Appendix P - Arnold Hall B5901 Asbestos Inspection Report.pdf
PDF 465 KB Posted
- Solicitation number
- FA890326R0069
About this file
This is an Asbestos Inspection Report dated June 16, 2016, documenting a limited asbestos survey conducted at Keesler Air Force Base (KAFB) Building 5901 in Biloxi, Mississippi.
The inspection was performed on June 14-15, 2016, by Clifford Meins, a Mississippi-certified asbestos inspector (Cert. #ABI-00001821, expiration 10/8/2016) representing Micro-Methods Laboratory Inc. Four samples were collected from thermal insulation materials on chill water lines and related components within the building. All samples—identified as black non-friable materials containing glass fibers and binders—tested negative for asbestos content. The report concludes that no asbestos-containing materials were identified during the inspection. The work order number is 1606296, and the contact for questions is Dave Bingham, Industrial Hygiene Supervisor. The inspection was conducted in compliance with State of Mississippi NESHAP regulations and included a limited visual survey focusing on detection of visible suspect materials, with laboratory analysis performed per client request.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B re n t
E an es
P A
E K ee sl er A
F B
L
S t.
B ld g
K ee sl er
A ir
F o rc e
B as e, M
S
R E
A sb es to s
In sp ec ti o n
A sb es to s In sp ec ti o n
R ep o rt
E n cl o se d a re t h e re su lt s o f th e su rv ey p er fo rm ed b y t h e in d u st ri al h y g ie n e d ep ar tm en t o n
/1
/2
I f y o u h av e an y q u es ti o n s co n ce rn in g t h is r ep o rt p le as e fe el f re e to c o n ta ct D av e
B in g h am
In d u st ri al
H y g ie n e
S u p er v is o r.
W o rk O rd er
Ju n e
D ea r B re n t E an es
S u n p le x
D ri v e
O ce a n
S p ri n g s, M S
.8
.6
P h o n e
.8
.6
F a x
K A
F B
B ld g
H a rr y P
H o w e ll
P re s id e n t
M a il in g A d d re ss
P O
B o x
O ce a n
S p ri n g s, M S
-1
Asbestos Survey Report
Summary Comments:
On 6/15/2016 Clifford Meins, Representative of Micro-Methods Laboratory Inc. performed a limited asbestos inspection of thermal insulation materials at building 5901 of Keesler AFB, Biloxi, Mississippi. The following is a summary of the findings.
Findings:
No asbestos containing materials were identified at the time of this inspection.
MS Certified Asbestos Inspector
Clifford Meins
Cert. # ABI-00001821 Exp. 10/8/2016
PAE Keesler AFB
06/14/16
Micro-Methods Laboratory, Inc.Laboratory:
Lab Contact:
Date Reported:
Asbestos Inspection
Tina Tomek For Charles D. Bingham
Client:
Client Reference:
Log-In:
PO Number:
6/16/2016
KAFB Bldg. 5901
Sample No: Client ID:1606296-01 01 Chill Water Line Elbow
Macroscopic
Description
No. of Layers and Layer
Designator
Percent of
Total Sample Non-Fibrous
Components*
Other Fibrous Non-
Asbestos Content
Total or Layer % Footnotes
Asbestos Content
Total or Layer %
Footnotes
Analytical
Date
Black non-friable 1 100 3 Glass Fibers 2 06/16/16None Detected
Sample No: Client ID:1606296-02 02 Chill Water Line
Macroscopic
Description
No. of Layers and Layer
Designator
Percent of
Total Sample Non-Fibrous
Components*
Other Fibrous Non-
Asbestos Content
Total or Layer % Footnotes
Asbestos Content
Total or Layer %
Footnotes
Analytical
Date
Black non-friable 1 100 3 Glass Fibers 2 06/16/16None Detected
Sample No: Client ID:1606296-03 03 Chill Water Line Above the Valve
Macroscopic
Description
No. of Layers and Layer
Designator
Percent of
Total Sample Non-Fibrous
Components*
Other Fibrous Non-
Asbestos Content
Total or Layer % Footnotes
Asbestos Content
Total or Layer %
Footnotes
Analytical
Date
Black non-friable 1 100 3 06/16/16None Detected
Sample No: Client ID:1606296-04 04 Chill Water Line
Macroscopic
Description
No. of Layers and Layer
Designator
Percent of
Total Sample Non-Fibrous
Components*
Other Fibrous Non-
Asbestos Content
Total or Layer % Footnotes
Asbestos Content
Total or Layer %
Footnotes
Analytical
Date
Black non-friable 1 100 3 06/16/16None Detected
The results in this report apply to the samples analyzed in accordance with the chain of custody document. This analytical report must be reproduced in its entirety.
PAE Keesler AFB
06/14/16
Micro-Methods Laboratory, Inc.Laboratory:
Lab Contact:
Date Reported:
Asbestos Inspection
Tina Tomek For Charles D. Bingham
Client:
Client Reference:
Log-In:
PO Number:
6/16/2016
KAFB Bldg. 5901
Footnotes and Definitions A-bnf Black non-friable
* Key to Non-Fibrous Components
1 = Rock/Mineral fragments 5 = Diatoms 9 = Vinyl 13 = Spores/Pollen
2 = Mica/Vermiculite 6 = Perlite 10 = Foam/Rubber 14 = Foil
3 = Binders 7 = Adhesive/Mastic 11 = Paint
4 = Opaques 8 = Tar 12 = Other
< Less Than
> Greater Than
The scope of services included a limited visual survey of the property. The survery focuses on the detection of visible suspect asbestos materials. The results of this survey are presented in the following report.
In addition to the visual survery, if asbestos samples were taken per client request, the results of completed laboratory analysis are included as an attachment to this report. Often materials are located in confined or inaccessible locations with little or no visible manifestation of their presence. These materials may be found in various areas such as under existing flooring materials, above ceilings, behind walls, materials within fixtures, electrical wiring casing, or buried pipes and wires. Because of the potential for hidden materials, it may not be possible to determine whether all suspect building materials have been identified, located, and subsequently tested. Destructive measures to access these potentially hidden materials were not employed by Micro-Methods Laboratory, Inc. as a part of this project. However, Micro-Methods Laboratory,Inc. does warrant that its investigations and methodology reflect our best efforts upon the prevailing standard of care in the environmental industry and the clients scope of work. It is not intended that the scope and/or cost of remedial action is to recommended or defined based on the results and recommendations made by this inspector. The results relative to this inspection are applicable to the single structure that is inspected. Detached structures should be inspected and reported separately. Based on the the opinion, judgment, and experience of the inspector, it is their discretion to determine the location and quantity of samples taken, including but not limited to collection of non-suspect samples. Inspections performed pursuant to this standard rely upon the opinon, judgment, and experience of the inspector, and are not intended to be technically exhaustive. Based on the opinion, judgment, and experience of the inspector, recommendation of additional inspections may be appropriate based on factors outside the data interpretation contained in this inspection. In the event a law, statue, or ordinance prohibits a procedure recommended in the standard, the inspector is relieved of the obligation to adhere to the prohibited part of the inspection.
This inspection was conducted according to the State of Mississippi NESHAP regulations by a state certified asbestos inspector.
The results in this report apply to the samples analyzed in accordance with the chain of custody document. This analytical report must be reproduced in its entirety.