570-17-210.OPC.IFC.DWG.20210618Part-8of10.pdf

PDF 2 MB Posted

Attached to
Z2DA--REMODEL EMERGENCY DEPARTMENT FOR OBSERVATION BEDS | 570-17-210
Solicitation number
36C26121R0066
Issued by

View the file

Other files

File Type Posted
36C26121R0066 0005.docx DOCX document
36C26121R0066 0004.docx DOCX document
Site Visit Sign-in Sheet--12.1.2021.pdf PDF
Site Visit Sign-in Sheet--11.10.2021.pdf PDF
36C26121R0066--Responses to Pre-Proposal RFIs (1-17)--Complete--12.6.2021.pdf PDF
Specification 11 73 00-rev01-12.03.2021.pdf PDF
36C26121R0066 0003.docx DOCX document
36C26121R0066--Responses to Pre-Proposal RFIs (1-17).pdf PDF
36C26121R0066 0002.docx DOCX document
36C26121R0066--Responses to Pre-Proposal RFIs (1-10).pdf PDF
ACM Report.pdf PDF
36C26121R0066 0001.docx DOCX document
570-17-210.OPC.IFC.DWG.20210618Part-7of10.pdf PDF
570-17-210.OPC.IFC.DWG.20210618Part-1of10.pdf PDF
570-17-210.OPC.IFC.DWG.20210618Part-10of10.pdf PDF
570-17-210.OPC.IFC.DWG.20210618Part-3of10.pdf PDF
570-17-210.OPC.IFC.DWG.20210618Part-6of10.pdf PDF
570-17-210.OPC.IFC.DWG.20210618Part-2of10.pdf PDF
570-17-210.OPC.IFC.DWG.20210618Part-5of10.pdf PDF
570-17-210.OPC.IFC.DWG.20210618Part-4of10.pdf PDF
570-17-210.OPC.IFC.DWG.20210618Part-9of10.pdf PDF
Factor 6 - Divisional Construction Costs.pdf PDF
REQUEST FOR INFORMATION (RFI) FORM--36C26121R0066.docx DOCX document
Factor 4 - Past Performance (Questionnaire).docx DOCX document
570-17-210.OPC.IFC.Specification.R2.20210618Part-4.pdf PDF
570-17-210.OPC.IFC.Specification.R2.20210618Part-2.pdf PDF
Factor 2 - Key Personnel Qualifications Resumes.xlsx XLSX spreadsheet
570-17-210.OPC.IFC.Specification.R2.20210618Part-3.pdf PDF
VHA_DIRECTIVE_1193_D_2021_08_13--Vaccination_Program.pdf PDF
General Decision Number CA20210018 10.08.2021.pdf PDF
Responsibility - Contractor Certification Regarding Safety and Environmental.pdf PDF
Site_Visit_MAP.pdf PDF
Factor 1 - Prime Contractor Project Experience.xlsx XLSX spreadsheet
570-17-210.OPC.IFC.Specification.R2.20210618Part-1.pdf PDF
36C26121R0066_2.docx DOCX document
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BOPC.3BOPC.2

BOPC.1

BOPC.A

BOPC.A.1

BOPC.B

BOPC.B.1

BOPC.C

BOPC.D

F /M

H B

VAV-1-6

VAV-1-2

CAV-1-7

CAV-1-2

CAV-1-5

CAV-1-4

EG

550 CFM

EG

550 CFM

EG

550 CFM

EG

460 CFM

EG

510 CFM

EG

80 CFM

SD

230 CFM

SD

230 CFM

SD

620 CFM

SD

600 CFM

SD

190 CFM

SD

280 CFM

SD

190 CFM

SD

200 CFM

SD

500 CFM

SD

530 CFM

SD

540 CFM

SD

180 CFM

SD

60 CFM

SD

160 CFM

SD

500 CFM

SD

175 CFM

RG

180 CFM

RG

470 CFM

RG

200 CFM

RG

620 CFM

SD

100 CFM

SD

260 CFM

SD

100 CFM

SD

330 CFM

RG

620 CFM

VAV-1-2

VAV-1-6

CAV-1-9

CAV-1-8

CAV-1-7

CAV-1-6

CAV-1-2

CAV-1-1

VAV-1-1 VAV-1-20

VAV-1-14

CAV-1-5

VAV-1-1

(E)8"ø SA

(E)8"ø SA

(E)16"ø SA(E)8"ø SA

(E)8"ø SA

(E)8"ø SA

(E )8

"ø S

A

(E)8"ø SA

(E )1

"ø

S A

(E)12"ø RA

(E)8"ø RA

(E)14"ø RA

(E)14"ø RA

(E )1

"ø

R A

(E)14"x10" RA

(E )1

"x

R A

(E )8

"ø R

A

(E )1

"x

E X

H

(E)14"x8" EXH

(E)14"x8" EXH

(E)14"x8" EXH

(E)12"ø EXH

(E)16"x12" EXH (E)14"x8" EXH

(E)14"x8" EXH

(E)6"ø EXH (E)6"ø EXH

(E)12"ø SA

(E)8"ø SA

(E)10"ø SA

(E)12"ø SA

(E)10"ø SA

(E)10"ø SA (E)8"ø SA

(E)10"ø SA(E )8

"ø S

A

(E)14"x8" RA

(E)14"x8" RA

(E)8"ø SA

(E)8"ø SA

(E)14"ø SA (E)12"ø SA

(E)12"ø SA

(E)12"ø SA

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

(E )1

"x

E X

H

12"ø SA

"ø

S A

12"ø SA

8"ø SA

8"x10" SA

8"ø SA

10"ø SA

(E)12"ø RA (E)12"ø RA

(E )4

"x

R A

(E)14"ø RA

(E )2

"x

R A

(E)8"ø SA

(E)18"x12" EXH

TRAUMA RM LARGE

B1C07

EXAM AREA

B1C04

ENTRANCE

ELEVATOR

B-19

ALCOVE,

WHEELCHAIR/

STRETCHER/ LIFT

B1D

SOCIAL WORK

OFFICE

B1C01

EXAM AREA

B1C03

VESTIBULE

VESTIBULE

LINEN CART ALCOVE

POLICE DISPATCH

B1C02

PROCEDURE RM

B1C05

CHARTING ALCOVE

WHEELCH. SCALE

---CORRIDOR

B1C-1A

TRAUMA RM SMALL

B1C06

TOILET

B1C08

CORRIDOR

B1C-8

CORRIDOR

B1C-5

NURSE STATION

B1C29A

CLINICAL CHARTING

RM

B1C29

CORRIDOR

B1C-7

AOD/ CHECK-IN

B1C30

INTERVENTION

(SECLUSION) ROOM

B1C28

WAITING

B1C-1

AC

10"ø SA 10"ø SA

8"ø SA

F4/MH100D

(E )1

"x

R A

8"ø SA

CAV-1-6

TRIAGE RM

B1C31

12"ø EXH

12"ø SA

12"ø SA

C A

V -1

-8

C A

V -1

-9

FPH-31

FPH-32

SD

160 CFM

8"ø SA

8"ø SA

8"ø SA

8"ø SA

10"x10" SA

RG

460 CFM

RG

75 CFM

RG

190 CFM

RG

100 CFM

8"ø RA

6"ø RA

6"ø RA

RG

190 CFM

C A

V -1

-1

(E)6"ø SA

(E)6"ø SA

(E)8"ø SA

(E)8"ø SA (E)12"ø SA 12"ø SA

8"ø SA

(E)8"ø SA

(E )8

"ø S

A (E

)1 "ø

S A

(E )3

"x

S A

(E )2

"x

S A

(E )2

"x

S A

(E )8

"ø S

A C

A V

-1 -3

12"ø SA

(E)8"ø SA

(E)8"ø SA 8"ø SA

6"ø RA

SD

160 CFM

32"x12" RA 26"x12" RA

(E)6"ø RA

10"ø SA

8"ø SA 6"ø SA

6"ø SA

SMOKE COMPARTMENT 1

SMOKE COMPARTMENT 2

TYP

TYP

TYP

TYP

WAITING

B1C-1

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

A

B

IM

/5

-1 -2

E x p a n d E

D B e d s

/5

-1

-2

.O P

C .M

E .r v t

/1

/2

:4

:5

A

M

MH100A

MECHANICAL DUCT PLAN - LEVEL

B - AREA A

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

06/18/2021 M. PERKINS G. WEAVER

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

A. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-CONSTRUCTION TAB

REPORT FOR THE EQUIPMENT AND ASSOCIATED SYSTEMS SHOWN ON THE

CONSTRUCTION DOCUMENTS AND UTILIZE ALL AVAILABLE AS-BUILT DRAWINGS

FROM THE OWNER. TEST AND BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO

CONSTRUCTION AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP

THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING EQUIPMENT

LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND TAG NUMBERS. IF THERE

ARE LOCATIONS WHERE THE DRAWINGS DO NOT REFLECT FIELD CONDITIONS, THE

TEST AND BALANCE CONTRACTOR SHALL INCLUDE THE AIRFLOW AND WATERFLOW

READINGS ON THE FORMS AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON

THE DRAWINGS. REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE

INFORMATION.

B. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED TO

ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA FOR THE

RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT ENGINEER FOR

REVIEW AND COMMENT PRIOR TO COMMENCING THE DEMOLITION AND/OR NEW

WORK ASSOCIATED WITH THE FACILITY RENOVATION.

C. PROVIDE AIR BALANCE REPORT PRIOR TO FINAL INSPECTION

D. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY

REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO VIOLATIONS

OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A CERTIFIED ROOFING

INSPECTOR MEETING THE REQUIREMENTS OF THE INSTALLED ROOF. ALL

WARRANTY VIOLATIONS WILL BE REQUIRED TO BE CORRECTED PRIOR TO CLOSE

OUT. ROOFS AND/OR ROOFING IMPACTED BY WORK INCLUDE B126.

E. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL PIPING

PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED

AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF

CAULKING MATERIAL.

F. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND CONDUIT PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL PROVIDE

NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN REQUIRED

EQUIPMENT ACCESS AND SERVICEABILITY.

G. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION OF

THOSE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR

TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY

FROM CONSTRUCTION DOCUMENTS.

H. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH ALL TRADES

PRIOR TO INSTALLATION.

I. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT CONNECTIONS

BETWEEN ALL DISSIMILAR METALS.

J. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

K. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED EXTERIOR PIPE

PENETRATIONS AND SEAL COMPLETELY.

L. CONTRACTOR TO PROVIDE TEMPORARY FLOORING WHILE MODIFYING

SUBFLOORING.

M. SEE M-501 FOR LOW PRESSURE DUCT FITTING DETAILS.

N. SEE M-501 FOR DIFFUSER AND REGISTER CONNECTION DETAILS.

O. REPLACE ALL EXISTING DUCT WRAP IN AREA OF WORK.

P. SEE M-700 SERIES FOR MECHANICAL EQUIPMENT SCHEDULES AND M-802 AND M-803

FOR CONTROL SEQUENCE.

Q. PROVIDE PRECONSTRUCTION TAB READINGS OF THE EXISTING SUPPLY AIR AND

RETURN AIR SERVING THE ROOMS IN THE AREA OF WORK. REBALANCE EXISTING

SUPPLY AND RETURN AIR SYSTEMS AFTER DEMOLITION IS COMPLETE.

R. TECHNICAL COORDINATION DRAWINGS OF COMPLETE ASSEMBLIES, REFLECTING

ACCURATE PROJECT CONDITIONS, SHALL BE SUBMITTED WITH EQUIPMENT

SELECTIONS TO ENSURE SPACE ALLOWANCES ARE REFLECTED IN THE ACTUAL

SPACE AVAILABLE. WHERE SIZE DEVIATIONS DIFFER FROM THE BASIS OF DESIGN,

CONTRACTOR SHALL HIGHLIGHT THE DIFFERENCES FOR AE/COR REVIEW WITHIN

THE SUBMITTAL. CONTRACTOR SHALL PROVIDE INSTALLATION ROUTE AND

VERIFICATION THAT ACCESS POINTS, PLACEMENT ROUTE, SUPPORTS, AND

REQUIRED EQUIPMENT CLEARANCES ARE IDENTIFIED ON THE ROUTE DRAWING.

1/4" = 1'-0" F1

MECHANICAL DUCT PLAN - BASEMENT - AREA A

KEYNOTES

1 PROVIDE NEW DDC TERMINAL UNIT, CONNECT TO EXISTING BUILDING AUTOMATION SYSTEM.

PROVIDE NEW THERMOSTAT TO MATCH EXISTING BUILDING STANDARDS, COORDINATE FINAL

LOCATION WITH COR. REFER TO SHEET M-501 FOR DETAILS AND M-803 FOR CONTROLS.

2 CONNECT EXISTING DUCTWORK TO NEW TERMINAL UNIT. PROVIDE TRANSITIONS AS NECESSARY TO

MAKE CONNECTION AND SEAL AIRTIGHT.

3 NEW 12” ROUND EXHAUST DUCT UP TO NEW EXHAUST FAN EF-1, ROUT AND BRACE ALONG EXTERIOR

WALL. RESEAL PENETRATION AS REQUIRED.

4 SMOKE COMPARTMENT BOUNDARY LINE, SEE SHEET G-101 FOR ADDITIONAL INFORMATION.

Revisions: Date:

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH

FIRE AND SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH

HATCH PATTERNS.

06/18/2021

BOPC.6BOPC.5.ABOPC.5BOPC.4

BOPC.A

BOPC.A.1

BOPC.B

BOPC.B.1

BOPC.C

BOPC.D

BOPC.E

F1/MH100A

VAV-1-12

VAV-1-17

VAV-1-18

VAV-1-6

SD

330 CFM

SD

160 CFM

SD

130 CFM

RG

130 CFM

RG

110 CFM

SD

110 CFM

SD

950 CFM

EG

950 CFM

EG

550 CFM

SD

230 CFM

SD

190 CFM

RG

620 CFM

RG

100 CFM

EG

95 CFM

SD

135 CFM

SD

150 CFM

SD

250 CFM

SD

150 CFM

EG

80 CFM

RG

150 CFM

SD

200 CFM

SD

80 CFM

SD

80 CFM

RG

150 CFM

SD

340 CFM

VAV-1-18

VAV-1-16

VAV-1-17

VAV-1-12

VAV-1-13

VAV-1-14

VAV-1-15

VAV-1-8

VAV-1-11

VAV-1-10

1 2 1 2

1 2

1 2

F D

EG

200 CFM

EG

210 CFM

CORRIDOR

B1C-1

WAITING

B1C-1

FEMALE RR

B1C32

MALE RR

B1C33

PAT TLT

B1C34J

NEW OBSERVATION

ROOM

B1C34G

PATIENT COMFORT

ROOM

BC127

CORRIDOR

B1C-9

NEW OBSERVATION

ROOM

B1C23

NEW OBSERVATION

ROOM

BC24

NEW OBSERVATION

ROOM

B1C21

HAC

BC50

CORRIDOR

B1C-6

PAT SHWR

B1C25B

CLEAN UTILITY

BC26

PAT TLT

B1C25A

HALL

B1C-6A

NEW NURSES

STATION

B1C34B

NEW NURSES

STATION

B1C34F

NEW OBSERVATION

ROOM

B1C34K

CORRIDOR

B1C-2

LINEN CLOSET

B1C41

ELEVATOR EQUIP RM

B1C40

ELEVATOR

S-5

ELEVATOR

S-6

HEAD NURSE

B1C37

CHIEF OF ER

B1C35

OBSERVATION/

TREATMENT RM

B1C14

CORRIDOR

B1C-4

SOILED UTILITY

B1C53

CLEAN UTILITY

B1C52

STF TLT

BC51

CORRIDOR

B1C-2

STAIR NO.4

B1C43

LINEN CLOSET

B1C42

NEW OBSERVATION

ROOM

B1C34A

NEW OBSERVATION

ROOM

B1C34C

NEW OBSERVATION

ROOM

B1C34E

NEW STORAGE

B1C34H

NEW STORAGE

B1C34D

EG

180 CFM

SD

150 CFM

SD

150 CFM

SD

250 CFM

SD

250 CFM

EG

80 CFM

VAV-1-9

F4/MH100D

F4/MH100Cx

(E)50"x12" SA

(E)54"x14" SA

(E)24"x12" SA

14"x12" SA

8"ø SA

(E)10"ø SA

(E)10"ø EXH

8"ø SA

(E)8"ø SA

12"x10" SA 8"ø SA

(E)6"ø SA

6"ø SA

(E)16"x12" SA

8"ø SA

8"ø RA

6"ø SA

(E)30"x12" SA

(E)24"x12" SA

(E)12"ø EXH(E)10"ø EXH

VAV-1-9(E)8"ø EXH

(E)8"ø EXH

"ø

E X

H

8"ø SA

8"ø SA

VAV-1-8

VAV-1-13

VAV-1-14

VAV-1-11

VAV-1-15

V A

V -1

-1

V A

V -1

-1

"ø

R A

8"ø EXH

EG

120 CFM

FSDFSDFSD

F S

D

8"ø RA 10"x12" SA

"ø

S A

8"ø SA

"x

S A

"x

S A

"x

S A

8"ø SA

8"ø SA 10"x10" SA

10"x10" SA

SD

175 CFM

"ø

S A

"ø

S A

8"ø SA

"ø

S A

8"ø SA

10"x10" SA

8"ø SA

8"ø SA

"x

R A

"ø

R A 8"ø RA

RG

485 CFM

SD

175 CFM

6"ø SA

8"ø SA

F S

D8 "ø

E X

H

8"ø SA

"ø

S A

RG

150 CFM RG

150 CFM

6"ø SA

10"ø SA

"ø

S A

8"ø SA

8"ø EXH

CD-19

135 CFM

1 2

1 2

RG

485 CFM

"ø

S A

"ø

E X

H

"ø

S A

"ø

E X

H

"ø

S A

(E)12"x8" SA

(E )2

"x

S A

(E)54"x14" SA

(E )1

"ø

R A

RG

240 CFM

(E )1

"x

S A

(E )1

"ø

S A

(E )1

"x

R A

(E )1

"ø

R A

(E)12"ø RA

(E)37"x12" SA(E)14"ø SA

FD

"ø

R A

8"ø RA

10"x10" SA

VAV-1-7

FD

RG

190 CFM

6"ø RA

CORRIDOR

B1C48

SD

160 CFM

(E)20"x12" SA

SD

150 CFM

26"x12" RA 22"x12" RA

"x

R A

RG

285 CFM

10"ø RA

10"ø RA

10"ø RA

RG

485 CFM

(E)6"ø RA

(E)6"ø RA

(E)8"ø RA(E)10"ø RA

(E)8"ø RA

"ø

S A

10"ø SA

FSD

FSD

FD

SMOKE COMPARTMENT 1

SMOKE COMPARTMENT 2

S M

O K

E C

O M

P A

R T

M E

N T

S M

O K

E C

O M

P A

R T

M E

N T

TYP

WAITING

B1C-1

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

B

B

IM

/5

-1 -2

E x p a n d E

D B e d s

/5

-1

-2

.O P

C .M

E .r v t

/1

/2

:4

:5

A

M

MH100B

MECHANICAL DUCT PLAN - LEVEL

B - AREA B

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

06/18/2021 M. PERKINS G. WEAVER

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

A. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-CONSTRUCTION TAB

REPORT FOR THE EQUIPMENT AND ASSOCIATED SYSTEMS SHOWN ON THE

CONSTRUCTION DOCUMENTS AND UTILIZE ALL AVAILABLE AS-BUILT DRAWINGS

FROM THE OWNER. TEST AND BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO

CONSTRUCTION AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP

THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING EQUIPMENT

LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND TAG NUMBERS. IF THERE

ARE LOCATIONS WHERE THE DRAWINGS DO NOT REFLECT FIELD CONDITIONS, THE

TEST AND BALANCE CONTRACTOR SHALL INCLUDE THE AIRFLOW AND WATERFLOW

READINGS ON THE FORMS AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON

THE DRAWINGS. REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE

INFORMATION.

B. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED TO

ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA FOR THE

RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT ENGINEER FOR

REVIEW AND COMMENT PRIOR TO COMMENCING THE DEMOLITION AND/OR NEW

WORK ASSOCIATED WITH THE FACILITY RENOVATION.

C. PROVIDE AIR BALANCE REPORT PRIOR TO FINAL INSPECTION

D. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY

REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO VIOLATIONS

OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A CERTIFIED ROOFING

INSPECTOR MEETING THE REQUIREMENTS OF THE INSTALLED ROOF. ALL

WARRANTY VIOLATIONS WILL BE REQUIRED TO BE CORRECTED PRIOR TO CLOSE

OUT. ROOFS AND/OR ROOFING IMPACTED BY WORK INCLUDE B126.

E. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL PIPING

PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED

AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF

CAULKING MATERIAL.

F. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND CONDUIT PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL PROVIDE

NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN REQUIRED

EQUIPMENT ACCESS AND SERVICEABILITY.

G. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION OF

THOSE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR

TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY

FROM CONSTRUCTION DOCUMENTS.

H. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH ALL TRADES

PRIOR TO INSTALLATION.

I. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT CONNECTIONS

BETWEEN ALL DISSIMILAR METALS.

J. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

K. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED EXTERIOR PIPE

PENETRATIONS AND SEAL COMPLETELY.

L. CONTRACTOR TO PROVIDE TEMPORARY FLOORING WHILE MODIFYING

SUBFLOORING.

M. SEE M-501 FOR LOW PRESSURE DUCT FITTING DETAILS.

N. SEE M-501 FOR DIFFUSER AND REGISTER CONNECTION DETAILS.

O. REPLACE ALL EXISTING DUCT WRAP IN AREA OF WORK.

P. SEE M-700 SERIES FOR MECHANICAL EQUIPMENT SCHEDULES AND M-802 AND M-803

FOR CONTROL SEQUENCE.

Q. PROVIDE PRECONSTRUCTION TAB READINGS OF THE EXISTING SUPPLY AIR AND

RETURN AIR SERVING THE ROOMS IN THE AREA OF WORK. REBALANCE EXISTING

SUPPLY AND RETURN AIR SYSTEMS AFTER DEMOLITION IS COMPLETE.

R. TECHNICAL COORDINATION DRAWINGS OF COMPLETE ASSEMBLIES, REFLECTING

ACCURATE PROJECT CONDITIONS, SHALL BE SUBMITTED WITH EQUIPMENT

SELECTIONS TO ENSURE SPACE ALLOWANCES ARE REFLECTED IN THE ACTUAL

SPACE AVAILABLE. WHERE SIZE DEVIATIONS DIFFER FROM THE BASIS OF DESIGN,

CONTRACTOR SHALL HIGHLIGHT THE DIFFERENCES FOR AE/COR REVIEW WITHIN

THE SUBMITTAL. CONTRACTOR SHALL PROVIDE INSTALLATION ROUTE AND

VERIFICATION THAT ACCESS POINTS, PLACEMENT ROUTE, SUPPORTS, AND

REQUIRED EQUIPMENT CLEARANCES ARE IDENTIFIED ON THE ROUTE DRAWING.

1/4" = 1'-0" F4

MECHANICAL DUCT PLAN - BASEMENT - AREA B

1 PROVIDE NEW DDC TERMINAL UNIT, CONNECT TO EXISTING BUILDING AUTOMATION SYSTEM. PROVIDE NEW THERMOSTAT TO MATCH EXISTING BUILDING STANDARDS, COORDINATE FINAL LOCATION WITH

COR. REFER TO SHEET M-501 FOR DETAILS AND M-803 FOR CONTROLS.

2 CONNECT EXISTING DUCTWORK TO NEW TERMINAL UNIT. PROVIDE TRANSITIONS AS NECESSARY TO

MAKE CONNECTION AND SEAL AIRTIGHT.

3 PROVIDE NEW EXHAUST, RETURN AND SUPPLY GRILLES, TYP.

4 DEDUCT ALTERNATE 1 OMITS ARCHITECTURAL RENOVATION WORK WITHIN THIS AREA, SEE SHEET

MH100B.1 FOR DEDUCT ALTERNATE 1 MECHANICAL LAYOUT.

5 THE RELOCATION OF THIS RETURN AIR GRILLE SHALL BE OMITTED UNDER DEDUCT ALTERNATE 1.

6 AS-BUILTS DO NOT IDENTIFY THIS AIR TERMINALS CFM.

7 SMOKE COMPARTMENT BOUNDARY LINE, SEE SHEET G-101 FOR ADDITIONAL INFORMATION.

8 PROVIDE FIRE/FIRE SMOKE DAMPER AT LOCATION SHOWN.

KEYNOTES

Revisions: Date:

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH

FIRE AND SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH

BOPC.A

BOPC.A.1

BOPC.B

BOPC.B.1

BOPC.C

BOPC.D

BOPC.E

1 2

1 2

1 2

VAV-1-6

VAV-1-13

VAV-1-10

EG

70 CFM

EG

80 CFM

SD

50 CFM

CR

0 CFM

SD

100 CFM

SD

50 CFM

SD

260 CFM

RG

100 CFM

RG

190 CFM

RG

90 CFM

SD

90 CFM

SD

330 CFM

SD

90 CFM

SD

160 CFM

SD

160 CFM

EG

80 CFM

RG

150 CFM

SD

160 CFM

RG

620 CFM

SD

160 CFM

EG

80 CFM

EG

80 CFM

SD

80 CFM

SD

100 CFM

RG

100 CFM

SD

100 CFM

SD

160 CFM

SD

130 CFM

RG

130 CFM

RG

110 CFM

SD

110 CFM

SD

950 CFM

EG

950 CFM

RG

240 CFM

EG

550 CFM

SD

230 CFM

SD

190 CFM

SD

160 CFM

RG

620 CFM

RG

100 CFM

RG

100 CFM

(E )1

"ø

E X

H

(E)12"ø EXH(E)10"ø EXH

(E)8"ø EXH

(E )1

"ø

S A

(E)6"ø EXH

(E)6"ø EXH

(E)8"ø SA

(E)8"ø SA

(E)8"ø SA

(E)8"ø SA

(E)8"ø EXH

(E)10"ø SA (E)14"x12" SA

(E)8"ø SA

(E )1

"x

R A

(E)12"ø RA

(E)12"ø RA

(E)10"ø RA

(E)8"ø RA

(E)8"ø RA

(E)6"ø RA (E)6"ø RA

(E)6"ø RA

(E)10"ø EXH(E)6"ø EXH

(E)8"ø EXH

(E )6

"ø E

X H

(E)12"ø SA

(E)8"ø SA

(E )8

"ø S

A

(E)8"ø SA (E)6"ø SA

(E)6"ø SA

(E)6"ø SA

(E)6"ø SA

(E)12"ø SA

(E )1

"ø

S A

(E )6

"ø S

A

(E)10"ø SA

(E )8

"ø S

A (E

)8 "ø

S A

(E)10"ø RA

(E)8"ø RA

(E)6"ø RA

(E )6

"ø S

A

(E)4"ø SA

(E)24"x12" SA

(E )1

"ø

S A

(E)54"x14" SA

(E)6"ø SA(E)6"ø SA

(E)4"ø SA

(E)4"ø SA

(E )6

"ø S

A(E)6"ø SA

(E)10"ø SA

(E )8

"ø S

A

(E)8"ø SA

(E )2

"x

R A

(E)8"ø RA

(E)6"ø RA

(E )2

"x

S A

(E)30"x12" SA

(E)5"ø SA

(E)6"ø SA(E)12"ø SA

(E)8"ø SA

(E)8"ø RA

(E)5"ø SA

(E)16"x12" SA

(E)10"ø SA

(E)6"ø RA

(E)6"ø RA

(E)12"x8" SA

(E)12"ø

(E)6"ø RA

(E)50"x12" SA(E)37"x12" SA(E)14"ø SA

(E)10"ø RA

(E)14"x12" EXH

(E)24"x12" SA

(E )1

"x

S A

(E )1

"ø

S A

(E )2

"x

S A(E)18"x10"

VAV-1-7

VAV-1-14 VAV-1-15

VAV-1-16

VAV-1-17

VAV-1-18

VAV-1-9

VAV-1-8

VAV-1-11

VAV-1-12

VAV-1-15

VAV-1-14

VAV-1-13

VAV-1-11

VAV-1-17

VAV-1-16

VAV-1-9

VAV-1-10

VAV-1-8

VAV-1-12

VAV-1-18

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

(E )1

"ø

S A

EG

200 CFM

EG

210 CFM

(E)6"ø RA

F1/MH100A

F4/MH100D

F4/MH100Cx

NURSE

B1C34A

MALE RR

B1C33

FEMALE RR

B1C32

WAITING

B1C-1

CORRIDOR

B1C-1

TRIAGE RM

B1C28

PATIENT COMFORT

ROOM

B1C27

OBSERVATION/

TREATMENT RM

B1C25

OBSERVATION/

TREATMENT RM

B1C26

OBS BEDS ROOM

B1C-6ANURSE STATION

B1C29A

CORRIDOR

B1C-8

CORRIDOR

B1C-7

TOILET

B1C24

OBSERVATION/

TREATMENT RM

B1C23

OBSERVATION/

TREATMENT RM

B1C14

SOILED UTILITY RM

B1C55

MECHANICAL ROOM

B1C39

HEAD NURSE

B1C53

OBSERVATION/

TREATMENT RM

B1C22

CORRIDOR

B1C-8

STAIR NO.4

B1C43

EQUIP STOR

B1C60

HAC

B1C57

CHIEF OF ER

B1C52

SPD

B1C51

CORRIDOR

B1C-2

ELEVATOR EQUIP RM

B1C40

ELEVATOR

S-6

ELEVATOR

S-5

CORRIDOR

B1C-2

POLICE CHIEF

OFFICE

B1C35

OBS BEDS ROOM

B1C-6A

CLOSET

B1C34D

SMALL TOILET

B1C34C

CRASH CART

ALCOVE

PUBLIC AFFAIRS

B1C37

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

B

B

IM

/5

-1 -2

E x p a n d E

D B e d s

/5

-1

-2

.O P

C .M

E .r v t

/1

/2

:5

:0

A

M

MH100B.1

MECHANICAL DUCT PLAN - LEVEL

B - AREA B - DEDUCT ALTERNATE 1

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

06/18/2021 M.PERKINS G. WEAVER

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

A. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-CONSTRUCTION TAB

REPORT FOR THE EQUIPMENT AND ASSOCIATED SYSTEMS SHOWN ON THE

CONSTRUCTION DOCUMENTS AND UTILIZE ALL AVAILABLE AS-BUILT DRAWINGS

FROM THE OWNER. TEST AND BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO

CONSTRUCTION AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP

THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING EQUIPMENT

LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND TAG NUMBERS. IF THERE

ARE LOCATIONS WHERE THE DRAWINGS DO NOT REFLECT FIELD CONDITIONS, THE

TEST AND BALANCE CONTRACTOR SHALL INCLUDE THE AIRFLOW AND WATERFLOW

READINGS ON THE FORMS AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON

THE DRAWINGS. REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE

INFORMATION.

B. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED TO

ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA FOR THE

RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT ENGINEER FOR

REVIEW AND COMMENT PRIOR TO COMMENCING THE DEMOLITION AND/OR NEW

WORK ASSOCIATED WITH THE FACILITY RENOVATION.

C. PROVIDE AIR BALANCE REPORT PRIOR TO FINAL INSPECTION

D. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY

REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO VIOLATIONS

OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A CERTIFIED ROOFING

INSPECTOR MEETING THE REQUIREMENTS OF THE INSTALLED ROOF. ALL

WARRANTY VIOLATIONS WILL BE REQUIRED TO BE CORRECTED PRIOR TO CLOSE

OUT. ROOFS AND/OR ROOFING IMPACTED BY WORK INCLUDE B126.

E. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL PIPING

PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED

AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF

CAULKING MATERIAL.

F. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND CONDUIT PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL PROVIDE

NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN REQUIRED

EQUIPMENT ACCESS AND SERVICEABILITY.

G. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION OF

THOSE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR

TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY

FROM CONSTRUCTION DOCUMENTS.

H. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH ALL TRADES

PRIOR TO INSTALLATION.

I. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT CONNECTIONS

BETWEEN ALL DISSIMILAR METALS.

J. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

K. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED EXTERIOR PIPE

PENETRATIONS AND SEAL COMPLETELY.

L. CONTRACTOR TO PROVIDE TEMPORARY FLOORING WHILE MODIFYING

SUBFLOORING.

M. SEE M-501 FOR LOW PRESSURE DUCT FITTING DETAILS.

N. SEE M-501 FOR DIFFUSER AND REGISTER CONNECTION DETAILS.

O. REPLACE ALL EXISTING DUCT WRAP IN AREA OF WORK.

P. SEE M-700 SERIES FOR MECHANICAL EQUIPMENT SCHEDULES AND M-802 AND M-803

FOR CONTROL SEQUENCE.

Q. PROVIDE PRECONSTRUCTION TAB READINGS OF THE EXISTING SUPPLY AIR AND

RETURN AIR SERVING THE ROOMS IN THE AREA OF WORK. REBALANCE EXISTING

SUPPLY AND RETURN AIR SYSTEMS AFTER DEMOLITION IS COMPLETE.

R. TECHNICAL COORDINATION DRAWINGS OF COMPLETE ASSEMBLIES, REFLECTING

ACCURATE PROJECT CONDITIONS, SHALL BE SUBMITTED WITH EQUIPMENT

SELECTIONS TO ENSURE SPACE ALLOWANCES ARE REFLECTED IN THE ACTUAL

SPACE AVAILABLE. WHERE SIZE DEVIATIONS DIFFER FROM THE BASIS OF DESIGN,

CONTRACTOR SHALL HIGHLIGHT THE DIFFERENCES FOR AE/COR REVIEW WITHIN

THE SUBMITTAL. CONTRACTOR SHALL PROVIDE INSTALLATION ROUTE AND

VERIFICATION THAT ACCESS POINTS, PLACEMENT ROUTE, SUPPORTS, AND

REQUIRED EQUIPMENT CLEARANCES ARE IDENTIFIED ON THE ROUTE DRAWING.

1 PROVIDE NEW DDC TERMINAL UNIT, CONNECT TO EXISTING BUILDING AUTOMATION SYSTEM. PROVIDE NEW THERMOSTAT TO MATCH EXISTING BUILDING STANDARDS, COORDINATE FINAL LOCATION WITH

COR. REFER TO SHEET M-501 FOR DETAILS AND M-803 FOR CONTROLS.

2 CONNECT EXISTING DUCTWORK TO NEW TERMINAL UNIT. PROVIDE TRANSITIONS AS NECESSARY TO

MAKE CONNECTION AND SEAL AIRTIGHT.

3 EXISTING DUCTWORK TO REMAIN.

KEYNOTES

1/4" = 1'-0" F4

MECHANICAL DUCT PLAN - LEVEL B - AREA B - DEDUCT ALTERNATE 3

Revisions: Date:

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH

FIRE AND SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH

FD

BOPC.D

BOPC.E

BOPC.F

BOPC.G

F1/MH100A

F4/MH100D

(E )3

"x

E X

H

(E)18"x12" EXH

(E)72"x20" OA

(E)48"x24" RA

(E)26"ø RA

(E)30"ø RA

(E )2

"x

R A

(E)18"x12" EXH

(E)18"x10" EXH

(E)50"x12" SA

(E)54"x14" SA

(E)30"x12" EXH

(E)24"x12" SA

(E)6"ø SA

8"ø RA

6"ø SA

(E )3

"x

S A

(E)24"x12" SA

8"ø RA 10"x12" SA

"ø

S A

8"ø SA

"x

S A

"x

S A

"x

R A

8"ø SA

(E )2

"x

R A

"ø

E X

H

"ø

S A

"ø

E X

H

"ø

S A

(E)12"x8" SA

(E )2

"x

S A

(E)54"x14" SA

(E )1

"ø

R A

(E )1

"x

S A

(E )1

"x

R A

36"ø EXH

65"x18" EXH

36"x12" RA

66"x24" OA

66"x24" OA

50"x24" RA

"ø

S A

(E)37"x12" SA

(E)14"ø SA

"ø

R A

8"ø RA

1-AHU-4

1-AHU-3

VAV-1-14

VAV-1-15

VAV-1-15

VAV-1-19

VAV-1-7

V A

V -1

-1

1 2

F D

FSDFSDFSD

F S

D

FD

F D

FD

EG

120 CFM

SD

160 CFM

EG

95 CFM

SD

150 CFM

EG

80 CFM

RG

150 CFM

SD

80 CFM

SD

80 CFM

RG

150 CFM

SD

340 CFM

SD

150 CFM

SD

150 CFM

SD

150 CFM

EG

120 CFM

RG

150 CFM

RG

150 CFM

RG

240 CFM

RG

450 CFM

SD

275 CFM

SD

300 CFM

SD

275 CFM

RG

200 CFM

SD

200 CFM

EG

60 CFM

SD

100 CFM

(E)10"ø SA

(E)10"ø SA

(E)10"ø SA

(E )1

"x

S A

(E )1

"x

S A

(E )8

"ø E

X H

(E)6"ø EXH (E)8"ø SA

(E)8"ø SA (E)8"ø RA

(E)12"ø RA

EQUIP STOR

B1C44

CONTROL ROOM

B1C45PAT HOLDING

B1C47

HAC

B1C49

CT SCANNER

B1C46

MECHANICAL ROOM

B1C17

AREAWAY

NEW OBSERVATION

ROOM

BC24

NEW OBSERVATION

ROOM

B1C23

NEW OBSERVATION

ROOM

B1C21

SOILED UTILITY

B1C53

OBSERVATION/

TREATMENT RM

B1C14

CORRIDOR

B1C-4 CORRIDOR

B1C-2

STF TLT

BC51CLEAN UTILITY

B1C52

HAC

BC50

LINEN CLOSET

B1C42

STAIR NO.4

B1C43

LINEN CLOSET

B1C41

ELEVATOR EQUIP RM

B1C40

CORRIDOR

B1C48

RG

400 CFM

S M

O K

E C

O M

P A

R T

M E

N T

S M

O K

E C

O M

P A

R T

M E

N T

VAV-1-6

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

C

B

IM

/5

-1 -2

E x p a n d E

D B e d s

/5

-1

-2

.O P

C .M

E .r v t

/1

/2

:5

:1

A

M

MH100C

MECHANICAL DUCT PLAN - LEVEL

B - AREA C

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

06/18/2021 M.PERKINS G. WEAVER

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

KEYNOTES

A. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-CONSTRUCTION TAB

REPORT FOR THE EQUIPMENT AND ASSOCIATED SYSTEMS SHOWN ON THE

CONSTRUCTION DOCUMENTS AND UTILIZE ALL AVAILABLE AS-BUILT DRAWINGS

FROM THE OWNER. TEST AND BALANCE CONTRACTOR SHALL VISIT SITE PRIOR

TO CONSTRUCTION AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND

DEVELOP THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING

EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND TAG

NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO NOT REFLECT

FIELD CONDITIONS, THE TEST AND BALANCE CONTRACTOR SHALL INCLUDE THE

AIRFLOW AND WATERFLOW READINGS ON THE FORMS AND LOCATE THE

EQUIPMENT AND/OR AIR DEVICE ON THE DRAWINGS. REFER TO SPECIFICATION

SECTION 23 05 93 FOR MORE INFORMATION.

B. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED TO

ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA FOR THE

RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT ENGINEER FOR

REVIEW AND COMMENT PRIOR TO COMMENCING THE DEMOLITION AND/OR NEW

WORK ASSOCIATED WITH THE FACILITY RENOVATION.

C. PROVIDE AIR BALANCE REPORT PRIOR TO FINAL INSPECTION

D. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY

REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO

VIOLATIONS OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A CERTIFIED

ROOFING INSPECTOR MEETING THE REQUIREMENTS OF THE INSTALLED ROOF.

ALL WARRANTY VIOLATIONS WILL BE REQUIRED TO BE CORRECTED PRIOR TO

CLOSE OUT. ROOFS AND/OR ROOFING IMPACTED BY WORK INCLUDE B126.

E. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL

PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE

CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED

FIRE PROOF CAULKING MATERIAL.

F. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND CONDUIT PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

G. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR TO FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION OF

THOSE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR

TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER

SIGNIFICANTLY FROM CONSTRUCTION DOCUMENTS.

H. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH ALL

TRADES PRIOR TO INSTALLATION.

I. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT

CONNECTIONS BETWEEN ALL DISSIMILAR METALS.

J. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

K. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED EXTERIOR

PIPE PENETRATIONS AND SEAL COMPLETELY.

L. CONTRACTOR TO PROVIDE TEMPORARY FLOORING WHILE MODIFYING

SUBFLOORING.

M. SEE M-501 FOR LOW PRESSURE DUCT FITTING DETAILS.

N. SEE M-501 FOR DIFFUSER AND REGISTER CONNECTION DETAILS.

O. REPLACE ALL EXISTING DUCT WRAP IN AREA OF WORK.

P. SEE M-701 AND M-702 FOR MECHANICAL EQUIPMENT SCHEDULES AND M-802 AND

M-803 FOR CONTROL SEQUENCE.

Q. PROVIDE PRECONSTRUCTION TAB READINGS OF THE EXISTING SUPPLY AIR AND

RETURN AIR SERVING THE ROOMS IN THE AREA OF WORK. REBALANCE EXISTING

SUPPLY AND RETURN AIR SYSTEMS AFTER DEMOLITION IS COMPLETE.

1/4" = 1'-0" F4

MECHANICAL DUCT PLAN - LEVEL B - AREA C - FUTURE

1 PROVIDE NEW DDC TERMINAL UNIT, CONNECT TO EXISTING BUILDING AUTOMATION SYSTEM. PROVIDE NEW THERMOSTAT TO MATCH EXISTING BUILDING STANDARDS, COORDINATE FINAL LOCATION WITH

COR. REFER TO SHEET M-501 FOR DETAILS AND M-803 FOR CONTROLS.

2 CONNECT EXISTING DUCTWORK TO NEW TERMINAL UNIT. PROVIDE TRANSITIONS AS NECESSARY TO

MAKE CONNECTION AND SEAL AIRTIGHT.

3 PROVIDE NEW EXHAUST, RETURN AND SUPPLY GRILLES, TYP.

4 DEDUCT ALTERNATE 1 OMITS ARCHITECTURAL RENOVATION WORK WITHIN THIS AREA, SEE SHEET

MH100B.1 FOR DEDUCT ALTERNATE 1 MECHANICAL LAYOUT.

5 NEW OUTSIDE AIR INTAKE FROM ROOF MOUNTED GRAVITY HOOD.

6 PROVIDE NEW AIR HANDLING UNIT WITH 100 PERCENT OUTSIDE AIR/EXHAUST EMERGENCY MODE, SEE

M-701 FOR SCHEDULE AND M-802 FOR CONTROLS.

7 VA REQUIRED FUTURE LAYOUT, COORDINATED WITH PROJECT 570-16-409. CONTRACTOR SHALL FIELD

VERIFY ALL DUCT ROUTING PRIOR TO CONSTRUCTION.

8 SMOKE COMPARTMENT BOUNDARY LINE, SEE SHEET G-101 FOR ADDITIONAL INFORMATION.

9 PROVIDE FIRE/FIRE SMOKE DAMPER AT LOCATION SHOWN. REFER TO DETAIL C1/M-502.

10 EXISTING THERMOSTAT LOCATION TO BE REUSED. COORDINATE FINAL ROUGH-IN LOCATION.

Revisions: Date:

BOPC.3BOPC.2BOPC.1

BOPC.D

BOPC.E

BOPC.F

BOPC.G

F4/MH100B

F1/MH100A

VAV-1-3

VAV-1-4

EG

180 CFM

RG

190 CFM

SD

340 CFM

EG

80 CFM

RG

130 CFM

SD

130 CFM

SD

170 CFM

SD

225 CFM

SD

75 CFM

EG

75 CFM

EG

225 CFM

SD

230 CFM

SD

230 CFM

SD

190 CFM

SD

160 CFM

RF-6

VAV-1-6

CAV-1-9

CAV-1-8

VAV-1-3

VAV-1-4

VAV-1-5

VAV-1-7

V A

V -1

-5

(E)24"x12" SA

(E)8"ø SA

(E)42"x12" RA

(E )1

"x

S A

(E)14"ø SA

(E )1

"x

E X

H

(E)10"ø RA

(E)8"ø RA

(E)10"ø EXH

(E)8"ø EXH

(E)8"ø EXH

(E)6"ø EXH

(E)6"ø SA

(E)6"ø EXH

(E)8"x8" EXH

(E )8

"x

E X

H

(E)6"x6" EXH(E)50"x24" RA

(E)48"x24" RA

(E)20"x12" RA

(E )1

"x

E X

H

(E)14"ø SA

(E )3

"x

S A

1 2

1 2

1 2

(E )1

"ø

E X

H

EF-1-11

EF-1-11 EF-1-10

STAIR

B1C21

OBSERVATION/

TREATMENT RM

B1C09

OBSERVATION/

TREATMENT RM

B1C10

OBSERVATION/

TREATMENT RM

B1C11

OBSERVATION/

TREATMENT RM

B1C12

OBSERVATION/

TREATMENT RM

B1C13

CORRIDOR

B1C-4

TELEPHONE CLOSET

B1C15

ELECTRIC CLOSET

B1C16

MECHANICAL ROOM

B1C17

AREAWAY

TRANSFORMER RM

B1C17A

ON-CALL RM

B1C18

TOILET

B1C19

STAFF LOUNGE

B1C20LOCKER RM

B1C20A

6"ø SA

8"ø SA

10"ø SA

6"ø SA

10"x6" SA

(E)24"x12" SA

(E)8"ø SA

(E)14"ø SA

8"ø SA

(E)8"ø RA

(E)18"x12" EXH

F1

MH100D

F4/MH100Cx

(E)24"x12" SA

8"ø SA

FPH-31

FPH-32

SD

160 CFM

EF-1-10

"ø

S A

"ø

S A

VAV-1-7

(E)14"ø SA

SD

160 CFM

(E)14"ø SA(E)14"ø SA

(E)14"ø SA

(E )2

"x

S A

(E)14"ø SA

16"x15" SA

6"ø SA

SMOKE COMPARTMENT 1

SMOKE COMPARTMENT 2

TYP

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Mechanical, Electrical and Plumbing:

KEY PLAN

D

B

IM

/5

-1 -2

E x p a n d E

D B e d s

/5

-1

-2

.O P

C .M

E .r v t

/1

/2

:5

:3

A

M

MH100D

MECHANICAL DUCT PLAN - LEVEL

B - AREA D

TRIPLE C - THE A-E GROUP

4401 Atlantic Avenue, Suite 200

Long Beach, CA 90807

562.452.7175

MAT PERKINS

REMODEL ED BEDS FOR

OBSERVATION BEDS

2615 E. CLINTON AVENUE, FRESNO, CA 93703

570-17-210

OPC

06/18/2021 M. PERKINS G. WEAVER

ISSUED FOR

CONSTRUCTION

GENERAL SHEET NOTES

A. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-CONSTRUCTION TAB

REPORT FOR THE EQUIPMENT AND ASSOCIATED SYSTEMS SHOWN ON THE

CONSTRUCTION DOCUMENTS AND UTILIZE ALL AVAILABLE AS-BUILT DRAWINGS

FROM THE OWNER. TEST AND BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO

CONSTRUCTION AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP

THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING EQUIPMENT

LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND TAG NUMBERS. IF THERE

ARE LOCATIONS WHERE THE DRAWINGS DO NOT REFLECT FIELD CONDITIONS, THE

TEST AND BALANCE CONTRACTOR SHALL INCLUDE THE AIRFLOW AND WATERFLOW

READINGS ON THE FORMS AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON

THE DRAWINGS. REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE

INFORMATION.

B. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED TO

ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA FOR THE

RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT ENGINEER FOR

REVIEW AND COMMENT PRIOR TO COMMENCING THE DEMOLITION AND/OR NEW

WORK ASSOCIATED WITH THE FACILITY RENOVATION.

C. PROVIDE AIR BALANCE REPORT PRIOR TO FINAL INSPECTION

D. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY

REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO VIOLATIONS

OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A CERTIFIED ROOFING

INSPECTOR MEETING THE REQUIREMENTS OF THE INSTALLED ROOF. ALL

WARRANTY VIOLATIONS WILL BE REQUIRED TO BE CORRECTED PRIOR TO CLOSE

OUT. ROOFS AND/OR ROOFING IMPACTED BY WORK INCLUDE B126.

E. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL PIPING

PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED

AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF

CAULKING MATERIAL.

F. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND CONDUIT PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL PROVIDE

NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN REQUIRED

EQUIPMENT ACCESS AND SERVICEABILITY.

G. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION OF

THOSE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR

TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY

FROM CONSTRUCTION DOCUMENTS.

H. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH ALL TRADES

PRIOR TO INSTALLATION.

I. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT CONNECTIONS

BETWEEN ALL DISSIMILAR METALS.

J. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

K. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED EXTERIOR PIPE

PENETRATIONS AND SEAL COMPLETELY.

L. CONTRACTOR TO PROVIDE TEMPORARY FLOORING WHILE MODIFYING

SUBFLOORING.

M. SEE M-501 FOR LOW PRESSURE DUCT FITTING DETAILS.

N. SEE M-501 FOR DIFFUSER AND REGISTER CONNECTION DETAILS.

O. REPLACE ALL EXISTING DUCT WRAP IN AREA OF WORK.

P. SEE M-700 SERIES FOR MECHANICAL EQUIPMENT SCHEDULES AND M-802 AND M-803

FOR CONTROL SEQUENCE.

Q. PROVIDE PRECONSTRUCTION TAB READINGS OF THE EXISTING SUPPLY AIR AND

RETURN AIR SERVING THE ROOMS IN THE AREA OF WORK. REBALANCE EXISTING

SUPPLY AND RETURN AIR SYSTEMS AFTER DEMOLITION IS COMPLETE.

R. TECHNICAL COORDINATION DRAWINGS OF COMPLETE ASSEMBLIES, REFLECTING

ACCURATE PROJECT CONDITIONS, SHALL BE SUBMITTED WITH EQUIPMENT

SELECTIONS TO ENSURE SPACE ALLOWANCES ARE REFLECTED IN THE ACTUAL

SPACE AVAILABLE. WHERE SIZE DEVIATIONS DIFFER FROM THE BASIS OF DESIGN,

CONTRACTOR SHALL HIGHLIGHT THE DIFFERENCES FOR AE/COR REVIEW WITHIN

THE SUBMITTAL. CONTRACTOR SHALL PROVIDE INSTALLATION ROUTE AND

VERIFICATION THAT ACCESS POINTS, PLACEMENT ROUTE, SUPPORTS, AND

REQUIRED EQUIPMENT CLEARANCES ARE IDENTIFIED ON THE ROUTE DRAWING.

1/4" = 1'-0" F4

MECHANICAL DUCT PLAN - BASEMENT - AREA D

1 PROVIDE NEW DDC TERMINAL UNIT, CONNECT TO EXISTING BUILDING AUTOMATION SYSTEM. PROVIDE NEW THERMOSTAT TO MATCH EXISTING BUILDING STANDARDS, COORDINATE FINAL LOCATION WITH

COR. REFER TO SHEET M-501 FOR DETAILS AND M-803 FOR CONTROLS.

2 CONNECT EXISTING DUCTWORK TO NEW TERMINAL UNIT. PROVIDE TRANSITIONS AS NECESSARY TO

MAKE CONNECTION AND SEAL AIRTIGHT.

4 SMOKE COMPARTMENT BOUNDARY LINE, SEE SHEET G-101 FOR ADDITIONAL INFORMATION.

5 CONNECT NEW DUCTWORK TO EXISTING DUCT MAIN, IN CEILING SPACE. COORDINATE EXACT LOCATION

WITH CEILING PLANS AND OTHER TRADES.

KEYNOTES

NTS

F1

EXISTING AREAWAY 103

Revisions: Date:

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH

FIRE AND SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH

File details come from the government source that posted it. Updated .