B420 Demolition and Parking Drawings IFC 3-5-2025.pdf
PDF 17 MB Posted
- Attached to
- ROADWAY & SITEWIDE IMPROVEMENTS Federal contract opportunity
- Solicitation number
- 70FA5025R00000012
About this file
These are construction drawings issued for the demolition of Building 420 and construction of a new parking lot at the FEMA Mount Weather Emergency Operations Center, dated March 5, 2025. The project involves comprehensive site work including: demolishing the existing 10,830 square foot single-story building, removing a 1,500-gallon underground fuel storage tank, salvaging two structural steel antennas, and constructing a new parking lot with 116 total parking spaces (113 standard and 3 oversized).
The project scope includes hazardous material abatement for asbestos and lead-based paint, utility removals and relocations, installation of a stormwater management system with six StormCapture modules, electrical infrastructure upgrades with new service equipment, lighting, underground conduits, and provisions for future electric vehicle charging stations. Additional features include a bus shelter, concrete sidewalks, landscaping, and erosion control measures. The total disturbed area is approximately 1.81 acres, with careful attention to environmental and safety requirements throughout the demolition and construction process.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 420 DEMOLITION & PARKING LOT CONSTRUCTION
FEMA MOUNT WEATHER EMERGENCY OPERATIONS CENTER
MARCH 5, 2025
ISSUED FOR CONSTRUCTION
DRAWING SET NO. EPS-9620
SOLICITATION NO. 70FA5019F00000177
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 22
3/5/2025
G-001
COVER SHEET
Sheet List Table Sheet Number Sheet Title
G-001 COVER SHEET
C-001 CIVIL LEGEND, NOTES & ABBREVIATIONS
CD-100 DEMOLITION PLAN
C-111 SITE PLAN
C-122 GRADING, DRAINAGE & UTILITY PLAN
C-131 LANDSCAPE PLAN
C-141 SIGNAGE AND MARKING PLAN
C-152 EROS. AND SED. CONTROL PLAN - PHASE I
C-161 EROS. AND SED. CONTROL PLAN - PHASE II
C-201 STORM SEWER PROFILES
C-500 SITE DETAILS
C-501 SITE DETAILS
C-502 STORM SEWER DETAILS
C-503 EROSION & SEDIMENT CONTROL NARRATIVE
C-504 EROSION & SEDIMENT CONTROL DETAILS
C-505 EROSION & SEDIMENT CONTROL DETAILS
C-506 EXISTING BUILDING 420 FLOOR PLAN
C-507 LANDSCAPE DETAILS
C-508 SOIL BORING LOGS
E-001 ELECTRICAL COVER SHEET
E-101 ELECTRICAL SITE PLAN
AN ASBESTOS INSPECTION WAS PERFORMED AND IS INCLUDED AS AN APPENDIX TO THE PROJECT SPECIFICATIONS. ACM WAS FOUND GENERALLY IN THE AREAS INDICATED IN THE REPORT. ASBESTOS- CONTAINING BUILDING MATERIALS MAY BE DISTURBED DURING THIS WORK. WHERE SUCH ACTIONS ARE REQUIRED, THE CONTRACTOR MUST HAVE THE ACM REMOVED BY A LICENSED ASBESTOS CONTRACTOR USING APPROVED PROCEDURES AS SPECIFIED. THE WORK REQUIRED FOR ASBESTOS ABATEMENT IS PERMITTED WITHIN THE OVERALL BUILDING PERMIT ISSUED. THE GENERAL CONTRACTOR MUST REVIEW AND CERTIFY THE LOCATIONS WHERE ACM WAS ABATED. NATURALLY OCCURRING ASBESTOS (NOA) MAY BE PRESENT ON SITE. IF CONTRACTOR DISTURBS NOA, CONTRACTOR SHALL HAVE A MITIGATION PLAN IN PLACE DURING EXCAVATION. IF LARGE QUANTITIES ARE ENCOUNTERED, NOA MUST BE BURIED AND
CAPPED ON SITE.
ASBESTOS DISCLOSURE STATEMENT
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS BEEN
CONDUCTED AND IS INCLUDED AS AN APPENDIX IN THE PROJECT SPECIFICATIONS. THIS REPORT IS PROVIDED FOR THE CONTRACTOR'S USE AND MAY NOT BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH)
REGULATIONS AS THEY PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED
BUILDING COMPONENTS SHALL BE RECYCLED TO THE GREATEST EXTENT POSSIBLE.
LEAD MATERIALS DISCLOSURE STATEMENT
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
C-001
CIVIL LEGEND,
NOTES &
ABBREVIATIONS
LEGEND
ADDITIONAL LEGEND INFORMATION PROVIDED ON APPLICABLE SHEETS
ABBREVIATIONS
SURVEY NOTES
1. EXISTING TOPOGRAPHIC AND PLANIMETRIC INFORMATION WAS
COMPILED FROM PHOTOGRAMMETRIC MAPPING BY QUANTUM SPATIAL
ON DECEMBER 21, 2017. SUPPLEMENTAL FIELD SURVEY IN SELECT
AREAS WAS CONDUCTED BY DEWBERRY ENGINEERS IN JANUARY 2024.
2. HORIZONTAL DATUM IS VIRGINIA STATE PLANE COORDINATE SYSTEM (VA
SPCS) NORTH ZONE (NAD 83) IN U.S. SURVEY FEET.
3. VERTICAL DATUM IS NORTH AMERICAN VERTICAL DATUM OF 1988 (NAVD
88) IN U.S. SURVEY FEET.
4. EXISTING UTILITY INFORMATION WAS COMPILED BY FIELD SURVEYS
COMPLETED BY DEWBERRY ENGINEERS INC IN NOVEMBER 2019.
GENERAL UTILITY NOTES
1. A MINIMUM COVER OF THREE (3) FEET IS REQUIRED OVER PROPOSED LINES
UNLESS SHOWN OTHERWISE IN DESIGN PROFILE.
2. UNLESS OTHERWISE NOTED, ALL UTILITIES ARE TO BE INSTALLED
UNDERGROUND. ALL UNDERGROUND UTILITIES ARE TO BE MARKED WITH FOIL
TAPE.
3. ALL EXISTING UTILITIES MAY OR MAY NOT BE SHOWN IN THEIR EXACT
LOCATION.
4. THE CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR ANY ACTIVE UTILITIES
DAMAGED DURING CONSTRUCTION AND NOTIFY THE COR OF THE DAMAGE.
5. LENGTHS OF LINES INDICATED ON THE DRAWINGS FOR UTILITY SYSTEMS ARE
APPROXIMATE ONLY. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
DETERMINE THE EXACT AMOUNT OF PIPING REQUIRED TO FURNISH A
COMPLETE WORKING SYSTEM IN ACCORDANCE WITH THE INTENT OF THE
DRAWINGS.
6. THE CONTRACTOR SHALL SUBMIT AN EXCAVATION REQUEST A MINIMUM OF
SEVEN (7) DAYS PRIOR TO DIGGING; MOUNT WEATHER PERSONNEL WILL
MARK UNDERGROUND UTILITIES UPON RECEIPT OF THE REQUEST. THE
CONTRACTOR IS RESPONSIBLE TO MAINTAIN AND PRESERVE MARKED
UTILITIES THROUGHOUT THE DURATION OF THE CONTRACT.
7. THE CONTRACTOR SHALL SUBMIT A UTILITY OUTAGE REQUEST A MINIMUM OF
SEVEN (7) DAYS IN ADVANCE OF ANY UTILITY OUTAGE.
GENERAL NOTES
1. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION AND
SEQUENCING OF DEMOLITION.
2. ALL WORK SHALL BE PERFORMED IN STRICT COMPLIANCE WITH THE MOST
CURRENT APPLICABLE FEDERAL, STATE , AND LOCAL LAWS AND
REGULATIONS, INCLUDING BUT NOT LIMITED TO, ENVIRONMENTAL
PROTECTION AGENCY (EPA), OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION (OSHA), VIRGINIA OCCUPATIONAL AND SAFETY HEALTH
COMPLIANCE PROGRAM (VOSH ENFORCEMENT), VIRGINIA OVERHEAD HIGH
VOLTAGE LINE SAFETY ACT, NATIONAL EMISSIONS STANDARDS FOR
HAZARDOUS AIR POLLUTANTS (NESHAPS), AND NATIONAL INSTITUTE OF
OCCUPATIONAL SAFETY AND HEALTH (NIOSH).
3. WHEN DURING THE COURSE OF CONSTRUCTION, ANY OBJECT OF AN
UNUSUAL NATURE IS ENCOUNTERED, THE CONTRACTOR SHALL CEASE WORK
IN THAT AREA AND IMMEDIATELY NOTIFY THE COR.
4. DRAINAGE STRUCTURES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE
CURRENT VIRGINIA DEPARTMENT OF TRANSPORTATION DESIGN STANDARDS
AND SPECIFICATIONS.
5. UNDERGROUND FACILITIES HAVE BEEN PLOTTED FROM AVAILABLE SURVEYS
AND RECORDS AND THEREFORE THEIR LOCATION MUST BE CONSIDERED
APPROXIMATE ONLY, THERE MAY BE OTHERS. THE EXISTENCE OF WHICH IS
PRESENTLY NOT KNOWN. THE CONTRACTOR SHALL PROTECT ALL UTILITIES
AT HIS OWN INITIATIVE AND EXPENSE.
6. COMPACTED STRUCTURAL FILLS SHALL BE PLACED IN MAXIMUM 8-INCH THICK
HORIZONTAL LOOSE LIFT LIFTS AND SHALL BE COMPACTED TO 95% OF
THEORETICAL MAXIMUM DENSITY AS DETERMINED BY ASTM SPECIFICATION
D-698 STANDARD PROCTOR METHOD. SOIL MOISTURE CONTENTS AT THE TIME
OF COMPACTION SHALL BE WITHIN 20 PERCENT OF THE SOILS' OPTIMUM
MOISTURE CONTENT.
7. ALL FILL SOILS UNDER EXPANDED PAVED AREAS SHALL BE COMPACTED TO
95% OF THEORETICAL MAXIMUM DENSITY AS DETERMINED BY ASTM
SPECIFICATION D-698 STANDARD PROCTOR METHOD. THE TOP 12 INCHES IN
PAVEMENT AREAS SHALL BE COMPACTED TO AT LEAST 100%.
8. CONCRETE AND ROCK CAN BE DISPOSED ONSITE IN THE EROSION CONTROL
STOCKPILE AS DESIGNATED BY THE COR. CONCRETE AND ROCKS SHALL BE
BROKEN INTO PIECES NOT LARGER THAN EIGHT (8) INCHES AND THERE SHALL
NOT BE ANY EXPOSED REINFORCING STEEL. SURPLUS SUITABLE SOIL
MATERIAL SHALL BE STOCKPILED BY THE COR. UNSUITABLE SOIL AND ALL
OTHER DEBRIS MATERIAL SHALL BE HAULED FROM THE SITE IN ACCORDANCE
WITH ALL LAWS/REGULATIONS. PROVIDE AN EROSION AND SEDIMENT
CONTROL PLAN FOR ANY OFFSITE DISPOSAL AREAS.
9. GRADING, EXCAVATING, CONSTRUCTION OF THE PROJECT SHALL NOT
COMMENCE UNTIL THE APPROPRIATE EROSION AND SEDIMENT CONTROL
MEASURES ARE IN PLACE AS SPECIFIED ON THIS PLAN.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL NECESSARY
PERMITS AND LICENSES REQUIRED BY THE STATE OF VIRGINIA OR OTHER
GOVERNING AGENCIES INVOLVED UNDER THIS CONTRACT.
11. APPROPRIATE FENCING AND BARRICADES SHALL USED WHEN WORK OCCURS
NEAR PEDESTRIAN WALKWAYS.
12. DIMENSIONS SHOWN AT CURB ARE TO FACE OF CURB.
13. PROVIDE POSITIVE DRAINAGE AT ALL GRADED AREAS.
14. IF PORTABLE TOILETS ARE NECESSARY FOR THE CONSTRUCTION OF THE
PROJECT, LOCATE A MINIMUM OF 50 FEET AWAY FROM THE NEAREST
STORMWATER FEATURE (INLET, SWALE, POND, ETC).
15. A SMOOTH GRADE SHALL BE MAINTAINED FROM EDGE OF PAVEMENT OF
EXISTING ROAD TO PROPOSED CURB AND GUTTER AND/OR PROPOSED
PAVEMENT TO PRECLUDE THE FORMING OF FALSE GUTTERS AND/OR THE
PONDING OF ANY WATER ON THE ROADWAY. REMOVE AND RECONSTRUCT
EXISTING PAVEMENT AND/OR CURB AS DICTATED BY FIELD CONDITIONS TO
PROVIDE POSITIVE DRAINAGE AT TIE-IN-POINTS.
16. ALL SOLID WASTE, HAZARDOUS WASTE, AND HAZARDOUS MATERIALS MUST
BE MANAGED IN ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE AND
LOCAL ENVIRONMENTAL REGULATIONS.
17. AIR QUALITY REGULATIONS: THE FOLLOWING SECTIONS OF THE CODE OF
VIRGINIA AND VIRGINIA ADMINISTRATIVE CODE ARE APPLICABLE:
· ASPHALT PAVING OPERATIONS (9 VAC 5-45-780 ET. SEQ.)
· FUGITIVE DUST AND EMISSIONS CONTROL (9 VAC 5-50-60 ET. SEQ.)
· BURNING IS NOT PERMITTED ON THE MWEOC
· PERMITS FOR FUEL BURNING EQUIPMENT (9 VAC 5-80-1100 ET. SEQ.)
18. THE REMOVAL OF ANY REGULATED PETROLEUM STORAGE TANKS, ABOVE
GROUND STORAGE TANKS (AST) OR UNDERGROUND STORAGE TANKS (UST),
MUST BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE VIRGINIA TANK
REGULATIONS 9 VAC 25-91-10 ET. SEQ. (AST) AND/OR 9 VAC 25-580-10 ET. SEQ.
(UST).
19. CONTRACTOR IS RESPONSIBLE FOR ALL PROJECT STAKEOUT
20. NATURALLY OCCURRING ASBESTOS HAS BEEN IDENTIFIED IN THE
SUBSURFACE SOIL/ROCK LAYERS ON THIS PROPERTY DURING PREVIOUS
GEOTECHNICAL INVESTIGATIONS. IMPLEMENT ALL BEST PRACTICES FOR
EARTHWORK CONSTRUCTION IN/AROUND NATURALLY OCCURING ASBESTOS,
EQUIPMENT AND PERSONEL DECONTAMINATION ALONG WITH AIR MONITORS
AND DISPOSAL PRACTICES IN STRICT COMPLIANCE WITH THE MOST CURRENT
APPLICABLE REGULATIONS.
PROJECT NARRATIVE
THE WORK CONSISTS OF THE FOLLOWING:
1. CONSTRUCTION LINE ITEM 1 (CLIN 1) (BASE BID) SHALL INCLUDE THE
FOLLOWING:
a. THE CONTRACTOR UNDER THIS CONTRACT SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, FACILITIES, MANAGEMENT, SURVEYS, TESTING, AND SERVICES NECESSARY TO ACCOMPLISH THE PROJECT CONTRACT
REQUIREMENTS. THE PROJECT SITE IS LOCATED AT THE MT. WEATHER
EMERGENCY OPERATION CENTER (MWEOC) 19833 BLUERIDGE
MOUNTAIN RD, MT. WEATHER, VA 20135.
b. DISMANTLE AND STORE ONSITE (WITHIN ONE (1) MILE HAULING
DISTANCE) EXISTING ANTENNAS TO THE CONCRETE FOUNDATIONS.
CONCRETE FOUNDATIONS SHALL BE RAZED TO A DEPTH OF FIVE (5)
FEET BELOW DESIGN DEPTH OF PARKING LOT SUBGRADE.
c. HAZARDOUS MATERIAL ABATEMENT FOR THE REMOVAL OF ASBESTOS
CONTAINING MATERIALS AND LEAD BASED PAINT WITHIN BUILDING 420.
d. DEMOLITION OF BUILDING 420.
e. DEMOLITION OF THE PARKING LOT ACCESS APRONS AND THE ASPHALT
PARKING LOT SERVING BUILDING 420.
f. DEMOLITION OF A 1,500 GALLON UNDERGROUND FUEL STORAGE TANK.
g. REMOVAL OF EXISTING UTILITIES AS INDICATED ON THE DRAWINGS.
h. CONCRETE CAN BE DISPOSED ON SITE IN THE DESIGNATED EROSION
CONTROL STOCK PILE. CONCRETE AND ROCKS SHALL BE BROKEN INTO
PIECES NO LARGER THAN 8" AND THERE SHALL NOT BE ANY EXPOSED
REINFORCING STEEL. ALL OTHER DEBRIS SHALL BE REMOVED FROM
THE SITE.
i. SITE WORK SHALL INCLUDE ESTABLISHING AND MAINTAINING EROSION
AND SEDIMENT CONTROLS THROUGHOUT CONSTRUCTION.
j. CONSTRUCTION OF PARKING LOT AND SIDEWALKS COMPLETE WITH
SIGNAGE, PAVEMENT MARKINGS, STORM DRAINAGE SYSTEM, BUS
SHELTER, AND SITE LIGHTING.
k. ESTABLISH NEW ELECTRICAL SERVICE ON EQUIPMENT ON A NEW
EXTERIOR CONCRETE PAD INTERCEPTING EXISTING FEEDERS TO
BUILDINGS 408 AND 410, CURRENTLY SERVED FROM BUILDING 420. NEW
ELECTRICAL SERVICE SHALL ACCOMMODATE SITE LIGHTS AND
OUTLETS.
l. REPLACEMENT OF THE EXISTING SIDEWALK ALONG BALLOON SHED
DRIVE.
m. CONDUIT/DUCT INSTALLATION AND BOXES/PEDESTALS FOR THE BUS
SHELTER PHONE, SECURITY CAMERAS, VEHICLE CHARGING STATION,
MOBILE COMMUNICATION VEHICLE POWER AND MOBILE
COMMUNICATION VEHICLE COMMUNICATION COMPLETE WITH PULL
STRINGS.
n. GRADING, TURF, AND LANDSCAPING ESTABLISHMENT.
2. CONSTRUCTION LINE ITEM 2 (CLIN 2) (BID OPTION 1) SHALL INCLUDE THE
FOLLOWING:
a. INSTALLATION OF FOUR (4) CHARGE POINT CT 250 CHARGING STATIONS
MATCHING SITE WIDE INFRASTRUCTURE. INSTALLATION SHALL INCLUDE
CHARGING STATION PEDESTALS AND MOBILE COMMUNICATION VEHICLE
PEDESTALS INCLUDING CONCRETE FOUNDATIONS, CONDUIT ROUTING
FROM JUNCTION BOXES, AND ALL ELECTRICAL EQUIPMENT AND
CIRCUITRY NECESSARY FOR COMPLETE OPERATIONAL SYSTEMS. WORK
TO INCLUDE COMMUNICATIONS CIRCUITRY FOR CHARGING STATIONS
FOR POINT OF SALE FUNCTIONALITY. COMMUNICATION PATH CONDUIT
REQUIRED FROM JUNCTION BOXES TO MOBILE COMMUNICATION
VEHICLE PEDESTALS.
STORMWATER NOTES
1. THE DEQ INSPECTOR SHOULD B INVITED TO THE PRE-CONSTRUCTION MEETING
AND NOTIFIED ONE WEEK PRIOR TO THE START OF LAND DISTRUBANCE.
PLEASE CONTACT MARK REMSBERG TO COORDINATE THESE NOTIFICATIONS.
MARK CAN BE REACHED AT 703-583-3874 OR
MARK.REMSBERG@DEQ.VIRGINIA.GOV. PLEASE REACH OUT TO MR. REMSBERG
TO ACCOMMODATE RENEWED DEQ ACCESS TO THE MWEOC FACILITY.
2. DEQ CONSTRUCTION GENERAL PERMIT SELF-SITE INSPECTIONS SHALL BE
PERFORMED ONCE EVERY 5-BUSINESS DAYS AND WITHIN 24 HOURS AFTER A
MEASURABLE STORM EVENT OR ONCE EVERY 4-BUSINESS DAYS. A
MEASURABLE STORM EVENT IS DEFINED AS A RAINFALL EVENT PRODUCING
0.25 INCHES OF RAIN OVER 24 HOURS OR SNOWMELT FROM A SNOW EVENT
PRODUCING 3.25 INCHES OR MORE OF SNOW WITHIN 24-HOUR PERIOD IN
ACCORDANCE WITH 9VAC25-880.1.
3. IF AN OFFSITE DISPOSAL AREA IS IDENTIFIED DURING CONSTRUCTION, THE
CONSTRUCTION ACTIVITY OPERATOR SHALL PROVIDE DETAILED INFORMATION
TO DEQ, THROUGH THE UPDATING OF ITS REGISTRATION STATEMENT,
REGARDING THE LOCATION OF THE DISPOSAL SITE AND MATERIAL TO BE
DISPOSED OF AT THAT SITE. THIS NOTIFICATION TO DEQ NEEDS TO OCCUR
PRIOR TO TRANSPORTING ANY MATERIAL OFF-SITE.
4. A NOTICE OF TERMINATION (NOT) PACKAGE MUST BE SUBMITTED, AND
ACCEPTED BY DEQ AS COMPLETE, PRIOR TO SCHEDULING A FINAL DEQ SITE
INSPECTION. THE NOTICE OF TERMINATION REQUIRES AS-BUILT
CONSTRUCTION RECORD DRAWINGS FOR ALL PERMANENT STORMWATER
INFRASTRUCTURE. THESE DRAWINGS SHOULD REPRESENT THE STORMWATER
MANAGEMENT FACILITIES AS THEY WERE CONSTRUCTED. THE INFORMATION
SHOULD BE DETAILED ENOUGH THAT THE FACILITY COULD BE
RECONSTRUCTED TO THE ORIGINAL CONSTRUCTED SPECIFICATIONS. PLEASE
REFER TO SECTION 4.4.3.1 OF DEQ'S UPDATED STORMWATER MANAGEMENT
HANDBOOK ENTITLED BMP RECORD DOCUMENTS AND CERTIFICATIONS FOR
MORE INFORMATION. SOME INFORMATION MAY NEED TO BE COLLECTED WHILE
THE FACILITY IS BEING CONSTRUCTED SINCE SOME VITAL COMPONENTS WILL
NOT BE VISIBLE OR ACCESSIBLE ONCE IT IS COMPLETED. A LICENSED
PROFESSIONAL OF RECORD MUST CERTIFY THAT THE FACILITY HAS BEEN
CONSTRUCTED IN ACCORDANCE WITH APPROVED PLANS AND SPECIFICATION,
AND IN ORDER TO CERTIFY THIS, CONSTRUCTION OF CERTAIN COMPONENTS
MUST BE OBSERVED.
STORMWATER LONG-TERM INSPECTION, OPERATION & MAINTENANCE REQUIREMENTS
A. GENERAL
DO NOT ENTER UNDERGROUND CHAMBERS OR VAULTS UNLESS OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION (OSHA) REGULATIONS FOR CONFINED SPACE ENTRY ARE FOLLOWED. ALL ACCESS BELOW GRADE SHOULD BE DONE BY A QUALIFIED ENGINEER AND/OR CONTRACTOR.
B. RESPONSIBILITY
INDIVIDUAL(S) RESPONSIBLE FOR THE O&M AND INSPECTION WORK WILL BE ROADS & GROUNDS STAFF TO INCLUDE TITLE AS “MAINTENANCE WORKER” AND “ENGINEERING EQUIPMENT OPERATOR.” WITH OVERSITE BY MOUNT WEATHER FACILITIES MANAGEMENT DIVISION AND ESOH.
C. RECOMMENDED SCHEDULE FOR MAINTENANCE AND INSPECTION.
C-1. OUTLET CONTROL STRUCTURE (OCS):
· AFTER MAJOR RAIN EVENTS: CHECK THAT THE OCS IS FUNCTIONING AS DESIGNED.
· ONCE A YEAR: CHECK IF SEDIMENT AND/OR DEBRIS HAVE ACCUMULATED IN THE OCS AND REMOVE, AS NECESSARY.
· EVERY TWO YEARS: CHECK SEALS WHERE STORM PIPES PENETRATE THE WALLS OF THE OCS. ALL SEALS MUST BE WATERTIGHT WITH NO VISIBLE
SIGNS OF SEEPAGE OR SOIL INTRUSION FROM OUTSIDE OF THE OCS. ANY SEAL REPAIRS SHOULD BE PERFORMED BY A QUALIFIED CONTRACTOR.
· EVERY FIVE YEARS: THE OWNER SHOULD HIRE A QUALIFIED ENGINEER/CONTRACTOR TO PERFORM A STRUCTURAL INSPECTION OF THE OCS
INCLUDING ALL STRUCTURAL ELEMENTS. THE ENGINEER/CONTRACTOR SHOULD PROVIDE THE OWNER WITH A REPORT THAT DOCUMENTS ALL FINDINGS OF THE INSPECTION INCLUDING ANY DEFICIENCIES FOUND WITH RECOMMENDATIONS ON HOW THEY SHOULD BE CORRECTED.
C-2. STORMCAPTURE MODULES BY OLDCASTLE INFRASTRUCTURE
· · FOLLOW MANUFACTURE'S REQUIREMENTS. REFERENCE COPY INCLUDED IN THE PROJECT'S DESIGN ANALYSIS REPORT:
C-3. PERMENENT LEVEL SPREADER
· INSPECT THE LEVEL SPREADER AT LEAST ONCE A YEAR AND AFTER EVERY MEASURABLE RAINFALL EVENT (I.E., 0.5 INCH PER 24 HOURS) AND MAKE
REPAIRS IMMEDIATELY AS NEEDED.
· MAINTAIN THE LEVEL SPREADER LIP AT ZERO GRADE TO ALLOW PROPER FUNCTION OF THE MEASURE. AVOID THE PLACEMENT OF ANY MATERIAL ON
THE LEVEL SPREADER AND PREVENT CONSTRUCTION TRAFFIC ACROSS THE STRUCTURE.
· IMMEDIATELY REPAIR ANY DAMAGE TO THE LEVEL SPREADER. INSPECT THE LEVEL SPREADER IN THE SAME CONDITIONS FOR SUBSIDENCE ALONG
THE PERIMETER OF THE MEASURE.
· INSPECT FOR LOW POINTS, SAGS, CRACKS, BREAKS, ETC. IN THE LEVEL SPREADER THAT WOULD RESULT IN CONCENTRATED FLOW DISCHARGING
OVER THE SPREADER. ANY IDENTIFIED ALTERATIONS TO THE GRADE OF THE LEVEL SPREADER MUST BE REPAIRED IMMEDIATELY.
· DEBRIS BUILDUP WITHIN THE CHANNEL SHOULD BE REMOVED WHEN IT HAS ACCUMULATED TO 20% OF CHANNEL CAPACITY. INSPECT THE
DOWNSTREAM AREA OF THE LEVEL SPREADER FOR ANY DEVELOPMENT OF WATER CHANNELIZATION OR SUBSIDENCE.
NOT IN CONTRACT
X X
XXXXXX
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
XXXXXX
X X
X X
XREMOVE EX.
TREES
X X
REMOVE EXISTING TREES WITHIN
LIMITS OF CLEARING AND GRADING
SEE NOTE 20
EX. CLEANOUT
(TO BE REMOVED)
EX. COMM
(TO REMAIN)
EX. CLEANOUT
(TO BE REMOVED)
EX. SSWR MH
(TO BE REMOVED)
EX. TRENCH DRAIN
(TO BE REMOVED)
EX. CONCRETE
(TO BE REMOVED)
EX. CONCRETE
(TO BE REMOVED)
EX. STORM
(TO BE REMOVED)
EX. ASPHALT
(TO BE REMOVED)
EX. ASPHALT
(TO BE REMOVED)
EX. COMM
(TO BE MAINTAINED)
EX. SANITARY SEWER
(TO BE REMOVED)
EX. WATER SERVICE
(TO BE REMOVED)
X X X X
EX. STORM
(TO BE REMOVED)
EX. CLEANOUT
(TO BE REMOVED) EX. ELEC
(TO BE REMOVED)
EX. SSWR
(TO BE REMOVED)
X X X X X X X X X X
X
X X
X X
X X
X
X X X X X X X X X X XX
CONC. SIDEWALK
(TO BE REMOVED)
CONC. SIDEWALK
(TO BE REMOVED)
CONC. SIDEWALK
(TO BE REMOVED)
EX. COMM MANHOLE
(TO REMAIN)
ELEC MANHOLE
(TO REMAIN)
EX. COMM MANHOLE
(TO REMAIN)
EX. COMM
(TO BE REMOVED)
X
XX
XX
PLUG DEMOLISHED INFLOW
(SEE NOTE 17)
EX. 1500 GALLON FUEL
TANK TO BE REMOVED
LIMITS OF DISTURBANCE
LIMITS OF DISTURBANCE
PLUG AND BLOCK EXISTING
WATERLINE AT TEE PER
DETAIL ON SHEET C-501
INSTALL PLUG AT EX.
MANHOLE PER DETAIL ON
SHEET C-501
X X X X
INSTALL PLUG AT EX.
STRUCTURE PER DETAIL ON
SHEET C-501
B-01
B-02
B-03
B-04
B-06
B-07
B-05
B-08
EX. WATER
(TO REMAIN)
EX. WATER
(TO REMAIN)
EX. ELECT.
(TO REMAIN)
EX. TELEPHONE
(TO REMAIN)
EX. WATER
(TO REMAIN)
EX. SEWAGE
FORCE MAIN
(TO BE REMOVED)
EX. COMM
(TO REMAIN)
EX. ELECT.
(TO BE REMOVED)
EX. COMM
(TO REMAIN)
X X
X X X X X X X X X X X X X X X X
EX. ELECT.
(TO REMAIN)
EX. COMM
(TO REMAIN)
EX. ELECT.
(TO REMAIN)
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X X
X
EX. SHURBS
(TO BE REMOVED)
X
EX. BUILDING 420
(TO BE DEMOLISHED)
EX. STORM PLUMBING
LEADERS & PIPES
(TO BE REMOVED)
X
EXISTING LIGHT
TO REMAIN IN SERVICE.
TEMPORARILY REMOVE AND
RECONSTRUCT/INSTALL LIGHT
POLE/FOUNDATION
IF NECESSARY TO FACILITATE
PROPOSED WORK.
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
CD-100
DEMOLITION PLAN
DEMOLITION NOTES
1. NO LAND DISTURBANCE, AS DEFINED IN 9VAC25-875-20,
ASSOCIATED WITH DEMOLITION SHALL OCCUR UNTIL DEQ’S
CONSTRUCTION GENERAL PERMIT COVERAGE LETTER IS
OBTAINED AND POSTED AT THE CONSTRUCTION SITE.
2. NO DEMOLITION CAN BEGIN UNTIL ALL PHASE 1 EROSION AND
SEDIMENT CONTROL MEASURES ARE IN PLACE.
3. THE CONTRACTOR SHALL HAVE ALL UTILITIES FIELD DELINEATED AND
MARKED PRIOR TO COMMENCEMENT TO WORK. MWEOC REQUIRES A
MINIMUM OF SEVEN (7) DAYS NOTICE TO COMPLETE UTILITY
MARKINGS.
4. ALL WORK SHALL BE PERFORMED IN STRICT COMPLIANCE WITH THE
MOST CURRENT APPLICABLE FEDERAL, STATE AND LOCAL LAWS AND
REGULATIONS, INCLUDING BUT NOT LIMITED TO ENVIRONMENTAL
PROTECTION AGENCY (EPA), OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION (OSHA), NATIONAL EMISSIONS STANDARDS FOR
HAZARDOUS AIR POLLUTANTS (NESHAPS) AND NATIONAL INSTITUTE
OF OCCUPATIONAL SAFETY AND HEALTH (NIOSH) AND DEQ'S
CONSTRUCTION GENERAL PERMIT.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION
OF WORK WITH MWEOC AND FOR THE IMPLEMENTATION OF REQUIRED
UTILITY-RELATED WORK.
6. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR UPON
ENCOUNTERING ANY HAZARDOUS MATERIALS DURING DEMOLITION
AND/OR CONSTRUCTION ACTIVITIES. THE CONTRACTOR SHALL
DOCUMENT SAME TO THE COR AND OBTAIN DIRECTION AS TO THE
APPROPRIATE ACTION(S) TO BE TAKEN IN ACCORDANCE WITH THE
CONSTRUCTION SPECIFICATION.
7. DISCONNECTION OF THE SERVICES AND SYSTEMS SUPPLYING
UTILITIES TO BE DEMOLISHED SHALL BE COMPLETED PRIOR TO OTHER
SITE DEMOLITION IN FULL COMPLIANCE WITH APPLICABLE CODES,
REGULATIONS, AND THE REQUIREMENTS OF MWEOC. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH
MWEOC. REFER TO THE CONSTRUCTION SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
8. NEW UTILITIES NEED TO BE INSTALLED AND READY FOR SERVICE
PRIOR TO DISCONNECTION/DEMOLITION OF EXISTING UTILITIES.
EXTENDED OUTAGES NEEDED FOR TRANSITION/CONNECTION TO NEW
UTILITY SERVICES SUCH AS ELECTRICAL, COMMUNICATIONS, WATER,
AND SANITARY MAY NEED TO BE CONDUCTED AFTER NORMAL DUTY
HOURS. COORDINATE CONNECTIONS/TRANSITIONS WITH THE COR.
9. PRIOR TO REMOVAL OF MATERIALS OVER EXISTING UTILITY SYSTEMS,
THE CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS AND, IF
AT VARIANCE WITH CONDITIONS AS REPRESENTED ON THE PLANS,
NOTIFY THE COR AND OBTAIN DIRECTIONS TO THE APPROPRIATE
ACTION(S) TO BE TAKEN.
10. PRIOR TO COMMENCING NEW WORK, THE CONTRACTOR SHALL
PROTECT FROM DAMAGE EXISTING ADJACENT AREAS. ALL ADJACENT
AREAS DAMAGED DURING DEMOLITION AND/OR CONSTRUCTION
ACTIVITIES SHALL BE RESTORED TO ORIGINAL OR BETTER CONDITION
AT NO ADDITIONAL COST TO THE GOVERNMENT.
11. THE CONTRACTOR SHALL PROTECT AND PREVENT DAMAGE TO
EXISTING ON-SITE UTILITY DISTRIBUTION FACILITIES.
12. DURING DEMOLITION AND/OR CONSTRUCTION ACTIVITIES, THE
CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR UPON
ENCOUNTERING ANY EXISTING UTILITIES AND/OR UTILITY SYSTEM
STRUCTURES NOT SHOWN ON THESE PLANS. THE CONTRACTOR
SHALL DOCUMENT SAME TO THE COR AND OBTAIN DIRECTIONS AS TO
THE APPROPRIATE ACTION(S) TO BE TAKEN. DO NOT DISTURB
WITHOUT COR PERMISSION.
13. ALL EXISTING UTILITY STRUCTURES TO REMAIN ARE REQUIRED TO BE
ADJUSTED FLUSH WITH PROPOSED GRADE, AS NEEDED. THIS
INCLUDES BUT IS NOT LIMITED TO MANHOLES, VALVES, CLEANOUTS,
HANDHOLES, METERS AND STORM DRAINAGE INLETS.
14. SITE LIGHTS AND LIGHT POLES THAT ARE REMOVED SHALL BE
SALVAGED AND RETURNED TO THE GOVERNMENT.
15. THERE IS A GOVERNMENT OPERATED SECURITY CAMERA ON BUILDING
420 WITH INFRASTRUCTURE TIED TO THE MWEOC CAMPUS SYSTEM
FOR DISPATCH. THE ET SHOP WILL RELOCATE THE CAMERA AND
INFRASTRUCTURE BEFORE DEMOLITION OF THE FACILITY.
16. PRIOR TO THE START OF BUILDING DEMOLITION, ONCE THE FIRE
ALARM IS DECOMMISSIONED, ET SHOP PERSONNEL WILL REMOVE THE
CABINET CONTAINING THE MN-NET RELAY AND THEN ALL OTHER
REMAINING FIRE ALARM DEVICES/EQUIPMENT CAN BE DEMOLISHED
WITH THE BUILDING BY THE CONTRACTOR.
17. DEMOLISHED INFLOW HOLE SHALL BE PLUGGED. CONTRACTOR SHALL
SEAL LEAKS AND VACUUM TEST FOR COMPLIANCE WITH PROJECT
SPECIFICATIONS.
18. SEE "ACM AND LBP INTERIOR SURVEY" PERFORMED IN FEBRUARY 2010
AND SHEET C-506 FOR BUILDING 420 FLOOR PLAN AND
ASBESTOS-CONTAINING MATERIALS (ACM) AND LEAD-BASE PAINT (LBP)
INTERIOR SURVEY FINDINGS.
19. WHERE TREES ARE NOTED TO BE REMOVED, OPERATIONS SHALL
INCLUDE CLEARING AND GRUBBING THE REMOVAL AREA AND
RETURNING GRADE TO A CONDITION THAT CAN BE MOWED.
20. SALVAGE EXISTING ANTENNAS: DISMANTLE EXISTING ANTENNAS TO
THE CONCRETE FOUNDATION AND STORE ONSITE. STORAGE
LOCATION PER COR DIRECTION WITHIN ONE (1) MILE HAULING
DISTANCE. RAZE CONCRETE FOUNDATION TO A DEPTH OF FIVE (5)
FEET BELOW PROPOSED PARKING LOT SUBGRADE.
PHASING NOTES
1. ACCESS TO BUILDING 444 SHALL BE MAINTAINED THROUGHOUT
CONSTRUCTION.
2. BALLOON SHED DRIVE SHALL REMAIN OPEN TO 2-LANE TRAFFIC AT ALL
TIMES.
18. PROVIDE TEMPORARY SERVICES OR BY-PASS FOR UTILITIES THAT ARE
IMPACTED FOR MORE THAN 4-HOURS TO SERVICE IMPACTED
BUILDING(S) (I.E. BUILDING 444) AS APPLICABLE.
DEMOLITION LEGEND
X X
9.5'19 .0
9.5'19 .0
9.5'19
.0
9.5'19 .0
.0
10.0'
.0
.0
22.0'
22.0'
9.
5'
17.0'
22.0'
22.0'
9.5
5' CONCRETE SIDEWALK
5' CONCRETE SIDEWALK
MODULAR BLOCK
RETAINING WALL
(MAX HT. ±4')
CG-6 CG-6
CG
-6
C G
-6
BUS SHELTER ON
CONCRETE PAD WITH
SURROUNDING CURB
SEE DETAILS ON
SHEET C-500
J
J
J
PARKING LOT
LIGHT (TYP.)
PARKING LOT
LIGHT (TYP.)
CLIN 2: INSTALL FOUR (4)
ELECTRIC VEHICLE
CHARGING STATIONS
(SEE ELEC. PLAN AND
C-500 FOR PAD DETAILS)
BOLLARD (TYP.)
CONCRETE STAIRCASE (VDOT S-2, W=5).
TOP OF STAIR=1704.5'. BOTTOM OF STAIR=1699.0'
PROVIDE HANDRAIL (VDOT HR-1).
5' CONCRETE SIDEWALK
3.0'
ROLL-UP COMM VEHICLE
CONNECTION POINTS
(SEE ELEC. PLAN)
DETECTABLE WARNING
SURFACE REQUIRED (SEE
DETAIL ON SHEET C-501)
DETECTABLE WARNING
SURFACE REQUIRED (SEE
DETAIL ON SHEET C-501)
DETECTABLE WARNING
SURFACE REQUIRED
(SEE DETAIL ON SHEET
C-501)
ELECTRICAL SERVICE
EQUIPMENT ON
CONCRETE PAD
DETECTABLE WARNING
SURFACE REQUIRED (SEE
DETAIL ON SHEET C-501)
6.
0' 16
.0
REALIGN GRAVEL ACCESS ROAD
AROUND EXTENT OF FILL
VDOT STD CG-12 TYPE B
(SEE DETAIL ON SHEET
C-501)
19.0' 1.0'9
C G
-6
LIMITS OF DISTURBANCE
LIMITS OF DISTURBANCE
CG-6
END CG-6
BEGIN CG-6
2 3
R7.0'
R7.5'
R1 0.0
R7.0'
R35.0'
R15.0'
R7.5' R7.5
R7.5'
R10.0'
R5 .0
R15 .0'
R15.0' R3.0'
R3.0'
R2.0
R2.0'
R2.0'
R2.0' R2.0'
59 60
R
9.
0'
SITE GEOMETRIC COORDINATES
POINT NO.
NORTHING
7,070,531.2
7,070,428.9
7,070,420.9
7,070,401.5
7,070,245.1
7,070,272.3
7,070,295.0
7,070,325.3
7,070,333.5
7,070,333.0
7,070,343.7
7,070,356.4
7,070,478.1
7,070,465.0
7,070,476.5
7,070,506.1
7,070,523.9
7,070,510.0
7,070,478.8
7,070,438.8
7,070,399.9
7,070,405.3
EASTING
11,656,282.2
11,656,203.5
11,656,214.0
11,656,208.0
11,656,411.3
11,656,432.2
11,656,487.1
11,656,510.4
11,656,507.1
11,656,481.5
11,656,461.9
11,656,460.2
11,656,302.1
11,656,292.0
11,656,289.3
11,656,312.2
11,656,291.7
11,656,331.6
11,656,333.0
11,656,375.9
11,656,426.7
11,656,430.8
SITE GEOMETRIC COORDINATES
POINT NO.
NORTHING
7,070,416.9
7,070,419.7
7,070,387.7
7,070,366.6
7,070,361.6
7,070,357.5
7,070,325.4
7,070,319.0
7,070,303.1
7,070,287.3
7,070,308.8
7,070,430.5
7,070,398.4
7,070,241.9
7,070,254.9
7,070,239.8
7,070,231.5
7,070,246.6
7,070,179.4
7,070,150.6
7,070,008.9
7,070,493.0
EASTING
11,656,429.2
11,656,434.0
11,656,476.6
11,656,479.5
11,656,519.1
11,656,500.3
11,656,487.3
11,656,471.9
11,656,459.7
11,656,447.5
11,656,423.6
11,656,265.5
11,656,205.6
11,656,408.9
11,656,382.7
11,656,400.3
11,656,393.1
11,656,375.4
11,656,367.2
11,656,325.7
11,656,437.0
11,656,312.1
SITE GEOMETRIC COORDINATES
POINT NO.
NORTHING
7,070,486.4
7,070,343.4
7,070,340.2
7,070,445.2
7,070,426.9
7,070,312.4
7,070,294.2
7,070,446.0
7,070,416.1
7,070,259.4
7,070,266.4
7,070,294.1
7,070,297.1
7,070,424.7
7,070,372.6
7,070,314.6
7,070,480.7
7,070,419.4
7,070,371.7
7,070,409.9
7,070,401.0
7,070,124.6
EASTING
11,656,299.5
11,656,450.1
11,656,451.2
11,656,265.2
11,656,251.2
11,656,437.8
11,656,423.8
11,656,168.2
11,656,201.0
11,656,316.9
11,656,316.0
11,656,343.6
11,656,339.6
11,656,273.0
11,656,340.8
11,656,416.1
11,656,316.5
11,656,387.1
11,656,457.7
11,656,192.9
11,656,194.4
11,656,366.2
SITE GEOMETRIC COORDINATES
POINT NO.
NORTHING
7,070,059.9
EASTING
11,656,405.9
WHEELSTOP (TYP.)
(SEE C-500 FOR DETAIL)
MANHOLE
PIPE END SECTION
MANHOLE
EXISTING ELECTRIC
HANDHOLE
EXISTING ELECTRIC
MANHOLE
C-111
SITE PLAN
LEGEND
ASPHALT PAVEMENT
CONCRETE SIDEWALK
PROPOSED PARKING TABULATION
PROPOSED PARKING SPACES (9.5'x19'): 113 PROPOSED OVERSIZED SPACES (10'x40'): 3
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
NOTE:
CONTRACTOR IS RESPONSIBLE
FOR PROJECT SURVEY STAKEOUT.
LIMITS OF DISTURBANCE
ADJUST EXISTING
HANDHOLD TO
PROPOSED
GRADE
15" RCP
MODULAR BLOCK
RETAINING WALL
(MAX HT. ±4')
ADJUST EX. COMM MH TO PROPOSED GRADE
EX. COMM
TO REMAIN
3:1 SLO
PE
3:1 SLOPE
15" R C
P
STM
STM
STORMWATER MANAGEMENT FACILITY UG-1
(6) STORMCAPTURE MODULES BY
OLDCASTLE INFRASTRUCTURE OR EQUAL
INSIDE DIMENSIONS: 7'W X 15'L X 6'H
TOTAL STORAGE=3,780 CF
INSIDE TOP ELEV=1691.00
SYSTEM INVERT=1685.00
IN=1688.75 (15" STM)
OUT=1685.00 (36" OPENING INTO FLOW CONTROL STR)
FLOW CONTROL STRUCTURE BY
OLDCASTLE INFRASTRUCTURE OR EQUAL
(SEE SHEET C-501 FOR DETAIL)
J
J
J
PARKING LOT
LIGHT (TYP.)
PARKING LOT
LIGHT (TYP.)
CLIN 2: INSTALL FOUR (4)
ELECTRIC VEHICLE
CHARGING STATIONS
(SEE ELEC. PLAN AND
C-500 FOR PAD DETAILS)
3:1 SLO
PE
ROLL-UP COMM VEHICLE
CONNECTION POINTS
(SEE ELEC. PLAN)0.5%1702.46
1701.78
1701.29
ELECTRICAL SERVICE
EQUIPMENT ON
CONCRETE PAD
6' PVC DRAIN
1701.82
1701.59
1702.06
1703.511707.33
1707.89
1702.91
1702.67 1700.78
OUT
STM
0A
STM
FCS
STM
0B
STM
15" RCP
1702 1703
1703.17
FFE=1707.85
15" RCP
167516761678
LEVEL SPREADER
WITH PLUNGE POOL
SEE DETAIL SHT C-500
C-122
GRADING,
DRAINAGE & UTILITY
PLAN
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
15" RCP 3:1 SLO
PE
3:1 SLOPE
15" R C
P
J
J
J
3:1 SLO
PE
0.5%
15" RCP
15" RCP
1 QM
15 AA
5 JV
3 PT
42 AA
42 CA
4 QM
85 HC
93 HC
21 RA
50 CA
99 RA
153 HC
38 RA
C-131
LANDSCAPE PLAN
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
9.5'19 .0
9.5'19 .0
9.5'19 .0
9.5'19 .0
.0
10.0'
.0
.0
22.0'
22.0'
9.
5'
17.0'
22.0'
9.5
J
J
J
3.0'
6.
0'
.0
19.0'
1.0'
LIMITS OF DISTURBANCE
LIMITS OF DISTURBANCE
C-141
SIGNAGE AND
MARKING PLAN
KEY NOTES
1. "ELECTRIC VEHICLE CHARGING STATION (LEFT
ARROW/RIGHT ARROW)" SIGN
2. "PARKING" SIGN (RIGHT ARROW) W/ LOT # SIGN
3. "PARKING" SIGN (LEFT ARROW) W/ LOT # SIGN
4. "STOP" SIGN
5. "RV/BUS PARKING ONLY" SIGN
6. "SHUTTLE STOP" SIGN
7. WAYFINDING SIGN
8. 6" WHITE PARKING STRIPE (TYP.)
9. STOP BAR (TYPE B, CLASS I, WHITE, 24" WIDTH)
10. PHONE DIRECTORY SIGN
(TO BE MOUNTED INSIDE SHELTER)
11. CROSSWALK (TYPE B, CLASS I, WHITE, 24"
WIDTH)
12. 6" WHITE STRIPES, 45° ANGLE, 24" SPACING
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
CAFE/CONFERENCE CENTER
BUILDINGS 433/437
BUILDINGS 407/405
SHUTTLE: 540-542-2117
EMERGENCY: 540-542-3333
SHUTTLE:
540-542-2117
EMERGENCY:
540-542-3333
LOCATION:
LOT 420
LOT
LOT
NOTES
1. ALL SIGNAGE TO BE ENGINEER GRADE
REFLECTIVE SHEETING ON ALUMINUM.
2. SUBMIT PRODUCTION PROOF OF EACH SIGN
PRIOR TO FABRICATION FOR COR APPROVAL.
3. LOCATIONS ARE APPROXIMATE; COORDINATE
FINAL AND ACCEPTABLE LOCATION WITH COR
PRIOR TO INSTALLATION.
4. SEE CROSSWALK PAINTING DETAIL ON SHEET
C-501.
DC
TS
LIMITS OF DISTURBANCE
PROVIDE DUST CONTROL AND TEMPORARY
SEEDING AS REQUIRED THROUGH
CONSTRUCTION PHASING. COORDINATE
WITH DEQ INSPECTOR.
0.19AC @ C=0.32
TO SILT FENCE
X
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X X
X
X
0.14AC @ C=0.90 TO
ROOF DRAINS
0.06AC @ C=0.90 TO
DRAINAGE EX.
TRENCH DRAIN
0.14AC @ C=0.90 TO
ROOF DRAINS
0.21AC @ C=0.50
TO INLET PROTECTION
0.13AC @ C=0.83
TO SILT FENCE
0.21AC @ C=0.39
TO SUPER SILT
FENCE
0'
0.23AC @ C=0.41
TO SUPER SILT
FENCE
0.12AC @ C=0.35
TO SUPER SILT
FENCE
CONCRETE
WASHOUT
X
X
X
TEMP
STOCKPILE
LOCATION
0.15AC @ C=0.35
TO SUPER SILT
FENCE
X
X X
X
X X X X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X
X
X
X
XX
X X
X X
X
X
X X
X X
X X
XX
XX XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX XX
XX
XX XX
XX
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
C-152
EROS. AND SED.
CONTROL PLAN -
PHASE I
15" RCP 3:1 SLO
PE
3:1 SLOPE
15" R C
P
J
J
J
3:1 SLO
PE
0.5%1702.46
1701.78
1701.29
1701.82
1701.59
1702.06
1703.511707.33
1707.89
1702.91
1702.67 1700.78
15" RCP
1702 1703
1703.17
FFE=1707.85
15" RCP
167516761678
LIMITS OF DISTURBANCE
LIMITS OF DISTURBANCE
0.65AC @ C=0.83 TO
DRAINAGE STR. 10.40AC @ C=0.87 TO
DRAINAGE STR. 2
X X
X X
X X
X
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X X
X
X
XX
XX
XX
XX
XX XX XX
XX XX XX XX XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
X
X X
X
X X X X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X
X
X
X
XX
X X
X X
X
X
C-161
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
EROS. AND SED.
CONTROL PLAN -
PHASE II
9+50 10+00 11+00 12+00 13+00 13+50
9+50 10+00 11+00 12+00 12+10
TO
P=
.1
STM
TO
P=
.0
STM
R
IM
=1
2.
FCS
STM
ST
A
+3
1.
=D I-3
B, (L
=6
(4 ' I
D
IN
V
O U
T=
.0
(1
5"
ST
A
+0
2.
=F
LO
W C
O N
TR
O
L
ST
R U
C
TU
R E
(S
EE
C -5
IN
V
O U
T=
.6
(1
5"
28.0 LF - 15" RCP (CL III)
@ 1.0%
75.0 LF - 15" RCP (CL III)
@ 1.0%
PROP. GRADE
EX. GRADE
PROP. GRADE
EX. GRADE
STORMCAPTURE SYSTEM
SEE SHEET C-502 FOR
DETAILS
LEVEL SPREADER
WITH PLUNGE
POOL, SEE DETAIL
SHEET C-500
PROP. GRADE
256.5 LF - 15" RCP (CL III)
@ 1.0%
2- 2"
E
LE
C D
U C
TS
TO
P
EL
EV
=1
5.
EX
. 6
" P
VC
S
SW
R F
M C
R O
SS
IN
G
TO
P
EL
EV
=1
4.
EX
. W
AT
ER
C R
O
SS
IN
G
IN
FO
N O
T
PR
O
VI
D
ED
EX
. E
LE
C
TR
IC
AL
D
U C
TS
(2
- 2 .5
EL
EV
=1
2.
EX
. E
LE
C
D U
C T
BA
N
K
TO
P=
.9
0, B
O T=
.2
ST
A
+7
5.
=D I-3
BB
L= 6'
IN
V
IN
=1
6.
(1 5"
IN
V O
U T=
.5
(1 5"
EX
. E
LE
C
TR
IC
AL
C
O N
D U
IT
S
(2
- 5
EL
EV
=1
1.
EX
. E
LE
C
C O
N D
U
IT
B
EN
D (2
- 5
EL
EV
=1
3.
EX
. E
LE
C
TR
IC
AL
D
U C
TS
(2
- 5
EL
EV
=1
4.
75.9 LF - 15" RCP (CL III)
@ 4.3%
ST
A
+7
4.
=V D
O T
ST
'D
M H
-2 D
I, 4'
IN
V
IN
=1
4.
(1
5"
IN
V
O U
T=
.3
(1
5"
R
IM
=1
1.
0A
STM
ST
A
+0
0.
=C O
N N
EC
T
IN
TO
ST
O
R M
C
AP
TU
R
E
SY
ST
EM
IN
VE
R T=
.7 5'
EX
. E
LE
C
D U
C T
BA
N
K
EX
. S
AN
IT
AR
Y
59.7 LF - 15" RCP (CL III)
@ 1.2%
ST
A
+9
8.
=V D
O T
ST
'D
M H
-2 D
I, 4'
IN
V
IN
=1
1.
(1
5"
IN
V
O U
T=
.5
(1
5"
TO
P=
.0
0B
STM
EX
. E
LE
C
TR
IC
AL
D
U C
TB
AN
K
EX
. S
AN
IT
AR
Y
(8 " P
VC
ST
A
+3
8.
=1 5"
E S-
IN
VE
R
T=
.8
0'
15" RCP
MODULAR BLOCK
RETAINING WALL
(MAX HT. ±4')
3:1 SLO
PE
3:1 SLOPE
15" R C
P
STM
STM
STORMWATER MANAGEMENT FACILITY UG-1
(6) STORMCAPTURE MODULES BY
OLDCASTLE INFRASTRUCTURE OR EQUAL
INSIDE DIMENSIONS: 7'W X 15'L X 6'H
TOTAL STORAGE=3,780 CF
INSIDE TOP ELEV=1691.00
SYSTEM INVERT=1685.00
IN=1688.75 (15" STM)
OUT=1685.00 (36" OPENING INTO FLOW CONTROL STR)
FLOW CONTROL STRUCTURE BY
OLDCASTLE INFRASTRUCTURE OR EQUAL
(SEE SHEET C-501 FOR DETAIL)
PARKING LOT
LIGHT (TYP.)
CLIN 2: INSTALL FOUR (4)
ELECTRIC VEHICLE
CHARGING STATIONS
(SEE ELEC. PLAN AND
C-500 FOR PAD DETAILS)
3:1 SLO
PE
1701.29
ELECTRICAL SERVICE
EQUIPMENT ON
CONCRETE PAD
6' PVC DRAIN
1702.91
1702.67 1700.78
OUT
STM
0A
STM
FCS
STM
0B
STM
15" RCP
1702 1703
1703.17
VDOT STD CG-12 TYPE B
(SEE DETAIL ON SHEET
C-501)
15" RCP
167516761678
LEVEL SPREADER
WITH PLUNGE POOL
SEE DETAIL SHT C-500
LIMITS OF DISTURBANCE
C-201
STORM SEWER
PROFILES
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
NOTE:
ELEVATIONS OF EXISTING UTILITIES ARE ASSUMED. TEST
PITS ARE REQUIRED AS NOTED TO VERIFY ACTUAL
ELEVATIONS OF CROSSING UTILITIES.
THE EXISTING LAND COVER JUST
DOWNSTREAM OF THE LEVEL
SPREADER IS A COMBINATION OF
UNDISTURBED HEAVY THICK STANDS
OF GRASS AND FOREST. THE
AVERAGE SLOPE OF THIS AREA IS
APPROXIMATELY 19 %.
C-500
SITE DETAILS
COMPACTED SUBGRADE
6" VDOT 21-B
SUBBASE
1.5" VDOT SM 9.5A
3" VDOT BM 25.0D
WIDTH AS SHOWN ON PLANS
SUBGRADE
xW2.9xW2.9 WWF CONCRETE W/ 6 x 6
BASE COURSE
AGGREGATE 6"
4"
SLOPE: 1/4" : 1' (MAX)
4" - 4000 PSI CONCRETE
(AIR ENTRAINED)
6" - COMPOUNDED
VDOT #57 STONE
xW1.4xW1.4 WWF CONCRETE W/ 6 x 6
BASE COURSE
AGGREGATE 6"
6"
6" HYDRAULIC CEMENT
3"
6'- 0"
M
IN
12'-6" MIN
CONCRETE SLAB
A
A
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
6" WIDE BREAK IN BARRIER CURB TO
ENSURE POSITIVE DRAINAGE (SLAB
FLUSH TO GRASS)
5'-0" WIDE BREAK IN BARRIER CURB TO
CONNECT TO SIDEWALK (SLAB FLUSH TO
WALKWAY)
CONCRETE
BARRIER CURB-
6" WIDTH,
TOP=1708.50',
2" RADIUS EDGES,
CLASS A3 CONCRETE
6' X 10'
4"
#4 @ 12" EACH WAY
4" VDOT STD 21A
AGGREGATE
6"
SUBGRADE
3" CLR (TYP)
4"
ALL EXPOSED EDGES
ALONG TOP OF SLAB SHALL
HAVE A 3/4" CHAMFER
12"
45"
56"
12" MIN
NOTES:
1. CONCRETE TO VDOT STD. A-3.
2. REBAR TO BE #4, TOP AND BOTTOM, 12 IN. O.C.
3. MOUNTING SURFACE TO BE SMOOTH AND CANNOT EXCEED A SLOPE OF 14 IN./FT.
4. CENTER CHARGING STATION IN FRONT OF PARKING STALLS
5. MOUNT CHARGER IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.
CHARGING STATION PAD DETAIL
NOT TO SCALE
CHARGER
.5
CURB
GUTTER
6"
24"
PARKING STALL 9.5'
12" MIN VDOT STD.
21A AGGREGATE
SECTION
PLAN
FFE=1707.85'
GRADE VARIES
" M
IN
BE
LO
W G
RA
DE
PROVIDE CODE COMPLIANT POWER &
COMM CONDUIT STUBS THROUGH SLAB.
CONTRACTOR TO COORDINATE EXACT
QUANTITY AND LOCATIONS BASED ON FIELD
LAYOUT.
PER PLAN
C-501
SITE DETAILS
KEY PLAN
E
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
1'-6"
1"
6"
LC
4" 2"
8" DIA.
38" DIA.
3 16
TRUNCATED DOME
DETAIL
238" C-C
8" C-C
2' -0
DETECTABLE WARNING
DETAIL
VARIABLE
4' MINIMUM.
PAY LIMITS
TRUNCATED DOME
VIRGINIA DEPARTMENT OF TRANSPORTATION
(ACCESS FOR MOBILITY IMPAIRMENTS)
DETECTABLE WARNING SURFACE
NOTES:
2. THE DETECTABLE WARNING SHALL BE PROVIDED BY TRUNCATED DOMES. TRUNCATED DOMES TO BE STAMPED IF CAST-IN-PLACE OR PRECAST IN TOP SURFACE. THE COLOR OF THE DETECTABLE WARNING SECTION SHALL BE A
1. DETECTABLE WARNING TO BE CLASS A-3 CONCRETE (CLASS A-4 IF PRECAST) WITH SLIP RESISTANT INTEGRAL SURFACE COVERING THE FULL WIDTH OF THE RAMP FLOOR BY 2 FOOT IN LENGTH IN THE DIRECTION OF
PEDESTRIAN TRAVEL OTHER TYPES OF MATERIAL WITH THE TRUNCATED DOME DETECTABLE WARNING MAY BE USED
WITH THE APPROVAL OF THE ENGINEER.
CONTRASTING COLOR WITH THE ADJACENT SURFACES (ADJACENT SURFACES INCLUDES FLARED SIDES). OR FEDERAL
SAFETY YELLOW.
NOTE: HANDRAIL TO BE MADE OF ALUMINUM IN LIEU OF STEEL
AS INDICATED IN VDOT STANDARD DETAIL HR-1.
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
C-502
STORM SEWER
DETAILS
NOTES
1. SEE C-501, FOR FLOW CONTROL STRUCTURE DETAIL AND
OUTLET/CONNECTION INVERTS.
2. STORMCAPTURE INVERT = 1685.00'
3. PIPE INVERT IN = 1688.75'
65432
APPROVED BY
CHECKED BY
A
B
C
D
F
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
SCALE
SEAL
REVISIONS
No. DescriptionDATE BY
NORTH
P O
B O
X
, B
E R
R Y
V
IL
LE
, V
IR
G
IN
IA
FE
D E
R A
L E
M E
R G
E N
C Y
M A
N A
G E
M E
N T
A G
E N
C Y
D E
P A
R
TM
E N
T O
F H
O M
E
LA
N D
S E
C U
R
IT
Y
IS
S
U E
D F
O R
C O
N S
TR
U
C
TI
O N
C O
N S
TR
U
C
TI
O N
A N
D P
A R
K
IN
G L
O T
B U
IL
D
IN
G
D E
M O
LI
TO
N
Dewberry Engineers Inc.
8401 ARLINGTON BLVD.
FAIRFAX, VA 22031
703.849.0100 (PHONE)
703.849.0518 (FAX)
KPM
TCC
TCC
3/5/2025
EPS-9620
OF 21
3/5/2025
IFC SUBMISSION3/5/2025
C-503
EROSION &
SEDIMENT
CONTROL
NARRATIVE
1. PERMANENT OR TEMPORARY SOIL STABILIZATION SHALL BE APPLIED TO DENUDED
AREAS WITHIN SEVEN DAYS AFTER FINAL GRADE IS REACHED ON ANY PORTION OF
THE SITE. TEMPORARY SOIL STABILIZATION SHALL BE APPLIED WITHIN SEVEN DAYS
TO DENUDED AREAS THAT MAY NOT BE AT FINAL GRADE BUT WILL REMAIN
DORMANT FOR LONGER THAN 14 DAYS. PERMANENT STABILIZATION SHALL BE
APPLIED TO AREAS THAT ARE TO BE LEFT DORMANT FOR MORE THAN ONE YEAR.
2. DURING CONSTRUCTION OF THE PROJECT, SOIL STOCKPILES AND BORROW AREAS
SHALL BE STABILIZED OR PROTECTED WITH SEDIMENT TRAPPING MEASURES. THE
APPLICANT IS RESPONSIBLE FOR THE TEMPORARY PROTECTION AND PERMANENT
STABILIZATION OF ALL SOIL STOCKPILES ON SITE AS WELL AS BORROW AREAS AND
SOIL INTENTIONALLY TRANSPORTED FROM THE PROJECT SITE.
3. A PERMANENT VEGETATIVE COVER SHALL BE ESTABLISHED ON DENUDED AREAS
NOT OTHERWISE PERMANENTLY STABILIZED. PERMANENT VEGETATION SHALL NOT
BE CONSIDERED ESTABLISHED UNTIL A GROUND COVER IS ACHIEVED THAT, IS
UNIFORM, MATURE ENOUGH TO SURVIVE AND WILL INHIBIT EROSION.
4. SEDIMENT BASINS AND TRAPS, PERIMETER DIKES, SEDIMENT BARRIERS AND OTHER
MEASURES INTENDED TO TRAP SEDIMENT SHALL BE CONSTRUCTED AS A FIRST
STEP IN ANY LAND-DISTURBING ACTIVITY AND SHALL BE MADE FUNCTIONAL BEFORE
UPSLOPE LAND DISTURBANCE TAKES PLACE.
5. STABILIZATION MEASURES SHALL BE APPLIED TO EARTHEN STRUCTURES SUCH AS
DAMS, DIKES AND DIVERSIONS IMMEDIATELY AFTER INSTALLATION.
6. SEDIMENT TRAPS AND SEDIMENT BASINS SHALL BE DESIGNED AND CONSTRUCTED
BASED UPON THE TOTAL DRAINAGE AREA TO BE SERVED BY THE TRAP OR BASIN.
A. THE MINIMUM STORAGE CAPACITY OF A SEDIMENT TRAP SHALL BE 134 CUBIC
YARDS PER ACRE OF DRAINAGE AREA AND THE TRAP SHALL ONLY CONTROL
DRAINAGE AREAS LESS THAN THREE ACRES.
B. SURFACE RUNOFF FROM DISTURBED AREAS THAT IS COMPRISED OF FLOW
FROM DRAINAGE AREAS GREATER THAN OR EQUAL TO THREE ACRES SHALL BE
CONTROLLED BY A SEDIMENT BASIN. THE MINIMUM STORAGE CAPACITY OF A
SEDIMENT BASIN SHALL BE 134 CUBIC YARDS PER ACRE OF DRAINAGE AREA.
THE OUTFALL SYSTEM SHALL, AT A MINIMUM, MAINTAIN THE STRUCTURAL
INTEGRITY OF THE BASIN DURING A TWENTY-FIVE YEAR STORM OF 24-HOUR
DURATION. RUNOFF COEFFICIENTS USED IN RUNOFF CALCULATIONS SHALL
CORRESPOND TO A BARE EARTH CONDITION OR THOSE CONDITIONS EXPECTED
TO EXIST WHILE THE SEDIMENT BASIN IS UTILIZED.
7. CUT AND FILL SLOPES SHALL BE DESIGNED AND CONSTRUCTED IN A MANNER THAT
WILL MINIMIZE EROSION. SLOPES THAT ARE FOUND TO BE ERODING EXCESSIVELY
WITHIN ONE YEAR OF PERMANENT STABILIZATION SHALL BE PROVIDED WITH
ADDITIONAL SLOPE STABILIZING MEASURES UNTIL THE PROBLEM IS CORRECTED.
8. CONCENTRATED RUNOFF SHALL NOT FLOW DOWN CUT OR FILL SLOPES UNLESS
CONTAINED WITHIN AN ADEQUATE TEMPORARY OR PERMANENT CHANNEL, FLUME
OR SLOPE DRAIN STRUCTURE.
9. WHENEVER WATER SEEPS FROM A SLOPE FACE, ADEQUATE DRAINAGE OR OTHER
PROTECTION SHALL BE PROVIDED.
10. ALL STORM SEWER INLETS THAT ARE MADE OPERABLE DURING CONSTRUCTION
SHALL BE PROTECTED SO THAT SEDIMENT-LADEN WATER CANNOT ENTER THE
CONVEYANCE SYSTEM WITHOUT FIRST BEING FILTERED OR OTHERWISE TREATED
TO REMOVE SEDIMENT.
11. BEFORE NEWLY CONSTRUCTED STORMWATER CONVEYANCE CHANNELS OR PIPES
ARE MADE OPERATIONAL, ADEQUATE OUTLET PROTECTION AND ANY REQUIRED
TEMPORARY OR PERMANENT CHANNEL LINING SHALL BE INSTALLED IN BOTH THE
CONVEYANCE CHANNEL AND RECEIVING CHANNEL.
12. WHEN WORK IN A LIVE WATERCOURSE IS PERFORMED, PRECAUTIONS SHALL BE
TAKEN TO MINIMIZE ENCROACHMENT, CONTROL SEDIMENT TRANSPORT AND
STABILIZE THE WORK AREA TO THE GREATEST EXTENT POSSIBLE DURING
CONSTRUCTION. NONERODIBLE MATERIAL SHALL BE USED FOR THE CONSTRUCTION
OF CAUSEWAYS AND COFFERDAMS. EARTHEN FILL MAY BE USED FOR THESE
STRUCTURES IF ARMORED BY NONERODIBLE COVER MATERIALS.
13. WHEN A LIVE WATERCOURSE MUST BE CROSSED BY CONSTRUCTION VEHICLES
MORE THAN TWICE IN ANY SIX-MONTH PERIOD, A TEMPORARY VEHICULAR STREAM
CROSSING CONSTRUCTED OF NONERODIBLE MATERIAL SHALL BE PROVIDED.
14. ALL APPLICABLE FEDERAL, STATE AND LOCAL REGULATIONS PERTAINING TO
WORKING IN OR CROSSING LIVE WATERCOURSES SHALL BE MET.
15. THE BED AND BANKS OF A WATERCOURSE SHALL BE STABILIZED IMMEDIATELY
AFTER WORK IN THE WATERCOURSE IS COMPLETED.
16. UNDERGROUND UTILITY LINES SHALL BE INSTALLED IN ACCORDANCE WITH THE
FOLLOWING STANDARDS IN ADDITION TO OTHER APPLICABLE CRITERIA:
A. NO MORE THAN 500 LINEAR FEET OF TRENCH MAY BE OPENED AT ONE TIME.
B. EXCAVATED MATERIAL SHALL BE PLACED ON THE UPHILL SIDE OF TRENCHES.
C. EFFLUENT FROM DEWATERING OPERATIONS SHALL BE FILTERED OR PASSED
THROUGH AN APPROVED SEDIMENT TRAPPING DEVICE, OR BOTH, AND
DISCHARGED IN A MANNER THAT DOES NOT ADVERSELY AFFECT FLOWING
STREAMS OR OFF-SITE PROPERTY.
D. MATERIAL USED FOR BACKFILLING TRENCHES SHALL BE PROPERLY
COMPACTED IN ORDER TO MINIMIZE EROSION AND PROMOTE STABILIZATION.
E. RESTABILIZATION SHALL BE ACCOMPLISHED IN ACCORDANCE WITH THIS
CHAPTER.
F. APPLICABLE SAFETY REQUIREMENTS SHALL BE COMPLIED WITH.
17. WHEN CONSTRUCTION VEHICLE ACCESS ROUTES INTERSECT PAVED OR PUBLIC
ROADS, PROVISIONS SHALL BE MADE TO MINIMIZE THE TRANSPORT OF SEDIMENT
BY VEHICULAR TRACKING ONTO THE PAVED SURFACE. WHERE SEDIMENT IS
TRANSPORTED ONTO A PAVED OR PUBLIC ROAD SURFACE, THE ROAD SURFACE
SHALL BE CLEANED THOROUGHLY AT THE END OF EACH DAY. SEDIMENT SHALL BE
REMOVED FROM THE ROADS BY SHOVELING OR SWEEPING AND TRANSPORTED TO
A SEDIMENT CONTROL DISPOSAL AREA. STREET WASHING SHALL BE ALLOWED ONLY
AFTER SEDIMENT IS REMOVED IN THIS MANNER. THIS PROVISION SHALL APPLY TO
INDIVIDUAL DEVELOPMENT LOTS AS WELL AS TO LARGER LAND-DISTURBING
ACTIVITIES.
18. ALL TEMPORARY EROSION AND SEDIMENT CONTROL MEASURES SHALL BE
REMOVED WITHIN 30 DAYS AFTER FINAL SITE STABILIZATION OR AFTER THE
TEMPORARY MEASURES ARE NO LONGER NEEDED, UNLESS OTHERWISE
AUTHORIZED BY THE VESCP OR VESMP AUTHORITY. TRAPPED SEDIMENT AND THE
DISTURBED SOIL AREAS RESULTING FROM THE DISPOSITION OF TEMPORARY
MEASURES SHALL BE PERMANENTLY STABILIZED TO PREVENT FURTHER EROSION
AND SEDIMENTATION.
19. PROPERTIES AND WATERWAYS DOWNSTREAM FROM DEVELOPMENT SITES SHALL
BE PROTECTED FROM SEDIMENT DEPOSITION, EROSION AND DAMAGE DUE TO
INCREASES IN VOLUME, VELOCITY AND PEAK FLOW RATE OF STORMWATER RUNOFF
FOR THE STATED FREQUENCY STORM OF 24-HOUR DURATION IN ACCORDANCE WITH
THE FOLLOWING STANDARDS AND CRITERIA. STREAM RESTORATION AND
RELOCATION PROJECTS THAT INCORPORATE NATURAL CHANNEL DESIGN
CONCEPTS ARE NOT MANMADE CHANNELS AND SHALL BE EXEMPT FROM THE FLOW
RATE CAPACITY AND VELOCITY REQUIREMENTS FOR NATURAL OR MANMADE
CHANNELS:
A. CONCENTRATED STORMWATER RUNOFF LEAVING A DEVELOPMENT SITE SHALL
BE DISCHARGED DIRECTLY INTO AN ADEQUATE NATURAL OR MAN-MADE
RECEIVING CHANNEL, PIPE OR STORM SEWER SYSTEM. FOR THOSE SITES
WHERE RUNOFF IS DISCHARGED INTO A PIPE OR PIPE SYSTEM, DOWNSTREAM
STABILITY ANALYSES AT THE OUTFALL OF THE PIPE OR PIPE SYSTEM SHALL BE
PERFORMED.
B. ADEQUACY OF ALL CHANNELS AND PIPES SHALL BE VERIFIED IN THE
FOLLOWING MANNER:
1. THE APPLICANT SHALL DEMONSTRATE THAT THE TOTAL DRAINAGE AREA TO
THE POINT OF ANALYSIS WITHIN THE CHANNEL IS ONE HUNDRED TIMES
GREATER THAN THE CONTRIBUTING DRAINAGE AREA OF THE PROJECT IN
QUESTION; OR
2.
A. NATURAL CHANNELS SHALL BE ANALYZED BY THE USE OF A TWO-YEAR
STORM TO VERIFY THAT STORMWATER WILL NOT OVERTOP CHANNEL
BANKS NOR CAUSE EROSION OF CHANNEL BED OR BANKS;
B. ALL PREVIOUSLY CONSTRUCTED MAN-MADE CHANNELS SHALL BE
ANALYZED BY THE USE OF A TEN-YEAR STORM TO VERIFY THAT
STORMWATER WILL NOT OVERTOP STORMWATER'S BANKS AND BY THE
USE OF A TWO-YEAR STORM TO DEMONSTRATE THAT STORMWATER
WILL NOT CAUSE EROSION OF CHANNEL BED OR BANKS; AND
C. PIPES AND STORM SEWER SYSTEMS SHALL BE ANALYZED BY THE USE
OF A TEN-YEAR STORM TO VERIFY THAT STORMWATER WILL BE
CONTAINED WITHIN THE PIPE OR SYSTEM.
C. IF EXISTING NATURAL RECEIVING CHANNELS OR PREVIOUSLY CONSTRUCTED
MAN-MADE CHANNELS OR PIPES ARE NOT ADEQUATE, THE APPLICANT SHALL:
1. IMPROVE THE CHANNEL TO A CONDITION WHERE A TEN-YEAR STORM WILL
NOT OVERTOP THE BANKS AND A TWO-YEAR STORM WILL NOT CAUSE
EROSION TO THE CHANNEL, THE BED, OR THE BANKS;
2. IMPROVE THE PIPE OR PIPE SYSTEM TO A CONDITION WHERE THE
TEN-YEAR STORM IS CONTAINED WITHIN THE APPURTENANCES; OR
3. DEVELOP A SITE DESIGN THAT WILL NOT CAUSE THE PRE-DEVELOPMENT
PEAK RUNOFF RATE FROM A TWO-YEAR STORM TO INCREASE WHEN
RUNOFF OUTFALLS INTO A NATURAL CHANNEL OR WILL NOT CAUSE THE
PRE-DEVELOPMENT PEAK RUNOFF RATE FROM A TEN-YEAR STORM TO
INCREASE WHEN RUNOFF OUTFALLS INTO A MAN-MADE CHANNEL; OR
4. PROVIDE A COMBINATION OF CHANNEL IMPROVEMENT, STORMWATER
DETENTION OR OTHER MEASURES WHICH IS SATISFACTORY TO THE VESCP
OR VESMP AUTHORITY TO PREVENT DOWNSTREAM EROSION.
D. THE APPLICANT SHALL PROVIDE EVIDENCE OF PERMISSION TO MAKE THE
IMPROVEMENTS.
E. ALL HYDROLOGIC ANALYSES SHALL BE BASED ON THE EXISTING WATERSHED
CHARACTERISTICS AND THE ULTIMATE DEVELOPMENT OF THE SUBJECT
PROJECT.
F. IF THE APPLICANT CHOOSES AN OPTION THAT INCLUDES STORMWATER
DETENTION HE SHALL OBTAIN APPROVAL FROM THE VESCP OR VESMP
AUTHORITY FOR MAINTENANCE OF THE DETENTION FACILITIES. THE PLAN SHALL
SET FORTH THE MAINTENANCE REQUIREMENTS OF THE FACILITY AND THE
PERSON RESPONSIBLE FOR PERFORMING THE MAINTENANCE.
G. OUTFALL FROM A DETENTION FACILITY SHALL BE DISCHARGED TO A RECEIVING
CHANNEL, AND ENERGY DISSIPATORS SHALL BE PLACED AT THE OUTFALL OF
ALL DETENTION FACILITIES AS NECESSARY TO PROVIDE A STABILIZED
TRANSITION FROM THE FACILITY TO THE RECEIVING CHANNEL.
H. ALL ON-SITE CHANNELS MUST BE VERIFIED TO BE ADEQUATE.
I. INCREASED VOLUMES OF SHEET FLOWS THAT MAY CAUSE EROSION OR
SEDIMENTATION ON ADJACENT PROPERTY SHALL BE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .