This document is a Geotechnical Engineering Report for roadway and parking modifications at the Mount Weather Emergency Operations Center (MWEOC) in Mount Weather, Virginia, prepared by Schnabel Engineering. The report details a subsurface exploration and analysis for an intersection construction project, including seven test borings and pavement core samples collected in May and June 2024.
The report provides comprehensive geotechnical recommendations for site grading, earthwork, and pavement construction, specifically addressing subgrade preparation, fill requirements, and pavement design. Key recommendations include using existing fill soils for structural fill, compacting materials to 95-100% of maximum dry density, and implementing full depth pavement sections with 1.5-inch asphalt surface course, 3-4-inch asphalt base course, and 6-8-inch dense-graded aggregate base course. The exploration revealed subsurface strata consisting of existing fill soils (Stratum A) and residual soils (Stratum B), with no groundwater observed during drilling. The report also provides detailed construction considerations, including guidance on rock excavation, site drainage, and potential challenges with moisture-sensitive on-site soils.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNCLASSIFIED
Mount Weather Emergency Operations Center
(MWEOC)
Facility Infrastructure Improvements
• Volume 4: B911 Parking and Intersection
Modifications
Technical Specifications
Project Specifications Issued for Construction
Solicitation No. 70FA5023F00000131
Department of Homeland Security
Federal Emergency Management Agency
P.O. Box 129, Berryville, Virginia 22611
March 5, 2025
MWEOC B911 Parking and Intersection Modifications
Contract No. 70FA5023F00000131
Issued for Construction
VOLUME 4 TABLE OF CONTENTS VOL4TOC - 1
TABLE OF CONTENTS
Volume 4
B911 Parking and Intersection Modifications Technical
Specifications
SECTION TITLE PAGES
Division 03 Concrete
03 30 53 Miscellaneous Cast-in-Place Concrete 9
Division 10 Specialties
10 14 26 Post and Panel Signage 4
Division 22 Plumbing
22 11 13 Facility Water Distribution Piping 12
22 13 13 Facility Sanitary Sewers 9
Division 26 Electrical
26 00 00 Electrical 4
26 00 10 Division 26 General Requirements 14
26 05 15 15KV Medium – Voltage Cables 6
26 05 19 Low-Voltage Electrical Power Conductors and Cables 7
26 05 26 Grounding and Bonding for Electrical Systems 3
26 05 33 Raceway and Boxes for Electrical Systems 12
26 05 53 Identification for Electrical Systems 6
26 05 90 Miscellaneous Equipment 2
26 12 00 Medium - Voltage Transformers 9
26 22 00 Low-Voltage Transformers 4
26 24 16 Panelboards 6
26 26 53 Electrical Vehicle Charging Equipment 9
26 50 00 Lighting 3
Division 31 Earthwork
31 10 00 Site Clearing 4
31 10 20 Erosion and Sediment Controls 6
31 20 00 Earth Moving 19
31 23 19 Dewatering 2
31 50 00 Excavation Support and Protection 5
Issued for Construction
VOLUME 4 TABLE OF CONTENTS VOL4TOC - 2
Division 32 Exterior Improvements
32 12 16 Asphalt Paving 10
32 13 13 Concrete Paving 8
32 17 23 Pavement Makings 3
32 31 13 Chain Link Fences 7
32 91 13 Soil Preparation 11
32 92 00 Turf and Grasses 10
32 93 00 Plants 7
Division 33 Utilities
33 05 00 Common Work Results for Utilities 10
33 42 00 Stormwater Conveyance 9
33 46 00 Subdrainage 5
34 71 13,16 Chain Link Reinforcing 3
APPENDIX A SCHNABEL GEOTECHNICAL ENGINEERING REPORT: MWEOC
ROADWAY/PARKING MODIFICATION REPAIR – ADDITIONAL
PARKING B911
APPENDIX B SCHNABEL GEOTECHNICAL ENGINEERING REPORT: MWEOC
ROADWAY/PARKING MODIFICATION REPAIR – INTERSECTION
CONSTRUCTION
IFC Submission
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 1
SECTION 033053 - MISCELLANEOUS CAST-IN-PLACE CONCRETE
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes cast-in-place concrete, including reinforcement, concrete materials, mixture design, placement procedures, and finishes.
B. Related requirements:
1. Section 321313 “Concrete Paving” for concrete curbs, gutters and sidewalks.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Design Mixtures: For each concrete mixture. Submit alternate design mixtures when characteristics of materials, Project conditions, weather, test results, or other circumstances warrant adjustments.
1. Indicate amounts of mixing water to be withheld for later addition at Project site.
C. Steel Reinforcement Shop Drawings: Placing Drawings that detail fabrication, bending, and placement. Include bar sizes, lengths, material, grade, bar schedules, stirrup spacing, bent bar diagrams, bar arrangement, splices and laps, mechanical connections, tie spacing, hoop spacing, and supports for concrete reinforcement.
D. Construction Joint Layout: Indicate proposed construction joints required to construct the structure.
1. Location of construction joints is subject to approval of the COR.
1.3 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer, manufacturer, and testing agency.
B. Welding certificates.
C. Material Certificates: For each of the following, signed by manufacturers:
1. Cementitious materials.
2. Admixtures.
3. Form materials and form-release agents.
4. Steel reinforcement and accessories.
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 2
5. Curing compounds.
6. Bonding agents.
7. Adhesives.
8. Vapor retarders.
9. Semirigid joint filler.
10. Joint-filler strips.
11. Repair materials.
1.4 QUALITY ASSURANCE
A. Installer Qualifications: A qualified installer who employs on Project personnel qualified as
ACI-certified Flatwork Technician and Finisher and a supervisor who is an ACI-certified
Concrete Flatwork Technician.
B. Manufacturer Qualifications: A firm experienced in manufacturing ready-mixed concrete products and that complies with ASTM C 94 requirements for production facilities and equipment.
1. Manufacturer certified according to NRMCA's "Certification of Ready Mixed Concrete
Production Facilities."
C. Testing Agency Qualifications: An independent agency, engaged by the Contractor, and acceptable to authorities having jurisdiction, qualified according to ASTM C 1077 and
ASTM E 329 for testing indicated.
1. Personnel conducting field tests shall be qualified as ACI Concrete Field Testing
Technician, Grade 1, according to ACI CP-1 or an equivalent certification program.
2. Personnel performing laboratory tests shall be ACI-certified Concrete Strength Testing
Technician and Concrete Laboratory Testing Technician, Grade I. Testing agency laboratory supervisor shall be an ACI-certified Concrete Laboratory Testing Technician, Grade II.
D. Welding Qualifications: Qualify procedures and personnel according to AWS D1.4.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Steel Reinforcement: Deliver, store, and handle steel reinforcement to prevent bending and damage.
1.6 FIELD CONDITIONS
A. Cold-Weather Placement: Comply with ACI 306.1 and as follows. Protect concrete work from physical damage or reduced strength that could be caused by frost, freezing actions, or low temperatures.
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 3
1. When average high and low temperature is expected to fall below 40 deg F for three successive days, maintain delivered concrete mixture temperature within the temperature range required by ACI 301.
2. Do not use frozen materials or materials containing ice or snow. Do not place concrete on frozen subgrade or on subgrade containing frozen materials.
3. Do not use calcium chloride, salt, or other materials containing antifreeze agents or chemical accelerators unless otherwise specified and approved in mixture designs.
B. Hot-Weather Placement: Comply with ACI 301 and as follows:
1. Maintain concrete temperature below 90 deg F at time of placement. Chilled mixing water or chopped ice may be used to control temperature, provided water equivalent of ice is calculated to total amount of mixing water. Using liquid nitrogen to cool concrete is
Contractor's option.
2. Fog-spray forms, steel reinforcement, and subgrade just before placing concrete. Keep subgrade uniformly moist without standing water, soft spots, or dry areas.
PART 2 - PRODUCTS
2.1 CONCRETE, GENERAL
A. Comply with ACI 301.
B. Comply with ACI 117.
2.2 STEEL REINFORCEMENT
A. Recycled Content of Steel Products: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25 percent.
B. Reinforcing Bars: ASTM A 615, Grade 60, deformed.
C. Plain-Steel Welded-Wire Reinforcement: ASTM A 1064, plain, fabricated from as-drawn steel wire into flat sheets.
2.3 CONCRETE MATERIALS
A. Cementitious Materials:
1. Portland Cement: ASTM C 150, Type I.
2. Fly Ash: ASTM C 618, Class C or F.
3. Slag Cement: ASTM C 989, Grade 100 or 120.
4. Blended Hydraulic Cement: ASTM C 595, Type IS, portland blast-furnace slag cement.
B. Normal-Weight Aggregate: ASTM C 33, 1-1/2-inch nominal maximum aggregate size.
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 4
C. Air-Entraining Admixture: ASTM C 260.
D. Chemical Admixtures: Certified by manufacturer to be compatible with other admixtures and that do not contribute water-soluble chloride ions exceeding those permitted in hardened concrete. Do not use calcium chloride or admixtures containing calcium chloride.
1. Water-Reducing Admixture: ASTM C 494, Type A.
2. Retarding Admixture: ASTM C 494, Type B.
3. Water-Reducing and Retarding Admixture: ASTM C 494, Type D.
4. High-Range, Water-Reducing Admixture: ASTM C 494, Type F.
5. High-Range, Water-Reducing and Retarding Admixture: ASTM C 494, Type G.
6. Plasticizing and Retarding Admixture: ASTM C 1017, Type II.
E. Water: ASTM C 94.
2.4 RELATED MATERIALS
A. Vapor Retarder: Plastic sheet, ASTM E 1745, Class A or B.
B. Vapor Retarder: Polyethylene sheet, ASTM D 4397, not less than 10 mils thick; or plastic sheet, ASTM E 1745, Class C.
C. Joint-Filler Strips: ASTM D 1751, asphalt-saturated cellulosic fiber, or ASTM D 1752, cork or self-expanding cork.
2.5 CURING MATERIALS
A. Evaporation Retarder: Waterborne, monomolecular film forming; manufactured for application to fresh concrete.
B. Absorptive Cover: AASHTO M 182, Class 3, burlap cloth or cotton mats.
C. Moisture-Retaining Cover: ASTM C 171, polyethylene film or white burlap-polyethylene sheet.
D. Water: Potable.
E. Clear, Waterborne, Membrane-Forming Curing Compound: ASTM C 309, Type 1, Class B.
F. Clear, Waterborne, Membrane-Forming Curing and Sealing Compound: ASTM C 1315, Type 1, Class A.
1. Products shall comply with the requirements of the California Department of Public
Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical
Emissions from Indoor Sources Using Environmental Chambers."
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 5
2.6 CONCRETE MIXTURES
A. Normal-Weight Concrete:
1. Minimum Compressive Strength: 3,000 psi as indicated at 28 days.
2. Maximum W/C Ratio: 0.50.
3. Cementitious Materials: Use fly ash, pozzolan, slag cement, and blended hydraulic cement as needed to reduce the total amount of portland cement, which would otherwise be used, by not less than 40 percent.
a. Slump Limit: 4 inches plus or minus 1 inch for concrete with verified slump of 2 to
4 inches before adding high-range water-reducing admixture or plasticizing admixture.
4. Air Content: Maintain within range permitted by ACI 301. Do not allow air content of trowel-finished floor slabs to exceed 3 percent.
B. Synthetic Fiber: Uniformly disperse in concrete mix at manufacturer's recommended rate, but not less than a rate of 1.0 lb/cu. yd.
2.7 CONCRETE MIXING
A. Ready-Mixed Concrete: Measure, batch, mix, and deliver concrete according to ASTM C 94 and ASTM C 1116, and furnish batch ticket information.
1. When air temperature is between 85 and 90 deg F, reduce mixing and delivery time from
1-1/2 hours to 75 minutes; when air temperature is above 90 deg F, reduce mixing and delivery time to 60 minutes, or provide mix with retardant admixture.
2. Project site mixing is not permitted.
PART 3 - EXECUTION
3.1 FORMWORK INSTALLATION
A. Design, construct, erect, brace, and maintain formwork according to ACI 301.
3.2 EMBEDDED ITEM INSTALLATION
A. Place and secure anchorage devices and other embedded items required for adjoining work that is attached to or supported by cast-in-place concrete. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 6
3.3 VAPOR-RETARDER INSTALLATION
A. Install, protect, and repair vapor retarders according to ASTM E 1643; place sheets in position with longest dimension parallel with direction of pour.
1. Lap joints 6 inches and seal with manufacturer's recommended adhesive or joint tape.
3.4 STEEL REINFORCEMENT INSTALLATION
A. Comply with CRSI's "Manual of Standard Practice" for fabricating, placing, and supporting reinforcement.
1. Do not cut or puncture vapor retarder. Repair damage and reseal vapor retarder before placing concrete.
3.5 JOINTS
A. General: Construct joints true to line with faces perpendicular to surface plane of concrete.
Refer to Section 321313 “Concrete Paving” for joints in concrete curbs, gutters and sidewalks
B. Contraction Joints in Slabs-on-Grade: Form weakened-plane contraction joints, sectioning concrete into areas as indicated. Construct contraction joints for a depth equal to at least one-fourth of concrete thickness
C. Isolation Joints in Slabs-on-Grade: After removing formwork, install joint-filler strips at slab junctions with vertical surfaces, such as column pedestals, foundation walls, grade beams, and other locations, as indicated.
1. Extend joint-filler strips full width and depth of joint, terminating flush with finished concrete surface unless otherwise indicated.
3.6 CONCRETE PLACEMENT
A. Before placing concrete, verify that installation of formwork, reinforcement, and embedded items is complete and that required inspections are completed.
B. Do not add water to concrete during delivery, at Project site, or during placement unless approved by the COR.
C. Before test sampling and placing concrete, water may be added at Project site, subject to limitations of ACI 301.
1. Do not add water to concrete after adding high-range water-reducing admixtures to mixture.
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 7
3.7 FINISHING FORMED SURFACES
A. Rough-Formed Finish: As-cast concrete texture imparted by form-facing material with tie holes and defects repaired and patched. Remove fins and other projections exceeding 1/2 inch.
1. Apply to concrete surfaces not exposed to public view.
B. Smooth-Formed Finish: As-cast concrete texture imparted by form-facing material, arranged in an orderly and symmetrical manner with a minimum of seams. Repair and patch tie holes and defective areas. Remove fins and other projections exceeding 1/8 inch.
1. Apply to concrete surfaces exposed to public view, to receive a rubbed finish, or to be covered with a coating or covering material applied directly to concrete.
C. Rubbed Finish: Apply the following rubbed finish, defined in ACI 301, to smooth-formed-finished as-cast concrete where indicated:
1. Smooth-rubbed finish.
2. Grout-cleaned finish.
3. Cork-floated finish.
D. Related Unformed Surfaces: At tops of walls, horizontal offsets, and similar unformed surfaces adjacent to formed surfaces, strike off smooth and finish with a texture matching adjacent formed surfaces. Continue final surface treatment of formed surfaces uniformly across adjacent unformed surfaces unless otherwise indicated.
3.8 FINISHING UNFORMED SURFACES
A. General: Comply with ACI 302.1R for screeding, restraightening, and finishing operations for concrete surfaces. Do not wet concrete surfaces.
B. Screed surfaces with a straightedge and strike off. Begin initial floating using bull floats or darbies to form a uniform and open-textured surface plane before excess moisture or bleedwater appears on surface.
1. Do not further disturb surfaces before starting finishing operations.
C. Scratch Finish: Apply scratch finish to surfaces indicated and surfaces to receive concrete floor topping or mortar setting beds for ceramic or quarry tile, portland cement terrazzo, and other bonded cementitious floor finishes unless otherwise indicated.
D. Float Finish: Apply float finish to surfaces indicated, to surfaces to receive trowel finish, and to floor and slab surfaces to be covered with fluid-applied or sheet waterproofing, fluid-applied or direct-to-deck-applied membrane roofing, or sand-bed terrazzo.
E. Trowel Finish: Apply a hard trowel finish to surfaces indicated and to floor and slab surfaces exposed to view or to be covered with resilient flooring, carpet, ceramic or quarry tile set over a cleavage membrane, paint, or another thin film-finish coating system.
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 8
F. Trowel and Fine-Broom Finish: Apply a partial trowel finish, stopping after second troweling, to surfaces indicated and to surfaces where ceramic or quarry tile is to be installed by either thickset or thinset methods. Immediately after second troweling, and when concrete is still plastic, slightly scarify surface with a fine broom.
G. Slip-Resistive Broom Finish: Apply a slip-resistive finish to surfaces indicated and to exterior concrete platforms, steps, and ramps. Immediately after float finishing, slightly roughen trafficked surface by brooming with fiber-bristle broom perpendicular to main traffic route.
H. Concrete Curbs: Refer to Section 321313 “Concrete Paving” for finishing requirements.
3.9 CONCRETE PROTECTING AND CURING
A. General: Protect freshly placed concrete from premature drying and excessive cold or hot temperatures. Comply with ACI 306.1 for cold-weather protection and with ACI 305.1 for hot-weather protection during curing.
B. Evaporation Retarder: Apply evaporation retarder to concrete surfaces if hot, dry, or windy conditions cause moisture loss approaching 0.2 lb/sq. ft. x h before and during finishing operations. Apply according to manufacturer's written instructions after placing, screeding, and bull floating or darbying concrete, but before float finishing.
C. Begin curing after finishing concrete but not before free water has disappeared from concrete surface.
D. Curing Methods: Cure formed and unformed concrete for at least seven days by one or a combination of the following methods:
1. Moisture Curing: Keep surfaces continuously moist for not less than seven days with the following materials:
a. Water.
b. Continuous water-fog spray.
c. Absorptive cover, water saturated, and kept continuously wet. Cover concrete surfaces and edges with 12-inch lap over adjacent absorptive covers.
2. Moisture-Retaining-Cover Curing: Cover concrete surfaces with moisture-retaining cover for curing concrete, placed in widest practicable width, with sides and ends lapped at least 12 inches, and sealed by waterproof tape or adhesive. Cure for not less than seven days. Immediately repair any holes or tears during curing period, using cover material and waterproof tape.
3. Curing Compound: Apply uniformly in continuous operation by power spray or roller according to manufacturer's written instructions. Recoat areas subjected to heavy rainfall within three hours after initial application. Maintain continuity of coating and repair damage during curing period.
4. Curing and Sealing Compound: Apply uniformly to floors and slabs indicated in a continuous operation by power spray or roller according to manufacturer's written instructions. Recoat areas subjected to heavy rainfall within three hours after initial
MISCELLANEOUS CAST-IN-PLACE CONCRETE 033053 - 9
application. Repeat process 24 hours later and apply a second coat. Maintain continuity of coating and repair damage during curing period.
3.10 JOINT FILLING
A. Prepare, clean, and install joint filler according to manufacturer's written instructions.
1. Defer joint filling until concrete has aged at least one month(s). Do not fill joints until construction traffic has permanently ceased.
B. Remove dirt, debris, saw cuttings, curing compounds, and sealers from joints; leave contact faces of joints clean and dry.
C. Install semirigid joint filler full depth in saw-cut joints and at least 2 inches deep in formed joints. Overfill joint and trim joint filler flush with top of joint after hardening.
3.11 FIELD QUALITY CONTROL
A. Testing Agency: Contractor will engage a qualified testing agency to perform tests and inspections.
B. Tests: Perform according to ACI 301.
1. Testing Frequency: Obtain one composite sample for each day's pour of each concrete mixture exceeding 5 cu. yd; but less than 25 cu. yd, plus one set for each additional 50 cu.
yd. or fraction thereof.
2. Testing Frequency: Obtain at least one composite sample for each 100 cu. yd. or fraction thereof of each concrete mixture placed each day.
END OF SECTION 033053
POST AND PANEL SIGNAGE 101426 - 1
SECTION 101426 - POST AND PANEL SIGNAGE
1.1 GENERAL
A. Regulatory Requirements
1. All regulatory signage must be in accordance with the MUTCD.
1.2 SUMMARY
A. Section Includes:
1. Nonilluminated post-and-panel signs.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: For signage.
1. Include fabrication and installation details and attachments to other work.
2. Show sign mounting heights, locations of supplementary supports to be provided by other installers, and accessories.
3. Show message list, typestyles, graphic elements, and layout for each sign at least half size.
C. Samples: For each exposed product and for each color and texture specified.
1.4 INFORMATIONAL SUBMITTALS
A. Sample warranty.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance data.
1.6 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of signs that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Five years from date of Substantial Completion.
POST AND PANEL SIGNAGE 101426 - 2
PART 2 - PRODUCTS
2.1 TRAFFIC SIGN POSTS
A. Steel Flanged Channel Section (U-Shape)
1. Fabricate steel posts from steel conforming to ASTM A36/A36M or ASTM A499 and with a minimum yield strength of 30 ksi and a minimum tensile strength of 50 ksi.
2. Punch or drill 5/16 to 3/8-inch diameter holes spaced at 1or 2-inch centers along the centerline of the web prior to galvanizing for the entire length of the post.
3. Galvanize posts after punching in accordance with ASTM A123/A123M.
B. Perforated Steel Tube
1. Fabricate steel posts from steel conforming to either ASTM A653/A653M, structural steel, Grade 340 50, Class 1, coating designation G90 or ASTM A1011/A1011M, struc-tural steel, Grade 340 50, hot-dip galvanized after punching in accordance with ASTM
A123/A123M.
2. Pre-punch holes approximately 7/16 inch in diameter spaced at approximately 1-inch centers along each side of the tube for the entire length of the post.
C. Steel Tube
1. Conform to ASTM A500/A500M, Grade B or C, and hot-dip galvanized in accordance with ASTM A123/A123M.
D. Structural Steel H Section
1. Conform to ASTM A709/A709M, Grade 345 50 or 345W 50W. Galvanize posts, Fuse plate and splice plate after fabrication in accordance with ASTM A123/A123M.
2. Slip Base, Fuse Plate and Splice Plate: Conform to ASTM A36/A36M, minimum yield strength 50,000 psi.
3. High-Strength Bolts, Nuts and Washers: High strength bolts must conform to ASTM
F3125/F3125M. Nuts must conform to ASTM A563M ASTM A563. Washers must con-form to ASTM F436/F436M. High strength bolts, nuts and washers must be zinc coated.
2.2 FLAT ALUMINUM SIGN POSTS
A. Aluminum sign panels must conform to ASTM B209M ASTM B209, alloy-temper
6061-T6 or 5052-H38. The blanks must be free from laminations, blisters, open seams, pits, holes, other defects that may affect their appearance or use. The thickness must be uniform and the blank commercially flat.
2.3 TRAFFIC SIGN RETROFLECTIVE SHEETING
POST AND PANEL SIGNAGE 101426 - 3
A. All background sheeting applied to flat sheet and extruded panel signs must be in accordance with ASTM D4956, Type III, IV, VII, VIII, IX or XI retroreflective sheeting and must have
Class 1, 3, or 4 adhesive backing. Retroreflective sheeting must be high intensity that is an unmetallized micro prismatic reflective material.
B. Retroreflective sheeting must have sufficient adhesion, strength and flexibility such that the sheeting can be handled, processed and applied according to the manufacturer's recommenda-tions without appreciable stretching, tearing, cracking or other damage.
C. Legend and Border
1. Apply retroreflective sheeting as legend and border in accordance with ASTM D4956, Type IX, XI, or AASHTO M 268 Type C or D, Class 1. Retroreflective sheeting must be an unmetallized cube corner micro prismatic reflective material.
2. Retroreflective sheeting applied as legend and border for specific signing applications, without a datum mark on the surface of the sheeting, must be evaluated for rotational sen-sitivity in accordance with AASHTO M 26.
3. For screen printed transparent colored areas or transparent colored overlay films on white sheeting, the coefficient of retroreflection (RA) must be no less than 70 percent of the original values for the corresponding color.
4. Adhesive performance for retroreflective sheeting must be in accordance with ASTM
D4956. The sheeting surface must be in condition to be readily screen processed and compatible with transparent overlay films, plus recommended transparent and opaque screen process colors. Furnish manufacturer's information as to the type of solvent or sol-vents that may be used to clean the surface of the sheeting without detrimental loss of performance and durability.
2.4. LETTERS, NUMBERS, ARROWS, SYMBOLS, AND BORDERS
A. Apply letters, numerals, arrows, symbols, and borders on the retroreflective sheeting or opaque background of the sign using the direct or reverse screen process. Apply messages and borders of a color darker than the background to the paint or the retroreflective sheeting using the direct process. Messages and borders must be of a color lighter than the sign back-ground and applied using the reverse screen process. Use opaque or transparent colors, inks, and paints of the type and quality recommended by the retroreflective sheeting manufacturer in the screen process. Perform the screening in a manner that results in a uniform color and tone, with sharply defined edges of legends and borders and without blemishes on the sign background that will affect intended use. Air dry or bake the signs after screening according to the manufacturer's recommendations to provide a smooth hard finish. Reject any signs with blisters or other blemishes.
2.5 HARDWARE
A. Bolts, nuts, post clips, lock and flat washers must be either aluminum alloy or commercial quality stainless steel, hot-dip galvanized or cadmium plated after fabrication.
B. Provide fiber washers of commercial quality.
POST AND PANEL SIGNAGE 101426 - 4
PART 3 - EXECUTION
3.1 SIGN POSTS
A. Steel Flanged Channel Section, Perforated Square Steel Tube; Round Steel Tube
1. Sign posts consist of a base post and sign post. Drive steel sign base posts with a suitable driving head. Attach sign posts to base posts. Replace any base posts damaged during driving or otherwise at no additional cost to the Government.
2. Embed steel sign base posts in concrete as indicated.
B. Structural Steel H Section Posts
1. Tighten all breakaway assembly bolts in a systematic manner to the prescribed torque in-dicated. Loosen each breakaway assembly bolt and re-tighten to the required torque in the same order as the initial tightening.
2. Burr the threads at the nut using a center punch to prevent the nut from loosening.
3. Tighten nuts on hinge plate bolts to the required minimum bolt tension values indicated.
3.2 SIGN PANELS
A. Clean, degrease and etch the face of metal panels using methods recommended by the retrore-flective sheeting manufacturer. After cleaning and degreasing, apply retroreflective sheeting material to the sign panels as recommended by the manufacturer.
B. Perform shearing, cutting and punching prior to preparing the blanks for application of reflec-tive material.
C. Do not field drill holes in any part of the panel. Use nylon washers recommended by the sign sheeting manufacturer between the bolt heads and sign faces on flat sheet aluminum signs.
D. Replace any damaged sign panels at no additional cost to the Government.
3.3 LOCATION OF SIGN POSTS
A. Locate and erect all signs in accordance with the drawings and MUTCD. Vertically mount signs at right angles to the direction of, and facing, the traffic that they are intended to serve.
B. Where mirror reflection from the sign face is encountered to such a degree as to reduce legi-bility, turn the sign slightly away from the road.
C. Mounted signs must present a smooth flat surface varying no more than 3/8 inch from a 4-foot straightedge placed in any position on the face of the sign after erection.
D. Mount signs on traffic signal posts with strap or clamp type sign supports. Each installed sign will be inspected by the Contracting Officer's representative prior to acceptance by the Gov-ernment.
END OF SECTION 101426
FACILITY WATER DISTRIBUTION PIPING 221113 - 1
UNCLASSIFED
SECTION 221113 - FACILITY WATER DISTRIBUTION PIPING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes water-distribution piping and related components outside the building for water service, fire-service mains, and combined water service and fire-service mains.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
B. Shop Drawings: Detail precast concrete vault assemblies and indicate dimensions, method of field assembly, and components.
1.4 INFORMATIONAL SUBMITTALS
A. Field quality-control test reports.
1.5 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For water valves and maintenance manuals.
1.6 QUALITY ASSURANCE
A. Regulatory Requirements:
1. Comply with requirements of authorities having jurisdiction supplying water. Include tapping of water mains and backflow prevention.
2. Comply with standards of authorities having jurisdiction for potable-water-service piping, including materials, installation, testing, and disinfection.
3. Comply with standards of authorities having jurisdiction for fire-suppression water-service piping, including materials, hose threads, installation, and testing.
B. Piping materials shall bear label, stamp, or other markings of specified testing agency.
C. Comply with ASTM F 645 for selection, design, and installation of thermoplastic water piping.
FACILITY WATER DISTRIBUTION PIPING 221113 - 2
D. Comply with FMG's "Approval Guide" or UL's "Fire Protection Equipment Directory" for fire-service-main products.
E. NFPA Compliance: Comply with NFPA 24 for materials, installations, tests, flushing, and valve and hydrant supervision for fire-service-main piping for fire suppression.
F. NSF Compliance:
1. Comply with NSF 14 for plastic potable-water-service piping. Include marking "NSF-pw" on piping.
2. Comply with NSF 61 Annex G for materials for water-service piping and specialties for domestic water.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Preparation for Transport: Prepare valves, including fire hydrants, according to the following:
1. Ensure that valves are dry and internally protected against rust and corrosion.
2. Protect valves against damage to threaded ends and flange faces.
3. Set valves in best position for handling. Set valves closed to prevent rattling.
B. During Storage: Use precautions for valves, including fire hydrants, according to the following:
1. Do not remove end protectors unless necessary for inspection; then reinstall for storage.
2. Protect from weather. Store indoors and maintain temperature higher than ambient dew-point temperature. Support off the ground or pavement in watertight enclosures when outdoor storage is necessary.
C. Handling: Use sling to handle valves and fire hydrants if size requires handling by crane or lift.
Rig valves to avoid damage to exposed parts. Do not use handwheels or stems as lifting or rigging points.
D. Deliver piping with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe-end damage and to prevent entrance of dirt, debris, and moisture.
E. Protect stored piping from moisture and dirt. Elevate above grade. Do not exceed structural capacity of floor when storing inside.
F. Protect flanges, fittings, and specialties from moisture and dirt.
G. Store plastic piping protected from direct sunlight. Support to prevent sagging and bending.
1.8 PROJECT CONDITIONS
A. Interruption of Existing Water-Distribution Service: Do not interrupt service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary water-distribution service according to requirements indicated:
FACILITY WATER DISTRIBUTION PIPING 221113 - 3
1. Notify COR no fewer than seven (7) days in advance of proposed interruption of service.
2. Do not proceed with interruption of water-distribution service without COR's written permission.
1.9 COORDINATION
A. Coordinate connection to water main with authorities having jurisdiction.
PART 2 - PRODUCTS
2.1 DUCTILE-IRON PIPE AND FITTINGS
A. Mechanical-Joint, Ductile-Iron Pipe: AWWA C151, with mechanical-joint bell and plain spigot end unless grooved or flanged ends are indicated.
1. Mechanical-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern.
2. Glands, Gaskets, and Bolts: AWWA C111, ductile- or gray-iron glands, rubber gaskets, and steel bolts.
B. Push-on-Joint, Ductile-Iron Pipe: AWWA C151, with push-on-joint bell and plain spigot end unless grooved or flanged ends are indicated.
1. Push-on-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern.
2. Gaskets: AWWA C111, rubber.
3. Mechanical-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern.
a. Glands, Gaskets, and Bolts: AWWA C111, ductile- or gray-iron glands, rubber gaskets, and steel bolts.
2.2 JOINING MATERIALS
A. Refer to Section 330500 "Common Work Results for Utilities" for commonly used joining materials.
B. Brazing Filler Metals: AWS A5.8, BCuP Series.
C. Bonding Adhesive for Fiberglass Piping: As recommended by fiberglass piping manufacturer.
2.3 PIPING SPECIALTIES
A. Transition Fittings: Manufactured fitting or coupling same size as, with pressure rating at least equal to and ends compatible with, piping to be joined.
FACILITY WATER DISTRIBUTION PIPING 221113 - 4
B. Tubular-Sleeve Pipe Couplings:
1. Description: Metal, bolted, sleeve-type, reducing or transition coupling, with center sleeve, gaskets, end rings, and bolt fasteners and with ends of same sizes as piping to be joined.
a. Standard: AWWA C219.
b. Center-Sleeve Material: Manufacturer's standard.
c. Gasket Material: Natural or synthetic rubber.
d. Pressure Rating: 150 psig minimum.
e. Metal Component Finish: Corrosion-resistant coating or material.
C. Split-Sleeve Pipe Couplings:
1. Description: Metal, bolted, split-sleeve-type, reducing or transition coupling with sealing pad and closure plates, O-ring gaskets, and bolt fasteners.
a. Standard: AWWA C219.
b. Sleeve Material: Manufacturer's standard.
c. Sleeve Dimensions: Of thickness and width required to provide pressure rating.
d. Gasket Material: O-rings made of EPDM rubber, unless otherwise indicated.
e. Pressure Rating: 150 psig minimum.
f. Metal Component Finish: Corrosion-resistant coating or material.
D. Flexible Connectors:
1. Nonferrous-Metal Piping: Bronze hose covered with bronze wire braid; with copper-tube, pressure-type, solder-joint ends or bronze flanged ends brazed to hose.
2. Ferrous-Metal Piping: Stainless-steel hose covered with stainless-steel wire braid; with
ASME B1.20.1, threaded steel pipe nipples or ASME B16.5, steel pipe flanges welded to hose.
E. Dielectric Fittings:
1. General Requirements: Assembly of copper alloy and ferrous materials with separating nonconductive insulating material. Include end connections compatible with pipes to be joined.
2. Dielectric Unions:
a. Description:
1) Standard: ASSE 1079.
2) Pressure Rating: 150 psig.
3) End Connections: Solder-joint copper alloy and threaded ferrous.
3. Dielectric Flanges:
a. Description:
1) Standard: ASSE 1079.
FACILITY WATER DISTRIBUTION PIPING 221113 - 5
2) Factory-fabricated, bolted, companion-flange assembly.
3) Pressure Rating: 150 psig.
4) End Connections: Solder-joint copper alloy and threaded ferrous; threaded solder-joint copper alloy and threaded ferrous.
4. Dielectric-Flange Insulating Kits:
a. Description:
1) Nonconducting materials for field assembly of companion flanges.
2) Pressure Rating: 150 psig.
3) Gasket: Neoprene or phenolic.
4) Bolt Sleeves: Phenolic or polyethylene.
5) Washers: Phenolic with steel backing washers.
5. Dielectric Nipples:
a. Description:
1) Standard: IAPMO PS 66
2) Electroplated steel nipple complying with ASTM F 1545.
3) Pressure Rating: 300 psig at 225 deg F.
4) End Connections: Male threaded or grooved.
5) Lining: Inert and noncorrosive, propylene.
2.4 GATE VALVES
A. AWWA, Cast-Iron Gate Valves:
1. Nonrising-Stem, Resilient-Seated Gate Valves:
a. Description: Gray- or ductile-iron body and bonnet; with bronze or gray- or ductile-iron gate, resilient seats, bronze stem, and stem nut.
1) Standard: AWWA C509.
2) Minimum Pressure Rating: 200 psig.
3) End Connections: Mechanical joint.
4) Interior Coating: Complying with AWWA C550.
2.5 GATE VALVE ACCESSORIES AND SPECIALTIES
A. Tapping-Sleeve Assemblies:
1. Description: Sleeve and valve compatible with drilling machine.
a. Standard: MSS SP-60.
b. Tapping Sleeve: Cast- or ductile-iron or stainless-steel, two-piece bolted sleeve with flanged outlet for new branch connection. Include sleeve matching size and type of pipe material being tapped and with recessed flange for branch valve.
FACILITY WATER DISTRIBUTION PIPING 221113 - 6
c. Valve: AWWA, cast-iron, nonrising-stem, resilient-seated gate valve with one raised face flange mating tapping-sleeve flange.
B. Valve Boxes: Comply with AWWA M44 for cast-iron valve boxes. Include top section, adjustable extension of length required for depth of burial of valve, plug with lettering
"WATER," and bottom section with base that fits over valve and with a barrel approximately 5 inches in diameter.
1. Operating Wrenches: Steel, tee-handle with one pointed end, stem of length to operate deepest buried valve, and socket matching valve operating nut.
C. Indicator Posts: UL 789, FMG-approved, vertical-type, cast-iron body with operating wrench, extension rod, and adjustable cast-iron barrel of length required for depth of burial of valve.
2.6 CHECK VALVES
A. AWWA Check Valves:
1. Description: Swing-check type with resilient seat. Include interior coating according to
AWWA C550 and ends to match piping.
a. Standard: AWWA C508.
b. Pressure Rating: 175 psig.
B. UL/FMG, Check Valves:
1. Description: Swing-check type with pressure rating; rubber-face checks, unless otherwise indicated; and ends matching piping.
a. Standards: UL 312 and FMG approved.
b. Pressure Rating: 175 psig.
2.7 DETECTOR CHECK VALVES
A. Detector Check Valves:
1. Description: Galvanized cast-iron body, bolted cover with air-bleed device for access to internal parts, and flanged ends. Include one-piece bronze disc with bronze bushings, pivot, and replaceable seat. Include threaded bypass taps in inlet and outlet for bypass meter connection. Set valve to allow minimal water flow through bypass meter when major water flow is required.
a. Standards: UL 312 and FMG approved.
b. Pressure Rating: 175 psig.
FACILITY WATER DISTRIBUTION PIPING 221113 - 7
2. Description: Iron body, corrosion-resistant clapper ring and seat ring material, flanged ends, with connections for bypass and installation of water meter.
a. Standards: UL 312 and FMG approved.
b. Pressure Rating: 175 psig.
2.8 FIRE HYDRANTS
A. Fire hydrants shall be Mueller Super Centurion 250 as detailed on the plans.
B. Hydrant markers shall be Hy-Viz stainless steel with springs and bolt mount, white and blue reflective tape; tag 3-inch by 5-inch.
PART 3 - EXECUTION
3.1 EARTHWORK
A. Refer to Section 312000 "Earth Moving" for excavating, trenching, and backfilling.
3.2 PIPING APPLICATIONS
A. General: Use pipe, fittings, and joining methods for piping systems according to the following applications.
B. Transition couplings and special fittings with pressure ratings at least equal to piping pressure rating may be used, unless otherwise indicated.
C. Do not use flanges or unions for underground piping.
D. Flanges, unions, grooved-end-pipe couplings, and special fittings may be used, instead of joints indicated, on aboveground piping and piping in vaults.
E. Underground water-service piping NPS 3/4 to NPS 3 shall be any of the following:
1. Soft copper tube, ASTM B 88, Type K, ASTM B 88, Type L; wrought copper, solder joint fittings and brazed, copper, pressure seal fittings; and pressure sealed joints.
F. Underground Fire-Service-Main Piping NPS 4 to NPS 12 shall be any of the following:
1. Ductile-iron, push-on-joint pipe; ductile-iron, push-on-joint fittings; and gasketed mechanical-joint pipe; ductile-iron, mechanical-joint fittings; and mechanical grooved-end pipe; ductile-iron-pipe appurtenances; and grooved joints.
FACILITY WATER DISTRIBUTION PIPING 221113 - 8
G. Underground Combined Water-Service and Fire-Service-Main Piping NPS 6 to NPS 12 shall be any of the following:
1. Ductile-iron, push-on-joint pipe; ductile-iron, push-on-joint fittings; and gasketed mechanical-joint pipe; ductile-iron, mechanical-joint fittings; and mechanical grooved-end pipe; ductile-iron-pipe appurtenances; and grooved joints.
3.3 VALVE APPLICATIONS
A. General Application: Use mechanical-joint-end valves for NPS 3 and larger underground installation. Use threaded- or flanged-end valves for installation in vaults. Use UL/FMG, nonrising-stem gate valves for installation with indicator posts. Use corporation valves and curb valves with ends compatible with piping, for NPS 2 and smaller installation.
B. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following requirements apply:
1. Underground Valves, NPS 3 and Larger: AWWA, cast-iron, nonrising-stem, resilient high-pressure, resilient-seated gate valves with valve box.
2. Underground Valves, NPS 4 and Larger, for Indicator Posts: UL/FMG, cast-iron, nonrising-stem gate valves with indicator post.
3. Use the following for valves in vaults and aboveground:
a. Gate Valves, NPS 2 and Smaller: Bronze, nonrising stem.
b. Gate Valves, NPS 3 and Larger: AWWA, cast iron, OS&Y rising stem, resilient seated UL/FMG, cast iron, OS&Y rising stem.
3.4 PIPING SYSTEMS - COMMON REQUIREMENTS
A. See Section 330500 "Common Work Results for Utilities" for piping-system common requirements.
3.5 PIPING INSTALLATION
A. Water-Main Connection: Arrange with utility company for tap of size and in location indicated in water main.
B. Water-Main Connection: Tap water main according to requirements of water utility company and of size and in location indicated.
C. Make connections larger than NPS 2 with tapping machine according to the following:
1. Install tapping sleeve and tapping valve according to MSS SP-60.
2. Install tapping sleeve on pipe to be tapped. Position flanged outlet for gate valve.
3. Use tapping machine compatible with valve and tapping sleeve; cut hole in main.
Remove tapping machine and connect water-service piping.
FACILITY WATER DISTRIBUTION PIPING 221113 - 9
4. Install gate valve onto tapping sleeve. Comply with MSS SP-60. Install valve with stem pointing up and with valve box.
D. Make connections NPS 2 and smaller with drilling machine according to the following:
1. Install service-saddle assemblies and corporation valves in size, quantity, and arrangement required by utility company standards.
2. Install service-saddle assemblies on water-service pipe to be tapped. Position outlets for corporation valves.
3. Use drilling machine compatible with service-saddle assemblies and corporation valves.
Drill hole in main. Remove drilling machine and connect water-service piping.
4. Install corporation valves into service-saddle assemblies.
5. Install manifold for multiple taps in water main.
6. Install curb valve in water-service piping with head pointing up and with service box.
E. Comply with NFPA 24 for fire-service-main piping materials and installation.
1. Install PE corrosion-protection encasement according to ASTM A 674 or AWWA C105.
2. Install copper tube and fittings according to CDA's "Copper Tube Handbook."
F. Install ductile-iron, water-service piping according to AWWA C600 and AWWA M41.
1. Install PE corrosion-protection encasement according to ASTM A 674 or AWWA C105.
G. Bury piping with depth of cover over top at least 30 inches, with top at least 12 inches below level of maximum frost penetration, and according to the following:
1. Under Driveways: With at least 36 inches cover over top.
H. Install piping by tunneling or jacking, or combination of both, under streets and other obstructions that cannot be disturbed.
I. Extend water-service piping and connect to water-supply source and building-water-piping systems at outside face of building wall in locations and pipe sizes indicated.
1. Terminate water-service piping at building wall until building-water-piping systems are installed. Terminate piping with caps, plugs, or flanges as required for piping material.
Make connections to building-water-piping systems when those systems are installed.
J. Install underground piping with restrained joints at horizontal and vertical changes in direction.
Use restrained-joint piping, thrust blocks, anchors, tie-rods and clamps, and other supports.
3.6 JOINT CONSTRUCTION
A. See Section 330500 "Common Work Results for Utilities" for basic piping joint construction.
B. Make pipe joints according to the following:
1. Copper-Tubing, Pressure-Sealed Joints: Use proprietary crimping tool and procedure recommended by copper, pressure-seal-fitting manufacturer.
FACILITY WATER DISTRIBUTION PIPING 221113 - 10
2. Ductile-Iron Piping, Gasketed Joints for Water-Service Piping: AWWA C600 and
AWWA M41.
3. Ductile-Iron Piping, Gasketed Joints for Fire-Service-Main Piping: UL 194.
4. Ductile-Iron Piping, Grooved Joints: Cut-groove pipe. Assemble joints with grooved-end, ductile-iron-piping couplings, gaskets, lubricant, and bolts according to coupling manufacturer's written instructions.
5. Install dielectric fittings in piping at connections of dissimilar metal piping and tubing.
a. Dielectric Fittings for NPS 2 and Smaller: Use dielectric nipples.
b. Dielectric Fittings for NPS 2-1/2 to NPS 4: Use dielectric flanges.
c. Dielectric Fittings for NPS 5 and Larger: Use dielectric flange kits.
3.7 ANCHORAGE INSTALLATION
A. Anchorage, General: Install water-distribution piping with restrained joints. Anchorages and restrained-joint types that may be used include the following:
1. Concrete thrust blocks.
2. Locking mechanical joints.
3. Set-screw mechanical retainer glands.
4. Bolted flanged joints.
5. Pipe clamps and tie rods.
B. Install anchorages for tees, plugs and caps, bends, crosses, valves, and hydrant branches.
Include anchorages for the following piping systems:
1. Gasketed-Joint, Ductile-Iron, Water-Service Piping: According to AWWA C600.
2. Gasketed-Joint, PVC Water-Service Piping: According to AWWA M23.
3. Fire-Service-Main Piping: According to NFPA 24.
C. Apply full coat of asphalt or other acceptable corrosion-resistant material to surfaces of installed ferrous anchorage devices.
3.8 VALVE INSTALLATION
A. AWWA Gate Valves: Comply with AWWA C600 and AWWA M44. Install each underground valve with stem pointing up and with valve box.
B. AWWA Valves Other Than Gate Valves: Comply with AWWA C600 and AWWA M44.
C. UL/FMG, Gate Valves: Comply with NFPA 24. Install each underground valve and valves in vaults with stem pointing up and with vertical cast-iron indicator post.
D. UL/FMG, Valves Other Than Gate Valves: Comply with NFPA 24.
E. MSS Valves: Install as component of connected piping system.
FACILITY WATER DISTRIBUTION PIPING 221113 - 11
3.9 FIRE HYDRANT INSTALLATION
A. General: Install each fire hydrant with separate gate valve in supply pipe, anchor with restrained joints or thrust blocks, and support in upright position.
B. Wet-Barrel Fire Hydrants: Install with valve below frost line. Provide for drainage.
C. AWWA Fire Hydrants: Comply with AWWA M17.
D. UL/FMG Fire Hydrants: Comply with NFPA 24.
3.10 FLUSHING HYDRANT INSTALLATION
A. Install post-type flushing hydrants with valve below frost line and provide for drainage. Support in upright position. Include separate gate valve or curb valve and restrained joints in supply piping.
B. Install ground-type flushing hydrants with valve below frost line and provide for drainage.
Install hydrant box flush with grade. Include separate gate valve or curb valve and restrained joints in supply piping.
C. Install sampling stations with valve below frost line and provide for drainage. Attach weather-resistant housing and support in upright position. Include separate curb valve in supply piping.
3.11 FIELD QUALITY CONTROL
A. Piping Tests: Conduct piping tests before joints are covered and after concrete thrust blocks have hardened sufficiently. Fill pipeline 24 hours before testing and apply test pressure to stabilize system. Use only potable water.
B. Hydrostatic Tests: Test at not less than one-and-one-half times working pressure for two hours.
1. Increase pressure in 50-psig increments and inspect each joint between increments. Hold at test pressure for 1 hour; decrease to 0 psig. Slowly increase again to test pressure and hold for 1 more hour. Maximum allowable leakage is 2 quarts per hour per 100 joints.
Remake leaking joints with new materials and repeat test until leakage is within allowed limits.
C. Prepare reports of testing activities.
3.12 IDENTIFICATION
A. Install continuous underground detectable warning tape during backfilling of trench for underground water-distribution piping. Locate below finished grade, directly over piping.
Underground warning tapes are specified in Section 312000 "Earth Moving."
FACILITY WATER DISTRIBUTION PIPING 221113 - 12
B. Permanently attach equipment nameplate or marker indicating plastic water-service piping, on main electrical meter panel. See Section 330500 "Common Work Results for Utilities" for identifying devices.
3.13 CLEANING
A. Clean and disinfect water-distribution piping as follows:
1. Purge new water-distribution piping systems and parts of existing systems that have been altered, extended, or repaired before use.
2. Use purging and disinfecting procedure prescribed by authorities having jurisdiction or, if method is not prescribed by authorities having jurisdiction, use procedure described in
NFPA 24 for flushing of piping. Flush piping system with clean, potable water until dirty water does not appear at points of outlet.
3. Use purging and disinfecting procedure prescribed by authorities having jurisdiction or, if method is not prescribed by authorities having jurisdiction, use procedure described in
AWWA C651 or do as follows:
a. Fill system or part of system with water/chlorine solution containing at least 50 ppm of chlorine; isolate and allow to stand for 24 hours.
b. Drain system or part of system of previous solution and refill with water/chlorine solution containing at…