PROJECT NOTES:
E0.1
ABBREVIATIONS
A or AMP AMPERES
AC ALTERNATING CURRENT
A/C AIR CONDITIONING
AF AMP FUSE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AL ALUMINUM
AS AMP SWITCH
ATS AUTOMATIC TRANSFER SWITCH
BAS BUILDING AUTOMATION SYSTEM
BKR BREAKER
C RACEWAY/CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
C.O.
RACEWAY/CONDUIT ONLY, WITH PULL STRING
CNTRL CONTROL
CU COPPER
DISC DISCONNECT
DIST DISTRIBUTION
DPDT DOUBLE POLE DOUBLE THROW
DWG DRAWING
EA EACH
EF EXHAUST FAN
ELEC ELECTRIC
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EX OR
EXIST
EXISTING
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FD FUSED DISCONNECT
FLR FLOOR
FO FIBER OPTIC
FSD FIRE SMOKE DAMPER
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
GEC GROUNDED ELECTRODE CONDUCTOR
GFI GROUND FALUT INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
HVAC
HEATING, VENTILATING & AIR CONDITIONING
HZ HERTZ
J-BOX JUNCTION BOX
KVA KILOVOLT AMPERES
KW KILOWATTS
LTG LIGHTING
LPW LUMENS PER WATT
MAG MAGNETIC STARTER
MAN MANUAL
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH METAL HALIDE
MIN MINIMUM
MSS MOTOR STARTER SWITCH
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFD NON-FUSED DISCONNECT
NIC NOT IN CONTRACT
NO NORMALLY OPEN
# NUMBER
OAE OR APPROVED EQUAL
OC ON CENTER
OCPD OVERCURRENT PROTECTION DEVICE
OH OVERHEAD
P POLE
PB PUSHBUTTON
PNL PANEL
PoE POWER OVER ETHERNET
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
RECEPT RECEPTACLE
RCPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RVNR REDUCED VOLTAGE NON-REVERSING
RVR REDUCED VOLTAGE REVERSING
SP SINGLE POLE TOGGLE SWITCH
SPEC SPECIFICATION
SPST SINGLE POLE SINGLE THROW
SSPB START-STOP PUSHBUTTON
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TB TELEPHONE BOARD
TC TIME CLOCK
TD TIME DELAY
TEL TELEPHONE
TSP TWISTED SHIELDED PAIR
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLT AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATTS
WP WEATHERPROOF
W/O WITHOUT
XFMR TRANSFORMER
Y WYE CONNECTED
DELTA CONNECTED
PHASE
*THESE ABBREVIATIONS COMPRISE A STANDARD LIST;
NOT ALL ABBREVIATIONS APPEAR ON THIS PROJECT.
1. PRIOR TO BID CONTRACTOR SHALL VISIT THE SITE. NOT ALL WORK REQUIRED TO COMPLETE THE PROJECT IS
SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL BECOME THOROUGHLY FAMILIAR WITH ALL THE WORK
REQUIRED TO COMPLETE THE PROJECT IN ADDITION TO THE LOCAL CONDITIONS AND INCLUDE SAID WORK IN
THE BID.
2. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING RACEWAY (BOTH SURFACE AND
CONCEALED) TO THE EXTENT POSSIBLE. THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT
POSSIBLE TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND ALLOWED PER CODE, FISHING
THROUGH WALLS WITH MC CABLE IS PREFERRED TO SURFACE-MOUNTED CONDUIT.
3. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF LAMPS AND BALLASTS OFF-SITE. IT IS
ASSUMED THE THE BALLASTS DO NOT CONTAIN PCBs. THE CONTRACTOR SHALL NOTIFY THE OWNER
IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBs.
4. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY DISRUPTION OF WORKERS IN THE
SPACE SHALL BE KEPT TO A MINIMUM AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING
IN THAT SPACE.
5. GENERAL WORK PRACTICES FOR ELECTRICAL CONSTRUCTION SHALL BE IN ACCORDANCE WITH NECA 1, "STANDARD PRACTICES FOR GOOD WORKMANSHIP IN ELECTRICAL CONTRACTING." THIS PUBLICATION IS
AVAILABLE FROM NECA BY TELEPHONE AT 301-657-3110 OR ON-LINE AT WWW.NECANET.ORG.
6. FIRE-RESISTANCE: PROVIDE A MINIMUM HORIZONTAL DISTANCE OF 24" BETWEEN OUTLET BOXES LOCATED ON
OPPOSITE SIDES OF FIRE-RESISTANCE RATED WALLS. WHERE THIS IS NOT POSSIBLE INSTALL UL LISTED PUTTY
PADS ON ALL OUTLET BOXES NOT MEETING THE 24" SEPARATION. PROVIDE A UL LISTED THROUGH
-PENETRATION FIRESTOP FOR PENETRATIONS OF FIRE-RESISTANCE RATED ASSEMBLIES.
7. CONDUCTORS ARE SIZED PER THE 75 DEGREE C RATING COLUMN OF NEC TABLE 310.16. IF THE TERMINAL USED
FOR A TERMINATION OF A PARTICULAR CONDUCTOR IS NOT MARKED, OR THE TERMINAL IS MARKED FOR 60
DEGREE C CONDUCTORS, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EITHER ADJUST THE AMPACITY
OF THE CONDUCTOR TO MATCH THE 60 DEGREE COLUMN OF TABLE 310.16, OR REPLACE THE TERMINAL WITH
ONE RATED FOR AT LEAST 75 DEGREES C
8. FOR 20A BRANCH CIRCUIT RUNS EXTENDING BEYOND 300 LINEAR FEET. CONDUCTOR SIZE SHALL BE A MINIMUM
OF #10 CU.
9. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE WITH MECHANICAL FOR PLENUM SPACES AND
PROVIDE PLENUM RATED CABLES WHERE REQUIRED FOR LIGHTING CONTROL, DATA AND ALL OTHER L.V.
SYSTEMS NOT INSTALLED IN CONDUIT.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL ELECTRICAL SERVICE WORK WITH
UTILITY. OWNER PAYS ALL FEES, CONTRACTOR DOES ALL SCHEDULING AND COORDINATION OF WORK. IT IS
THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE ALL SCHEDULES ARE MET.
11. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH 120V BRANCH CIRCUIT.
12. SALVAGE ALL EXISTING BRASS FACEPLATES TO OWNER, DURING DEMOLITION OF OUTLETS.
ELECTRICAL SYMBOL LEGEND
SYMBOL DESCRIPTIONS
MOUNTING HEIGHT
(AFF), UNO
PANEL AND CIRCUIT DESIGNATION ARE SHOWN NEXT TO EACH DEVICE (PANEL NAME - CIRCUIT
NUMBER). BRANCH CIRCUIT WIRE SIZE IS #12 UNLESS NOTED OTHERWISE. A SINGLE INSULATED
GREEN GROUND CONDUCTOR SHALL BE PROVIDED WITH EACH HOME RUN. PROVIDE A SEPARATE
NEUTRAL FOR EACH CIRCUIT. HOME RUNS SHALL HAVE NO MORE THAN THREE CIRCUITS. LINE
VOLTAGE AND LOW VOLTAGE WIRING IS NOT SHOWN ON PLANS.
RACEWAY CONCEALED IN WALL, FLOOR, OR CEILING IN FINISHED SPACES, EXPOSED IN UNFINISHED
SPACES.
RACEWAY TURNED UP AND CONTINUED
RACEWAY TURNED DOWN AND CONTINUED
RACEWAY BELOW FLOOR OR BELOW GRADE
RACWAY STUB-OUT OR STUB-UP WITH BUSHED END
PAD MOUNTED TRANSFORMER
UTILITY ELECTRIC METER
MOTOR CONNECTION
METER
LINE BREAK
HANDHOLE
SURFACE FLUORESCENT TO SCALE. STEM INDICATES WALL MOUNTED.
RECESSED FLUORESCENT LUMINAIRE, 'a', AND 'b'.DESIGNATES SWITCH LEGS.
RECESSED EMERGENCY FLUORESCENT LUMINAIRE, 'a', AND 'b'.DESIGNATES SWITCH LEGS.
SURFACE FLUORESCENT STRIP LUMINAIRE.
EXIT SIGN. ARROW(S) INDICATE DIRECTION OF TRAVEL, SHADED AREA INDICATES ILLUMINATED
FACE(S). STEM INDICATES WALL MOUNTED. CELING MOUNTED OTHERWISE.
WALL MOUNTED LUMINAIRE
RECESSED CAN LUMINAIRE
POLE MOUNTED LUMINAIRE ASSEMBLY SECURED TO CONCRETE BASE. LETTER INDICATES FIXTURE
TYPE.
POLE MOUNTED, DUAL-HEAD, LUMINAIRE ASSEMBLY SECURED TO CONCRETE BASE. LETTER
INDICATES FIXTURE TYPE.
SWITCH:
SINGLE POLE 46"
3-WAY 46"
4-WAY 46"
WALL SWITCHES WITH SWITCH LEG CIRCUITS 'a', AND 'b'. PROVIDE SEPARATE SWITCH FOR EACH LEG.
46"
SMALL MOTOR DISCONNECT WITH THERMAL OVERLOADS 46"
WALL SWITCHES WITH SWITCH LEG CIRCUITS 'a', AND 'b'. PROVIDE SEPARATE SWITCH FOR EACH LEG.
46"
DIMMER SWITCH: DIMMER - ON/OFF. LEVITON ILLUMATECH MODEL# IP710-DL CONTRACTOR TO
PROVIDE ALL MODULES SPECIFIC FOR EACH LIGHT.
46"
LOW VOLTAGE SWITCH 46"
WALL SWITCHM DUAL TECH. MOTION DETECTOR, COOPER ONW-D-1001-MV-N-W. NO EXCEPTIONS.
46"
KEYED SWITCH 46"
MOTION DETECTOR. COOPER OAC-DT1000-R DUAL TECHNOLOGY CEILING MOUNT. NO EXCEPTIONS.
WALL MOTION DETECTOR. COOPER OAC-DT SERIES DUAL TECHNOLOGY WALL MOUNT. NO
EXCEPTIONS.
72"
PHOTOCELL. COOPER OAC-DT SERIES CEILING MOUNT. NO EXCEPTIONS.
SIMPLEX RECEPTACLE. 18"
DUPLEX RECEPTACLE. 18"
4PLEX RECEPTACLE. 18"
DUPLEX RECEPTACLE MOUNTED 4" ABOVE BACKSPLASH OR 4" ABOVE TOP OF LAVATORY ELEVATION
SPECIAL PURPOSE OUTLET, LETTER INDICATES TYPE. SEE SPEC.
18"
POKE-THRU FLOOR BOX WITH COMBINATION 4PLEX RECEPTACLE AND 2 TELEPHONE/DATA OUTLETS.
LEGRAND EVOLUTION MODEL 8STC WITH COVER, MODEL 8CTCGY, OR EQUALS.
JUNCTION BOX
FUSED DISCONNECT SWITCH
COMBINATION MOTOR STARTER
BRANCH CIRCUIT PANELBOARD
BREAKER
GROUNDING BUS
PUSHBUTTON 54"
FIRE ALARM MANUAL STATION 46"
HORN/STROBE 82"
STROBE 82"
SPRINKLER TAMPER SWITCH
SPRINKLER FLOW SWITCH
SPRINKLER PRESSURE SWITCH
DOOR HOLDER
RATE-OF-RISE HEAT DETECTOR
SMOKE DETECTOR
SMOKE DETECTOR "D" INDICATES DUCT DETECTOR. DUCT DETECTOR FURNISHED BY ELEC, INSTALLED
BY MECH, AND WIRED BY ELEC.
SPEAKER: FOR SOUND-MASKING SYSTEM. DYNASOUND MODEL DS1356, OR EQUAL.
WIRELESS ACCESS POINT WITH ONE DATA. (1)
CEILING
ANALOG TELEPHONE OUTLET WITH TWO ANALOG CABLE DROPS U.N.O. REFER TO SPECS FOR CABLING
REQ. (1)
18"
TELEPHONE/DATA OUTLET WITH TWO DATA AND ONE VOICE CABLE DROPS. U.N.O. REFER TO SPECS
FOR CABLING REQ, UNLESS NOTED OTHERWISE. (1)
18"
(1) FOR EACH TELEPHONE AND/OR COMPUTER OUTLET, CABLE TELEVISION OUTLET, INSTALL
REQUIRED BACKCAN, CONDUIT (1" MINIMUM) w/INSULATED THROAT BUSHING AND PULL CORD, TO
ACCESSIBLE SPACE ABOVE CEILINGS, UNLESS NOTED OTHERWISE, PROVIDE AND TERMINATE
COMMUNICATION CABLE AND TELEVISION CABLE TO SPECIFIED JACKS.
1. THESE SYMBOLS COMPRISE A STANDARD LIST; NOT ALL SYMBOLS APPEAR ON THIS PROJECT.
2. ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE ABOVE FINISHED FLOOR. MOUNTING HEIGHTS
INDICATED ON ARCHITECTURAL WALL ELEVATIONS OR AS NOTED SPECIFICALLY ON THE DRAWINGS
OR IN THE SPECIFICATIONS SHALL TAKE PRECEDENCE OVER MOUNTING HEIGHTS LISTED.
DEVICE
P - 1
HH
ab
M a b
D
LV
OC
K
F
F
T
S
F
S
P
S
D
LUMINAIRE SCHEDULE
TYPE LAMPS DESCRIPTIONS MANUFACTURER CATALOG NO. OR SERIES
MOUNTING/
VOLTAGE
NOTES
A8 45.4W LED
8' LED PENDANT, 102 LUMENS PER WATT, 0-10V DIMMING. FINISH COLOR WHITE.
COOPER
DSI-WS-2L40-1-D-120-AC48-T1-8-
DC
SUSPENDED/
120V
1,5
B1 40W LED
2x4, LINEAR VOLUMETRIC, 0-10V DIMMING. FINISH COLOR WHITE.
COOPER R2X-WO-2L40-1D-120-24-XX-W6
RECESSED/
1,3
B1E 40W LED
SAME AS TYPE B1, WITH EMERGENCY BALLAST.
COOPER R2X-WO-2L40-1A-120-24-XX-W6
RECESSED/
1,3
D1 32W LED
6" LED DOWNLIGHT, 0-10V DIMMING. FINISH COLOR WHITE.
ATLANTIC LED6DLM20-4K-1-517/6LED10-WH
RECESSED/
1,3
D1E 32W LED
SAME AS TYPE D1, WITH INTEGRAL EMERGENCY BATTERY.
ATLANTIC
LED6DLM20-4K-1-LEM-
517/6LED10-WH
RECESSED/
1,3
D2 18W LED 6" LED DOWNLIGHT. FINISH COLOR WHITE. ATLANTIC LED6DLM11-4K-1-517/6LED10-WH
RECESSED/
1,3
D2E 18W LED
SAME AS TYPE D2, WITH INTEGRAL EMERGENCY BATTERY.
ATLANTIC
LED6DLM11-4K-1-LEM-
517/6LED10-WH
RECESSED/
1,3
E2 87W LED
DECORATIVE OUTDOOR LED FIXTURE, TYPE 3 DISTRIBUTION, FLAT-LENS FOR FULL
CUT-OFF, FOR ROUND POLE. SEE SHEET E1.1 AND E2.1.
PHILIPS DMS50-90W80LED-4K-R-LE3F
POLE-MOUNT/
E3 87W LED
DECORATIVE OUTDOOR LED FIXTURE, TYPE 3 DISTRIBUTION, DUAL-HEADS, FLAT-LENS
FOR FULL CUT-OFF, FOR ROUND POLE. SEE SHEET E1.1 AND E1.2.
PHILIPS DMS50-90W80LED-4K-R-LE3F
POLE-MOUNT/
F1 50W LED LENSED LED STRIP. COOPER
SNLED-LD1-49-LC-UNV-L840
-CD1-U
SURFACE/
1,7
F1E 50W LED
LENSED LED STRIP WITH INTEGRAL 1,400 LUMEN EMERGENCY BATTERY PACK.
COOPER
SNLED-LD1-49-LC-120-
EL10W-L840-CD1-U
SURFACE/
G1
(2) 13W GU24
WALL SCONCE. POLISHED CHROME FINISH. PROVIDE MISSION ELEGANT FROSTED BELL
SHADE #B9348. 4000k LAMP COLOR TEMPERATURE.
REJUVENATION
JORDAN VALLEY #A6475 with
#B9348 SHADE
WALL/
J1 23W CFL
MEDIUM-BASE PORCELAIN SOCKET. (FOR ATTIC LIGHTING)
LEVITON 9875
SURFACE/
P1 38.4W LED
18" DIAMETER SCHOOLHOUSE WITH PENDANT. 3408 LUMENS. FINISH COLOR DARK
BRONZE. TAPERED ESCUTCHEON PLATE.
ADVENT AIP8133-144403
STEM/
1,8
P2 38.4W LED
14" DIAMETER SCHOOLHOUSE WITH PENDANT. 3408 LUMENS. FINISH COLOR DARK
BRONZE. TAPERED ESCUTCHEON PLATE.
ADVENT AIP8131-144404
STEM/
1,8
S1
(1) 13W GU24
SCONCE WITH OIL-RUBBED BRONZE FINISH, AND 4000k LAMP COLOR TEMPERATURE.
REJUVENATION
JORDAN VALLEY #A9901 with
#B9348 SHADE
WALL/
UC LED
24" UNDER CABINET LIGHT WITH INTERNAL DRIVER. HARD WIRE TO WALL. ROCKER
SWITCH.
COOPER HU1024D830P/HU101P/HU106P
SURFACE/
X1
X2
LED'S
EXIT SIGN, EDGE-LIT, 90 MINUTE EMERGENCY OPERATION. "xW" - 1W FOR 1 FACE, OR
2W FOR 2 FACE.
e3LIGHTING ELT-EM-R-xW-WH-SC-UC
UNIVERSAL/
NOTES:
1. NO SUBSTITUTIONS ALLOWED. THE CONTRACTOR SHALL PROVIDE THE SAME LUMINAIRE MODELS, WHERE NEEDED IN PHASE 2, AS WERE PROVIDED IN PHASE 1.
2. VERIFY FINISH WITH ARCHITECT.
3. PROVIDE WITH 0-10V DIMMING.
4. CIRCUIT VIA TYPE EM INVERTER.
5. LAMP DATA IS FOR 4' CROSS-SECTION OF FIXTURE.
6. SUBMITTED LUMINAIRE REQUIRES PRIOR APPROVAL.
7. PROVIDE WITH WIRE-GUARD IN ELEVATOR PIT AND HOIST-WAY.
8. REFER TO ARCHITECT PLANS FOR EXACT PENDANT STEM LENGTHS, AND VERIFY EXACT MOUNTING HEIGHT TO BOTTOM OF FIXTURES, PRIOR TO ORDERING..
GENERAL NOTES: ALL LIGHTING SHALL MEET THE BUY AMERICAN ACT. IF LIGHTING DOES NOT MEET THE BUY AMERICAN ACT, THE GENERAL CONTRACTOR IS RESPONSIBLE TO VERIFY
COMPLIANCE.
THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL CEILING TYPES AND PROVIDE ALL REQUIRED MOUNTING ACCESSORIES. FOR FIRE-RATED CEILING ASSEMBLIES, VERIFY ALL RECESSED
LUMINAIRE HOUSINGS ARE FIRE-RATED OR PROVIDE FIRE-RATED, DROP-OVER ENCLOSURES OR TENT LUMINAIRE. VERIFY THAT DROP-OVER ENCLOSURES OR TENTS ALLOW FOR AIR SPACE
AROUND LUMINAIRE PER MANUFACTURER'S RECOMMENDATIONS. BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
2014 MORRISON-MAIERLE, INC.
28342 PE
BLOOMFIELD
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
A T
A D E F G H KCB J
M
DOWN DOWN
DOWN DOWN
DOWNDOWN
UP UP
RAMP
DOWN
RAMP
DOWN
RAMP
DOWN
DOWN DOWN
UP UP
101.4
DEMO
TEMP DOOR
AND
WALL
R R R
CARD
READER
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
(N) FE CAB
1008.1.8 DOOR
ARRANGEMENT:
SPACE BETWEEN TWO
DOORS IN A SERIES SHALL
BE 48" MIN. PLUS THE
WIDTH OF A DOOR
SWINGING INTO THE
SPACE. DOORS IN A
SERIES SHALL SWING
EITHER IN THE SAME
DIRECTION OR AWAY
FROM THE SPACE
BETWEEN THE DOORS.
CARD READER,
NO HOLD OPENS
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
EX PNL
EX PNL
EX MECH. RM
(IN BASEMENT)
FI
R
ST
F
LO
O
R D
EM
O
P
LA
N
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO
CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS, BOXES AND
OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE FINAL PLACEMENT OF
MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD VERIFIED.
THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. COORDINATE AVAILABLE SPACE FOR EQUIPMENT AND PIPING SYSTEMS
WITH OTHER TRADES. REFER TO ARCHITECTURAL, STRUCTURAL,
PLUMBING, AND ELECTRICAL DRAWINGS AND FIRE PROTECTION SHOP
DRAWINGS FOR ADDITIONAL DETAILS NECESSARY FOR COORDINATION.
4. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL
DRAWINGS TO VERIFY HOW AND WHERE CONCRETE CAN BE CUT.
5. INTENT OF ALL WORK: PHASE 2 - REMODEL AND FINISH THE FIRST AND
SECOND FLOORS; PHASE 3 - REMODEL AND FINISH THE BASEMENT.
6. NOT ALL EXISTING EQUIPMENT/DEVICES FOR DEMO HAVE BEEN SHOWN ON
THESE PLANS.
7. PERTAINING TO THE AREA CONTAINED BETWEEN GRIDLINES "1" AND "2", "A"
AND "D": SALVAGE ALL BRASS FACEPLATES FROM DEMO'D OUTLETS TO
CONTRACTING OFFICER.
KEY NOTES:
USFS BUILDING 26 - FIRST FLOOR ELECTRICAL DEMO PLAN 16
DE7.1 : DE7.1 1/8" = 1'-0"
NORTH
DE7.1
1. PHASE 2 AREA FOR ELECTRICAL DEMO: DISCONNECT/REMOVE ALL
EQUIPMENT, POWER, LIGHTING, SIGNAL DEVICES, CONDUIT AND WIRE BACK
TO THEIR SOURCE, INCLUDING TEMPORARY INTERIOR LIGHTING FROM PHASE
1, UNLESS NOTED OTHERWISE. ALL EXTERIOR LIGHTING IS TO REMAIN.
CONTRACTOR CAN RE-USE EXISTING CONDUIT, FOR NEW CIRCUITS, WHERE
DEEMED ACCEPTABLE. SEE KEYNOTE 4, THIS SHEET.
2. EX RADON FAN: TO REMAIN.
3. PROTECT ALL NEWLY INSTALLED ELECTRICAL EQUIPMENT, FIXTURES,
DEVICES, CONDUIT AND CONDUCTOR PATHS TO THE DEMO'D AREA.
4. PERTAINING TO EX MECH ROOM IN BASEMENT BELOW THIS REGION: EXISTING
BOILER, WATER HEATER AND THEIR HOUSE-KEEPING PAD ARE TO BE DEMO'D
COMPLETELY. DISCONNECT/REMOVE EX CIRCUITS AND RELATED
DISCONNECTS, BACK TO SOURCE PANEL.
GENERAL NOTES:
2014 MORRISON-MAIERLE, INC.
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
1-HOUR FIRE-
RESISTIVE RATED
CEILING:
(2) LAYERS
" GYP. BD.
DEMO (E)
ACCESS
HATCH
DEMO (E)
ACCESS
HATCH
DOWNDOWN
DOWN
DOWNDOWN
DOWNDOWN
DOWNDOWN
DOWN
DOWN
(E)
SWR
(N)
FSR
BOILER
VENT
BOILER
VENT
R
R
R
EX
F1
EX PNL
EX PNL
SE
C
O N
D F
LO
O
R D
EM
O
P
LA
N
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO COORDINATE
WITH EACH OTHER AND VERIFY THAT THERE ARE NO CONFLICTS IN LOCATION
OF DUCTS, CONDUITS, DIFFUSERS, BOXES AND OTHER ITEMS THROUGHOUT
THIS PROJECT BEFORE FINAL PLACEMENT OF MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD VERIFIED.
THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. COORDINATE AVAILABLE SPACE FOR EQUIPMENT AND PIPING SYSTEMS WITH
OTHER TRADES. REFER TO ARCHITECTURAL, STRUCTURAL, PLUMBING, AND
ELECTRICAL DRAWINGS AND FIRE PROTECTION SHOP DRAWINGS FOR
ADDITIONAL DETAILS NECESSARY FOR COORDINATION.
4. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL DRAWINGS
TO VERIFY HOW AND WHERE CONCRETE CAN BE CUT.
5. INTENT OF ALL WORK: PHASE 2 - REMODEL AND FINISH THE FIRST AND
SECOND FLOORS; PHASE 3 - REMODEL AND FINISH THE BASEMENT.
6. NOT ALL EXISTING EQUIPMENT/DEVICES FOR DEMO HAVE BEEN SHOWN ON
THESE PLANS.
KEY NOTES:
USFS BUILDING 26 - SECOND FLOOR ELECTRICAL DEMO PLAN 16
DE7.2 : DE7.2 1/8" = 1'-0"
NORTH
DE7.2
1. PHASE 2 AREA FOR ELECTRICAL DEMO: REMOVE ALL EQUIPMENT, DEVICES,
CONDUIT AND CONDUCTORS ENTIRELY, UNLESS NOTED OTHERWISE. ALL
EXTERIOR LIGHTING TO REMAIN. CONTRACTOR CAN RE-USE EXISTING
CONDUIT FOR NEW CIRCUITS, WHERE DEEMED ACCEPTABLE.
2. THIS FIXTURE WAS ADDED AS PART OF PHASE 1. DISCONNECT AND REMOVE
FIXTURE, CONDUIT AND CONDUCTORS, BACK TO NEAREST UPSTREAM
DEVICE, TO MAINTAIN ORIGINAL CIRCUIT CONTINUITY.
3. PROTECT ALL NEWLY INSTALLED ELECTRICAL EQUIPMENT, FIXTURES,
DEVICES, CONDUIT AND CONDUCTOR PATHS TO THE DEMO'D AREA..
4. PERTAINING TO THE AREA CONTAINED BETWEEN GRIDLINES "1" AND "2", "A"
AND "D": SALVAGE ALL BRASS FACEPLATES FROM DEMO'D OUTLETS TO
CONTRACTING OFFICER.
GENERAL NOTES:
2014 MORRISON-MAIERLE, INC.
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
N O
R T
H P
A R
K
IN
G
IM
PR
O V
EM
EN
T L
IG
H
T
IN
G P
LA
N
NORTH PARKING IMPROVEMENT LIGHTING PLAN16
E1.1 : E1.1 1" = 20'-0"
NORTH
E1.1
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE
NO CONFLICTS IN LOCATION OF PIPES, CONDUITS, EXISTING
OVERHEAD AND BURIED SERVICES AND OTHER ITEMS
THROUGHOUT THIS PROJECT BEFORE FINAL PLACEMENT OF
MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD
VERIFIED. THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. REFER TO ARCHITECTURAL, CIVIL, AND ELECTRICAL DRAWINGS
FOR ADDITIONAL DETAILS NECESSARY FOR COORDINATION
BETWEEN ALL SYSTEMS.
4. SEE CIVIL SHEETS FOR NORTHWESTERN ENERGY DEMO.
KEY NOTES:
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
GENERAL NOTES:
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
A T
0 2020 4010
SCALE
IN FEET
LED LAMP
LONG REINF.
SEE
SCHEDULE
ANCHOR
BOLTS FROM
POLE MANF.
2'-6"
DEPTH OF EMBED
SEE SCHEDULE.
HORIZ. TIES
SEE
SCHEDULE
PROVIDE LONG AT ALL FOUR CORNERS OF SQUARE PIER.
PROVIDE SPACING OF S/3 AT TOP 1'-0" OF PIER.
DEPTH BELOW FINISHED GRADE.
SPACE LONG. STEEL EVENLY AROUND PERIMETER.
PROVIDE REINF. CLEARANCE PER ACI 318.
HEIGHT AFG
SEE SCHEDULE UNO
FINISH GRADE. COMPACT SOILI N
6" MAX LIFTS IN EXCAVATED AREA
AROND POLE FOUNDATION
POLE FDN
SIZE. SEE
SCHEDULE
SEE SITE PLAN
FOR CONDUIT SIZE
1" CHAMFER
LIGHT FIXTURE BASE SCHEDULE *****
POLE
HEIGHT
SIZE
LONG
STL
HORIZONTAL
STL **
14' - 30'
DEPTH ***
HEIGHT AFG
7'-0"
7'-0"
2'-6"
2'-6"
20" SQ.
24" Ø
(4) # 7 *
(6) # 6 ****
#3 AT 12" O.C.
#3 AT 12" O.C.
HORIZ. TIES SEE
SCHEDULE
CONTRACTOR SHALL PREP EXPOSED BASE FOR EUCLID VERTICOAT. APPLY PER MANUFACTURER
INSTRUCTIONS TO PROVIDE A FINISHED APPEARANCE
POLE BASE DETAIL10
E1.1:E1.2 NOT TO SCALE
NOT TO SCALE
LIGHT POLE ELEVATION20
E1.1:E1.2
E3
E3
E2
1. PROVIDE PAD-MOUNTED, COMBINATION METERBASE PEDESTAL
WITH INTEGRAL LOADCENTER, MILBANK CP3B "SL" SERIES, OR
APPROVED EQUAL, FOR PARKING LOT LIGHTING AND FUTURE
ACCESS GATE POWER. SEE DETAIL 8, THIS SHEET.
2. COORDINATE WITH UTILITY (NWE), FOR EXACT SECONDARY
RISER AND CONDUIT REQUIREMENTS, PRIOR TO BID.
COORDINATE WITH CIVIL FOR EXISTING BURIED SERVICES.
3. PROVIDE (1) 1" C.O. WITH PULL-STRING BACK TO POWER
PEDESTAL, FOR FUTURE ACCESS GATE. COORDINATE EXACT
LOCATION WITH OWNER, PRIOR TO TRENCHING.
4. CIRCUIT BACK TO PNL S1 IN POWER PEDESTAL, WITH #10 CU IN
1" C.
5. STUB/CAP 1" CONDUIT, WITH PULL-STRING, PAST EDGE OF
PARKING LOT, FOR FUTURE LIGHTING EXPANSION.
6. PROVIDE (1) 1" C.O. WITH PULL-STRING BACK TO POWER
PEDESTAL, FOR FUTURE WARE-YARD LIGHTING.
DUAL-HEAD PARTIAL DETAIL
COLOR AS SELECTED
BY C.O.
NEW POLE-MOUNT
UTILITY XFMR ON
EXISTING POLE,
BY UTILITY.
CIRCUIT TO SOUTH
PARKING LOT LIGHTING
NOT TO SCALE
METER DETAIL8
E2.5:E9.2
1"C TO LIGHTING
2"C.0 TO TRANSFORMER
FINISHED GRADE
PHOTOCELL
NEMA 3R LIGHTING CONTROL ENCLOSURE WITH DEFINITE
PURPOSE LIGHTING CONTACTORS CONTROLLED VIA
PHOTOCELL AND TIMECLOCK (INTEGRAL TO METER PEDESTAL
UNIT). CONTACTOR SHALL BE SIZED TO ACCOMMODATE ALL
CIRCUITS SHOWN ON PANEL SCHEDULE, UNLESS NOTED
OTHERWISE. SEE PANEL SCHEDULE, SHEET E1.2.
METER BASE PEDESTAL WITH
120/240V, 1Ø 100A DISCONNECT
PER UTILITY REQUIREMENTS.
INTEGRAL LOAD CENTER (PANEL "S1")
CONCRETE BASE
NOTE:
CONTRACTOR SHALL PROVIDE 1-1" SPARE C.O.
STUBBED TO OUTSIDE CONCRETE PAD.
GND PER NEC
POWER PEDESTAL
METERBASE WITH
PANEL "S1"
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SO
U
T H
P A
R K
IN
G
I M
PR
O
V
EM
EN
T
L
IG
H T
IN
G
P
LA
N
SOUTH PARKING IMPROVEMENT LIGHTING PLAN16
E1.2 : E1.2 1" = 20'-0"
NORTH
E1.2
KEY NOTES:
1. CIRCUIT BACK TO PNL S1 IN POWER PEDESTAL, WITH #8 CU IN 1"
C.
2. PROVIDE (1) 1" C.O. WITH PULL-STRING BACK TO POWER
PEDESTAL, FOR FUTURE ACCESS GATE. COORDINATE EXACT
LOCATION WITH OWNER, PRIOR TO TRENCHING.
3. STUB/CAP CONDUIT, WITH PULL-STRING, PAST SOUTH END OF
PARKING LOT, FOR FUTURE EXPANSION.
4. SEE CIVIL DRAWINGS FROM NORTHWESTERN ENERGY DEMO.
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
A T
0 2020 4010
SCALE
IN FEET
E3
E3
E3
TO PNL S1 IN POWER
PEDESTAL AT NORTH
PARKING LOT.
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE
NO CONFLICTS IN LOCATION OF PIPES, CONDUITS, EXISTING
OVERHEAD AND BURIED SERVICES AND OTHER ITEMS
THROUGHOUT THIS PROJECT BEFORE FINAL PLACEMENT OF
MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD
VERIFIED. THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. REFER TO ARCHITECTURAL, CIVIL, AND ELECTRICAL DRAWINGS
FOR ADDITIONAL DETAILS NECESSARY FOR COORDINATION
BETWEEN ALL SYSTEMS.
GENERAL NOTES:
EXISTING CONCRETE BLOCK
TO REMAIN. ROUTE LIGHTING
CONDUIT TO AVOID CONFLICT.
TO PIT
LUMINAIRE
GF1
BLR1
BLR2
BS104
BS108
EH2
HP2
EH3
M M
HP1
MM M M
REMOTE-MOUNTED
COOLING TOWER VFD
CONTROL PANEL,
CERUS CTP1 SERIES.
WH1
DHWP1
BP1
M
BP2
M
BS106
ECU1
INDOOR
UH2
UH1
WS1
P2
P1
M
M
P3 M
EF3
M
001.1
001.3
003.1
002.1
004.1
008.1
PNL M2B
HP4
M
M
HP3
MM
M M
M1B-11
MECH. ROOM (SOUTH)
MECH. ROOM (NORTH)
EX PNL M1A
EX FACP
EX PNL M2A
EX PNL C
EX MDM
EX EXTERIOR LIGHTING CONTROL
PANEL AND EM INVERTER
EX MDR
EX RB
EX MDP
BLR3
BLR4
M
M
P4
P5
UH4
(TEMPORARY HEAT
FOR PHASE 2)
UH3
(TEMPORARY HEAT
FOR PHASE 2)
M
M
BP3 BP4
(2) 3/4" EX CONDUIT
AVAILABLE FOR
NEW CIRCUITS
M1B-19,21,23
M1B-13,15,17
M1B-25,27,29 M1B-37,39.41
M1B-31,33,35
M1B-7,9,11
PNL M1B
M1B-38,40
M1B-32
M1B-2,4
BS130
M1B-2,4
BS129
M1A-2 M1A-4
M1A-13
M2B-10,12,14
M2B-16,18,20
M2B-6
A D E F G H KCB J
BA
SE
M
EN
T P
O W
ER
P
LA
N
USFS BUILDING 26 - BASEMENT POWER PLAN16
E2.0 : E2.0 1/8" = 1'-0"
NORTH
E2.0
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE
NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS,
BOXES AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE
FINAL PLACEMENT OF MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD
VERIFIED. THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. COORDINATE AVAILABLE SPACE FOR EQUIPMENT AND PIPING
SYSTEMS WITH OTHER TRADES. REFER TO ARCHITECTURAL,
STRUCTURAL, PLUMBING, AND ELECTRICAL DRAWINGS AND FIRE
PROTECTION SHOP DRAWINGS FOR ADDITIONAL DETAILS
NECESSARY FOR COORDINATION.
4. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL
DRAWINGS TO VERIFY HOW AND WHERE CONCRETE CAN BE CUT.
5. REFERENCE MECHANICAL COORDINATION SCHEDULE, SHEET
E9.3, FOR ADDITIONAL EQUIPMENT STARTER/DISCONNECT AND
CIRCUIT INFORMATION.
6. PERIMETER WALLS HAVE BEEN FURRED OUT. PROVIDE SHALLOW
BOX FOR ALL OUTLETS IN PERIMETER WALLS.
7. ALL EXTERIOR OUTLETS SHALL BE INSTALLED IN FLUSH-MOUNT
JBOX. CONTRACTOR SHALL SAW-CUT EXTERIOR WALL CEMENT,
TO FLUSH-MOUNT JBOX. PATCH/PAINT TO MATCH EXISTING
FINISH.
8. HOLD ALL ELECTRICAL CONDUIT TIGHT TO THE UNDERSIDE OF
STRUCTURE, AND ROUTE IN JOIST SPACES WHERE POSSIBLE TO
MAXIMIZE HEAD HEIGHT FOR FUTURE PHASES.
9. ALL WORK SHOWN ON THIS SHEET IS PART OF PHASE 3.
10. SHADED ITEM ARE EXISTING, TO REMAIN.
11. ALL FIRE WALLS ARE 12" THICK CONCRETE. ELECTRICAL
CONTRACTOR RESPONSIBLE FOR ALL CORE DRILLING.
KEY NOTES:
GENERAL NOTES:
2014 MORRISON-MAIERLE, INC.
1. INTERCEPT CIRCUIT FROM EXISTING BOILER RECEPTACLE AND EXTEND TO
NEW BOILER RECEPTACLE. ALL BOILERS ARE TO SHUNT OFF, VIA EXISTING
BOILER SHUNT TRIP.
2. FOR NEW BOILER PUMP BP4, CONTRACTOR SHALL EXTEND AVAILABLE 3/4"
CONDUIT (INSTALLED IN PREVIOUS PHASE) FROM BP4 BACK TO EX PANEL M1A.
3. THIS CIRCUIT EXTENDS UP TO FIRST FLOOR EQUIPMENT. SEE SHEE E2.1.
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
A T
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
BS102
FC102B
FC102A
FC101C
FC100A
FC100B
FC102D
FC102C
FC103
FC105A
FC108A
FC108C
FC107B
FC107C
FC107A
FC107D
FC104
FC106A
FC101B
FC100C
BS103
FC107F
FC107E
FC108B
FC108D
FC108E
FC106B
BS205
BS100
FC101A
FC101D
EH1
FC105B
BS105
FC108F
M
CT1
FC108G
BS101
BS107
M
M
M
ECU1
OUTDOOR
FSD
UR1
UR1
L1
L1
WC1
WC2
WC2
WC2
WC2
WC1
EF1
M
EH4
CONF/
NURSE
CONFERENCE
OFFICE
125OFFICE
OPEN
OFFICE
OPEN
OFFICE
ENTRY
HALL
RECEPTION
BREAK
PRIVATE
OFFICE
HR
JANITOR
WOMENS
RESTROOM
MENS
RESTROOM
EXECUTIVE
ASSISTANT
(2 STAFF)
REGIONAL
FORESTER
DEPUTY
REGIONAL
FORESTER
DEPUTY
REGIONAL
FORESTER
COFFEE / PRINT
115LARGE
CONFERENCE
TELE/DATA
PRINT / COPY / FAX
CONFERENCE
ENTRY
ELEVATOR
A
PORCH
STAIR
PORCH
DOWN DOWN
DOWN DOWN
DOWNDOWN
UP UP
RAMP
DOWN
RAMP
DOWN
RAMP
DOWN
DOWN DOWN
UP
CONFERENCE
UP
DEMO
TEMP DOOR
AND
WALL
(N)
FSR R R R
OFFICE
OFFICE
OFFICE
OPEN
OFFICE
OPEN
OFFICE
OFFICE
OFFICE
OPEN
OFFICE
CONFERENCE
STAIR
PORCH
CARD
READER
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
(N) FE CAB
1008.1.8 DOOR
ARRANGEMENT:
SPACE BETWEEN TWO
DOORS IN A SERIES SHALL
BE 48" MIN. PLUS THE
WIDTH OF A DOOR
SWINGING INTO THE
SPACE. DOORS IN A
SERIES SHALL SWING
EITHER IN THE SAME
DIRECTION OR AWAY
FROM THE SPACE
BETWEEN THE DOORS.
CARD READER,
NO HOLD OPENS
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
SMALL
CONFERENCE
FC133C
BS136
FC136
FC132B
FC132A
FC132F
FC132E
FC133B
FC133D
2 2
BS133
GFI
FC132H
FC132D
FC132G
1-HR FIRE
RATING
1-HR FIRE RATING
EX PNL L1A
EX PNL R1A
EX PoE NETWORK SWITCH
EX FA ANNUNCIATOR
EX 4" C.O. BETWEEN BASEMENT AND FIRST FLOOR
EX 4" C.O. BETWEEN FIRST AND SECOND FLOOR
EX SWITCHGEAR, WITH
SERVICE DISCONNECT
AND METER.
PNL L1B
PNL R1B
(3) EX 1" C, AVAILABLE FOR
USE IN THIS PROJECT
(FOR POWER/DATA)
R1B-1
R1B-1
R1B-1
R1B-1
R1B-3 R1B-3
R1B-3
R1B-5 R1B-5
R1B-5
R1B-7
R1B-7
R1B-9
R1B-9
R1B-11
R1B-9
R1B-11
R1B-11
R1B-13
R1B-13
R1B-13
R1B-15
R1B-15
R1B-25
R1B-25
R1B-25
R1B-25
R1B-2,4,6
R1B-8,10,12
R1B-14,16,18
R1B-20,22,24
R1B-32,34,36
R1B-56,58,60
R1B-62,64,66
R1B-21
R1B-19
R1B-21
FC134
FC135
BS135
BS134
EH6
FC132C
BS132A
BS128
FC129
FC128B
FC130
FC128A
EX CONDUIT AVAILABLE FOR
NEW PANIC SIGNAL SYSTEM.
AUDIBLE/VISIBLE
ALERT DEVICE.
PANIC SYSTEM
PUSH-BUTTON
R1B-23
R1B-19
R1B-17
M1B-6,8
M1B-2,4
M1B-2,4
M1B-2,4
M1B-2,4
M1B-2,4
M1B-2,4
M1B-2,4 M1B-2,4
M1B-2,4
M1B-2,4
M1B-2,4
M1B-2,4
M1B-2,4
M1B-2,4
FC133A
M1B-6,8
M1B-6,8
M1B-6,8
M1B-6,8
M1B-6,8
M1B-6,8
M1B-6,8
M1B-6,8
M1B-36
M1B-6,8
M1B-6,8
R1B-7R1B-7
BS132B
M1B-2,4
BS139
M1B-2,4
FC139
M1B-2,4
R1B-27
R1B-27
POWER POLE
POWER POLE
R1B-38,40,42
R1B-44,46,48
R1B-50,52,54
R1B-67,69,71
R1B-26,28,30
R1B-68,70,72
R1B-27
R1B-27
EX
FI
R
ST
F
LO
O
R P
O W
ER
P
LA
N
USFS BUILDING 26 - FIRST FLOOR POWER PLAN16
E2.1 : E2.1 1/8" = 1'-0"
NORTH
E2.1
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO
CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS,
BOXES AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE
FINAL PLACEMENT OF MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD
VERIFIED. THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. COORDINATE AVAILABLE SPACE FOR EQUIPMENT AND PIPING
SYSTEMS WITH OTHER TRADES. REFER TO ARCHITECTURAL,
STRUCTURAL, PLUMBING, AND ELECTRICAL DRAWINGS AND FIRE
PROTECTION SHOP DRAWINGS FOR ADDITIONAL DETAILS
NECESSARY FOR COORDINATION.
4. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL
DRAWINGS TO VERIFY HOW AND WHERE CONCRETE CAN BE CUT.
5. REFERENCE MECHANICAL COORDINATION SCHEDULE, SHEET E9.3,
FOR ADDITIONAL EQUIPMENT CIRCUIT INFORMATION.
6. PERIMETER WALLS HAVE BEEN FURRED OUT TO 1-1/2". PROVIDE
SHALLOW BOX FOR ALL OUTLETS IN PERIMETER WALLS.
7. ALL EXTERIOR OUTLETS SHALL BE INSTALLED IN FLUSH-MOUNT
JBOX. CONTRACTOR SHALL SAW-CUT EXTERIOR WALL CEMENT TO
FLUSH-MOUNT JBOX. PATCH/PAINT TO MATCH EXISTING FINISH.
8. MOUNT ALL ADA PUSH-BUTTONS AT +42" AFF, TO TOP OF
PUSH-BUTTON.
9. SHADED ITEMS ARE EXISTING, TO REMAIN.
10. ALL FIRE WALLS ARE 12" THICK CONCRETE. ELECTRICAL
CONTRACTOR RESPONSIBLE FOR ALL CORE DRILLING
KEY NOTES:
1. ALL MEANS AND MATERIALS FOR WORK ON THIS WALL SECTION
SHALL MEET 1-HR FIRE RATING REQUIREMENTS.
2. OPEN OFFICE AREA - POWER AND DATA TO RUN TO FURNITURE:
PROVIDE (3) HOT, (3) NEUTRALS, (1) GROUND, (1) ISOLATED
GROUND CONDUCTORS TO 4-11/16" SQUARE, FLUSH-MOUNT
JBOX WITH MODULAR FACE-PLATE IN WALL AT FURNITURE PANEL
LOCATION. RUN ISOLATED GROUND CONDUCTOR TO GROUND
BUS IN THE PANEL. PLUGGABLE, MODULAR FURNITURE WHIPS TO
CONNECT BETWEEN FACE-PLATE AND FURNITURE PANEL.
COORDINATE EXACT LOCATION WITH FURNITURE CONTRACTOR,
PRIOR TO ROUGH-IN. SEE KEYNOTE 1, SHEET E2.4, FOR
ASSOCIATED TELE/DATA REQUIREMENTS. MODULAR FACEPLATE
AND WHIP BY FURNITURE PROVIDER. (TYP OF ALL POWERED
FURNITURE DROP LOCATIONS.)
3. ALL SHADED WORK SHOWN SOUTH OF THIS GRID LINE IS
EXISTING, TO REMAIN, UNLESS NOTED OTHERWISE.
4. PART OF PANIC SIGNAL SYSTEM: PROVIDE COMPLETE
MANUALLY-ACTIVATED, HARD-WIRED, 120V PANIC SIGNAL
SYSTEM, WITH ENCLOSED PUSH-BUTTON, REMOTE-MOUNTED
AUDIBLE ALERT DEVICE, AND ALL NECESSARY TRANSFORMERS,
ACCESSORIES FOR COMPLETE WORKING SYSTEM. INSTALL
PUSH-BUTTON IN RECEPTION 102 DESK AREA, AND AUDIBLE
ALERT DEVICE IN OFFICE 128. WHEN PUSH-BUTTON IS
ACTIVATED, THE ALERT SYSTEM AUDIBLE ALARM SHALL TURN
ON. THE AUDIBLE ALERT TONE CAN BE SILENCED AT THE
REMOT-MOUNTED AUDIBLE ALERT DEVICE, BUT THE ALARM
SHALL STAY ACTIVE UNTIL THE PUSH-BUTTON IS PRESSED A
SECOND TIME. THE PUSH-BUTTON SHALL INDICATE WHEN IT IS IN
THE ACTIVE STATE. COORDINATE WITH OWNER FOR EXACT
DEVICE LOCATIONS, PRIOR TO ROUGH-IN. DESIGN IS BASED ON
THE TEKTONE CM800 STAND-ALONE EMERGENCY CALL SYSTEM,
INCLUDING: MODEL# CM800/4 ANNUNCIATOR AND EMERGENCY
PUSH-BUTTON SF154B.
5. THIS CIRCUIT EXTENDS TO BASEMENT EQUIPMENT. SHEET SHEET
E2.0.
6. SURFACE CONDUIT BETWEEN FLOORS IS ACCEPTABLE IN THIS
ROOM ONLY.
7. POWER POLE (BY FURNITURE PROVIDER): ELECTRICAL
CONTRACTOR SHALL PROVIDE JUNCTION BOX IN ACCESSIBLE
CEILING AND WHIP CONNECTIONS DOWN POWER POLE TO
POWERED FURNITURE PANEL. PROVIDE LONG ENOUGH WHIP
CONNECTION TO ACCOMMODATE SLIGHT ADJUSTMENT OF THE
POWERED FURNITURE PANEL LOCATION IN THE AREA INDICATED.
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
A
209.1
207.1
206.2
201.1
202.2
202.1 203.1 204.1
205.1
206.1
\pxqc;(E)\PSWR\pxqc;(N)\PFSR
\pxqc;BOILER\PVENT
\pxqc;BOILER\PVENT
\pxqc;R
\pxqc;R
\pxqc;R
\pxqc;(N)\PFSR
M
FC200A
FC200B
FC200C
FC201
FC200D
FC200E
FC200F
FC203
FC204
FC202A FC202E
FC202B
FC202F
FC202C
FC202G
FC202D
FC202H
FC205A
FC205B
BS206
FC206
BS204
BS203
BS201
FC205C
BS202
BS200
D
D
D
HEAT TRACE
EF2
M
EH4
OFFICE
OFFICE
OFFICE
SMALL
CONFERENCE
SMALL
CONFERENCE
OPEN
OFFICE
OPEN
OFFICE
STAIR
ELEVATOR
A
PORCH
PORCH
DOWNDOWN
DOWN
DOWNDOWN
DOWNDOWN
DOWNDOWN
DOWN
TELE/DATA
211JANITOR
SMALL
CONFERENCE
DOWN
(E)
SWR
(N)
FSR
BOILER
VENT
BOILER
VENT
R
R
R
R R
12"Ø
EXHAUST
12"Ø
EXHAUST
6"Ø 8"Ø
WOMENS
RR
MENS
RR
OFFICE
(N)
FSR R R R
DOWN
OFFICE
OPEN
OFFICE
LARGE
CONFERENCE
CONFERENCE
OPEN
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
FILES
OFFICE
CONFERENCE
OFFICE
STAIR
PORCH
PLOT
HALL
OFFICE
OFFICE
GFI
2 2
FC224A
FC226
FC223C
FC223A
FC223B
FC223E
FC233A
BS221
BS229
BS223
FC233B
FC227B
FC227C
FC229A
FC229B
FC223D
FC222A
FC222D
FC222B FC222E
PROJECTOR SCREEN
PROJECTOR (CEILING)
FC213A
GFI
UR1
L1
WC2
UR1
WC1WC1
WC2
WC2
WC2
L1
GFI
GFI
GFI
FC217D
FC217C
FC217A FC217B
FC217E
1-HR FIRE RATING
1-HR FIRE RATING
EX PNL R2A
EX PoE NETWORK SWITCH
NEW PNL R2B
GFI
FC213B
R2B-1
R2B-1
R2B-1
R2B-1 R2B-1
R2B-3
R2B-3
R2B-3
R2B-5
R2B-5
R2B-5
R2B-7
R2B-7
R2B-7
R2B-9
R2B-9
R2B-9
R2B-11
R2B-11
R2B-11
R2B-13
R2B-13
R2B-13
R2B-2
R2B-15
R2B-17
R2B-17
R2B-29
R2B-23
R2B-29R2B-29
R2B-29
R2B-29
R2B-29
R2B-31
R2B-31
R2B-31
R2B-57 R2B-57
R2B-51
R2B-51
R2B-51
R2B-53
R2B-53
R2B-53
R2B-55
R2B-55
R2B-55
R2B-35
R2B-35
R2B-35
R2B-37
R2B-37
R2B-37
R2B-39
R2B-39
R2B-41
R2B-41
R2B-43
R2B-43 R2B-43
R2B-43
R2B-45
R2B-45
R2B-45
R2B-49
R2B-49
R2B-47 R2B-47
R2B-8,10,12
R2B-38,40,42 R2B-44,46,48
R2B-21
MICROWAVE
FRIDGE
FC227A
BS233
FC224B
BS224
BS226
BS222
FC222F
FC222C
FC217F FC217G
BS217
BS213
BS227
R2B-19
GFI
R2B-27
R2B-25
R2B-15
R2B-17
M1B-10,12
M1B-10,12
M1B-10,12
M1B-10,12
M1B-10,12
M1B-10,12
M1B-10,12
M1B-10,12
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-14,16
M1B-18,20
M1B-18,20 M1B-18,20
M1B-18,20 M1B-18,20
M1B-18,20
M1B-18,20
M1B-18,20
M1B-18,20
M1B-18,20
M1B-18,20
M1B-18,20
FC221
M1B-14,16
ATTIC HATCH
FC227A
M1B-10,12
HRV2
M1B-30,32
M1B-34
HEAT-TRACE
M1B-34
(IN ATTIC)
M2B-1
M2B-1
M2B-1
M2B-1
M2B-1
M2B-1
M2B-1
M2B-1
M2B-1
M2B-1
EWC1
R2B-33
R2B-33
R2B-33
GFI
R2B-17
R2B-57
5 5
EH7
M2B-2
R2B-23
R2B-2
R2B-2
FLOORBOX
FLOORBOX
SE
C
O N
D F
LO
O
R P
O W
ER
P
LA
N
USFS BUILDING 26 - SECOND FLOOR POWER PLAN16
E2.2 : E2.2 1/8" = 1'-0"
NORTH
E2.2
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO
CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS,
BOXES AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE
FINAL PLACEMENT OF MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD
VERIFIED. THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. COORDINATE AVAILABLE SPACE FOR EQUIPMENT AND PIPING
SYSTEMS WITH OTHER TRADES. REFER TO ARCHITECTURAL,
STRUCTURAL, PLUMBING, AND ELECTRICAL DRAWINGS AND FIRE
PROTECTION SHOP DRAWINGS FOR ADDITIONAL DETAILS
NECESSARY FOR COORDINATION.
4. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL
DRAWINGS TO VERIFY HOW AND WHERE CONCRETE CAN BE CUT.
5. REFERENCE MECHANICAL COORDINATION SCHEDULE, SHEET E9.3,
FOR ADDITIONAL EQUIPMENT CIRCUIT INFORMATION.
6. PERIMETER WALLS HAVE BEEN FURRED OUT TO 1-1/2". PROVIDE
SHALLOW BOX FOR ALL OUTLETS IN PERIMETER WALLS.
7. ALL EXTERIOR OUTLETS SHALL BE INSTALLED IN FLUSH-MOUNT
JBOX. CONTRACTOR SHALL SAW-CUT EXTERIOR WALL CEMENT TO
FLUSH-MOUNT JBOX. PATCH/PAINT TO MATCH EXISTING FINISH.
8. VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT, PRIOR
TO ROUGH-IN.
9. ALL FIRE WALLS ARE 12" THICK CONCRETE. ELECTRICAL
CONTRACTOR RESPONSIBLE FOR ALL CORE DRILLING.
10. ALL FIRE WALLS ARE 12" THICK CONCRETE. ELECTRICAL
CONTRACTOR RESPONSIBLE FOR ALL CORE DRILLING.
KEY NOTES:
GENERAL NOTES:
2014 MORRISON-MAIERLE, INC.
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
1. 1HR FIRE-RATING BOUNDARY: ALL MEANS AND MATERIALS FOR
WORK IN THIS AREA SHALL MEET 1-HR FIRE RATING
REQUIREMENTS. ALL PENETRATIONS WILL REQUIRE CORE DRILL
THROUGH EXISTING WALL.
2. OPEN OFFICE AREA - POWER AND DATA TO RUN TO FURNITURE:
PROVIDE (3) HOT, (3) NEUTRALS, (1) GROUND, (1) ISOLATED
GROUND CONDUCTORS TO 4-11/16" SQUARE, FLUSH-MOUNT
JBOX WITH MODULAR FACE-PLATE IN WALL AT FURNITURE
PANEL LOCATION. RUN ISOLATED GROUND CONDUCTOR TO
GROUND BUS IN THE PANEL. PLUGGABLE, MODULAR FURNITURE
WHIPS TO CONNECT BETWEEN FACE-PLATE AND FURNITURE
PANEL. COORDINATE EXACT LOCATION WITH FURNITURE
CONTRACTOR, PRIOR TO ROUGH-IN. SEE KEYNOTE 1, SHEET
E2.5, FOR ASSOCIATED TELE/DATA REQUIREMENTS. MODULAR
FACEPLATE AND WHIP BY FURNITURE PROVIDER. (TYP OF ALL
POWERED FURNITURE DROP LOCATIONS.)
3. PROJECTOR SCREEN SYSTEM: CIRCUIT WALL-0MOUNTED
MOTORIZED PROJECTOR SCREEN VIA TOGGLE SWITCH PER
MANUFACTURER RECOMMENDATIONS. COORDINATE WITH
PENDANT LIGHT FIXTURE LOCATION AND PROJECTOR
MANUFACTURER RECOMMENDATIONS FOR EXACT
CEILING-MOUNT PROJECTOR MOUNTING LOCATION, PRIOR TO
ROUGH-IN.
4. CIRCUIT VIA 12V TRANSFORMER, PER MANUFACTURER
RECOMMENDATIONS. (TYPICAL OF ALL UR1, WC1 AND WC2
EQUIPMENT.)
5. FEED OUTLET FROM ATTIC SPACE, IN FURRED OUT WALL.
6. ALL SHADED WORK SHOWN SOUTH OF THIS GRID LINE IS
EXISTING, TO REMAIN, UNLESS NOTED OTHERWISE.
7. PROVIDE (15') SELF-REGULATED, 5W/FT HEAT-TRACE, WITH
GFI-PROTECTED CONTROLLER, AMBIENT SENSOR AND ALL
NECESSARY ACCESSORIES. ADHERE HEAT-TRACE TO THE
BOTTOM OF HRV2 (DRAIN PAN). DESIGN IS BASED ON RAYCHEM
MODEL 5XL1 TRACE AND MODEL ECW-GF CONTROLLER.
8. FLOOR POWER/DATA ENTRY POINT FOR WHIP CONNECTION TO
POWERED FURNITURE: ELECTRICAL CONTRACTOR SHALL
PROVIDE FLOOR BOX WITH (1) 2" CONDUIT ENTRY FOR DATA AND
(1) 3/4" CONDUIT ENTRY FOR POWER, WIREMOLD #6ATCFFBK OR
EQUAL, WITH 2" BUTTON HOUSING ASSEMBLY ACCESSORY
WIREMOLD #152CHA, OR EQUAL. SEE KEYNOTE 2 THIS SHEET,
AND KEYNOTE 9, SHEET E2.5.
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
A
BS102
FC102B
FC102A
FC101C
FC100A
FC100B
FC102D
FC102C
FC103
FC105A
FC108A
FC108C
FC107B
FC107C
FC107A
FC107D
FC104
FC106A
FC101B
FC100C
BS103
FC107F
FC107E
FC108B
FC108D
FC108E
FC106B
BS205
BS100
FC101A
FC101D
EH1
FC105B
BS105
FC108F
M
CT1
FC108G
BS101
BS107
S S
S S
S S
S S
S S
S S
S S
W
W
W
W
ECU1
OUTDOOR
FSD
UR1
UR1
L1
L1
WC1
WC2
WC2
WC2
WC2
WC1
EF1
M
EH4
CONF/
NURSE
CONFERENCE
OFFICE
125OFFICE
OPEN
OFFICE
OPEN
OFFICE
ENTRY
HALL
RECEPTION
BREAK
PRIVATE
OFFICE
HR
JANITOR
WOMENS
RESTROOM
MENS
RESTROOM
EXECUTIVE
ASSISTANT
(2 STAFF)
REGIONAL
FORESTER
DEPUTY
REGIONAL
FORESTER
DEPUTY
REGIONAL
FORESTER
COFFEE / PRINT
115LARGE
CONFERENCE
TELE/DATA
PRINT / COPY / FAX
CONFERENCE
ENTRY
ELEVATOR
A
PORCH
STAIR
PORCH
DOWN DOWN
DOWN DOWN
DOWNDOWN
UP UP
RAMP
DOWN
RAMP
DOWN
RAMP
DOWN
DOWN DOWN
UP
CONFERENCE
UP
DEMO
TEMP DOOR
AND
WALL
R R R
OFFICE
OFFICE
OFFICE
OPEN
OFFICE
OPEN
OFFICE
OFFICE
OFFICE
OPEN
OFFICE
CONFERENCE
STAIR
PORCH
CARD
READER
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
(N) FE CAB
1008.1.8 DOOR
ARRANGEMENT:
SPACE BETWEEN TWO
DOORS IN A SERIES SHALL
BE 48" MIN. PLUS THE
WIDTH OF A DOOR
SWINGING INTO THE
SPACE. DOORS IN A
SERIES SHALL SWING
EITHER IN THE SAME
DIRECTION OR AWAY
FROM THE SPACE
BETWEEN THE DOORS.
CARD READER,
NO HOLD OPENS
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
SALVAGE
HARDWARE,
RE-USE DOOR &
HINGES, NEW
HARDWARE
SMALL
CONFERENCE
S
S
1 1
S S
S S
S S
S
S
S S
S S
S S
S S
S S
1-HR FIRE
RATING
1-HR FIRE RATING
EX PoE NETWORK SWITCH
EX TTB
EX FA ANNUNCIATOR
W
W
EX 4" C.O. BETWEEN BASEMENT AND FIRST FLOOR
EX 4" C.O. BETWEEN FIRST AND SECOND FLOOR
SPEAKER CONTROLLER. SEE
DETAIL 18, SHEET E9.2.
S
ABOVE COUNTER
S
S
S
AUDIBLE/VISIBLE
ALERT DEVICE.
PANIC SYSTEM
PUSH-BUTTON
EX SERVER RACK,
FOR NEW PATCH PANEL
ABOVE COUNTER
POWERED FURNITURE
TELE/DATA OUTLET.
(TYPICAL OF ALL.)
(5) EX 2" C AND (3) EX
4" C, AVAILABLE FOR
USE IN THIS PROJECT
POWER POLE
POWER POLE
EX
FI
R
ST
F
LO
O
R S
IG
N
A L
PL
A
N
USFS BUILDING 26 - FIRST FLOOR SIGNAL PLAN16
E2.4 : E2.4 1/8" = 1'-0"
NORTH
E2.4
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO
CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS,
BOXES AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE
FINAL PLACEMENT OF MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD
VERIFIED. THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. COORDINATE AVAILABLE SPACE FOR EQUIPMENT AND PIPING
SYSTEMS WITH OTHER TRADES. REFER TO ARCHITECTURAL,
STRUCTURAL, PLUMBING, AND ELECTRICAL DRAWINGS AND FIRE
PROTECTION SHOP DRAWINGS FOR ADDITIONAL DETAILS
NECESSARY FOR COORDINATION.
4. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL
DRAWINGS TO VERIFY HOW AND WHERE CONCRETE CAN BE CUT.
5. THE TEL/DATA DESIGN INTENT: ELECTRICAL CONTRACTOR
PROVIDES BOX AND CONDUIT TO ACCESSIBLE CEILING.
CABLING CONTRACTOR SHALL PULL CABLING FROM WORK
AREA OUTLET (WAO) BACK TO THE I.T. ROOM ON SAME
FLOOR IN OPEN RACEWAY (UTILIZE D-RINGS AND J-HOOKS). 2
DATA, 1 PHONE, CAT6 TO EACH WAO. POWERED FURNITURE
TO GET 3 DATA. 1 PHONE, CAT6. COIL IN THE I.T. ROOM FOR
EACH FLOOR AS SPECIFIED. DO NOT ALLOW COILS TO SIT ON
THE FLOOR. PULL AND TERMINATE FIBER BETWEEN EACH
FLOOR. TEST ALL CAT6 AND FIBER AS SPECIFIED. INSTALL
RACKS AS SPECIFIED. ALL PATCH PANELS AND OTHER
SERVER EQUIPMENT IS BY OWNER. TEL/DATA OUTLETS IN
THE FURNITURE; HOMERUN CABLING THROUGH FURNITURE
RACEWAY TO NEAREST TELECOMMUNICATION OUTLET IN
NORTH WALL. ROUTE POWER THROUGH THE BOTTOM
CHANNEL. TEL/DATA CABLING SHALL BE ROUTED THROUGH
THE TOP CHANNEL.
6. PERIMETER WALLS HAVE BEEN FURRED OUT TO 1-1/2". PROVIDE
SHALLOW BOX FOR ALL OUTLETS IN PERIMETER WALLS.
7. ALL EXTERIOR OUTLETS SHALL BE INSTALLED IN FLUSH-MOUNT
JBOX. CONTRACTOR SHALL SAW-CUT EXTERIOR WALL CEMENT TO
FLUSH-MOUNT JBOX. PATCH/PAINT TO MATCH EXISTING FINISH.
8. ALL FIRE WALLS ARE 12" THICK CONCRETE. ELECTRICAL
CONTRACTOR RESPONSIBLE FOR ALL CORE DRILLING
KEY NOTES:
1. OPEN OFFICE POWERED FURNITURE: PROVIDE (1) TELEPHONE
AND (2) DATA DROPS AT EACH WORKSTATION, WITH CAT6 CABLE
BACK TO I.T. ROOM. RUN THROUGH FURNITURE TO JACK
LOCATIONS. AT EXTERIOR WALL LOCATIONS IN THE OPEN OFFICE
AREAS, THE FURNITURE REQUIRES 16 TO 20 CABLES AT THE
ENTRANCE LOCATION. PROVIDE REQUIRED NUMBER OF 3/4" RIGID
INSULATION BEHIND. CONDUIT CAN TERMINATE IN THE WALL
BEHIND A 4-SQUARE MUD RING IN THE SHEET ROCK (NO BACK
BOX). THIS WOULD HAVE TO HAPPEN TWICE, SIDE BY SIDE, AT THE
LARGER DROP LOCATIONS (ONLY (3) CAT6 FIT IN A 3/4" C). THIS
WILL ONLY LEAVE 4" SQUARES IN THE WALL UN-INSULATED. SEE
POWER PLANS FOR POWER CIRCUIT REQUIREMENTS. (TYP OF ALL
POWERED FURNITURE DROP LOCATIONS. COORDINATE EXACT
LOCATION WITH FURNITURE CONTRACTOR, PRIOR TO ROUGH-IN.
2. PART OF ALT. #2 - SOUND-MASKING SYSTEM: PROVIDE SPEAKER,
CIRCUIT BACK TO SOUND CONTROLLER IN SAME SPACE. SEE
DETAIL 18, SHEET E9.2. COORDINATE FINAL LOCATION WITH
OTHER DISCIPLINES TO AVOID CONFLICT WITH LIGHTING, HVAC
DUCT, PIPING AND DIFFUSERS. (TYPICAL OF ALL).
3. PART OF ALT. #2 - SOUND MASK SYSTEM. SEE DETAIL 18, SHEET
E9.2.
4. WIRELESS ACCESS POINT: PROVIDE CONDUIT, AND SINGLE CAT6
CABLE, FROM I.T. ROOM TO JBOX ON CEILING AT THIS LOCATION.
WIRELESS DEVICE PROVIDED BY OTHERS. VERIFY EXACT
LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
5. 1HR FIRE-RATING BOUNDARY: ALL MEANS AND MATERIALS FOR
WORK ON THIS WALL SECTION SHALL MEET 1-HR FIRE RATING
REQUIREMENTS.
6. ALL SHADED ITEMS, SOUTH OF GRID-LINE D, ARE EXISTING,
UNLESS NOTED OTHERWISE.
7. PART OF PANIC SIGNAL SYSTEM. SHEET SHEET E2.1.
8. POWERED FURNITURE WORKSTATION TELE/DATA OUTLET:
PROVIDE (1) TELE/DATA OUTLET AT EACH POWERED FURNITURE
WORK-STATION. EACH TELE/DATA OUTLET SHALL HAVE (1)
TELEPHONE AND (2) DATA JACKS. VERIFY EXACT LOCATION PRIOR
TO ROUGH-IN. SEE KEYNOTE 1, THIS SHEET.
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
ARIAN C.
A
S
N
O
P
I
S
S
E
F
O
R
I
G
E
R
N
O
M
L
E
E
R
E
N
G
I
N
D
E
R
E T
A
N
A
209.1
207.1
206.2
201.1
202.2
202.1 203.1 204.1
205.1
206.1
\pxqc;(E)\PSWR\pxqc;(N)\PFSR
\pxqc;BOILER\PVENT
\pxqc;BOILER\PVENT
\pxqc;R
\pxqc;R
\pxqc;R
\pxqc;(N)\PFSR
IN MACHINE SPACE AT
TOP OF HOISTWAY
TO HOIST-WAY
MACHINE- SPACE
LUMINAIRE
FC200A
FC200B
FC200C
FC201
FC200D
FC200E
FC200F
FC203
FC204
FC202A FC202E
FC202B
FC202F
FC202C
FC202G
FC202D
FC202H
FC205A
FC205B
BS206
FC206
BS204
BS203
BS201
FC205C
BS202
BS200
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
D
D
D
HEAT TRACE
(IN ATTIC)
W
W
EF2
EH4
OFFICE
OFFICE
OFFICE
SMALL
CONFERENCE
SMALL
CONFERENCE
OPEN
OFFICE
OPEN
OFFICE
STAIR
ELEVATOR
A
PORCH
PORCH
DOWNDOWN
DOWN
DOWNDOWN
DOWNDOWN
DOWNDOWN
DOWN
TELE/DATA
211JANITOR
SMALL
CONFERENCE
DOWN
(E)
SWR
(N)
FSR
BOILER
VENT
BOILER
VENT
R
R
R
R R
12"Ø
EXHAUST
12"Ø
EXHAUST
6"Ø 8"Ø
WOMENS
RR
MENS
RR
OFFICE
(N)
FSR R R R
DOWN
OFFICE
OPEN
OFFICE
LARGE
CONFERENCE
CONFERENCE
OPEN
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
FILES
OFFICE
CONFERENCE
OFFICE
STAIR
PORCH
PLOT
HALL
OFFICE
OFFICE
1 1
S
S S
S
S S
S S
S S
S S
S S
S S
S S
PROJECTOR (CEILING)
1-HR FIRE RATING
1-HR FIRE RATING
EX PoE NETWORK SWITCH
W
W
SPEAKER CONTROLLER. SEE
DETAIL 18, SHEET E9.2. (TYP OF ALL)
ABOVE COUNTER
ABOVE COUNTER
S
S
S
S
S
S
S
ABOVE COUNTER
EX SERVER RACK,
FOR NEW PATCH PANEL
ABOVE COUNTER
7POWERED FURNITURE
TELE/DATA OUTLET
(TYPICAL OF ALL)
7 7
7 7
W
W
FLOORBOX
FLOORBOX
SE
C
O N
D F
LO
O
R S
IG
N
A L
PL
A
N
USFS BUILDING 26 - SECOND FLOOR SIGNAL PLAN16
E2.5 : E2.5 1/8" = 1'-0"
NORTH
E2.5
1. IT IS ABSOLUTELY NECESSARY FOR ALL TRADES INVOLVED TO
COORDINATE WITH EACH OTHER AND VERIFY THAT THERE ARE NO
CONFLICTS IN LOCATION OF DUCTS, CONDUITS, DIFFUSERS,
BOXES AND OTHER ITEMS THROUGHOUT THIS PROJECT BEFORE
FINAL PLACEMENT OF MATERIALS.
2. ALL DIMENSIONS AND EXACT UNIT LOCATIONS ARE TO BE FIELD
VERIFIED. THESE DRAWINGS REPRESENT SCHEMATIC SYSTEMS.
3. COORDINATE AVAILABLE SPACE FOR EQUIPMENT AND PIPING
SYSTEMS WITH OTHER TRADES. REFER TO ARCHITECTURAL,
STRUCTURAL, PLUMBING, AND ELECTRICAL DRAWINGS AND FIRE
PROTECTION SHOP DRAWINGS FOR ADDITIONAL DETAILS
NECESSARY FOR COORDINATION.
4. COORDINATE ALL CONCRETE PENETRATIONS WITH STRUCTURAL
DRAWINGS TO VERIFY HOW AND WHERE CONCRETE CAN BE CUT.
5. THE TEL/DATA DESIGN INTENT: ELECTRICAL CONTRACTOR
PROVIDES BOX AND CONDUIT TO ACCESSIBLE CEILING.
CABLING CONTRACTOR SHALL PULL CABLING FROM WORK
AREA OUTLET (WAO) BACK TO THE I.T. ROOM ON SAME
FLOOR IN OPEN RACEWAY (UTILIZE D-RINGS AND J-HOOKS). 2
DATA, 1 PHONE, CAT6 TO EACH WAO. POWERED FURNITURE
TO GET 3 DATA. 1 PHONE, CAT6. COIL IN THE I.T. ROOM FOR
EACH FLOOR AS SPECIFIED. DO NOT ALLOW COILS TO SIT ON
THE FLOOR. PULL AND TERMINATE FIBER BETWEEN EACH
FLOOR. TEST ALL CAT6 AND FIBER AS SPECIFIED. INSTALL
RACKS AS SPECIFIED. ALL PATCH PANELS AND OTHER
SERVER EQUIPMENT IS BY OWNER. TEL/DATA OUTLETS IN
THE FURNITURE; HOMERUN CABLING THROUGH FURNITURE
RACEWAY TO NEAREST TELECOMMUNICATION OUTLET IN
NORTH WALL. ROUTE POWER THROUGH THE BOTTOM
CHANNEL. TEL/DATA CABLING SHALL BE ROUTED THROUGH
THE TOP CHANNEL.
6. PERIMETER WALLS HAVE BEEN FURRED OUT TO 1-1/2". PROVIDE
SHALLOW BOX FOR ALL OUTLETS IN PERIMETER WALLS.
7. ALL FIRE WALLS ARE 12" THICK CONCRETE. ELECTRICAL
CONTRACTOR RESPONSIBLE FOR ALL CORE DRILLING
KEY NOTES:
GENERAL NOTES:
2014 MORRISON-MAIERLE, INC.
BU
IL
D
IN
G
P H
A
SE
N O
R T
H W
IN
G
R
EN
O V
A T
IO
N
U S
FO
R
ES
T
S
ER
V
IC
E, N
O R
T H
ER
N
R
EG
IO
N
R
EG
IO
N A
L O
FF
IC
E www.aearchitects.com
O W
N
ER
PR
O
JE
C
T
D R
A W
IN
G
A R C H I T E C T U R E
H I S T O R I C
I N T E R I O R S
ARCHITECTS PC
608 NORTH 29TH STREET
BILLINGS, MT 59101
PH 4 0 6 . 2 4 8 . 2 6 3 3
FAX 4 0 6 . 2 4 8 . 2 4 2 7
428 EAST MENDENHALL STREET
BOZEMAN, MT 59715
PH 4 0 6 . 4 5 1 .7 3 1 0
222 NORTH HIGGINS AVENUE
MISSOULA, MT 59802
PH 4 0 6 . 7 2 1 . 5 6 4 3
FAX 4 0 6 . 7 2 1 . 1 8 8 7
PROJECT #
ISSUE DATE
REVISIONS
13104.10 05.18.15
1. POWERED FURNITURE: PROVIDE (1) TELEPHONE AND (2) DATA
DROPS AT EACH WORKSTATION, WITH CAT6 CABLE BACK TO I.T.
ROOM. RUN DATA CABLES THROUGH FURNITURE TO JACK
LOCATIONS. COORDINATE EXACT LOCATION WITH FURNITURE
CONTRACTOR, PRIOR TO ROUGH-IN. AT EXTERIOR WALL
LOCATIONS IN THE OPEN OFFICE AREAS, THE FURNITURE
REQUIRES 16 TO 20 CABLES AT THE ENTRANCE LOCATION.
PROVIDE REQUIRED NUMBER OF 3/4" RIGID INSULATION BEHIND.
CONDUIT CAN TERMINATE IN THE WALL BEHIND A 4-SQUARE
MUD RING IN THE SHEET ROCK (NO BACK BOX). THIS WOULD
HAVE TO HAPPEN TWICE, SIDE BY SIDE, AT THE LARGER DROP
LOCATIONS (ONLY (3) CAT6 FIT IN A 3/4" C). THIS WILL ONLY
LEAVE 4" SQUARES IN THE WALL UN-INSULATED. SEE POWER
PLANS FOR POWER CIRCUIT REQUIREMENTS. (TYP OF ALL
POWERED FURNITURE DROP LOCATIONS.)
2. WIRELESS ACCESS POINT: PROVIDE CONDUIT AND A SINGLE
CAT6 CABLE FROM I.T. ROOM TO JBOX ON CEILING AT THIS
LOCATION. WIRELESS DEVICE PROVIDED BY OTHERS.