Att 05 - Dental Final Drawing 5 of 6.pdf

PDF 14 MB Posted

Attached to
Y1DA--Project 612-164 - Dental Expansion and Relocation Northern California VAMC Located on Travis AFB, California
Solicitation number
36C77624R0085
Issued by

About this file

This document appears to be Attachment 05 - Dental Final Drawing 5 of 6 related to Solicitation No. 36C77624R0085 for Project 612-164 - Dental Expansion and Relocation at the Northern California VAMC located on Travis AFB, California. The solicitation is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The project involves the expansion and relocation of dental facilities at the Northern California VAMC. The attachment provides detailed drawings of the dental facility layout and design. No other key details about the solicitation requirements, response dates, pricing, or set-asides are included in this specific document.

View the file

Other files

File Type Posted
Dental Expansion and Relocation RFI-Questions 9.27.2024.pdf PDF
36C77624R0085 0005.docx DOCX document
3 Dental Final Spec 2 of 3.pdf PDF
4 Dental Final Spec 3 of 3.pdf PDF
5 Prelim Contractor Construct Fence Area.pdf PDF
RevJA_Brand Name_All Redacted.pdf PDF
2 Dental Final Spec 1 of 3.pdf PDF
6 Prelim Contractor Laydown Area.pdf PDF
1 Dental Expansion and Relocation_Responses to Questions.pdf PDF
36C77624R0085 Amd 04.docx DOCX document
36C77624R0085 Amd 03.docx DOCX document
S04 - Site Visit Agenda.doc DOC document
Dental Pre-Bid Site Walk Attendence 20240829.pdf PDF
Amd 02 Dental Expansion and Relocation RFI-Questions.pdf PDF
36C77624R0085 Amd 02.docx DOCX document
36C77624R0085 Amd 01.docx DOCX document
Amd 01 Dental Expansion and Relocation-Questions.xlsx XLSX spreadsheet
Att 15-Dental Final Support Doc 7 of 8.pdf PDF
Att 02 - Dental Final Drawing 2 of 6.pdf PDF
Att 09-Dental Final Support Doc 1 of 8.pdf PDF
Att 04 - Dental Final Drawing 4 of 6.pdf PDF
Att 16-Dental Final Support Doc 8 of 8.pdf PDF
Att 01 - Dental Final Drawing 1 of 6.pdf PDF
Att 19-Limitations on Subcontracting.docx DOCX document
Att 21-Division Cost Breakdown.xlsx XLSX spreadsheet
Att 03 - Dental Final Drawing 3 of 6.pdf PDF
Att 08 - Dental Final Spec 2 of 2.pdf PDF
Att 06 - Dental Final Drawing 6 of 6.pdf PDF
Att 07 - Dental Final Spec 1 of 2.pdf PDF
36C77624R0085_1 FINAL.docx DOCX document
Att 17b-DBIDS Enrollment QR.pdf PDF
Att 14-Dental Final Support Doc 6 of 8.pdf PDF
Att 18-DBA WD CA20240007 0726.pdf PDF
Att 17c-DVES - Slide Deck.pptx PPTX presentation
Att 13-Dental Final Support Doc 5 of 8.pdf PDF
Att 20-PPQ form.docx DOCX document
Att 17a-Site Visit Information.docx DOCX document
Att 11-Dental Final Support Doc 3 of 8.pdf PDF
Att 10-Dental Final Support Doc 2 of 8.pdf PDF
Att 12-Dental Final Support Doc 4 of 8.pdf PDF
Att 22-JA_Brand Name_redacted.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F.E.C.

F .E

.C

F .E

.C

G J K ML

H

7.7

J.6

6.8

DIRECTOR

CHIEF

WAITING

RECEPTION

1000A

HAC

FMS

ADMIN

TOILET

1000B

TOILET

1000C

OIT

DIRTY

F.R.

CORRIDOR

1C06

CORRIDOR

1C05

CORRIDOR

1C07

"ø

8"ø

TU

TU

16"x16"20"x20"

TU

"ø

10"ø 12"ø

"ø 8"ø 8"ø

14"ø

8"ø

8"ø

"ø

8"ø

8"ø

8"ø

8"ø

TU

"ø

"ø

"ø

6"ø

6"ø

"ø

8"ø

12"ø

6"ø

"ø

8"ø

"ø

"ø

"ø

12"ø

"ø

12"ø

10"ø

10"ø

"ø

TU

AREA B

FOR CONTINUATION

SEE MH101B

A R

E A

A F

O R

C O

N T

IN

U

A T

IO

N

S E

E M

H

A

"ø

"ø

8"ø

8"ø

12"ø

18"ø 14"ø

10"ø4

"ø

"ø

8"ø

FCU

FCU

SFDR

SFDR

TU

8"ø

GENERAL NOTES

1. FIRE STOP PENETRATIONS OF RATED WALLS.

2. SEAL ROOF PENETRATIONS WATER TIGHT.

3. SEE MH102C FOR DIFFUSER AND GRILLE LOCATIONS IN

REFELCETED CEILING PLAN.

4. SEE MH103 FOR EQUIPMENT ON ROOF.

5. INSTALLATION OF FLEXIBLE DUCTWORK IS PROHIBITED IN

ALL PATIENT CARE AREAS AND CRITICAL SPACES WITH

AIR PRESSURIZATION REQUIREMENTS.

6. MAINTAIN MIN. 3 FT CLEARANCE FOR SERVICE ACCESS IN

FRONT OF ELECTRIC REHEAT COILS

SHEET NOTES

1 DIFFUSER WITH OPPOSED BLADE DAMPER

2 INSTALL SMOKE/FIRE DAMPER IN DUCT AT PENETRATION OF RATED

WALL, SEE DETAIL 11/M501

3 INSTALL TERMINAL UNIT IN LOCATION SHOWN, SEE DETAIL 8/M501

4 TRANSFER DUCT OVER CEILING, SIZE AS NOTED.

5 TRANSFER DUCT OVER CEILING WITH SFDR AT RATED WALL, SIZE AS

NOTED; SEE DETAIL 11/M501

6 WALL MOUNTED FAN COIL UNIT; SEE DETAIL 5/M502

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:06:54 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. KORTE

MH101C

ENLARGED MECHANICAL FLOOR PLAN

- C

K. LAWS

612-164

R. KORTE

08/10/2022

1/4" = 1'-0" MH101C

1 ENLARGED MECHANICAL FLOOR PLAN - C

NORTH

Revisions: Date:

OSOS

OS

OS

OS OS

OS OS

OS

OS

OS

OS

GENERAL NOTES

1. INSTALL THERMOSTAT AT +48" AFF.

2. SEE MH101A FOR CONTINUATION OF DUCTWORK ABOVE.

SHEET NOTES

1 TRANSFER GRILLE, RG-A

2 DIFFUSER WITH 2-WAY CORNER THROW AS INDICATED BY DIRECTIONAL

ARROWS

A B C D E F G

3.3

F.6

6.8

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

10 DENTIST

6 DENTIST

STORAGE

BARIATRIC

OPERATORY

X-RAY

RECOVERY

ORAL

SURGERY

CORRIDOR

1C02

CORRIDOR

1C03

CORRIDOR

1C04

CORRIDOR

1C01

CD-C, 8"ø

120 CFM

CD-C, 8"ø

120 CFM

RG-A, 8"ø

120 CFM

RG-A, 8"ø

120 CFM

CD-C, 8"ø

120 CFM

RG-4, 8"ø

120 CFM

CD-C, 8"ø

120 CFM

RG-A, 8"ø

120 CFM

CD-C, 8"ø

120 CFM

CD-C, 8"ø

120 CFM

CD-C, 8"ø

120 CFM

RG-A, 8"ø

120 CFM

RG-A, 8"ø

120 CFM

RG-A, 8"ø

120 CFM

RG-A, 8"ø

110 CFM

RG-A, 8"ø

110 CFM

RG-A, 8"ø

110 CFM

RG-A, 8"ø

110 CFM

CD-C, 8"ø

110 CFM

CD-C, 8"ø

110 CFM

CD-C, 8"ø

110 CFM

CD-C, 8"ø

110 CFM

CD-A, 8"ø

200 CFM

RG-A, 12"ø

400 CFM

(TYP 4)

(TYP 2)

CD-A, 8"ø

100 CFM

RG-A, 8"ø

100 CFM

RG-A, 8"ø

100 CFM

(TYP 2)

CD-A, 8"ø

100 CFM

(TYP 2)

CD-A, 8"ø

100 CFM

(TYP 6)

RG-A, 10"ø

300 CFM

(TYP 2)

RG-A, 8"ø

125 CFM

RG-A, 8"ø

125 CFM

RG-A, 8"ø

125 CFM

RG-A, 8"ø

125 CFM

RG-A, 8"ø

125 CFM

RG-A, 8"ø

125 CFM

CD-C, 8"ø

125 CFM

CD-C, 8"ø

125 CFM

CD-C, 8"ø

125 CFM

CD-C, 8"ø

125 CFM

CD-C, 8"ø

125 CFM

CD-C, 8"ø

125 CFM

CD-B, 8"ø

200 CFM

RG-A, 8"ø

200 CFM

(TYP 2)

(TYP 2)

CD-A, 8"ø

150 CFM

RG-A, 8"ø

150 CFM

CD-A, 8"ø

175 CFM

RG-A, 10"ø

350 CFM

(TYP 2)

T

T T

T

T T

T

T

T

T

T

CD-A, 8"ø

200 CFM

(TYP 4)

A R

E A

B F

O R

C O

N T

IN

U

A T

IO

N

S E

E M

H

B

TU-11

TU-14TU-13

TU-12TU-2

TU-1

TU-15

TU-16

TU-4TU-3

TU-22

CD-A, 8"ø

150 CFM

OPERATORY

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:06:57 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. KORTE

MH102A

ENLARGED MECHANICAL REFLECTED

CEILING PLAN - A

K. LAWS

612-164

R. KORTE

08/10/2022

1/4" = 1'-0" MH102A

1 OVERALL MECHANICAL REFLECTED CEILING PLAN

.E

.C

F.E.C.

OS

OS

OS

OS

OS

OS

OS

G J K ML

H

3.3

J.6

CD-B, 10"ø

250 CFM

CD-B, 10"ø

260 CFM

CB-B, 10"ø

260 CFM

CD-B, 10"ø

260 CFM

CD-C, 10"ø

300 CFM

CD-B, 10"ø

250 CFM

T

T

T

TOILETS

1037A

MECHANICAL

OPERATORY

DIRECTOR

STORAGE

NORMAL

POWER

1040B

E. POWER

1040A

CONFERENCE

LOUNGE

LABORATORY

CLEAN

TOILETS

1035A

LOCKERS

LOCKERS

CORRIDOR

1C04

EG-B, 8"ø

175 CFM

CORRIDOR

1C05

EG-B, 8"ø

100 CFM

EG-B, 8"ø

175 CFM

EG-B, 8"ø

100 CFM

RG-A, 8"ø

185 CFM

CD-C, 8"ø

185 CFM

CD-C, 8"ø

185 CFM

RG-A, 8"ø

185 CFM

TTU-5

CD-A, 8"ø

170 CFMRG-A, 8"ø

170 CFM

T

T

CD-A, 12"ø

0 CFM

CD-A, 12"ø

375 CFM

T

1-FCU-2

T

1-FCU-1

T

CD-C, 6"ø

100 CFM

RG-A, 6"ø

100 CFM

T

CORRIDOR

1C04

1-FCU-3

A R

E A

A F

O R

C O

N T

IN

U

A T

IO

N

S E

E M

H

C

AREA C

FOR CONTINUATION

SEE MH102C

2 1

TU-4

TU-19

TU-18

TU-21

TU-20

TU-6

BS

(TYP.)3

(TYP.)3

FCU

SW-A, 18"x6"

300 CFM

(TYP.4)

514"⌀

1230 CFM

EG-A, 8"ø

200 CFM

FCU

FCU

GENERAL NOTES

1. INSTALL THERMOSTAT AT +48" AFF.

2. SEE MH101B FOR CONTINUATION OF DUCTWORK ABOVE.

3. SEE MH103 FOR CONTINUATION ON ROOF PLAN.

4. FIRE STOP PIPING PENETRATIONS OF RATED WALLS.

SHEET NOTES

1 TRANSFER GRILLE, RG-A

2 TRANSFER GRILLE, RG-B

3 INSTALL REFRIGERANT PIPING OVER CEILING

4 INSTALL REFRIGERANT PIPING UP THRU ROOF

5 EXHAUST DUCT UP, SIZE AS NOTED

6 SUSPEND BS BOX OVER CEILING, FROM STRUCTURE ABOVE SEE DETAIL

2/M503

7 SUSPEND FAN-COIL UNIT FROM STRUCTURE ABOVE. SEE DETAIL 1/M503

8 DIFFUSER WITH 2-WAY CORNER THROW AS INDICATED BY DIRECTIONAL

ARROWS

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:06:59 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. KORTE

MH102B

ENLARGED MECHANICAL REFLECTED

CEILING PLAN - B

K. LAWS

612-164

R. KORTE

08/10/2022

1/4" = 1'-0" MH102B

1 MECHANICAL REFLECTED CEILING PLAN - B

.E

.C

F .E

.C

OS

OS

OS

OS

OS

OS

OS

SHEET NOTES

1 TRANSFER GRILLE, RG-A

2 DIFFUSER WITH 2-WAY CORNER THROW AS INDICATED BY DIRECTIONAL

ARROWS

4 WALL MOUNTED FAN-COIL UNIT; SEE DETAIL 5/M502

3 INSTALL REFRIGERANT PIPING OVER CEILING

GENERAL NOTES

1. INSTALL THERMOSTAT AT +48" AFF.

2. SEE MH101C FOR CONTINUATION OF DUCTWORK ABOVE.

G J K ML

H

7.7

J.6

6.8

DIRECTOR

CHIEF

WAITING

RECEPTION

1000A

HAC

FMS

ADMIN

TOILET

1000B

TOILET

1000C

OIT

DIRTY

F.R.

CORRIDOR

1C06

CORRIDOR

1C05

CORRIDOR

1C07

CORRIDOR

1C04

CD-A, 8"ø

150 CFM

(TYP 3)

EG-B, 6"ø

100 CFM

EG-B, 6"ø

100 CFM

EG-A, 8"ø

200 CFM

CD-C, 8"ø

150 CFM

RG-A, 8"ø

150 CFM

EG-A, 10"ø

300 CFM

RG-A, 8"ø

150 CFM

CD-C, 8"ø

150 CFM

CD-C, 8"ø

150 CFM

RG-A, 8"ø

150 CFM

T

T

T

T

T

T

AREA B

FOR CONTINUATION

SEE MH102B

A R

E A

A F

O R

C O

N T

IN

U

A T

IO

N

S E

E M

H

A

T

TU-9

TU-7

TU-17

TU-21

1-FCU-5

1-FCU-4

TU-10

FCU

FCU

C D

-A

"ø

C

F M

RG-A, 10"ø

225 CFM

RG-A, 10"ø

225 CFM

CD-D, 8"ø

175 CFM

RG-A, 12"ø

500 CFM

RG-A, 12"ø

500 CFM

CD-D, 8"ø

175 CFM

CD-D, 8"ø

170 CFM

(TYP. 5)

T

TU-8

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:03 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. KORTE

MH102C

ENLARGED MECHANICAL REFLECTED

CEILING PLAN - C

K. LAWS

612-164

R. KORTE

08/10/2022

1/4" = 1'-0" MH102C

1 MECHANICAL REFLECTED CEILING PLAN - C

DN

A B C D E F G J K ML

H

3.3

F.6

7.7

J.6

RIDGE

S L

O P

E

6.8

S L O

P E

S L

O P

E S

L O

P E

S L

O P

E S

L O

P E

S L

O P

E

S L

O P

E

S L

O P

E

S L

O P

E

S L O

P E

RIDGE RIDGE

S L

O P

E

RTU

CU

CU

CU

EF

EF

EF

8"ø

43"x43"

DUCT THRU ROOF

55"x24"

DUCT THRU ROOF

DUCT THRU ROOF

14"ø DUCT THRU ROOF

16"x16"

DUCT THRU ROOF

ROOF

ACCESS

(TYP.)

3 7

4 9

4 9

4 10

3 8

OSA

GENERAL NOTES

1. SEAL ROOF PENTRATIONS WATER TIGHT.

2. SEE MH101 FOR CONTINUATION OF DUCTWORK BELOW.

3. MAINTAIN MIN. 25 FEET BETWEEN OUTSIDE AIR INTAKES AND VENTS

AND EXHAUST DISCHARGES

SHEET NOTES

1 HVAC UNIT MOUNTED ON ROOF CURB, SEE DETAIL 1/M502

2 EXHAUST FAN MOUNTED ON ROOF CURB, SEE DETAIL 2/M502

3 EXHAUST FAN MOUNTED ON ROOF PLATFORM WITH DISCHARGE STACK,

SEE DETAILS 3/M502 AND 4/M502

4 CONDENSING UNIT MOUNTED ON ROOF PLATFORM, SEE DETAIL 6/M502

5 ROUND DUCT UP THRU ROOF,SEAL WATER TIGHT, SEE DETAIL 7/M502

6 REFRIGERANT PIPING UP THRU ROOF,SEAL WATER TIGHT, SEE DETAIL

8/M502 AND 10/M502 FOR SUPPORT

7 MOUNT EXHAUST FAN ON 4'-6" x 3'-0" ROOF PLATFORM, SEE DETAIL 4/M502

8 MOUNT EXHAUST FAN ON 4'-0" x 3'-0" ROOF PLATFORM, SEE DETAIL 4/M502

9 MOUNT CONDENSING UNIT ON 4'-0" x 2'-0" ROOF PLATFORM, SEE DETAIL 4/M502

10 MOUNT CONDENSING UNIT ON 4'-0" x 3'-6" ROOF PLATFORM, SEE DETAIL 4/M502

1/8" = 1'-0" MH103

1 MECHANICAL ROOF PLAN

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:06 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. BLAYLOCK

MH103

MECHANICAL ROOF PLAN

K. LAWS

612-164

R. BLAYLOCK

08/10/2022

RECEPTACLE SHALL BE MOUNTED 18" ON CENTER AFF, AND SWITCHES AND WALL

OCCUPANCY SWITCHES SHALL BE MOUNTED 48" ON CENTER AFF, UNLESS

OTHERWISE NOTED

RECEPTACLE, TELECOMMUNICATION OUTLET AND SWITCH SUFFIX OF:

-A MOUNTED ±6" ABOVE COUNTERTOP OR BACKSPLASH.

-B MOUNTED ±6" FROM THE EDGE OF THE SINK TOP AND ±40" AFF OR

±6" ABOVE THE EDGE OF THE SINK TOP

-C MOUNTED ON CEILING

-F MOUNTED ON FLOOR / SUB CONSOLE OF CABINET

-W MOUNTED 48" AFF

-H MOUNTED ±12" BELOW CEILING LINE

-S SURFACE MOUNTED

GFCI GROUND FAULT CIRCUIT INTERRUPTER

SC SAFETY TYPE (TAMPER RESISTANT)

WP WEATHER PROTECTED (NEMA 3R) ENCLOSURE

PHASE CONDUCTOR

NEUTRALGROUND

IDENTIFIES PANEL AND CIRCUIT NUMBER(S). HASH MARKS INDICATES NUMBER

A, B, C INDICATES SEPARATE CONTROL OF CIRCUITS AS DESIGNATED

5-20R, GROUNDING TYPE - EMERGENCY POWER

DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING

TYPE WITH GROUND FAULT CIRCUIT INTERRUPTER (GFCI) - EMERGENCY POWER

DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING

QUADRAFLEX-RECEPTACLE (DOUBLE DUPLEX), NEMA 5-20R,

GROUNDING TYPE WITH GROUND FAULT CIRCUIT INTERRUPTER - EMERGENCY POWER

QUADRAFLEX-RECEPTACLE (DOUBLE DUPLEX), NEMA

QUADRAFLEX-RECEPTACLE (DOUBLE DUPLEX), NEMA

ELECTRIC PANELBOARD, FLUSH MOUNTED

ELECTRIC PANELBOARD, SURFACE MOUNTED

SWITCH, 20A, 1 POLE, 120/277 V, UNLESS OTHERWISE INDICATED

OF PHASE, NEUTRAL AND GREEN GROUND WIRES

BRANCH CIRCUIT HOMERUN TO PANELBOARD; LETTER AND NUMBER NOTATION

CONDUIT OR WIRE RUN EXPOSED OR ABOVE THE CEILING

5-20R, GROUNDING TYPE WITH GROUND FAULT CIRCUIT INTERRUPTER

QUAD-RECEPTACLE (DOUBLE DUPLEX), NEMA

DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING

TYPE WITH GROUND FAULT CIRCUIT INTERRUPTER (GFCI)

DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING TYPE

D DIMMER

4 4 WAY SWITCH

3 3 WAY SWITCH

DISCONNECT SWITCH, UNFUSED

SP SPEAKER-PUBLIC ADDRESS/PAGING

GENERAL NOTES

SUFFIX OF:

THERMOSTAT

ELECTRICAL DISTRIBUTION PANEL

T

EP

TYPE - EMERGENCY POWER

GFCI

A-1,3

GFCI

5-20R, GROUNDING TYPE

JUNCTION BOX

GFCI

GFCI

J J

CURRENT TRANSFORMER

POWERPWR

GROUND FAULT CIRCUIT-INTERRUPTER

NOT APPLICABLEN/A

GFP GROUND FAULT PROTECTION

GOVERNMENT

MECHANICAL

LOCATION

KILOVOLT

MAXIMUM

GREEN

HAND-OFF-AUTOMATIC

HERTZ

KILOWATT

KILO-AMPERES

HEIGHT

LIGHT

KILOVOLT-AMPERE

JUNCTION BOX

GROUND

LOC

MECH'L

MAX

LTG

KV

KW

KA

KVA

H-O-A

J.B.

Hz

HT

GRN

GOV

GND

FLOOR

COPPER

ELEVATION

ELECTRIC

DRAWING

DISCONNECT

DISTRIBUTION

EQUIPMENT

FOOT, FEET

EXISTING

FLOOD

GALVANIZED

FULL LOAD AMPS

ELECTRICAL METALLIC TUBING

EQUIP

EXIST/(E)

FLD

GALV

GFCI

FLR

FT

FLA

ELECT

DWG

EMT

ELEV

DIST

DISC

CT

CU

SHIELDED TWISTED WIRE PAIR

MOUNTING HEIGHT ABOVE FINISHED+12"A.F.F.

Ø

WT

XFMR

WP

W

V

VA

UON

FLOOR OR GRADE

PHASE

UNLESS OTHERWISE NOTED

WEATHERPROOF

WIRE TROUGH

TRANSFORMER

WIRE

VOLT AMPS

VOLT

STP

U/G

UL

UBC

TYP

TBD

TEMP

TERM

TV

SWBD

SW

ST

RECEPT

RGS

RPS

UNDERWRITERS LABORATORIES

UNIFORM BUILDING CODE

UNDERGROUND

TYPICAL

TO BE DETERMINED

TERMINAL

TEMPORARY

TELEVISION

RIGID GALVANIZED STEEL

SWITCHBOARD

SWITCH

STREET

RECEPTACLE

REMOTE POWER SUPPLY

CONTRACTING OFFICER REPRESENTATIVE

ELECTRICAL ABBREVIATIONS

AMERICAN NATIONAL STANDARDS INSTITUTE

COMMUNICATION

CATALOG

CEILING

CONDUIT

CIRCUIT

CONNECTED

CIRCUIT BREAKER

AMPERE

AMPS INTERRUPTING CAPACITY

BUILDING

BARE COPPER

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

COMM

CONN

CLG

COR

CKT

C

CAT

C.B.

BLDG

A/AMP

AWG

B.C.

AIC

ANSI

AFF

2.

1.

MANUFACTURERS ASSOCIATION

PNL

PRI

PVC

PH

PR

PA

P

O.L.

NEMA

NF

NTS

NO.

NEC

PUBLIC ADDRESS

POLYVINYL CHLORIDE

PANEL

PRIMARY

PHASE

PAIR

OVERLOAD

POLE

NATIONAL ELECTRICAL

NOT TO SCALE

NATIONAL ELECTRICAL CODE

NON-FUSED

NUMBER

1. PENETRATION OF CONDUITS, RACEWAYS AND WIRING THROUGH FIRE RATED WALLS, FLOOR AND CEILINGS SHALL BE FIRE-STOPPED IN ACCORDANCE WITH SPECIFICATION SECTION 07 84 00. FIRE

STOPPING MATERIALS AND METHODS SHALL BE A U.L. LISTED ASSEMBLY.

2. METHODS AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). EQUIPMENT SHALL BE IN ACCORDANCE WITH THE STANDARDS OF NEMA AND ANSI. EQUIPMENT SHALL BE NEW AND LISTED BY U.L. AND INSTALLED IN ACCORDANCE WITH

THE CONDITIONS STATED IN THAT LISTING.

3. BEFORE ENERGIZING, EQUIPMENT SHALL BE TESTED TO BE FREE OF GROUNDS AND SHORTS.

4. RECEPTACLES, OUTLETS, SWITCHES, DISCONNECT, CONDUITS AND JUNCTION BOXES (ABOVE AND

BELOW CEILING) SHALL BE PERMANENTLY MARKED AS TO INDICATE THE CIRCUIT NUMBER AND

SOURCE PANELBOARD. PERMANENT MARKING FOR BELOW THE CEILING DEVICES SHALL BE CLEAR 3/8" WIDE STICK-ON LABEL WITH BLACK LETTERING. PERMANENT MARKING FOR ABOVE THE CEILING

DEVICES MAY BE HAND LABELED WITH PERMANENT MARKER.

5. UNLESS OTHERWISE INDICATED, POWER AND LIGHTING CONDUCTORS SHALL BE TYPE THHN/THWN-2, 600 VOLT, 90°C, SOLID OR STRANDED COPPER IN ACCORDANCE WITH SPECIFICATIONS 26 05 19, AND NOT

SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS AND #14 AWG FOR CONTROL

CIRCUITS.

6. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED IN STRICT ACCORDANCE WITH THE LATEST

EDITION OF NATIONAL ELECTRIC CODE (NEC). PROVIDE EQUIPMENT GROUNDING CONDUCTORS.

CONDUIT CANNOT BE USED AS THE ONLY MEANS OF GROUNDING.

7. FIXTURES AND EQUIPMENT SHALL BE SUPPORTED/MOUNTED TO COMPLY WITH THE SEISMIC

REQUIREMENTS OF THE IBC AND ASCE 7.

8. CONDUIT CONNECTIONS TO MOTORS AND LIGHTING FIXTURES SHALL BE MADE WITH FLEXIBLE

METAL OR LIQUID TIGHT FLEXIBLE CONDUIT NOT MORE THAN 2 FEET LONG.

9. MECHANICAL ELECTRICALLY OPERATED EQUIPMENT SHALL BE PROVIDED WITH "WITHIN SIGHT"

PADLOCKABLE DISCONNECTING SWITCH CONSISTING OF HORSEPOWER RATED SWITCH, MOLDED

CASE CIRCUIT BREAKER OR TOGGLE SWITCH, IN ACCORDANCE WITH NEC. OUT OF SIGHT

LOCKABLE DISCONNECTING DEVICES ARE NOT ACCEPTABLE TO MEET THIS REQUIREMENT.

10. CONTRACTOR SHALL COORDINATE ELECTRICAL WORK WITH OTHER TRADES.

11. LABEL AND IDENTIFY ALL PANEL SCHEDULES.

12. PROVIDE DEDICATED NEUTRAL ON EACH NEW 120V AND 277V CIRCUITS.

13. ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH SPECIFICATION 26 05 33. CONDUITS

SHALL RUN ABOVE THE CEILING OR BEHIND THE FINISH WALL, UNLESS OTHERWISE NOTED.

14. "PROVIDE" MEANS "FURNISH AND INSTALL".

15. ALL ELECTRICAL CONSTRUCTION WORK, METHODS AND MATERIALS SHALL BE IN COMPLIANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) AND APPLICABLE GOVERNMENT

AND VETERANS ADMINISTRATION RULES AND REGULATIONS.

16. ROUTE ALL TELECOMMUNICATION CIRCUITS 18" MINIMUM APART FROM ELECTRICAL CIRCUITS. IN

LOCATIONS WHERE MINIMUM SEPARATION CAN NOT BE OBTAINED, WRAP TELECOMMUNICATION

CIRCUITS WITH GROUNDED METALLIC SHEET TO REDUCE NOISE INTERFERENCE.

17. ALL TELECOMMUNICATION WIRES SHALL BE SUPPORTED BY HANGERS OR WIRE TRAYS. WIRES LAID

ON SUSPENDED CEILING IS PROHIBITED.

18.

19.

20.

ALL ABOVE CEILING RACEWAYS, OUTLETS, J.B's AND PULL BOXES SHALL BE HUNG ON THE CHANNELS OF CEILING CONSTRUCTION,TO THE STRUCTURAL MEMBERS, OR RUNS ALONG STRUCTURAL. WALL MOUNTING

IS NOT PERMITTED.

PROVIDE ADDITIONAL ACCESS PANEL, AS REQUIRED, ON GYPSUM BOARD/HARD CEILING FOR ELECTRICAL

DEVICES, EQUIPMENT, JUNCTION BOXES, ETC. ACCESS.

MINIMUM SIZE OF CONDUITS SHALL BE 3/4" UNLESS OTHERWISE NOTED.

ELEC'L ELECTRICAL

CO CONTRACTING OFFICER

HATCHED GRAY THIN LINE INDICATES DEMOLISH PER DRAWING NOTES

DETAIL NUMBER

DRAWING NUMBER ON WHICH DETAIL IS DRAWN

NOTE REFERENCE

PS POWER SUPPLY

BOLD LINE INDICATES NEW WORK

CONDUIT OR WIRE RUN UNDERGROUND

INTERNATIONAL BUILDING CODEIBC

TELECOM TELECOMMUNICATION

VFD VARIABLE FREQUENCY DRIVE

OS OCCUPANCY SENSOR - CEILING MOUNTED

OCCUPANCY WALL SWITCH - WALL MOUNTEDOS

PUSHBUTTON

VAMC VETERANS AFFAIRS MEDICAL CENTER

RECEPTACLE, NEMA 6-20R, OR 6-30R 250V (GROUNDING TYPE)

RECEPTACLE, NEMA 6-20R, 250V (GROUNDING TYPE) - EMERGENCY POWER

RECEPTACLE, NEMA L6-20R, 250V TWIST LOCK

(GROUNDING TYPE) - EMERGENCY POWER

CEILING RECESSED LIGHTING FIXTURE (TYP.) LETTER IN LIGHT FIXTURE DESIGNATES

FIXTURE TYPE. SEE LIGHTING FIXTURE SCHEDULE FOR DETAILS.

GRAY THIN LINE INDICATES EXISTING WORK

SP

MOTION DETECTOR

SUFFIX 'P' INDICATES ADDITIONAL AMBIENT LIGHT CONTROL FEATURE

SUFFIX OF:

P INDICATES ADDITIONAL AMBIENT LIGHT CONTROL FEATURE

F 360° COVERFACE

H 180° COVERFACE

T TRANSFORMER

XX###

RM ROOM

LEGEND LEGEND

ELECTRICAL STRIP MOLD OUTLETS

SURFACE MOUNTED CEILING STRIP LIGHT

SUSPENDED STRIP LIGHT

EXIT SIGN

X

X

X

X

X CEILING RECESSED LIGHTING FIXTURE ON EMERGENCY POWER (TYP.)

P PHOTOCELL; NEMA 3R ENCLOSURE

UTP UNSHIELDED TWISTED PAIR

RECESSED DOWNLIGHT

L

SCHED SCHEDULE

MAIN LUG ONLYMLO

X - DESIGNATE 6-20R Y - DESIGNATE 6-30R

20A, 2P, 3 WIRE, 250V GROUNDING, FLUSH MOUNTED,

TWIST LOCK RECEPTACLE

VACANCY SWITCH - WALL MOUNTEDVS

X

X

XX WALL MOUNTED LIGHT FIXTURE

OPERATORY TRACK LIGHT

NEW/(N) NEW

(R) RELOCATE

ENCLOSED CIRCUIT BREAKERCB

TOP MOUNTEDT

1 FACE1

2 FACES2

CALL FOR ASSISTANCE PULL CORDCA

CA CALL FOR ASSISTANCE HORN/STROBE

MISCELLANEOUS

MINIMUM

MOUNTING

MOUNTEDMTD

MTG

MISC

MIN

SFDR SMOKE/FIRE DAMPER

S T

A

T E

O F CA L I FOR N

I A

EXP.________

E 17641 9-30-2023

R

EG

IS

TE

RED

PROFESS IONAL

ENG

INE

ERA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:08 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. BLAYLOCK

E001

GENERAL NOTES, LEGEND AND

ABBREVIATIONS

G. FERNANDEZ

612-164

R. BLAYLOCK

08/10/2022

.E

.C

F.E.C.

F .E

.C

F .E

.C

F.E.C.

F .E

.C

OSOS

OS

OS

OS OS

OS OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

A B C D E F G J K ML

H

3.3

F.6

7.7

J.6

6.8

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

O P

E R

A T

O R

Y

O P

E R

A T

O R

Y

O P

E R

A T

O R

Y

O P

E R

A T

O R

Y

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

DIRECTOR

CHIEF

WAITING

RECEPTION

1000A

10 DENTIST

6 DENTIST

STORAGE

BARIATRIC

OPERATORY

X-RAY

RECOVERY

ORAL

SURGERY

STORAGE

NORMAL

POWER

1040B

E. POWER

1040A

MECHANICAL

CONFERENCE

LOUNGE

LABORATORY

TOILETS

1037A

CLEAN

TOILETS

1035A

HAC

FMS

ADMIN

TOILET

1000B

TOILET

1000C

OIT

DIRTY

F.R.

LOCKERS

LOCKERS

CORRIDOR

1C02

CORRIDOR

1C03

CORRIDOR

1C04

CORRIDOR

1C01

OPERATORY

EL101C

EL101B

EL101A

PLAN - A

PLAN - B

PLAN - C

GENERAL NOTES

1. WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING

FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FIXTURE

SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND APPEARANCE

SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN ON FIXTURE

SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO COR OR VAMC

REPRESENTATIVE FOR APPROVAL.

2. PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURE,

WHENEVER POSSIBLE.

3. SEE SHEETS EL101A, EL101B, & EL101C FOR A MORE DETAILED AND

ENLARGED DRAWING.

1/8" = 1'-0" EL101

1 ELECTRICAL LIGHTING PLAN

S T

A

T E

O F CA L I FOR N

I A

EXP.________

E 17641 9-30-2023

R

EG

IS

TE

RED

PROFESS IONAL

ENG

INE

ERA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:11 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. BLAYLOCK

EL101

ELECTRICAL LIGHTING PLAN

G. FERNANDEZ

612-164

R. BLAYLOCK

08/10/2022

.E

.C

F.E.C.

F .E

.C

F .E

.C

VS VS

VS VS

VS VS

VS VS

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

OSOS

OS

OS

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

VS VSVSVS

V S

V S

OS OS

VS

V S

V S

V S

VS

V S

V S

VS VS

OS OS

OS

OS

OS

V S

OS

V S

A B C D E F G

3.3

F.6

6.8

T1

T1

T1

T1

T1

T2

A R

E A

B F

O R

C O

N T

IN

U

A T

IO

N

S E

E E

L

B

A

A

A

A

A

A

A

A

J D D

J

J

D D

D D

D D

TRACK DENTAL

LIGHT (TYP)

B

A A A A A A A A A A A A A

JJJ

B B B B

B

B

B

BBBBBB

B

B

B

B

B

C

C

C

C

A

A

A

A

D D

D D

D D

D D D

D D D

D D

A A A A A A A A A A A A

D D

D D

D D

D D

D D

D D

A A

C C

C

C

D D

D D

E E

E

EEE

E E E

EEE

E EEEE

E E E E E

EEEEE

D D

D D

D D

D

J J J

J

D

OPERATORY

OPERATORY

1005OPERATORY

OPERATORY

OPERATORY

O P

E R

A T

O R

Y

O P

E R

A T

O R

Y

O P

E R

A T

O R

Y

O P

E R

A T

O R

Y

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

OPERATORY

10 DENTIST

6 DENTIST

STORAGE

BARIATRIC

OPERATORY

X-RAY

RECOVERY

ORAL

SURGERY

CORRIDOR

1C02

CORRIDOR

1C03

CORRIDOR

1C04

CORRIDOR

1C01

LSH1 - 2

CH1 - 1

NH1 - 1

CH1 - 1

LSH1 - 2

LSH1 - 1

NH1 - 2

LSH1 - 1

NH1 - 2

LSH1 - 1

CH1 - 5NH1 - 2

CH1 - 5NH1 - 2CH1 - 5NH1 - 2CH1 - 5NH1 - 2CH1 - 5NH1 - 2CH1 - 5NH1 - 2

LSH1 - 1

CH1 - 5

NH1 - 2

NH1 - 5

NH1 - 5

LSH1 - 2

NH1 - 1

CH1 - 1

LSH1 - 2

NH1 - 1

NH1 - 1

CH1 - 1

LSH1 - 1

NH1 - 1

CH1 - 1

NH1 - 1

CH1 - 1

NH1 - 2 NH1 - 2

NH1 - 2

CH1 - 1

NH1 - 2

NH1 - 1

NH1 - 1

NH1 - 1CH1 - 1

NH1 - 1

LSH1 - 1

LSH1 - 2

LSH1 - 2

CH1 - 1

NH1 - 1

NH1 - 5

LSH1 - 2

NH1 - 1

CH1 - 1

NH1 - 1

CH1 - 1

NH1 - 1

LSH1 - 1

CH1 - 1

NH1 - 1

CH1 - 1

NH1 - 1

NH1 - 1

NH1 - 1 NH1 - 1 NH1 - 1

NH1 - 1 CH1 - 1 NH1 - 1 NH1 - 1

NH1 - 1

NH1 - 1

NH1 - 1

CH1 - 5

NH1 - 2

CH1 - 5 CH1 - 5

CH1 - 5CH1 - 5

NH1 - 2NH1 - 2

NH1 - 2NH1 - 2

LSH1 - 1

NH1 - 2

NH1 - 2

NH1 - 2NH1 - 2

NH1 - 5 NH1 - 5

NH1 - 5

NH1 - 1 NH1 - 1

NH1 - 2 NH1 - 2

NH1 - 2

LSH1 - 2LSH1 - 2

CH1 - 1

B

D D

OPERATORY

LSH1 - 2

2' x 2' ACT System

AREA C

FOR CONTINUATION SEE

EL101C

CH1 - 2

LSH1 - 2 J

PNL NH1, CKT. 1,2

4#10 & 1#10 GND

3/4" C

PNL CH1, CKT. 1,5

4#10 & 1#10 GND

3/4" C

C

D D

1. FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES IS

NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE

EQUIPMENT IS SHOWN. CONTRACTOR SHALL PROVIDE AND INSTALL

BRANCH FEEDER CONDUITS, OUTLET BOXES, WIRE AND JUNCTION

BOXES FOR NEW WIRING INSTALLATION. CONTRACTOR SHALL PROVIDE

CONDUITS AND WIRES MEETING NEC AND VAMC REQUIREMENTS.

TYPICAL HOMERUN IS 6 AWG #10 AND 1 AWG #10 GND (GREEN) IN 3/4" C,

UNLESS OTHERWISE NOTED.

2. LIGHT SWITCHES AND OCCUPANCY / VACANCY SWITCH MOUNTED 48"

AFF, UNLESS OTHERWISE NOTED.

GENERAL NOTES

3. OCCUPANCY SENSOR QUANTITY AND LOCATION SHOWN IS FOR

REFERENCE ONLY. PROVIDE OCCUPANCY SENSORS TO COMPLETELY

COVER THE AREA WHERE OCCUPANCY SENSORS ARE INSTALLED.

5. WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING

FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FISTURE

SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND APPEARANCE

SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN ON FIXTURE

SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO COR OR VAMC

REPRESENTATIVE FOR APPROVAL.

6. PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURE,

WHENEVER POSSIBLE.

4. OCCUPANCY SENSORS AND OCCUPANCY / VACANCY SWITCH SHALL BE

DUAL TECHNOLOGY TYPE, UNLESS OTHERWISE NOTED.

S T

A

T E

O F CA L I FOR N

I A

EXP.________

E 17641 9-30-2023

R

EG

IS

TE

RED

PROFESS IONAL

ENG

INE

ERA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:16 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. BLAYLOCK

EL101A

ELECTRICAL ENLARGED LIGHTING

PLAN-A

G. FERNANDEZ

612-164

R. BLAYLOCK

08/10/2022

1/4" = 1'-0" EL101A

1 ELECTRICAL ENLARGED LIGHTING PLAN-A NORTH

.E

.C

F.E.C.

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

V S

VS VS

VS VS

V S

V S

VS

OS

OS

V S

OS

V S

OS

OS

OS

OS

G J K ML

H

3.3

J.6

T2

T1

AREA C

FOR CONTINUATION

SEE EL101C

A R

E A

A F

O R

C O

N T

IN

U

A T

IO

N

S E

E E

L

A

J J

J

J

J

J

A

A A A

AAA

A A A

A

B

B

B

B

B B B B B

B

C

C

C

C

C

CC

C

CCC

C

C

D

D D

D D

PNL NH1, CKT 5

2#12 & 1#12 GND

3/4"C

STORAGE

NORMAL

POWER

1040B

E. POWER

1040A

MECHANICAL

CONFERENCE

LOUNGE

LABORATORY

TOILETS

1037A

CLEAN

TOILETS

1035A

LOCKERS

LOCKERS

CORRIDOR

1C04

NH1 - 5

LSH1 - 2

LSH1 - 2

NH1 - 3

NH1 - 3

NH1 - 3

NH1 - 3

NH1 - 3

NH1 - 3

NH1 - 3NH1 - 3

NH1 - 2

NH1 - 2 NH1 - 3

CH1 - 3

CH1 - 3

CH1 - 3

NH1 - 3

NH1 - 3

NH1 - 3

CH1 - 3

NH1 - 3

NH1 - 3

LSH1 - 1

NH1 - 3NH1 - 3NH1 - 3

NH1 - 3 NH1 - 3

LSH1 - 2

LSH1 - 2

LSH1 - 2

LSH1 - 2

LSH1 - 2

LSH1 - 2

NH1 - 3

NH1 - 3 NH1 - 3

NH1 - 3

CH1 - 3

CH1 - 3

CH1 - 3

LSH1 - 2

CH1 - 3

CH1 - 3

CH1 - 3

CH1 - 3

CH1 - 3

H

H

H

H H

H

CH1 - 3 CH1 - 3

CH1 - 3CH1 - 3

E

E E

E

F

F

F

PNL NH1, CKT 3, 4

2#12 & 1#12 GND

3/4"C

PNL CH1, CKT 3, 4

4#10 & 1#10 (GND)

3/4"C

PNL LSH1, CKT 1, 2

4#10 & 1#10 (GND)

3/4"C

G

G

G

G

G

G

G

G

NH1 - 3

B

CH1 - 3

CH1 - 3

CH1 - 3

1 (TYP)

CH1 - 3

C

3 3

1. FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES IS

NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE

EQUIPMENT IS SHOWN. CONTRACTOR SHALL PROVIDE AND INSTALL

BRANCH FEEDER CONDUITS, OUTLET BOXES, WIRE AND JUNCTION

BOXES FOR NEW WIRING INSTALLATION. CONTRACTOR SHALL PROVIDE

CONDUITS AND WIRES MEETING NEC AND VAMC REQUIREMENTS.

TYPICAL HOMERUN IS 6 AWG #10 AND 1 AWG #10 GND (GREEN) IN 3/4" C,

UNLESS OTHERWISE NOTED.

2. LIGHT SWITCHES AND OCCUPANCY / VACANCY SWITCH MOUNTED 48"

AFF, UNLESS OTHERWISE NOTED.

GENERAL NOTES

3. OCCUPANCY SENSOR QUANTITY AND LOCATION SHOWN IS FOR

REFERENCE ONLY. PROVIDE OCCUPANCY SENSORS TO COMPLETELY

COVER THE AREA WHERE OCCUPANCY SENSORS ARE INSTALLED.

4. OCCUPANCY SENSORS AND OCCUPANCY / VACANCY SWITCH SHALL BE

DUAL TECHNOLOGY TYPE, UNLESS OTHERWISE NOTED.

5. WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING

FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FISTURE

SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND APPEARANCE

SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN ON FIXTURE

SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO COR OR VAMC

REPRESENTATIVE FOR APPROVAL.

6. PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURE,

WHENEVER POSSIBLE.

1 MOUNTED ±9' AFF

SHEET NOTES

S T

A

T E

O F CA L I FOR N

I A

EXP.________

E 17641 9-30-2023

R

EG

IS

TE

RED

PROFESS IONAL

ENG

INE

ERA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:17 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. BLAYLOCK

EL101B

ELECTRICAL ENLARGED LIGHTING

PLAN-B

G. FERNANDEZ

612-164

R. BLAYLOCK

08/10/2022

1/4" = 1'-0" EL101B

1 ELECTRICAL ENLARGED LIGHTING PLAN-B NORTH

.E

.C

F .E

.C

VS VS

V S

V S

VS

VS

VS

V S

V S

OS

OS

OS

OS

OS

OS

G J K ML

H

7.7

J.6

6.8

T2

AREA B

FOR CONTINUATION

SEE EL101BA

R E

A A

F O

R C

O N

T

IN

U A

T

IO

N S

E E

E L

A

A R

E A

A F

O R

C O

N T

IN

U

A T

IO

N

S E

E E

L

A

B B B

B

B B

NH1 - 3

B

B B B B

B

B

C C

C

C

CH1 - 4

C

D D

D

D

D

D

D

I

I I

I

TO PHOTOCELL SWITCH A

MOUNTED ON THE ROOF

2#12 & 1#12 GND

3/4"C

OPERATORY

DIRECTOR

CHIEF

WAITING

RECEPTION

1000A

HAC

FMS

ADMIN

TOILET

1000B

TOILET

1000C

OIT

DIRTY

F.R.

3 3

NH1 - 5

CH1 - 4

NH1 - 4

CH1 - 4

NH1 - 4

NH1 - 4

CH1 - 4

NH1 - 4

NH1 - 4 NH1 - 4

NH1 - 4

E

NH1 - 4 NH1 - 4 NH1 - 4 NH1 - 4

NH1 - 5

LSH1 - 2

NH1 - 5

LSH1 - 2

LSH1 - 2

CH1 - 4 CH1 - 4

CH1 - 4

CH1 - 4

NH1-4

NH1 - 4

NH1 - 4

NH1 - 4

NH1 - 4

NH1 - 4

LSH1 - 1

NH1 - 3

LSH1 - 1

NH1 - 4 NH1 - 4

B

NH1 - 3

LSH1 - 1NH1 - 3

NH1 - 4NH1 - 4

LSH1 - 1

NH1 - 2

LSH1 - 1

NH1 - 4 CH1 - 4 CH1 - 4 NH1 - 4

NH1-4

NH1-4

NH1-4

CH1 - 4

C C

C

LSH1 - 2

LSH1 - 2

C

C

C

J

J

J

J

NH1 - 4

F

H H

G G G

G

G

G G

G

G

G

G G G G

CH1 - 4 CH1 - 4

CH1 - 4

H

LSH1 - 1

F

CH1 - 4

E E

E E

1 (TYP)

2 (TYP)

LSH1 - 2 LSH1 - 2

G G

TO PHOTOCELL SWITCH B

MOUNTED ON THE ROOF

2#12 & 1#12 GND

3/4"C

2 (TYP)

LSH1-2

1. FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES IS

NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE

EQUIPMENT IS SHOWN. CONTRACTOR SHALL PROVIDE AND INSTALL

BRANCH FEEDER CONDUITS, OUTLET BOXES, WIRE AND JUNCTION

BOXES FOR NEW WIRING INSTALLATION. CONTRACTOR SHALL PROVIDE

CONDUITS AND WIRES MEETING NEC AND VAMC REQUIREMENTS.

TYPICAL HOMERUN IS 6 AWG #10 AND 1 AWG #10 GND (GREEN) IN 3/4" C,

UNLESS OTHERWISE NOTED.

2. LIGHT SWITCHES AND OCCUPANCY / VACANCY SWITCH MOUNTED 48"

AFF, UNLESS OTHERWISE NOTED.

GENERAL NOTES

3. OCCUPANCY SENSOR QUANTITY AND LOCATION SHOWN IS FOR

REFERENCE ONLY. PROVIDE OCCUPANCY SENSORS TO COMPLETELY

COVER THE AREA WHERE OCCUPANCY SENSORS ARE INSTALLED.

4. OCCUPANCY SENSORS AND OCCUPANCY / VACANCY SWITCH SHALL BE

DUAL TECHNOLOGY TYPE, UNLESS OTHERWISE NOTED.

5. WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING

FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FISTURE

SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND APPEARANCE

SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN ON FIXTURE

SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO COR OR VAMC

REPRESENTATIVE FOR APPROVAL.

6. PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURE,

WHENEVER POSSIBLE.

SHEET NOTES

1 PROVIDE PERIMETER LIGHT WITH INTEGRATED PHOTOCELL.

2 FIXTURE MOUNTING SEE DRAWING AE505

S T

A

T E

O F CA L I FOR N

I A

EXP.________

E 17641 9-30-2023

R

EG

IS

TE

RED

PROFESS IONAL

ENG

INE

ERA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:21 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. BLAYLOCK

EL101C

ELECTRICAL ENLARGED LIGHTING

PLAN-C

G. FERNANDEZ

612-164

R. BLAYLOCK

08/10/2022

1/4" = 1'-0" EL101C

1 ELECTRICAL ENLARGED LIGHTING PLAN-C NORTH

DN

A B C D E F G J K ML

H

3.3

F.6

7.7

J.6

6.8

1 1 1 1

2 2

PNL NH1, CKT, 6

2#12 & 1#12 GND (GREEN)

3/4"C

WP

NH1 - 6

NH1 - 6

NH1 - 6

NH1 - 6NH1 - 6NH1 - 6NH1 - 6

NH1 - 6

NH1 - 6

NH1 - 6

NH1 - 6

K

K

K K K K

K

K K

K

J

5 PHOTOCELL SWITCH A

PHOTOCELL SWITCH B

1. ALL OUTDOOR ELECTRICAL CONDUITS SHALL BE RIGID STEEL

CONDUITS.

2. ALL OUTDOOR ELECTRICAL EQUIPMENT SHALL BE IN NEMA 3R

ENCLOSURES, UNLESS OTHERWISE NOTED.

GENERAL NOTES

SHEET NOTES

1 MOUNTED ON TOP OF MECHANICAL SCREEN FRAME. PROVIDE

MOUNTING BRACKET.

2 MOUNT ±6" BELOW TOP OF WALL. PROVIDE WALL MOUNTING BRACKET.

3 PROVIDE WEATHER PROTECT COVER. MOUNT SWITCH ±48" AFF

4 MOUNT ±6" BELOW TOP OF WALL. PHOTOCELL NOT NEEDED.

5 PROVIDE PHOTOCELL FOR LIGHTS ON THE PORTICO. PHOTOCELL IS TO

FACE NORTH

S T

A

T E

O F CA L I FOR N

I A

EXP.________

E 17641 9-30-2023

R

EG

IS

TE

RED

PROFESS IONAL

ENG

INE

ERA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:23 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. BLAYLOCK

EL102

ELECTRICAL ROOF LIGHTING PLAN

G. FERNANDEZ

612-164

R. BLAYLOCK

08/10/2022

1/8" = 1'-0" EL102

1 ELECTRICAL ROOF LIGHTING PLAN

LIGHTING FIXTURE SCHEDULE

FIXTURE SYMBOL

FIXTURE

DESIGNATION

DESCRIPTION AND MANUFACTURER LAMP

INPUT WATT W/

DRIVER

FIXTURE

MOUNTING

FIXTURE LOCATION REMARKS

A

LED, 4900 LUMENS MINIMUM, 2'-0" X 4'-0" RECESSED TROFFER, LED ELECTRONIC DIMMING DRIVER, 5000˚K, CRI≥85, UNIVERSAL VOLTAGE.

LED 42.2

CEILING

RECESSED

ALL DENTAL OPERATORIES, LABORATORY

COOPER LIGHTING, METALUX BRAND, ENCOUNTER LED SERIES, CAT. NO. 24EN-LD2-49-UNV-L950-CD1 OR

APPROVED EQUAL

B

LED, 3900 LUMENS MINIMUM, 2'-0" X 4'-0" RECESSED TROFFER, RIBBED FROSTED ACRYLIC LENS, LED

ELECTRONIC DIMMING DRIVER, 3500˚K, CRI≥80, UNIVERSAL VOLTAGE.

LED 31.9

CEILING

RECESSED

ALL CORRIDORS, RECEPTION ROOM

COOPER LIGHTING, METALUX BRAND, SKYRIDGE LED SERIES, CAT. NO. 24SR-LD2-39-C-UNV-L835-CD1 OR

APPROVED EQUAL

C

LED, 4000 LUMENS MINIMUM, 2'-0" X 4'-0" RECESSED TROFFER, RIBBED FROSTED ACRYLIC LENS, LED

ELECTRONIC DIMMING DRIVER, 3500˚K, CRI≥80, UNIVERSAL VOLTAGE.

LED 29

CEILING

RECESSED

HAC, STORAGE, DENTAL INSTRUMENTS, TOILETS,

LOCKERS, CLEAN ROOM, DIRTY ROOM, ADMIN,

CHIEF, DIRECTOR, LOUNGECOOPER LIGHTING, METALUX BRAND, CRUZE SB, CAT. NO. 24CZ-LD5-40-UNV-L835-CD1 OR APPROVED EQUAL

D

LED, 14200 LUMENS MINIMUM, 2'-0" X 4'-0" RECESSED GRID, PATTERN 12 ACRYLIC LENS, LED ELECTRONIC

DIMMING DRIVER, 5000˚K, CRI≥80, UNIVERSAL VOLTAGE.

LED 163.9

CEILING

RECESSED

ORAL SURGERY

COOPER LIGHTING, FAIL-SAFE BRAND, CLM SERIES, CAT. NO. CLMFG-24-4-INS-A12125-LD4-5LO-50-UNV-EDD1

OR APPROVED EQUAL

E

LED, 3400 LUMENS MINIMUM, 2'-0" X 2'-0" RECESSED TROFFER, RIBBED FROSTED ACRYLIC LENS, LED

ELECTRONIC DIMMING DRIVER, 3500˚K, CRI≥80, UNIVERSAL VOLTAGE.

LED 29.4

CEILING

RECESSED

10 DENTIST OFFICE, 6 DENTIST OFFICE, DRINKING

FOUNTAIN BETWEEN TOILETS 100C AND 100B,

FMSCOOPER LIGHTING, METALUX BRAND, CRUZE SB, CAT. NO. 22CZ-LD5-34-UNV-L835-CD1 OR APPROVED EQUAL

F

LED, 1175 LUMENS MINIMUM, 2 FT., WALL BRACKET, FROSTED ACRYLIC LENS, LED ELECTRONIC DIMMING

DRIVER, 3500˚K, CRI≥80, UNIVERSAL VOLTAGE.

LED 18 WALL SURFACE TOILETS

COOPER LIGHTING, JAYLUM SCONCE LED, JAYLUM-JS, CAT. NO. JS-L-N-2-l35-1d-UNV-SU-WA-STD-W OR

APPROVED EQUAL

G

LED, 1000 LUMENS MINIMUM, 8 INCH RECESSED WIDE BEAM DOWNLIGHT, LED ELECTRONIC DIMMING

DRIVER, 3500˚K, CRI≥80, UNIVERSAL VOLTAGE

LED 10.2

CEILING

RECESSED

CONFERENCE ROOM, WAITING AREA, RECEPTION

AREACOOPER LIGHTING, PORTFOLIO BRAND, CAT. NO. LD8B-10D010-ER8B-10208035-8LBW1LI OR APPROVED

EQUAL

H

LED, 7800 LUMENS MINIMUM, CLEAR LENS STRIPLIGHT, 8 FT., LED ELECTRONIC DIMMING DRIVER, 3500˚K, CRI≥80, UNIVERSAL VOLTAGE

LED 55.4

CEILING PENDANT

NORMAL POWER ELECTRICAL ROOM,

EMERGENCY POWER ELECTRICAL ROOM,

MECHANICAL ROOM, OIT, FRCOOPER LIGHTING, METALUX BRAND, SNLED LENSED LED STRIPLIGHT SERIES, CAT. NO. 8TSNLED-LD5-75SL-

LC-UNV-L835-CD1 OR APPROVED EQUAL

I

LED, 10000 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 8 FT., LED ELECTRONIC DIMMING DRIVER, 3500˚K, CRI≥80, UNIVERSAL VOLTAGE

LED 82

UNDER DECK

SURFACE

WAITING AREA (DECORATIVE RESIN PANELS)

COOPER LIGHTING, METALUX BRAND, SNLED INDUSTRIAL, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SNLED-

LD5-72HL-RM-UNV-L835-CD1-SCA OR APPROVED EQUAL

J

EXTERIOR LED WALL LIGHT, 3000 LUMENS MINIMUM, QTR. SPHERE, DARK BRONZE, TYPE IV DISTIBUTION, LED ELECTRONIC DRIVER, 4000˚K, CRI≥70, UNIVERSAL VOLTAGE

LED 30 WALL SURFACE EXTERIOR WALL, STAIR

HUBBELL OUTDOOR LIGHTING, GEOPAK SERIES 1, CAT. NO QSP1-12L-30-4K7-4-UNV-DBS-PC OR APPROVED

EQUAL

K

EXTERIOR LED WALL SURFACE-MOUNTED FLOODLIGHT, 5900 LUMENS, 4000˚K, CRI≥70, ELECTRONIC LED

DRIVER, UNIVERSAL VOLTAGE

LED 51 POLE ROOF

COOPER LIGHTING, LUMARK BRAND, NIGHT FALCON CAT. NO. NFFLD-S-C15-D-UNV-66-S-CB OR APPROVED

EQUAL

L

LED, 10000 LUMENS MINIMUM, PARKING LOT LIGHT, SQUARE POLE MOUNTED, SHOE BOX STYLE, DARK

BRONZE, 4000˚K, CRI≥85, UNIVERSAL VOLTAGE

LED 108 POLE MOUNTED PARKING LOT

LITHONIA LIGHTING, KAD LED BRAND, CAT. NO. KAD LED-30C-1000-40K-R3-MVOLT-SPUMBANK04 OR

APPROVED EQUAL

M

RED LED EDGE-LIT EXIT SIGN, 120/277 V, WITH SEALED MAINTENANCE FREE BATTERY AND SOLID STATE

CHARGING SYSTEM

LED 3.5

CEILING

TOP MOUNTED

CORRIDORS

COOPER LIGHTING, SURE-LITES BRAND, CAT. NO. EUR70R OR APPROVED EQUAL

A

A

B

B

C

C

D

E

E

F F

G G

H

I

J

K

L

2 3

PROVIDE

INTEGRATED

PHOTO CELL

EXCEPT THE

STAIR LIGHT

6 7

1. WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING

FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FIXTURE

SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND APPEARANCE

SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN ON FIXTURE

SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO COTR OR VAMC

REPRESENTATIVE FOR APPROVAL.

2. LED LAMP SHALL HAVE A MINIMUM COLOR TEMPERATURE OF 3500°K

AND CRI OF 85, UNLESS OTHERWISE NOTED.

GENERAL NOTES

3. PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURES. WHEN

AVAILABLE.

SHEET NOTES

1 PROVIDE FIXTURE MOUNTING MATCHING CEILING TYPE.

2 REFER TO LIGHTING PLAN FOR SIGNAGE MOUNTING AND NUMBER OF

FACES.

3 FILL IN DIRECTION INDICATOR POINTING DIRECTION.

4 MOUNTED ±3" ABOVE MIRROR TO BOTTOM OF FIXTURE.

5 MOUNTING HEIGHT TO BE 9' AFF - PROVIDE SCA ADJUSTABLE 48" STEM

SET OR EQUAL

6 MOUNT ±2' ABOVE DECORATIVE CEILING SUSPENDED FROM THE DECK.

PROVIDE SCA ADJUSTABLE48" STEM SET OR EQUAL.

7 FIXTURE IS PENDANT MOUNTED UNDER DECK

8 PROVIDE DISTRIBUTION TYPE III LIGHTS WITH INTEGRATED PHOTOCELL

AND DARK BRONZE FINISH. MATCH EXISTING PARKING LOT LIGHTS IN

THE ADJACENT AREA TO THE EAST.

9 PROVIDE SLIP FITTER MOUNTING

S T

A

T E

O F CA L I FOR N

I A

EXP.________

E 17641 9-30-2023

R

EG

IS

TE

RED

PROFESS IONAL

ENG

INE

ERA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h o n e f o o t o n e in c h o n e f o o t

VA FORM 08-6231

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

Dwg. of

VA MEDICAL CENTER, FAIRFIELD, CA 94535

K.F. DAVIS ENGINEERING, INC.

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

6/14/2023 2:07:27 PMC:\Users\ashrestha\Documents\FAIRFIELD - DENTAL - CENTRAL_V2021_FINAL_Anil.ShresthaMSEWP.rvt

RELOCATE AND EXPAND

DENTAL CLINIC TO

FAIRFIELD

R. BLAYLOCK

EL701

ELECTRICAL LIGHTING SCHEDULE

G. FERNANDEZ

612-164

R. BLAYLOCK

08/10/2022 Revisions: Date:

NIC

NIC

REF.

F .E

.C

F.E.C.

F .E

.C

F .E

.C

F.E.C.

F .E

.C

UP

G F

C I

G F

C I

GFCI

J

GFCI

J

GFCI

G F

C I

G F

C I

G F

C I

GFCI

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

GFCI

G F

C I

GFCIGFCI

GFCI

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

G F

C I

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

J

J

J

J

J

J

J

G F

C I

J J J

J

J

J

J

J

J

J

J

J

JJJ

J

J

J

J J

J

J

J J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J J

J

J

J

601_ "441_

52"

40"

" 5

3 _ 4

1 _ 2

711_ " 711_

59"59"1

27"

1 _ 2

1 _ 2

853_ " 52"

283_

27"

138"

283_

551_ "50"

551_ "50"

1 _ 4

27"283_

27"283_

3 _ 4

1 _ 4

1 _ 4

1 _ 4

1 _ 2

1 _ 2

3 _ 4

1 _ 4

1 _ 4

1 _ 4

1 _ 4

1 _ 4

591_ " 68" 621_

" 681_

" 621_

" 681_

" 621_

" 681_

" 621_

" 681_

" 621_

" 681_

" 1273_

651_ " 62" 681_

" 621_

" 681_

" 621_

" 681_

" 621_

" 681_

" 621_

" 681_

" 591_

3 _ 4

1 _ 4

27"

273_

1 _ 4

1 _ 2

4'-6 1_

4'-4 1__

OUT OF SPEC

OUT OF SPEC

OUT OF SPEC

OUT OF SPEC

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

O U

T O

F S

P E

C

OUT OF SPEC

371_ " 431_

3 _ 4

303_ " 333_

37"

3_

C e il in g

M o n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

CL

O D m m

T u b i n g

F o r

C e n t r a l

V a c u m

O n l y s e e g e n e r a l n o t e s m m

N o m i n a l

P i p e

F o r

G r a v i t y

D r a i n w h e n

R e q u i r e d

1 _ 4

7_ 8

7_ 8

5_

5m m

5m m

6m m

0m m

1m m

1m m

12/03

Lower Rail

Lower Rail

Power Supply (locate as needed)

Power Distribution Box (locate as needed)

QUAD ELECTRICAL BOX

Supplied By A-DEC (Check amperage requirements) Locate as needed

03/16

09/05

L o w er R a il

L o w er R a il

T ra s h R e ce p tac le

P o w e r D istrib utio n B o x

L o c a te a s n e ed e d

Q U A D

E L E C T R I C A L

B O X

S u p p l i e d

B y

A d e c

C h e c k

A m p e r a g e

R e q u i r e m e n t s

L o c a t e a s

N e e d e d

/1

L o w er

R a il

L o w er

R a il

T ra s h

R e ce p ta c le

/1

371_ " 431_

3 _ 4

303_ " 333_

37"

3_

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

CL

O D m m

T u b i n g

F o r

C e n t r a l

V a c l y s e e g e n e r a l n o t e s m m

N o m i n a l

P i p e

F o r

G r a v i t y

D r a i n w h e n

R e q u i r e d

1_ 4

7_ 8

7_ 8

5_

5m m

5m m

6m m

0m m

1m m

1m m

12/03

Lower Rail

Lower Rail

Power Supply (locate as needed)

Power Distribution Box (locate as needed)

QUAD ELECTRICAL BOX

Supplied By A-DEC (Check amperage requirements) Locate as needed

03/16

09/05

L o w er R a il

L o w er R a il

T ra s h R e ce p tac le

P o w e r D istrib utio n B o x

L o c a te a s n e ed e d

Q U A D

E L E C T R I C A L

B O X

S u p p l i e d

B y

A d e c

C h e c k

A m p e r a g e

R e q u i r e m e n t s

L o c a t e a s

N e e d e d

/1

L o w er

R a il

L o w er

R a il

T ra s h

R e ce p ta c le

/1

371_ " 431_

3 _ 4

303_ " 333_

37"

3_

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

CL

O D m m

T u b i n g

F o r

C e n t r a l

V a c l y s e e g e n e r a l n o t e s m m

N o m i n a l

P i p e

F o r

G r a v i t y

D r a i n w h e n

R e q u i r e d

1_ 4

7_ 8

7_ 8

5_

5m m

5m m

6m m

0m m

1m m

1m m

12/03

Lower Rail

Lower Rail

Power Supply (locate as needed)

Power Distribution Box (locate as needed)

QUAD ELECTRICAL BOX

Supplied By A-DEC (Check amperage requirements) Locate as needed

03/16

09/05

L o w er R a il

L o w er R a il

T ra s h R e ce p tac le

P o w e r D istrib utio n B o x

L o c a te a s n e ed e d

Q U A D

E L E C T R I C A L

B O X

S u p p l i e d

B y

A d e c

C h e c k

A m p e r a g e

R e q u i r e m e n t s

L o c a t e a s

N e e d e d

/1

L o w er

R a il

L o w er

R a il

T ra s h

R e ce p ta c le

/1

371_ " 431_

3 _ 4

303_ " 333_

37"

3_

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

CL

O D m m

T u b i n g

F o r

C e n t r a l

V a c l y s e e g e n e r a l n o t e s m m

N o m i n a l

P i p e

F o r

G r a v i t y

D r a i n w h e n

R e q u i r e d

1_ 4

7 _ 8

7 _ 8

5 _

5m m

5m m

6m m

0m m

1m m

1m m

12/03

Lower Rail

Lower Rail

Power Supply (locate as needed)

Power Distribution Box (locate as needed)

QUAD ELECTRICAL BOX

Supplied By A-DEC (Check amperage requirements) Locate as needed

03/16

09/05

L o w er R a il

L o w er R a il

T ra s h R e ce p tac le

P o w e r D istrib utio n B o x

L o c a te a s n e ed e d

Q U A D

E L E C T R I C A L

B O X

S u p p l i e d

B y

A d e c

C h e c k

A m p e r a g e

R e q u i r e m e n t s

L o c a t e a s

N e e d e d

/1

L o w er

R a il

L o w er

R a il

T ra s h

R e ce p ta c le

/1

371_ " 431_

3 _ 4

303_ " 333_

37"

3_

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

CL

O D m m

T u b i n g

F o r

C e n t r a l

V a c l y s e e g e n e r a l n o t e s m m

N o m i n a l

P i p e

F o r

G r a v i t y

D r a i n w h e n

R e q u i r e d

1_ 4

7_ 8

7_ 8

5_

5m m

5m m

6m m

0m m

1m m

1m m

12/03

Lower Rail

Lower Rail

Power Supply (locate as needed)

Power Distribution Box (locate as needed)

QUAD ELECTRICAL BOX

Supplied By A-DEC (Check amperage requirements) Locate as needed

03/16

09/05

L o w er R a il

L o w er R a il

T ra s h R e ce p tac le

P o w e r D istrib utio n B o x

L o c a te a s n e ed e d

Q U A D

E L E C T R I C A L

B O X

S u p p l i e d

B y

A d e c

C h e c k

A m p e r a g e

R e q u i r e m e n t s

L o c a t e a s

N e e d e d

/1

L o w er

R a il

L o w er

R a il

T ra s h

R e ce p ta c le

/1

371_ " 431_

3 _ 4

303_ " 333_

37"

3_

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

CL

O D m m

T u b i n g

F o r

C e n t r a l

V a c l y s e e g e n e r a l n o t e s m m

N o m i n a l

P i p e

F o r

G r a v i t y

D r a i n w h e n

R e q u i r e d

1_ 4

7_ 8

7_ 8

5_

5m m

5m m

6m m

0m m

1m m

1m m

12/03

Lower Rail

Lower Rail

Power Supply (locate as needed)

Power Distribution Box (locate as needed)

QUAD ELECTRICAL BOX

Supplied By A-DEC (Check amperage requirements) Locate as needed

03/16

09/05

L o w er R a il

L o w er R a il

T ra s h R e ce p tac le

P o w e r D istrib utio n B o x

L o c a te a s n e ed e d

Q U A D

E L E C T R I C A L

B O X

S u p p l i e d

B y

A d e c

C h e c k

A m p e r a g e

R e q u i r e m e n t s

L o c a t e a s

N e e d e d

/1

L o w er

R a il

L o w er

R a il

T ra s h

R e ce p ta c le

/1

371_ " 431_

3 _ 4

303_ " 333_

37"

3_

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il n it o r

M o u n t P o s it io n i n g

P o in t

(s e e M o n it o r M n t t a b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

C e il in g M o n it o r M o u n t

/C e il in g M o u n t

L ig h t

P o s it io n in g

P o in t

(s e e M o n it o r M n t ta b le

CL

O D m m

T u b i n g

F o r

C e n t r a l

V a c l y s e e g e n e r a l n o t e s m m

N o m i n a l

P i p e

F o r

G r a v i t y

D r a i n w h e n

R e q u i r e d

1 _ 4

7_ 8

7_ 8

5_

5m m

5m m

6m m

0m m

1m m

1m m

12/03

Lower Rail

Lower Rail

Power Supply (locate as needed)

Power Distribution Box (locate as needed)

QUAD ELECTRICAL BOX

Supplied By A-DEC (Check amperage requirements) Locate as needed

03/16

09/05

L o w er R a il

L o w er R a il

T ra s h R e ce p tac le

P o w e r D istrib utio n B o x

L o c a te a s n e ed e d

Q U A D

E L E C T R I C A L

B O X

S u p p l i e d

B y

A d e c

C h e c k

A m p e r a g e

R e q u i r e m e n t s

L o c a t e…