This is a Premise Wiring Guidance document issued by the 81st Communications Squadron at Keesler Air Force Base, Revision F, August 2024. The document serves as supplemental guidance for Local Area Network (LAN) cabling installations and renovations on the base, establishing standards that complement TIA/EIA commercial telecommunications wiring standards.

All premise wiring work on Keesler AFB must comply with TIA/EIA standards and the supplemental requirements outlined in this guidance. Contractors selected for premise wiring projects must have at least one experienced, technically certified BICSI technician on-site and must provide as-built drawings, test results for new or relocated cabling, and restore work areas to original condition. The 81 CS quality assurance office (81 CS/SCQ) serves as the approving authority. New construction or renovation projects require coordination with the 81 CS/SCXP Plans and Programs Office (contact 377-7500) prior to implementation. All copper cables, connectors, ports, jacks, outlets, and patch panels must be TIA/EIA Category 6 rated and compatible with Panduit Mini-Com UTP RJ45 TG Jack Modules. Cables must be color-coded by function: yellow for alarms/cameras, gray for public address systems, red for secure communications, and blue for data/voice. All LAN cabling terminations must use the T-568B standard with pairs untwisted no more than 0.5 inches and cable jackets stripped back no more than 1 inch. Cable management requires metal cable trays in all communication rooms, independent ceiling support every 60 inches maximum, avoidance of fluorescent ballasts and electrical equipment, and use of Velcro or nylon ties (not staples) to protect cable geometry. All labeling must be machine-generated without serifs, in uppercase, and sized for easy readability. Grounding connections must maintain clear bare metal-to-metal contact, and cabinets, racks, and enclosures must each have dedicated bonding conductors rather than serial bonding. The document includes a comprehensive reference list of applicable TIA, NFPA, ANSI, and other standards, plus a detailed QA inspection checklist.

View the file

Other files

File Type Posted
SOW_Title_II_09022026.pdf PDF
Appendix A - Air Force Facilities Sustainability Requirements Scoresheet.xlsx XLSX spreadsheet
Appendix M - Arnold Hall B5901 Restroom As-Builts.pdf PDF
Appendix P - Arnold Hall B5901 Asbestos Inspection Report.pdf PDF
Appendix C - Keesler AFB Installation Facilities Standards (IFS).pdf PDF
Appendix D - Keesler AFB Premise Wiring Guidance.pdf PDF
Appendix E - SWPPP Guidance Manual.pdf PDF
Appendix H - Jones Hall SID Binder.pdf PDF
Appendix H - Jones Hall AFB Drawings Vole 2 of 2_optimized.pdf PDF
Appendix L - Arnold Hall B5901 Drawings.pdf PDF
Appendix N - Arnold Hall B5901 Specifications.pdf PDF
Appendix O - Arnold Hall B5901 Hazardous Material Survey.pdf PDF
RFQD-TII-Jones Hall - 17 Jun 2026.pdf PDF
Appendix B - Air Force Sustainable Design and Development (SDD) Implementing Guidance.pdf PDF
Appendix F - Keesler Architectural Compatibility Guide (ACG).pdf PDF
Appendix K - Jones Hall B6902 Hazardous Material Survey.pdf PDF
Appendix Q - Jones Hall B6902 Hazardous Materials Report.pdf PDF
Appendix A - Air Force Facilities Sustainability Requirements Scoresheet.xlsx XLSX spreadsheet
Appendix G - Jones Hall B6902 DD Form 1391.pdf PDF
Appendix H - Jones Hall RLF Drawings Vol 1 of 2.pdf PDF
Appendix I - Jones Hall B6902 As-Built.pdf PDF
Appendix J - Jones Hall B6902 100 percent Specifications.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PREMISE WIRING GUIDANCE

Revision F, August 2024

This guide is supplemental in nature and not all inclusive.

81st COMMUNICATIONS SQUADRON PREMISE WIRING GUIDANCE

Revision F, 2024 Page 2 of 16

GENERAL

1. The purpose of this document is to supplement Telecommunications Industry Association/Electronic Industry Alliance (TIA/EIA) commercial standards for premise wiring (Local Area Network [LAN] cabling) on Keesler AFB.

2. New construction or renovations programming premise wiring work requires coordination with the 81 CS/SCXP Plans and Programs Office, contact # 377- 7500 prior to implementation.

3. All premise wiring installed on Keesler AFB will conform to TIA/EIA wiring standards listed at the end of this document and the supplemental guidance contained in the attachments within this document.

4. Any deviations from the attached standards and this supplement should be coordinated and approved by the 81 CS/SCXP.

5. Contractual responsibilities:

5.1 Contractors selected to complete premise wiring work must have at least one experienced\technically certified Building Industry Consulting Service International (BICSI) technician on site.

5.2 Provide as-built drawings for the premise wiring work accomplished identifying installation/relocation work.

5.3 Provide test results for new\relocated premise wiring work accomplished.

5.4 Contractors shall be responsible for restoring work areas to original condition.

5.5 81 CS quality assurance office 81 CS/SCQ will be the approving authority for premise wiring work accomplished in new construction or renovations.

Revision F, 2024 Page 3 of 16

RACK 1 RACK 1

RACK 1 RACK 1

RACKS & CABINETS (If installed)

Racks and cabinets will be labeled on the front and rear at the top and bottom on a permanent part of the cabinet/rack. Text on labels shall be machine printed without serifs, uppercase and large enough to be read while standing near the cabinet/rack. The label color will contrast with surface upon which it is affixed (white on a dark surface, black on a light surface)(TIA-606-D-2021, para 5.1.2.6).

Revision F, 2024 Page 4 of 16

Premise Power Requirements

SWITCH TYPE POWER REQUIREMENT

Cisco 9600, 9400 type Two NEMA Locking L6-30 female Plug connectors.

Cisco 9200, 9300 type Four NEMA 5-20R

* Coordinate with 81 CS/SCXP to determine switch requirement.

Revision F, 2024 Page 5 of 16

Cat 5e UTP

CABLING

All copper cables, connectors, ports, jacks, outlets, and patch panels shall be TIA/EIA Category 6 rated and must be compatible with Panduit Mini-Com UTP RJ45 TG Jack Modules.

Cat 6 UTP

Cat 6 FTP

Cat 6A UTP

CABLE COLOR CODING

All installations and renovations will use the following cable color code:

Alarms/Cameras – yellow

Public Address (PA) Systems – gray

Secure Comm (encrypted) – red

Data/Voice - blue

Revision F, 2024 Page 6 of 16

TERMINATIONS

All premise cabling supporting a LAN will be terminated using the T-568B standard. Terminations will be made to available patch panel slots using the standard outlined below and appropriate labeling applied. If no patch panel slots are available a new patch panel will be installed. Deviation from this requirement will be considered on a case-by-case basis i.e., where space for a patch panel is not available.

Pairs will not be untwisted more than .5 inch. Cable jacket will not be stripped back more than 1 inch. No nicks on the inner conductors.

Revision F, 2024 Page 7 of 16

CABLE MANAGEMENT

The Contractor shall ensure a neat and orderly installation utilizing proper cable management IAW current applicable standards. Data drops shall be routed in a manner to ensure the cables are protected and aesthetically pleasing along the cable path. Metal raceways (cable ladder or wire basket) shall be installed and/or utilized in all communication rooms.

• Cable trays shall be installed and/or utilized in all communication rooms.

• Cables will be independently supported off the ceiling with supports no more than 60 inches apart.

• Cable route should avoid fluorescent light ballasts, electrical cables and motors.

Revision F, 2024 Page 8 of 16

CABLE MANAGEMENT (continued)

• Cable jackets must not be distorted. Velcro or nylon are acceptable – Velcro is better at protecting cable geometry. Staples will not be used.

• Any building penetrations (to include wall, ceiling, or floor), shall be in compliance with National Fire Protection Agency (NFPA) regulations and coordinated with CSC’s structural office and fire department.

Revision F, 2024 Page 9 of 16

Example of a single quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

Example of a second quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #5 of the patch panel

OUTLETS

All labeling on outlets shall be machine generated, without serifs, uppercase and large enough to be easily read (TIA-606-D-2021, para 5.1.2.6).

The naming scheme used on top of the outlet provides information on where the drop is terminated on the far end and is broken down into four sections. The naming should read:

“Comm Rm #” – Rack # - Panel # - Port # on Panel

If two drops are installed the top will be the first port number and the bottom will be the second port number. If more that two drops are installed then the numbering will be from left to right starting with the top row. See below for examples.

The bottom label identifies the room number and outlet number in that room. If there is only one drop in the room then the label should read “ROOM # - 1”. If multiple outlets are installed in one room the first outlet shall be identified by standing at the entrance to the room and numbering in a clockwise direction from left to right. The example

Confirm with 81st Communications Squadron (81 CS/SCXP) on the naming of the outlets.

Revision F, 2024 Page 10 of 16

Behind the outlets the cables shall be labeled within 12 inches from the end of the cable jacket. Each cable will be identified by the naming scheme above for each port number where the cable is terminated on the panel.

(Example of data cables labeled within 12 inches from faceplate behind outlet)

PATCH PANELS

All labeling on patch panels shall be machine generated, without serifs, uppercase and large enough to be easily read (TIA-606-D-2021, para 5.1.2.6). The numbering of the panels will start from the top of the rack, or cabinet, down to the last panel installed and shall be installed in the center of the panel.

110-1-1-1

110-1-1-2

110-1-1-3

110-1-1-4

Revision F, 2024 Page 11 of 16

The front of the panels will have the room number, outlet number and network drop identifier under the corresponding port number. See example below for multiple options for labeling ports on a patch panel.

Cables behind the patch panels shall be labeled within 12 inches from the termination point behind the panel. The labels will identify the room number, outlet number and port that the cable is terminated at the far end. Below is an example of what labels should look like behind a patch panel.

Revision F, 2024 Page 12 of 16

GROUNDING

If installed, all grounds will be labeled with information tags similar to the examples below (ANSI/TIA-607-E-2024 para 6.5.2).

All ground connections will have a clear margin of bare metal-to-metal contact (ANSI/TIA-607-B para 7.6).

Cabinets, racks and other enclosures shall not be bonded serially, each shall have their own dedicated bonding conductor (ANSI/TIA-607-E, para 7.1.4).

Example tag, Panduit LTYK Label Kit. Not endorsed

Revision F, 2024 Page 13 of 16

Premise Wiring References

NUMBER TITLE WEBSITE OR LOCATION

BICSI TDM Manual Building Industries Consulting

Services International (BICSI) Telecommunications Distribution Methods (TDM) Manual http://www.bicsi.org/

NFPA 70 (2023) National Fire Protection Association (NFPA), National Electric Code (NEC) http://www.nfpa.org/

29 CFR 1910.268 Occupational Safety and Health Standards, Telecommunications http://www.osha.gov

ANSI American National Standards Institute (ANSI) and Internet Standards Resources http://www.ansi.org/

TIA Telecommunications Industry Association (TIA): TIA Standards See Commodity Specific Appendices and Individual Task Orders https://tiaonline.org/

TIA-526-7-A (Jul 2015) Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568.0-E

(Mar 2020)

Generic Telecommunications Cabling for Customer Premises https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568 SET (Mar 2020)

Commercial Building Telecommunications Cabling Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568.2-D

(Sep 2018)

Balanced Twisted-Pair Telecommunications Cabling and Components Standard http://www.tiaonline.org/

TIA-568.3-E

(Sep 2022)

Optical Fiber Cabling and Components Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

ASTM D4566-20 Standard Test Methods for Electrical Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable http://webstore.ansi.org/

TIA-569-E (May 2019) Telecommunications Pathways and Spaces https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-570-E (May 2024) Residential Telecommunications Cabling Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-598-D (Jul 2014) Optical Fiber Cable Color Coding https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-606-D (Oct 2021) Administration Standard for Telecommunications Infrastructure https://global.ihs.com/csf_hom e.cfm?&csf=TIA http://www.bicsi.org/ http://www.nfpa.org/ http://www.osha.gov/ http://www.ansi.org/ http://www.tiaonline.org/ http://webstore.ansi.org/

Revision F, 2024 Page 14 of 16

TIA-607-E

(May 2024)

Telecommunications Bonding and Grounding (Earthing) for Customer Premises https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA/EIA-758-B

(Mar 2012)

Customer-Owned Outside Plant Telecommunications Infrastructure Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

EIA/ECA-310-E

(Dec 2005)

Racks, Panels and Associated Equipment https://standards.globalspec.c om/std/195405/EIA/ECA-310

ICEA S-80-576 (2002) Category 1 & 2 Individually Unshielded Twisted Pair Indoor Cables for Use in Communications Wiring Systems https://www.techstreet.com/ice a/searches/33123596

ICEA S-83-596-2016 Fiber Optic Premises Distribution Cable https://www.techstreet.com/ice a/subgroups/54441

GR-409, Issue 2 (Nov 2008)

Generic Requirements for Indoor Fiber Optic Cable https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=21553131 5SEARCH&DOCUMENT=gr

GR-20, Issue 4 (July 2013)

Generic Requirements for Optical Fiber and Optical Fiber Cable https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=21553131 5SEARCH&DOCUMENT=gr

NEMA TC 2-2020 Electrical Polyvinyl Chloride (PVC) Conduit http://www.nema.org/stds/tc2.cfm

NEMA TC 6&8-2020 PVC Plastic Utilities Duct for Underground Installations http://www.nema.org/stds/tc6_8.c fm

NEMA TC 9-2020 Fittings for PVC Plastic Utilities Duct for Underground Installation http://www.nema.org/stds/tc9.cfm

RUS Bulletin 1751F-

Underground Plant Design https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 51F-643.pdf

RUS Bulletin 1751F-

Underground Plant Construction https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 51F-644.pdf

RUS Bulletin 1753F-

801(PC-5A)

RUS Standard for Service Installations at Customer Access Locations https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 53F-801.pdf

RUS Bulletin 1753F-

401 (PC-2)

RUS Standards for Splicing Copper and Fiber Optic Cable https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 53F-401.pdf

RUS Bulletin 1753F- 601a

RUS Specifications for Fiber Optic Cables (PE-90a) https://www.rd.usda.gov/files/ UTP_Bulletins_1753F- 601a.pdf http://www.techstreet.com/ice http://www.techstreet.com/ice http://www.nema.org/stds/tc2.cfm http://www.nema.org/stds/tc6_8.c http://www.nema.org/stds/tc9.cfm http://www.rd.usda.gov/sites/ http://www.rd.usda.gov/sites/ http://www.rd.usda.gov/sites/ http://www.rd.usda.gov/sites/ http://www.rd.usda.gov/files/

Revision F, 2024 Page 15 of 16

Premise Wiring Guide Checklist

Below is a complementary checklist base on this guidance to assist on what could be inspected by a Quality Assurance Evaluator. Consult the Statement of Objectives and the 81CS/SCXP Plans and Programs Office as this checklist is may not be all-inclusive to the work agree upon.

YES NO N/A

RACKS/CABINETS

Is the rack/cabinet that was installed labeled on the front and rear at the top and bottom on a permanent part of the rack/cabinet?

Are the placed labels machine printed without serifs, uppercased and large to read while standing near the rack/cabinet?

Does the label color contrast with the surface of the rack/cabinet?

PREMISE POWER REQUIREMENTS

Does the installed power outlets match the switch/equipment requirements as identified by 81CS/SCXP?

CABLING

Are all copper cables, connectors, ports, jacks, outlets and patch panels rated for TIA/EIA Category 6?

Are all copper cables, connectors, ports, jacks and outlets compatible with Panduit Mini-Com RJ45 TG jack Modules?

Are installed cables matching the appropriate color code as outlined on page 5 of this guide?

TERMINATIONS

Are premise cabling supporting a LAN terminated using the T-568B standard on the connector(s) AND/OR patch panel(s)?

Are all conductor pairs NOT untwisted more that .5 inches?

Are all cable jacked NOT stripped back more that 1 inch?

CABLE MANAGEMENT

Are all network cables laid neat and orderly during installation, utilizing proper cable management IAW current applicable standards?

Are data drops routed in a manner to ensure the cables are protected and aesthetically pleasing along the cable path?

Are metal raceways (cable ladders or wire baskets) installed and/or utilized in all communication rooms?

Are cables trays installed and/or utilized in all communication rooms?

Are installed cables independently supported off the ceiling with supports no more than 60 inches apart?

If able, are cables routed to avoid fluorescent light ballasts, electrical cables and motors?

Are Velcro or nylon cable ties installed in a manner to avoid distorting the cable jacket?

Are all building penetrations that were utilized during installation compliant with NFPA regulations and coordinated with CSC’s structural office and fire department?

Revision F, 2024 Page 16 of 16

(CONTINUED) YES NO N/A

OUTLETS

Are all labels machine generated, without serifs, uppercase and large enough to be easily read?

Are all outlets labeled using the approved naming scheme and following the examples on page 9 of this guide?

Are outlets numbered appropriately to the location in the room as instructed on page 9 of this guide?

Are machine generated labels placed on each cable within 12 inches from the faceplate as instructed on page 10 of this guide?

PATCH PANELS

Are all labels machine generated, without serifs, uppercase and large enough to be easily read?

Are panel numbered in order starting from the top of the rack down to the last panel?

Are the front panel ports labeled with room number, outlet number and network drop identifier under the corresponding port number?

Are terminated cables labeled within 12 inches from the end of the cable with the room number, outlet number and port identifier?

GROUNDING

Are newly installed grounds labeled with information tags?

Do ground connections have a clear margin of bare metal-to-metal contact?

Are newly installed cabinets, racks and/or other enclosures bonded with their own dedicated bonding conductor and NOT serially?

GENERAL
Premise Power Requirements
CABLING
TERMINATIONS
CABLE MANAGEMENT
OUTLETS
PATCH PANELS
GROUNDING