SEISMIC BRACING REQUIREMENTS
EARTHQUAKE PROTECTION NOTES:
A. ALL EARTHQUAKE BRACING TO BE IN ACCORDANCE WITH NFPA-13 2007 OR CURRENT EDITION APPROVED BY
LOCAL AHJ.
B. LISTED FLEXIBLE COUPLINGS SHALL ONLY BE INSTALLED WHERE REQUIRED BY NFPA-13.
C. FLEXIBLE COUPLINGS SHALL BE LOCATED IN ACCORDANCE WITH NFPA-13 AS FOLLOWS:
1. WITHIN 24" FROM THE TOP AND BOTTOM OF ALL RISERS.
2. WITHIN 12" ABOVE AND 24" BELOW FLOORS IN MULTISTORY BUILDINGS.
3. WITHIN 1' OF ALL CONCRETE AND MASONRY WALL PENETRATIONS UNLESS CLEARANCE IS PROVIDED BY
SECTION 9.3.4.
4. WITHIN 24" OF BUILDING EXPANSION JOINTS.
5. WITHIN 24" OF THE TOP OF DROPS EXCEEDING 15' IN LENGTH TO PORTIONS OF SYSTEMS SUPPLYING MORE
THAN ONE SPRINKLER, REGARDLESS OF SIZE
6. ABOVE AND BELOW ANY INTERMEDIATE POINTS OF SUPPORT FOR A RISER OR OTHER VERTICAL PIPE.
1. CLEARANCE SHALL BE PROVIDED AROUND ALL PIPING EXTENDING THROUGH WALLS, FLOORS, PLATFORMS, AND FOUNDATIONS, INCLUDING DRAINS, FDCS, AND OTHER AUXILIARY PIPING PER SECTION 9.3.4 OR FLEXIBLE
COUPLINGS SHALL BE PROVIDED.
2. LONGITUDINAL SWAY BRACING SPACED AT A MAXIMUM OF 80 FEET SHALL BE PROVIDED FOR FEED AND CROSS
MAINS AND NOT MORE THAN 40 FEET FROM THE END.
3. TOPS OF RISERS OVER 3 FEET SHALL BE SECURED AGAINST DRIFTING IN ANY DIRECTION USING A 4-WAY
BRACE.
4. LATERAL SWAY BRACING SPACED AT A MAXIMUM OF 40 FEET SHALL BE PROVIDED FOR FEED AND CROSS
MAINS.
5. BRACING SHALL BE ATTACHED DIRECTLY TO FEED AND CROSS MAINS.
6. THE LAST LENGTH OF PIPE AT THE END OF FEED OR CROSS MAINS SHALL BE PROVIDED WITH A LATERAL
BRACE. LATERAL BRACES SHALL BE ALLOWED TO ACT AS A LONGITUDINAL BRACE IF THEY ARE WITHIN 24" OF
THE CENTERLINE OF THE PIPING BRACED.
7. SWAY BRACING IS NOT REQUIRED FOR BRANCH LINES 2" AND SMALLER.
8. THE END SPRINKLER ON EACH BRANCH LINE SHALL BE RESTRAINED AGAINST EXCESSIVE MOVEMENT BY
APPROVED MEANS.
9. C-TYPE CLAMPS (INCLUDING BEAM AND LARGE FLANGE CLAMPS) WITH OR WITHOUT RETAINING STRAPS, SHALL
NOT BE USED TO ATTACH BRACES TO THE BUILDING STRUCTURE.
10. ALL BEAM HANGERS SHALL BE EQUIPPED WITH RETAINER STRAPS.
GENERAL NOTES:
A. SUBMIT ALL SHOP DRAWINGS TO LOCAL AUTHORITY HAVING JURISDICTION (AHJ) AND RECEIVE APPROVAL PRIOR
TO STARTING CONSTRUCTION.
B. COORDINATE ALL PIPING WITH OTHER TRADES PRIOR TO STARTING CONSTRUCTION.
C. ALL MATERIALS & INSTALLATIONS OF THIS AUTOMATIC FIRE SPRINKLER SYSTEM TO CONFORM TO NFPA 13 & 14
(2007 EDITION) OR CURRENT EDITION APPROVED BY LOCAL AHJ.
D. UNDERGROUND PIPING TO BE PROVIDED BY OTHERS. TEST AND FLUSHING CERTIFICATION TO BE PROVIDED
BEFORE FPS IS TO CONNECT TO ANY PIPING.
E. FIRE PROTECTION CONTRACTOR (FPC) WILL PROVIDE A RELIABLE MODEL A4 SPARE HEAD CABINET WITH A
MINIMUM OF EACH TYPE OF SPRINKLER HEAD USED PER NFPA 13. WITH THE APPROPRIATE HEAD WRENCH FOR
EACH HEAD USED AS OUTLINED IN THE SPRINKLER HEAD LEGEND.
F. IT IS THE OWNERS RESPONSIBILITY TO PROVIDE ADEQUATE HEAT.
G. DRAINS WILL BE PROVIDED IN ACCORDANCE WITH NFPA 13. FPS DRAINS TO BE PIPED TO OUTSIDE OR AS
INDICATED ON DRAWINGS.
H. ALL SYSTEM PIPING SHALL BE HYDROSTATICALLY TESTED AT 200 PSI OR AT 50 PSI ABOVE THE SYSTEM
OPERATING PRESSURE, WHICHEVER IS GREATER.
I. ALL ELECTRICAL WIRING, CONDUIT, DETECTION, AND ALARM/CONTROL PANELS TO BE DONE BY ELECTRICAL
CONTRACTOR. TAMPER AND FLOW SWITCHES SHALL BE BY FPC.
J. PIPE SIZING PER HYDRAULIC CALCULATIONS.
K. MAIN PIPING 2-1/2" - 4" TO BE ANSI/ASTM A-795, EITHER SCHEDULE 40 BLACK SPRINKLER PIPING WITH THREADED
ENDS AND ANVIL CAST IRON FITTINGS, OR GROOVED ENDS AND VICTAULIC GROOVED COUPLINGS AND FITTINGS
(UNLESS SHOWN OTHERWISE).
L. BRANCH LINE PIPING 2" AND SMALLER TO BE ANSI/ASTM A-795, EITHER SCHEDULE 40 BLACK SPRINKLER PIPING
WITH THREADED ENDS AND ANVIL CAST IRON FITTINGS, OR GROOVED ENDS AND VICTAULIC GROOVED FITTINGS.
M. ALL GROOVED COUPLINGS TO BE "VICTAULIC" #005 ZERO-FLEX RIDGED COUPLINGS AND "VICTAULIC" #075 FLEX
COUPLINGS.
N. FPC TO START WORK AT POINT 1'-0" ABOVE FINISHED FLOOR.
O. SPRINKLER HEADS IN AREAS WITH DROPPED CEILINGS TO BE WHITE CONCEALERS NOT REQUIRED TO BE
INSTALLED IN CENTER OF CEILING TILES.
P. SPRINKLER HEADS IN AREAS EXPOSED TO THE DECK TO BE UPRIGHT HEADS.
Q. CUTTING, PATCHING, AND RESTORATION OF FLOORS, WALLS, AND CEILING TO BE DONE BY FPC.
R. SIGNS, HYDRAULIC PLACARDS AND SYSTEM INFORMATION DISPLAYS PROVIDED BY FPS WILL BE MANUFACTURED
BY FPPI INC.
S. FIRE STOPPING USED WILL BE HILTI FS-ONE
T. REFER TO ARCHITECTURAL PLANS FOR SECTION VIEWS OF BUILDINGS.
U. REFER TO ARCHITECTURAL CEILING PLAN FOR EXISTING HISTORICAL CEILINGS TO REMAIN.
V. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL DRAWINGS TO VERIFY HOW AND WHERE
CONCRETE CAN BE CUT.
W. COORDINATE REMOVAL OF PIPING WITH ASBESTOS ABATEMENT CONTRACTOR.
X. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE WITH MECHANICAL AND ELECTRICAL CONTRACTORS TO
ENSURE THAT HVAC AND LIGHT FIXTURES DON’T CONFLICT WITH SPRINKLERS.
Y. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS SO THAT SPRINKLER HEADS DON’T RUIN THE CEILING
AESTHETICS
FIRE SPRINKLER CONTRACTOR SHALL ORDER A HYDRANT
FLOW TEST PRIOR TO DESIGN TO VERIFY PRESSURE.
STATIC PRESSURE HAS BEEN MEASURED AT 78 PSI ON THE
12 INCH WATER LINE IN THE STREET. SEE FIGURE BELOW.
HYDRANT FLOW TEST
REFER TO STRUCTURAL SPECIFICATIONS FOR SEISMIC
DESIGN REQUIREMENTS.
FI
R
E
PR
O T
EC
T
IO
N
S
PE
C
IF
IC
A
T
IO
N S
F0.1
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
2014 MORRISON-MAIERLE, INC.
WHWH
DF DF
STAIR
RESTROOM
MECH / ELECT
TELE/DATA
ELEV
MACHINE
ELEVATOR
VESTIBULE VESTIBULE
001.1
001.3
UP UP
UP
DOWN
17"
DOWN
17"
DOWN
17"
DOWN
17"
UP UP
UP
UP
003.1
ELECTRICAL
UP
002.1
004.1
008.1
STAIR
MECH / ELECT
EXISTING FIRE
SPRINKLER
RISER
HYDRAULIC DESIGN AREA
ALLOWABLE DESIGN: MECHANICAL ROOM
ORDINARY HAZARD (GROUP I): 0.15 GPM/1500 SF
COMBINED INSIDE - OUTSIDE HOSE ALLOWANCE:
250 GPM@60-90 MIN.
SYSTEM TYPE: WET
EXISTING WET FIRE SPRINKLER MAIN
EXISTING DRY FIRE SPRINKLER MAIN
FIRE RISER
LOCATION (E)
FIRE RISER
LOCATION (E)
FIRE RISER
LOCATION (E)
EXISTING FIRE
DEPARTMENT
CONNECTION.
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
FIRE RISER
LOCATION (E)
FIRE RISER
LOCATION (E)
APPROXIMATE EXTENT OF FUTURE
WORK. COORD. AND PROVIDE
PROVISIONS FOR FUTURE
EXPANSION WITHIN PHASE 2 WORK.
CAPPED FOR
FUTURE
EXTENSION
APPROXIMATE EXTENT OF FUTURE
WORK. COORD. AND PROVIDE
PROVISIONS FOR FUTURE
EXPANSION WITHIN PHASE 2 WORK.
APPROXIMATE EXTENT OF FUTURE
WORK. COORD. AND PROVIDE
PROVISIONS FOR FUTURE
EXPANSION WITHIN PHASE 2 WORK.
WET SYSTEM - LIGHT HAZARD
0.10 GPM/1500 SF
COMBINED HOSE ALLOWANCE: 250 GPM @ 60-90 MIN.
WET SYSTEM - ORDINARY HAZARD
0.10 GPM/1500 SF
COMBINED HOSE ALLOWANCE: 250 GPM @ 60-90 MIN.
DRY OR GLYCOL SPRINKLERS
(REQUIRED IN UNCONDITIONED SPACES SUCH AS
ATTICS AND EXTERIOR OVERHANGS
CONSTRUCTED OF COMBUSTIBLE MATERIALS)
A D E F G H KCB J
BA
SE
M
EN
T F
IR
E
PR
O
T
EC
T
IO
N P
LA
N
USFS BUILDING 26 - BASEMENT FIRE PR0TECTION PLAN 16
F2.0 : F2.0 1/8" = 1'-0"
NORTH
F2.0
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
2014 MORRISON-MAIERLE, INC.
1. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE WITH
MECHANICAL AND ELECTRICAL CONTRACTORS TO ENSURE THAT
HVAC AND LIGHT FIXTURES DON’T CONFLICT WITH SPRINKLERS.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS SO THAT
SPRINKLER HEADS DON’T RUIN THE CEILING AESTHETICS
(TYPICAL ALL SPACES). PROVIDE SIDEWALL HEADS OR ROUTE
PIPING IN JOIST SPACE AS NECESSARY. COORDINATE WITH
GENERAL CONTRACTOR.
3. EXISTING PLASTER CEILINGS TO REMAIN IN MANY LOCATION
UNDER NEW GYP CEILING. COORDINATE WITH ARCHITECTURAL
REFLECTED CEILING PLAN AND ARCHITECTURAL DEMO PLANS.
COORDINATE WITH GENERAL CONTRACTOR AND OTHER TRADES
TO MINIMIZED PLASTER DAMAGE SO THAT NEW CEILING CAN BE
SECURED AGAINST EXISTING CEILING.
4. THESE CONSTRUCTION DOCUMENTS ARE LIMITED TO THE
IDENTIFIED CONSTRUCTION AREA. THE FIRE SPRINKLER SYSTEM
TO BE INSTALLED FOR THIS PHASE SHALL PROVIDE FULL
COVERAGE IN ACCORDANCE WITH NFPA 13 REQUIREMENTS BUT IS
TO BE LIMITED TO THE PLAN AREAS IDENTIFIED. NOTE THAT SOME
OF THE WORK REQ'D FOR THIS PHASE OF CONSTRUCTION
EXTENDS INTO FUTURE AREAS. COORD. W/ GEN. CONT'R.
5. THE FIRE SPRINKLER WATER SERVICE, RISER, BACKFLOW AND
OTHER PRIMARY EQUIPMENT WERE INSTALLED IN THE FIRST
PHASE OF CONSTRUCTION AND WERE BE DESIGNED FOR THE
ENTIRE BUILDING (ALL PHASES). THE DESIGN THIS PHASE SHALL
CONSIDER EASE OF EXPANSION INTO FUTURE CONSTRUCTION
PHASES.
6. ALL FIRE PROTECTION WORK SHALL BE APPROVED BY THE AHJ
(FIRE MARSHALL) PRIOR TO THE STARTING OF ANY PLANNING,
DESIGN AND/OR CONSTRUCTION.
GENERAL NOTES:
FIRE PROTECTION SYSTEM LEGEND:
CONF/
NURSE
CONFERENCE
OFFICE
125OFFICE
OPEN
OFFICE
OPEN
OFFICE
ENTRY
HALL
RECEPTION
BREAK
PRIVATE
OFFICE
HR
JANITOR
WOMENS
RESTROOM
MENS
RESTROOM
EXECUTIVE
ASSISTANT
(2 STAFF)
REGIONAL
FORESTER
DEPUTY
REGIONAL
FORESTER
DEPUTY
REGIONAL
FORESTER
COFFEE / PRINT
115LARGE
CONFERENCE
TELE/DATA
PRINT / COPY / FAX
CONFERENCE
ENTRY
ELEVATOR
A
PORCH
STAIR
PORCH
DOWN DOWN
DOWN DOWN
DOWNDOWN
UP UP
RAMP
DOWN
RAMP
DOWN
RAMP
DOWN
DOWN DOWN
UP
CONFERENCE
UP
DEMO
TEMP DOOR
AND
WALL
OFFICE
OFFICE
OFFICE
OPEN
OFFICE
OPEN
OFFICE
OFFICE
OFFICE
OPEN
OFFICE
CONFERENCE
STAIR
PORCH
CARD
READER
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
(N) FE CAB
1008.1.8 DOOR
ARRANGEMENT:
SPACE BETWEEN TWO
DOORS IN A SERIES SHALL
BE 48" MIN. PLUS THE
WIDTH OF A DOOR
SWINGING INTO THE
SPACE. DOORS IN A
SERIES SHALL SWING
EITHER IN THE SAME
DIRECTION OR AWAY
FROM THE SPACE
BETWEEN THE DOORS.
CARD READER,
NO HOLD OPENS
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
SMALL
CONFERENCE
PRIVATE
OFFICE
HR
CONFERENCE
OFFICE
125OFFICE
OPEN
OFFICE
(12 STAFF)
OPEN
OFFICE
(16 STAFF)
ENTRY
HALL
RECEPTION
(2 STAFF)
BREAK
PRIVATE
OFFICE
JANITOR
WOMENS
RESTROOM
MENS
RESTROOM
EXECUTIVE
ASSISTANT
(2 STAFF)
REGIONAL
FORESTER
DEPUTY
REGIONAL
FORESTER
DEPUTY
REGIONAL
FORESTER
COFFEE / PRINT
115LARGE
CONFERENCE
TELE/DATA
PRINT / COPY / FAX
CONFERENCE
ENTRY
ELEVATOR
A
PORCH
STAIR
PORCH
DOWN DOWN
DOWN DOWN
DOWNDOWN
UP UP
RAMP
DOWN
RAMP
DOWN
RAMP
DOWN
DOWN DOWN
UP
CONFERENCE
UP
(E)
SWR
HYDRAULIC DESIGN AREA
ALLOWABLE DESIGN: GENERAL OFFICE SPACE
LIGHT HAZARD: 0.10 GPM/1500 SF
COMBINED INSIDE - OUTSIDE HOSE ALLOWANCE:
250 GPM@60-90 MIN.
SYSTEM TYPE: WET
EXISTING
PLASTER
CEILINGS
APPROXIMATE
CONSTRUCTION
AREA OF WORK
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
FIRE RISER
LOCATION (E)
FIRE RISER
LOCATION (E)
CAPPED FOR
FUTURE
DRY FIRE RISER
LOCATION (E) UP
TO SECOND
FLOOR
FIRE RISER
LOCATION (E)
DRY UP TO
ATTIC
D R
Y
S
Y S
T E
M
D R
Y
S
Y S
T E
M
CAPPED DRY
FOR FUTURE
PHASE
WET UP TO
2ND FLOOR
DRY SYSTEM
DRY UP TO
2ND FLOOR
WET CONTINUED
UP TO 2ND FLOOR
CONTINUE FIRE RISER
FROM EXISTING
LOCATION BELOW
A D E F G H KCB J
WET SYSTEM - LIGHT HAZARD
0.10 GPM/1500 SF
COMBINED HOSE ALLOWANCE: 250 GPM @ 60-90 MIN.
WET SYSTEM - ORDINARY HAZARD
0.10 GPM/1500 SF
COMBINED HOSE ALLOWANCE: 250 GPM @ 60-90 MIN.
DRY OR GLYCOL SPRINKLERS
(REQUIRED IN UNCONDITIONED SPACES SUCH AS
ATTICS AND EXTERIOR OVERHANGS
CONSTRUCTED OF COMBUSTIBLE MATERIALS)
FI
R
ST
F
LO
O
R F
IR
E
PR
O
T
EC
T
IO
N P
LA
N
USFS BUILDING 26 - FIRST FLOOR FIRE PROTECTION PLAN 16
F2.1 : F2.1 1/8" = 1'-0"
NORTH
F2.1
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
2014 MORRISON-MAIERLE, INC.
1. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE WITH
MECHANICAL AND ELECTRICAL CONTRACTORS TO ENSURE THAT
HVAC AND LIGHT FIXTURES DON’T CONFLICT WITH SPRINKLERS.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS SO THAT
SPRINKLER HEADS DON’T RUIN THE CEILING AESTHETICS
(TYPICAL ALL SPACES). PROVIDE SIDEWALL HEADS OR ROUTE
PIPING IN JOIST SPACE AS NECESSARY. COORDINATE WITH
GENERAL CONTRACTOR.
3. EXISTING PLASTER CEILINGS TO REMAIN IN MANY LOCATION
UNDER NEW GYP CEILING. COORDINATE WITH ARCHITECTURAL
REFLECTED CEILING PLAN AND ARCHITECTURAL DEMO PLANS.
COORDINATE WITH GENERAL CONTRACTOR AND OTHER TRADES
TO MINIMIZED PLASTER DAMAGE SO THAT NEW CEILING CAN BE
SECURED AGAINST EXISTING CEILING.
4. THESE CONSTRUCTION DOCUMENTS ARE LIMITED TO THE
IDENTIFIED CONSTRUCTION AREA. THE FIRE SPRINKLER SYSTEM
TO BE INSTALLED FOR THIS PHASE SHALL PROVIDE FULL
COVERAGE IN ACCORDANCE WITH NFPA 13 REQUIREMENTS BUT IS
TO BE LIMITED TO THE PLAN AREAS IDENTIFIED. NOTE THAT SOME
OF THE WORK REQ'D FOR THIS PHASE OF CONSTRUCTION
EXTENDS INTO FUTURE AREAS. COORD. W/ GEN. CONT'R.
5. THE FIRE SPRINKLER WATER SERVICE, RISER, BACKFLOW AND
OTHER PRIMARY EQUIPMENT WERE INSTALLED IN THE FIRST
PHASE OF CONSTRUCTION AND WERE BE DESIGNED FOR THE
ENTIRE BUILDING (ALL PHASES). THE DESIGN THIS PHASE SHALL
CONSIDER EASE OF EXPANSION INTO FUTURE CONSTRUCTION
PHASES.
6. ALL FIRE PROTECTION WORK SHALL BE APPROVED BY THE AHJ
(FIRE MARSHALL) PRIOR TO THE STARTING OF ANY PLANNING,
DESIGN AND/OR CONSTRUCTION.
OFFICE
170 SF
OFFICE
173 SF
OFFICE
170 SF
SMALL
CONFERENCE
105 SF
SMALL
CONFERENCE
145 SF
OPEN
OFFICE
OPEN
OFFICE
STAIR
ELEVATOR
A
PORCH
PORCH
DOWNDOWN
DOWN
DOWNDOWN
DOWNDOWN
DOWNDOWN
DOWN
TELE/DATA
211JANITOR
SMALL
CONFERENCE
105 SF
DOWN
(E)
SWR
(N)
FSR
BOILER
VENT
BOILER
VENT
R
R
R
R R
12"Ø
EXHAUST
12"Ø
EXHAUST
6"Ø 8"Ø
WOMENS
RR
180 SF
MENS
RR
165 SF
OFFICE
S&PF
150 SF
(N)
FSR R R R
DOWN
OFFICE
HR
150 SF
OPEN
OFFICE
FIRE
(10 CUBI, 1 TELE)
LARGE
CONFERENCE
ADMIN
465 SF
CONFERENCE
OGC
260 SF
OPEN
OFFICE
OGC
(2 CUBI)
OFFICE
OGC
150 SF
OFFICE
OGC
150 SF
OFFICE
OGC
155 SF
OFFICE
OGC
225 SF
OFFICE
OGC
150 SF
OFFICE
OGC
150 SF
OFFICE
OGC
150 SF
FILES
OGC
OFFICE
FIRE
140 SF
CONFERENCE
155 SF
OFFICE
FIRE
140 SF
STAIR
PORCH
PLOT
HALL
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
SMALL
CONFERENCE
SMALL
CONFERENCE
OPEN
OFFICE
(23 STAFF)
OPEN
OFFICE
(22 STAFF)
STAIR
ELEVATOR
A
209.1
207.1
206.2
201.1
201.2
202.2
202.1 203.1 204.1
PORCH
PORCH
DOWNDOWN
DOWN
DOWNDOWN
DOWNDOWN
DOWN
DOWNDOWN
DOWN
TELE/DATA
211ELECTRICAL
SMALL
CONFERENCE
205.1
211.1
DOWN
206.1
(E)
SWR
(N)
FSR
BOILER
VENT
BOILER
VENT
R
R
R
R R
12"Ø
EXHAUST
12"Ø
EXHAUST
6"Ø 8"Ø
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
HYDRAULIC DESIGN AREA
ALLOWABLE DESIGN: GENERAL OFFICE SPACE
LIGHT HAZARD: 0.10 GPM/1500 SF
COMBINED INSIDE - OUTSIDE HOSE ALLOWANCE:
250 GPM@60-90 MIN.
SYSTEM TYPE: WET
HYDRAULIC DESIGN AREA
ALLOWABLE DESIGN: EXTERIOR CANOPY
LIGHT HAZARD: 0.10 GPM/1500 SF
COMBINED INSIDE/OUTSIDE HOSE ALLOWANCE:
250 GPM@60-90 MIN.
SYSTEM TYPE: DRY
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
NEW RISER
CONTINUED
FROM RISER
BELOW.
FIRE RISER
LOCATION (E)
DRY FIRE RISER
LOCATION (E)
FIRE RISER
LOCATION (E)
DRY FIRE RISER
(E) UP TO ATTIC
D R
Y
S
Y S
T E
M
DRY SYSTEM
UP FROM
2ND FLOOR
UP FROM
2ND FLOOR
IN WALL
A D E F G H KCB JA D E F G H KCB J
WET SYSTEM - LIGHT HAZARD
0.10 GPM/1500 SF
COMBINED HOSE ALLOWANCE: 250 GPM @ 60-90 MIN.
WET SYSTEM - ORDINARY HAZARD
0.10 GPM/1500 SF
COMBINED HOSE ALLOWANCE: 250 GPM @ 60-90 MIN.
DRY OR GLYCOL SPRINKLERS
(REQUIRED IN UNCONDITIONED SPACES SUCH AS
ATTICS AND EXTERIOR OVERHANGS
CONSTRUCTED OF COMBUSTIBLE MATERIALS)
SE
C
O N
D F
LO
O
R F
IR
E
PR
O
T
EC
T
IO
N P
LA
N
USFS BUILDING 26 - SECOND FLOOR FIRE PROTECTION PLAN 16
F2.2 : F2.2 1/8" = 1'-0"
NORTH
F2.2
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
2014 MORRISON-MAIERLE, INC.
1. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE WITH
MECHANICAL AND ELECTRICAL CONTRACTORS TO ENSURE THAT
HVAC AND LIGHT FIXTURES DON’T CONFLICT WITH SPRINKLERS.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS SO THAT
SPRINKLER HEADS DON’T RUIN THE CEILING AESTHETICS
(TYPICAL ALL SPACES). PROVIDE SIDEWALL HEADS OR ROUTE
PIPING IN JOIST SPACE AS NECESSARY. COORDINATE WITH
GENERAL CONTRACTOR.
3. EXISTING PLASTER CEILINGS TO REMAIN IN MANY LOCATION
UNDER NEW GYP CEILING. COORDINATE WITH ARCHITECTURAL
REFLECTED CEILING PLAN AND ARCHITECTURAL DEMO PLANS.
COORDINATE WITH GENERAL CONTRACTOR AND OTHER TRADES
TO MINIMIZED PLASTER DAMAGE SO THAT NEW CEILING CAN BE
SECURED AGAINST EXISTING CEILING.
4. THESE CONSTRUCTION DOCUMENTS ARE LIMITED TO THE
IDENTIFIED CONSTRUCTION AREA. THE FIRE SPRINKLER SYSTEM
TO BE INSTALLED FOR THIS PHASE SHALL PROVIDE FULL
COVERAGE IN ACCORDANCE WITH NFPA 13 REQUIREMENTS BUT IS
TO BE LIMITED TO THE PLAN AREAS IDENTIFIED. NOTE THAT SOME
OF THE WORK REQ'D FOR THIS PHASE OF CONSTRUCTION
EXTENDS INTO FUTURE AREAS. COORD. W/ GEN. CONT'R.
5. THE FIRE SPRINKLER WATER SERVICE, RISER, BACKFLOW AND
OTHER PRIMARY EQUIPMENT WERE INSTALLED IN THE FIRST
PHASE OF CONSTRUCTION AND WERE BE DESIGNED FOR THE
ENTIRE BUILDING (ALL PHASES). THE DESIGN THIS PHASE SHALL
CONSIDER EASE OF EXPANSION INTO FUTURE CONSTRUCTION
PHASES.
6. ALL FIRE PROTECTION WORK SHALL BE APPROVED BY THE AHJ
(FIRE MARSHALL) PRIOR TO THE STARTING OF ANY PLANNING,
DESIGN AND/OR CONSTRUCTION.
C
303.1
C
303.2
12"Ø
EXHAUST
12"Ø
EXHAUST
6"Ø 8"Ø
C
304.2
C
304.1
ATTIC
NORTH
ELEVATOR
A
C
302.1
ATTIC
NORTHEAST
ATTIC
SOUTHEAST
ATTIC
SOUTH
ATTIC
CENTER
C
302.2
C
302.3
C
303.1
C
303.2
HYDRAULIC DESIGN AREA
ALLOWABLE DESIGN: UNCONDITIONED ATTIC
LIGHT HAZARD: 0.10 GPM/1500 SF
COMBINED INSIDE/OUTSIDE HOSE ALLOWANCE:
250 GPM@60-90 MIN.
SYSTEM TYPE: DRY
(DRY) RISER
LOCATION
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
EXISTING DRY
RISER UP FROM
BELOW
EXISTING FIRE
SUPPRESSION
SYSTEM AREA
A D E F G H KCB JA D E F G H KCB J
WET SYSTEM - LIGHT HAZARD
0.10 GPM/1500 SF
COMBINED HOSE ALLOWANCE: 250 GPM @ 60-90 MIN.
WET SYSTEM - ORDINARY HAZARD
0.10 GPM/1500 SF
COMBINED HOSE ALLOWANCE: 250 GPM @ 60-90 MIN.
DRY OR GLYCOL SPRINKLERS
(REQUIRED IN UNCONDITIONED SPACES SUCH AS
ATTICS AND EXTERIOR OVERHANGS
CONSTRUCTED OF COMBUSTIBLE MATERIALS)
A T
T
IC
F
IR
E
PR
O T
EC
T
IO
N
P
LA
N
USFS BUILDING 26 - ATTIC PLAN FIRE PROTECTION PLAN 16
F2.3 : F2.3 1/8" = 1'-0"
NORTH
F2.3
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
2014 MORRISON-MAIERLE, INC.
1. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE WITH
MECHANICAL AND ELECTRICAL CONTRACTORS TO ENSURE THAT
HVAC AND LIGHT FIXTURES DON’T CONFLICT WITH SPRINKLERS.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS SO THAT
SPRINKLER HEADS DON’T RUIN THE CEILING AESTHETICS
(TYPICAL ALL SPACES). PROVIDE SIDEWALL HEADS OR ROUTE
PIPING IN JOIST SPACE AS NECESSARY. COORDINATE WITH
GENERAL CONTRACTOR.
3. EXISTING PLASTER CEILINGS TO REMAIN IN MANY LOCATION
UNDER NEW GYP CEILING. COORDINATE WITH ARCHITECTURAL
REFLECTED CEILING PLAN AND ARCHITECTURAL DEMO PLANS.
COORDINATE WITH GENERAL CONTRACTOR AND OTHER TRADES
TO MINIMIZED PLASTER DAMAGE SO THAT NEW CEILING CAN BE
SECURED AGAINST EXISTING CEILING.
4. THESE CONSTRUCTION DOCUMENTS ARE LIMITED TO THE
IDENTIFIED CONSTRUCTION AREA. THE FIRE SPRINKLER SYSTEM
TO BE INSTALLED FOR THIS PHASE SHALL PROVIDE FULL
COVERAGE IN ACCORDANCE WITH NFPA 13 REQUIREMENTS BUT IS
TO BE LIMITED TO THE PLAN AREAS IDENTIFIED. NOTE THAT SOME
OF THE WORK REQ'D FOR THIS PHASE OF CONSTRUCTION
EXTENDS INTO FUTURE AREAS. COORD. W/ GEN. CONT'R.
5. THE FIRE SPRINKLER WATER SERVICE, RISER, BACKFLOW AND
OTHER PRIMARY EQUIPMENT WERE INSTALLED IN THE FIRST
PHASE OF CONSTRUCTION AND WERE BE DESIGNED FOR THE
ENTIRE BUILDING (ALL PHASES). THE DESIGN THIS PHASE SHALL
CONSIDER EASE OF EXPANSION INTO FUTURE CONSTRUCTION
PHASES.
6. ALL FIRE PROTECTION WORK SHALL BE APPROVED BY THE AHJ
(FIRE MARSHALL) PRIOR TO THE STARTING OF ANY PLANNING,
DESIGN AND/OR CONSTRUCTION.
L
E
S
S
T
H
A
N
ADD'L "AP" OR STANDARD
SPRINKLERS AS REQ'D
MORE
THAN 4'-0"
M
I N
"BB"
NO ADD'L
SPRINKLER
REQ'D.
M
I
N
4'-0" OR
LESS
M
I N
"BB"
"SD"
N
"BB" = BACK-TO-BACK DUAL DIRECTIONAL ATTIC SPRINKLER
"SD" = SINGLE DIRECTIONAL ATTIC SPRINKLER
"HIP" = TYCO MODEL HIP ATTIC SPRINKLER
"AP" = TYCO MODEL AP (ATTIC PLUS) SPRINKLER
STD. = STANDARD SPRAY SPRINKLER
M
A X
M
I N
4-12
FOR ROOF PITCH LESS THAN
4:12, 12" MAX. BELOW PEAK
AND 1" MIN. BELOW BOTTOM
OF TOP CHORD OR RAFTER
"BB", "SD",
OR "HIP"
M
I N
SCISSOR TRUSS
BOTTOM CHORD
"BB" OR "SD"
6'-0" MAX. - 4'-0" MIN.
RIDGE
TRUSS
"AP" OR STD.
7'-0" MIN. FOR "AP" - 6'-0" MIN. FOR STD.
RIDGE
TRUSS
ATTIC
SPRINKLER
BRANCH
LINE
"BB", "SD"
OR "HIP"
6" MIN.
RIDGE
TRUSS
"BB" OR "HIP"
M
A X
M
I N
6" MAX.
X
"BB"
X
10'-0" MAX. "BB" SPAN
"AP" COVERAGE
X
"AP" @ 7'-0" TO
8'-0" O.C.
X
10'-0" MAX. "SD" SPAN
"AP" COVERAGE
N
ADD'L "AP" OR STANDARD
SPRINKLERS AS REQ'D
BRANCH
LINE
ADD'L "AP" OR STANDARD
SPRINKLERS AS REQ'D
"AP" @ 7'-0" TO
8'-0" O.C.
HANGER ROD
TURN BUCKLE (AS
REQUIRED)
INSULATION
PIPE
SHEET METAL
SADDLE INSERT
CLEVIS TYPE HANGER FOR
PIPE 2" & LARGER
HANGER ROD
TURN BUCKLE
(AS REQUIRED)
INSULATION
PIPE
SHEET METAL
SADDLE INSERT
PIPE STRAP TYPE HANGER
FOR PIPE LESS THAN 2"
4-WAY ADAPTER
QUICK
CLAMP
SPRINKLER PIPE
1"Ø SCHED. 40
PIPE
CONNECT TO STRUCTURE
PER APPLICABLE PIPE
SUPPORT DETAIL
HANGER ROD SIZE
PER SCHEDULE
HANGER ROD SIZE
PER SCHEDULE
PIPE SIZE ROD SIZE
4"Ø & LESS
"Ø
5, 6 & 8"Ø
10 & 12"Ø
"Ø
"Ø
SPRINKLER PIPE
1"Ø SCHED. 40
PIPE
QUICK
CLAMP
SUPPORT STRUCTURE
ANCHORAGE
SUPPORT STRUCTURE
F9.1 : F2.3 SCALE: NOT TO SCALE
ATTIC SPRINKLER DETAILS12
11 2-WAY SWAY BRACE DETAIL 15 4-WAY SWAR BRACE DETAIL
14 PIPE HANGER DETAILS
SCALE: NOT TO SCALE
SCALE: NOT TO SCALESCALE: NOT TO SCALE F9.1: F9.1
F9.1: F9.1
D
ET
A
IL
S
F9.1
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
2014 MORRISON-MAIERLE, INC.
File details come from the government source that posted it. Updated .