About this file

This document is a detailed architectural drawing (AE302) for a Veterans Affairs construction project focused on patient privacy improvements at the Lake City, FL facility. The technical drawings provide comprehensive wall sections and architectural details for a renovation project, specifically showing duct support, window head and post configurations, rooftop post enclosures, and various wall section specifications. The drawings include precise technical annotations for construction elements such as existing and new wall constructions, metal studs, plywood, flashing membranes, roofing modifications, and structural interface details. The technical drawings are part of bid documents for Project #573A4-18-603, which involves correcting patient privacy deficiencies on the 2nd North and 2nd South floors of the medical facility.

View the file

Other files

File Type Posted
36C24825R0127 0001.pdf PDF
PRIOR SOLICITATION 36C24825R0067 573A418603 Site Visit.pdf PDF
2025 06 24 Site Visit 573A4-18-603.pdf PDF
RFIs 2025 07 09 36C24825R0127 22N2S.xlsx XLSX spreadsheet
36C24825R0127 CLAUSE SHEET.docx DOCX document
Sheet AE452 Headwall Interior Elevations.pdf PDF
SOLICITATION 36C24825R0127 BB Correct PT Privacy Def 2N 2S LC VAMC.pdf PDF
2024 01 29 Drawings Architectural.pdf PDF
2024 01 29 Drawings Mechanical.pdf PDF
Specifications Vol 2.pdf PDF
Specifications Vol 1.pdf PDF
Exhibit E Performance Relevancy Survey v2.docx DOCX document
Visitor Sign In 36C24825R0067 573A418603.pdf PDF
SOLICITATION 36C24825R0127 BB Correct PT Privacy Def 2N 2S LC VAMC.pdf PDF
2024 01 29 Drawings Electrical.pdf PDF
2024 01 29 Drawings Fire Protection.pdf PDF
2024 01 29 Drawings Plumbing.pdf PDF
AE709.pdf PDF
SAM DBA 05_02_25.pdf PDF
Exhibit B LOS Certification Solicitation Version.doc DOC document
Exhibit D Contract Progress Schedule.pdf PDF
Exhibit I Price Matrix.xlsx XLSX spreadsheet
RFIs 36C24825R0067 Correct Patient Privacy.xlsx XLSX spreadsheet
2024 01 29 Drawings Structural.pdf PDF
AE503.pdf PDF
Exhibit C EMR.docx DOCX document
Exhibit F Past and Present Performance Questionnaire.docx DOCX document
RFIs 36C24825R0067 Correct Patient Privacy.pdf PDF
Exhibit A QA RFIs.xlsx XLSX spreadsheet
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S502

SECOND OR THIRD FLOOR

THIRD OR FOURTH FLOOR

DUCT SUPPORT

FRAME: SEE STRUCT

DUCT AND

INSULATION SEE

MECHANICAL

DUCT SUPPORT

FRAME: SEE STRUCT

EXIST BRICK WALL

EXIST CLAY TILE WALL

EXIST 5/8" PLASTER

NEW GMS STUDS AND

GWB ONLY AT IDENTIFIED

WINDOW HEAD POCKETS

EXIST CONC FLOOR BEAMS

INTERIOR EXTERIOR

EXIST CONC FLOOR BEAMS

REMOVE AND REPLACE

EXIST BRICK AS REQD.

INFILL WITH MATCHING

BRICK TO A TIGHT FIT.

PROVIDE CLR SEALANT

FOR WATERTIGHT

INSTALLATION (TYP).

REGLET FLASHING, BACKER

ROD AND SEALANT W/

METAL TERMINATION BAR

AND COUNTERFLASHING.

DUCT AND INSULATION

SEE MECHANICAL

PROVDE METAL DUCT

CLOSURE & CONTINUOUS

WATER TIGHT SEAL AS

REQUIRED, 4 SIDES

DRIP EDGE AT BOTTOM SIDE

M A

X D

U C

T C

LE

A

R A

N C

E

1'

4"

8'

" C

E

IL

IN

G

H E

IG

H

T

2"

REGLET FLASHING, BACKER

ROD AND SEALANT W/

METAL TERMINATION BAR

AND COUNTERFLASHING.

M A

X D

U C

T C

LE

A

R A

N C

E

2nd or 3rd FLOOR LINE

DUCT AND INSULATION

SEE MECHANICAL

PROVDE METAL DUCT

CLOSURE & CONTINUOUS

WATER TIGHT SEAL AS

REQUIRED, 4 SIDES

1'

1/

2"

FURRED WALL BEYOND

DRIP EDGE AT BOTTOM SIDE

1'

8"

1'

1/

2"

V

IF

2'

1"

1' - 2"

3"

EXIST STL COPING

OVER EXIST

STONE CAP

CONT MTL CLEAT

FASTENING

5/8" EXT GRADE

PLYWOOD ON 2 1/2"

MTL FRAMING

CONT SEALANT

SS BAND CLAMP MTL SHROUD

STL POST: SEE STRUCT

4" MTL STUDS

5/8" EXT GRADE PLYWOOD

REMOVE EXIST CANT TO

PREFORM NEW WORK

FLASHING MEMBRANE

CUT IN NEW ROOFING TO EXIST

PER MFR RECOMMENDATIONS

1'

1/

2"

M A

X D

U C

T C

LE

A

R A

N C

E

8'-3" TYP WINDOW HD

8'-0" CEILING HEIGHT

PROVIDE 4" CANTS AT

MOD BIT ROOFING

2nd or 3rd FLOOR LINE or TOP/ROOF SLAB

CONT SEALANT

2'-2"

DEMO EXIST CELINGS

WHERE SHOWN ON DEMO

RCP PLANS

2 1/2" GMS FRAMING

4" GMS FRAMING

ACT CEILING:

SEE RCP PLANS EXIST WINDOWS

EXIST BRICK VENEER

SHADED AREAS ARE

ALL EXIST CONSTR

AE302

AE302

AE302

5/8" GWB, TYP

CONT

SEALANT

SS BAND CLAMP

STL POST: SEE STRUCT

4" MTL STUDS

5/8" EXT GRADE PLYWOOD

REMOVE EXIST CANT TO

PREFORM NEW WORK IN

"X" AREA

FLASHING MEMBRANE

CUT IN NEW ROOFING TO

EXIST PER MFR

RECOMMENDATIONS

PROVIDE 4" CANTS AT

MOD BIT ROOFING

EXIST STL

COPING OVER

EXIST STONE

CAP

CONT MTL

CLEAT

FASTENING

5/8" EXT GRADE

PLYWOOD ON 2

1/2" MTL

FRAMING

MTL

SHROUD

TOP/ROOF

1'- 4"

EXISTING

PARAPET CONSTR

BEYOND

CONT

SEALANT

SS BAND

CLAMP

TYP POSITION OF

STL POST IN

FOREGROUND:

SEE STRUCT

MTL "L" FLASHING

WELDED TO EXIST

COPING (EA SIDE)

MEMBRANE

FLASHING

OVER

PLYWOOD

CONT MTL

CLEAT

FASTENING

5/8" EXT GRADE

PLYWOOD ON 2

1/2" MTL

FRAMING

MTL

SHROUD

TOP/ROOF

1'- 4"

EXIST PARAPET

CONSTR

2'- 2"

1'

- 4

EXIST MTL COPING

OVER EXIST STONE

COPING

EXIST CANT

BELOW

NEW CANTS

BELOW AT

MOD BIT

ROOFING

MEMBRANE

FLASHING ON 5/8"

EXT GRADE

PLYWOOD

MTL SHROUD

ABV DASHED

FOR CLARITY

EXIST

ROOFING

SURFACE

BELOW

STL POSTS:

SEE STRUCT

AE302

AE302

CONT TERM BAR

CONT SEALANT

SS BAND CLAMP

MTL SHROUD

STL POST: SEE STRUCT

4" MTL STUDS

5/8" EXT GRADE PLYWOOD

REMOVE EXIST CANT TO

PREFORM NEW WORK

FLASHING MEMBRANE

CUT IN NEW ROOFING

TO EXIST PER MFR

RECOMMENDATIONS

PROVIDE 4" CANTS AT

MOD BIT ROOFING

2nd or 3rd FLOOR LINE or TOP/ROOF SLAB

CONT SEALANT

SHADED AREAS

ARE ALL EXIST

CONSTR

CONT MTL CLEAT

FASTENING

AE302

AE302

AE302

CONT

SEALANT

SS BAND CLAMP

STL POST: SEE STRUCT

4" MTL STUDS

5/8" EXT GRADE PLYWOOD

REMOVE EXIST CANT TO

PREFORM NEW WORK IN

"X" AREA

FLASHING MEMBRANE

CUT IN NEW ROOFING TO

EXIST PER MFR

RECOMMENDATIONS

PROVIDE 4" CANTS AT

MOD BIT ROOFING

CONT MTL

CLEAT

FASTENING

5/8" EXT GRADE

PLYWOOD ON 2

1/2" MTL

FRAMING

MTL

SHROUD

TOP/ROOF

1'- 4"

EXISTING WALL

CONSTR BEYOND

CONT

SEALANT

SS BAND

CLAMP

TYP POSITION OF

STL POST IN

FOREGROUND:

SEE STRUCT

MEMBRANE

FLASHING

OVER

PLYWOOD

CONT MTL

CLEAT

FASTENING

5/8" EXT GRADE

PLYWOOD ON 2

1/2" MTL

FRAMING

MTL

SHROUD

TOP/ROOF

REMOVE EXIST

CANT AS REQD TO

PERFORM THE

WORK

EXIST

BLDG WALL

BEYOND

1'

- 4

EXIST WALL

CONSTR

EXIST CANT

BELOW

MEMBRANE

FLASHING ON 5/8"

EXT GRADE

PLYWOOD

MTL SHROUD

ABV DASHED

FOR CLARITY

EXIST

ROOFING

SURFACE

BELOW

STL POSTS:

SEE STRUCT

1'- 2"

CONT TERM BAR

ALL SHADED AREAS

ARE EXIST CONSTR

AE302

AE302

NEW CANTS

BELOW AT

MOD BIT

ROOFING

EXISTING WINDOW

WINDOW SILL PLATE

5/8" GYP. BOARD ON 2-1/2"

STUD FURRING @ 16" O.C.

FURRING WALL

BEYOND

INTERIOR EXTERIOR

7 3/4"

2"

4"

7' - 10"

8' - 0"

EXISTING WALL

EXISTING WALL

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

BID DOCUMENTS

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

Building #64

CRM JD/DB/EO5/

/2

9:

:0

A

M

WALL SECTIONS AND DETAILS CORRECT PATIENT PRIVACY

DEFICIENCIES - BLDG 64-UNIT A

LAKE CITY VAMC

Lake City, FL

AE302

573A4-18-603

JAN. 29, 2024

3/4" = 1'-0"AE302

9 ELEVATION AT DUCT SUPPORT

1 1/2" = 1'-0"AE302

10 DUCT PENETRATION FLASHING DETAIL ABOVE WINDOWS

1 1/2" = 1'-0"AE302

4 WALL SECTION - WINDOW HEAD AND POSTS AT PARAPETS

1 1/2" = 1'-0"AE302

1 ROOFTOP POST ENCLOSURE SECTION 1

1 1/2" = 1'-0"AE302

2 ROOFTOP POST ENCLOSURE SECTION 2

1 1/2" = 1'-0"AE302

3 PLAN DETAIL 1 - SHROUD AND FRAMING AT ROOFTOP POSTS

1 1/2" = 1'-0"AE302

8 WALL SECTION - POSTS AT PERPENDICULAR WALL

1 1/2" = 1'-0"AE302

5 ROOFTOP POST ENCLOSURE SECTION 3

1 1/2" = 1'-0"AE302

6 ROOFTOP POST ENCLOSURE SECTION 4

1 1/2" = 1'-0"AE302

7 PLAN DETAIL 2 - SHROUD AND FRAMING AT ROOFTOP POSTS

0' 4" 8" 1' - 4" 2'

SCALE: 1-1/2" = 1' - 0"

1 1/2" = 1'-0"AE302

9A WALL SECTION AT EXISTING WINDOW

Sheets
AE302 - WALL SECTIONS AND DETAILS
AE503 - TYPICAL ROOF DETAILS
AE709 - SIGNAGE TYPE AND SCHEDULE

File details come from the government source that posted it. Updated .