This Addendum Table 1 is associated with the Rouge Valley Sewage Disposal System (RVSDS) SRF Project Plan for Phases 2C/3C Sewer Rehabilitation in Wayne County, Michigan. The document provides detailed technical specifications for sewer rehabilitation, specifically focusing on liner specifications for multiple interceptor segments across two designated areas (Area A and Area B). The table includes critical engineering parameters such as existing pipe geometry, assumed liner for design, and maximum allowable liner characteristics, including inner diameter measurements, roughness coefficients, and open channel capacities for various sewer segments.
The table presents technical data for five specific sewer interceptors with varying prevailing slopes ranging from 0.06% to 0.13%, and documents the proposed liner thickness and performance characteristics. The highlighted notation indicates a maximum cross-section reduction allowance, which includes considerations for grouting and voids. The data suggests a comprehensive approach to sewer system rehabilitation that maintains hydraulic performance while accommodating structural improvements. The document is dated 6/7/2024 and was prepared by Applied Science, Inc., indicating ongoing engineering assessment for the sewer rehabilitation project.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inner Diameter
(in)
Roughness Coefficient
Open Channel Capacity
(cfs)
Liner Thickness
(mm)
Inner Diameter
(in)
Roughness Coefficient
Open Channel Capacity
(cfs)
Max. Liner Thickness
(mm)
Inner Diameter
(in)
Roughness Coefficient
Open Channel Capacity
(cfs)
RVI RVI 6-38 RVI 6-30 0.13% 66 0.016 97.6 24.0 64.1 0.013 111.1 62.7 61.1 0.013 97.6
MRIR NHV 3-15 NHV 3-01 0.12% 54 0.016 54.8 21.0 52.3 0.013 62.1 51.4 50.0 0.013 54.8
MRPIE MR I-16 MR I-11 0.06% 60 0.016 53.8 21.0 58.3 0.013 61.5 57.3 55.5 0.013 53.8
RVI RVI 6-22 RVI 6-13 0.07% 78 0.016 111.3 28.5 75.8 0.013 126.7 74.1 72.2 0.013 111.3
MRIR NHV 2-32 NHV 2-21 0.08% 66 0.016 78.3 24.0 64.1 0.013 89.2 62.7 61.1 0.013 78.3
Assumed Liner for Design Max. Allowable Liner
Area A
Area B
Rehabilitation Area
Prevailing Slope
Downstream GIS Structure ID
Upstream GIS Structure ID
Existing Pipe Geometry
Interceptor
Applied Science, Inc.
6/7/2024
RDaavettila Text Box
RDaavettila Callout
MAX CROSS SECTION REDUCTION ALLOWED INCLUDING ANY GROUTING/VOIDS
RDaavettila Text Box
ADDENDUM TABLE 1