BLD 562 300A (SN 70503603)_260401_0925.pdf
PDF 1 MB Posted
- Attached to
- Design/Build B562 MAU#1 Replacement
- Solicitation number
- ACQR6148962
About this file
This is an NEC220.87 electrical load analysis report generated by Fluke for Building 562 (Serial Number 70503603) covering an evaluation period from April 1, 2026 to April 8, 2026. The report assesses the electrical capacity and load requirements for a panel with a 600-ampere (A) circuit breaker rating, using the 80% continuous load capacity calculation method standard in the National Electrical Code (NEC).
The connected load study identifies a maximum average demand of 73A and maximum 3-hour continuous load of 71A, with a total connected load of 91A using the NEC 220.87 Exception method. The panel currently has an available continuous load capacity of 409A and combined continuous and non-continuous capacity of 509A, with a base load of 46A. The plan/projected load analysis incorporates a planned additional load of 300A, resulting in a projected total load of 391A and projected continuous load of 305A, which represents 78.0% of the planned additional continuous load. This leaves a projected remaining continuous load capacity of 175A and total remaining capacity of 209A, indicating sufficient capacity for the planned electrical additions to Building 562.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4/10/2026 8:49:13 AM
From:
To:
Period:
Evaluation Period
4/1/2026 9:30:00 AM
4/8/2026 9:15:00 AM
6d 23h 45m 0s
NEC220.87 Report
BLD 562 (SN 70503603)_260401_0925.fca2 page 1 of 2
4/10/2026 8:49:13 AM
Settings
Panel Circuit Breaker Rating 600A
80% of Panel Circuit Breaker Rating 480A
Seasonal Adjustments 0A
Known Non Operating Load 0A
Planned Additional Load 300A
Maximum values detected on Phase C
Continuous Load Capacity calculations based on: 80% CBR
Connected Load Study
Maximum Average Demand (MAD) 73A
Maximum 3-hour Continuous Load (MCL) 71A
Total Connected Load (NEC 220.87 Exception method) 91A
Base Load (Minimum Average Demand) 46A
Available Capacity Continuous Load 409A
Available Capacity Cont. & Non-Cont. 509A
Plan/Projected Load Analysis
Projected Load 391A
Projected Remaining Load Capacity 209A
Planned Additional Continuous Load % 78.0%
Projected Continuous Load 305A
Projected Remaining Continuous Load Capacity 175A