This document is the 81st Communications Squadron Premise Wiring Guidance, Revision G (August 2023), which serves as supplemental technical guidance for Local Area Network cabling installations at Keesler Air Force Base.

The guidance mandates that all premise wiring installations conform to TIA/EIA commercial standards and requires coordination with the 81 CS/SCXP Plans and Programs Office prior to implementation. Contractors must employ at least one BICSI-certified technician and deliver as-built drawings, test results, and restore work areas upon completion. All copper cabling must be Category 6 rated and compatible with Panduit Mini-Com UTP RJ45 TG Jack Modules, with specific color coding applied: purple for cameras, gray for public address systems, red for secure communications, blue for data/voice, yellow for Keesler Technical Training Environment, and pink for AWAKEN systems (excluding SCIFs). Terminations must follow 568B standards with pairs untwisted no more than 0.5 inches and cable jacket stripped back no more than 1 inch. Cable management requires metal cable trays in communication rooms, independent ceiling support at intervals no greater than 60 inches apart, avoidance of fluorescent ballasts and electrical cables, and use of Velcro or nylon ties rather than staples. Labeling must be machine-generated, uppercase, sans-serif, and coordinated with 81 CS/SCXP. Power requirements vary by switch type: Cisco 9600/9400 switches require two NEMA Locking L6-30 female plugs, while Cisco 9200/9300 switches require four NEMA 5-20R outlets. The 81 CS/SCQ quality assurance office serves as the approving authority for all work.

View the file

Other files

File Type Posted
SOW_Title_II_09022026.pdf PDF
Appendix A - Air Force Facilities Sustainability Requirements Scoresheet.xlsx XLSX spreadsheet
Appendix M - Arnold Hall B5901 Restroom As-Builts.pdf PDF
Appendix P - Arnold Hall B5901 Asbestos Inspection Report.pdf PDF
RFQD-TII-Jones Hall - 17 Jun 2026.pdf PDF
Appendix B - Air Force Sustainable Design and Development (SDD) Implementing Guidance.pdf PDF
Appendix F - Keesler Architectural Compatibility Guide (ACG).pdf PDF
Appendix K - Jones Hall B6902 Hazardous Material Survey.pdf PDF
Appendix Q - Jones Hall B6902 Hazardous Materials Report.pdf PDF
Appendix R - Premise Wiring Guidance.pdf PDF
Appendix C - Keesler AFB Installation Facilities Standards (IFS).pdf PDF
Appendix E - SWPPP Guidance Manual.pdf PDF
Appendix H - Jones Hall SID Binder.pdf PDF
Appendix H - Jones Hall AFB Drawings Vole 2 of 2_optimized.pdf PDF
Appendix L - Arnold Hall B5901 Drawings.pdf PDF
Appendix N - Arnold Hall B5901 Specifications.pdf PDF
Appendix O - Arnold Hall B5901 Hazardous Material Survey.pdf PDF
Appendix A - Air Force Facilities Sustainability Requirements Scoresheet.xlsx XLSX spreadsheet
Appendix G - Jones Hall B6902 DD Form 1391.pdf PDF
Appendix H - Jones Hall RLF Drawings Vol 1 of 2.pdf PDF
Appendix I - Jones Hall B6902 As-Built.pdf PDF
Appendix J - Jones Hall B6902 100 percent Specifications.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PREMISE WIRING GUIDANCE

Revision G, August 2023

This guide is supplemental in nature and not all inclusive.

81st COMMUNICATIONS SQUADRON PREMISE WIRING GUIDANCE

Revision G, 2023 Page 2 of 13

GENERAL

1. The purpose of this document is to supplement Telecommunications Industry Association/Electronic Industry Alliance (TIA/EIA) commercial standards for premise wiring (Local Area Network cabling) on Keesler AFB.

2. New construction or renovations programming premise wiring work requires coordination with the 81 CS/SCXP Plans and Programs Office, contact # 377- 7500 prior to implementation.

3. All premise wiring installed on Keesler AFB will conform to TIA/EIA wiring standards listed at the end of this document and the supplemental guidance contained in the attachments within this document.

4. Any deviations from the attached standards and this supplement should be coordinated and approved by the 81 CS/SCXP.

5. Contractual responsibilities:

5.1 Contractors selected to complete premise wiring work must have at least one experienced\technically certified Building Industry Consulting Service International (BICSI) technician on site.

5.2 Provide as-built drawings for the premise wiring work accomplished identifying installation/relocation work.

5.3 Provide test results for new\relocated premise wiring work accomplished.

5.4 Contractors shall be responsible for restoring work areas to original condition.

5.5 81 CS quality assurance office 81 CS/SCQ will be the approving authority for premise wiring work accomplished in new construction or renovations.

Revision G, 2023 Page 3 of 13

RACKS/CABINETS (If installed)

Cabinets/Racks will be labeled on the front and rear at the top and bottom on a permanent part of the cabinet/rack. Text on labels shall be machine printed without serifs, uppercase and large enough to be read while standing near the cabinet/rack. The label color will contrast with surface upon which it is affixed (white on a dark surface, black on a light surface)(ANSI/TIA/EIA-606-A-1 section 11).

RACK 1 RACK 1

RACK 1 RACK 1

Revision G, 2023 Page 4 of 13

Premise Power Requirements

SWITCH TYPE POWER REQUIREMENT

Cisco 9600, 9400 type Two NEMA Locking L6-30 female Plug connectors.

Cisco 9200, 9300 type Four NEMA 5-20R

* Coordinate with 81 CS/SCXP to determine switch requirement.

Revision G, 2023 Page 5 of 13

CABLING

All copper cables, connectors, ports, jacks, outlets, and patch panels shall be TIA/EIA Category 6 rated and must be compatible with Panduit Mini-Com UTP RJ45 TG Jack Modules.

Cat 6 UTP

Cat 6 FTP

Cat 6A UTP

CABLE COLOR CODING

All installations and renovations will use the following cable color code:

DOES NOT APPLY TO SCIFS

Cameras – purple Public Address (PA) Systems – gray

Secure Comm (encrypted) – red

Data/Voice - blue

Keesler Technical Training Environment (KTTE) - yellow AWAKEN (LWS) - Pink

Cat 5e UTP

Revision G, 2023 Page 6 of 13

TERMINATIONS

All premise cabling supporting a Local Area Network will be terminated using 568B standards. Terminations will be made to available patch panel slots using the standard outlined below and appropriate labeling applied. If no patch panel slots are available a new patch panel will be installed. Deviation from this requirement will be considered on a case-by-case basis i.e., where space for a patch panel is not available.

Pairs will not be untwisted more than .5 inch. Cable jacket will not be stripped back more than 1 inch. No nicks on the inner conductors.

Revision G, 2023 Page 7 of 13

CABLE MANAGEMENT

The Contractor shall ensure a neat and orderly installation utilizing proper cable management IAW current applicable standards. Data drops shall be routed in a manner to ensure the cables are protected and aesthetically pleasing along the cable path. Metal raceways (cable ladder or wire basket) shall be installed and/or utilized in all communication rooms.

Cable trays shall be installed and/or utilized in all communication rooms.

Cables will be independently supported off the ceiling with supports no more than 60 inches apart.

Cable route should avoid fluorescent light ballasts, electrical cables and motors.

Revision G, 2023 Page 8 of 13

CABLE MANAGEMENT (continued)

Cable jackets must not be distorted. Velcro or nylon are acceptable – Velcro is better at protecting cable geometry. Staples will not be used.

Any building penetrations (to include wall, ceiling, or floor), shall be in compliance with National Fire Protection Agency (NFPA) regulations and coordinated with CSC’s structural office and fire department.

Revision G, 2023 Page 9 of 13

LABELING

All labeling shall be machine generated, without serifs, uppercase and large enough to be easily read (ANSI/TIA/EIA-606-A-1 section 11).

The naming scheme shall also be coordinated with the 81st Communications Squadron (81 CS/SCXP).

Outlet(s)

Patch Panel(s)

Example of RACK 1 PANEL 1 located in TR 110 and connecting to Room 32 Outlets 1 and 2.

Example of a single quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

Example of a second quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #5 of the patch panel

32-1 A B C D

32-2 A B C D

Revision G, 2023 Page 10 of 13

LABELING (continued)

Cables - All cables will be labeled on both ends with encoded identifiers per (ANSI/TIA/EIA-606-A-1 section 11).

(located within 12 inches of faceplate) (located within 12 inches of patch panel)

110-1-1-1 32-1-A

32-1-B

110-1-1-3 32-1-C

110-1-1-4 32-1-D

RACK 1

Example of a single quad data outlet located in room 32 and terminated in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

110-1-1-2

Revision G, 2023 Page 11 of 13

GROUNDING (TIA-607-B) (If installed)

All grounds will be labeled (ANSI/TIA-607-B para 7.8) (if installed).

All ground connections will have a clear margin of bare metal-to-metal contact (ANSI/TIA-607-B para 7.6).

Cabinets, racks and other enclosures shall not be bonded serially, each shall have their own dedicated bonding conductor (ANSI/TIA-607-B para 7.1.4).

Revision G, 2023 Page 12 of 13

Premise Wiring References

NUMBER TITLE WEBSITE OR LOCATION

BICSI TDM Manual Building Industries Consulting Services International (BICSI) Telecommunications Distribution Methods (TDM) Manual http://www.bicsi.org/

NFPA 70 (2008) National Fire Protection Association (NFPA), National Electric Code (NEC) http://www.nfpa.org/

29 CFR 1910.268 Occupational Safety and Health Standards, Telecommunications http://www.osha.gov

ANSI American National Standards Institute (ANSI) and Internet Standards Resources http://www.ansi.org/

TIA Telecommunications Industry Association (TIA): TIA Standards See Commodity Specific Appendices and Individual Task Orders https://tiaonline.org/

TIA-526-7 (Jul 2015) Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568.0

(Mar 2020)

Generic Telecommunications Cabling for Customer Premises https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568 SET (Mar 2020)

Commercial Building Telecommunications Cabling Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568.2

(Sep 2018)

Balanced Twisted-Pair Telecommunications Cabling and Components Standard http://www.tiaonline.org/

TIA-568.3 (Oct 2016) Optical Fiber Cabling and Components Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

ASTM D4566-20 Standard Test Methods for Electrical Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable http://webstore.ansi.org/

TIA-569 (May 2019) Telecommunications Pathways and Spaces https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-570 (Jul 2018) Residential Telecommunications Cabling Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-598 (Jul 2014) Optical Fiber Cable Color Coding https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-606 (Oct 2021) Administration Standard for Telecommunications Infrastructure https://global.ihs.com/csf_hom e.cfm?&csf=TIA

Revision G, 2023 Page 13 of 13

TIA-607

(Jul 2019)

Commercial Building Grounding and Bonding Requirements for Telecommunications https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA/EIA-758 (Mar 2012)

Customer-Owned Outside Plant Telecommunications Infrastructure Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

EIA/ECA-310 (Dec 2005)

Racks, Panels and Associated Equipment https://standards.globalspec.c om/std/195405/EIA/ECA-310

ICEA S-80-576 (2002) Category 1 & 2 Individually Unshielded Twisted Pair Indoor Cables for Use in Communications Wiring Systems https://www.techstreet.com/ice a/searches/33123596

ICEA S-83-596-2016 Fiber Optic Premises Distribution Cable https://www.techstreet.com/ice a/subgroups/54441

GR-409, Issue 2 (Nov 2008)

Generic Requirements for Indoor Fiber Optic Cable https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=21553131 5SEARCH&DOCUMENT=gr

GR-20, Issue 4 (July 2013)

Generic Requirements for Optical Fiber and Optical Fiber Cable https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=21553131 5SEARCH&DOCUMENT=gr

NEMA TC 2-2020 Electrical Polyvinyl Chloride (PVC) Conduit http://www.nema.org/stds/tc2.cfm

NEMA TC 6&8-2020 PVC Plastic Utilities Duct for Underground Installations http://www.nema.org/stds/tc6_8.c fm

NEMA TC 9-2020 Fittings for PVC Plastic Utilities Duct for Underground Installation http://www.nema.org/stds/tc9.cfm

RUS Bulletin 1751F-

Underground Plant Design https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 51F-643.pdf

RUS Bulletin 1751F-

Underground Plant Construction https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 51F-644.pdf

RUS Bulletin 1753F-

801(PC-5A)

RUS Standard for Service Installations at Customer Access Locations https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 53F-801.pdf

RUS Bulletin 1753F-

401 (PC-2)

RUS Standards for Splicing Copper and Fiber Optic Cable https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 53F-401.pdf

RUS Bulletin 1753F- 601a

RUS Specifications for Fiber Optic Cables (PE-90a) https://www.rd.usda.gov/files/ UTP_Bulletins_1753F- 601a.pdf

File details come from the government source that posted it. Updated .