Atch 17 - Electrical 2 of 4.pdf

PDF 19 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - Tomah Federal contract opportunity
Solicitation number
36C77622B0031
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document outlines requirements for a federal contract solicitation. The solicitation number 36C77622B0031 from the Department of Veterans Affairs Technology Acquisition Center Austin is for infrastructure upgrades and renovations at the Tomah VA medical center in Wisconsin. The project involves electrical, HVAC, communication, physical security, and fiber optic upgrades across multiple buildings on campus. Work will also include modifying impacted roads, walks, grading, drainage and other utilities. Data center WAN updates and hazardous material abatement are within the scope of services. Responses are due based on the standard solicitation timeline and awards will be made thereafter.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - Tomah, newest first.
File Type Posted
Follow-up Questions and Responses 7-26-22.pdf PDF
36C77622B0031 0005.pdf PDF
36C77622B0031 0004.pdf PDF
36C77622B0031 0003.pdf PDF
Atch 28 - Construction Wage Rates - Monroe - 7-15-22.pdf PDF
Technical Questions - LATE - Tomah 7-20-22.pdf PDF
OIT-StdTelecomSpacesPgs64-67.pdf PDF
Atch 28 - Construction Wage Rates - Monroe - 6-17-22.pdf PDF
Technical Questions - FINAL - Tomah 7-6-22.pdf PDF
36C77622B0031 0002.pdf PDF
Site Visit Sign-in Sheet - Tomah 6-14-22.pdf PDF
36C77622B0031 0001.pdf PDF
Atch 1 - Specs Division 00-10.pdf PDF
Atch 8 - Civil 2 of 2.pdf PDF
Atch 10 - Architectural 2 of 2.pdf PDF
Atch 12 - Telecommunications 1 of 4.pdf PDF
Atch 14 - Telecommunications 3 of 4.pdf PDF
Atch 20 - Mechanical 1 of 4.pdf PDF
Atch 22 - Mechanical 3 of 4.pdf PDF
Atch 23 - Mechanical 4 of 4.pdf PDF
Atch 25 - Appendix C-D Specs on TOC.pdf PDF
Atch 27 - Limitations on Subcontracting - Construction.docx DOCX document
Atch 28 - Construction Wage Rates - Monroe - 4-29-22.pdf PDF
Atch 29 - Contractor Safety - Environmental Form.docx DOCX document
Atch 6 - General.pdf PDF
Atch 13 - Telecommunications 2 of 4.pdf PDF
Atch 16 - Electrical 1 of 4.pdf PDF
Atch 21 - Mechanical 2 of 4.pdf PDF
Atch 3 - Specs Division 26-28.pdf PDF
Atch 4 - Specs Division 31-33.pdf PDF
Atch 5 - Sheet Index - EHRM Upgrades.pdf PDF
Atch 7 - Civil 1 of 2.pdf PDF
Atch 9 - Architectural 1 of 2.pdf PDF
Atch 26 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Atch 30 - Site Visit - Map.pdf PDF
Atch 11 - Hazmat.pdf PDF
36C77622B0031 - 5-25-22.pdf PDF
Atch 2 - Specs Division 21-23.pdf PDF
Atch 15 - Telecommunications 4 of 4.pdf PDF
Atch 18 - Electrical 3 of 4.pdf PDF
Atch 19 - Electrical 4 of 4.pdf PDF
Atch 24 - Appendix A-B Specs on TOC.pdf PDF
Show all 42

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3128A

3126A

3124A

3119 3119A

3117A

3111A

3109A

3107A

3105A

3137A

3137 3139

3139A

3149 3148

3151 3153

3146 3154

3161 3163 3165

3190A 3190

3189A

3187A

3185A

3184A

31823182A

3178A

3176A

31743174A

3172A

3142 3144

3100 3170

1C39

C

1C371C33

1C32

1C34

C

3150A

3150B

C

S32 S30

31663131

3147A

1C35

B401-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:0

:4

P M

B401-ED113

THIRD FLOOR DEMOLITION -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B401

10/06/21 GJL ASQ

16477

N O R

HT

1/8" = 1'-0"

THIRD FLOOR DEMOLITION - ELECTRICAL

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

Revisions: Date:

STAMP

ELEVELEV

1113A

1143AA 1143 1143B

1165A

1143A

1144S12 1146

1150A

1166 S10

1184A 1184B

1C19

1116 1118

1120A

1182A 1182B

1C171C151C13

1145A

DN.

UP UP

EE E

B401-EP200

B401-EP200

CU B401-1.1

CU B401-2.1

CU B401-3.1

B401IT-1-11

WP

B401IT-1-CR-2,4

B401IT-2-CR-2,4

B401IT-3-CR-2,4 1

DS-30R

DS-30R

DS-30R

B401-EP200

WP

WP

WP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:0

:4

P M

B401-EP111

FIRST FLOOR - ELECTRICAL EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B401

02/11/2022 GJL ASQ

16477

N O R

HT

1/8" = 1'-0"

FIRST FLOOR - ELECTRICAL

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

KEYNOTES:

1. OUTDOOR UNIT TO POWER INDOOR UNIT.

PROVIDE 2#10 & 1#12 IN 1/2" CONDUIT.

COORDINATE EXACT LOCATION WITH M.C.

0 8' 16'4'

UP

DN

UP

2128A

2126A

2124A

2119A

2117A

2111A

2109A

2107A

2105A

2137A

2137 2139

2139A

2149 2148

2151 2153

2146 2154

2161 2163 2165

2190A 2190

2189A

2187 2187A

2185A

2184A

2182A

2178A

2176A

2174A

21722172A

2140 2142 2144

2100 2170

C

1C21

1C23

C

1C24

C

2150A

2150B

C

S22

EXST STAIR

S20

21662131

1C22A

C

B

C

B

1C25 1C27

C

B

1C28A

C

B

C

A

C

A B401-EP200

B401-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:0

:5

P M

B401-EP112

SECOND FLOOR - ELECTRICAL EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B401

02/11/2022 GJL ASQ

16477

N O R

HT

1/8" = 1'-0"

SECOND FLOOR - ELECTRICAL

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

3128A

3126A

3124A

3119 3119A

3117A

3111A

3109A

3107A

3105A

3137A

3137 3139

3139A

3149 3148

3151 3153

3146 3154

3161 3163 3165

3190A 3190

3189A

3187A

3185A

3184A

31823182A

3178A

3176A

31743174A

3172A

3142 3144

3100 3170

1C39

C

1C371C33

1C32

1C34

C

3150A

3150B

C

S32 S30

31663131

3147A

1C35

B401-EP200

B401-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:0

:5

P M

B401-EP113

THIRD FLOOR - ELECTRICAL EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B401

02/11/2022 GJL ASQ

16477

N O R

HT

1/8" = 1'-0"

THIRD FLOOR - ELECTRICAL

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

SD

A1

A11

2D

2D 4D

D

D

-C A

M

E

E

1D-CAM E

1D-CAM

1V

2D 2D

2D2D 4D

2D 4D

D

D

-C A

M

A11

A1

E

SD

SD

1184A 1184B

2161 2163

C

B

1D-CAM

E

1D-CAM

3161 3163

1D-CAM

E

OFFICE

130 SF

1164A

TELECOM

A

B401IT-1

b

A

B401IT-1-CR

a

A

B401IT-1

b a b

OFFICE

130 SF

1164A

TELECOM

SSAC B401-1.1

B401IT-1-CR-1

42"

B401IT-1-3

42"

B401IT-1-CR-1

42"

B401IT-1-3

42"

B401IT-1-CR-1

42"

B401IT-1-3

42"

B401IT-1-CR-1

42"

B401IT-1

B401IT-1-5,7,9

B401IT-1-CR-3,5,7

6 7

B401IT-1-CR

SSAC B401-2.1

B401IT-2-CR-1

42"

B401IT-2-1

42"

B401IT-2-CR-1

42"

B401IT-2-1

42"

B401IT-2-CR-1

42"

B401IT-2-CR-3,5,7

B401IT-2-3,5,7

B401IT-2

4 5

6 7

B401IT-2-CR

SSAC B401-3.1

B401IT-3-1

42"

B401IT-3-CR-1

42"

B401IT-3-1

42"

B401IT-3-CR-1

42"

B401IT-3-CR-3,5,7

B401IT-3-3,5,7

B401IT-3

4 5

6 7

B401IT-3-CR

(E)CUH

A

B401IT-2

b

A

B401IT-2

b

A

B401IT-2-CR

a a b

A

B401IT-3

b

A

B401IT-3

b

A

B401IT-3-CR

a a b

SWITCHBOARD B401-DP-208-CR

SWITCHBOARD B401-DP-480-EQ

ATS ATS MCB

SWITCHBOARD B401-MDP-480ATS

ATS

DP-208-NP

(E)SSAC B401-2

(E)SSAC B401-3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:0

:5

P M

B401-EP200

ELECTRICAL ENLARGED PLANS EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B401

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - ELECTRICAL

LIGHTING & FIRE ALARM -

TR-401-1-1

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - ELECTRICAL POWER - TR-401-1-1

N O R

HT

1/4" = 1'-0"

SECOND FLOOR - ELECTRICAL

POWER - TR-401-2-1

5 N O R

HT

1/4" = 1'-0"

THIRD FLOOR - ELECTRICAL

POWER - TR-401-3-1

KEYNOTES:

1. INDOOR UNIT TO BE POWERED BY OUTDOOR

UNIT. PROVIDE SWITCH & 120V CONNECTION

FOR CONDENSATE PUMP ASSOCIATED WITH

FAN UNIT FROM FAN UNIT POWER.

COORDINATE EXACT LOCATION WITH M.C.

2. CONNECT SMOKE DETECTOR TO NEAREST

EXISTING SLC.

3. DISCONNECT AND REMOVE LIGHTS AND

RECEPTACLES IN AREA OF NEW IT ROOM.

MAINTAIN CIRCUIT CONTINUITY TO ADJOINING

SPACES.

4. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-30R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#10, 1#12 GND

TO PANEL FOR EACH RECEPTACLE.

5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE, 4-WIRE RACK MOUNTED UPS FOR

EACH RACK TOWER.

6. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

7. PROVIDE ONE RACK MOUNTED ZONE PDU

UNIT. 30 AMP 3 PHASE, 120/208V, 5-WIRE WITH

(4) L21-30R, (6) 5-20R AND TWO 10' POWER

CORDS. ZONIT#ZPDS-208V-30A-L21-4L21-20R-

CR.

8. EXISTING FIRE ALARM AND ALERT AUDIO

DEVICES SHALL BE RELOCATED AS SHOWN ON

2/E200.

9. RELOCATED FIRE ALARM AND ALERT AUDIO

DEVICES. PROVIDE NEW CIRCUITING TO

REVISED LOCATION.

10. PROVIDE CONNECTION TO EXISTING

RECEPTACLE CIRCUITS IN ROOM.

11. EXISTING LIGHT SHALL BE RELOCATED AS

SHOWN ON E200.

12. RELOCATED 1X4 LIGHT. PROVIDE CONNECTION

TO EXISTING CIRCUIT AND NEW SWITCH AT

NEW DOOR.

13. PROVIDE NEW LED LIGHTS AT SAME

LOCATION.

N O R

HT

1/4" = 1'-0"

FIRST FLOOR DEMOLITION -

ELECTRICAL - TR-401-1-1

N O R

HT

1/4" = 1'-0"

SECOND FLOOR - ELECTRICAL

LIGHTING & FIRE ALARM -

TR-401-2-1

N

O R

HT

1/4" = 1'-0"

THIRD FLOOR - ELECTRICAL

LIGHTING & FIRE ALARM -

TR-401-3-1

CONSTRUCTION NOTES:

1. REFER TO TECHNOLOGY PLANS FOR IT ROOM

LAYOUT AND RACK LAYOUT/DETAILS.

2. REFER TO SHEET E003 DETAIL LAYOUT & ONE-

LINE OF RACK.

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - ELECTRICAL ROOM

0 4' 8'2' 0 4' 8'2' 0 4' 8'2'

0 4' 8'2'0 4' 8'2'

0 4' 8'2'

0 4' 8'2'

0 4' 8'2'

0 4' 8'2' 0 4' 8'2'

Revisions: Date:

N O R

HT

1/4" = 1'-0"

SECOND FLOOR DEMOLITION -

ELECTRICAL - TR-401-2-1

N

O R

HT

1/4" = 1'-0"

THIRD FLOOR DEMOLITION -

ELECTRICAL - TR-401-3-1

BASEMENT

FIRST FLOOR

B401IT-1-CR

4#3 & 1#8 GND. IN 1 1/4" C.

B401-DP-208-CR

FIRST FLOOR

B401IT-2-CR

FIRST FLOOR

B401IT-3-CR

4#3 & 1#8 GND. IN 1 1/4" C.

4#3 & 1#8 GND. IN 1 1/4" C.

4#3 & 1#8 GND. IN 1 1/4" C.

B401-DP-208-NP

4#3 & 1#8 GND. IN 1 1/4" C.

4#3 & 1#8 GND. IN 1 1/4" C.

B401IT-1

B401IT-3

B401IT-2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:0

:5

P M

B401-EP300

ELECTRICAL ONE-LINE DIAGRAMS EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B401

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

NO SCALE

PARTIAL POWER RISER

KEYNOTES:

1. PROVIDE NEW 100A/3P BREAKERS TO MATCH

EXISTING TYPE AND AIC RATING.

SPACE

1200A 3P

CPM-2-1

SPARE

SPARE

B401IT-1-CR 2CP-2-3

B401IT-2-CR 2CP-2-2

SPACE

SPACE

CP-1B

2CP-1-2

MAIN

B401DP-DP-208-CR

800A MCB, 120/208V, 3 PHASE, 4 WIRE

B401IT-3-CR

SPARE

2CP-1-3

150A 3P

150A 3P

150A 3P

150A 3P

250A 3P

250A 3P

150A 3P

100A 3P

100A 3P

100A 3P

NEW 100A/3P BREAKER.

SPACE

B401IT-3

NP-2-1

MAIN

B401-DP-208-NP

800A MCB, 120/208V, 3 PHASE, 4 WIRE

SPACE

TUNEL

B401IT-1

B401IT-2 100A

3P

100A 3P

EXIST.

3P

EXIST.

3P

SPACE

SPACE

100A 3P

2NP-1-3225A

3P

2NP-1-2225A

3P

2NP-2-2225A

3P

2NP-2-3225A

3P

2NP-3-1225A

3P

SPACE

SPACENEW 100A/3P BREAKER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:0

:5

P M

B401-EP301

ELECTRICAL ONE-LINE DIAGRAMS EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B401

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

NO SCALE

ELEVATION OF DISTRIBUTION PANEL - CRITICAL

1 NO SCALE

ELEVATION OF DISTRIBUTION PANEL - NORMAL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:0

:5

P M

B401-EP400

ELECTRICAL SCHEDULES EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B401

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 19.6 A

TOTAL CONNECTED AMPS: 27.97 A

Receptacles 0.72 kVA 70.00% 0.504 kVA TOTAL ESTIMATED DEMAND LOAD: 7.053 kVA

Power 9 kVA 70.00% 6.3 kVA TOTAL CONNECTED LOAD: 10.08 kVA

Lighting 0.356 kVA 70.00% 0.249 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 28.19 29.73 26.50

Total Load: 3.36 kVA 3.54 kVA 3.18 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

11 CU GFI REC. 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 12 --

-- 9 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

5 L21-30R RACK 30 A 3 3 0 -- -- -- 1 20 A SPARE 6 --

3 TELECOM ROOM REC. 20 A 1 0.54 0 -- -- -- 1 20 A SPARE 4 --

1 LIGHTING 20 A 1 0.36 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: TELECOM 1164A WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B401IT-1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 18.9 A

TOTAL CONNECTED AMPS: 26.97 A

Receptacles 0.36 kVA 70.00% 0.252 kVA TOTAL ESTIMATED DEMAND LOAD: 6.801 kVA

Power 9 kVA 70.00% 6.3 kVA TOTAL CONNECTED LOAD: 9.72 kVA

Lighting 0.356 kVA 70.00% 0.249 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 28.46 28.42 25.00

Total Load: 3.36 kVA 3.36 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.36 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0 -- -- -- 1 20 A SPARE 4 --

1 TELECOM ROOM REC. 20 A 1 0.36 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B401IT-2

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 18.9 A

TOTAL CONNECTED AMPS: 26.97 A

Receptacles 0.36 kVA 70.00% 0.252 kVA TOTAL ESTIMATED DEMAND LOAD: 6.801 kVA

Power 9 kVA 70.00% 6.3 kVA TOTAL CONNECTED LOAD: 9.72 kVA

Lighting 0.356 kVA 70.00% 0.249 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 28.46 28.42 25.00

Total Load: 3.36 kVA 3.36 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.36 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0 -- -- -- 1 20 A SPARE 4 --

1 TELECOM ROOM REC. 20 A 1 0.36 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B401IT-3

Revisions: Date:

FS - FUSED SWITCH

MX - MANUAL SWITCH

MS - MANUAL STARTER

SS - SOLID STATE

RV - REDUCED VOLTAGE AUTOXFMR

SW - 2 SPEED, 1 WINDING

TW - 2 SPEED, 2 WINDING

RE - REVERSING HL - HANDLE PADLOCK HASP

YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR

FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. & (2)-N.C.

STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS

*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR

CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) TS - 2 SPEED SELECTOR SWITCH IN DOOR

NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1 PHASE)

FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) PF - PHASE LOSS PROTECTION (5 HP OR GREATER, 3 PHASE...

DISCONNECT TYPE: ACCESSORIES & OPTIONS

NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.

DISCONNECT AND STARTER SCHEDULE

ITEM

DISCONNECT TYPE &

RATING

CIRCUIT

VOLTAGE POLES

STARTER

ENCLOSURE

REQUIRED ACCESSORIES

& OPTIONS COMMENTSTYPE RATING

NEMA

SIZE TYPE

DS-30R NFU 30 A 208 V 3 NEMA 1 FUSED AT ** AMPS

DS-30R NFU 30 A 208 V 3 NEMA 1 FUSED AT ** AMPS

DS-30R NFU 30 A 208 V 3 NEMA 1 FUSED AT ** AMPS

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND... 22.1 A

TOTAL CONNECTED AMPS: 31.64 A

Receptacles 0.72 kVA 70.00% 0.504 kVA TOTAL ESTIMATED DEMAND... 7.978 kVA

Power 10.5 kVA 70.00% 7.35 kVA TOTAL CONNECTED LOAD: 11.40 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 38.44 33.92 25.00

Total Load: 4.47 kVA 3.93 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0.75 -- -- -- -- -- -- 4 --

1 TELECOM ROOM REC. 20 A 1 0.72 0.75 2 30 A CU B401-1.1 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

KVA RATING: SCCR: 10 kA

LOCATION: TELECOM 1164A WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B401IT-1-CR

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND... 21.8 A

TOTAL CONNECTED AMPS: 31.14 A

Receptacles 0.54 kVA 70.00% 0.378 kVA TOTAL ESTIMATED DEMAND... 7.852 kVA

Power 10.5 kVA 70.00% 7.35 kVA TOTAL CONNECTED LOAD: 11.22 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 36.94 33.92 25.00

Total Load: 4.29 kVA 3.93 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0.75 -- -- -- -- -- -- 4 --

1 TELECOM ROOM REC. 20 A 1 0.54 0.75 2 30 A CU B401-21 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

KVA RATING: SCCR: 10 kA

LOCATION: WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B401IT-2-CR

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND... 21.4 A

TOTAL CONNECTED AMPS: 30.64 A

Receptacles 0.36 kVA 70.00% 0.252 kVA TOTAL ESTIMATED DEMAND... 7.726 kVA

Power 10.5 kVA 70.00% 7.35 kVA TOTAL CONNECTED LOAD: 11.04 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 35.44 33.92 25.00

Total Load: 4.11 kVA 3.93 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0.75 -- -- -- -- -- -- 4 --

1 TELECOM ROOM REC. 20 A 1 0.36 0.75 2 30 A CU B401-3.1 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

KVA RATING: SCCR: 10 kA

LOCATION: WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B401IT-3-CR

DP-208-NP

DP-208-NP DP-208-CR

DP-208-NP DP-208-CR

DP-208-CR

2C14

2C11

1220A

S15

2C13

1225A

1230 1282

A

2C17

1264A

1236 1238 1240

S13402E5

402E5A

1250A

1250B

1250C 1250D

1280C

1280A

1280D

2C19

1280B

402M5

B402-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:0

P M

B402-ED111

FIRST FLOOR DEMOLITION -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

N O R

HT

1/8" = 1'-0"

FIRST FLOOR DEMOLITION - ELECTRICAL

2241A

2201 2200

2C21

2C23

2235 2237

S15 2232 2234 2238

2240A

2240C

B

2254 2258

2258A

S13 2286

2C29

2289A

2292A

2257A22572255

2275 2274

2269A 2274A

2263 2264

2C28

2C272

2217A 2218

2218A

2C22

2205A 2204A

2282A

B402-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:0

P M

B402-ED112

SECOND FLOOR DEMOLITION -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

N O R

HT

1/8" = 1'-0"

SECOND FLOOR DEMOLITION - ELECTRICAL

LOUNGE

VISITOR

CONFERENCE

STAFF

LOBBY

HALLWAY

CART

CRASH

ELEVATOR #1

ELEVATOR #2

3201 3200

32023203

32043205

3205A 3204A

32083209

2C31

3229 3231

2C33

3217A

2C32

32223221

S15 3228 3230

3240C

3240B

3240A

3218A

2C37

3252 3254

3254A

S13

3253 3255 3255A

3263A 3264A

32583259

2C38

3276A

32803281

3277A

2C39

3239A

STORAGE

SPD

B402-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:0

P M

B402-ED113

THIRD FLOOR DEMOLITION -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

N O R

HT

1/8" = 1'-0"

THIRD FLOOR DEMOLITION - ELECTRICAL

CONFERENCE

CONTROL

ELEVATOR

LOBBY

CONFERENCE

PRMS

STORAGE

GENERAL

HALLWAY

ELEVATOR #1

ELEVATOR #2

2C11

1220A

S15

2C13

1225A

1230 1282

A

2C17

1264A

1236 1238 1240

S13402E5

402E5A

1250A

1250B

1250C 1250D

1280C

1280A

1280D

2C19

1280B

402M5

E E

E

1225A

TOILET /

SHOWER

TELECOM

B402-EP200

B402-EP200

CU B402-1.1

CU B402-2.1

CU B402-3.1

B402IT-1-11

WP

B402IT-1-CR-2,4

B402IT-2-CR-2,4

B402IT-3-CR-2,4

DS-30R

DS-30R

DS-30R

B402-EP200

WP

WP

WP

B402-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:0

P M

B402-EP111

FIRST FLOOR - ELECTRICAL EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

N O R

HT

1/8" = 1'-0"

FIRST FLOOR - ELECTRICAL

KEYNOTES:

1. OUTDOOR UNIT TO POWER INDOOR UNIT.

PROVIDE 2#10 & 1#12 IN 1/2" CONDUIT.

COORDINATE EXACT LOCATION WITH M.C.

VISITOR

OFFICE

PHYSICIANS

LOBBY

CART

CRASH

HALLWAY

ELEVATOR #1

ELEVATOR #2

2241A

2201 2200

2C21

2C23

2235 2237

S15 2232 2234 2238

2240A

2240C

B

2254 2258

2258A

S13 2286

2C29

2289A

2292A

2257A22572255

2275 2274

2269A 2274A

2263 2264

2C28

2C272

2217A 2218

2218A

2C22

2205A 2204A

2282A

OFFICE

TELECOM

TELECOM

B402-EP200

B402-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:1

P M

B402-EP112

SECOND FLOOR - ELECTRICAL EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

N O R

HT

1/8" = 1'-0"

SECOND FLOOR - ELECTRICAL

VISITOR

CONFERENCE

STAFF

LOBBY

HALLWAY

CART

CRASH

ELEVATOR #1

ELEVATOR #2

3201 3200

32023203

32043205

3205A 3204A

32083209

2C31

3229 3231

2C33

3217A

2C32

32223221

S15 3228 3230

3240C

3240B

3240A

3218A

2C37

3252 3254

3254A

S13

3253 3255 3255A

3263A 3264A

32583259

2C38

3276A

32803281

3277A

2C39

3239A

STORAGE

SPD

3231A

TELECOM

EXAM

TELECOM

B402-EP200

B402-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:1

P M

B402-EP113

THIRD FLOOR - ELECTRICAL EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

N O R

HT

1/8" = 1'-0"

THIRD FLOOR - ELECTRICAL

OFFICE

SD

OFFICE

E

OFFICE

SD

E

E

SD

402E5A

STORAGE

SPD

402E5

TELECOM

A

B402IT-1

b

A

B402IT-1-CR

a ab

TELECOM

SSAC B402-1.1

B402IT-1-1

42"

B402IT-1-1

42"

B402IT-1-1

42"

B402IT-1-CR-1

42"

B402IT-1-1

42"

B402IT-1-CR-1

42"

B402IT-1-CR-1

42"

B402IT-1

B402IT-1-3,5,7

B402IT-1-CR-3,5,7

6 7

B402IT-1-CR

TELECOM

A

B402IT-2

b

A

B402IT-2-CR

a ab

TELECOM

SSAC B402-2.1

B402IT-2-1

42"

B402IT-2-1

42"

B402IT-2

B402IT-2-CR-1

42"

B402IT-2-1

42"

B402IT-2-CR-1

42"

B402IT-2-CR-1

42"

B402IT-2-1

42"

B402IT-2-3,5,7

B402IT-2-CR-3,5,7

6 7

B402IT-2-CR

B402IT-3-1

42"

B402IT-3-CR-1

42"

B402IT-3-1

42"

B402IT-3-CR-1

42"

B402IT-3-1

42"

B402IT-3-CR-1

42"

B402IT-3-1

42"

B402IT-3

SSAC B402-3.1

B402IT-3-CR-3,5,7

B402IT-3-3,5,7

6 7

B402IT-3-CR

A

B402IT-3

b

A

B402IT-3-CR

a ab

ATS-480 EQ

B402-DP-208-CR

ATS-480 CR

DP-208-CRATS-480 CS

8 8

B402-MDP-480

B402-MDP-208

B402-MSB-480-EQ

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/2

/2

:3

:1

P

M

B402-EP200

ELECTRICAL ENLARGED PLANS EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - ELECTRICAL -

LIGHTING & FIRE ALARM -

TR-402-1-1

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - ELECTRICAL

POWER - TR402-1-1

N O R

HT

1/4" = 1'-0"

SECOND FLOOR - ELECTRICAL -

LIGHTING & FIRE ALARM -

TR-402-2-1

N O R

HT

1/4" = 1'-0"

SECOND FLOOR - ELECTRICAL

POWER - TR-402-2-1

N O R

HT

1/4" = 1'-0"

THIRD FLOOR - ELECTRICAL

POWER - TR-402-3-1

N O R

HT

1/4" = 1'-0"

THIRD FLOOR - ELECTRICAL -

LIGHTING & FIRE ALARM -

TR-402-3-1

KEYNOTES:

1. INDOOR UNIT TO BE POWERED BY OUTDOOR

UNIT. PROVIDE SWITCH & 120V CONNECTION

FOR CONDENSATE PUMP ASSOCIATED WITH

FAN UNIT FROM FAN UNIT POWER.

COORDINATE EXACT LOCATION WITH M.C.

2. CONNECT SMOKE DETECTOR TO NEAREST

EXISTING SLC.

3. NOT USED.

4. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-30R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#10, 1#12 GND

TO PANEL FOR EACH RECEPTACLE.

5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE, 4-WIRE RACK MOUNTED UPS FOR

EACH RACK TOWER.

6. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

7. PROVIDE ONE RACK MOUNTED ZONE PDU

UNIT. 30 AMP 3 PHASE, 120/208V, 5-WIRE WITH

(4) L21-30R, (6) 5-20R AND TWO 10' POWER

CORDS. ZONIT#ZPDS-208V-30A-L21-4L21-20R-

CR.

8. DISCONNECT AND REMOVE LIGHTS AND

RECEPTACLES IN ROOM. MAINTAIN CIRCUIT

CONTINUITY TO ADJOINNING SPACES.

CONSTRUCTION NOTES:

1. REFER TO TECHNOLOGY PLANS FOR IT ROOM

LAYOUT AND RACK LAYOUT/DETAILS.

2. REFER TO SHEET E003 DETAIL FOR LAYOUT &

ONE-LINE OF RACK.

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - ELECTRICAL -

ELECTRICAL ROOM

N O R

HT

1/4" = 1'-0"

FIRST FLOOR DEMOLITION -

ELECTRICAL - TR-402-1-1

N O R

HT

1/4" = 1'-0"

SECOND FLOOR DEMOLITION -

ELECTRICAL - TR402-2-1

N O R

HT

1/4" = 1'-0"

THIRD FLOOR DEMOLITION -

ELECTRICAL - TR-402-3-1

0 4' 8'2' 0 4' 8'2'

0 4' 8'2' 0 4' 8'2'

0 4' 8'2' 0 4' 8'2'

0 4' 8'2'

0 4' 8'2' 0 4' 8'2'

0 4' 8'2'

Revisions: Date:

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - ELECTRICAL - Callout 1

B402IT-1-CR

4#3 & 1#8 GND IN 1 1/4" C.

B402-DP-208-CR

SECOND FLOOR

THIRD FLOOR

ROOF

B402IT-2-CR

4#3 & 1#8 GND IN 1 1/4" C.

B402IT-3-CR

4#3 & 1#8 GND IN 1 1/4" C.

BASEMENT FLOOR

B402IT-1

4#3 & 1#8 GND IN 1 1/4" C.

B402-DP-208

B402IT-2

B402IT-3

4#3 & 1#8 GND IN 1 1/4" C.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:1

P M

B402-EP300

ELECTRICAL ONE-LINE DIAGRAMS EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

NO SCALE

PARTIAL POWER RISER

KEYNOTES:

1. PROVIDE NEW 100A/3P BREAKERS TO MATCH

EXISTING TYPE AND AIC RATING.

CP-1-G

CP-1-2

CP-1-3

CP-5-1

CP-3-2

CP-3-1

CP-2-2

CP-2-3

CP-5-1

CP-4-1

SPARE

MAIN

CP-1-1

B402-DP-208-CR

CP-2-1

B402IT-2-CR

B402IT-3-CR100A

3P

100A 3P

225A 3P

225A 3P

100A 3P

100A 3P

225A 3P

225A 3P

B402IT-1-CR

100A 3P

100A 3P

100A 3P

NEW 100A/3P BREAKERS.

400A 3P

NP-2-2

NP-2-3

B402-DP-208-LS

B402IT-2

B402IT-3

B402IT-1

100A 3P

100A 3P

100A 3P

NEW 100A/3P BREAKERS.

EXIST.

3P

SPACE

NP-1-2

NP-1-3

SPACE

SPARE

SPACE

MAIN

600A

SPACE

SPACE

SPACE

SPACE

225A 3P

300A 3P

SPACE

MAIN EXIST.

3P

NP-3-1

NP-2-1

NP-4-1

NP-6-1

NP-5-1

225A 3P

225A 3P

225A 3P

225A 3P

225A 3P

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:1

P M

B402-EP301

ELECTRICAL ONE-LINE DIAGRAMS EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

NO SCALE

ELEVATION OF DISTRIBUTION PANEL - CRITICAL

1 NO SCALE

ELEVATION OF DISTRIBUTION PANEL - NORMAL

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:1

P M

B402-EP400

ELECTRICAL SCHEDULES EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

B402

02/11/2022 GJL ASQ

16477

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 19.6 A

TOTAL CONNECTED AMPS: 27.97 A

Receptacles 0.9 kVA 70.00% 0.63 kVA TOTAL ESTIMATED DEMAND LOAD: 7.054 kVA

Power 9 kVA 70.00% 6.3 kVA TOTAL CONNECTED LOAD: 10.08 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 31.00 26.48 26.50

Total Load: 3.72 kVA 3.18 kVA 3.18 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

11 CU GFI REC. 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0 -- -- -- 1 20 A SPARE 4 --

1 TELECOM ROOM REC. 20 A 1 0.72 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: TELECOM 105 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B402IT-1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 19.2 A

TOTAL CONNECTED AMPS: 27.47 A

Receptacles 0.72 kVA 70.00% 0.504 kVA TOTAL ESTIMATED DEMAND LOAD: 6.928 kVA

Power 9 kVA 70.00% 6.3 kVA TOTAL CONNECTED LOAD: 9.90 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 31.23 26.71 25.00

Total Load: 3.72 kVA 3.18 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0 -- -- -- 1 20 A SPARE 4 --

1 TELECOM ROOM REC. 20 A 1 0.72 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: TELECOM 204 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B402IT-2

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 19.2 A

TOTAL CONNECTED AMPS: 27.47 A

Receptacles 0.72 kVA 70.00% 0.504 kVA TOTAL ESTIMATED DEMAND LOAD: 6.928 kVA

Power 9 kVA 70.00% 6.3 kVA TOTAL CONNECTED LOAD: 9.90 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 31.23 26.71 25.00

Total Load: 3.72 kVA 3.18 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0 -- -- -- 1 20 A SPARE 4 --

1 TELECOM ROOM REC. 20 A 1 0.72 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: TELECOM 304 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B402IT-3

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 21.8 A

TOTAL CONNECTED AMPS: 31.14 A

Receptacles 0.54 kVA 70.00% 0.378 kVA TOTAL ESTIMATED DEMAND LOAD: 7.852 kVA

Power 10.5 kVA 70.00% 7.35 kVA TOTAL CONNECTED LOAD: 11.22 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 36.94 33.92 25.00

Total Load: 4.29 kVA 3.93 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0.75 -- -- -- -- -- -- 4 --

1 TELECOM ROOM REC. 20 A 1 0.54 0.75 2 30 A CU B402-1.1 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: TELECOM 105 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B402IT-1-CR

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 21.8 A

TOTAL CONNECTED AMPS: 31.14 A

Receptacles 0.54 kVA 70.00% 0.378 kVA TOTAL ESTIMATED DEMAND LOAD: 7.852 kVA

Power 10.5 kVA 70.00% 7.35 kVA TOTAL CONNECTED LOAD: 11.22 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 36.94 33.92 25.00

Total Load: 4.29 kVA 3.93 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0.75 -- -- -- -- -- -- 4 --

1 TELECOM ROOM REC. 20 A 1 0.54 0.75 2 30 A CU B402-2.1 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: TELECOM 204 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B402IT-2-CR

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 21.8 A

TOTAL CONNECTED AMPS: 31.14 A

Receptacles 0.54 kVA 70.00% 0.378 kVA TOTAL ESTIMATED DEMAND LOAD: 7.852 kVA

Power 10.5 kVA 70.00% 7.35 kVA TOTAL CONNECTED LOAD: 11.22 kVA

Lighting 0.178 kVA 70.00% 0.124 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 36.94 33.92 25.00

Total Load: 4.29 kVA 3.93 kVA 3.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 3 0 -- -- -- 1 20 A SPARE 6 --

3 L21-30R RACK 30 A 3 3 0.75 -- -- -- -- -- -- 4 --

1 TELECOM ROOM REC. 20 A 1 0.54 0.75 2 30 A CU B402-3.1 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: TELECOM 304 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B402IT-3-CR

Revisions: Date:

MDP-208 MDP-208 MDP-208

DP-208-CR DP-208-CR DP-208-CR

FS - FUSED SWITCH

MX - MANUAL SWITCH

MS - MANUAL STARTER

SS - SOLID STATE

RV - REDUCED VOLTAGE AUTOXFMR

SW - 2 SPEED, 1 WINDING

TW - 2 SPEED, 2 WINDING

RE - REVERSING HL - HANDLE PADLOCK HASP

YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR

FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. & (2)-N.C.

STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS

*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR

CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) TS - 2 SPEED SELECTOR SWITCH IN DOOR

NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1 PHASE)

FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) PF - PHASE LOSS PROTECTION (5 HP OR GREATER, 3 PHASE...

DISCONNECT TYPE: ACCESSORIES & OPTIONS

NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.

DISCONNECT AND STARTER SCHEDULE

ITEM

DISCONNECT TYPE &

RATING

CIRCUIT

VOLTAGE POLES

STARTER

ENCLOSURE

REQUIRED ACCESSORIES

& OPTIONS COMMENTSTYPE RATING

NEMA

SIZE TYPE

DS-30R NFU 30 A 208 V 3 NEMA 1 FUSED AT ** AMPS

DS-30R NFU 30 A 208 V 3 NEMA 1 FUSED AT ** AMPS

DS-30R NFU 30 A 208 V 3 NEMA 1 FUSED AT ** AMPS

1309A

1335A 1341

3C12

1319A

S18

1340 1342 1350A 1350 1352 S16 1370 1370A

13553C15 1379

13471345

3C13 3C17

3C14

1315A

403E6A

403E6

S S

S

UP

DN DN

UP

E

B403-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:1

P M

B403-ED111

FIRST FLOOR DEMOLITION -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

02/11/2022 GJL ASQ

16477

N O R

HT

1/8" = 1'-0"

FIRST FLOOR DEMOLITION - ELECTRICAL

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

3C25

3C273C23

2348234623442342

3C29

2361 2362

2361A 2362A

2363 2364

2391A

3C28

2391 2390

2389 2388A

2387A 2388

2387 2386

2386A 2378A

2345 S16

2365 2366

2366A

2367A

C

2357A

2345BS18

3C24

3C26

2345A

3C21

3C22

2326A

2309A 2310A

2303A

2315A

2321A

2327 2326

2323A 2324

2323 2322A

2321 2322

2309 2310

2307 2308

2304A

UP

DN

DN

UP

B403-EP200

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com SES Project :

B

IM

/2

V

A T o m a h

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-7

.B

.E

T

R

.r v t

/8

/2

:2

:2

P M

B403-ED112

SECOND FLOOR DEMOLITION -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, TOMAH, WI

TOMAH, WI

676-700

02/11/2022 GJL ASQ

16477

N O R

HT

1/8" = 1'-0"

SECOND FLOOR DEMOLITION - ELECTRICAL

225 W WASHINGTON STREET

SUITE 2700 CHICAGO, IL 60606

312.294.0501 FAX: 312.294.0003

www.imegcorp.com # 21003227.00

3303A

3303 3304

3304A

3309A

3309 3310

3310A

3315A

3329A

3325A

3328A 3328

3322A

3C32

3C31

3337 3

3C33A

3336 3338 3345A

3C33

3344 3346

3C35

3345B

3357A

3386A

3C38 33863387

A

A

33903391 3391A

3361A

3361 3362

3362A

3367A

3367 3368

3368A

3C39

3365 3366

3370A

3378S16

3C37

S18

3307 3308

UP

DN

DN

B403-EP200