283113.003.01 - Digital Addressable Fire-Alarm System - SD - AAN 2nd Floor Buildout.pdf

PDF 4 MB Posted

Attached to
B401 Tenant Buildout
Solicitation number
70FA5026Q00000002
Issued by

About this file

This document is a comprehensive fire alarm system submittal for the FEMA Building 401 2nd Floor Tenant located at 19844 Blue Ridge Mountain Road in Bluemont, VA. The submittal, prepared by Convergint for The Christman Company, details the installation of a digital, addressable fire alarm system using an existing Edwards EST-3 Fire Alarm Control Panel. The system will be installed for Tenant 5A & 5B and includes 24 total smoke detectors, 4 heat detectors, multiple signal modules, notification appliances, and a VESDA air sampling detection system.

The submittal includes detailed technical specifications, device calculations, battery sizing, speaker circuit plans, and spare capacity analysis. Key system features include Class A signaling and notification circuits, voice evacuation capabilities, network connectivity to a central monitoring station, and 5-year warranty coverage. The project involves adding a second loop card to the existing fire alarm panel, implementing underfloor VESDA detection, and ensuring comprehensive coverage across the building's second floor, including various office spaces, corridors, mechanical rooms, and future tenant areas.

View the file

Other files

File Type Posted
PP_Questionnaire.docx DOCX document
B401Tele Room 102 - 202 - pathway and Rack elevations.pdf PDF
Copy of B401 Tenant-6 Bidder Inquiries - 021326 REV-6 FINAL to post.xlsx XLSX spreadsheet
B401 Base Bldg A6.20 Window Schedule & Details.pdf PDF
70FA5026Q00000001 A0002.pdf PDF
GFCI Government Furnished Contractor Installed Materials.pdf PDF
B401 Base Bldg A2.01 Window Elevations.pdf PDF
B401 Base Bldg A1.01 L2 FP - Window Types.pdf PDF
B401 T6 Bre-Bid Conference Sign in Sheet.pdf PDF
B401 Base Bldg A2.02 Window Elevations.pdf PDF
101423.002.00 - Interior Signage -SAMPLE-2.pdf PDF
101423.001.00 - Interior Signage.pdf PDF
Level-2 Mech Piping Plan Existing.pdf PDF
101423 Signage spec from Tenant 1 and 2.pdf PDF
265219.001.00 - Emergency and Exit Lighting - SAMPLE SUBMITTAL MWEOC Std..pdf PDF
Level-2 Power Plan Existing.pdf PDF
B401 Base Bldg A2.00 Window Elevations.pdf PDF
101423.001.00 - Interior Signage -SAMPLE-1.pdf PDF
OF 336 70FA5026Q00000002.pdf PDF
70FA5026Q00000002 A0001.pdf PDF
B401 T6 IFC FFE Plan Schedules1.pdf PDF
B401 T6 IFC FFE Spec Book.pdf PDF
B401 Tenant6 Dry Cooler IFC Plans - Combined.pdf PDF
B401 Tenant 6 Vol I-II IFC Specifications.pdf PDF
Previous Bidder Inquiries QA Ref Only 12.08.25 REV6.pdf PDF
B401 Base-Building Subcontractor List.docx DOCX document
GFCI Government Furnished Contractor Installed Materials.docx DOCX document
70FA5026Q00000002 final.pdf PDF
B401 Base-Building MECH Dwgs.pdf PDF
283113 - Digital Addressable Fire Alarm - Tenant 3 4 - 10-3-23 FEMA APP w comments.pdf PDF
70FA5026Q00000002 solicitation.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

283113.003.01 FEMA Project FEMA Bldg. 401 - 70FA5020C00000008

TCC Job No. 220867 A/E Mason & Hanger

To Michael McPeak From The Christman Company

Submitting Contractor TEI

Specification Division 28 - Electronic Safety and Security

FOR APPROVAL

Submittal 283113.003.01 – Digital, Addressable Fire-Alarm System -

Tenant 5A & 5B

Notes Specifications Included This submittal includes shop drawings for digital, addressable fire-alarm system added in this fit-out.

283113 – 1.7C

☒ Shop Drawings ☐ Sample ☐ Preconstruction Documentation ☐ Test Reports ☐ Qualification Data ☐ Delegated Design ☐ Product Data ☐ Owner’s Manual Data ☐ Certificates ☐ Warranty

☒ Specified Item ☒ No Exceptions Taken ☐ Substitute Item ☐ Make Corrections Noted ☐ FIO ☐ Revise and Resubmit

☐ Rejected as Noted

Reviewed for general conformance with the technical specifications and the drawings. Any information shown herein is subject to the requirements of the plans and specifications. All dimensions to be verified in field by the subcontractor. Any approval does not negate the requirement to follow Contract Documents.

Reviewed By: Zach Holder Submitted By: Zach Holder Submittal Date:

8/20/2024 Due Date: 9/3/2024 mmcpeak

APPROVED EXCEPT AS NOTED

mmcpeak Typewritten Text

1. Reference Drawing F2 & F4: There should be a total of seven (7) VESDA (ASPF) zones on Level 2. Coordinate zone designations accordingly.

Ph : 301-874-4630

4840 Winchester Blvd, Suite 1

Frederick, MD 21703

D ate: 8/14/2024

Job: 5117-004-01 Mt. Weather Bldg 401

Letter of Transmittal

Transmittal #: 73To: Austin White

The Christman Company

22560 Glenn Drive

Suite 108

Sterling, VA 20164

Ph: (858)699-7345 Fax: 703-740-5646

Subject: Submittal

Samples

Change order

Shop drawings

Under separate cover via the following items:AttachedWE ARE SENDING YOU

Submittal

Prints Plans

Copy of letter Specifications

DescriptionNo.DateCopiesDocument Type

1 8/14/24 283113-3 Rev 1 FIRE ALARM SYSTEM - 2ND FL WEST FITOUTSubmittal

Other

PRINTS RETURNED AFTER LOAN TO USFOR BIDS DUE

For review and comment

Return ___ corrected printsReturned for corrections

Submit ___ copies for distributionApproved as noted

For approval Resubmit ___ copies for approvalApproved as submitted

THESE ARE TRANSMITTED as checked below:

Remarks:

For your use

As requested

Copy To:

Signature:From: Denise Strasser (TEI Electrical Solutions)

If enclosures are not as noted, kindly notify us at once. Page 1 of 1

Ph : 301-874-4630

4840 Winchester Blvd, Suite 1

Frederick, MD 21703

Job:

Mt. Weather Bldg 401

Spec Section No:

19844 Blue Ridge Mountain Road

Bldg 401

Submittal No:

283113

Sent Date:

Revision No: 1

Submittal

8/14/2024

5117-004-01

Bluemont, VA 20135

Spec Section Title: DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM/MASS NOTIFICATION SYSTEM

Submittal Title: FIRE ALARM SYSTEM - 2ND FL WEST FITOUT

Contractor's Stamp

Architect's Stamp

Engineer's Stamp

Craig Dixon

Contractor:

General Contractor:

The Christman Company

Austin White

Tissa Enterprises, Inc. dba TEI Electrical Solutions

Fire Alarm Submittal Action Plan

MT. WEATHER BLDG 401 2FL TENANT Project Type:FIRE ALARM System Type: EDWARDS

RENOVATION EST-3

Review Date

Reviewer Review

Comment Status Resolution Follow-up/Final Verification & Date

Review Date

8/8/2024 ZH 1 PG. 20, ROOM 214A SEC COOP TELECOM, Add heat detector as required to provide coverage to match all other Telecom Rooms.

Heat detector not shown in room 214A. Heat detector added to room 214A.

8/8/2024 ZH 2 PG 22, ROOM 214A SEC COOP TELECOM, VESDA

drawing does not show end cap sample port.

Xtralis Pipe Cad drawings does show end cap. VESDA end cap not shown in room 214A. End cap added to room 214A.

8/8/2024 ZH 3

PG 20, Need to correct VESDA Zone numbers.

Zone 2 is duplicated. Should be 7 zones total.

Zone 2 shown as a duplicate on page 20.

Per contract drawings the Zones were reconfigured from the original installation documents. Zone 2 was enlarged and Zone 1 was made smaller, there is still a total of 5 zones on Level 2.

Sincerely

Richard Salmon Systems Designer III

NICET IV 87901

In an effort to prevent any delays in construction, Any coordination issues involving final location of devices shall be included and provided to owner on as-built documents at close of project. The actual location of the devices shall not produce any significant changes to system design and operation.

If you have any questions regarding any portion of this response, please contact me at 703 631-7476 or at rich.salmon@convergint.com

Eng. Comments Responses_08-14-24_rs.xlsx VIERRA Submittal Action Plan 1

REV#1

24083F

7/15/2024

RS

Richard Salmon

Nicet Level IV

Certification No. 87901

SYSTEM INSTALLED BY:

TEI Electrical Solutions

4840 Winchester Blvd-Suite 1

Frederick, MD 21703

Exist. EST-3 Fire Alarm Control System

Manufactured by UTC

(703) 631-7476

3650 Concorde Parkway-Suite 100

Chantilly, VA 20150

BLUEMONT, VA 20135

SYSTEM SUPPLIED AND SERVICED BY:

CONVERGINT CTC-443

Chantilly, VA

19844 BLUERIDGE MOUNTAIN ROAD

PROPOSED

FIRE ALARM/MNS SYSTEM

MOUNT WEATHER-BLDG 401

2ND FLOOR TENANT

Page

Scope

Nicet Certificates

Revision Sheet

Bill of Materials 1

ASSD (VESDA) Bill of Materials 2

Description of Operations 3

Addressable Loop 2 (Existing) 5

Addressable Loop 2A 8

Remote FACP Calculations 9

Speaker Calculations 10

Spare Calculations/Voltage Drop 11

Battery Calculations - Signal Panel 12

Catalog Data Pages **

TABLE OF CONTENTS

24083F_ Scope Scope

In your review of the proposed submittals we submit the following for your assistance and consideration.

The following criterion have been implemented during the design process of the Fire Alarm System:

General

The building is a Four-story structure with a small Penthouse. Occupancy use is (B) Business.

System

We have designed the fire alarm system using the existing EST-3 Fire Alarm Control Panel. A second loop card shall be added to convert Loop2 into two loops.

This scope includes a tenant fitout to the 2nd floor. Underfloor detection shall be accomplished with VESDA air sampling detectors.

A Audio Source Unit has been included in this system. Live voice messages and pre-recorded messages can be received from the main campus paging panel via the

VOIP to Audio System. Fire Alarm activity from this system shall be reported to a Central Fireworks.

Wiring

The Fire Alarm System has been designed with Class "A" Signaling Circuits and Class "A" Notification Circuits. T-Tapping of addressable circuit is NOT PERMITTED.

T-Tapping of Notification Circuits also Prohibited .

Notification

The system is designed with voice evacuation.

Existing power supplies have been provided for the Notification Appliances. These units, shall be located as shown on dwgs and shall be activated via a synchronization module. All wall mounted Notification Appliances shall be white in color, and Ceiling mounted notification devices shall be White in color.

All interior speaker shall be set at 1/2 watt initially, and exterior speakers set to 2 watts initially.

Installation

Battery Sizing has been calculated for 24 Hours standby with 15 minutes alarm per specification to comply w/ NFPA 72-2019 10.6.7.2.1(2)

All Fire Alarm Control Equipment shall be in locations protected by a smoke detector NFPA 72 2019 10.4.4

Control function interface devices (relays) shall be located within 3ft of the component controlling the emergency function. NFPA 72 2019 21.2.4

The fire alarm control panel (FACP) and extender panels shall be connected to the emergency power circuit.

Observation:

Contract documents: System Matrix denotes Duct Smoke detectors as alarm and supvervisory intiating devices.

The submittal booklet contains but is not limited to the following:

• Bill of materials.

• Sequence of Operation

• Addressable Device List

• Spare capacity

• Voltage Drop Calculations

• Speaker Loads

• Battery calculations.

The submittal drawings contain but are not limited to the following:

• Floor Plans and Wiring

• Riser Diagrams and circuit layouts.

• Details and drawings of FACP, Signal Panel and connections.

• Symbol legends, mounting and installation details.

The purpose of our shop drawings is to aid in the installation of proprietary systems. If there is a discrepancy between the contract and Convergint shop drawings that has not been addressed in this letter, the submittal booklet and shop drawings or if you have any questions in regards to any portion of this submission, please contact me at rich.salmon@convergint.com or (703) 631-7476.

Respectfully, Richard Salmon

Fire alarm Design Engineer

Convergint

NICET IV #87901

rich.salmon@convergint.com mailto:rich.salmon@convergint.com

24083F_ Rev Sheet

Changes Y/N

Mod # Description Date By Dwg

Original Submission 7/15/2024 RS

1 REVISED PER ENG COMMENTS DTD 07/25/24 8/14/2024 RS Y

Revision Sheet

24083F_ Rev Sheet

Changes Y/N

Booklet

Y

24083F_ BOM

Qty Cat No Description Manufature Cat. Sheet #

EST3 System Components

Signature Series Dual Loop Card

1 3-SDC1 Signature Driver Card (Loop 2A) EST 85010-0129

Signature Series Intelligent Detectors

20 SIGA-OSD Multi-criteria optical smoke detector (UL268 Compliant) EST 85001-1001

4 SIGA-HRD Heat detector, combination 135F fixed with 15F/min ROR, EST 85001-0647

Detector Bases

24 SIGA-SB Standard Detector Base EST 85001-1001

Signature Series Life Safety Modules

Input Modules

2 SIGA-CT1 Single Input Module EST 85001-0241

Signal Modules

3 SIGA-UM Universal Class A/B Module EST 85001-0275

Genesis G4 LED Series Accessories

2 GRSW-10 Total Universal Mounting Plate, 10 Pack EST 85001-0667

Genesis G1 LED Fire Strobes, Wall Mount, Multi-candela, 1 Gang

3 G1VWA Selectable - 15, 30, 75 cd - White - Alert EST 85001-0667

Genesis LED Series Ceiling Mount 25/70 Vrms Speaker/Strobes (1/4W to 2W) 520HZ and High Fidelity Capable (STI .81)

11 GCSVWA Ceiling Speaker/Strobe, 15-110cd, White, ALERT Marking EST 85001-1025

24083F_ BOM-VESDA

Qty Cat No Description Manuf. Cat. Sheet #

2ND FLOOR-ZONE 2 TENANT

2 VP-CLIP Pipe Clip single point fix VESDA VES-003

1 VP-COUP VESDA Couplings (15/Box) VESDA VES-004

1 VP-EC Endcap (25/Box) VESDA VES-005

2 VP-ELB-90 VESDA 90 Degree Elbows (20/Box) VESDA VES-006

3 VP-P-210 VESDA Sample Pipe, Box of 15 Pieces, 210 Feet Total VESDA VES-007

1 VP-TEE T Piece (15/Box) VESDA VES-008

1 E700-SP-DCL-PNT VESDA Sample Pt. Labels (50/Sheet) VESDA VES-009

24083F_ DOP

Activation of any Manual Pull Station, Area Smoke Detector, Sprinkler Waterflow Switch shall cause the following:

1. Send an alarm signal (via Network) to the Central Control Building (# 921).

2. Visually indicate via control panel LCD display, the floor, area and type of device in alarm. The ALARM (red) LED shall light; the internal control panel alarm shall sound; and the first line of the eighty (80) character LCD shall indicate the REAL TIME, the number of

MESSAGES WAITING, the TYPE OF ALARM, the ALARM ZONE NUMBER, and the TIME THAT THE ALARM OCCURRED. The second line shall display the user specified message. In order to reduce false alarms, all inputs shall be capable of alarm verification.

The system shall be capable of setting the sensitivity of all analog detectors by point and shall be capable of displaying the analog value of the detector by device and/or traditional input and vectoring the value to a remote printer. The system shall automatically identify any analog detector which becomes dirty (maintenance alert) prior to false alarming.

3. Visually indicate via LCD Annunciator display, the floor, area and type of device in alarm.

4. Continuous actuation of all alarm notification appliances. All audible/visual signaling devices shall sound continuously until manually silenced. It shall be possible to silence the audible portion of the appliance without extinguishing the visual strobe. A subsequent alarm received after silencing shall again cause the initiating circuits to be activated. The fire alarm signals shall be distinctive from all other alarm signals.

5. Upon receipt of an alarm signal from the building's fire alarm system, the FACP shall automatically transmit a pre-recorded fire alarm message throughout the building.

Activation of any valve tamper switch, or other supervisory device, will automatically cause the following:

1. Send a supervisory signal (via Network) to the Central Control Building (# 921).

2. Visually indicate via control panel LCD display, the area and type of device activated.

3. Visually indicate via LCD Annunciator display, the floor, area and type of device in alarm

4. Sound an audible trouble signal at the fire alarm control panel and the remote annunciators.

Any open circuit, short circuit or ground fault on any supervised circuit (alarm initiating, alarm indicating, annunciation or control relay), loss of primary AC power, primary AC power below 96 Volts, low battery, loss of battery, or any internal system trouble will automatically cause the following:

1. Send a trouble signal (via Network) to the Central Control Building (# 921).

2. Visually indicate via control panel LCD, the source and the location of the trouble.

2. Visually indicate via control panel LCD display, the area and type of device activated.

4. Sound an audible trouble signal at the fire alarm control panel and the remote annunciators.

24083F_ DOP

Upon completion of the installation and after satisfactory testing of the system by the contractor in the presence of the equipment supplier, the contractor shall test the system in the presence of the Architect/Engineer, Fire Marshal and/or owner's representative, and other authorities having jurisdiction.

The distributor shall provide 24 hour/7days a week (including holidays) service capability. Service performed at times other than normal working hours (Monday thru Friday, 8:00 AM to 5:00 PM, excluding holidays) shall be billable at an additional cost to the owner.

GUARANTEE

All Control equipment and field devices will have a warranty of (5) years from the date of acceptance. All other materials, peripherals, installation and workmanship for five (5) years from the date of acceptance, unless otherwise specified.

The contractor will warranty all wiring and raceways to be free from inherent mechanical or electrical defects for five (5) years from the date of final acceptance of the system.

24083F_ Loop 2

DEVICE NEW LABELS/DEVICES IN BOLD LOOP ROOM SENSOSR MODULE MODULE DESCRIPTION

SMOKE DETECTOR LOOP 2 300A VEST 0001

SMOKE DETECTOR LOOP 2 300 LOBBY 0002

SMOKE DETECTOR LOOP 2 324 IG SUPPORT OFC 0003

SMOKE DETECTOR LOOP 2 310 LEADERSHIP CONF RM 0004

SMOKE DETECTOR LOOP 2 310 LEADERSHIP CONF RM 0005

SMOKE DETECTOR LOOP 2 310 LEADERSHIP CONF RM 0006

SMOKE DETECTOR LOOP 2 310A ELEC. RM 0007

SMOKE DETECTOR LOOP 2 311 RECONSTITUTION RM 0008

SMOKE DETECTOR LOOP 2 312 LOCKERS 0009

SMOKE DETECTOR LOOP 2 300 LOBBY 0010

SMOKE DETECTOR LOOP 2 306 CORRIDOR 0011

SMOKE DETECTOR LOOP 2 306 CORRIDOR 0012

SMOKE DETECTOR LOOP 2 306 CORRIDOR 0013

DUCT SMOKE DETECTOR LOOP 2 301 HSKPG 0014

HEAT DETECTOR LOOP 2 301 HSKPG 0015

DUCT SMOKE DETECTOR LOOP 2 301 HSKPG 0016

DUCT SMOKE DETECTOR LOOP 2 301 HSKPG 0017

SMOKE DETECTOR LOOP 2 302 TELE. RM 0018

SMOKE DETECTOR LOOP 2 303 TOILET RM 0019

SMOKE DETECTOR LOOP 2 304 TOILET RM 0020

SMOKE DETECTOR LOOP 2 305 ELEC 0021

SMOKE DETECTOR LOOP 2 300 LOBBY 0022

SMOKE DETECTOR LOOP 2 307 MECH RM 0023

DUCT SMOKE DETECTOR LOOP 2 307 MECH RM 0024

DUCT SMOKE DETECTOR LOOP 2 307 MECH RM 0025

DUCT SMOKE DETECTOR LOOP 2 307 MECH RM 0026

DUCT SMOKE DETECTOR LOOP 2 307 MECH RM 0027

SMOKE DETECTOR LOOP 2 308 BREAK RM 0028

SMOKE DETECTOR LOOP 2 309 CORRIDOR 0029

SMOKE DETECTOR LOOP 2 320 DEP. SECRETARY 0030

SMOKE DETECTOR LOOP 2 318 DEP SEC STAFF 0031

SMOKE DETECTOR LOOP 2 319B CLASS. TLECOM 0032

SMOKE DETECTOR LOOP 2 329 IT WORK RM 0033

SMOKE DETECTOR LOOP 2 328 STORAGE 0034

SMOKE DETECTOR LOOP 2 327 STORAGE 0035

SMOKE DETECTOR LOOP 2 326 TELECOM 0036

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA CRDR 0037

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0038

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0039

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0040

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0041

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0042

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0043

SMOKE DETECTOR LOOP 2 315B CORRIDOR 0044

SMOKE DETECTOR LOOP 2 315B CORRIDOR 0045

SMOKE DETECTOR LOOP 2 319 SCIF SUITE 0046

SMOKE DETECTOR LOOP 2 319A SCIF CONF. SPACE 0047

SMOKE DETECTOR LOOP 2 314 HUD EM RESP CTR 0048

SMOKE DETECTOR LOOP 2 313 CONF. ROOM 0049

SMOKE DETECTOR LOOP 2 208 BREAK RM 0050

SMOKE DETECTOR LOOP 2 209 CORRIDOR 0051

SMOKE DETECTOR LOOP 2 209 CORRIDOR 0052

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0053

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0054

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0055

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0056

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0057

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0058

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0059

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0060

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0061

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0062

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0063

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0064

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0065

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0066

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0067

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0068

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0069

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0070

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0071

SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0072

SMOKE DETECTOR LOOP 2 209 CORRIDOR 0073

SMOKE DETECTOR LOOP 2 209 CORRIDOR 0074

SMOKE DETECTOR LOOP 2 209 CORRIDOR 0075

SMOKE DETECTOR LOOP 2 206 CORRIDOR 0076

DUCT SMOKE DETECTOR LOOP 2 201 HSKPG 0077

HEAT DETECTOR LOOP 2 201 HSKPG 0078

DUCT SMOKE DETECTOR LOOP 2 201 HSKPG 0079

DUCT SMOKE DETECTOR LOOP 2 201 HSKPG 0080

SMOKE DETECTOR LOOP 2 202 TELE RM 0081

SMOKE DETECTOR LOOP 2 203 TOILET RM 0082

SMOKE DETECTOR LOOP 2 204 TOILET RM 0083

SMOKE DETECTOR LOOP 2 205 ELEC 0084

SMOKE DETECTOR LOOP 2 200 LOBBY 0085

SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0086

SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0087

SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0088

SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0089

SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0090

SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0091

SMOKE DETECTOR LOOP 2 200A VEST 0092

SMOKE DETECTOR LOOP 2 200 LOBBY 0093

SMOKE DETECTOR LOOP 2 207 MECH RM 0094

DUCT SMOKE DETECTOR LOOP 2 207 MECH RM 0095

DUCT SMOKE DETECTOR LOOP 2 207 MECH RM 0096

DUCT SMOKE DETECTOR LOOP 2 207 MECH RM 0097

DUCT SMOKE DETECTOR LOOP 2 207 MECH RM 0098

HEAT DETECTOR LOOP 2 202 TELE RM 0099

HEAT DETECTOR LOOP 2 205 ELEC 0100

HEAT DETECTOR LOOP 2 207 MECH RM 0101

HEAT DETECTOR LOOP 2 302 TELE. RM 0102

HEAT DETECTOR LOOP 2 305 ELEC 0103

HEAT DETECTOR LOOP 2 307 MECH RM 0104

24083F_ Loop 2

DEVICE NEW LABELS/DEVICES IN BOLD LOOP ROOM SENSOSR MODULE MODULE DESCRIPTION

SMOKE DETECTOR LOOP 2 325 IG OFFICE 0105

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0106

SMOKE DETECTOR LOOP 2 330 CONF. ROOM 0107

SMOKE DETECTOR LOOP 2 315A RECEPT. AREA 0108

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0109

SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0110

SMOKE DETECTOR LOOP 2 317 PUBLIC AFFAIRS EXEC. 0111

SMOKE DETECTOR LOOP 2 323 STORAGE 0112

SMOKE DETECTOR LOOP 2 322 PUBLIC AFFAIRS 0113

HEAT DETECTOR LOOP 2 321 ELEC. ROOM 0114

SMOKE DETECTOR LOOP 2 321 ELEC. ROOM 0115

HEAT DETECTOR LOOP 2 319B CLASS. TLECOM 0116

HEAT DETECTOR LOOP 2 326 TELECOM 0117

HEAT DETECTOR LOOP 2 310A ELEC. RM 0118

MANUAL PULL STATION LOOP 2 300A VEST 0126

AED CABINET MONITORING LOOP 2 300 LOBBY 0127 (SIGA-CT1) MONITOR MODULE

MANUAL PULL STATION LOOP 2 01 STAIR 0128

TAMPER SWITCH LOOP 2 02 STAIR 0129 (SIGA-CT2) DUAL MONITOR MODULE

FLOW SWITCH 0130

MANUAL PULL STATION LOOP 2 02 STAIR 0131

MANUAL PULL STATION LOOP 2 03 STAIR 0132

MANUAL PULL STATION LOOP 2 03 STAIR 0133

AED CABINET MONITORING LOOP 2 200 LOBBY 0134 (SIGA-CT1) MONITOR MODULE

MANUAL PULL STATION LOOP 2 01 STAIR 0135

TAMPER SWITCH LOOP 2 02 STAIR 0136 (SIGA-CT2) DUAL MONITOR MODULE

FLOW SWITCH 0137

MANUAL PULL STATION LOOP 2 02 STAIR 0138

ASFP PANEL FAULT #1 LOOP 2 307 MECH RM 0139 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #1 LOOP 2 307 MECH RM 0140 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #1 LOOP 2 307 MECH RM 0141 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #1 LOOP 2 307 MECH RM 0142 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #1 LOOP 2 307 MECH RM 0143 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #2 LOOP 2 307 MECH RM 0144 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #2 LOOP 2 307 MECH RM 0145 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #2 LOOP 2 307 MECH RM 0146 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #2 LOOP 2 307 MECH RM 0147 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #2 LOOP 2 307 MECH RM 0148 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #1 LOOP 2 207 MECH RM 0149 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #1 LOOP 2 207 MECH RM 0150 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #1 LOOP 2 207 MECH RM 0151 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #1 LOOP 2 207 MECH RM 0152 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #1 LOOP 2 207 MECH RM 0153 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #2 LOOP 2 207 MECH RM 0154 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #2 LOOP 2 207 MECH RM 0155 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #2 LOOP 2 207 MECH RM 0156 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #2 LOOP 2 207 MECH RM 0157 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #2 LOOP 2 207 MECH RM 0158 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #3 LOOP 2 207 MECH RM 0159 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #3 LOOP 2 207 MECH RM 0160 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #3 LOOP 2 307 MECH RM 0161 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #3 LOOP 2 207 MECH RM 0162 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #3 LOOP 2 207 MECH RM 0163 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #4 LOOP 2 207 MECH RM 0164 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #4 LOOP 2 207 MECH RM 0165 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #4 LOOP 2 207 MECH RM 0166 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #4 LOOP 2 207 MECH RM 0167 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #4 LOOP 2 207 MECH RM 0168 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #5 LOOP 2 207 MECH RM 0169 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #5 LOOP 2 207 MECH RM 0170 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #5 LOOP 2 207 MECH RM 0171 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #5 LOOP 2 207 MECH RM 0172 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #5 LOOP 2 207 MECH RM 0173 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #3 LOOP 2 307 MECH RM 0174 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #3 LOOP 2 307 MECH RM 0175 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #3 LOOP 2 307 MECH RM 0176 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #3 LOOP 2 307 MECH RM 0177 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #3 LOOP 2 307 MECH RM 0178 (SIGA-CT1) MONITOR MODULE

CLASS A/B MODULE LOOP 2 210 LEVEL 2 FUTURE TENANT 0179 (SIGA-UM) CONTROL MODULE

CLASS A/B MODULE LOOP 2 211 LEVEL 2 FUTURE TENANT 0181 (SIGA-UM) CONTROL MODULE

CLASS A/B MODULE LOOP 2 310 LEVEL 3 FUTURE TENANT 0183 (SIGA-UM) CONTROL MODULE

CLASS A/B MODULE LOOP 2 311 LEVEL 3 FUTURE TENANT 0185 (SIGA-UM) CONTROL MODULE

BOOSTER PANEL #2 ACTIVATION LOOP 2 207 MECH RM 0187 CONTROL MODULE (SIGA-CC1S)

BOOSTER PANEL #3 ACTIVATION LOOP 2 307 MECH RM 0188 CONTROL MODULE (SIGA-CC1S)

ASFP PANEL FAULT #4 LOOP 2 307 MECH RM 0189 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #4 LOOP 2 307 MECH RM 0190 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #4 LOOP 2 307 MECH RM 0191 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #4 LOOP 2 307 MECH RM 0192 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #4 LOOP 2 307 MECH RM 0193 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #5 LOOP 2 307 MECH RM 0194 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ALERT #5 LOOP 2 307 MECH RM 0195 (SIGA-CT1) MONITOR MODULE

ASFP PANEL ACTION #5 LOOP 2 307 MECH RM 0196 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 1 #5 LOOP 2 307 MECH RM 0197 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FIRE 2 #5 LOOP 2 307 MECH RM 0198 (SIGA-CT1) MONITOR MODULE

REMICA SUPERVISION LOOP 2 200 LOBBY 0199 (SIGA-CT1) MONITOR MODULE

ASFP PANEL FAULT #6 LOOP 2 307 MECH RM 0200 (SIGA-CT2) MONITOR MODULE

ASFP PANEL ALERT #6 LOOP 2 307 MECH RM 0201 (SIGA-CT2) MONITOR MODULE

ASFP PANEL ACTION #6 LOOP 2 307 MECH RM 0202 (SIGA-CT2) MONITOR MODULE

ASFP PANEL FIRE 1 #6 LOOP 2 307 MECH RM 0203 (SIGA-CT2) MONITOR MODULE

ASFP PANEL FIRE 2 #6 LOOP 2 307 MECH RM 0204 (SIGA-CT1) MONITOR MODULE

CLASS A/B MODULE LOOP 2 319 SCIF SUITE CORRIDOR 0205 (SIGA-UM) CONTROL MODULE

24083F_ LOOP 2A

DEVICE TYPE LOOP# SENSOR MODULE LOCATION MODULE DESCRIPTION

SMOKE DETECTOR LOOP 2A 0251 217 OPEN OFFICE WK AREA

SMOKE DETECTOR LOOP 2A 0252 219 ELEC. ROOM

HEAT DETECTOR LOOP 2A 0253 219 ELEC. ROOM

SMOKE DETECTOR LOOP 2A 0254 219 CORRIDOR

SMOKE DETECTOR LOOP 2A 0255 220 COO OFFICE

SMOKE DETECTOR LOOP 2A 0256 219 CORRIDOR

SMOKE DETECTOR LOOP 2A 0257 223 SO OFFICE

SMOKE DETECTOR LOOP 2A 0258 222 CHAIR OFFICE

SMOKE DETECTOR LOOP 2A 0259 218 SEC CONF. ROOM

SMOKE DETECTOR LOOP 2A 0260 219 OIT OFFICE

SMOKE DETECTOR LOOP 2A 0261 217 OPEN OFFICE WK AREA

SMOKE DETECTOR LOOP 2A 0262 217 OPEN OFFICE WK AREA

SMOKE DETECTOR LOOP 2A 0263 216 SCIF WORKROOM

SMOKE DETECTOR LOOP 2A 0264 215 SCIF

SMOKE DETECTOR LOOP 2A 0265 213 NCUA CHAIRMAN

SMOKE DETECTOR LOOP 2A 0266 212 NCUA CONF. ROOM

SMOKE DETECTOR LOOP 2A 0267 212A NCUA OIT TELECOM

HEAT DETECTOR LOOP 2A 0268 212A NCUA OIT TELECOM

SMOKE DETECTOR LOOP 2A 0269 215A SCIF SERVER RM

HEAT DETECTOR LOOP 2A 0270 215A SCIF SERVER RM

DUCT SMOKE DETECTOR LOOP 2A 0271 214A SEC COOP TELECOM

DUCT SMOKE DETECTOR LOOP 2A 0272 214 VESTIBULE

SMOKE DETECTOR LOOP 2A 0273 217 OPEN OFFICE WK AREA

HEAT DETECTOR LOOP 2A 0274 214A SEC COOP TELECOM

CLASS "A" SIG MODULE LOOP 2A 0376 217 OPEN OFFICE WK AREA SIGA-UM

CLASS "A" SIG MODULE RTN LOOP 2A 0377 217 OPEN OFFICE WK AREA SIGA-UM

CLASS "A" SIG MODULE LOOP 2A 0378 303 TOILET RM SIGA-UM

CLASS "A" SIG MODULE RTN LOOP 2A 0379 304 TOILET RM SIGA-UM

CLASS "A" SIG MODULE LOOP 2A 0380 303 TOILET RM SIGA-UM

CLASS "A" SIG MODULE RTN LOOP 2A 0381 304 TOILET RM SIGA-UM

MONITOR MODULE LOOP 2A 0382 VESDA ZONE 2 PIPE 2 FIRE 2 SIGA-CT1

24083F_ REMOTE FACP

RCC7

CURRENT EA. CURRENT TOTAL

QTY PART NO. DESCRIPTION STBY ALRM STBY ALRM

1 3-CPU/PPS Main CPU #1 155.00 165.00 155.00 165.00

3-LCD Front Panel Display 40.00 42.00 0.00 0.00

1 3-RS232 COMM CARD 58.00 58.00 58.00 58.00

3-RS485 COMM BOARD 98.00 98.00 0.00 0.00

3-FIB FIBER COMM BOARD 217.00 217.00 0.00 0.00

SMXLO SINGLE MODE TRANSCEIVER 45.00 45.00 0.00 0.00

3-ASU/4 AUDIO/MIC PANEL 210.00 210.00 0.00 0.00

2 3-SSDC1 ADDRSSABLE LOOP MODULE 144.00 204.00 288.00 408.00

1 3-SDDC1 ADDRSSABLE DUAL LOOP MODULE 264.00 336.00 264.00 336.00

0 3-MODCOM Modem Communicator and Dialer 60.00 90.00 0.00 0.00

3-EVDVRA SWITCH DRIVER MODULE 22.00 22.00 0.00 0.00

3-ANN-CPU3 CPU-CARD ANNUNCATOR 144.00 144.00 0.00 0.00

3-REMICA Remote Microphone 52.00 52.00 0.00 0.00

3-ZA20 AMPLIFIER 20 WATT 35.00 1250.00 0.00 0.00

3-ZA40 AMPLIFIER 40 WATT 62.00 2480.00 0.00 0.00

3-ZA40 AMPLIFIER 40 WATT BACKUP 64.00 64.00 0.00 0.00

KDPISP KEYPAD 95.00 95.00 0.00 0.00

3-SAC SECURITY CONTROLLER 40.00 40.00 0.00 0.00

3-6Sxxx Front Panel Switchbank 20.00 20.00 0.00 0.00

3-12S1GY 12 Switch, 12 Grn, 12 Yel Ctrl Dis Mod 2.00 38.00 0.00 0.00

3-12S1RY 12 Switch, 12 Red, 12 Yel Ctrl Dis Mod 2.00 38.00 0.00 0.00

0.00 0.00 0.00 0.00

MN-COM1S Ethernet Device Server Network Interface 60.00 60.00 0.00 0.00

MN-FVPN VoIP Unit, audio encoder/decoder 89.00 89.00 0.00 0.00

MN-PASM Pre-AMP Supervison Module 100.00 100.00 0.00 0.00

MN-FNS4C2F3 CISCO Ethernet Network Switching Hub 350.00 350.00 0.00 0.00

BBC Booster Power Multiple Batteries 70.00 70.00 0.00 0.00

Bell NOTIFICATON CIRCUIT 0.00 85.00 0.00 85.00

Full Addressable Loop Load Using Highest Module Current

500 SIGA SENSORS Intelligent Smoke/Heat *** 0.05 0.05 22.50 22.50

500 SIGA MODULES Intelligent Universal Module *** 0.40 0.68 198.00 340.00

CURRENTS GIVEN IN MILLIAMPS

*** Calculations configured for full capacity of additional devices required per specs.

**calculations added for LOOP2A**

Enter Req'd TOTAL CURRENT 985.50 1414.50 by Number

24 Hours Total Standby Hours 23652 ma

15 Minutes Total Alarm Hours 353.625 ma

Battery Size Required 28.81 Amps

Battery Size Provided (Existing) 35AH

60 Minutes Alarm Total 1414.50 ma

Note: A twenty percent safety margin has been added to all of the final battery calculations per NFPA 72-2013 10.6.7.2.1 (1).

Addressable Device Loops have been configured for maximum loop loading of devices.

Bell

24083F_ Spkr Calcs

Amplifier Calcuations

SPKEAKER CKT LENGTH # DEV

TOTAL

WATTS

REQUIRED

(1/2W)

WATTS

AVAILABL

E

WATTS

USED

SPARE

CAPACITY Amplifier

S2 1000' 16 8

S2A 500' 3 1.5

S2B 150' 3 1.5

S2C 700' 5 2.5

S2D 350' 2 1

S2E 200' 1 0.5

S3 700' 15 7.5

S3A 350' 23 11.5

S3B 200' 5 2.5

S3C 200' 3 1.5

40 95.00% 5.00% AMP 2

24083F_ Spare Cap

ADDRESSABLE LOOPS SPARE CAPACITY

BLDG #401

ADDRESSABLE DEVICE LOOP #2

SENSORS

USED 94.40% 118 Total Devices Used

SPARE 5.60% 7 Spare Sensor Addresses

MODULES

USED 64.80% 81 Total Modules Used

SPARE 35.20% 44 Spare Module Addresses

Total Loop Capacity

USED 79.60% 199 Total Addresses Used

SPARE 20.40% 51 Total Spare Addresses

ADDRESSABLE DEVICE LOOP #2A

SENSORS

USED 18.40% 23 Total Devices Used

SPARE 81.60% 102 Spare Sensor Addresses

MODULES

USED 5.60% 7 Total Modules Used

SPARE 94.40% 118 Spare Module Addresses

Total Loop Capacity

USED 12.00% 30 Total Addresses Used

SPARE 88.00% 220 Total Spare Addresses

VOLTAGE DROP CALCULATIONS - WORST CASE

Signal Ckt # Current Distance EOL Voltage

3 0.609 338' 22.93

4 0.602 293' 23.08

Notes:

1. Voltage drop calculations are based on a 24VDC input.

2. Actual Voltage drops will reflect a higher reading than shown.

3. Field tests will verify proper voltage and operation of circuits.

4. Calculations based on using wire resistance of 3.07 ohms per conductor or total of 6.4 ohms per 1000 ft.

24083F_ SigBatCalcsA

Signal Panel #2 Ckt# 3 4 3 4

G4VRF LED Genesis Wall Strobe, 15-110cd, Red, FIRE 0.028 3 1 0.084 0.028

GCVWF LED Genesis Ceiling Strobe, 15-115cd, White, FIRE 0.035 3 0.000 0.105

G4SVRF LED Genesis Wall Speaker/Strobe, 15-110cd, Red, FIRE 0.028 3 0.000 0.084

GCSVWF LED Genesis Ceiling Speaker/Strobe, 15-115cd, White, FIRE 0.035 15 11 0.525 0.385

INDIVIDUAL CIRCUIT TOTALS: 0.609 0.602

**NOTE** Changes made to Ckt#3 for this scope**

Standby Time (Hrs) 24 Standby Current 0.070 Battery Required 2.1 AH

Alarm Time (Min) 15 Alarm Current 1.481 Battery Provided 7.2 AH

MOUNT WEATHER BLDG 401

19844 BLUE RIDGE MOUNTAIN RD

BLUMOUNT, VA 20135

METALLIC CONDUIT 12" MIN.

SCHEDULE 80 PVC PIPE/FITTINGS

NOTES:

1. WHERE CONDUIT DOES NOT COMPLETELY FILL THE WALL OPENING, SEAL PENETRATION WITH

ACOUSTICAL JOINT SEALANT CAULKING.

2. DETAIL APPLIES TO ALL METALLIC CONDUIT ENTERING A SCIF SPACE.

METALLIC CONDUIT

SPECIAL WALL PARTITION

6" MAX

ATTACK SIDESECURE SIDE

PACKAGING AND SEALANT FOR FIRE RATED CONSTRUCTION WHERE

APPLICABLE - WHERE NO FIRESTOPPING IS REQUIRED PACK SOLID

WITH HIGH STRENGTH GROUT - SEAL WITH ACOUSTICAL CAULKING

EXTEND GROUND WIRE TO BUILDING

STRUCTURAL STEEL OR NEAREST GROUND BAR

(NOT LOCATED WITHIN AN ELECTRICAL PANEL).

PIPE CLAMP WITH GROUND WIRE

3. SIZE CONDUIT IN ACCORDANCE WITH NEC 760.

RISER OUT (+)

RISER OUT (-)

DATA IN (-)

DATA IN (+) DATA OUT (-)

DATA OUT (+)

24VDC TO ANNUNCIATORS

TO MAIN FACP

RS-485 NETWORK

INPUT 2

G N

D +24V

EG

N D

107654 98 A+G

N D

+24V

B-B+A-

R

EM

O

TE AN

N U

N . (C

PU

3-AN

N

C

PU

D

ISPLAY SU

PPO

R

T M O

D U

LE

3-AN

N

SM

FILLER

PLATE

3-FP

OUTPUT INPUT 1

BATTERY

3-BPS

AUX POWER

3.5A EACH

+ +TB1

P4 CONNECTS TO 3-PPS

3-BPSMON

P6 CONNECTS TO 3-PPS

VIA P3 DATA CABLE

VIA P2 POWER CABLE

ON BACK

3-BPS/MON

AUX POWER

3.5A EACH

BATTERY

TB1 +-

P4 CONNECTS TO 3-PPS

P6 CONNECTS TO 3-PPS

VIA P3 DATA CABLE

VIA P2 POWER CABLE

ON BACK

3-PSMON

H N G

3-PPS

3-PS/MON

3-ZA40B

BACK-UP NAC/BBACK-UP

S

TB2

NAC/B

S

FOR 70 VDC

SET JP-1 & JP-2

TO TC#1

Ditek

DTK-120HW

SET JP-1 & JP-2SET JP-1 & JP-2

FOR 70 VDC FOR 70 VDC

AMP 3 AMP 4AMP 2

BATTERY CABINET - BC-1

65ah BATTERY

BATTERY CABINET - BC-1

65ah BATTERY

3-ZA40B

BACK-UP NAC/B

S

BACK-UP

TB2

NAC/B

SS

NAC/A

S S

NAC/A

S

FROM TC#1

TO TC#1

FROM TC#1

MN-FNS4C2F3

SI

G

A- M

C C

2A

SI

G

A- U

IO

6R

SI

G

A- M

C C

2A

SI

G

A- M

C C

2A

SI

G

A- M

C C

2A

SI

G

A- M

C C

2A

3-ZA40B

BACK-UP NAC/B

S

TB2

BACK-UP NAC/B

S

UNUSED

SET JP-1 & JP-2

FOR 70 VDC

AMP 4

BACKUP

TO TC#1

FROM TC#1

3-ZA40B

BACK-UP NAC/B

S

TB2

BACK-UP NAC/B

S

UNUSED

SET JP-1 & JP-2

FOR 70 VDC

AMP 1

TO TC#1

FROM TC#1

3-ZA20B

BACK-UP NAC/B

S

TB2

BACK-UP NAC/B

S

UNUSED

SI

G

A- M

C C

2A

SI

G

A- U

IO

2R

SI

G

A- M

C C

2A

SP

AR

E

LRMF

LRMF

LRMF

LRMF

LOOP 3

AUX POWER

3.5A EACH

BATTERY

TB1 +-

P4 CONNECTS TO 3-PPS

P6 CONNECTS TO 3-PPS

VIA P3 DATA CABLE

VIA P2 POWER CABLE

ON BACK

3-PSMON

H N G

3-PPS

3-PS/MON

3-SSDC1 3-SDDC2

Ditek

DTK-120HW

LOOP 2LOOP 1

B

SUPPLY

LOOP 2

LOOP 2

RETURN

LOOP 1

B

SUPPLY

LOOP 1

RETURN

LOOP 3

SUPPLY

RETURN

BATTERY CABINET - BC-1

35ah BATTERY35ah BATTERY

3-SSDC1

LOOP 3

B

LRMF

LOOP 2A

SUPPLY

LOOP 2A

LOOP 2A

RETURN

converg nt

3650 CONCORDE PARKWAY SUITE-100

CHANTILLY, VA. 20150

CTC 443

OFFICE: (703) 631-7476 - FAX: (703) 330-0086

WWW.CONVERGINT.COM

This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request.

This document cannot be reproduced by any means without the written authorization of Convergint Technologies LLC.

19844 BLUE RIDGE MOUNTAIN RD

BLUMOUNT, VA 20135

converg nt

3650 CONCORDE PARKWAY SUITE-100

CHANTILLY, VA. 20150

CTC 443

OFFICE: (703) 631-7476 - FAX: (703) 330-0086

WWW.CONVERGINT.COM

This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request.

19844 BLUE RIDGE MOUNTAIN RD

BLUMOUNT, VA 20135

MANUAL FIRE ALARM BOX

DUCT-TYPE SMOKE DETECTOR LOCATED IN SUPPLY DUCT OF AHU

SPOT-TYPE SMOKE DETECTOR - IN LEVELS 1,2, 4, AND 5 ELEVATOR LOBBIES

SPOT-TYPE SMOKE DETECTOR - LEVEL 3 ELEVATOR LOBBY

WET PIPE SPRINKLER WATERFLOW SWITCH

SPRINKLER VALVE TAMPER SWITCH

MASS NOTIFICATION ACTIVATION

FIRE ALARM NETWORK COMMUNICATION FAILURE

FARA MICROPHONE ACTIVATED

FIRE ALARM CONTROL UNIT TROUBLE

SYSTEM INPUTS

X

X

X X

X X

X X

X X

X X X X X

XX

X X

X X X

XX

DI

SP

LA

Y

AL

PH

AN

UM

ER

IC

M

ES

SA

GE

O N

FA

CU

A

ND

A

NN

UN

CI

AT

OR

S

A B C D E F G H I J K L M N O P Q R S

AC

TU

AT

E

CO

MM

ON

A

UD

IB

LE

/V

IS

IB

LE

A

LA

RM

IN

DI

CA

TO

RS

O

N

FA

CU

A

ND

A

NN

UN

CI

AT

OR

S

AC

TU

AT

E

CO

MM

ON

A

UD

IB

LE

/V

IS

IB

LE

S

UP

ER

VI

SO

RY

IN

DI

CA

TO

RS

O N

FA

CU

A

ND

A

NN

UN

CI

AT

OR

S

AC

TU

AT

E

CO

MM

ON

A

UD

IB

LE

/V

IS

IB

LE

T

RO

UB

LE

IN

DI

CA

TO

RS

O

N

FA

CU

A

ND

A

NN

UN

CI

AT

OR

S

TR

AN

SM

IT

A

LA

RM

S

IG

NA

L T O

CE

NT

RA

L M

ON

IT

OR

IN

G

ST

AT

IO

N

TR

AN

SM

IT

S

UP

ER

VI

SO

RY

S

IG

NA

L T O

CE

NT

RA

L M

ON

IT

OR

IN

G

ST

AT

IO

N

TR

AN

SM

IT

T

RO

UB

LE

S

IG

NA

L T O

CE

NT

RA

L M

ON

IT

OR

IN

G

ST

AT

IO

N

AC

TI

VA

TE

R

EC

OR

DE

D

FI

RE

A

LA

RM

M

ES

SA

GE

AC

TI

VA

TE

S

TR

OB

ES

AC

TI

VA

TE

A

PP

LIC

AB

LE

R

EC

OR

DE

D

MA

SS

N

OT

IF

IC

AT

IO

N

ME

SS

AG

E

OV

ER

RI

DE

R

EC

OR

DE

D

FI

RE

A

LA

RM

M

ES

SA

GE

OV

ER

RI

DE

R

EC

OR

DE

D

MA

SS

N

OT

IF

IC

AT

IO

N

ME

SS

AG

E

NO

T

US

ED

SE

ND

S

IG

NA

L T

O

BA

S

TO

S

TO

P

FA

N

OF

A

SS

OC

IA

TE

D

AH

U

SE

ND

M

UT

E

SI

GN

AL

T O

PA

S

YS

TE

M

CONTROL UNIT

ANNUNCIATION NOTIFICATION CONTROL

SYSTEM OUTPUTS

INPUT/OUTPUT MATRIX

AC

TI

VA

TE

N

ET

W

OR

K

CO

MM

UN

IC

AT

IO

N

LO

SS

E

RR

OR

M

ES

SA

GE

W

IT

H

PA

NE

L A

DD

RE

SS

T O

AL

L N

ET

W

OR

KE

D

PA

NE

LS

AC

TI

VA

TE

A

LA

RM

M

ES

SA

GE

A

T

CE

NT

RA

L M

ON

IT

OR

IN

G

ST

AT

IO

N

NE

TW

OR

K

PA

NE

L W

IT

H

AD

DR

ES

S

OF

D

EV

IC

E

AC

TI

VA

TE

S

UP

ER

VI

SO

RY

M

ES

SA

GE

A T

CE

NT

RA

L M

ON

IT

OR

IN

G

ST

AT

IO

N

NE

TW

OR

K

PA

NE

L W

IT

H

AD

DR

ES

S

OF

D

EV

IC

E

AC

TI

VA

TE

T

RO

UB

LE

M

ES

SA

GE

A

T

CE

NT

RA

L M

ON

IT

OR

IN

G

ST

AT

IO

N

NE

TW

OR

K

PA

NE

L W

IT

H

AD

DR

ES

S

OF

D

EV

IC

E

X X X X X

RE

CA

LL

E

LE

VA

TO

R

TO

P

RI

MA

RY

LE

VE

L (

LE

VE

L 3

RE

CA

LL

E

LE

VA

TO

R

TO

S

EC

ON

DA

RY

LE

VE

L (

LE

VE

L 2

IN

IT

IA

TE

E

LE

VA

TO

R

PO

W

ER

S

HU

NT

T

RI

P

T U V X

X X

X X

X X

X X

X X

X X

X X

X X

X

X

DUCT-TYPE SMOKE DETECTOR LOCATED AT CONNECTION FROM RETURN AIR PLENUM TO AIR SYSTEM X X X X X X X

X X X

X

SPOT-TYPE SMOKE DETECTOR - IN ELEVATOR HOISTWAY X X X X X X XX X

HEAT DETECTOR X X X X X X XX

NO

T

US

ED

W X

X X XX X

NO

T

US

ED

ASPIRATING SMOKE DETECTION PANEL: POWER SUPPLY TROUBLE

ASPIRATING SMOKE DETECTION PANEL: DETECTION PANEL TROUBLE

ASPIRATING SMOKE DETECTION PANEL: ALERT

ASPIRATING SMOKE DETECTION PANEL: ALARM

X X X X X

X X

X X

X X X

X X X

X X X

X X X

X X X

X X X

X X X

X X

AED CABINET OPEN X X X X

HIGH WATER LEVEL IN ELEVATOR SUMP X X X X

HEAT DETECTOR - ELEVATOR CONTROL CLOSET XX X X X X X X

FACU MICROPHONE ACTIVATED

X XX

FAS SHALL BE GE EDWARDS EST3 TO MATCH SITE STANDARD. THE CONTRACTOR IS

RESPONSIBLE FOR COORDINATION OF SYSTEM REQUIREMENTS WITH ALL CONDITIONS OF

THE BUILDING AND SITE INCLUDING, BUT NOT LIMITED TO, BLIND SPACES, SHELVING, LIGHTS, GRILLES AND DIFFUSERS, PIPING, DUCT WORK, DOORS, WINDOWS, EQUIPMENT PLATFORMS, WALLS (FIRE RATED AND NON-FIRE-RATED), BEAMS, JOISTS, COLUMNS, HVAC EQUIPMENT, ELECTRICAL PANELS AND EQUIPMENT, CEILINGS, AREAS WITHOUT CEILINGS, WALL

CONSTRUCTION, FLOORS AND ALL CONSTRUCTION, EQUIPMENT AND BUILDING

APPURTENANCES.

A.C. POWER CONDUCTORS SUPPLYING POWER TO THE FACU, SUBPANELS, POWER

EXTENDERS, ETC. SHALL BE LABELED, MECHANICALLY SECURED, AND RED-MARKED IN

ACCORDANCE WITH NFPA 72. A MACHINE-PRODUCED LABEL SHALL BE PROVIDED INSIDE THE

DOOR OF EACH ENCLOSURE INDICATING THE LOCATION OF THE CIRCUIT DISCONNECTING

MEANS (PANEL LOCATION, PANEL IDENTIFICATION, AND CIRCUIT IDENTIFICATION).

COORDINATE THE LOCATION AND QUANTITY OF DEDICATED A.C. POWER CIRCUITS WITH THE

ELECTRICAL CONTRACTOR.

CUSTOMIZED AUDIO MESSAGES PROVIDED BY THE OWNER, GIVEN SUFFICIENT TIME TO

HAVE THE MESSAGES RECORDED, SHALL BE INCORPORATED INTO THE SYSTEM; MEMORY

CAPACITY OF FACU SHALL BE UPGRADED AS NECESSARY. FACU SHALL ALSO ACCEPT AND

BE CAPABLE OF BROADCASTING MASS NOTIFICATION MESSAGES RECEIVED FROM CENTRAL

MONITORING SITES. FAS INSTALLER SHALL UPDATE TWO FIREWORKS STATIONS AND MAIN

PANELS WITH GRAPHICS AND MASS NOTIFICATION OUTPUT CHANNELS FOR SERVICE TO THE

BUILDING. FIRE ALARM EVACUATION SIGNAL INTELLIGIBILITY SHALL BE TESTED UTILIZING A

METHOD(S) DESCRIBED IN NFPA 72; FAS INSTALLER SHALL ELIMINATE ALL FEEDBACK ON

AUDIO LOOP BETWEEN MICROPHONE AND SPEAKER CIRCUITS.

WITH RESPECT TO BOTH VISUAL COVERAGE AND AUDIBLE SIGNAL INTELLIGIBILITY, THE

LOCATION AND QUANTITY OF NOTIFICATION DEVICES INDICATED ON THE FIRE PROTECTION

DESIGN DRAWINGS ARE FOR SCHEMATIC / BIDDING PURPOSES ONLY. THE CONTRACTOR

SHALL BE RESPONSIBLE FOR ENSURING ADEQUATE COVERAGE, REGARDLESS IF

ADDITIONAL DEVICES ARE NECESSARY.

END-OF-LINE DEVICES ARE NOT SHOWN AND SHALL BE PROVIDED AS REQUIRED BY THE

SYSTEM MANUFACTURER.

1.

2.

3.

4.

5.

IN ACCORDANCE WITH THE DRAWINGS, SPECIFICATIONS, AND APPLICABLE CODES AND

STANDARDS. FLOW AND TAMPER SWITCHES SHALL BE DISCRETE POINTS; PARALLELING

INPUTS INTO ADDRESSABLE MODULES IS PROHIBITED.

THE FAS SHALL BE INTEGRATED INTO THE SITEWIDE NETWORK AND FIRE ALARM SIGNALS

SHALL BE AUTOMATICALLY TRANSMITTED TO THE SITE CENTRAL MONITORING STATION.

FIBER OPTIC CABLE WILL BE MADE AVAILABLE TO THE FACU BY THE TELECOM CONTRACTOR.

PROVIDE THE FOLLOWING CONNECTIONS INTO THE FACU:

2 PAIRS SINGLE MODE FIBER NETWORK "IN"

2 PAIRS SINGLE MODE FIBER NETWORK "OUT"

ALL INITIATING DEVICES SHALL BE INTELLIGENT / ADDRESSABLE WHERE POSSIBLE.

SEPARATE ADDRESSABLE MONITOR MODULES SHALL BE PROVIDED FOR EACH

CONVENTIONAL INPUT DEVICE SUCH THAT EACH DEVICE IS INDIVIDUALLY INDICATED AT THE

FACU AS A DISTINCT INPUT. ALL INITIATING DEVICES SHALL BE INSTALLED IN ACCORDANCE

WITH MANUFACTURERS INSTRUCTIONS.

THE PATHWAY PERFORMANCE SHALL COMPLY WITH THE NFPA 72 REQUIREMENTS FOR THE

FOLLOWING:

9.1. SIGNALING LINE CIRCUITS (SLC) SHALL BE CLASS A STRANDED COPPER

9.2. NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE CLASS A STRANDED

COPPER

9.3. CIRCUIT SURVIVABILITY SHALL MEET LEVEL 1

9.4. A SINGLE FAULTY DEVICE SHALL NOT COMPROMISE AN ENTIRE LOOP

7.

8.

9.

ALL WIRES SHALL BE CHECKED FOR GROUNDS, SHORTS, OPENS, AND CORRECT RESISTANCE,

CAPACITANCE, AND OTHER APPLICABLE PARAMETERS PRIOR TO TERMINATION OF THE

CIRCUITS AT THE FACU OR SUBPANELS AND PRIOR TO THE INSTALLATION OF DEVICES.

ALL WIRING SHALL BE IN METALLIC CONDUIT. ALL CONDUIT SHALL BE PAINTED RED, 3/4-IN.

MINIMUM. IDENTIFY ALL CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS. ALL FIRE

ALARM JUNCTION BOXES AND COVERS SHALL BE PAINTED RED IN UNFINISHED AREAS.

PULL ALL CONDUCTORS SPLICE FREE; T-TAPS ARE PROHIBITED. THE USE OF WIRE NUTS,

CRIMPED CONNECTORS, OR TWISTING OF CONDUCTORS IS PROHIBITED. ALL TERMINATIONS

MUST BE AT A TERMINAL STRIP WITHIN A FIRE ALARM TERMINAL CABINET OR DEVICE SCREW

TERMINAL. RUN ALL WIRING TO CONTROL PANELS AND OTHER CABINETS IN THE VERTICAL OR

HORIZONTAL PLANE, MAKE ALL TURNS AT 90-DEGREE ANGLES, AND TIGHTLY BUNDLE AND

WRAP ALL WIRE. ALL WIRING MUST BE SOLID COPPER, EXCEPT FOR SPEAKER CIRCUITS OR

CIRCUITS REQUIRING SHIELDING. ALL SLC AND IDC SHALL BE MINIMUM 16-GAUGE. UNDER NO

CIRCUMSTANCES SHALL CONDUCTORS BE SIZED SMALLER THAN THE MANUFACTURERS'

REQUIREMENTS.

ALL FIRE ALARM VISUAL NOTIFICATION APPLIANCES (STROBES) SHALL BE SYNCHRONIZED ON A

MINIMUM PER-FLOOR BASIS. ALL FIRE ALARM VISUAL NOTIFICATION APPLIANCES SHALL BE

MARKED "ALERT" AND SHALL BE PROVIDED WITH CLEAR LENSES. NOTIFICATION APPLIANCES

INSTALLED IN ACOUSTIC TILE CEILINGS SHALL BE CENTERED IN THE TILES.

OTHERWISE.

FIRE ALARM SYSTEM INPUT (MONITORING) AND OUTPUT (CONTROL) MODULES SHALL BE

LOCATED WITHIN 3 FT. OF THE MONITORED / CONTROLLED EQUIPMENT WHERE POSSIBLE.

COORDINATE THE LOCATION OF CEILING MOUNTED SMOKE AND HEAT DETECTORS WITH HVAC

DIFFUSERS AND LIGHTING FIXTURES. SUSPENDED CEILING-MOUNTED DETECTORS SHALL BE

CENTERED IN THE TILE.

ALL SYSTEM SMOKE DETECTORS SHALL BE PROTECTED BY DUST COVERS UP UNTIL THE TIME

OF FINAL ACCEPTANCE TESTING.

10.

11.

12.

13.

14.

15.

16.

17.

MANUAL PULL STATIONS SHALL BE FLUSH-MOUNTED IN FINISHED AREAS AND SURFACE-MOUNTED

LOCATE THE FAS NAC POWER SUPPLIES AS NEEDED, COORDINATE THE AC POWER FOR THE

NAC POWER SUPPLIES WITH THE ELECTRICAL CONTRACTOR.

PROVIDE MONITORED TAMPER SWITCH FOR FIRE ALARM CONTROL UNIT.

SUPERVISION SHALL BE PROVIDED FOR THE SPRINKLER SYSTEM POST INDICATING VALVE

(PIV); SEE CIVIL DRAWING C1.30 FOR PIV LOCATION.

A TOTAL (COMPLETE) COVERAGE SMOKE DETECTION SYSTEM, IN ACCORDANCE WITH NFPA 72,

SHALL BE INSTALLED THROUGHOUT THE BUILDING.

FIRE ALARM SYSTEM SHALL PROVIDE NOTIFICATION SIGNAL TO BAS IN THE EVENT OF ANY

GENERAL BUILDING ALARM CONDITION AND BAS SHALL INITIATE AS REQUIRED VENTILATION

AND AHU SYSTEM SHUT DOWN OPERATIONS. UPON CLEARING OF FIRE ALARMSIGNAL THE BAS

SHALL RETURN TO NORMAL OPERATIONS WITHOUT OPERATOR INTERVENTION.THE BAS

CONTROL PANEL IS LOCATED IN MECHANICAL ROOM 107 ON LEVEL 1.

ISOLATION MODULES SHALL BE PROVIDED AT PENETRATIONS INTO SECURE AREAS AND

TENANT SPACES BOUNDED BY SPECIAL WALLS. SPEAKER CIRCUITS SERVING SECURE AREAS

AND TENANT SPACES SHALL BE CLASS A ORIGINATING FROM THE MODULE AND SHALL BE

CONFINED TO THE AREA WHICH THEY SERVE.

PROVIDE Z-BENDS AT ALL AIR SAMPLING PIPE PENETRATION POINTS INTOSECURE AREAS AND

TENANT SPACES BOUNDED BY SPECIAL WALLS. AIR SAMPLING PIPE NETWORKS SHALL BE

CONFINED TO THE AREA WHICH THEY SERVE.

ALL PENETRATIONS INTO SECURE AREAS AND TENANT SPACES BOUNDED BY SPECIAL WALLS

SHALL BE LIMITED TO THE LOCATIONS IDENTIFIED ON THE DRAWINGS. REFER TO

ARCHITECTURAL DRAWING A0.10 FOR SPECIAL WALL LOCATIONS. CIRCUITS AND PIPING SHALL

NOT BE ROUTED INTO OR THROUGH SECURE AREAS AND TENANT SPACES WHICH THEY DO

NOT SERVE.

18.

19.

20.

21.

22.

23.

24.

25.

converg nt

3650 CONCORDE PARKWAY SUITE-100

CHANTILLY, VA. 20150

CTC 443

OFFICE: (703) 631-7476 - FAX: (703) 330-0086

WWW.CONVERGINT.COM

This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request.

19844 BLUE RIDGE MOUNTAIN RD

BLUMOUNT, VA 20135

SECURE SIDE NON-SECURE SIDE

SPECIAL WALL PARTITION

0'-6" MAX

NOTES:

1. WHERE PIPE SLEEVES ARE USED, COMPLETELY PACK VOID AREAS BETWEEN PIPE AND SLEEVE WITH MINERAL WOOL INSULATION AND SEAL PENETRATION WITH ACOUSTICAL JOINT SEALANT CAULKING.

2. WHERE PIPE DOES NOT COMPLETELY FILL THE WALL OPENING, SEAL PENETRATION WITH ACOUSTICAL

JOINT SEALANT CAULKING.

3. Z-BEND MAY BE INSTALLED VERTICAL OR HORIZONTAL.

4. DETAIL APPLIES TO ALL AIR ASPIRATING SMOKE DETECTOR SAMPLING PIPING ENTERING A SCIF SPACE.

0' -6

" M

AX

PACKING AND SEALANT FOR FIRE RATED CONSTRUCTION WHERE

APPLICABLE - WHERE NO FIRESTOPPING IS REQUIRED PACK SOLID WITH

MINERAL WOOL INSULATION AND SEAL WITH ACOUSTICAL CAULKING

SPECIAL WALL AIR SAMPLING PIPE

Z-BEND DETAIL

VESDA AIR SAMPLING NOTES:

ILLUMINATE BAROGRAPH AND ALERT LED AT VESDA DETECTOR.

A PRE-ALARM CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.

ACTIVATION OF A VESDA ALERT CONDITION SHALL CAUSE:

A TROUBLE SIGNAL SENT TO BUILDING F.A.C.P.

ILLUMINATE BAROGRAPH AND ACTION LED AT VESDA DETECTOR.

ACTIVATION OF A VESDA ACTION CONDITION SHALL CAUSE:

ACTIVATION OF A VESDA FIRE 2 CONDITION SHALL CAUSE:

ILLUMINATE BAROGRAPH AND FIRE 2 LAMP AT VESDA DETECTOR. AN ALARM CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.

ENERGIZE PRE-ACTION SOLENOID.

A PRE-ALARM CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.

ACTIVATION OF A VESDA FIRE 1 CONDITION SHALL CAUSE:

ILLUMINATE BAROGRAPH AND FIRE 1 LAMP AT VESDA DETECTOR.

AN ALARM CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.AN ALARM SIGNAL SENT TO BUILDING F.A.C.P.

A TROUBLE SIGNAL SENT TO BUILDING F.A.C.P.

AN ALARM SIGNAL SENT TO BUILDING F.A.C.P.

HVAC SHUTDOWN AND DAMPER CLOSURE.

SEQUENCE OF OPERATIONS

THIS SEQUENCE SHALL BE POSTED AT THE CONTROL PANEL.

A TROUBLE CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.

ACTIVATION OF A VESDA FAULT CONDITION SHALL CAUSE:

A TROUBLE SIGNAL SENT TO BUILDING F.A.C.P.

FAULT CONDITION DISPLAYED AT THE VESDA DETECTOR.

ACTIVATION OF A VESDA ALERT CONDITION SHALL CAUSE:

ACTIVATION OF A VESDA ACTION CONDITION SHALL CAUSE:

ACTIVATION OF A VESDA FIRE 2 CONDITION SHALL CAUSE:

ACTIVATION OF A VESDA FIRE 1 CONDITION SHALL CAUSE:

SEQUENCE OF OPERATIONS

ACTIVATION OF A VESDA FAULT CONDITION SHALL CAUSE:

POWER SUPPLY VPS-300US 120

L N G

To 120VAC/60HZ

VPS-300US 120 - POWER SUPPLY

TRANSFORMER

120 VAC

28 VAC

FAULT INDICATOR

BAT +

D C

O U

TPU

TS

L1

L2

VR1

VR2

RL1

C1

C2

C4 C3

-O ut1+

-O ut2+

-O ut3+

FAULT MONITORING

NCNO C

12 Volt/ 12 AMP-HR 12 Volt/ 12 AMP-HR

12 Volt/ 12 AMP-HR 12 Volt/ 12 AMP-HR

12 Volt/ 12 AMP-HR 12 Volt/ 12 AMP-HR

THREE DETECTORS

VBC-001

1ST FLOOR INSTALL (0)

2ND FLOOR INSTALL (1)

3RD FLOOR INSTALL (1)

4TH FLOOR INSTALL (1)

converg nt

3650 CONCORDE PARKWAY SUITE-100

CHANTILLY, VA. 20150

CTC 443

OFFICE: (703) 631-7476 - FAX: (703) 330-0086

WWW.CONVERGINT.COM

This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request.

Reviewed By: Zach Holder
Submitted By: Zach Holder Submittal Date: 8/20/2024 Due Date: 9/3/2024
2024-08-27T12:46:50-0400
MICHAEL L MCPEAK

File details come from the government source that posted it. Updated .