283113.003.01 - Digital Addressable Fire-Alarm System - SD - AAN 2nd Floor Buildout.pdf
PDF 4 MB Posted
- Attached to
- B401 Tenant Buildout
- Solicitation number
- 70FA5026Q00000002
About this file
This document is a comprehensive fire alarm system submittal for the FEMA Building 401 2nd Floor Tenant located at 19844 Blue Ridge Mountain Road in Bluemont, VA. The submittal, prepared by Convergint for The Christman Company, details the installation of a digital, addressable fire alarm system using an existing Edwards EST-3 Fire Alarm Control Panel. The system will be installed for Tenant 5A & 5B and includes 24 total smoke detectors, 4 heat detectors, multiple signal modules, notification appliances, and a VESDA air sampling detection system.
The submittal includes detailed technical specifications, device calculations, battery sizing, speaker circuit plans, and spare capacity analysis. Key system features include Class A signaling and notification circuits, voice evacuation capabilities, network connectivity to a central monitoring station, and 5-year warranty coverage. The project involves adding a second loop card to the existing fire alarm panel, implementing underfloor VESDA detection, and ensuring comprehensive coverage across the building's second floor, including various office spaces, corridors, mechanical rooms, and future tenant areas.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
283113.003.01 FEMA Project FEMA Bldg. 401 - 70FA5020C00000008
TCC Job No. 220867 A/E Mason & Hanger
To Michael McPeak From The Christman Company
Submitting Contractor TEI
Specification Division 28 - Electronic Safety and Security
FOR APPROVAL
Submittal 283113.003.01 – Digital, Addressable Fire-Alarm System -
Tenant 5A & 5B
Notes Specifications Included This submittal includes shop drawings for digital, addressable fire-alarm system added in this fit-out.
283113 – 1.7C
☒ Shop Drawings ☐ Sample ☐ Preconstruction Documentation ☐ Test Reports ☐ Qualification Data ☐ Delegated Design ☐ Product Data ☐ Owner’s Manual Data ☐ Certificates ☐ Warranty
☒ Specified Item ☒ No Exceptions Taken ☐ Substitute Item ☐ Make Corrections Noted ☐ FIO ☐ Revise and Resubmit
☐ Rejected as Noted
Reviewed for general conformance with the technical specifications and the drawings. Any information shown herein is subject to the requirements of the plans and specifications. All dimensions to be verified in field by the subcontractor. Any approval does not negate the requirement to follow Contract Documents.
Reviewed By: Zach Holder Submitted By: Zach Holder Submittal Date:
8/20/2024 Due Date: 9/3/2024 mmcpeak
APPROVED EXCEPT AS NOTED
mmcpeak Typewritten Text
1. Reference Drawing F2 & F4: There should be a total of seven (7) VESDA (ASPF) zones on Level 2. Coordinate zone designations accordingly.
Ph : 301-874-4630
4840 Winchester Blvd, Suite 1
Frederick, MD 21703
D ate: 8/14/2024
Job: 5117-004-01 Mt. Weather Bldg 401
Letter of Transmittal
Transmittal #: 73To: Austin White
The Christman Company
22560 Glenn Drive
Suite 108
Sterling, VA 20164
Ph: (858)699-7345 Fax: 703-740-5646
Subject: Submittal
Samples
Change order
Shop drawings
Under separate cover via the following items:AttachedWE ARE SENDING YOU
Submittal
Prints Plans
Copy of letter Specifications
DescriptionNo.DateCopiesDocument Type
1 8/14/24 283113-3 Rev 1 FIRE ALARM SYSTEM - 2ND FL WEST FITOUTSubmittal
Other
PRINTS RETURNED AFTER LOAN TO USFOR BIDS DUE
For review and comment
Return ___ corrected printsReturned for corrections
Submit ___ copies for distributionApproved as noted
For approval Resubmit ___ copies for approvalApproved as submitted
THESE ARE TRANSMITTED as checked below:
Remarks:
For your use
As requested
Copy To:
Signature:From: Denise Strasser (TEI Electrical Solutions)
If enclosures are not as noted, kindly notify us at once. Page 1 of 1
Ph : 301-874-4630
4840 Winchester Blvd, Suite 1
Frederick, MD 21703
Job:
Mt. Weather Bldg 401
Spec Section No:
19844 Blue Ridge Mountain Road
Bldg 401
Submittal No:
283113
Sent Date:
Revision No: 1
Submittal
8/14/2024
5117-004-01
Bluemont, VA 20135
Spec Section Title: DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM/MASS NOTIFICATION SYSTEM
Submittal Title: FIRE ALARM SYSTEM - 2ND FL WEST FITOUT
Contractor's Stamp
Architect's Stamp
Engineer's Stamp
Craig Dixon
Contractor:
General Contractor:
The Christman Company
Austin White
Tissa Enterprises, Inc. dba TEI Electrical Solutions
Fire Alarm Submittal Action Plan
MT. WEATHER BLDG 401 2FL TENANT Project Type:FIRE ALARM System Type: EDWARDS
RENOVATION EST-3
Review Date
Reviewer Review
Comment Status Resolution Follow-up/Final Verification & Date
Review Date
8/8/2024 ZH 1 PG. 20, ROOM 214A SEC COOP TELECOM, Add heat detector as required to provide coverage to match all other Telecom Rooms.
Heat detector not shown in room 214A. Heat detector added to room 214A.
8/8/2024 ZH 2 PG 22, ROOM 214A SEC COOP TELECOM, VESDA
drawing does not show end cap sample port.
Xtralis Pipe Cad drawings does show end cap. VESDA end cap not shown in room 214A. End cap added to room 214A.
8/8/2024 ZH 3
PG 20, Need to correct VESDA Zone numbers.
Zone 2 is duplicated. Should be 7 zones total.
Zone 2 shown as a duplicate on page 20.
Per contract drawings the Zones were reconfigured from the original installation documents. Zone 2 was enlarged and Zone 1 was made smaller, there is still a total of 5 zones on Level 2.
Sincerely
Richard Salmon Systems Designer III
NICET IV 87901
In an effort to prevent any delays in construction, Any coordination issues involving final location of devices shall be included and provided to owner on as-built documents at close of project. The actual location of the devices shall not produce any significant changes to system design and operation.
If you have any questions regarding any portion of this response, please contact me at 703 631-7476 or at rich.salmon@convergint.com
Eng. Comments Responses_08-14-24_rs.xlsx VIERRA Submittal Action Plan 1
REV#1
24083F
7/15/2024
RS
Richard Salmon
Nicet Level IV
Certification No. 87901
SYSTEM INSTALLED BY:
TEI Electrical Solutions
4840 Winchester Blvd-Suite 1
Frederick, MD 21703
Exist. EST-3 Fire Alarm Control System
Manufactured by UTC
(703) 631-7476
3650 Concorde Parkway-Suite 100
Chantilly, VA 20150
BLUEMONT, VA 20135
SYSTEM SUPPLIED AND SERVICED BY:
CONVERGINT CTC-443
Chantilly, VA
19844 BLUERIDGE MOUNTAIN ROAD
PROPOSED
FIRE ALARM/MNS SYSTEM
MOUNT WEATHER-BLDG 401
2ND FLOOR TENANT
Page
Scope
Nicet Certificates
Revision Sheet
Bill of Materials 1
ASSD (VESDA) Bill of Materials 2
Description of Operations 3
Addressable Loop 2 (Existing) 5
Addressable Loop 2A 8
Remote FACP Calculations 9
Speaker Calculations 10
Spare Calculations/Voltage Drop 11
Battery Calculations - Signal Panel 12
Catalog Data Pages **
TABLE OF CONTENTS
24083F_ Scope Scope
In your review of the proposed submittals we submit the following for your assistance and consideration.
The following criterion have been implemented during the design process of the Fire Alarm System:
General
The building is a Four-story structure with a small Penthouse. Occupancy use is (B) Business.
System
We have designed the fire alarm system using the existing EST-3 Fire Alarm Control Panel. A second loop card shall be added to convert Loop2 into two loops.
This scope includes a tenant fitout to the 2nd floor. Underfloor detection shall be accomplished with VESDA air sampling detectors.
A Audio Source Unit has been included in this system. Live voice messages and pre-recorded messages can be received from the main campus paging panel via the
VOIP to Audio System. Fire Alarm activity from this system shall be reported to a Central Fireworks.
Wiring
The Fire Alarm System has been designed with Class "A" Signaling Circuits and Class "A" Notification Circuits. T-Tapping of addressable circuit is NOT PERMITTED.
T-Tapping of Notification Circuits also Prohibited .
Notification
The system is designed with voice evacuation.
Existing power supplies have been provided for the Notification Appliances. These units, shall be located as shown on dwgs and shall be activated via a synchronization module. All wall mounted Notification Appliances shall be white in color, and Ceiling mounted notification devices shall be White in color.
All interior speaker shall be set at 1/2 watt initially, and exterior speakers set to 2 watts initially.
Installation
Battery Sizing has been calculated for 24 Hours standby with 15 minutes alarm per specification to comply w/ NFPA 72-2019 10.6.7.2.1(2)
All Fire Alarm Control Equipment shall be in locations protected by a smoke detector NFPA 72 2019 10.4.4
Control function interface devices (relays) shall be located within 3ft of the component controlling the emergency function. NFPA 72 2019 21.2.4
The fire alarm control panel (FACP) and extender panels shall be connected to the emergency power circuit.
Observation:
Contract documents: System Matrix denotes Duct Smoke detectors as alarm and supvervisory intiating devices.
The submittal booklet contains but is not limited to the following:
• Bill of materials.
• Sequence of Operation
• Addressable Device List
• Spare capacity
• Voltage Drop Calculations
• Speaker Loads
• Battery calculations.
The submittal drawings contain but are not limited to the following:
• Floor Plans and Wiring
• Riser Diagrams and circuit layouts.
• Details and drawings of FACP, Signal Panel and connections.
• Symbol legends, mounting and installation details.
The purpose of our shop drawings is to aid in the installation of proprietary systems. If there is a discrepancy between the contract and Convergint shop drawings that has not been addressed in this letter, the submittal booklet and shop drawings or if you have any questions in regards to any portion of this submission, please contact me at rich.salmon@convergint.com or (703) 631-7476.
Respectfully, Richard Salmon
Fire alarm Design Engineer
Convergint
NICET IV #87901
rich.salmon@convergint.com mailto:rich.salmon@convergint.com
24083F_ Rev Sheet
Changes Y/N
Mod # Description Date By Dwg
Original Submission 7/15/2024 RS
1 REVISED PER ENG COMMENTS DTD 07/25/24 8/14/2024 RS Y
Revision Sheet
24083F_ Rev Sheet
Changes Y/N
Booklet
Y
24083F_ BOM
Qty Cat No Description Manufature Cat. Sheet #
EST3 System Components
Signature Series Dual Loop Card
1 3-SDC1 Signature Driver Card (Loop 2A) EST 85010-0129
Signature Series Intelligent Detectors
20 SIGA-OSD Multi-criteria optical smoke detector (UL268 Compliant) EST 85001-1001
4 SIGA-HRD Heat detector, combination 135F fixed with 15F/min ROR, EST 85001-0647
Detector Bases
24 SIGA-SB Standard Detector Base EST 85001-1001
Signature Series Life Safety Modules
Input Modules
2 SIGA-CT1 Single Input Module EST 85001-0241
Signal Modules
3 SIGA-UM Universal Class A/B Module EST 85001-0275
Genesis G4 LED Series Accessories
2 GRSW-10 Total Universal Mounting Plate, 10 Pack EST 85001-0667
Genesis G1 LED Fire Strobes, Wall Mount, Multi-candela, 1 Gang
3 G1VWA Selectable - 15, 30, 75 cd - White - Alert EST 85001-0667
Genesis LED Series Ceiling Mount 25/70 Vrms Speaker/Strobes (1/4W to 2W) 520HZ and High Fidelity Capable (STI .81)
11 GCSVWA Ceiling Speaker/Strobe, 15-110cd, White, ALERT Marking EST 85001-1025
24083F_ BOM-VESDA
Qty Cat No Description Manuf. Cat. Sheet #
2ND FLOOR-ZONE 2 TENANT
2 VP-CLIP Pipe Clip single point fix VESDA VES-003
1 VP-COUP VESDA Couplings (15/Box) VESDA VES-004
1 VP-EC Endcap (25/Box) VESDA VES-005
2 VP-ELB-90 VESDA 90 Degree Elbows (20/Box) VESDA VES-006
3 VP-P-210 VESDA Sample Pipe, Box of 15 Pieces, 210 Feet Total VESDA VES-007
1 VP-TEE T Piece (15/Box) VESDA VES-008
1 E700-SP-DCL-PNT VESDA Sample Pt. Labels (50/Sheet) VESDA VES-009
24083F_ DOP
Activation of any Manual Pull Station, Area Smoke Detector, Sprinkler Waterflow Switch shall cause the following:
1. Send an alarm signal (via Network) to the Central Control Building (# 921).
2. Visually indicate via control panel LCD display, the floor, area and type of device in alarm. The ALARM (red) LED shall light; the internal control panel alarm shall sound; and the first line of the eighty (80) character LCD shall indicate the REAL TIME, the number of
MESSAGES WAITING, the TYPE OF ALARM, the ALARM ZONE NUMBER, and the TIME THAT THE ALARM OCCURRED. The second line shall display the user specified message. In order to reduce false alarms, all inputs shall be capable of alarm verification.
The system shall be capable of setting the sensitivity of all analog detectors by point and shall be capable of displaying the analog value of the detector by device and/or traditional input and vectoring the value to a remote printer. The system shall automatically identify any analog detector which becomes dirty (maintenance alert) prior to false alarming.
3. Visually indicate via LCD Annunciator display, the floor, area and type of device in alarm.
4. Continuous actuation of all alarm notification appliances. All audible/visual signaling devices shall sound continuously until manually silenced. It shall be possible to silence the audible portion of the appliance without extinguishing the visual strobe. A subsequent alarm received after silencing shall again cause the initiating circuits to be activated. The fire alarm signals shall be distinctive from all other alarm signals.
5. Upon receipt of an alarm signal from the building's fire alarm system, the FACP shall automatically transmit a pre-recorded fire alarm message throughout the building.
Activation of any valve tamper switch, or other supervisory device, will automatically cause the following:
1. Send a supervisory signal (via Network) to the Central Control Building (# 921).
2. Visually indicate via control panel LCD display, the area and type of device activated.
3. Visually indicate via LCD Annunciator display, the floor, area and type of device in alarm
4. Sound an audible trouble signal at the fire alarm control panel and the remote annunciators.
Any open circuit, short circuit or ground fault on any supervised circuit (alarm initiating, alarm indicating, annunciation or control relay), loss of primary AC power, primary AC power below 96 Volts, low battery, loss of battery, or any internal system trouble will automatically cause the following:
1. Send a trouble signal (via Network) to the Central Control Building (# 921).
2. Visually indicate via control panel LCD, the source and the location of the trouble.
2. Visually indicate via control panel LCD display, the area and type of device activated.
4. Sound an audible trouble signal at the fire alarm control panel and the remote annunciators.
24083F_ DOP
Upon completion of the installation and after satisfactory testing of the system by the contractor in the presence of the equipment supplier, the contractor shall test the system in the presence of the Architect/Engineer, Fire Marshal and/or owner's representative, and other authorities having jurisdiction.
The distributor shall provide 24 hour/7days a week (including holidays) service capability. Service performed at times other than normal working hours (Monday thru Friday, 8:00 AM to 5:00 PM, excluding holidays) shall be billable at an additional cost to the owner.
GUARANTEE
All Control equipment and field devices will have a warranty of (5) years from the date of acceptance. All other materials, peripherals, installation and workmanship for five (5) years from the date of acceptance, unless otherwise specified.
The contractor will warranty all wiring and raceways to be free from inherent mechanical or electrical defects for five (5) years from the date of final acceptance of the system.
24083F_ Loop 2
DEVICE NEW LABELS/DEVICES IN BOLD LOOP ROOM SENSOSR MODULE MODULE DESCRIPTION
SMOKE DETECTOR LOOP 2 300A VEST 0001
SMOKE DETECTOR LOOP 2 300 LOBBY 0002
SMOKE DETECTOR LOOP 2 324 IG SUPPORT OFC 0003
SMOKE DETECTOR LOOP 2 310 LEADERSHIP CONF RM 0004
SMOKE DETECTOR LOOP 2 310 LEADERSHIP CONF RM 0005
SMOKE DETECTOR LOOP 2 310 LEADERSHIP CONF RM 0006
SMOKE DETECTOR LOOP 2 310A ELEC. RM 0007
SMOKE DETECTOR LOOP 2 311 RECONSTITUTION RM 0008
SMOKE DETECTOR LOOP 2 312 LOCKERS 0009
SMOKE DETECTOR LOOP 2 300 LOBBY 0010
SMOKE DETECTOR LOOP 2 306 CORRIDOR 0011
SMOKE DETECTOR LOOP 2 306 CORRIDOR 0012
SMOKE DETECTOR LOOP 2 306 CORRIDOR 0013
DUCT SMOKE DETECTOR LOOP 2 301 HSKPG 0014
HEAT DETECTOR LOOP 2 301 HSKPG 0015
DUCT SMOKE DETECTOR LOOP 2 301 HSKPG 0016
DUCT SMOKE DETECTOR LOOP 2 301 HSKPG 0017
SMOKE DETECTOR LOOP 2 302 TELE. RM 0018
SMOKE DETECTOR LOOP 2 303 TOILET RM 0019
SMOKE DETECTOR LOOP 2 304 TOILET RM 0020
SMOKE DETECTOR LOOP 2 305 ELEC 0021
SMOKE DETECTOR LOOP 2 300 LOBBY 0022
SMOKE DETECTOR LOOP 2 307 MECH RM 0023
DUCT SMOKE DETECTOR LOOP 2 307 MECH RM 0024
DUCT SMOKE DETECTOR LOOP 2 307 MECH RM 0025
DUCT SMOKE DETECTOR LOOP 2 307 MECH RM 0026
DUCT SMOKE DETECTOR LOOP 2 307 MECH RM 0027
SMOKE DETECTOR LOOP 2 308 BREAK RM 0028
SMOKE DETECTOR LOOP 2 309 CORRIDOR 0029
SMOKE DETECTOR LOOP 2 320 DEP. SECRETARY 0030
SMOKE DETECTOR LOOP 2 318 DEP SEC STAFF 0031
SMOKE DETECTOR LOOP 2 319B CLASS. TLECOM 0032
SMOKE DETECTOR LOOP 2 329 IT WORK RM 0033
SMOKE DETECTOR LOOP 2 328 STORAGE 0034
SMOKE DETECTOR LOOP 2 327 STORAGE 0035
SMOKE DETECTOR LOOP 2 326 TELECOM 0036
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA CRDR 0037
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0038
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0039
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0040
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0041
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0042
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0043
SMOKE DETECTOR LOOP 2 315B CORRIDOR 0044
SMOKE DETECTOR LOOP 2 315B CORRIDOR 0045
SMOKE DETECTOR LOOP 2 319 SCIF SUITE 0046
SMOKE DETECTOR LOOP 2 319A SCIF CONF. SPACE 0047
SMOKE DETECTOR LOOP 2 314 HUD EM RESP CTR 0048
SMOKE DETECTOR LOOP 2 313 CONF. ROOM 0049
SMOKE DETECTOR LOOP 2 208 BREAK RM 0050
SMOKE DETECTOR LOOP 2 209 CORRIDOR 0051
SMOKE DETECTOR LOOP 2 209 CORRIDOR 0052
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0053
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0054
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0055
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0056
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0057
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0058
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0059
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0060
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0061
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0062
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0063
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0064
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0065
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0066
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0067
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0068
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0069
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0070
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0071
SMOKE DETECTOR LOOP 2 211 LEVEL 2 FUTURE TENANT 0072
SMOKE DETECTOR LOOP 2 209 CORRIDOR 0073
SMOKE DETECTOR LOOP 2 209 CORRIDOR 0074
SMOKE DETECTOR LOOP 2 209 CORRIDOR 0075
SMOKE DETECTOR LOOP 2 206 CORRIDOR 0076
DUCT SMOKE DETECTOR LOOP 2 201 HSKPG 0077
HEAT DETECTOR LOOP 2 201 HSKPG 0078
DUCT SMOKE DETECTOR LOOP 2 201 HSKPG 0079
DUCT SMOKE DETECTOR LOOP 2 201 HSKPG 0080
SMOKE DETECTOR LOOP 2 202 TELE RM 0081
SMOKE DETECTOR LOOP 2 203 TOILET RM 0082
SMOKE DETECTOR LOOP 2 204 TOILET RM 0083
SMOKE DETECTOR LOOP 2 205 ELEC 0084
SMOKE DETECTOR LOOP 2 200 LOBBY 0085
SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0086
SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0087
SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0088
SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0089
SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0090
SMOKE DETECTOR LOOP 2 210 LEVEL 2 FUTURE TENANT 0091
SMOKE DETECTOR LOOP 2 200A VEST 0092
SMOKE DETECTOR LOOP 2 200 LOBBY 0093
SMOKE DETECTOR LOOP 2 207 MECH RM 0094
DUCT SMOKE DETECTOR LOOP 2 207 MECH RM 0095
DUCT SMOKE DETECTOR LOOP 2 207 MECH RM 0096
DUCT SMOKE DETECTOR LOOP 2 207 MECH RM 0097
DUCT SMOKE DETECTOR LOOP 2 207 MECH RM 0098
HEAT DETECTOR LOOP 2 202 TELE RM 0099
HEAT DETECTOR LOOP 2 205 ELEC 0100
HEAT DETECTOR LOOP 2 207 MECH RM 0101
HEAT DETECTOR LOOP 2 302 TELE. RM 0102
HEAT DETECTOR LOOP 2 305 ELEC 0103
HEAT DETECTOR LOOP 2 307 MECH RM 0104
24083F_ Loop 2
DEVICE NEW LABELS/DEVICES IN BOLD LOOP ROOM SENSOSR MODULE MODULE DESCRIPTION
SMOKE DETECTOR LOOP 2 325 IG OFFICE 0105
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0106
SMOKE DETECTOR LOOP 2 330 CONF. ROOM 0107
SMOKE DETECTOR LOOP 2 315A RECEPT. AREA 0108
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0109
SMOKE DETECTOR LOOP 2 315 ERG WORK AREA 0110
SMOKE DETECTOR LOOP 2 317 PUBLIC AFFAIRS EXEC. 0111
SMOKE DETECTOR LOOP 2 323 STORAGE 0112
SMOKE DETECTOR LOOP 2 322 PUBLIC AFFAIRS 0113
HEAT DETECTOR LOOP 2 321 ELEC. ROOM 0114
SMOKE DETECTOR LOOP 2 321 ELEC. ROOM 0115
HEAT DETECTOR LOOP 2 319B CLASS. TLECOM 0116
HEAT DETECTOR LOOP 2 326 TELECOM 0117
HEAT DETECTOR LOOP 2 310A ELEC. RM 0118
MANUAL PULL STATION LOOP 2 300A VEST 0126
AED CABINET MONITORING LOOP 2 300 LOBBY 0127 (SIGA-CT1) MONITOR MODULE
MANUAL PULL STATION LOOP 2 01 STAIR 0128
TAMPER SWITCH LOOP 2 02 STAIR 0129 (SIGA-CT2) DUAL MONITOR MODULE
FLOW SWITCH 0130
MANUAL PULL STATION LOOP 2 02 STAIR 0131
MANUAL PULL STATION LOOP 2 03 STAIR 0132
MANUAL PULL STATION LOOP 2 03 STAIR 0133
AED CABINET MONITORING LOOP 2 200 LOBBY 0134 (SIGA-CT1) MONITOR MODULE
MANUAL PULL STATION LOOP 2 01 STAIR 0135
TAMPER SWITCH LOOP 2 02 STAIR 0136 (SIGA-CT2) DUAL MONITOR MODULE
FLOW SWITCH 0137
MANUAL PULL STATION LOOP 2 02 STAIR 0138
ASFP PANEL FAULT #1 LOOP 2 307 MECH RM 0139 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #1 LOOP 2 307 MECH RM 0140 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #1 LOOP 2 307 MECH RM 0141 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #1 LOOP 2 307 MECH RM 0142 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #1 LOOP 2 307 MECH RM 0143 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #2 LOOP 2 307 MECH RM 0144 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #2 LOOP 2 307 MECH RM 0145 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #2 LOOP 2 307 MECH RM 0146 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #2 LOOP 2 307 MECH RM 0147 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #2 LOOP 2 307 MECH RM 0148 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #1 LOOP 2 207 MECH RM 0149 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #1 LOOP 2 207 MECH RM 0150 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #1 LOOP 2 207 MECH RM 0151 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #1 LOOP 2 207 MECH RM 0152 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #1 LOOP 2 207 MECH RM 0153 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #2 LOOP 2 207 MECH RM 0154 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #2 LOOP 2 207 MECH RM 0155 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #2 LOOP 2 207 MECH RM 0156 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #2 LOOP 2 207 MECH RM 0157 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #2 LOOP 2 207 MECH RM 0158 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #3 LOOP 2 207 MECH RM 0159 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #3 LOOP 2 207 MECH RM 0160 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #3 LOOP 2 307 MECH RM 0161 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #3 LOOP 2 207 MECH RM 0162 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #3 LOOP 2 207 MECH RM 0163 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #4 LOOP 2 207 MECH RM 0164 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #4 LOOP 2 207 MECH RM 0165 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #4 LOOP 2 207 MECH RM 0166 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #4 LOOP 2 207 MECH RM 0167 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #4 LOOP 2 207 MECH RM 0168 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #5 LOOP 2 207 MECH RM 0169 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #5 LOOP 2 207 MECH RM 0170 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #5 LOOP 2 207 MECH RM 0171 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #5 LOOP 2 207 MECH RM 0172 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #5 LOOP 2 207 MECH RM 0173 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #3 LOOP 2 307 MECH RM 0174 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #3 LOOP 2 307 MECH RM 0175 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #3 LOOP 2 307 MECH RM 0176 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #3 LOOP 2 307 MECH RM 0177 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #3 LOOP 2 307 MECH RM 0178 (SIGA-CT1) MONITOR MODULE
CLASS A/B MODULE LOOP 2 210 LEVEL 2 FUTURE TENANT 0179 (SIGA-UM) CONTROL MODULE
CLASS A/B MODULE LOOP 2 211 LEVEL 2 FUTURE TENANT 0181 (SIGA-UM) CONTROL MODULE
CLASS A/B MODULE LOOP 2 310 LEVEL 3 FUTURE TENANT 0183 (SIGA-UM) CONTROL MODULE
CLASS A/B MODULE LOOP 2 311 LEVEL 3 FUTURE TENANT 0185 (SIGA-UM) CONTROL MODULE
BOOSTER PANEL #2 ACTIVATION LOOP 2 207 MECH RM 0187 CONTROL MODULE (SIGA-CC1S)
BOOSTER PANEL #3 ACTIVATION LOOP 2 307 MECH RM 0188 CONTROL MODULE (SIGA-CC1S)
ASFP PANEL FAULT #4 LOOP 2 307 MECH RM 0189 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #4 LOOP 2 307 MECH RM 0190 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #4 LOOP 2 307 MECH RM 0191 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #4 LOOP 2 307 MECH RM 0192 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #4 LOOP 2 307 MECH RM 0193 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #5 LOOP 2 307 MECH RM 0194 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ALERT #5 LOOP 2 307 MECH RM 0195 (SIGA-CT1) MONITOR MODULE
ASFP PANEL ACTION #5 LOOP 2 307 MECH RM 0196 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 1 #5 LOOP 2 307 MECH RM 0197 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FIRE 2 #5 LOOP 2 307 MECH RM 0198 (SIGA-CT1) MONITOR MODULE
REMICA SUPERVISION LOOP 2 200 LOBBY 0199 (SIGA-CT1) MONITOR MODULE
ASFP PANEL FAULT #6 LOOP 2 307 MECH RM 0200 (SIGA-CT2) MONITOR MODULE
ASFP PANEL ALERT #6 LOOP 2 307 MECH RM 0201 (SIGA-CT2) MONITOR MODULE
ASFP PANEL ACTION #6 LOOP 2 307 MECH RM 0202 (SIGA-CT2) MONITOR MODULE
ASFP PANEL FIRE 1 #6 LOOP 2 307 MECH RM 0203 (SIGA-CT2) MONITOR MODULE
ASFP PANEL FIRE 2 #6 LOOP 2 307 MECH RM 0204 (SIGA-CT1) MONITOR MODULE
CLASS A/B MODULE LOOP 2 319 SCIF SUITE CORRIDOR 0205 (SIGA-UM) CONTROL MODULE
24083F_ LOOP 2A
DEVICE TYPE LOOP# SENSOR MODULE LOCATION MODULE DESCRIPTION
SMOKE DETECTOR LOOP 2A 0251 217 OPEN OFFICE WK AREA
SMOKE DETECTOR LOOP 2A 0252 219 ELEC. ROOM
HEAT DETECTOR LOOP 2A 0253 219 ELEC. ROOM
SMOKE DETECTOR LOOP 2A 0254 219 CORRIDOR
SMOKE DETECTOR LOOP 2A 0255 220 COO OFFICE
SMOKE DETECTOR LOOP 2A 0256 219 CORRIDOR
SMOKE DETECTOR LOOP 2A 0257 223 SO OFFICE
SMOKE DETECTOR LOOP 2A 0258 222 CHAIR OFFICE
SMOKE DETECTOR LOOP 2A 0259 218 SEC CONF. ROOM
SMOKE DETECTOR LOOP 2A 0260 219 OIT OFFICE
SMOKE DETECTOR LOOP 2A 0261 217 OPEN OFFICE WK AREA
SMOKE DETECTOR LOOP 2A 0262 217 OPEN OFFICE WK AREA
SMOKE DETECTOR LOOP 2A 0263 216 SCIF WORKROOM
SMOKE DETECTOR LOOP 2A 0264 215 SCIF
SMOKE DETECTOR LOOP 2A 0265 213 NCUA CHAIRMAN
SMOKE DETECTOR LOOP 2A 0266 212 NCUA CONF. ROOM
SMOKE DETECTOR LOOP 2A 0267 212A NCUA OIT TELECOM
HEAT DETECTOR LOOP 2A 0268 212A NCUA OIT TELECOM
SMOKE DETECTOR LOOP 2A 0269 215A SCIF SERVER RM
HEAT DETECTOR LOOP 2A 0270 215A SCIF SERVER RM
DUCT SMOKE DETECTOR LOOP 2A 0271 214A SEC COOP TELECOM
DUCT SMOKE DETECTOR LOOP 2A 0272 214 VESTIBULE
SMOKE DETECTOR LOOP 2A 0273 217 OPEN OFFICE WK AREA
HEAT DETECTOR LOOP 2A 0274 214A SEC COOP TELECOM
CLASS "A" SIG MODULE LOOP 2A 0376 217 OPEN OFFICE WK AREA SIGA-UM
CLASS "A" SIG MODULE RTN LOOP 2A 0377 217 OPEN OFFICE WK AREA SIGA-UM
CLASS "A" SIG MODULE LOOP 2A 0378 303 TOILET RM SIGA-UM
CLASS "A" SIG MODULE RTN LOOP 2A 0379 304 TOILET RM SIGA-UM
CLASS "A" SIG MODULE LOOP 2A 0380 303 TOILET RM SIGA-UM
CLASS "A" SIG MODULE RTN LOOP 2A 0381 304 TOILET RM SIGA-UM
MONITOR MODULE LOOP 2A 0382 VESDA ZONE 2 PIPE 2 FIRE 2 SIGA-CT1
24083F_ REMOTE FACP
RCC7
CURRENT EA. CURRENT TOTAL
QTY PART NO. DESCRIPTION STBY ALRM STBY ALRM
1 3-CPU/PPS Main CPU #1 155.00 165.00 155.00 165.00
3-LCD Front Panel Display 40.00 42.00 0.00 0.00
1 3-RS232 COMM CARD 58.00 58.00 58.00 58.00
3-RS485 COMM BOARD 98.00 98.00 0.00 0.00
3-FIB FIBER COMM BOARD 217.00 217.00 0.00 0.00
SMXLO SINGLE MODE TRANSCEIVER 45.00 45.00 0.00 0.00
3-ASU/4 AUDIO/MIC PANEL 210.00 210.00 0.00 0.00
2 3-SSDC1 ADDRSSABLE LOOP MODULE 144.00 204.00 288.00 408.00
1 3-SDDC1 ADDRSSABLE DUAL LOOP MODULE 264.00 336.00 264.00 336.00
0 3-MODCOM Modem Communicator and Dialer 60.00 90.00 0.00 0.00
3-EVDVRA SWITCH DRIVER MODULE 22.00 22.00 0.00 0.00
3-ANN-CPU3 CPU-CARD ANNUNCATOR 144.00 144.00 0.00 0.00
3-REMICA Remote Microphone 52.00 52.00 0.00 0.00
3-ZA20 AMPLIFIER 20 WATT 35.00 1250.00 0.00 0.00
3-ZA40 AMPLIFIER 40 WATT 62.00 2480.00 0.00 0.00
3-ZA40 AMPLIFIER 40 WATT BACKUP 64.00 64.00 0.00 0.00
KDPISP KEYPAD 95.00 95.00 0.00 0.00
3-SAC SECURITY CONTROLLER 40.00 40.00 0.00 0.00
3-6Sxxx Front Panel Switchbank 20.00 20.00 0.00 0.00
3-12S1GY 12 Switch, 12 Grn, 12 Yel Ctrl Dis Mod 2.00 38.00 0.00 0.00
3-12S1RY 12 Switch, 12 Red, 12 Yel Ctrl Dis Mod 2.00 38.00 0.00 0.00
0.00 0.00 0.00 0.00
MN-COM1S Ethernet Device Server Network Interface 60.00 60.00 0.00 0.00
MN-FVPN VoIP Unit, audio encoder/decoder 89.00 89.00 0.00 0.00
MN-PASM Pre-AMP Supervison Module 100.00 100.00 0.00 0.00
MN-FNS4C2F3 CISCO Ethernet Network Switching Hub 350.00 350.00 0.00 0.00
BBC Booster Power Multiple Batteries 70.00 70.00 0.00 0.00
Bell NOTIFICATON CIRCUIT 0.00 85.00 0.00 85.00
Full Addressable Loop Load Using Highest Module Current
500 SIGA SENSORS Intelligent Smoke/Heat *** 0.05 0.05 22.50 22.50
500 SIGA MODULES Intelligent Universal Module *** 0.40 0.68 198.00 340.00
CURRENTS GIVEN IN MILLIAMPS
*** Calculations configured for full capacity of additional devices required per specs.
**calculations added for LOOP2A**
Enter Req'd TOTAL CURRENT 985.50 1414.50 by Number
24 Hours Total Standby Hours 23652 ma
15 Minutes Total Alarm Hours 353.625 ma
Battery Size Required 28.81 Amps
Battery Size Provided (Existing) 35AH
60 Minutes Alarm Total 1414.50 ma
Note: A twenty percent safety margin has been added to all of the final battery calculations per NFPA 72-2013 10.6.7.2.1 (1).
Addressable Device Loops have been configured for maximum loop loading of devices.
Bell
24083F_ Spkr Calcs
Amplifier Calcuations
SPKEAKER CKT LENGTH # DEV
TOTAL
WATTS
REQUIRED
(1/2W)
WATTS
AVAILABL
E
WATTS
USED
SPARE
CAPACITY Amplifier
S2 1000' 16 8
S2A 500' 3 1.5
S2B 150' 3 1.5
S2C 700' 5 2.5
S2D 350' 2 1
S2E 200' 1 0.5
S3 700' 15 7.5
S3A 350' 23 11.5
S3B 200' 5 2.5
S3C 200' 3 1.5
40 95.00% 5.00% AMP 2
24083F_ Spare Cap
ADDRESSABLE LOOPS SPARE CAPACITY
BLDG #401
ADDRESSABLE DEVICE LOOP #2
SENSORS
USED 94.40% 118 Total Devices Used
SPARE 5.60% 7 Spare Sensor Addresses
MODULES
USED 64.80% 81 Total Modules Used
SPARE 35.20% 44 Spare Module Addresses
Total Loop Capacity
USED 79.60% 199 Total Addresses Used
SPARE 20.40% 51 Total Spare Addresses
ADDRESSABLE DEVICE LOOP #2A
SENSORS
USED 18.40% 23 Total Devices Used
SPARE 81.60% 102 Spare Sensor Addresses
MODULES
USED 5.60% 7 Total Modules Used
SPARE 94.40% 118 Spare Module Addresses
Total Loop Capacity
USED 12.00% 30 Total Addresses Used
SPARE 88.00% 220 Total Spare Addresses
VOLTAGE DROP CALCULATIONS - WORST CASE
Signal Ckt # Current Distance EOL Voltage
3 0.609 338' 22.93
4 0.602 293' 23.08
Notes:
1. Voltage drop calculations are based on a 24VDC input.
2. Actual Voltage drops will reflect a higher reading than shown.
3. Field tests will verify proper voltage and operation of circuits.
4. Calculations based on using wire resistance of 3.07 ohms per conductor or total of 6.4 ohms per 1000 ft.
24083F_ SigBatCalcsA
Signal Panel #2 Ckt# 3 4 3 4
G4VRF LED Genesis Wall Strobe, 15-110cd, Red, FIRE 0.028 3 1 0.084 0.028
GCVWF LED Genesis Ceiling Strobe, 15-115cd, White, FIRE 0.035 3 0.000 0.105
G4SVRF LED Genesis Wall Speaker/Strobe, 15-110cd, Red, FIRE 0.028 3 0.000 0.084
GCSVWF LED Genesis Ceiling Speaker/Strobe, 15-115cd, White, FIRE 0.035 15 11 0.525 0.385
INDIVIDUAL CIRCUIT TOTALS: 0.609 0.602
**NOTE** Changes made to Ckt#3 for this scope**
Standby Time (Hrs) 24 Standby Current 0.070 Battery Required 2.1 AH
Alarm Time (Min) 15 Alarm Current 1.481 Battery Provided 7.2 AH
MOUNT WEATHER BLDG 401
19844 BLUE RIDGE MOUNTAIN RD
BLUMOUNT, VA 20135
METALLIC CONDUIT 12" MIN.
SCHEDULE 80 PVC PIPE/FITTINGS
NOTES:
1. WHERE CONDUIT DOES NOT COMPLETELY FILL THE WALL OPENING, SEAL PENETRATION WITH
ACOUSTICAL JOINT SEALANT CAULKING.
2. DETAIL APPLIES TO ALL METALLIC CONDUIT ENTERING A SCIF SPACE.
METALLIC CONDUIT
SPECIAL WALL PARTITION
6" MAX
ATTACK SIDESECURE SIDE
PACKAGING AND SEALANT FOR FIRE RATED CONSTRUCTION WHERE
APPLICABLE - WHERE NO FIRESTOPPING IS REQUIRED PACK SOLID
WITH HIGH STRENGTH GROUT - SEAL WITH ACOUSTICAL CAULKING
EXTEND GROUND WIRE TO BUILDING
STRUCTURAL STEEL OR NEAREST GROUND BAR
(NOT LOCATED WITHIN AN ELECTRICAL PANEL).
PIPE CLAMP WITH GROUND WIRE
3. SIZE CONDUIT IN ACCORDANCE WITH NEC 760.
RISER OUT (+)
RISER OUT (-)
DATA IN (-)
DATA IN (+) DATA OUT (-)
DATA OUT (+)
24VDC TO ANNUNCIATORS
TO MAIN FACP
RS-485 NETWORK
INPUT 2
G N
D +24V
EG
N D
107654 98 A+G
N D
+24V
B-B+A-
R
EM
O
TE AN
N U
N . (C
PU
3-AN
N
C
PU
D
ISPLAY SU
PPO
R
T M O
D U
LE
3-AN
N
SM
FILLER
PLATE
3-FP
OUTPUT INPUT 1
BATTERY
3-BPS
AUX POWER
3.5A EACH
+ +TB1
P4 CONNECTS TO 3-PPS
3-BPSMON
P6 CONNECTS TO 3-PPS
VIA P3 DATA CABLE
VIA P2 POWER CABLE
ON BACK
3-BPS/MON
AUX POWER
3.5A EACH
BATTERY
TB1 +-
P4 CONNECTS TO 3-PPS
P6 CONNECTS TO 3-PPS
VIA P3 DATA CABLE
VIA P2 POWER CABLE
ON BACK
3-PSMON
H N G
3-PPS
3-PS/MON
3-ZA40B
BACK-UP NAC/BBACK-UP
S
TB2
NAC/B
S
FOR 70 VDC
SET JP-1 & JP-2
TO TC#1
Ditek
DTK-120HW
SET JP-1 & JP-2SET JP-1 & JP-2
FOR 70 VDC FOR 70 VDC
AMP 3 AMP 4AMP 2
BATTERY CABINET - BC-1
65ah BATTERY
BATTERY CABINET - BC-1
65ah BATTERY
3-ZA40B
BACK-UP NAC/B
S
BACK-UP
TB2
NAC/B
SS
NAC/A
S S
NAC/A
S
FROM TC#1
TO TC#1
FROM TC#1
MN-FNS4C2F3
SI
G
A- M
C C
2A
SI
G
A- U
IO
6R
SI
G
A- M
C C
2A
SI
G
A- M
C C
2A
SI
G
A- M
C C
2A
SI
G
A- M
C C
2A
3-ZA40B
BACK-UP NAC/B
S
TB2
BACK-UP NAC/B
S
UNUSED
SET JP-1 & JP-2
FOR 70 VDC
AMP 4
BACKUP
TO TC#1
FROM TC#1
3-ZA40B
BACK-UP NAC/B
S
TB2
BACK-UP NAC/B
S
UNUSED
SET JP-1 & JP-2
FOR 70 VDC
AMP 1
TO TC#1
FROM TC#1
3-ZA20B
BACK-UP NAC/B
S
TB2
BACK-UP NAC/B
S
UNUSED
SI
G
A- M
C C
2A
SI
G
A- U
IO
2R
SI
G
A- M
C C
2A
SP
AR
E
LRMF
LRMF
LRMF
LRMF
LOOP 3
AUX POWER
3.5A EACH
BATTERY
TB1 +-
P4 CONNECTS TO 3-PPS
P6 CONNECTS TO 3-PPS
VIA P3 DATA CABLE
VIA P2 POWER CABLE
ON BACK
3-PSMON
H N G
3-PPS
3-PS/MON
3-SSDC1 3-SDDC2
Ditek
DTK-120HW
LOOP 2LOOP 1
B
SUPPLY
LOOP 2
LOOP 2
RETURN
LOOP 1
B
SUPPLY
LOOP 1
RETURN
LOOP 3
SUPPLY
RETURN
BATTERY CABINET - BC-1
35ah BATTERY35ah BATTERY
3-SSDC1
LOOP 3
B
LRMF
LOOP 2A
SUPPLY
LOOP 2A
LOOP 2A
RETURN
converg nt
3650 CONCORDE PARKWAY SUITE-100
CHANTILLY, VA. 20150
CTC 443
OFFICE: (703) 631-7476 - FAX: (703) 330-0086
WWW.CONVERGINT.COM
This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request.
This document cannot be reproduced by any means without the written authorization of Convergint Technologies LLC.
19844 BLUE RIDGE MOUNTAIN RD
BLUMOUNT, VA 20135
converg nt
3650 CONCORDE PARKWAY SUITE-100
CHANTILLY, VA. 20150
CTC 443
OFFICE: (703) 631-7476 - FAX: (703) 330-0086
WWW.CONVERGINT.COM
This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request.
19844 BLUE RIDGE MOUNTAIN RD
BLUMOUNT, VA 20135
MANUAL FIRE ALARM BOX
DUCT-TYPE SMOKE DETECTOR LOCATED IN SUPPLY DUCT OF AHU
SPOT-TYPE SMOKE DETECTOR - IN LEVELS 1,2, 4, AND 5 ELEVATOR LOBBIES
SPOT-TYPE SMOKE DETECTOR - LEVEL 3 ELEVATOR LOBBY
WET PIPE SPRINKLER WATERFLOW SWITCH
SPRINKLER VALVE TAMPER SWITCH
MASS NOTIFICATION ACTIVATION
FIRE ALARM NETWORK COMMUNICATION FAILURE
FARA MICROPHONE ACTIVATED
FIRE ALARM CONTROL UNIT TROUBLE
SYSTEM INPUTS
X
X
X X
X X
X X
X X
X X X X X
XX
X X
X X X
XX
DI
SP
LA
Y
AL
PH
AN
UM
ER
IC
M
ES
SA
GE
O N
FA
CU
A
ND
A
NN
UN
CI
AT
OR
S
A B C D E F G H I J K L M N O P Q R S
AC
TU
AT
E
CO
MM
ON
A
UD
IB
LE
/V
IS
IB
LE
A
LA
RM
IN
DI
CA
TO
RS
O
N
FA
CU
A
ND
A
NN
UN
CI
AT
OR
S
AC
TU
AT
E
CO
MM
ON
A
UD
IB
LE
/V
IS
IB
LE
S
UP
ER
VI
SO
RY
IN
DI
CA
TO
RS
O N
FA
CU
A
ND
A
NN
UN
CI
AT
OR
S
AC
TU
AT
E
CO
MM
ON
A
UD
IB
LE
/V
IS
IB
LE
T
RO
UB
LE
IN
DI
CA
TO
RS
O
N
FA
CU
A
ND
A
NN
UN
CI
AT
OR
S
TR
AN
SM
IT
A
LA
RM
S
IG
NA
L T O
CE
NT
RA
L M
ON
IT
OR
IN
G
ST
AT
IO
N
TR
AN
SM
IT
S
UP
ER
VI
SO
RY
S
IG
NA
L T O
CE
NT
RA
L M
ON
IT
OR
IN
G
ST
AT
IO
N
TR
AN
SM
IT
T
RO
UB
LE
S
IG
NA
L T O
CE
NT
RA
L M
ON
IT
OR
IN
G
ST
AT
IO
N
AC
TI
VA
TE
R
EC
OR
DE
D
FI
RE
A
LA
RM
M
ES
SA
GE
AC
TI
VA
TE
S
TR
OB
ES
AC
TI
VA
TE
A
PP
LIC
AB
LE
R
EC
OR
DE
D
MA
SS
N
OT
IF
IC
AT
IO
N
ME
SS
AG
E
OV
ER
RI
DE
R
EC
OR
DE
D
FI
RE
A
LA
RM
M
ES
SA
GE
OV
ER
RI
DE
R
EC
OR
DE
D
MA
SS
N
OT
IF
IC
AT
IO
N
ME
SS
AG
E
NO
T
US
ED
SE
ND
S
IG
NA
L T
O
BA
S
TO
S
TO
P
FA
N
OF
A
SS
OC
IA
TE
D
AH
U
SE
ND
M
UT
E
SI
GN
AL
T O
PA
S
YS
TE
M
CONTROL UNIT
ANNUNCIATION NOTIFICATION CONTROL
SYSTEM OUTPUTS
INPUT/OUTPUT MATRIX
AC
TI
VA
TE
N
ET
W
OR
K
CO
MM
UN
IC
AT
IO
N
LO
SS
E
RR
OR
M
ES
SA
GE
W
IT
H
PA
NE
L A
DD
RE
SS
T O
AL
L N
ET
W
OR
KE
D
PA
NE
LS
AC
TI
VA
TE
A
LA
RM
M
ES
SA
GE
A
T
CE
NT
RA
L M
ON
IT
OR
IN
G
ST
AT
IO
N
NE
TW
OR
K
PA
NE
L W
IT
H
AD
DR
ES
S
OF
D
EV
IC
E
AC
TI
VA
TE
S
UP
ER
VI
SO
RY
M
ES
SA
GE
A T
CE
NT
RA
L M
ON
IT
OR
IN
G
ST
AT
IO
N
NE
TW
OR
K
PA
NE
L W
IT
H
AD
DR
ES
S
OF
D
EV
IC
E
AC
TI
VA
TE
T
RO
UB
LE
M
ES
SA
GE
A
T
CE
NT
RA
L M
ON
IT
OR
IN
G
ST
AT
IO
N
NE
TW
OR
K
PA
NE
L W
IT
H
AD
DR
ES
S
OF
D
EV
IC
E
X X X X X
RE
CA
LL
E
LE
VA
TO
R
TO
P
RI
MA
RY
LE
VE
L (
LE
VE
L 3
RE
CA
LL
E
LE
VA
TO
R
TO
S
EC
ON
DA
RY
LE
VE
L (
LE
VE
L 2
IN
IT
IA
TE
E
LE
VA
TO
R
PO
W
ER
S
HU
NT
T
RI
P
T U V X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
DUCT-TYPE SMOKE DETECTOR LOCATED AT CONNECTION FROM RETURN AIR PLENUM TO AIR SYSTEM X X X X X X X
X X X
X
SPOT-TYPE SMOKE DETECTOR - IN ELEVATOR HOISTWAY X X X X X X XX X
HEAT DETECTOR X X X X X X XX
NO
T
US
ED
W X
X X XX X
NO
T
US
ED
ASPIRATING SMOKE DETECTION PANEL: POWER SUPPLY TROUBLE
ASPIRATING SMOKE DETECTION PANEL: DETECTION PANEL TROUBLE
ASPIRATING SMOKE DETECTION PANEL: ALERT
ASPIRATING SMOKE DETECTION PANEL: ALARM
X X X X X
X X
X X
X X X
X X X
X X X
X X X
X X X
X X X
X X X
X X
AED CABINET OPEN X X X X
HIGH WATER LEVEL IN ELEVATOR SUMP X X X X
HEAT DETECTOR - ELEVATOR CONTROL CLOSET XX X X X X X X
FACU MICROPHONE ACTIVATED
X XX
FAS SHALL BE GE EDWARDS EST3 TO MATCH SITE STANDARD. THE CONTRACTOR IS
RESPONSIBLE FOR COORDINATION OF SYSTEM REQUIREMENTS WITH ALL CONDITIONS OF
THE BUILDING AND SITE INCLUDING, BUT NOT LIMITED TO, BLIND SPACES, SHELVING, LIGHTS, GRILLES AND DIFFUSERS, PIPING, DUCT WORK, DOORS, WINDOWS, EQUIPMENT PLATFORMS, WALLS (FIRE RATED AND NON-FIRE-RATED), BEAMS, JOISTS, COLUMNS, HVAC EQUIPMENT, ELECTRICAL PANELS AND EQUIPMENT, CEILINGS, AREAS WITHOUT CEILINGS, WALL
CONSTRUCTION, FLOORS AND ALL CONSTRUCTION, EQUIPMENT AND BUILDING
APPURTENANCES.
A.C. POWER CONDUCTORS SUPPLYING POWER TO THE FACU, SUBPANELS, POWER
EXTENDERS, ETC. SHALL BE LABELED, MECHANICALLY SECURED, AND RED-MARKED IN
ACCORDANCE WITH NFPA 72. A MACHINE-PRODUCED LABEL SHALL BE PROVIDED INSIDE THE
DOOR OF EACH ENCLOSURE INDICATING THE LOCATION OF THE CIRCUIT DISCONNECTING
MEANS (PANEL LOCATION, PANEL IDENTIFICATION, AND CIRCUIT IDENTIFICATION).
COORDINATE THE LOCATION AND QUANTITY OF DEDICATED A.C. POWER CIRCUITS WITH THE
ELECTRICAL CONTRACTOR.
CUSTOMIZED AUDIO MESSAGES PROVIDED BY THE OWNER, GIVEN SUFFICIENT TIME TO
HAVE THE MESSAGES RECORDED, SHALL BE INCORPORATED INTO THE SYSTEM; MEMORY
CAPACITY OF FACU SHALL BE UPGRADED AS NECESSARY. FACU SHALL ALSO ACCEPT AND
BE CAPABLE OF BROADCASTING MASS NOTIFICATION MESSAGES RECEIVED FROM CENTRAL
MONITORING SITES. FAS INSTALLER SHALL UPDATE TWO FIREWORKS STATIONS AND MAIN
PANELS WITH GRAPHICS AND MASS NOTIFICATION OUTPUT CHANNELS FOR SERVICE TO THE
BUILDING. FIRE ALARM EVACUATION SIGNAL INTELLIGIBILITY SHALL BE TESTED UTILIZING A
METHOD(S) DESCRIBED IN NFPA 72; FAS INSTALLER SHALL ELIMINATE ALL FEEDBACK ON
AUDIO LOOP BETWEEN MICROPHONE AND SPEAKER CIRCUITS.
WITH RESPECT TO BOTH VISUAL COVERAGE AND AUDIBLE SIGNAL INTELLIGIBILITY, THE
LOCATION AND QUANTITY OF NOTIFICATION DEVICES INDICATED ON THE FIRE PROTECTION
DESIGN DRAWINGS ARE FOR SCHEMATIC / BIDDING PURPOSES ONLY. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR ENSURING ADEQUATE COVERAGE, REGARDLESS IF
ADDITIONAL DEVICES ARE NECESSARY.
END-OF-LINE DEVICES ARE NOT SHOWN AND SHALL BE PROVIDED AS REQUIRED BY THE
SYSTEM MANUFACTURER.
1.
2.
3.
4.
5.
IN ACCORDANCE WITH THE DRAWINGS, SPECIFICATIONS, AND APPLICABLE CODES AND
STANDARDS. FLOW AND TAMPER SWITCHES SHALL BE DISCRETE POINTS; PARALLELING
INPUTS INTO ADDRESSABLE MODULES IS PROHIBITED.
THE FAS SHALL BE INTEGRATED INTO THE SITEWIDE NETWORK AND FIRE ALARM SIGNALS
SHALL BE AUTOMATICALLY TRANSMITTED TO THE SITE CENTRAL MONITORING STATION.
FIBER OPTIC CABLE WILL BE MADE AVAILABLE TO THE FACU BY THE TELECOM CONTRACTOR.
PROVIDE THE FOLLOWING CONNECTIONS INTO THE FACU:
2 PAIRS SINGLE MODE FIBER NETWORK "IN"
2 PAIRS SINGLE MODE FIBER NETWORK "OUT"
ALL INITIATING DEVICES SHALL BE INTELLIGENT / ADDRESSABLE WHERE POSSIBLE.
SEPARATE ADDRESSABLE MONITOR MODULES SHALL BE PROVIDED FOR EACH
CONVENTIONAL INPUT DEVICE SUCH THAT EACH DEVICE IS INDIVIDUALLY INDICATED AT THE
FACU AS A DISTINCT INPUT. ALL INITIATING DEVICES SHALL BE INSTALLED IN ACCORDANCE
WITH MANUFACTURERS INSTRUCTIONS.
THE PATHWAY PERFORMANCE SHALL COMPLY WITH THE NFPA 72 REQUIREMENTS FOR THE
FOLLOWING:
9.1. SIGNALING LINE CIRCUITS (SLC) SHALL BE CLASS A STRANDED COPPER
9.2. NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE CLASS A STRANDED
COPPER
9.3. CIRCUIT SURVIVABILITY SHALL MEET LEVEL 1
9.4. A SINGLE FAULTY DEVICE SHALL NOT COMPROMISE AN ENTIRE LOOP
7.
8.
9.
ALL WIRES SHALL BE CHECKED FOR GROUNDS, SHORTS, OPENS, AND CORRECT RESISTANCE,
CAPACITANCE, AND OTHER APPLICABLE PARAMETERS PRIOR TO TERMINATION OF THE
CIRCUITS AT THE FACU OR SUBPANELS AND PRIOR TO THE INSTALLATION OF DEVICES.
ALL WIRING SHALL BE IN METALLIC CONDUIT. ALL CONDUIT SHALL BE PAINTED RED, 3/4-IN.
MINIMUM. IDENTIFY ALL CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS. ALL FIRE
ALARM JUNCTION BOXES AND COVERS SHALL BE PAINTED RED IN UNFINISHED AREAS.
PULL ALL CONDUCTORS SPLICE FREE; T-TAPS ARE PROHIBITED. THE USE OF WIRE NUTS,
CRIMPED CONNECTORS, OR TWISTING OF CONDUCTORS IS PROHIBITED. ALL TERMINATIONS
MUST BE AT A TERMINAL STRIP WITHIN A FIRE ALARM TERMINAL CABINET OR DEVICE SCREW
TERMINAL. RUN ALL WIRING TO CONTROL PANELS AND OTHER CABINETS IN THE VERTICAL OR
HORIZONTAL PLANE, MAKE ALL TURNS AT 90-DEGREE ANGLES, AND TIGHTLY BUNDLE AND
WRAP ALL WIRE. ALL WIRING MUST BE SOLID COPPER, EXCEPT FOR SPEAKER CIRCUITS OR
CIRCUITS REQUIRING SHIELDING. ALL SLC AND IDC SHALL BE MINIMUM 16-GAUGE. UNDER NO
CIRCUMSTANCES SHALL CONDUCTORS BE SIZED SMALLER THAN THE MANUFACTURERS'
REQUIREMENTS.
ALL FIRE ALARM VISUAL NOTIFICATION APPLIANCES (STROBES) SHALL BE SYNCHRONIZED ON A
MINIMUM PER-FLOOR BASIS. ALL FIRE ALARM VISUAL NOTIFICATION APPLIANCES SHALL BE
MARKED "ALERT" AND SHALL BE PROVIDED WITH CLEAR LENSES. NOTIFICATION APPLIANCES
INSTALLED IN ACOUSTIC TILE CEILINGS SHALL BE CENTERED IN THE TILES.
OTHERWISE.
FIRE ALARM SYSTEM INPUT (MONITORING) AND OUTPUT (CONTROL) MODULES SHALL BE
LOCATED WITHIN 3 FT. OF THE MONITORED / CONTROLLED EQUIPMENT WHERE POSSIBLE.
COORDINATE THE LOCATION OF CEILING MOUNTED SMOKE AND HEAT DETECTORS WITH HVAC
DIFFUSERS AND LIGHTING FIXTURES. SUSPENDED CEILING-MOUNTED DETECTORS SHALL BE
CENTERED IN THE TILE.
ALL SYSTEM SMOKE DETECTORS SHALL BE PROTECTED BY DUST COVERS UP UNTIL THE TIME
OF FINAL ACCEPTANCE TESTING.
10.
11.
12.
13.
14.
15.
16.
17.
MANUAL PULL STATIONS SHALL BE FLUSH-MOUNTED IN FINISHED AREAS AND SURFACE-MOUNTED
LOCATE THE FAS NAC POWER SUPPLIES AS NEEDED, COORDINATE THE AC POWER FOR THE
NAC POWER SUPPLIES WITH THE ELECTRICAL CONTRACTOR.
PROVIDE MONITORED TAMPER SWITCH FOR FIRE ALARM CONTROL UNIT.
SUPERVISION SHALL BE PROVIDED FOR THE SPRINKLER SYSTEM POST INDICATING VALVE
(PIV); SEE CIVIL DRAWING C1.30 FOR PIV LOCATION.
A TOTAL (COMPLETE) COVERAGE SMOKE DETECTION SYSTEM, IN ACCORDANCE WITH NFPA 72,
SHALL BE INSTALLED THROUGHOUT THE BUILDING.
FIRE ALARM SYSTEM SHALL PROVIDE NOTIFICATION SIGNAL TO BAS IN THE EVENT OF ANY
GENERAL BUILDING ALARM CONDITION AND BAS SHALL INITIATE AS REQUIRED VENTILATION
AND AHU SYSTEM SHUT DOWN OPERATIONS. UPON CLEARING OF FIRE ALARMSIGNAL THE BAS
SHALL RETURN TO NORMAL OPERATIONS WITHOUT OPERATOR INTERVENTION.THE BAS
CONTROL PANEL IS LOCATED IN MECHANICAL ROOM 107 ON LEVEL 1.
ISOLATION MODULES SHALL BE PROVIDED AT PENETRATIONS INTO SECURE AREAS AND
TENANT SPACES BOUNDED BY SPECIAL WALLS. SPEAKER CIRCUITS SERVING SECURE AREAS
AND TENANT SPACES SHALL BE CLASS A ORIGINATING FROM THE MODULE AND SHALL BE
CONFINED TO THE AREA WHICH THEY SERVE.
PROVIDE Z-BENDS AT ALL AIR SAMPLING PIPE PENETRATION POINTS INTOSECURE AREAS AND
TENANT SPACES BOUNDED BY SPECIAL WALLS. AIR SAMPLING PIPE NETWORKS SHALL BE
CONFINED TO THE AREA WHICH THEY SERVE.
ALL PENETRATIONS INTO SECURE AREAS AND TENANT SPACES BOUNDED BY SPECIAL WALLS
SHALL BE LIMITED TO THE LOCATIONS IDENTIFIED ON THE DRAWINGS. REFER TO
ARCHITECTURAL DRAWING A0.10 FOR SPECIAL WALL LOCATIONS. CIRCUITS AND PIPING SHALL
NOT BE ROUTED INTO OR THROUGH SECURE AREAS AND TENANT SPACES WHICH THEY DO
NOT SERVE.
18.
19.
20.
21.
22.
23.
24.
25.
converg nt
3650 CONCORDE PARKWAY SUITE-100
CHANTILLY, VA. 20150
CTC 443
OFFICE: (703) 631-7476 - FAX: (703) 330-0086
WWW.CONVERGINT.COM
This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request.
19844 BLUE RIDGE MOUNTAIN RD
BLUMOUNT, VA 20135
SECURE SIDE NON-SECURE SIDE
SPECIAL WALL PARTITION
0'-6" MAX
NOTES:
1. WHERE PIPE SLEEVES ARE USED, COMPLETELY PACK VOID AREAS BETWEEN PIPE AND SLEEVE WITH MINERAL WOOL INSULATION AND SEAL PENETRATION WITH ACOUSTICAL JOINT SEALANT CAULKING.
2. WHERE PIPE DOES NOT COMPLETELY FILL THE WALL OPENING, SEAL PENETRATION WITH ACOUSTICAL
JOINT SEALANT CAULKING.
3. Z-BEND MAY BE INSTALLED VERTICAL OR HORIZONTAL.
4. DETAIL APPLIES TO ALL AIR ASPIRATING SMOKE DETECTOR SAMPLING PIPING ENTERING A SCIF SPACE.
0' -6
" M
AX
PACKING AND SEALANT FOR FIRE RATED CONSTRUCTION WHERE
APPLICABLE - WHERE NO FIRESTOPPING IS REQUIRED PACK SOLID WITH
MINERAL WOOL INSULATION AND SEAL WITH ACOUSTICAL CAULKING
SPECIAL WALL AIR SAMPLING PIPE
Z-BEND DETAIL
VESDA AIR SAMPLING NOTES:
ILLUMINATE BAROGRAPH AND ALERT LED AT VESDA DETECTOR.
A PRE-ALARM CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.
ACTIVATION OF A VESDA ALERT CONDITION SHALL CAUSE:
A TROUBLE SIGNAL SENT TO BUILDING F.A.C.P.
ILLUMINATE BAROGRAPH AND ACTION LED AT VESDA DETECTOR.
ACTIVATION OF A VESDA ACTION CONDITION SHALL CAUSE:
ACTIVATION OF A VESDA FIRE 2 CONDITION SHALL CAUSE:
ILLUMINATE BAROGRAPH AND FIRE 2 LAMP AT VESDA DETECTOR. AN ALARM CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.
ENERGIZE PRE-ACTION SOLENOID.
A PRE-ALARM CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.
ACTIVATION OF A VESDA FIRE 1 CONDITION SHALL CAUSE:
ILLUMINATE BAROGRAPH AND FIRE 1 LAMP AT VESDA DETECTOR.
AN ALARM CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.AN ALARM SIGNAL SENT TO BUILDING F.A.C.P.
A TROUBLE SIGNAL SENT TO BUILDING F.A.C.P.
AN ALARM SIGNAL SENT TO BUILDING F.A.C.P.
HVAC SHUTDOWN AND DAMPER CLOSURE.
SEQUENCE OF OPERATIONS
THIS SEQUENCE SHALL BE POSTED AT THE CONTROL PANEL.
A TROUBLE CONDITION DISPLAYED AT THE "FCP" CONTROL PANEL.
ACTIVATION OF A VESDA FAULT CONDITION SHALL CAUSE:
A TROUBLE SIGNAL SENT TO BUILDING F.A.C.P.
FAULT CONDITION DISPLAYED AT THE VESDA DETECTOR.
ACTIVATION OF A VESDA ALERT CONDITION SHALL CAUSE:
ACTIVATION OF A VESDA ACTION CONDITION SHALL CAUSE:
ACTIVATION OF A VESDA FIRE 2 CONDITION SHALL CAUSE:
ACTIVATION OF A VESDA FIRE 1 CONDITION SHALL CAUSE:
SEQUENCE OF OPERATIONS
ACTIVATION OF A VESDA FAULT CONDITION SHALL CAUSE:
POWER SUPPLY VPS-300US 120
L N G
To 120VAC/60HZ
VPS-300US 120 - POWER SUPPLY
TRANSFORMER
120 VAC
28 VAC
FAULT INDICATOR
BAT +
D C
O U
TPU
TS
L1
L2
VR1
VR2
RL1
C1
C2
C4 C3
-O ut1+
-O ut2+
-O ut3+
FAULT MONITORING
NCNO C
12 Volt/ 12 AMP-HR 12 Volt/ 12 AMP-HR
12 Volt/ 12 AMP-HR 12 Volt/ 12 AMP-HR
12 Volt/ 12 AMP-HR 12 Volt/ 12 AMP-HR
THREE DETECTORS
VBC-001
1ST FLOOR INSTALL (0)
2ND FLOOR INSTALL (1)
3RD FLOOR INSTALL (1)
4TH FLOOR INSTALL (1)
converg nt
3650 CONCORDE PARKWAY SUITE-100
CHANTILLY, VA. 20150
CTC 443
OFFICE: (703) 631-7476 - FAX: (703) 330-0086
WWW.CONVERGINT.COM
This document and the information/depictions contained/shown is the exclusive property of Convergint Technologies LLC and shall be handled as proprietary and confidential information and must be returned upon request.
| Reviewed By: Zach Holder |
| Submitted By: Zach Holder Submittal Date: 8/20/2024 Due Date: 9/3/2024 |
| 2024-08-27T12:46:50-0400 | |