This is a design specification document for fire protection systems at a Hydrazine Fuel Storage and Servicing Facility. The document outlines comprehensive fire protection requirements across multiple building systems and references applicable federal and industry standards including UFC 3-600-01, NFPA codes, and DoD specifications.

The facility requires an automatic wet pipe sprinkler suppression system designed per UFC 3-600-01 and NFPA 13, with a Double Check valve assembly or Reduced Pressure Principle Backflow Preventer. The system must accommodate multiple occupancy classifications: Light Hazard (Office and Restroom) at 0.1 gpm/sf, Ordinary Hazard (Mechanical and Electrical Rooms) at 0.2 gpm/sf, Extra Hazard Group 2 (Service Area) at 0.4 gpm/sf, and Storage (Class II Liquid) at 0.45 gpm/sf. The total building sprinkler area is 863 square feet with an estimated fire water flow rate of 320 gpm plus 500 gpm for fire hose allowance. A 6-foot fire water connection will be provided at the Fire Riser room, sourced from site water distribution. A fire alarm and mass notification system must be integrated with the sprinkler system, featuring addressable circuits, radio transceiver connectivity to the base fire department, audio/visual signals (75 dB minimum with dual strobes for fire and mass notification), and battery backup power. The Fire Alarm & Mass Notification panel will be located in the Electrical Room. Additional fire protection elements include fire hydrants connected to site water distribution and duct smoke detectors at air handling units providing full alarm activation per NFPA 90A.

View the file

Other files

File Type Posted
Appendix N - RKMF173010 BLDG 10707 Fire Sprinkler Shop Drawings.pdf PDF
Appendix K - 2025 Hydrant Inspection and Flow Test Data Bldg 10707.pdf PDF
Solicitation Questions and Answers.pdf PDF
Attachment 1 - Solicitation - FA486126Q0025.pdf PDF
Appendix E - Nellis and Creech AFB IFS_22 Jan 2019.pdf PDF
Appendix C - RKMF103011 BLDG 10432 Fire Sprinkler Shop Drawings.pdf PDF
Appendix A - RKMF 173010 As Built Drawings Sections Fire Plumbing.pdf PDF
Attachment 4 - Performance_Work_Statement__Fire_Suppression_Certification - CAO 25AUG26.pdf PDF
Attachment 2 - Price List.pdf PDF
Appendix D - RKMF103011 BLDG 10440 Fire Sprinkler Shop Drawings.pdf PDF
Appendix B - RKMF 103011 F-35 Muns As Built Drawings Sections Fire Plumbing.pdf PDF
Appendix H - Environmental Permit Guidance.pdf PDF
Attachment 5 - SCA Wage Determination 2015-5593 Revision 32 - CAO 22 AUG 26.pdf PDF
Appendix F - Nellis and Creech AFB IFS Mech-Plumb Req_29 Dec 2025.pdf PDF
Appendix M - Hydrant Inspection and Flow Test Data Bldg 10440.pdf PDF
Appendix I - Hydrazine Fuel Storage and Servicing Facility Specification 2144.pdf PDF
Appendix G - Nellis AFB Sole Source EMCS Letter.pdf PDF
Appendix K - Hydrant Inspection and Flow Test Data Bldg 10701.pdf PDF
Appendix L - Hydrant Inspection and Flow Test Data Bldg 10432.pdf PDF
Attachment 3 - Past Performance List of References.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UFC 3-600-01, Design: Fire Protection Engineering for Facilities

UFC 3-460-01, Petroleum Fuel Facilities

NFPA 13, Installation of Sprinkler Systems

NFPA 20, Installation of Stationary Pumps

NFPA 22, Water Tank for Private Fire Protection

NFPA 30, Flammable and Combustible Liquids

NFPA 400, Hazardous Materials

AFMAN 91-201, Explosives Safety Standards

Installation Development and Design (ID2) Handbook

UFC 3-600-01 NFPA 13

NFPA 13 and UFC 3-600-01

UFC 3-600-01, Fire Protection Engineering for Facilities

UFC 4-010-01, DoD Minimum Antiterrorism Standards for Buildings

UFC 4-021-01, Design and O&M Mass Notification Systems

NFPA 72, National Fire Alarm and Signaling Code

NFPA 90A,

File details come from the government source that posted it. Updated .