BLD 562 200A (SN 70503603)_260401_0925.pdf
PDF 1 MB Posted
- Attached to
- Design/Build B562 MAU#1 Replacement
- Solicitation number
- ACQR6148962
About this file
This is an electrical load analysis report (NEC220.87 Report) generated by Fluke for Building 562 (Serial Number 70503603) covering an evaluation period from April 1, 2026 to April 8, 2026. The report analyzes the electrical capacity and load conditions of a 600-ampere panel circuit breaker system.
The connected load study indicates a maximum average demand of 73 amperes and a maximum 3-hour continuous load of 71 amperes, with a total connected load of 91 amperes using the NEC 220.87 Exception method. The facility currently has an available continuous load capacity of 409 amperes and combined continuous and non-continuous capacity of 509 amperes. The plan/projected load analysis accounts for an additional 200-ampere planned load and projects a total load of 291 amperes with a remaining load capacity of 309 amperes. After incorporating the planned additional continuous load at 78.0% of capacity, the projected continuous load is 227 amperes, leaving a projected remaining continuous load capacity of 253 amperes. The report is based on continuous load capacity calculations using 80 percent of the panel circuit breaker rating (480 amperes).
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4/10/2026 8:48:53 AM
From:
To:
Period:
Evaluation Period
4/1/2026 9:30:00 AM
4/8/2026 9:15:00 AM
6d 23h 45m 0s
NEC220.87 Report
BLD 562 (SN 70503603)_260401_0925.fca2 page 1 of 2
4/10/2026 8:48:53 AM
Settings
Panel Circuit Breaker Rating 600A
80% of Panel Circuit Breaker Rating 480A
Seasonal Adjustments 0A
Known Non Operating Load 0A
Planned Additional Load 200A
Maximum values detected on Phase C
Continuous Load Capacity calculations based on: 80% CBR
Connected Load Study
Maximum Average Demand (MAD) 73A
Maximum 3-hour Continuous Load (MCL) 71A
Total Connected Load (NEC 220.87 Exception method) 91A
Base Load (Minimum Average Demand) 46A
Available Capacity Continuous Load 409A
Available Capacity Cont. & Non-Cont. 509A
Plan/Projected Load Analysis
Projected Load 291A
Projected Remaining Load Capacity 309A
Planned Additional Continuous Load % 78.0%
Projected Continuous Load 227A
Projected Remaining Continuous Load Capacity 253A
BLD 562 (SN 70503603)_260401_0925.fca2 page 2 of 2