panel_a_woodshop_A02.pdf

PDF 456 KB Posted

Attached to
Co-Located Sitka Office Renovation Federal contract opportunity
Solicitation number
AG-0116-S-14-0021
Issued by
Department of Agriculture Forest Service R10-Alaska Region

About this file

Woodshop Panel A Sheet

View the file

Other files for this federal contract opportunity

Other files attached to Co-Located Sitka Office Renovation, newest first.
File Type Posted
A09.pdf PDF
A08.pdf PDF
Sitka_Amendment_Drawings_Civil_A07.pdf PDF
Sitka_Amendment_Sign_Pages_A07.pdf PDF
A07.pdf PDF
A06.pdf PDF
A05.pdf PDF
Sig-in_sheet.pdf PDF
Pre-Proposal_Site-Visit_Agenda.pdf PDF
A04.pdf PDF
A03.pdf PDF
E1SitkaElecSitePlan-20140730_A02.pdf PDF
FlagPoleLight_A02.pdf PDF
235216-BIOMASS_BOILER_A02.pdf PDF
A02.pdf PDF
236200-AIR_TO_WATER_HEAT_PUMPS_A02.pdf PDF
260548_A02.pdf PDF
221429_sf-SUMP_PUMPS_A02.pdf PDF
CreeAreaAREEDGDASpecSheet_A02.pdf PDF
M-P-Drawingreplacement-20140730_A02.pdf PDF
panel_b_autoshop_A02.pdf PDF
211000_SF-Fire-Suppression_Systems_A02.pdf PDF
237219FIXED_PLATE_AIR_A02.pdf PDF
260529_A02.pdf PDF
A01.pdf PDF
Factor_3_form.pdf PDF
lpta_questionnaire.pdf PDF
SitkaOfficeSiteDev_ACM_LBP_reports.pdf PDF
Factor_1_form.pdf PDF
Wage_determination.pdf PDF
D60441FINAL_sitka_geotech.pdf PDF
Factor_2_form.pdf PDF
SITKA_solicitation.pdf PDF
ColocatedSitkaOfficeSiteDev7_8_14.pdf PDF
Sitka_Specifications.pdf PDF
070914_Drawings.pdf PDF
Technical_Criteria_Pre-Notice.pdf PDF
LPTA_Factor_1_form.pdf PDF
lpta_questionnaire.pdf PDF
LPTA_Factor_3_form.pdf PDF
LPTA_Factor_2_form.pdf PDF
DRAFTColocatedSitkaOfficeSiteDev6-14-14.pdf PDF
DRAFT_Sitka_CD_Drawings.pdf PDF
Show all 43

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

POLE WIRE C.B. LOAD LOAD VA LOAD C.B. WIRE POLE

NO. SIZE AMP/P TOTAL TYPE A B TYPE TOTAL AMP/P SIZE NO.

1 20/1 Outlets Back wall 1000 C 2000 C 1000 Celing Lights 20/1 2

3 1000 C 2000 C 1000 Celing Lights 20/1 4

5 1000 C 2000 C 1000 Celing Lights 20/1 6

7 1000 C 2000 C 1000 Yard Light 20/1 8

9 20/1 Furnace 1000 C 2000 C 1000 10

11 1000 C 2000 C 1000 12

13 20/1 Bath 1000 C 2000 C 1000 Outlet Bench 20/1 14

15 20/1 Store Room 1000 C 2000 C 1000 16

17 20/1 Office 1000 C 2000 C 1000 18

19 20/1 Office 1000 C 2000 C 1000 20

21 1000 C 2000 C 1000 22

23 1000 C 2000 C 1000 24

25 1000 C 2000 C 1000 26

27 1000 C 2000 C 1000 28

29 Air Compressor 1000 C 2000 C 1000 30

31 Air Compressor 1000 C 2000 C 1000 32

33 1000 C 2000 C 1000 34

35 1000 C 2000 C 1000 36

37 Water Heater 1000 C 2000 C 1000 Sprinkler Alarm 20/1 38

39 1000 C 2000 C 1000 Sprinkler Compressor 20/1 40

41 1000 C 2000 C 1000 42

CONNECTED LOAD PER PHASE VA 22000 20000

CONNECTED LOAD PER PHASE A 183 167 LOCATION: ____________________________

LOAD SUMMARY CONN. DEMAND DEMAND DATE: 03/09/07

VA FACTOR VA VOLTS: 120/240V,1PH,3W PANEL

TYPE "A": RECEPTACLES (FIRST 10KVA) 100% MAIN C.B.:

TYPE "A": RECEPTACLES (OVER 10KVA) 50% BUS: A

TYPE "B": NON-CONTINUOUS LOADS 100% POLES:

TYPE "C": CONTINUOUS LOADS 42000 125% 52500 MOUNTING: SURFACE

TOTAL DEMAND LOAD VA 42000 52500 AIC RATING: 10,000

TOTAL DEMAND LOAD AMPS 219 SUBFEED C.B:

REV 8/30/07

Enter data in non green areas only

MINIMUM SERVICE SIZE 273.4 AMPS AG-0116-S-14-0021