to Section 1.

[10] Includes factory-installed grounding kit.

[11] Not service entrance rated—Refer to Table 3.34 for more information.

[12] If a neutral assembly is required, order and field install SN0610.

[13] If a neutral assembly is required, order and field install a SN20A Neutral Assembly Kit. For a 200% neutral application, order and field install (2) SN20A Neutral Assembly Kits and (1)

SN20NI Neutral Jumper Kit.

[14] If a neutral assembly is required, order and field install D600SN.

[15] Only applicable to 200 A - 600 A except D325NT, D325NTR, D326NTand D326NTR.

[16] Only applicable to D325NT, D325NTR, D326NT, D326NTR, T327N and T327NR.

[17] Ampere rating of fuse or circuit breaker not to exceed switch ampere rating.

[18] Only applicable to DU324 and DU324RB. HD, JD = 25 kA maximum.

[19] SCCR = 50 kA, applicable to DU222RB, DU322 and DU322RB.

[20] Only applicable to DU323, DU323RB, DU325 and DU326.

3-10 © 2019 Schneider Electric All Rights Reserved

Heavy Duty Safety Switches 600 Volt—Single Throw Non-Fusible Switches www.se.com/usClass 3110 / Refer to Catalog 3100CT1602

600 Volt—Single Throw Non-Fusible Table 3.15: 600 Volt—Single Throw Non-Fusible

System Amperes

NEMA

Type 1 Indoor

NEMAType 3R Rainproof [19]

NEMAType 4, 4X, 5 [20] 304 Stainless Steel [21] Dust tight, Watertight

Corrosion Resistant [19]

NEMAType 12K With

Knockouts [19]

NEMAType 3R, 5 or 12 [22] Without

Knockouts [19]

Horsepower Ratings (Max.)

Volts ac dc [23] 240 480 600

Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. 1Ø 3Ø 1Ø 3Ø 1Ø 3Ø 250 600 2-Wire (2 Blades)—600 Vac, 600 Vdc

Use three-wire devices for two-wire applications.

60 — — — — — — — — 100 — — — — — — — — 200 — — — — — — — —

400 HU265 HU265R HU265DS — HU265AWK — 125 — 250 — — 50 50

600 HU266 HU266R HU266DS — HU266AWK — 200 — 400 — — 50 50

800 HU267 HU267R [24] — — HU267AWK — — — — 50 — — 50

1200 HU268 HU268R [24] — — HU268AWK — — — — 50 — — 50

3-Wire (3 Blades)—600 Vac, 600 Vdc

30 HU361 HU361RB HU361DS HU361A HU361AWK 5 10 7-1/2 20 10 30 5 15

30 HU361EI[25] HU361RBEI

[25] HU361DSEI [25] HU361AEI [25] HU361AWKEI[25] 5 10 7-1/2 20 10 30 5 15

30 — HU3612RB [26] — HU3612A[26] HU3612AWK[26] 5 10 7-1/2 20 10 30 5 15

60 HU362 HU362RB HU362DS HU362A HU362AWK 10 20 25 50 30 60 10 30

60 — — HU362DSEI[25] — — 10 20 25 50 30 60 10 30

100 HU363 HU363RB HU363DS HU363A HU363AWK 20 40 40 75 40 100 20 50

200 HU364 HU364RB HU364DS HU364A HU364AWK 15 60 50 125 50 150 40 50

400 HU365 HU365R HU365DS — HU365AWK — 125 — 250 — 350 50 50

600 HU366 HU366R HU366DS — HU366AWK — 200 — 400 — 500 50 50

800 HU367 HU367R [24] — — HU367AWK — — — 500 50 500 — 50

1200 HU368 HU368R [24] — — HU368AWK — — — — 50 500 — 50

4-Wire (4 Blades)—600 Vac, 600 Vdc [27] 2Ø 3Ø 2Ø 3Ø 2Ø 3Ø

30 HU461 [28] — HU461DS — HU461AWK [29] 10 10 20 20 25 30 10[30] 15[30]

60 HU462 [28] — HU462DS — HU462AWK 20 20 40 50 50 60 10 30

100 HU463 [28] — HU463DS — HU463AWK 30 40 50 75 50 75 20 30

200 HU464 [28] — HU464DS — HU464AWK 50 60 50 125 50 150 40 50

400 HU465 — — — HU465AWK — 125 — 250 — 350 50 50

600 HU466 — — — — — 200 — 400 — 500 50 50

6-Wire (6 Blades)—600 Vac [27] 3Ø 3Ø 3Ø

30 — — HU661DS — HU661AWK — 10 — 20 — 30 — —

60 — — HU662DS — HU662AWK — 20 — 50 — 60 — —

100 — — HU663DS — HU663AWK — 50 — 75 — 75 — —

200 — — HU664DS — HU664AWK — 60 — 125 — 150 — —

S A

FE

T Y S W

ITC

H E S

[19] For Rainproof Bolt-On Hubs and Watertight Hubs see Hubs, page 3-15.

[20] Complete rating is NEMAType 3, 3R, 4, 4X, 5 and 12.

[21] For 316 stainless, see 316 Grade Stainless Steel—NEMAType 3, 3R, 4, 4X, 5, 12, page 3-12.

[22] Also suitable for NEMAType 3R application by removing drain screw from bottom endwall.

[23] For switching dc, use two outside switching poles.

[24] Suitable for NEMAType 5 applications with drain screw installed.

[25] Switches with EI suffix are stocked with factory-installed electrical interlocks with one normally-open and one normally-closed contact.

[26] Use 60 A enclosure accessories, including electrical interlocks.

[27] Not suitable for use as service equipment.

[28] No knockouts are provided.

[29] Requires 60 A accessories. See NEMAType 4, 4X, 5, 7, 9, and 12, page 3-23 for series rating.

[30] HU461AWK (Series F6) is rated 5 hp@250 Vdc, 15 hp@600 Vdc.

Fail-Safe CLM/LD4 LED

Project Catalog # Type

Prepared by Notes Date

ADC142337 page 1 October 1, 2021 8:43 AM

Top Product Features

• Recessed grid- or flange-mount, surface-mount; Flange fits into grid ceilings; Overlapping and inset doors

• Die-formed heavy gauge steel, aluminum or stainless steel housing and door

• Pattern 12 acrylic or polycarbonate lens; Other lenses available

• IP65 rated, NSF listed and Class 100 rated (ISO 5-8); Wet Location listing under covered ceilings

• 2000K, 2700K, 3000K, 3500K, 4000K and 5000K CCT; 80 CRI minimum; Red LEDs available

• Options to meet Buy American Act requirements

Typical Applications:

Cleanroom • Pharmaceuticals • Vivariums • Hosedown • Food Prep

• High Abuse • Healthcare • Vandal Resistant

Interactive Menu

• Order Information page 2

• Product Specifications page 3

• Product Warranty

2x4 Mounting Detail

19.250” 488.95

42.000” 1066.80

21.000” 533.40

2.000” Dia Power Entry

.312” Dia Mounting Holes

(4) Places

9.625” 244.48

24.000” 609.60

48.000” 1219.20

7/8" EKO'S

for Alternate Power Entry

* Overall Fixture Depth = 3.5”

48.000” 1219.20

11.878” 301.70

7.128” 181.05

3.564” 90.53

42.000”

1066.80 21.000”

533.40

.312” 7.92

Mtg Holes

(4) Places

2.000” Dia 50.80

Power Entry

7/8" EKO'S for Alternate

Power Entry

1x4 Mounting Detail

* Overall Fixture Depth = 3.5”

24.000” 609.60

24.000” 609.60

18.000” 457.20

19.750” 501.65

9.000” 228.60

9.875” 250.83

.312”Dia 7.92

Mtg Holes

(4) Places

2.000” Dia 50.80

Power Entry

7/8" EKO'S for Alternate Power Entry

2x2 Mounting Detail

* Overall Fixture Depth = 3.5” additional product diagrams

Product Certification

Dimensional and Mounting Details - Surface

Product features

Fail-Safe

CLM | LD4 LED

Sealed / Cleanroom / Vivarium / Darkroom Recessed Flange, Recessed Grid, Surface 1' x 2', 1' x 4', 2' x 2' and 2' x 4' http://www.cooperlighting.com

Order Information SAMPLE ORDER NUMBER: CLMF-12-4-ALH-INA-A12125-LD4-2STD-40-UNV-EDC2-MSB4-AMD (White only)

CLMG-24-2-INS-A19156-LD4-4STDR63-120-EDC1-EL10W-DF-AMA (Red only) CLMG-24-2-INS-A19156-LD4-2HI40/2STDR63-UNV-EDC2 (White/Red)

Domestic Preferences

Product Family

Width Length Housing Material

Door Type Lens LEDs No. of LEDs

Domestic Preferences (9)

Product Family

Width Length Housing Material

Door Type Lens LEDs No of LEDs

[Blank]=Standard BAA= Buy American Act

CLMF=Cleanroom Moderate Recessed Flange (2)

CLMG=Cleanroom Moderate Grid

(1", 1-1/2" NEMA G)

CLMS=Cleanroom Moderate Surface (Surface available in 1x4, 2x2 and 2x4 ) (7)

24=24" Wide 12=12" Wide

2=2' Length 4=4' Length

[Blank]=Cold Rolled Steel, Powder Coat Painted White ALH=Aluminum Housing, Painted Powder Coat White SHB=Stainless Steel (304), Powder Coat Painted White SH316P=Stainless Steel (316), Powder Coat Painted White SHB=Stainless Steel (304) Brushed SH316P=Stainless Steel (316) Brushed

Inset Die Formed, One Piece INS=Inset Door, Die-formed Steel, Painted White INA=Inset Door, Die-formed Aluminum, Painted White INSSP=Inset Door,Die-formed Stainless Steel, Painted White (Replace P with B for Brushed) INSS316P=inset Door, Die-formed

(316) Stainless Steel Painted White (Replace P with B for Brushed)

Overlapping, One Piece OLS=Overlapping Door, Die-formed Steel, Painted White OLA=Overlapping Door, Die-formed Aluminum, Painted White OLSSP=Overlapping Door, Die-formed Stainless Steel, Painted White (Replace P with B for Brushed) OLSS316P=Overlapping Door, Die-formed (316) Stainless Steel, Painted White (Replace P with B for Brushed)

A12125=Pattern 12 Acrylic, 0.125" Thick, Inverted A19156=Pattern 19, 0.156" Thick, Inverted P12125=Pattern Polycarbonate, 0.125" Thick, Inverted

Other Lenses / thicknesses available, consult factory or the Lens Ordering Guide on web-site

LD4=Linear LED, Version 4.0

1=(1) LED Module in X-section 2=(2) LED Modules in X-section 3=(3) LED Modules in X-section (8) (1x4, 2x2, 2x4 Only) 4=(4) LED Modules in X-section (2x2, 2x4 Only) 5=(5) LED Modules in X-section (6) (2x2, 2x4 Only)

Notes

(9) Only product configurations with this designated prefix are built to be compliant with the Buy American Act of 1933 (BAA). Please refer to