Appendix K - Hydrant Inspection and Flow Test Data Bldg 10701.pdf
PDF 205 KB Posted
- Attached to
- 99 CES Fire Suppression Certification
- Solicitation number
- FA486126Q0025
About this file
This is a Fire Hydrant Inspection and Flow Test Record documenting the inspection and testing of Fire Hydrant #155 located in Area II near Building 10150 at Nellis Air Force Base (99th CES). The inspection was completed on November 6, 2019, by Inspector LOVE-G and is conducted on a five-year basis in accordance with Unified Facilities Criteria (UFC) 3-600-02 and National Fire Protection Association 25 standards.
The inspection encompasses multiple components including verification of the dry hydrant's accessibility, leaks, and worn threads; operational testing of yard monitor nozzles; examination of hose house conditions and valve functionality; and comprehensive flow testing. The Mueller brand hydrant (Model No. 531, manufactured in 1997) was tested and verified to be operational and in proper working condition. Key flow test results include a static pressure of 110 PSI, residual pressure primary of 20 PSI, residual pressure secondary of 0.9 PSI, pitot pressure of 10 PSI, and a total flow during test of 591 GPM at a 2.5-inch outlet size with 0.9 coefficient. All inspection checklist items were marked complete with "X" marks, including verification that the hydrant was left in service. The water pressure-flow curve graph plots the relationship between flow (in GPM) and pressure (in PSI), showing the hydrant's performance characteristics with measurements at 531 GPM and 591 GPM points.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Y N/A N Y N/A N
A-1.0 D-1.0
A-1.1 X D-1.1 X
A-1.2 X
A-1.3
D-1.3 X A-1.4 X
B-1.0
B-1.1 X
B-1.2
B-1.3 X
C-1.0
C-1.1 X
C-1.2 X
D-1.9 Hydrant left in Service X
2.5
GPM
Inspector's Initial __________
Date Completed: 6 NOV 2019
RWP Number:
OUTLET
SIZE COEFFICIENT SIZE
NO. 531
RESIDUAL PRESSURE PRIMARY RESIDUAL PRESSURE SECONDARY
Date: ____________________
WATER FLOW GPM
AT 0 PSIAT 20 PSI RESIDUAL
GPM591531
(All "NO" answers to be fully explained.)
Mueller
WFSM Shop 652-4815
Nellis AFB 99th CES
STATIC PRESSURE
HYDRANT NUMBER PITOT PRESSURE
MANUFACTURER
TOTAL FLOW DURING TEST
AREA II - NEAR BLDG. 10150
0.9
YEAR
WATER FLOW TEST RECORD
Inspection of Hose Houses:
Inspected for accessibility and condition D-1.8 Verified that all valves closed properly, are not seeping or leaking X
Verified inventory and its condition
CLASS B ORANGE
X
Lubricated to ensure proper operating conditions D-1.7 Closed the hydrant slowly being careful not to cause a "water hammer" and spike the pressure above the normal static pressure on the gauge at the secondary location X
Conducted flow test to verify proper function and range of motion X
D-1.6 Took and recorded the residual pressure at the secondary location
Inspection of Yard Monitor Nozzles: D-1.5 Took and recorded the residual pressure on the hydrant cap gauge X
Inspected for condition
Lubricated Hydrant to ensure ease of operation D-1.4 Completely opened hydrant, took and recorded a pitot reading X
X Verified drainage of barrel (after all operations and before cold weather) X
Attached diffuser to hydrant being tested
Flow Testing Hydrant:
Inspected for accessibility, leaks, and worn threads Attached pressure gauge to outlet STATIC
Operated to ensure proper functioning D-1.2 Attached pressure gauge to adjacent hydrant and take reading (should be the same)
INSPECTION AND FLOW TEST
Fire Hydrants
The Following inspection and flow testing tasks are to be performed on a 5 YEAR basis. These tasks are guidelined under the Unified Facilities Criteria (UFC) 3-600- 02 and National Fire Protection Assocation 25
ALL QUESTIONS ARE TO BE FULLY ANSWERED AND ALL BLANKS TO BE FILLED
LOCATION/BUILDING NUMBER:
Inspector Name: LOVE-G
Comments:
Fire Hydrant # 155
Inspection of Dry Hydrant:
0 500 1000
Pr es su re
, p si g
Flow, gpm
Data