2024 01 29 Drawings Fire Protection.pdf
PDF 10 MB Posted
- Solicitation number
- 36C24825R0127
About this file
These are fire protection design drawings for a renovation project at the Lake City VA Medical Center, specifically for Building 64, Unit A. The documents detail comprehensive fire protection systems for a two-story healthcare facility, including:
Sprinkler System Design: The drawings specify a fully sprinklered facility with multiple sprinkler zones on the second and third floors, utilizing wet pipe systems. Different occupancy types are identified with varying design densities, including light hazard (0.10 GPM/SF) and ordinary hazard group areas (0.15-0.20 GPM/SF). The system includes quick response sprinkler heads throughout, with specific installation requirements such as centering sprinklers in ceiling tiles and avoiding placement above electrical panels. Fire pump and jockey pump specifications are provided, with a 1000 GPM fire pump operating at 70 PSI.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATIC PRESSURE
PSI
RESIDUAL PRESSURE
PSI
FLOW RATE
GPM
150 130 1000
NOTES: FLOW DATA TAKEN FROM FIRE PUMP TEST ON 1/16/2023.
DATA IS FROM THE DISCHARGE OF THE FIRE PUMP.
WATER FLOW TEST DATA
SPACE SYSTEM
TYPE
OCCUPANCY TYPE DESIGN DENSITY
GPM/SF
DESIGN AREA
SF
MAXIMUM SPRINKLER
COVERAGE, SF
OFFICES AREAS, CORRIDORS,
RESTROOMS
ELECTRICAL, EQUIPMENT,
MECHANICAL ROOMS
WET
WET
LIGHT HAZARD
ORDINARY HAZARD, GROUP 1
0.10
0.15
HOSE STREAM
GPM
1500 100 225
1500 250 130
NOTES: 1. ALL SPACES NOT SHOWN AS ORDINARY HAZARD GROUP 1 ARE LIGHT HAZARD.
2. ACTUAL FLOW RATES SHALL BE BASED ON HYDRAULIC CALCULATIONS.
3. REMOTE AREA REDUCTION WITH QUICK RESPONSE SPRINKLERS IS PERMITTED, IAW NFPA 13 REQUIREMENTS.
SPRINKLER SYSTEM DESIGN DATA
STORAGE ROOM, CLEAN &
SPOILED LINEN ROOM
WET ORDINARY HAZARD, GROUP 2 0.20 1500 250 130
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH
NFPA 72 - 2022 EDITION, VA FIRE PROTECTION DESIGN MANUAL.
PROVIDE WIRING AS RECOMMENDED BY MANUFACTURER.
CONTRACTOR MUST SUBMIT SHOP DRAWINGS FOR REVIEW.
COORDINATE FIRE ALARM SYSTEM WITH ALL TRADES TO ENSURE
PROPER COMPLIANCE WITH CODES AND TO AVOID CONFLICTS.
IN AREAS WITH LAY-IN CEILING TILES, INSTALL CEILING MOUNTED
FIRE ALARM DEVICES CENTER OF TILE.
DESIGN AND PROVIDE THE SPRINKLER SYSTEM IN ACCORDANCE
WITH NFPA 13 - 2022 EDITION, VA FIRE PROTECTION DESIGN
MANUAL. CONTRACTOR MUST SUBMIT SHOP DRAWINGS FOR
REVIEW.
COORDINATE SPRINKLER SYSTEM WITH ALL TRADES TO ENSURE
PROPER COMPLIANCE WITH CODES AND TO AVOID CONFLICTS.
IN AREAS WITH LAY-IN CEILING TILES, INSTALL SPRINKLER HEADS
CENTER OF TILE.
DESIGN AND PROVIDE THE SPRINKLER SYSTEM FOR THE HAZARD
OCCUPANCY SHOWN ON THIS SHEET AND BY HYDRAULIC
CALCULATION.
RUN PIPING IN ROOMS AND CORRIDORS CONCEALED ABOVE
CEILINGS. IN ROOMS WITH CEILINGS OF EXPOSED
CONSTRUCTION, RUN THE PIPING EXPOSED USING UPRIGHT
SPRINKLER HEADS, EXCEPT AS NOTED OTHERWISE.
NO PIPE PENETRATIONS OF STRUCTURAL MEMBERS, EXCEPT AS
NOTED, ARE PERMITTED WITHOUT THE APPROVAL OF THE
ARCHITECT/ENGINEER.
PROVIDE PIPE PENETRATIONS OF FIRE OR SMOKE PARTITIONS
OR WALLS AND MAKE FIRE AND SMOKE TIGHT.
PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING
ASSEMBLIES FOR EACH PENETRATION OF FIRE-RATED
ASSEMBLIES.
RUN SPRINKLER PIPING SUCH THAT IT DOES NOT RUN ABOVE
ELECTRICAL PANELS, SWITCH GEAR, AND SIMILAR EQUIPMENT.
PROVIDE QUICK RESPONSE SPRINKLER HEADS THROUGHOUT.
MARK
FP-1
FIRE PUMP SCHEDULE
JP-1
SYSTEM FLOW RATE
GPM
PRESSURE
PSI
TYPE MOTOR
FIRE
PUMP
JOCKEY
PUMP
HORIZONTAL
SPLITCASE
(MAX)
1.5
460/3
480/3
HP RPM VOLT/PHASE
CHECK VALVE
SPRINKLER HEAD, UPRIGHT
SPRINKLER HEAD, PENDANT
RA
TS
CM
GATE VALVE WITH TAMPER SWITCH
FIRE DEPARTMENT CONNECTIONFDC
DUCT SMOKE DETECTOR
SMOKE DETECTOR, CEILING MOUNTED
REMOTE ANNUNCIATOR
M MAGNETIC DOOR HOLDER
CONTACT MONITOR MODULE
TAMPER SWITCH
MANUAL PULL STATION, MOUNT 4'-0" AFF
S
F
CONTROL INTERFACECI
10 SPRINKLER CALCULATION NODE
REFERENCE
D
RELAYR
NEW TO EXISTING
HORNSTROBE UNIT W/ CANDELA RATING,
WALL MOUNTED
F
SIDE WALL SPRINKLER
WATERFLOW SWITCH - PADDLE TYPEFRISER DOWN
CAPPED PIPE
BALL VALVE
BACKFLOW PREVENTER
RISER UP
UNDERGROUND PIPEUG
DEMO TO THIS POINT HORN/STROBE UNIT W/ CANDELA RATING,
CEILING MOUNTED
C F
FACP FIRE ALARM CONTROL PANEL
FIRE PROTECTION LEGEND
# DEMOLITION NOTE IDENTIFICATION
INDICATES ITEM TO BE REMOVED
GENERAL
ABOVE FINISHED FLOORAFF
# CONSTRUCTION NOTE IDENTIFICATION
INDICATES NEW ITEM
INDICATES EXISTING ITEM
REMOVE TO THIS POINT
CONNECT NEW TO EXISTING
ROOM NUMBER IDENTIFICATIONXXX
POST INDICATOR VALVEPIV
BACK FLOW PREVENTERBFP
SPRINKLER FIRE ALARM
DUCT DETECTOR TEST STATIONDDTS
NEWDEMO
TS
M
S
F
F
T/R DUAL INPUT MODULE
R
CHIME/STROBE UNIT F
D
ON CENTERO.C.
ORDINARY HAZARD GROUP 2OH2
ORDINARY HAZARD GROUP 1OH1
FIRE HYDRANTFH
WEATHERPROOF (SUBSCRIPT)WP
ELECTRICAL POWER (120V AC)EP
CEILING MOUNTED (SUBSCRIPT)C
EXISTING (SUBSCRIPT)E
HOSE VALVE CONNECTIONHVC
F
F
EXISTING
TS
M
S
F
F
R
F
F
F
FACP
LIGHT HAZARDLH
F F
CM
D D
CM
TS
CM
TS
CM CM CM F F S
F
FIRE ALARM
CONTROL PANEL
NOTES:
PROVIDE HORN/STROBE CIRCUITS AS REQUIRED. NO CIRCUIT SHALL
BE LOADED MORE THAN 70 PERCENT PRIOR TO FINAL INSPECTION
TO ALLOW ADDITIONAL UNITS TO BE ADDED AS MAY BE REQUIRED
BY LOCAL AUTHORITY. STROBES SHALL BE SYNCHRONIZED.
COORDINATE INTERLOCKS BETWEEN FIRE ALARM ACTIVATION AND
HVAC SHUTDOWN AS REQUIRED.
COORDINATE WITH SPRINKLER CONTRACTOR FOR QUANTITY OF
FLOW AND TAMPER SWITCH MONITORING POINTS AND THEIR EXACT
LOCATIONS.
RISER DIAGRAM IS FOR REFERENCE ONLY. DEVICE LOCATIONS AND
QUANTITIES SHALL BE AS SHOWN ON THE FLOOR PLANS.
FIRST FLOOR
CORRIDOR
S S
CM
TS
CM
F
F S
F F F F
AHU-1AHU-2
1.
2.
3.
TS F F
FIRST FLOOR
THIRD FLOOR
S
SECOND FLOOR
DUCT SMOKE DETECTOR
AREA SMOKE DETECTOR
DOOR RELEASE SMOKE DETECTOR
ELEVATOR SMOKE DETECTOR
MANUAL PULL STATION
SPRINKLER WATERFLOW/PRESSURE SWITCH
R
EC
AL
L
EL
EV
A
TO
R
SH
U
T D
O W
N A
IR
H
AN
D
LE
R
TR
A
N
SM
IT
A
A
LA
R M
S
IG
N
AL
T O
F
IR
E A
LA
R
M C
O N
TR
O
L
PA
N
EL
IN
IT
IA
TE
S U
PE
R
VI
SO
R Y
SI
G
N
AL
T O
A
H
O U
R M
A N
N
ED
P O
IN
T
FO
R
IM
M
ED
IA
TE
R
ES
PO
N
SE
C
LO
SE
D
A M
PE
R
S O
N F
A N
C
LO
SE
A
SS
O
C
IA
TE
D
S M
O
KE
B
AR
R
IE
R D
O O
R S
O N
T H
E
FL
O O
R
N O
TI
FY
F
IR
E D
EP
A
R
TM
EN
T
SO
U
N D
G
EN
ER
A
L
BU
IL
D
IN
G
A
LA
R M
SY
ST
EM
O
U
TP
U T
SYSTEM INPUT
WATER CONTROL VALVE TAMPER
NOTES: DESIGN INTENT IS THAT EXISTING SYSTEM SEQUENCE OF OPERATIONS IS TO
BE MAINTAINED.
1.
SPRINKLER ZONE - SECOND FLOOR WARD 2 NORTH
SPRINKLER ZONE - SECOND FLOOR CENTER
SPRINKLER ZONE - SECOND FLOOR WARD 2 SOUTH
SPRINKLER ZONE - THIRD FLOOR CENTER
SPRINKLER ZONE:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
FIRE PROTECTION LEGEND NOTES AND
DETAILS
F001
NOT TO SCALE
E1
FIRE ALARM RISER DIAGRAM
NOT TO SCALE
F8
FIRE ALARM SEQUENCE OF OPERATION
MATRIX
DEMOLITION PLAN LEGEND
EXISTING CONSTRUCTION TO
REMAIN
EXISTING CONSTRUCTION TO BE
DEMOLISHED
2-HOUR FIRE BARRIER
1-HOUR FIRE BARRIER
1-HOUR SMOKE PARTITION
AREA OF DEMOLITION
AREA OF DEMOLITION
F F
F
F
F
S
F
F
M
M
F
S
S
S
F
S
S
M
M
F F
R
F
F
R
F
F
STAIR 1
STAIR 2
STAIR 3
TS
F
2ND FLOOR
STAIR 1
EXISTING
SPRINKLER RISER
FLOOR CONTROL VALVE ASSEMBLY
ELEVATION VIEW
TS
F
2ND FLOOR STAIR 2
EXISTING
SPRINKLER RISER
FLOOR CONTROL VALVE
ASSEMBLY
ELEVATION VIEW
TS
F
2ND FLOOR
STAIR 3
EXISTING
SPRINKLER RISER
FLOOR CONTROL VALVE ASSEMBLY
ELEVATION VIEW
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
SECOND FLOOR FIRE PROTECTION
DEMOLITION PLAN
FD101
SCALE: 3/32" = 1'-0"
SECOND FLOOR - DEMOLITION PLAN
KEY PLAN
B64A
GRAPHIC SCALE(S)
KEY PLAN
DEMO KEY NOTES#
GENERAL NOTES
RATED PARTITION LEGEND
3/32" = 1' - 0" 0 5' 10' 20' 40'
1. CONTRACTOR SHALL REMOVE ALL EXISTING FIRE ALARM SYSTEM
COMPONENTS (I.E., INITIATING DEVICES, NOTIFICATION DEVICES, WIRING
AND CONDUITS) IN 2 NORTH AND 2 SOUTH CORE AREA.
2. CONTRACTOR SHALL REMOVE ALL SPRINKLER SYSTEM COMPONENTS (I.E.
PIPING, SUPPORT HANGERS AND BRACES, AND SPRINKLER HEADS) IN
DEMOLITION AREA BACK TO THE ISOLATION VALVE.
NORTH
3. SEE SHEET F-001 FOR FIRE PROTECTION LEGEND.
AREA OF DEMOLITION
AREA OF DEMOLITION
S
F
F
STAIR 1
STAIR 2
STAIR 3
DEMOLITION PLAN LEGEND
EXISTING CONSTRUCTION TO
REMAIN
EXISTING CONSTRUCTION TO BE
DEMOLISHED
2-HOUR FIRE BARRIER
1-HOUR FIRE BARRIER
1-HOUR SMOKE PARTITION
3RD FLOOR
TS
F
3RD FLOOR
STAIR 2 EXISTING
SPRINKLER STANDPIPE RISER WITH
HOSE VAVLE CONNECTION &
FLOOR CONTROL VALVE ASSEMBLY
ELEVATION VIEW
HVC
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
THIRD FLOOR FIRE PROTECTION DEMOLITION
PLAN
FD102
SCALE: 3/32" = 1'-0"
THIRD FLOOR - DEMOLITION PLAN
KEY PLAN
B64A
GRAPHIC SCALE(S)
KEY PLAN
DEMO KEY NOTES#
GENERAL NOTES
RATED PARTITION LEGEND
3/32" = 1' - 0" 0 5' 10' 20' 40'
1.
2.
NORTH
3. SEE SHEET F-001 FOR FIRE PROTECTION LEGEND.
CONTRACTOR SHALL REMOVE ALL EXISTING FIRE ALARM SYSTEM
COMPONENTS (I.E., INITIATING DEVICES, NOTIFICATION DEVICES, WIRING
AND CONDUITS) IN 2 NORTH AND 2 SOUTH CORE AREA.
CONTRACTOR SHALL REMOVE ALL SPRINKLER SYSTEM COMPONENTS (I.E.
PIPING, SUPPORT HANGERS AND BRACES, AND SPRINKLER HEADS) IN
DEMOLITION AREA BACK TO THE ISOLATION VALVE.
A.I.I.
BEDROOM
2NB-1
BARIATRIC
ISOLATION
TLT
2NA-3
A.I.I.
BARIATRIC
BEDROOM
2NA-1
A.I.I.
BARIATRIC
ANTE ROOM
2NA-2
A.I.I. ANTE
ROOM
2NB-2
A.I.I.
BEDROOM
2NC-1
A.I.I. ANTE
ROOM
2NC-2
A.I.I. ANTE
ROOM
2ND-2
PATIENT
ISOLATION
TLT
2ND-3
PATIENT
ISOLATION
TLT
2NC-3
A.I.I.
BEDROOM
2NE-1
CORRIDOR
C2-3
PATIENT
ISOLATION
TLT
2NE-3
A.I.I. ANTE
ROOM
2NE-2
SOILED
UTILITY RM
A.I.I.
BEDROOM
2NF-1
CORRIDOR
C2-4
ALCOVE
C2-4A
A.I.I.
BEDROOM
2NJ-1
PATIENT
ISOLATION
TLT
2NF-3
A.I.I. ANTE
ROOM
2NF-2
A.I.I. ANTE
ROOM
2NJ-2
PATIENT
ISOLATION
TLT
2NJ-3
CORRIDOR
C2-4
PATIENT
ISOLATION
TLT
2NG-3
A.I.I. ANTE
ROOM
2NG-2
A.I.I. ANTE
ROOM
2NH-2
PATIENT
ISOLATION
TLT
2NH-3
A.I.I.
BEDROOM
2NG-1
A.I.I.
BEDROOM
2NH-1
CLEAN
UTILITY RM
MED. GAS
STORAGE
ONCOLOGY
EXAM
EXISTING
INFUSION
CLINIC
TELECOM
ROOM
CLEAN
LINEN
CORRIDOR
C2-5
PUBLIC
ELEVATOR
LOBBY
C2-1
STAIR #2
S2.2
MED. PREP
2NN-5
HAND WASH
ALCOVE
2NN-3
NOURISH
2NN-4
EQUIPMENT
STORAGE
A213 CORRIDOR
C2-8
CORRIDOR
C2-8A
FAM. TLT
FAM. TLT
CORRIDOR
C2-3
NURSE
STATION-NORTH
2NN-2
NURSE
MANAGER
2NN-1STAIR #1
S1.2
STERILE
SUPPLY
MSD
HAC
421 7 9 10 12 13 15 16 17 20
23 26 27
U
S
X
Y
Z
15 15
15 15
C C
C
C
C C
C
C
C
C
AHU-1
C
C
C
C
C
CI
CI
MD OFFICE
PATIENT
ISOLATION
TLT
2NB-3
T
V
A.I.I.
BEDROOM
2ND-1
2-HOUR FIRE BARRIER
1-HOUR FIRE BARRIER
1-HOUR SMOKE PARTITION
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
SECOND FLOOR FIRE ALARM PLAN 2 NORTH
FA101
SCALE: 1/8" = 1'-0"
SECOND FLOOR - FIRE ALARM - 2 NORTH KEY PLAN
B64A
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
GENERAL NOTES
RATED PARTITION LEGEND
1/8" = 1' - 0" 0 5' 10' 15' 30'
1. UPON SMOKE DETECTOR INITIATING ALARM SIGNAL, POWER FROM DOOR
HOLERS SHALL BE DE-ENERGIZED TO ALLOW RELEASE OF DOOR.
2. FIRE ALARM ZONE BOUNDARIES ON 2ND FLOOR SHALL BE THE SAME AS
THOSE FOR THE SPRINKLER ZONES SHOWN ON SHEETS FX101 AND FX102.
1. SEE SHEET F-001 FOR FIRE PROTECTION LEGEND AND GENERAL NOTES.
SERVICE
ELEVATOR
LOBBY
C2-2
MED. PREP
2SN-5
NOURISH
2SN-4
NURSE
STATION-SOUTH
2SN-2
NURSE
ASSIST
MANAGER
2SN-1
STAIR #3
S3.2
EXISTING
ELECTRICAL
ROOM
MULTI-PURPOSE
ROOM/
STAFF
LOUNGE
STAFF TLT
204A
CLEAN
UTILITY RM
MED. GAS
STORAGE
SOILED
UTILITY RM
A.I.I.
BEDROOM
2SJ-1
A.I.I.
BEDROOM
2SF-1
CORRIDOR
C2-7
PATIENT
ISOLATION
TLT
2SJ-3
A.I.I. ANTE
ROOM
2SJ-2
A.I.I. ANTE
ROOM
2SF-2
PATIENT
ISOLATION
TLT
2SF-3
PATIENT
ISOLATION
TLT
2SH-3
A.I.I. ANTE
ROOM
2SH-2
A.I.I. ANTE
ROOM
2SG-2
PATIENT
ISOLATION
TLT
2SG-3
A.I.I.
BEDROOM
2SH-1
A.I.I.
BEDROOM
2SG-1
A.I.I. ANTE
ROOM
2SE-2
PATIENT
ISOLATION
TLT
2SE-3
A.I.I.
BEDROOM
2SE-1
CORRIDOR
C2-6
HAC
STERILE
SUPPLY
MSD
A.I.I.
BEDROOM
2SD-1
A.I.I. ANTE
ROOM
2SD-2
A.I.I. ANTE
ROOM
2SC-2
PATIENT
ISOLATION
TLT
2SD-3
PATIENT
ISOLATION
TLT
2SC-3
A.I.I.
BEDROOM
2SC-1
A.I.I.
BEDROOM
2SB-1
PATIENT
ISOLATION
TLT
2SB-3
BARIATRIC
ISOLATION
TLT
2SA-3
A.I.I.
BARIATRIC
ANTE ROOM
2SA-2
A.I.I. ANTE
ROOM
2SB-2
A.I.I.
BARIATRIC
BEDROOM
2SA-1
FAMILY
LOUNGE
40 42 44 46 47 50 52 53 54
39 43
U
33 37
S
C
C
C
C
C
C
C
C
C
AHU-2
15C
15C
15C
30C
15C
15C
CI
CI
V
W
T
R
X
Y
Z
2-HOUR FIRE BARRIER
1-HOUR FIRE BARRIER
1-HOUR SMOKE PARTITION
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
SECOND FLOOR FIRE ALARM PLAN 2 SOUTH
FA102
SCALE: 1/8" = 1'-0"
SECOND FLOOR - FIRE ALARM - 2 SOUTH KEY PLAN
B64A
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
GENERAL NOTES
RATED PARTITION LEGEND
1/8" = 1' - 0" 0 5' 10' 15' 30'
NORTH
1. SEE SHEET F-001 FOR FIRE PROTECTION LEGEND.
2. FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
72 - 2022 EDITIION, VA FIRE PROTECTION DESIGN MANUAL. PROVIDE
WIRING AS RECOMMENDED BY MANUFACTURER. CONTRACTOR MUST
SUBMIT SHOP DRAWINGS FOR REVIEW.
1. UPON SMOKE DETECTOR INITIATING ALARM SIGNAL, POWER FROM DOOR
HOLERS SHALL BE DE-ENERGIZED TO ALLOW RELEASE OF DOOR.
2. FIRE ALARM ZONE BOUNDARIES ON 2ND FLOOR SHALL BE THE SAME AS
THOSE FOR THE SPRINKLER ZONES SHOWN ON SHEETS FX101 AND FX102.
TOILET
311A STAFF
LOUNGE
311 NURSE
EDUCATOR
SOCIAL
WORKER
TELECOM
ROOM
SERENITY
ROOM
EXISTING
ELECTRICAL
ROOM
LAUNDRY
305 STAFF
LOUNGE
TOILET
304A
ELEC.
A301
ELEC
A363
SERVICE
ELEVATOR
LOBBY
C3-2
FAMILY
DINING
ROOM
FAMILY TLT.
FAMILY TLT.
CORRIDOR
C3-8A
EQUIPMENT
STORAGE
3-NORTH
SCREENED
BALCONY
STAIR #2
S2.3
17 20
33 37
32 35 23 26 27
D.70
D.32
C
C
C
C
C
AHU-4
C
C
C
15 C 15 C
15 C
C
C3-1
PUBLIC
ELEVATOR
LOBBY
C3-5
CORRIDOR
C
C
2-HOUR FIRE BARRIER
1-HOUR FIRE BARRIER
1-HOUR SMOKE PARTITION
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
THIRD FLOOR FIRE ALARM PLAN
FA103
SCALE: 1/8" = 1'-0"
THIRD FLOOR - FIRE ALARM
KEY PLAN
B64A
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
GENERAL NOTES
RATED PARTITION LEGEND
1/8" = 1' - 0" 0 5' 10' 15' 30'
NORTH
1. SEE SHEET F-001 FOR FIRE PROTECTION LEGEND.
2. FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
72 - 2022 EDITIION, VA FIRE PROTECTION DESIGN MANUAL. PROVIDE
WIRING AS RECOMMENDED BY MANUFACTURER. CONTRACTOR MUST
SUBMIT SHOP DRAWINGS FOR REVIEW.
A.I.I.
BEDROOM
2NB-1
BARIATRIC
ISOLATION
TLT
2NA-3
A.I.I.
BARIATRIC
BEDROOM
2NA-1
A.I.I.
BARIATRIC
ANTE ROOM
2NA-2
A.I.I. ANTE
ROOM
2NB-2
A.I.I.
BEDROOM
2NC-1
A.I.I. ANTE
ROOM
2NC-2
A.I.I. ANTE
ROOM
2ND-2PATIENT
ISOLATION
TLT
2ND-3
PATIENT
ISOLATION
TLT
2NC-3
A.I.I.
BEDROOM
2NE-1
CORRIDOR
C2-3
PATIENT
ISOLATION
TLT
2NE-3
A.I.I. ANTE
ROOM
2NE-2 SOILED
UTILITY RM
A.I.I.
BEDROOM
2NF-1
CORRIDOR
C2-4
ALCOVE
C2-4A
A.I.I.
BEDROOM
2NJ-1
PATIENT
ISOLATION
TLT
2NF-3
A.I.I. ANTE
ROOM
2NF-2
A.I.I. ANTE
ROOM
2NJ-2
PATIENT
ISOLATION
TLT
2NJ-3
CORRIDOR
C2-4
PATIENT
ISOLATION
TLT
2NG-3
A.I.I. ANTE
ROOM
2NG-2
A.I.I. ANTE
ROOM
2NH-2
PATIENT
ISOLATION
TLT
2NH-3
A.I.I.
BEDROOM
2NG-1
A.I.I.
BEDROOM
2NH-1
CLEAN
UTILITY RM
MED. GAS
STORAGE
ONCOLOGY
EXAM
EXISTING
INFUSION
CLINIC
TELECOM
ROOM
CLEAN
LINEN
CORRIDOR
C2-5
PUBLIC
ELEVATOR
LOBBY
C2-1
STAIR #2
S2.2
MED. PREP
2NN-5
HAND WASH
ALCOVE
2NN-3
NOURISH
2NN-4
EQUIPMENT
STORAGE
A213
CORRIDOR
C2-8
CORRIDOR
C2-8A
FAM. TLT
CORRIDOR
C2-3
NURSE
STATION-NORTH
2NN-2
NURSE
MANAGER
2NN-1STAIR #1
S1.2
STERILE
SUPPLY
MSD
HAC
219 1
SPRINKLER ZONE - SECOND FLOOR CENTER
NOTE: AREA OF NEW WORK IS ENTIRE SECOND FLOOR
SPRINKLER ZONE - SECOND FLOOR WARD 2 NORTH
OH1
421 7 9 10 12 13 15 16 17 20
23 26 27
OH2
OH1
OH2
OH2 OH2OH1
OH1
MD OFFICE
U
S
X
Y
Z
T
V
A.I.I.
BEDROOM
2ND-1
2-HOUR FIRE BARRIER
1-HOUR FIRE BARRIER
1-HOUR SMOKE PARTITION
TS
F
2ND FLOOR
STAIR 1
SPRINKLER RISER
FLOOR CONTROL VALVE ASSEMBLY
ELEVATION VIEW
TS
F
2ND FLOOR STAIR 2
SPRINKLER RISER
FLOOR CONTROL VALVE
ASSEMBLY
ELEVATION VIEW
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
SECOND FLOOR SPRINKLER PLAN 2 NORTH
FX101
SCALE: 1/8" = 1'-0"
SECOND FLOOR - SPRINKLER - 2 NORTH
KEY PLAN
B64A
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
GENERAL NOTES
RATED PARTITION LEGEND
1/8" = 1' - 0" 0 5' 10' 15' 30'
1.
1. SEE ELEVATION VIEW DETAIL ON THIS SHEET FOR CONNECTION OF NEW
SPRINKLER PIPING.
SEE SHEET F-001 FOR FIRE PROTECTION LEGEND AND GENERAL NOTES.
2-HOUR FIRE BARRIER
1-HOUR FIRE BARRIER
1-HOUR SMOKE PARTITION
SERVICE
ELEVATOR
LOBBY
C2-2
MED. PREP
2SN-5
NOURISH
2SN-4
NURSE
STATION-SOUTH
2SN-2
NURSE
ASSIST
MANAGER
2SN-1
STAIR #3
S3.2
EXISTING
ELECTRICAL
ROOM
MULTI-PURPOSE
ROOM/
STAFF
LOUNGE
STAFF TLT
204A
CLEAN
UTILITY RM
MED. GAS
STORAGE
SOILED
UTILITY RM
A.I.I.
BEDROOM
2SJ-1
A.I.I.
BEDROOM
2SF-1
CORRIDOR
C2-7PATIENT
ISOLATION
TLT
2SJ-3
A.I.I. ANTE
ROOM
2SJ-2
A.I.I. ANTE
ROOM
2SF-2
PATIENT
ISOLATION
TLT
2SF-3
PATIENT
ISOLATION
TLT
2SH-3
A.I.I. ANTE
ROOM
2SH-2
A.I.I. ANTE
ROOM
2SG-2
PATIENT
ISOLATION
TLT
2SG-3
A.I.I.
BEDROOM
2SH-1
A.I.I.
BEDROOM
2SG-1
A.I.I. ANTE
ROOM
2SE-2
PATIENT
ISOLATION
TLT
2SE-3
A.I.I.
BEDROOM
2SE-1
CORRIDOR
C2-6
HAC
STERILE
SUPPLY
MSD
A.I.I.
BEDROOM
2SD-1
A.I.I. ANTE
ROOM
2SD-2
A.I.I. ANTE
ROOM
2SC-2PATIENT
ISOLATION
TLT
2SD-3
PATIENT
ISOLATION
TLT
2SC-3
A.I.I.
BEDROOM
2SC-1
A.I.I.
BEDROOM
2SB-1
PATIENT
ISOLATION
TLT
2SB-3
BARIATRIC
ISOLATION
TLT
2SA-3A.I.I.
BARIATRIC
ANTE ROOM
2SA-2
A.I.I. ANTE
ROOM
2SB-2
A.I.I.
BARIATRIC
BEDROOM
2SA-1
FAMILY
LOUNGE
SPRINKLER ZONE - SECOND FLOOR CENTER SPRINKLER ZONE - SECOND FLOOR WARD 2 SOUTH
NOTE: AREA OF NEW WORK IS ENTIRE SECOND FLOOR
OH1
OH1
OH2
40 42 44 46 47 50 52 53 54
39 43
33 37
OH2
OH2
OH1
U
S
V
W
T
R
X
Y
Z
TS
F
2ND FLOOR
STAIR 3
SPRINKLER RISER
FLOOR CONTROL VALVE ASSEMBLY
ELEVATION VIEW
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
SECOND FLOOR SPRINKLER PLAN 2 SOUTH
FX102
KEY PLAN
B64A
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
GENERAL NOTES
RATED PARTITION LEGEND
1/8" = 1' - 0" 0 5' 10' 15' 30'
SCALE: 1/8" = 1'-0"
SECOND FLOOR - SPRINKLER - 2 SOUTH NORTH
1.
1. SEE ELEVATION VIEW DETAIL ON THIS SHEET FOR CONNECTION OF NEW
SPRINKLER PIPING.
TOILET
311A
STAFF
LOUNGE
NURSE
EDUCATOR
SOCIAL
WORKER
TELECOM
ROOM
SERENITY
ROOM
EXISTING
ELECTRICAL
ROOM
LAUNDRY
STAFF
LOUNGE
TOILET
304A
ELEC.
A301
SERVICE
ELEVATOR
LOBBY
C3-2
FAMILY
DINING
ROOM
FAMILY TLT.
FAMILY TLT.
CORRIDOR
C3-8A
EQUIPMENT
STORAGE
3-NORTH
SCREENED
BALCONY
STAIR #2
S2.3
SPRINKLER ZONE - THIRD FLOOR CENTER
SPRINKLER ZONE - THIRD
FLOOR WARD 3 NORTH
AREA OF NEW WORK
AREA OF NEW WORK
15 40
33 37
32 35 23 26 27
D.70
D.32
17 20
OH1
OH1OH1OH1
ELEC
A363
OH1
OH1
3-SOUTH
SCREENED
BALCONY
A374
OH2
C3-1
PUBLIC
ELEVATOR
LOBBY
C3-5
CORRIDOR
2-HOUR FIRE BARRIER
1-HOUR FIRE BARRIER
1-HOUR SMOKE PARTITION
3RD FLOOR
TS
F
3RD FLOOR
STAIR 2
SPRINKLER STANDPIPE RISER WITH
HOSE VAVLE CONNECTION &
FLOOR CONTROL VALVE ASSEMBLY
ELEVATION VIEW
HVC
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
THIRD FLOOR SPRINKLER PLAN
FX103
KEY PLAN
B64A
SCALE: 1/8" = 1'-0"
THIRD FLOOR - SPRINKLER
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
GENERAL NOTES
RATED PARTITION LEGEND
1/8" = 1' - 0" 0 5' 10' 15' 30'
NORTH
1.
1. PROVIDE ADDED AND RELOCATED SPRINKLERS TO ACCOMODATE REVISED
FLOOR AND CEILING PLANS.
B
6' -0
8"
EL. 0'
3' -0
8"
C EL. 9'
4' -0
8"
B
A
EL. 0'
FIRE
PUMP
UP 9'-0" TO C
5' -0
8"
4'-0"
8"
3' -0
8"
4' -0
8"
8'-0"
8" 8"
CEL. 9' D
E 4'-0"
8" F
GH
UP 1'-0" TO K
J
1' -0
8"
KEL. 10'
J EL. 9'
KEL. 10'
5' -0
8"
4'-0"
8"
3' -0
8"
1' -0
8" 5'-0"
8"
'-0
8"
UP 12'-0" TO S
R
EL. 9'
EL. 10'
P N
M L
'-0
6"
R EL. 10'
2ND FLOOR
2'-0"
2-1/2"
4'-0"1' -0
2- 1/
2"
4'-0"
6"
1'-0"
6"
S 8'
-0
6"
V
U T
TS
F
2ND FLOOR
STAIR 1
SPRINKLER STANDPIPE RISER
FLOOR CONTROL VALVE ASSEMBLY
PLAN VIEW
ELEVATION VIEW
PLAN VIEW ELEVATION VIEW
PLAN VIEW
ELEVATION VIEW
4' -0
8"
B
A
EL. 0'
FIRE
PUMP
UP 9'-0" TO C
1' -0
8"
FEL. 10'
E EL. 9'
2ND FLOOR
STAIR 2
SPRINKLER STANDPIPE RISER WITH
HOSE VAVLE CONNECTION &
FLOOR CONTROL VALVE ASSEMBLY
HVC
CEL. 9' 4'-0"
8" D
UP 2'-0" TO E F
'-0
8"
JEL. 10'
G
F EL. 10'
'-0
8"
10'-0"
8"
2ND FLOOR
'-0
8"
3' -0
6" 6"
6'-0"
2-1/2"
5' -0
2- 1/
2"
TS
F
L
K
J
K
B
6' -0
8"
EL. 0'
3' -0
8"
C EL. 9' 2'
-0
8"
UP 12'-0" TO K
PLAN VIEW
ELEVATION VIEW
ELEVATION VIEW
PLAN VIEW
PLAN VIEW ELEVATION VIEW
4' -0
8"
B
A
EL. 0'
FIRE
PUMP
UP 9'-0" TO C
1' -0
8"
FEL. 10'
E EL. 9'
CEL. 9' 4'-0"
8" D
UP 1'-0" TO E F
5'
-0
8"
K
G
F EL. 10'
8' -0
8"
10'-0"
8"
20'-0"
8"
J
H
'-0
6"
K EL. 10'
2ND FLOOR
2'-0"
6"
L
8' -0
6"
M
TS
F
2ND FLOOR
STAIR 3
SPRINKLER STANDPIPE RISER
FLOOR CONTROL VALVE ASSEMBLY
6"
2'-0"
2-1/2"
B
6' -0
8"
EL. 0'
3' -0
8"
C EL. 9'
2' -0
8"
UP 10'-0" TO L
PLAN VIEW ELEVATION VIEW
ELEVATION VIEW
PLAN VIEW
PLAN VIEW ELEVATION VIEW
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CORRECT PATIENT PRIVACY
DEFICIENCES - BLDG 64-UNIT A
LAKE CITY VAMC
573A4-18-603
Lake City, FL
JANUARY 29, 2024REVISIONS: DZT EVA
SPRINKLER PIPE DIAGRAMS
FX701
NOT TO SCALE
PIPING SUPPLY LAYOUT - SECOND FLOOR
SPRINKLER SYSTEM - STAIR #1
SCALE: 1/2" = 1'-0"
PIPING SUPPLY LAYOUT - SECOND FLOOR
SPRINKLER SYSTEM - STAIR #2
SCALE: 1/2" = 1'-0"
PIPING SUPPLY LAYOUT - SECOND FLOOR
SPRINKLER SYSTEM - STAIR #3
| Sheets |
| F001 - FIRE PROTECTION LEGEND NOTES AND DETAILS |
| FA101 - SECOND FLOOR FIRE ALARM PLAN 2 NORTH |
| FA102 - SECOND FLOOR FIRE ALARM PLAN 2 SOUTH |
| FA103 - THIRD FLOOR FIRE ALARM PLAN |
| FD101 - SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN |
| FD102 - THIRD FLOOR FIRE PROTECTION DEMOLITION PLAN |
| FX101 - SECOND FLOOR SPRINKLER PLAN 2 NORTH |
| FX102 - SECOND FLOOR SPRINKLER PLAN 2 SOUTH |
| FX103 - THIRD FLOOR SPRINKLER PLAN |
| FX701 - SPRINKLER PIPE DIAGRAMS |
| 2024-01-23T21:06:05-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:47:40-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:49:38-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:50:54-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:52:54-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:54:08-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:55:05-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:56:17-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:57:30-0500 | |
| Deam Z Tolete |
| 2024-01-23T21:58:21-0500 | |
| Deam Z Tolete |
File details come from the government source that posted it. Updated .