265219.001.00 - Emergency and Exit Lighting - SAMPLE SUBMITTAL MWEOC Std..pdf
PDF 5 MB Posted
- Attached to
- B401 Tenant Buildout
- Solicitation number
- 70FA5026Q00000002
About this file
This document is a submittal package for emergency and exit lighting fixtures for FEMA Building 762, submitted by Valley Lighting, LLC on behalf of Harkins Builders to Warner Construction (Frederick). The package was prepared on December 3, 2023, and reviewed/approved on March 14, 2024, with exceptions noted by M. Wilson (Project Engineer I) and Erick J. Daniels (COTR).
The submittal specifies four fixture types for Specification Section 265219: 137 units of Lithonia Lighting ELM4L emergency lights (Type E, 640 lumens, 3.3 watts per lamp head, LED with 90-minute battery backup and 24-hour recharge time); 5 units of Exitronix S902-WB-SR-RC-AG-G2 exit signs (Type X1, single-face, red letters/clear panel, universal mount, UL 924 listed); 31 units of Exitronix S902-WB-SR-RC-AG-G2 exit signs (Type X2, identical specification to X1); and 7 units of Exitronix S903-WB-SR-RM-AG-G2 double-face exit signs (Type X3, red letters/mirror panel). Key notes indicate the lighting schedule shows 144 Type E fixtures, requiring quantity verification; fixtures must be BAA (Buy America Act) compliant; and remote test kits are required per specification 265219-2.1.F.8. The exit signs feature 90-minute emergency run time, 24-hour recharge capability, and Guardian self-test/self-diagnostics. Cost and delivery schedule information are not included in this product data submittal. GC coordination is required for final quantity and placement based on forthcoming Design Changes (CCD-11, third deck).
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LETTER OF TRANSMITTAL
TO: DATE:
JOB #:
RE:
TO WHOM IT MAY CONCERN:
We are sending you the following items Attached Under Separate Cover, via _______________:
Submittals Specifications Copy of Letter Change Order
Shop Drawings Plans Samples Other-
Date Quantity Description
These are transmitted as checked below:
For Signatures Approved As Submitted Resubmit _____ Copies for Approval
For Your Use Approved As Noted Submit _____ Copies for Distribution
As Requested Returned for Corrections Return _____ Corrected Prints
For Approval For Review and Comment FOR BIDS DUE ON __________
REMARKS:
Signed: _________________________________ Received: __________________________________ cc: file r, Harkins Builders, Inc.
575 E. Swedesford Road Wayne, PA 19087 610.627.4945
HARKINSBUILDERS.COM
Harkins Builders, Inc.
10490 Little Patuxent Parkway Suite 400 Columbia, MD 21044 410-750-2600
3/14/24
12649
265219.001.00 - Emergency and Exit Lighting
Erick Daniels
COR-II
FEMA Bld 762
3/14/24 1 265219.001.00 - Emergency and Exit Lighting Product Data
Please see attached Emergency and Exit Lighting Product Data for your review and approval.
Melissa A Wilson Digitally signed by Melissa A Wilson
DN: C=US,
E=MWilson@harkinsbuilders.com, O="Harkins Builders, Inc", CN=Melissa A Wilson Date: 2024.03.14 12:00:41-04'00'
ERICK J DANIELS
Digitally signed by ERICK J
DANIELS
Date: 2024.08.25 10:00:56 -04'00'
LETTER OF TRANSMITTAL
TO: DATE:
JOB #:
RE:
TO WHOM IT MAY CONCERN:
We are sending you the following items Attached Under Separate Cover, via _______________:
Submittals Specifications Copy of Letter Change Order
Shop Drawings Plans Samples Other-
Date Quantity Description
These are transmitted as checked below:
For Signatures Approved As Submitted Resubmit _____ Copies for Approval
For Your Use Approved As Noted Submit _____ Copies for Distribution
As Requested Returned for Corrections Return _____ Corrected Prints
For Approval For Review and Comment FOR BIDS DUE ON __________
REMARKS:
Signed: _________________________________ Received: __________________________________ cc: file r, Harkins Builders, Inc.
575 E. Swedesford Road Wayne, PA 19087 610.627.4945
HARKINS BUILDERS.COM
Harkins Builders, Inc.
10490 Little Patuxent Parkway Suite 400 Columbia, MD 21044 410-750-2600
Project #:
HBI Job #:
Spec Section:
Submittal #:
Shop Drawings Product Data O&M Data
Sample Warranty Other:_____________
No Exceptions Taken Make Corrections Noted For Information Only
Revise and Re-Submit Rejected Other:_____________
Specified Item Substitute Item Item Not Specified Other:_______________
Or Equal per Specification Per Contract Clarification Owner Approved VE
(Explanation in Notes Below)
Notes:
Reviewed for general conformance with the Contract Documents, including the drawings and specifications. The requirements of the
Contract Documents shall take precedence and govern over any information contained herein. All dimensions shall be verified in the field by the Subcontractor prior to performing the Work.
REVIEWED BY:
TITLE: DATE:
SUBMITTAL REVIEW COMMENTS:
(REVIEWER STAMP HERE)
SUBMITTAL REVIEW STAMP
MOUNT WEATHER
ENGINEERING DIVISION
Approved as submitted.
Approved-Exceptions As Noted.
Revise and Resubmit.
Disapproved, see comments.
Action Not Required.
COTR
Harkins Builders Inc.
Project Engineer I
SubmiƩal
Project
FEMA B762
265219 Emergency and Exit LighƟng
Prepared for
Harkins Builders
12/3/2023
Date: Nov 29, 2023
Valley Lighting, LLC 601-U Hammonds Ferry Rd.
Linthicum MD 21090 Phone: (410) 636-6010 Fax: (410) 636-6136
Job Name
MOUNT WEATHER BUILDING 762
SPEC SECTION 265219 - EMERGENCY AND EXIT LIGHTING
Contractor:
Warner Construction 1530 Tilco Dr, Suite A Frederick MD 21704
Nov 29, 2023
Warner Construction 1530 Tilco Dr, Suite A Frederick MD 21704
RE: MOUNT WEATHER BLDG 762
SPEC SECTION 265219 - EMERGENCY AND EXIT LIGHTING
Qty Type MFG Part 137 E Lithonia Lighting ELM4L
5 X1 EXITRONIX S902-WB-SR-RC-AG-G2
31 X2 EXITRONIX S902-WB-SR-RC-AG-G2
7 X3 EXITRONIX S903-WB-SR-RM-AG-G2
HBI: Light Fixture Type E has 144 fixtures shown on lighting schedule (E6.01), Verify quantity prior to ordering edanie11 Text Box GC to coordinate QTY and placement based on forthcoming CCD-11 (3rd Deck Design Changes)
Submitted by Valley Lighting, LLC
Job Name:
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
ELM4L
Notes:
Type:
E
VL23-717
Pg. 1 of 5
Specifications
Length: 13 3/8 (33.95)
Depth: 3 45/64 (9.39)
Height: 5 15/16 (15.06)
Weight: ELM4L 3 lb (1.4kg)
Weight: ELM6L 3 lb (1.4kg)
Weight: ELM6L HO 3.5 lbs (1.59 kg)
Weight: ELM6L EHO 3.75 lbs (1.7 kg)
3.70 (9.39)
5.93 (15.06)
13.37 (33.95)
5.93 (15.06)
3.70 (9.39)
13.37 (33.95)
5.93 (15.06)
11.26 (28.60)
Catalog Number
Notes
Type
FEATURES & SPECIFICATIONS
INTENDED USE — Provides a minimum of 90 minutes illumination for the rated wattage upon loss of AC power to meet and exceed code required emergency lighting. Ideal for applications requiring attractive LED unit equipment with quick installation and unparalleled performance for mounting heights from 7.5’ to 30’. Certain airborne contaminants can diminish the integrity of acrylic and/or polycarbonate.
Click here for Acrylic-Polycarbonate Compatibility table for suitable uses.
CONSTRUCTION — The housing is a standard white (black optional) thermoplastic with a compact and low-profile contemporary design. It is 5VA flame rated, impact-resistant, scratch-resistant and corrosion proof. The UV-stable resin resists discoloration from natural and man-made light sources. There is a low-profile, integrated and back-lit test switch with an easily visible multi-color LED status indicator. The back-plate contains a universal j-box mounting pattern to facilitate ease of installation on a wide variety of j-boxes and the front housing allows tool-less access for ease of maintenance.
The lamp heads have a unique track-and-swivel arrangement permitting full range of direction of optical aiming.
OPTICS — The ELM4L features two high-performance LEDs rated at 3.3 watts per lamp head and delivers a total of 640 lumens in a spot pattern (SP640L).
The ELM6L features three high-performance LEDs rated at 5.3 watts per lamp head and delivers a total of 1,100 lumens in a spot pattern (SP1100L).
The typical life of an LED is 10 years. The LED light sources typically never need to be replaced under normal conditions for normal off applications.
CCT: 5000K
ELECTRICAL — Orderable in multiple voltages (see ordering tree for specific voltages.)
Current-limiting charger maximizes battery life and minimizes energy consumption to provide low operating costs. Small battery chargers Certified in the CA Title 20 Appliance Efficiency Database.
Short-circuit protection — current-limiting charger circuitry protects printed circuit board from shorts.
Regulated charge voltage maintains a stable charge voltage over a wide range of line voltages.
Prevents over/undercharging that shortens battery life and reduces capacity. Filtered charger input minimizes charge voltage ripple and extends battery life.
BATTERY: Sealed, maintenance-free nickel-cadmium (ELM4L only) or Lithium Iron Phosphate battery. Optional High-Output (HO option) and Extra High Output (EHO option), LTP battery type only, provides a wide variety of remote capacities and/or extended run-times.
Automatic 24-hour recharge after a 90-minute discharge.
Advanced electrical design provides constant light output throughout the entire discharge period.
Brownout protection is automatically switched to emergency mode when supply voltage drops below approxi-mately 80 percent nominal of 120, 220, 277 or 347. Other input voltages may vary.
AC/LVD reset allows battery connection before AC power is applied and prevents battery damage from deep discharge.
Self-Diagnostics: Continuously monitors AC functionality. Test switch and remote tester (RTKIT accessory) provide manual activation of 30-second diagnostic testing for on-demand visual inspection. Standard derangement monitoring will indicate disconnected battery, charger failure and displays green flashing indicator light while in emergency mode. Single multi-chromatic LED indicator to display two-state charging, test activation and three-state self-diagnostics.
SELF-DIAGNOSTICS and REMOTE TEST (SDRT and AELR option):
Self-diagnostic testing: Five minutes every 30 days and 90 minutes annually. Diagnostic evaluation of lamps, AC to DC transfer, battery charging and condition of microprocessor. Automatic test is easily postponed for eight hours by activating manual test switch or use of remote tester (RTKIT accessory).
AELR option: STAR (Self-testing Automated Reporting) radio transmits monthly and annual test results and diagnostics information for automated reporting requirements.
For more information visit AcuityBrands.com/STAR INSTALLATION — Wall and ceiling mount standard. Blind-mate connector ensures easy installation and safe maintenance. 7/8" entrance provision at top of unit for standard 1/2" conduit entry. Tool-less removal of front cover from back-plate for ease of installation and maintenance.
LISTINGS — UL damp location listed standard and wet location listed when used with the WPVS accessory, all at 50-104°F (10-40°C). Meets or exceeds all applicable requirements for UL 924, NFPA 101 (current Life Safety code), NFPA 70 (NEC), NOM (Norma Oficial Mexicana), California Energy Commission Title 20 section
1605.3 (W)(4), FCC Title 47, Part 15, Subpart B and OSHA. List and labeled to comply with Canadian Standards C22.2 No. 141-10.
BUY AMERICAN ACT — Product with the BAA option is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT regulations.
Please refer to www.acuitybrands.com/buy-american for additional information.
WARRANTY — 5-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed.
Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions NOTE: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specifications subject to change without notice.
Contemporary Commercial LED Emergency Light
ELM4L
640 Lumens
ELM6L
1100 Lumens
LITHIUM IRON PHOSPHATE
NICKEL CADMIUM
EMERGENCY ELM4L_ELM6L
MOUNTING
All dimensions are inches (centimeters) unless otherwise indicated.
TM
† Small Battery Chargers Certified in the CA Title 20 Appliance Efficiency Database.
Index Page
265219-2.2 pmarsha6 Highlight
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
ELM4L
Notes:
Type:
E
VL23-717
ELM4L-ELM6L Quantum® LED Contemporary Commercial Emergency Light
ELM4L_ELM6L
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 1-800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 2018-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22 Pg. 2 of 5
Other Accessories: Order as separate catalog number.
WPVS LRG W Wet protective vandal shield, white (must be used for wet location applications) WPVS LRG B Wet protective vandal shield, black (must be used for wet location applications) ELA WG1 Wireguard, 13 3/4"H x 15 1/4"W x 6"D (see spec sheet ELA-WG).
RTKIT Remote test kit, up to 40' away (includes goggles, laser and battery)
Series Lamp Type Housing Color Voltage Battery Type Automatic Testing Options
ELM4L1 640 lumens, adjustable optics
(blank) SP640L 640 lumen, 6.6 watt, Spot Pattern, two lamp
(blank) White B Black
(blank) 120-277 VAC, 50/60Hz UVOLT 120 - 347 VAC, 50/60Hz
(blank) Nicad (blank) None (blank) none WPVS Wet protective vandal shield 2
BAA Buy America(n) Act Compliant
PM Pendant Mount 3
Series1 Lamp Type Housing Color Voltage Battery Type Automatic Testing Options
ELM4L 640 lumens, adjustable optics
ELM6L 1100 lumens, adjustable optics
(blank) SP640L 640 lumen,
6.6 watt, Spot Pattern, two lamp
(blank) SP1100L 1100 lumen,
10.6 watt, Spot Pattern, two lamp
(blank) White B Black
UVOLT 120 - 347 VAC,
50/60Hz
LTP Lithium Iron Phosphate
(blank) none 2
SDRT Self-diagnostics, remote test
AELR Automated Emergency Lighting Reporting 3
LLH Less lamp heads 4
HO High-output battery EHO Extra High-output battery WPVS Wet protective vandal shield 5
BAA Buy America(n) Act Compliant
PM Pendant mount 6
ORDERING INFORMATION For shortest lead times, configure product using bolded options.
ORDERING INFORMATION For shortest lead times, configure product using bolded options.
Example: ELM4L
Example: ELM6L UVOLT LTP SDRT
Notes
1 Does not support remote loads.
2 Must be ordered when using for wet location applications.. WPVS breaks out and ships separately and color will match (ex: WPVS LRG B). Decreases delivered lumens up to 20%. See spec sheet WPVS for more information.
3 Pendant mount option will include a 12" long 3/8-16 UNC threaded rod and hardware. Not available with any other lengths.
Notes
1 Extended run-time or remote capacity is standard. New ELMRE and ELMRW style remotes are compatible with both SDRT and non-SDRT versions (see page 4).
2 Only available with ELM4L.
3 SDRT option required. AELR radio transmits monthly and annual test results and diagnostics information for automated reporting requirements. Only available with LTP battery type. Not available with BAA option.
4 ELM4L with LLH (less lamp heads) not available with SDRT. ELM6L with LLH only available with SDRT.
5 Must be ordered when using for wet location applications. WPVS breaks out and ships separately and color will match (ex:
WPVS LRG B). Decreases delivered lumens up to 20%. See spec sheet WPVS for more information.
6 Pendant mount option will include a 12" long 3/8-16 UNC threaded rod and hardware. Not available with any other lengths.
NICKEL CADMIUM BATTERY MODELS
LITHIUM IRON PHOSPHATE BATTERY MODELS
ELM4L-ELM6L mounted inside the WPVS
Looking for Contractor Select readily available configurations? Click here to visit Contractor Select™ spec sheet or go to www.contractorselect.com
Index Page
HBI: Provide remote test kit per 265219-2.1.F.8
HBI: Provide BAA compliant fixtures
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
ELM4L
Notes:
Type:
E
VL23-717
ELM4L-ELM6L Quantum® LED Contemporary Commercial Emergency Light
ELM4L_ELM6L
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 1-800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 2018-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22 Pg. 3 of 5
*Note: To see complete photometric report or download the .ies file for this product, visit Lithonia Lighting ELM4L and ELM6L home page.
SPACING GUIDELINES
Example of single ELM6L illuminating a 3' path of egress
Example of multiple ELM6L units illuminating a 3' path of egress
76'
1 FC average
3'
7.5
3'
98'
1 FC average
Maximum Spacing Guidelines — ELM4L 1
Mounting Height
Illumination Level
Single Luminaire Multiple Luminaire Application
Notes3' Path of Egress
6' Path of Egress
3' Path of Egress
6' Path of Egress
7.5' 1FC Avg 1 62' 58' 67' 60' 100'Corridor, 8' wide, and 12' high with
80/50/20 reflectances
10' 1FC Avg 1 62' 58' 67' 60'
7.5' 1FC Avg 1 52' 40' 66' 58'
Retail open area: 200' X
15' X 30' with 80/50/20 reflectances
10' 1FC Avg 1 52' 48' 64' 60'
12' 1FC Avg 1 52' 48' 62' 59'
16' 1FC Avg 1 52' 44' 61' 58'
20' 1FC Avg 1 44' 42' 60' 58'
24' 1FC Avg 1 34' 34' 42' 58'
Maximum Spacing Guidelines — ELM6L 1
Mounting Height
Illumination Level
Single Luminaire Multiple Luminaire Application
Notes3' Path of Egress
6' Path of Egress
3' Path of Egress
6' Path of Egress
7.5' 1FC Avg 1 76' 74' 98' 90' 100' Corridor, 8' wide, and 12' high with
80/50/20 reflectances
10' 1FC Avg 1 76' 74' 98' 88'
7.5' 1FC Avg 1 60' 48' 77' 68'
Retail open area: 200' X
15' X 30' with 80/50/20 reflectances
10' 1FC Avg 1 78' 56' 85' 82'
12' 1FC Avg 1 68' 66' 77' 74'
16' 1FC Avg 1 72' 68' 72' 74'
20' 1FC Avg 1 66' 64' 70' 68'
24' 1FC Avg 1 66' 56' 65' 62'
Notes:
1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ration of 40:1.
Index Page
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
ELM4L
Notes:
Type:
E
VL23-717
ELM4L-ELM6L Quantum® LED Contemporary Commercial Emergency Light
ELM4L_ELM6L
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 1-800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 2018-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22 Pg. 4 of 5
REMOTES
Notes
| 1 | Compatible with SDRT and non-SDRT versions. |
| 2 | Order the WPVS accessory for wet location listing and vandal protection. |
| 3 | See ELMRW Spec sheet for color options. Available in aluminum glossy, white glossy, black glossy, and dark |
bronze textured.
Notes
| 1 | These are in addition to the lamp heads on the product. |
| 2 | ELMRW not available with SP1100L lamp type. For SP1100L wet location applications, order ELMRE with WPVS. |
BATTERY CAPACITY AND LOADING
Battery Option (LTP Only) Battery Voltage Total Capacity 90 Minutes LP220L (1.2 Watts each) Maximum
# Remote Lamps1 SP640L (3.3 Watts each)
Maximum # Remote Lamps1 SP1100L (5.3 Watts each)
Maximum # Remote Lamps1,2
ELM4L LLH LTP 9.6V 11 watts 9 3 2
ELM4L LLH HO 9.6V 22 watts 18 6 4
ELM4L LLH EHO 12.8V 32 watts 26 9 6
ELM4L LTP 9.6V 11 watts 3 1 0
ELM4L LTP HO 9.6V 22 watts 12 4 2
ELM4L LTP EHO 12.8V 32 watts 21 7 6
ELM6L LTP 9.6V 11 watts 0 0 0
ELM6L LTP HO 9.6V 22 watts 9 3 2
ELM6L LTP EHO 12.8V 32 watts 17 6 4
ELM6L LLH LTP 9.6V 11 watts 9 3 2
ELM6L LLH LTP HO 9.6V 22 watts 18 6 4
ELM6L LLH LTP EHO 12.8V 32 watts 26 9 6
ELMRE Compatible Remotes1,2
LTP Compatible Remote Accessories: Order as separate catalog number.
ELMRE LP220L SGL 1,2 Single LED Indoor remote head, white.
ELMRE LP220L T 1,2 Twin LED Indoor remote heads, white.
ELMRE SP640L SGL 1,2 Single LED Indoor remote head, white.
ELMRE SP640L T 1,2 Twin LED Indoor remote heads, white.
ELMRE SP1100L SGL 1,2 Single LED Indoor remote head, white.
ELMRE SP1100L T 1,2 Twin LED Indoor remote heads, white.
ELMRW LP220L DDBTXD SGL 1,3 Single LED Wet Location remote head, dark bronze, 110 lumens ELMRW LP220L DDBTXD T 1,3 Twin LED Wet Location remote heads, dark bronze, 220 lumens ELMRW SP640L DDBTXD SGL 1,3 Single LED Wet Location remote head, dark bronze, 320 lumens ELMRW SP640L DDBTXD T 1,3 Twin LED Wet Location remote heads, dark bronze, 640 lumens
ELMRE LP220L SGL ELMRE SP640L SGL ELMRE SP100L SGLELMRE LP220L T ELMRE SP640L T ELMRE SP1100L T
ELMRW LP220L DDBTXD SGL ELMRW LP220L DDBTXD T ELMRW SP640L DDBTXD SGL ELMRW SP640L DDBTXD T
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
ELM4L
Notes:
Type:
E
VL23-717
ELM4L-ELM6L Quantum® LED Contemporary Commercial Emergency Light
ELM4L_ELM6L
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 1-800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 2018-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/08/22 Pg. 5 of 5
SPECIFICATIONS
Notes
1 At 77°F ambient temperature, charge/discharge cycles and prolonged full discharge may reduce useful life.
2 All life safety equipment, including emergency lighting for path of egress must be tested in accordance with all National Fire Protection Association (NFPA) and local codes. Failure to perform the required testing could jeopardize the safety of occupants and will void all warranties.
3 Temperature range where unit will provide capacity for 90 minutes. Higher and lower temperatures affect life and capacity.
4 Battery life is negatively impacted by many variables including temperature, charging rates, number of cycles and deep discharges due to long periods of time without AC power.
ELECTRICAL
Primary Circuit
Type Volts Input amps Watts
Nicad 120 0.032 3.15
347 0.036 3.15
Lithium Iron Phosphate
(SDRT)
120 0.028 2.78
347 0.033 2.78
Lithium Iron Phosphate (HO option)
120 0.046 4.77
347 0.046 4.77
Lithium Iron Phosphate
(EHO option)
120 0.052 5.95
347 0.045 5.95
BATTERY
Nicad (6V)
Typical Shelf life1 Typical life1 Maintenance2 Temperature range3,4
3 years 6-8 years none 50-104°F (10-40°C)
Lithium Iron Phosphate (standard and HO option) (9.6V)
Typical Shelf life1 Typical life1 Maintenance2 Temperature range3,4
1 year 6-8 years none 50-104°F (10-40°C)
Lithium Iron Phosphate (EHO option) (12.8V)
Typical Shelf life1 Typical life1 Maintenance2 Temperature range3,4
1 year 6-8 years none 50-104°F (10-40°C)
BATTERY CAPACITY FOR EXTENDED RUN-TIMES
Battery Option
Total Capacity 2 hours
Remote Capacity 2 hours*
Total Capacity 4 hours
Remote Capacity 4 hours*
ELM4L - LTP 8.25 watts NA NA NA
ELM4L - HO 16.5 watts 9.9 watts 8.25 watts NA
ELM4L EHO 24 watts 17.4 watts 12 watts 5.4 watts
ELM6L - LTP 8.25 watts** 8.25 watts** NA NA
ELM6L HO 16.5 watts 5.9 watts 8.25 watts** 8.25 watts**
ELM6L EHO 24 watts 13.4 watts 12 watts 12 watts**
* Remote capacity left after using standard lamps shipped mounted on luminiare. ELM4L standard high performance LED lamp heads are rated at 3.3 watts each, delivering a total of 640 lumens. ELM6L standard high performance LED lamp heads are rated at 5.3 watts each, delivering a total of 1,100 lumens. These lamps are different in both wattage and performance from the LT24 compatible remotes.
** LLH option only
INDOOR PHOTOMETRIC REPORT
CATALOG: ELM4L
Test #: ISF 36302 Test Lab: ACUITY BRANDS LIGHTING, DECATUR LAB Test Date: 10/9/2017 Catalog: ELM4L Description: ELM4L SP640L Series: ELM4L Emergency Light Lamp Catalog: ELP L372 Lamp: ONE 3.3-WATT LED Lamp Output: Total luminaire Lumens: 344.8, absolute photometry * Input Wattage: 2.5 Luminous Opening: Circular (Dia: 1.8") Cie Class: Direct Max Cd: 697.0 at Horizontal: 45°, Vertical: 2.5° Spacing Criterion: @ 0 = 0.53 / @ 90 = 0.52
*Test based on absolute photometry where lamp lumens=lumens total.
*Cutoff Classification and efficiency cannot be properly calculated for absolute photometry.
Visual Photometric Tool 1.2.46 copyright 2024, Acuity Brands Lighting.
This Photometric report has been generated using methods recommended by the IESNA. Calculations are based on Photometric data provided by the manufacturer, and the accuracy of this Photometric report is dependent on the accuracy of the data provided. End-user environment and application (including, but not limited to, voltage variation and dirt accumulation) can cause actual Photometric performance to differ from the performance calculated using the data provided by the manufacturer. This report is provided without warranty as to accuracy, completeness, reliability or otherwise. In no event will Acuity Brands Lighting be responsible for any loss resulting from any use of this report.
ISF 36302
VISUAL PHOTOMETRIC TOOL PAGE 1 OF 3
Zonal Lumen Summary Zone Lumens % Luminaire 0-30 226.4 65.7% 0-40 268.5 77.9% 0-60 315.2 91.4% 60-90 29.5 8.6% 70-100 13.9 4% 90-120 0.1 0% 0-90 344.7 100% 90-180 0.1 0% 0-180 344.8 100%
Lumens Per Zone Zone Lumens % Total Zone Lumens % Total 0-10 58.5 17.0% 90-100 0.1 0% 10-20 100.6 29.2% 100-110 0.000 0% 20-30 67.3 19.5% 110-120 0.000 0% 30-40 42.0 12.2% 120-130 0.000 0% 40-50 26.7 7.8% 130-140 0.000 0% 50-60 20.0 5.8% 140-150 0.000 0% 60-70 15.7 4.6% 150-160 0.000 0% 70-80 10.5 3.0% 160-170 0.000 0% 80-90 3.3 1.0% 170-180 0.000 0%
Average Luminance (Cd/m2) 0 45 90 135 180 225 270 315 360
0 418460 418460 418460 418460 418460 418460 418460 418460 418460 45 29288 33595 34457 31872 27565 24120 24120 27565 29288 55 23363 25487 26549 26549 22301 21239 19115 23363 23363 65 24502 25943 21619 23061 18737 20178 23061 27384 24502 75 30595 28241 21181 18827 16474 18827 23534 30595 30595 85 27955 34944 20966 13978 6989 6989 13978 27955 27955
Coefficients Of Utilization - Zonal Cavity Method Effective Floor Cavity Reflectance: 20%
RCC %: 80 70 50 30 10 0
RW %:
RCR: 0
70 50 30 0
1.19 1.19 1.19 1.19
1.12 1.09 1.06 1.03
1.06 1.00 .95 .91
1.00 .93 .87 .82 .95 .86 .80 .75 .90 .81 .74 .70 .85 .76 .70 .65 .81 .72 .65 .61 .78 .68 .62 .58 .75 .65 .59 .55 .72 .62 .56 .52
70 50 30 0
1.16 1.16 1.16 1.00
1.10 1.07 1.04 .91
1.03 .98 .94 .84 .98 .91 .86 .77 .93 .85 .79 .72 .88 .80 .74 .67 .84 .75 .69 .63 .80 .71 .65 .60 .77 .67 .62 .57 .73 .64 .58 .54 .70 .61 .56 .51
50 30 20
1.11 1.11 1.11
1.03 1.00 .98 .95 .91 .88 .88 .84 .80 .83 .78 .74 .78 .73 .69 .74 .68 .64 .70 .64 .61 .66 .61 .57 .63 .58 .54 .60 .55 .52
50 30 20
1.06 1.06 1.06 .99 .97 .95 .92 .89 .86 .86 .82 .79 .81 .77 .73 .76 .72 .68 .72 .67 .64 .69 .64 .60 .65 .61 .57 .62 .58 .54 .60 .55 .52
50 30 20
1.02 1.02 1.02 .95 .94 .93 .89 .87 .85 .84 .81 .78 .79 .75 .72 .75 .71 .68 .71 .67 .63 .67 .63 .60 .64 .60 .57 .62 .57 .54 .59 .55 .51
1.00 .91 .83 .76 .71 .66 .62 .58 .55 .53 .50
VISUAL PHOTOMETRIC TOOL PAGE 2 OF 3
Candela Table - Type C 0 22.5 45 67.5 90 112.5 135 157.5 180 202.5 225 247.5 270 292.5 315 337.5 360 0 687 687 687 687 687 687 687 687 687 687 687 687 687 687 687 687 687 5 675 680 691 693 689 673 659 648 637 626 621 618 616 632 652 672 675
10 573 596 633 646 624 607 573 517 489 463 447 430 432 462 518 591 573 15 377 421 479 517 489 459 392 344 307 277 259 269 280 297 327 388 377 20 238 265 288 319 300 253 222 202 185 166 163 168 180 193 206 231 238 25 157 164 170 182 169 155 145 128 123 114 110 116 126 134 140 153 157 30 108 113 114 114 112 103 96 84 82 77 74 81 88 94 100 108 108 35 75 78 80 80 77 70 62 56 55 50 49 53 60 65 71 77 75 40 50 52 54 56 54 50 46 43 41 37 36 36 39 43 46 50 50 45 34 36 39 42 40 39 37 34 32 29 28 28 28 30 32 34 34 50 26 27 30 33 32 31 30 28 26 24 23 22 22 23 25 27 26 55 22 22 24 26 25 25 25 22 21 20 20 19 18 20 22 23 22 60 19 19 21 21 19 19 20 18 16 16 17 17 17 19 20 21 19 65 17 17 18 17 15 15 16 14 13 13 14 15 16 17 19 19 17 70 15 15 15 14 12 11 12 11 10 11 12 13 13 15 16 17 15 75 13 12 12 11 9 8 8 7 7 8 8 9 10 12 13 14 13 80 9 9 9 8 6 5 5 4 4 4 4 5 5 7 9 10 9 85 4 5 5 5 3 2 2 1 1 1 1 1 2 3 4 5 4 90 1 1 1 1 1 0 0 0 0 0 0 0 0 0 1 1 1 95 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
100 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 105 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 110 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 115 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 120 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 125 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 130 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 135 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 140 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 145 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 150 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 155 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 160 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 165 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 170 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 175 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 180 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
VISUAL PHOTOMETRIC TOOL PAGE 3 OF 3
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
S902-WB-SR-RC-AG-G2
Notes:
Type:
X1
VL23-717
Specifications are subject to change without notice.
Installation must be performed in accordance with Barron Lighting Group installation instructions.
800.533.3948 • barronltg.comPage 1 of 2
S900 Series Universal Swivel Mount LED Edge-Lit Exit
10800157 Rev 27
FEATURES & BENEFITS
| • | Suitable for installation in existing drywall applications |
| • | S900U option includes both single- and double-face panel configurations |
| • | Includes surface mounting canopy as well as bracket for recessed mounting |
applications
| • | UL 924 Listed 90 minute emergency run time, 24 hour recharge time |
| • | Field-selectable directional chevrons |
| • | UL Listed for Damp Locations |
| • | California Energy Commission (CEC) compliant |
The Exitronix S900 Series LED Edge-lit Exit features a pivoting design for simple installation in any application, including surface and recessed wall, ceiling and sloped ceilings. Includes surface mounting canopy as well as hardware for recessed mounting applications, making this the most versatile Edge-lit sign available. The S900U option includes both single- and double-face configurations for easy ordering and stocking.
SPECIFICATIONS
Illumination: Long-life, high-intensity, red or green LEDs Construction: Extruded aluminum housing with high-grade, acrylic panel Input: 120/277VAC Dual Primary, 60Hz Battery: Maintenance-free NiCad battery Operating Temp: 0°C to 40°C (32°F to 104°F) Run Time: UL Listed 90 minute emergency run time, 24 hour recharge time Mounting: Ceiling and end surface mounting or recessed Finish: Brushed aluminum, black or white Certfications: UL Listed for Damp Locations, meets or exceeds
CEC, NEC and NFPA 101 Warranty: Any component that fails due to a manufacturing defect is guaranteed for three years with a separate two year prorated warranty on the battery. The warranty does not cover physical damage, abuse or instances of uncontrollable natural forces. See the full Exitronix warranty document for detailed information.
ORDERING INFORMATION Example: S902-WB-SR-RC-AG-G2 Series Power Source Mounting Panel Finish S902 = Single-face LB = AC Only SR3 = Universal Single-face Double-face AG = Brushed Aluminum (gray endcaps) S903 = Double-face WB = With Battery GC = Green Letters/Clear Panel GM = Green Letters/Mirror Panel BL4 = Black S900U1 = Universal GM = Green Letters/Mirror Panel RM = Red Letters/Mirror Panel WH = White S900UM2 = Universal RC = Red Letters/Clear Panel Universal
RM = Red Letters/Mirror Panel G = Green Options (Factory Installed) R = Red G25 = Self-test/Self-diagnostics
Notes 1 Includes one single-face clear and one double-face mirrored panel in selected colors Accessories6 (Field Installed) 2 Includes one single-face mirror and one double-face mirror panel (Consult factory for LB configurations) ER1-Kit = 1' Pendant Mount Kit 3 SR includes kits for surface & recessed mounting ER2-Kit = 2' Pendant Mount Kit 4 Consult factory for availability S900U-G-FP = Green Single Mirror Panel for S900U only 5 Not available on LB configurations S900U-R-FP = Red Single Mirror Panel for S900U only 6 Order as separate line item S900-PENDANT-ADAPTER = Pendant Adapter
265219-2.3
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
S902-WB-SR-RC-AG-G2
Notes:
Type:
X1
VL23-717
Specifications are subject to change without notice.
Installation must be performed in accordance with Barron Lighting Group installation instructions.
800.533.3948 • barronltg.comPage 2 of 2
CONSTRUCTION
Housing Available in either a Black, Brushed Aluminum or White finish.
Surface - Engineering grade aluminum extrusion with mounting canopy.
Recessed - Extruded aluminum housing supplied with galvanized steel adjustable bar hanger assembly.
Panels Constructed of clear acrylic. Stencil letters are 6” high with 3/4” stroke, with minimum of 100' viewing distance rating as required by UL 924 standard.
Double-face panels are supplied with a mirror insert. Units are supplied with field-selectable directional chevrons for placement in all applications.
ILLUMINATION
High-output red or green LEDs provide superior brightness. Energy consumption of less than 3W for AC only and less than 5W for battery back-up units. LEDs are a maintenance-free solution, providing up to 100,000 hours of use without failure.
ELECTRICAL
Input Dual-voltage input 120 or 277VAC at 60Hz.
Nickel Cadmium Battery - NiCad (With Battery Only) Exitronix NiCad batteries are maintenance-free.
Emergency (WB Only) The CSXE Series exit will operate for a minimum of 90 minutes during a loss of power with a 24 hour maximum recharge time for the battery.
Solid-State Transfer The circuit features solid-state switching, eliminating concerns of damaged contact or mechanical failures associated with relays. The switching circuit detects a loss of line voltage and automatically switches to emergency mode.
Low Voltage Disconnect When the battery’s terminal voltage falls below predetermined levels, the low voltage circuit disconnects the emergency lighting load. The disconnect remains in effect until normal power is restored, preventing deep battery discharge and improving the life of the battery. The disconnect will also automatically reconnect the load circuit once the battery voltage returns to a normal value after charging.
Test Button Test button is easy to locate and allows for manual verification of proper operation of the transfer circuit and emergency lamps.
INSTALLATION
Surface Mounting: completely universal canopy provides for end or ceiling mounting. All hardware is included.
Recessed Mounting: recessed ceiling mount, accessible above the plenum.
Electronics and battery contained in housing. Plug-in battery connector supplied for easy installation. All hardware is included.
OPTIONS
Guardian Self-test/Self-diagnostics (Option: G2) The Guardian circuit continuously monitors the operating condition of the AC power, battery supply voltage and charging circuit.
The purpose of this option is to provide visual signaling in response to a fault at the EXIT sign battery and/or battery charger. If a failure is detected, visual status will occur immediately via the dual color LED. Refer to instruction manual for detailed information.
The Guardian circuit also monitors the transfer circuit as well as performing automatic code compliance testing.
CONFORMANCE TO CODES AND STANDARDS
The S900 Series is UL 924 Listed for Damp Locations. The series meets or exceeds the CEC and NEC requirements as well as NFPA 101.
DIMENSIONS
14.5” 4.4”
11.5”
11.8”
10.2”
4.3”
12.4”
11.4”
11.8” 3.4”
9.7”
10.2”
4.3”
12.4”
11.4”
11.8” 3.4”
9.7”
PENDANT ADAPTER
10800157 Rev 27
Index Page
HBI Note: Light Fixture Schedule (E6.01) shows wattage for exit signs as 3 watts. Manufacturer product data shows battery backup consumes 5 watts.
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
S902-WB-SR-RC-AG-G2
Notes:
Type:
X2
VL23-717
Specifications are subject to change without notice.
Installation must be performed in accordance with Barron Lighting Group installation instructions.
800.533.3948 • barronltg.comPage 1 of 2
S900 Series Universal Swivel Mount LED Edge-Lit Exit
10800157 Rev 27
FEATURES & BENEFITS
| • | Suitable for installation in existing drywall applications |
| • | S900U option includes both single- and double-face panel configurations |
| • | Includes surface mounting canopy as well as bracket for recessed mounting |
applications
| • | UL 924 Listed 90 minute emergency run time, 24 hour recharge time |
| • | Field-selectable directional chevrons |
| • | UL Listed for Damp Locations |
| • | California Energy Commission (CEC) compliant |
The Exitronix S900 Series LED Edge-lit Exit features a pivoting design for simple installation in any application, including surface and recessed wall, ceiling and sloped ceilings. Includes surface mounting canopy as well as hardware for recessed mounting applications, making this the most versatile Edge-lit sign available. The S900U option includes both single- and double-face configurations for easy ordering and stocking.
SPECIFICATIONS
Illumination: Long-life, high-intensity, red or green LEDs Construction: Extruded aluminum housing with high-grade, acrylic panel Input: 120/277VAC Dual Primary, 60Hz Battery: Maintenance-free NiCad battery Operating Temp: 0°C to 40°C (32°F to 104°F) Run Time: UL Listed 90 minute emergency run time, 24 hour recharge time Mounting: Ceiling and end surface mounting or recessed Finish: Brushed aluminum, black or white Certfications: UL Listed for Damp Locations, meets or exceeds
CEC, NEC and NFPA 101 Warranty: Any component that fails due to a manufacturing defect is guaranteed for three years with a separate two year prorated warranty on the battery. The warranty does not cover physical damage, abuse or instances of uncontrollable natural forces. See the full Exitronix warranty document for detailed information.
ORDERING INFORMATION Example: S902-WB-SR-RC-AG-G2 Series Power Source Mounting Panel Finish S902 = Single-face LB = AC Only SR3 = Universal Single-face Double-face AG = Brushed Aluminum (gray endcaps) S903 = Double-face WB = With Battery GC = Green Letters/Clear Panel GM = Green Letters/Mirror Panel BL4 = Black S900U1 = Universal GM = Green Letters/Mirror Panel RM = Red Letters/Mirror Panel WH = White S900UM2 = Universal RC = Red Letters/Clear Panel Universal
RM = Red Letters/Mirror Panel G = Green Options (Factory Installed) R = Red G25 = Self-test/Self-diagnostics
Notes 1 Includes one single-face clear and one double-face mirrored panel in selected colors Accessories6 (Field Installed) 2 Includes one single-face mirror and one double-face mirror panel (Consult factory for LB configurations) ER1-Kit = 1' Pendant Mount Kit 3 SR includes kits for surface & recessed mounting ER2-Kit = 2' Pendant Mount Kit 4 Consult factory for availability S900U-G-FP = Green Single Mirror Panel for S900U only 5 Not available on LB configurations S900U-R-FP = Red Single Mirror Panel for S900U only 6 Order as separate line item S900-PENDANT-ADAPTER = Pendant Adapter
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
S902-WB-SR-RC-AG-G2
Notes:
Type:
X2
VL23-717
Specifications are subject to change without notice.
Installation must be performed in accordance with Barron Lighting Group installation instructions.
800.533.3948 • barronltg.comPage 2 of 2
CONSTRUCTION
Housing Available in either a Black, Brushed Aluminum or White finish.
Surface - Engineering grade aluminum extrusion with mounting canopy.
Recessed - Extruded aluminum housing supplied with galvanized steel adjustable bar hanger assembly.
Panels Constructed of clear acrylic. Stencil letters are 6” high with 3/4” stroke, with minimum of 100' viewing distance rating as required by UL 924 standard.
Double-face panels are supplied with a mirror insert. Units are supplied with field-selectable directional chevrons for placement in all applications.
ILLUMINATION
High-output red or green LEDs provide superior brightness. Energy consumption of less than 3W for AC only and less than 5W for battery back-up units. LEDs are a maintenance-free solution, providing up to 100,000 hours of use without failure.
ELECTRICAL
Input Dual-voltage input 120 or 277VAC at 60Hz.
Nickel Cadmium Battery - NiCad (With Battery Only) Exitronix NiCad batteries are maintenance-free.
Emergency (WB Only) The CSXE Series exit will operate for a minimum of 90 minutes during a loss of power with a 24 hour maximum recharge time for the battery.
Solid-State Transfer The circuit features solid-state switching, eliminating concerns of damaged contact or mechanical failures associated with relays. The switching circuit detects a loss of line voltage and automatically switches to emergency mode.
Low Voltage Disconnect When the battery’s terminal voltage falls below predetermined levels, the low voltage circuit disconnects the emergency lighting load. The disconnect remains in effect until normal power is restored, preventing deep battery discharge and improving the life of the battery. The disconnect will also automatically reconnect the load circuit once the battery voltage returns to a normal value after charging.
Test Button Test button is easy to locate and allows for manual verification of proper operation of the transfer circuit and emergency lamps.
INSTALLATION
Surface Mounting: completely universal canopy provides for end or ceiling mounting. All hardware is included.
Recessed Mounting: recessed ceiling mount, accessible above the plenum.
Electronics and battery contained in housing. Plug-in battery connector supplied for easy installation. All hardware is included.
OPTIONS
Guardian Self-test/Self-diagnostics (Option: G2) The Guardian circuit continuously monitors the operating condition of the AC power, battery supply voltage and charging circuit.
The purpose of this option is to provide visual signaling in response to a fault at the EXIT sign battery and/or battery charger. If a failure is detected, visual status will occur immediately via the dual color LED. Refer to instruction manual for detailed information.
The Guardian circuit also monitors the transfer circuit as well as performing automatic code compliance testing.
CONFORMANCE TO CODES AND STANDARDS
The S900 Series is UL 924 Listed for Damp Locations. The series meets or exceeds the CEC and NEC requirements as well as NFPA 101.
10.2”
4.3”
12.4”
11.4”
11.8” 3.4”
10.2”
4.3”
12.4”
11.4”
11.8” 3.4”
9.7”
PENDANT ADAPTER
10800157 Rev 27
Index Page
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
S903-WB-SR-RM-AG-G2
Notes:
Type:
X3
VL23-717
Specifications are subject to change without notice.
Installation must be performed in accordance with Barron Lighting Group installation instructions.
800.533.3948 • barronltg.comPage 1 of 2
S900 Series Universal Swivel Mount LED Edge-Lit Exit
10800157 Rev 27
FEATURES & BENEFITS
| • | Suitable for installation in existing drywall applications |
| • | S900U option includes both single- and double-face panel configurations |
| • | Includes surface mounting canopy as well as bracket for recessed mounting |
applications
| • | UL 924 Listed 90 minute emergency run time, 24 hour recharge time |
| • | Field-selectable directional chevrons |
| • | UL Listed for Damp Locations |
| • | California Energy Commission (CEC) compliant |
The Exitronix S900 Series LED Edge-lit Exit features a pivoting design for simple installation in any application, including surface and recessed wall, ceiling and sloped ceilings. Includes surface mounting canopy as well as hardware for recessed mounting applications, making this the most versatile Edge-lit sign available. The S900U option includes both single- and double-face configurations for easy ordering and stocking.
SPECIFICATIONS
Illumination: Long-life, high-intensity, red or green LEDs Construction: Extruded aluminum housing with high-grade, acrylic panel Input: 120/277VAC Dual Primary, 60Hz Battery: Maintenance-free NiCad battery Operating Temp: 0°C to 40°C (32°F to 104°F) Run Time: UL Listed 90 minute emergency run time, 24 hour recharge time Mounting: Ceiling and end surface mounting or recessed Finish: Brushed aluminum, black or white Certfications: UL Listed for Damp Locations, meets or exceeds
CEC, NEC and NFPA 101 Warranty: Any component that fails due to a manufacturing defect is guaranteed for three years with a separate two year prorated warranty on the battery. The warranty does not cover physical damage, abuse or instances of uncontrollable natural forces. See the full Exitronix warranty document for detailed information.
ORDERING INFORMATION Example: S902-WB-SR-RC-AG-G2 Series Power Source Mounting Panel Finish S902 = Single-face LB = AC Only SR3 = Universal Single-face Double-face AG = Brushed Aluminum (gray endcaps) S903 = Double-face WB = With Battery GC = Green Letters/Clear Panel GM = Green Letters/Mirror Panel BL4 = Black S900U1 = Universal GM = Green Letters/Mirror Panel RM = Red Letters/Mirror Panel WH = White S900UM2 = Universal RC = Red Letters/Clear Panel Universal
RM = Red Letters/Mirror Panel G = Green Options (Factory Installed) R = Red G25 = Self-test/Self-diagnostics
Notes 1 Includes one single-face clear and one double-face mirrored panel in selected colors Accessories6 (Field Installed) 2 Includes one single-face mirror and one double-face mirror panel (Consult factory for LB configurations) ER1-Kit = 1' Pendant Mount Kit 3 SR includes kits for surface & recessed mounting ER2-Kit = 2' Pendant Mount Kit 4 Consult factory for availability S900U-G-FP = Green Single Mirror Panel for S900U only 5 Not available on LB configurations S900U-R-FP = Red Single Mirror Panel for S900U only 6 Order as separate line item S900-PENDANT-ADAPTER = Pendant Adapter
MOUNT WEATHER BLDG 762 - SPEC SECTION
265219 - EMERGENCY AND EXIT LIGHTING
Contractor: Warner Construction (Frederick)
Catalog Number:
S903-WB-SR-RM-AG-G2
Notes:
Type:
X3
VL23-717
Specifications are subject to change without notice.
Installation must be performed in accordance with Barron Lighting Group installation instructions.
800.533.3948 • barronltg.comPage 2 of 2
CONSTRUCTION
Housing Available in either a Black, Brushed Aluminum or White finish.
Surface - Engineering grade aluminum extrusion with mounting canopy.
Recessed - Extruded aluminum housing supplied with galvanized steel adjustable bar hanger assembly.
Panels Constructed of clear acrylic. Stencil letters are 6” high with 3/4” stroke, with minimum of 100' viewing distance rating as required by UL 924 standard.
Double-face panels are supplied with a mirror insert. Units are supplied with field-selectable directional chevrons for placement in all applications.
ILLUMINATION
High-output red or green LEDs provide superior brightness. Energy consumption of less than 3W for AC only and less than 5W for battery back-up units. LEDs are a maintenance-free solution, providing up to 100,000 hours of use without failure.
ELECTRICAL
Input Dual-voltage input 120 or 277VAC at 60Hz.
Nickel Cadmium Battery - NiCad (With Battery Only) Exitronix NiCad batteries are maintenance-free.
Emergency (WB Only) The CSXE Series exit will operate for a minimum of 90 minutes during a loss of power with a 24 hour maximum recharge time for the battery.
Solid-State Transfer The circuit features solid-state switching, eliminating concerns of damaged contact or mechanical failures associated with relays. The switching circuit detects a loss of line voltage and automatically switches to emergency mode.
Low Voltage Disconnect When the battery’s terminal voltage falls below predetermined levels, the low voltage circuit disconnects the emergency lighting load. The disconnect remains in effect until normal power is restored, preventing deep battery discharge and improving the life of the battery. The disconnect will also automatically reconnect the load circuit once the battery voltage returns to a normal value after charging.
Test Button Test button is easy to locate and allows for manual verification of proper operation of the transfer circuit and emergency lamps.
INSTALLATION
Surface Mounting: completely universal canopy provides for end or ceiling mounting. All hardware is included.
Recessed Mounting: recessed ceiling mount, accessible above the plenum.
Electronics and battery contained in housing. Plug-in battery connector supplied for easy installation. All hardware is included.
OPTIONS
Guardian Self-test/Self-diagnostics (Option: G2) The Guardian circuit continuously monitors the operating condition of the AC power, battery supply voltage and charging circuit.
The purpose of this option is to provide visual signaling in response to a fault at the EXIT sign battery and/or battery charger. If a failure is detected, visual status will occur immediately via the dual color LED. Refer to instruction manual for detailed information.
The Guardian circuit also monitors the transfer circuit as well as performing automatic code compliance testing.
CONFORMANCE TO CODES AND STANDARDS
The S900 Series is UL 924 Listed for Damp Locations. The series meets or exceeds the CEC and NEC requirements as well as NFPA 101.
10.2”
4.3”
12.4”
11.4”
11.8” 3.4”
10.2”
4.3”
12.4”
11.4”
11.8” 3.4”
9.7”
PENDANT ADAPTER
10800157 Rev 27
Index Page
| 265219.001.00 - Transmittal - Emergency and Exit Lighting-comments-ejd-print |
| 265219.001.00 - Emergency and Exit Lighting-comments |
| Cover Letter |
| Bill of Material |
| E - ELM4L - 74 |
| X1 - S902-WB-SR-RC-AG-G2 - 155 |
| X2 - S902-WB-SR-RC-AG-G2 - 157 |
| X3 - S903-WB-SR-RM-AG-G2 - 159 |
| Text1: 3/14/24 |
| Text2: 12649 |
| Text3: 265219.001.00 - Emergency and Exit Lighting |
| Text5: Erick Daniels |
COR-II
FEMA Bldg 762
| Check Box1: Yes |
| Check Box2: Off |
| Check Box3: Yes |
| Check Box4: Off |
| Check Box5: Off |
| Check Box6: Off |
| Check Box7: Off |
| Check Box8: Off |
| Check Box9: Off |
| Check Box10: Off |
| Text6: |
| Text7: 3/14/24 |
| Text8: 1 |
| Text10: 265219.001.00 - Emergency and Exit Lighting Product Data |
| Text11: |
| Text12: |
| Text14: |
| Text15: |
| Text16: |
| Text18: |
| Text19: |
| Text20: |
| Text22: |
| Text23: |
| Text24: |
| Text26: |
| Text27: |
| Text28: |
| Text30: |
| Text31: |
| Text32: |
| Text34: |
| Check Box11: Off |
| Check Box12: Off |
| Check Box13: Off |
| Check Box14: Yes |
| Check Box15: Off |
| Check Box16: Off |
| Check Box17: Off |
| Check Box18: Off |
| Text35: |
| Text36: |
| Text37: |
| Text38: |
| Text33: |
| Text39: |
| Text40: |
| Check Box19: Off |
| Check Box20: Off |
| Check Box21: Off |
| Check Box22: Off |
| Text41: |
Please see attached Emergency and Exit Lighting Product Data for your review and approval.
| Text42: |
| Text2#1: FEMA 762 |
| Text3#1: 265219 |
| Text5#1: 265219.001.00 |
| Check Box1#1: Off |
| Check Box2#1: Off |
| Check Box3#1: Yes |
| Check Box4#1: Off |
| Text6#1: |
| Check Box5#1: Off |
| Check Box6#1: Off |
| Check Box7#1: Off |
| Check Box8#1: Off |
| Check Box9#1: Yes |
| Check Box10#1: Off |
| Text7#1: |
| Check Box11#1: Off |
| Check Box12#1: Off |
| Check Box13#1: Off |
| Check Box14#1: Off |
| Check Box15#1: Off |
| Check Box16#1: Off |
| Check Box17#1: Off |
| Check Box18#1: Off |
| Text8#1: |
| Check Box19#1: Off |
| Text9: |
| Text10#1: M. Wilson |
| Text11#1: PE I |
| Text12#1: 3/14/24 |
| Text13: Note to Reviewer/FEMA: |
- Light Fixture Schedule (E6.01) shows wattage for exit signs as 3 watts. Manufacturer product data shows battery backup consumes 5 watts.
HBI Comments:
- Light Fixture Type E has 144 fixtures shown on lighting schedule (E6.01), Verify quantity prior to ordering
- Light Fixture Type E - Provide BAA compliant fixtures
- Light Fixture Type E - Provide remote test kit per 265219-2.1.F.8 Text14#1: 12649
File details come from the government source that posted it. Updated .