5.9_-_Electrical.pdf
PDF 1009 KB Posted
- Attached to
- CFD Station #344 HVAC Renovation
- Solicitation number
- IFB-2026-019
- Issued by
- Hamilton County, Indiana
About this file
This electrical design document file (5.9_-_Electrical.pdf) supports the City of Carmel Fire Station #44 HVAC Renovation project located at 5032 E Main Street, Carmel, Indiana 46033. The project involves comprehensive replacement of the heating, ventilating, and air conditioning systems, together with related electrical, controls, and ancillary work. The electrical scope includes demolition and removal of existing HVAC-related electrical infrastructure, installation of new power distribution and motor control systems, fire alarm system upgrades and expansions, and associated wiring and conduit work. Sealed bids for the overall project are due on Wednesday, December 16, 2026, at 10:00 a.m., submitted via the City's e-Procurement Portal at https://procurement.opengov.com/portal/carmelin. The project is managed by the Board of Public Works and Safety for the City of Carmel, Hamilton County, Indiana. The electrical documentation establishes detailed specifications for equipment including new circuit breakers, motor starters, disconnect switches, fire alarm devices, receptacles, lighting controls, and support infrastructure, with mounting heights, conductor sizing schedules, and seismic restraint requirements in accordance with the 2009 Indiana Electrical Code (2008 NEC with Amendments) and NFPA 72.
The electrical work requires coordination with mechanical, plumbing, and architectural divisions to ensure proper installation of HVAC-related components, emergency shutdown systems, and building modifications. Specific power requirements include new disconnect switches and circuit breakers serving RTU-1 (70A-3P), RTU-2 (150A-3P), and other mechanical equipment, along with new 20A-3P breaker for a pump controller. The contractor must provide all cutting, patching, grounding connections, seismic restraints, and conduit support systems as detailed in the specifications. Existing electrical equipment has right of first refusal to the owner. All materials and calculations for seismic restraints must be submitted by a professional engineer registered in Indiana and approved by the architect and engineer prior to installation. No pricing information, set-asides, or contract award dates are specified in this technical electrical document.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL LEGEND & SYMBOLS
• EXIT SIGN
• DIRECTIONAL ARROWS AS INDICATED
• SHADING INDICATES ILLUMINATED
FACE
• CONNECT TO UNSWITCHED BRANCH
CIRCUIT INDICATED
• END / WALL / CEILING
• LIGHTING FIXTURE
• TYPE AS INDICATED
• POLE MOUNTED LIGHT FIXTURE
• TYPE AS INDICATED
• EMERGENCY BATTERY WALL PACK
• TYPE AS INDICATED
• SHADING INDICATES EMERGENCY
FIXTURE CONNECTED TO BATTERY
INVERTER OR GENERATOR
• CONNECT BATTERY INVERTER TO
UNSWITCHED SOURCE IN ADDITION TO
SWITCHING INDICATED
• TRACK AND TRACK LIGHT FIXTURE
• LIGHT FIXTURE
• TYPE AS INDICATED
• WALL MOUNTED FIXTURE
• TYPE AS INDICATED
LIGHTING
SUBSCRIPTS FOR LIGHTING FIXTURES INDICATE THE FOLLOWING, U.O.N.
NL - NIGHT LIGHT, PANEL SWITCHED, U.O.N.
POWER DISTRIBUTION
• POWER DISTRIBUTION PANELBOARD
• 208Y/120V; 3Ø, 4W
• FLOOR / SURFACE
• BRANCH CIRCUIT PANELBOARD
• 208Y/120V OR 480Y/277V; 3Ø, 4W
• FLUSH / SURFACE
• TERMINAL CABINET, TYPE AS NOTED
ON DRAWINGS
• FLUSH / SURFACE
• DRY- TYPE TRANSFORMER, RATING AS
INDICATED
• HOUSEKEEPING PAD
• SWITCHBOARD W/MAIN CIRCUIT
BREAKER SECTION
• HOUSEKEEPING PAD
• AUTOMATIC TRANSFER SWITCH
• WORKING CLEARANCE ABOUT
ELECTRICAL EQUIPMENT
• ELECTRIC MANHOLE
• GROUND ROD
• MOTOR - "M" INDICATES HORSEPOWER
• HEAVY-DUTY, NON-FUSED DISCONNECT
SWITCH (DS-#)
• HEAVY-DUTY, FUSED DISCONNECT
SWITCH (DS-#)
• COMBINATION MOTOR STARTER AND
DISCONNECT SWITCH (MS-#)
• VARIABLE FREQUENCY DRIVE (MS-#)
• FRACTIONAL HOURSEPOWER MANUAL
CONTROLLER WITH THERMAL
OVERLOADS (MS-#)
• EMERGENCY POWER OFF BUTTON
• SIMPLEX RECEPTACLE
• NEMA 5-20R, 125V, 20A
WIRING DEVICES
SUBSCRIPTS FOR RECEPTACLES, JUNCTION BOXES AND OTHER DEVICES INDICATE THE
FOLLOWING, U.O.N:
F - FLUSH IN FLOOR
GFCI - GROUND FAULT CIRCUIT
INTERRUPTER
H - HORIZONTALLY MOUNTED
IG - ISOLATED GROUND
L - LOCKING TYPE
R - RECESS IN EXISTING WALL (CUT/PATCH)
S - SURFACE MOUNTED
TR - TAMPER RESISTANT
WP - WEATHERPROOF IN-USE
X - MOUNTED IN EXISTING OUTLET BOX
• DUPLEX RECEPTACLE
• NEMA 5-20R,125V, 20A
• DOUBLE DUPLEX (QUADRAPLEX) RECEPTACLE
• NEMA 5-20R,125V, 20A
• DUPLEX RECEPTACLE
• EMERGENCY CIRCUIT
• NEMA 5-20R, 125V, 20A
• DOUBLE DUPLEX (QUADRAPLEX) RECEPTACLE
• EMERGENCY CIRCUIT
• NEMA 5-20R, 125V, 20A
• SPECIAL RECEPTACLE
• NEMA CONFIGURATION AS INDICATED ON
DRAWING
• JUNCTION BOX
• DIRECT CONNECTION TO EQUIPMENT
• PULLBOX
• PROVIDE PULLBOXES INDICATED AS A
MINIMUM
• PROVIDE ADDITIONAL PULLBOXES, SIZED
PER NEC, AS REQUIRED
• FLUSH JUNCTION BOX WITH FURNITURE FEED
ADAPTING CONNECTOR MOUNTED AT 6" A.F.F.
• SURFACE-MOUNTED RACEWAY
• RECEPTACLES IN LOCATIONS INDICATED
• WIREWAY
• WALL MOUNTED U.O.N.
• FLOOR BOX
• SINGLE POLE SWITCH
• THREE-WAY SWITCH
• THREE-WAY SWITCH WITH PILOT LIGHT
• FOUR-WAY SWITCH
• SINGLE POLE SWITCH W/ PILOT LIGHT
• KEY OPERATED SINGLE POLE SWITCH
• KEY OPERATED THREE-WAY SWITCH
M EMH
ATS
J J
FB
M
J
MS-#
• PUSH BUTTON CONTROL STATION
PB
P
3P
K
3K
MCB
D
PANELBOARD NAMING
1 2 A 1
BRANCH PANELBOARDS
SEQUENTIAL PANEL NUMBER
FLOOR PLAN UNIT
A - UNIT A
B - UNIT B
VOLTAGE
2 - 208Y/120V 4 - 480Y/277V
FLOOR NUMBER
B - BASEMENT
1 - 1ST FLOOR
2 - 2ND FLOOR
1 2 A DP 1
POWER DISTRIBUTION PANELBOARDS
SEQUENTIAL PANEL NUMBER
"DISTRIBUTION PANELBOARD"
FLOOR PLAN UNIT
A - UNIT A
B - UNIT B
VOLTAGE
2 - 208Y/120V 4 - 480Y/277V
FLOOR NUMBER
B - BASEMENT
1 - 1ST FLOOR
2 - 2ND FLOOR
LIGHTING CONTROL DEVICES
OS1
O1
• MANUAL CONTROLS & AUTO-ON / AUTO-OFF
• 1000 SQFT COVERAGE
• TWO RELAYS IN POWER PACK
SYMBOL MOUNTING
WALL
DIMMING
TYPE
0-10V
OCCUPANCY
SENSOR TYPE
SWITCH/
BUTTONS
CONTROL DESCRIPTION
• (1) MANUAL SWITCH ON (TO SELECTED LIGHT LEVEL)/OFF
• (1) MANUAL LIGHT LEVEL WITH SLIDER
(1)N/A
D
DS
WALL 0-10V • (1) MANUAL SWITCH ON (TO SELECTED LIGHT LEVEL)/OFF
• (1) MANUAL LIGHT LEVEL WITH SLIDER
• MANUAL ON / AUTO OFF
(1)DUAL TECH.
D
DL
WALL LINE VOLT. • (1) MANUAL SWITCH ON (TO SELECTED LIGHT LEVEL)/OFF
• (1) MANUAL LIGHT LEVEL WITH SLIDER
(1)N/A
WALL N/A DUAL TECH.
(1)
OS2
WALL N/A DUAL TECH.
(1) • (1) MANUAL SWITCH ON/OFF
• MANUAL ON / AUTO OFF
OS3
WALL N/A DUAL TECH.
(2) • (2) MANUAL SWITCH ON/OFF
• MANUAL ON / AUTO OFF
CEILING N/A DUAL TECH. N/A
O2
• AUTO-ON / AUTO-OFF ONLY
• 1000 SQFT COVERAGE
• TWO RELAYS IN POWER PACK
CEILING N/A DUAL TECH. N/A
O3
• MANUAL CONTROLS & AUTO-ON / AUTO-OFF
• 1000 SQFT COVERAGE
• TWO RELAYS IN POWER PACK
• PLUG-LOAD CONTROL OF RECEPTACLES INDICATED IN
ROOM, U.O.N.
CEILING N/A DUAL TECH. N/A
D
DMX
WALL DMX N/A MULTI. • DMX COLOR CHANGING CONTROLLER
• NICOLAUDIE STICK-CU4
HB
• MANUAL CONTROLS & AUTO-ON / AUTO-OFF
• TWO RELAYS IN POWER PACK
• HIGHBAY COVERAGE
CEILING N/A PIR N/A
• (1) MANUAL SWITCH ON/OFF
• AUTO ON / AUTO OFF
DH
• DAY-LIGHT HARVESTING CONTROLLER W/AUTO DIMMINGCEILING N/A N/A N/A
• DUPLEX RECEPTACLE
• SPLIT-WIRE
• NEMA 5-20R, 125V, 20A
• DUPLEX RECEPTACLE
• PLUG-LOAD CONTROLLED
• NEMA 5-20R, 125V, 20A
• DOUBLE DUPLEX (QUADRAPLEX) RECEPTACLE
• PLUG-LOAD CONTROLLED
• NEMA 5-20R, 125V, 20A
HALF
CONTROLLED
FULLY
CONTROLLED
CONDUIT & FEEDER
• OVERHEAD ELECTRICAL SERVICE
• UNDERGROUND ELECTRICAL
SERVICE
• CONDUIT - TURNED UP
• CONDUIT - TURNED DOWN
• HOMERUN TO PANEL WITH CIRCUIT
NUMBER(S) AS INDICATED
• GROUND CONDUCTOR
• PHASE CONDUCTOR
• NEUTRAL CONDUCTOR
• ONE-LINE DIAGRAM
• EXISTING FEEDER & CONDUIT
• ONE-LINE DIAGRAM
• DEMOLISHED FEEDER & CONDUIT
• ONE-LINE DIAGRAM
• NEW (NORMAL) FEEDER & CONDUIT
• ONE-LINE DIAGRAM
• NEW (EMERGENCY) FEEDER & CONDUIT
• ONE-LINE DIAGRAM & FLOOR PLANS
• NEW FEEDER & CONDUIT SIZE
• REFER TO 'FEEDER & BRANCH
CIRCUIT SCHEDULE (COPPER)' OR
'FEEDER SCHEDULE (ALUMINUM)'
BASED ON SPECIFICATIONS AND
PROVIDE BOTH FEEDER AND
CONDUIT SIZE INDICATED
F###
• FIRE ALARM CONTROL UNIT
• FLUSH / SURFACE
FIRE ALARM SYSTEM
SUBSCRIPTS FOR FIRE ALARM SYSTEM DEVICES INDICATE THE FOLLOWING, U.O.N:
S - SURFACE MOUNTED
R - RECESS IN EXISTING WALL (CUT/PATCH)
• REMOTE FIRE ALARM CONTROL UNIT
• FLUSH / SURFACE
• FIRE ALARM ANNUNCIATOR UNIT
• FLUSH / SURFACE
• MANUAL PULL STATION
• SPEAKER
• WALL / CEILING
• VISUAL STROBE
• WALL / CEILING
• BELL WITH VISUAL INDICATOR
• WALL
• DUCT DETECTOR - SUPPLY DUCT
• DUCT DETECTOR - RETURN DUCT
• DOOR HOLD RELEASE DEVICE
• SUPPLIED BY DIVISION 8
• SPRINKLER SYSTEM TAMPER SWITCH
• SPRINKLER SYSTEM FLOW SWITCH
• POST INDICATOR VALVE
• SPEAKER/STROBE
• WALL / CEILING
• HORN
• WALL / CEILING
M
S
S
H
H
V
B
R
TS
FS
P
S F
R F
S D
R D
FACU FACU
RACU RACU
FAA FAA
AR
• ADDRESSABLE RELAY MODULE FOR
CONTROL / MONITORING
• SPRINKLER SYSTEM PRESSURE SWITCH
PS
• HORN/STROBE
• WALL / CEILING
• SMOKE DETECTOR
• CEILING
• HEAT DETECTOR
• CEILING
SR
F
• COMBINATION SMOKE / HEAT DETECTOR
• CEILING
S
S
H
H
V
• POWER DISTRIBUTION PANELBOARD
• 480Y/277V; 3Ø, 4W
• FLOOR / SURFACE
HALF
CONTROLLED
FULLY
CONTROLLED
SYMBOL MOUNTING HEIGHT ABOVE FINISHED FLOOR (U.O.N.)
• +18" TO CENTER OF RECEPTACLE
• +6" ABOVE TOP OF COUNTERTOP TO BOTTOM OF
RECEPTACLE
• +46" TO CENTER OF LIGHT SWITCH / CONTROLSOS1, OS2, OS3,
3, 4, P, 3P, K, 3K
D
• +46" TO CENTER OF DIMMER / CONTROLSD1, D2, D3, DMX
• COORDINATE MOUNTING HEIGHT WITH EQUIPMENT IF
NOT INDICATED ON DRAWING
• +46" TO CENTER OF MOTOR STARTER TOGGLE SWITCHMS
• +46" TO CENTER OF EMERGENCY SHUT-OFF
B H H S S V
• +80" TO BOTTOM OF WALL MOUNTED FIRE ALARM DEVICE
M
• +46" TO CENTER OF MANUAL PULL STATION
• REFER TO SPECIFICATIONS AND 'GENERAL SYMBOLS &
ABBREVIATIONS NOTES (ALL DRAWINGS)'
• +90" TO TOP OF POWER DISTRIBUTION PANELBOARD'S
TRIM
• +72" TO TOP OF PANELBOARD'S TRIM
• +72" TO TOP OF EQUIPMENT
• +72" TO TOP OF EQUIPMENT
• +18" TO CENTER OF RECEPTACLE
• +6" ABOVE TOP OF COUNTERTOP TO BOTTOM OF
RECEPTACLE
• FLUSH TO CEILING
MOUNTING HEIGHTS
ANNOTATION SYMBOLS
• CIRCUIT TAG
PANEL-CKT
• ROOM CIRCUIT TAG
PANEL-CKT
• CIRCUIT NUMBER NOMENCLATURE BASED
ON # OF POLES
1P OR SWITCHBOARD: PANEL-CKT
2P: PANEL-(X,Y)
3P: PANEL-(X,Y,Z)
WP - WEATHERPROOF
X - MOUNTED IN EXISTING OUTLET BOX
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:4
:5
A
M
C
R e v it L o c a l\
-0
.4
H B ld g
E
\2
-0
.4
H
B ld g
E s m a th is .r v t
2026-028.44H
10.28.2026
SYMBOLS
E-001
SACM
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
E -0
S Y
M B
O L S
GENERAL ROUGH-IN MOUNTING HEIGHT NOTES
# NOTES
A COMPLETE COMPLIANCE WITH ALL ASPECTS OF ADA STANDARDS FOR ACCESSIBLE
DESIGN AND ICC/ANSI A117.1 IS REQUIRED OF ALL PROJECTS AND ACTIVITIES.
B MOUNTING HEIGHTS INDICATED ARE FOR TYPICAL DEVICES, UNLESS NOTED OR SPECIFIED
OTHERWISE.
C COORDINATE MOUNTING HEIGHTS OF ANY DEVICES WHICH ARE NOT INDICATED BY
ARCHITECT OR AND/OR ENGINEER.
D REFERENCE DIVISIONS 8, 10, 14, 22, 23, AND 27 FOR ADDITIONAL MOUNTING HEIGHTS.
# Revision Date
F20 12 12 3/4"
1P,1N,1G 2P,1G
2P,1N,1G 3P,1G
3P,1N,1G 3P,1N
EQUIP/SERV
GROUND
FEEDER/BRANCH
CIRCUIT LABEL
CONDUCTOR SIZE PER
CONDUIT
CONDUIT SIZE & QUANTITY
FEEDER & BRANCH CIRCUIT SCHEDULE (COPPER)
3P,2N,1G 3P,3N,1G 3P,1N,2G
PHASE &
NEUTRAL
3/4" 3/4" 3/4" 3/4" 3/4"
F30 10 10 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
F40 8 10 3/4" 3/4" 1" 1" 1" 1"
F50 6 10 1" 1" 1" 1-1/4" 1-1/4" 1"
F60 4 10 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4"
F70 4 8 1" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 1-1/4"
F80 3 8 1" 1-1/4" 1-1/4" 1-1/2" 1-1/2" 1-1/4"
F90 2 8 1" 1-1/4" 1-1/2" 1-1/2
2" 1-1/2"
F100 1 8 1-1/4" 1-1/2" 1-1/2" 2" 2" 2"
F110 1 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"
F125 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"
F150 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"
F175 2/0 6 1-1/2" 2" 2" 2-1/2" 2-1/2" 2"
F200 3/0 6 1-1/2" 2" 2" 2-1/2" 3" 2-1/2"
F225 4/0 4 2" 2" 2-1/2" 3" 2-1/2"
F250 250 4 2" 2-1/2" 3" 3" 3"
F300 350 4 2" 2-1/2" 3" 3-1/2" 3"
F350 500 3 2-1/2" 3" 3-1/2" 4" 3-1/2"
F400 3/0 3 (2) 1-1/2" (2) 2" (2) 2-1/2" (2) 2-1/2" (2) 2-1/2"
F450 4/0 2 (2) 2" (2) 2" (2) 2-1/2" (2) 3" (2) 2-1/2"
F500 250 2 (2) 2" (2) 2-1/2" (2) 3" (2) 3" (2) 3"
F600 350 1 (2) 2-1/2" (2) 3" (2) 3" (2) 3-1/2" (2) 3"
F700 500 1/0 (2) 2-1/2" (2) 3" (2) 3-1/2" (2) 4" (2) 3-1/2"
F800 350 2/0 (3) 2-1/2" (3) 3" (3) 3" (3) 3-1/2" (3) 3"
F900 350 2/0 (3) 2-1/2" (3) 3" (3) 3" (3) 3-1/2"
F1000 500 2/0 (3) 2-1/2" (3) 3" (3) 3-1/2" (3) 4"
F1200 350 3/0 (4) 2-1/2" (4) 3" (4) 3" (4) 3-1/2"
F1600 500 4/0 (5) 3" (5) 3" (5) 3-1/2" (5) 4"
F2000 500 250 (6) 3" (6) 3" (6) 3-1/2" (6) 4"
F2500 500 350 (7) 4" (7) 3-1/2" (7) 3-1/2" (7) 4"
F3000 500 500 (8) 4" (8) 4" (8) 4"
CONDUCTOR
SIZE
SINGLE PHASE
MAXIMUM BRANCH CIRCUIT CONDUCTOR LENGTHS (FEET)
#12
#8
#6
#4
#3
#2
#1
BRANCH CIRCUIT BREAKER SIZE
#10
120 VOLT
20A-1P 30A-1P
N/A
208 VOLT
20A-2P 30A-2P
N/A
277 VOLT
20A-1P 30A-1P
N/A
480 VOLT
20A-2P 30A-2P
N/A
CONDUCTOR
SIZE
THREE PHASE
#12
#8
#6
#4
#3
#2
#1
BRANCH CIRCUIT BREAKER SIZE
#10
208 VOLT
20A-3P 30A-3P
N/A
480 VOLT
20A-3P 30A-3P
N/A
NOTES:
1. MAINTAIN A MAXIMUM VOLTAGE DROP OF 3%. ADJUST CONDUCTOR SIZE PER MAXIMUM
BRANCH CIRCUIT LENGTH.
2. BRANCH CIRCUIT LENGTHS ARE BASED ON CONDUCTOR DISTANCE FROM PANELBOARD TO
LOAD.
3. PROVIDE JUNCTION BOX TO MAKE WIRE TRANSITION FOR FINAL TERMINATION ON DEVICE,
FIXTURE, EQUIPMENT, ETC.
4. CALCULATIONS BASED ON COPPER CONDUCTORS, 80% LOADING OF BRANCH CIRCUIT
BREAKER, AND 0.95 POWER FACTOR.
A AMPERE
ALTERNATING CURRENT; ARMORED CABLE
AMP SIZE OF CIRCUIT BREAKER FRAME/FUSED SWITCH
ABOVE FINISHED COUNTERTOP
ARC FAULT CIRCUIT INTERRUPTER
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMERICAN NATIONAL STANDARDS INSTITUTE
ASYMMETRICAL
AMP TRIP SIZE CIRCUIT BREAKER/FUSED SWITCH
AUTOMATIC TRANSFER SWITCH
AUXILIARY
AVERAGE
AMERICAN WIRE GAUGE
BATTERY
BRANCH CIRCUIT PANELBOARD
BREAKER
BOLTED PRESSURE SWITCH
CONDUIT; CELSIUS
CABINET
CIRCUIT BREAKER
CENTER TO CENTER
CANDELA
CUBIC FEET
CENTERLINE
CEILING
CONCRETE MASONRY UNIT
COLUMN
COMBINATION
CONCRETE
CONDUCTOR
CONNECTION
CONTINUOUS; CONTINUED
CONSTRUCTION
CONTROL PANEL
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
COPPER; CONDENSING UNIT
CABINET UNIT HEATER
CYLINDER
DEEP; DEPTH
DIRECT BURIED
DIRECT CURRENT
DEDICATED DEVICE ON INDIVIDUAL BRANCH CIRCUIT
DEMOLISH; DEMOLITION
DIAMETER
DIAGONAL
DISCONNECT
DISTRIBUTION
DOWN
DOUBLE-POLE, DOUBLE-THROW
DOUBLE-POLE, SINGLE-THROW
DISHWASHER
DRAWING
EACH
ELECTRICAL CONTRACTOR; DIVISIONS 26-28
EXHAUST FAN
ELECTRICAL GROUND BAR
ELECTRICAL GROUNDING CONDUCTOR
ELECTRIC HAND DRYER
ELECTRICAL
ELEVATOR; ELEVATION
EMERGENCY
ELECTRICAL METALLIC TUBING
ENCLOSURE
ENGINE
ELECTRICALLY OPERATED
EMERGENCY POWER OFF
EQUAL
EQUIPMENT
ENERGY REDUCTION MAINTENANCE SWITCH
ESTIMATED
EXISTING TO REMAIN
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXPOSED
EXISTING
EXTERIOR
FUSED; FAHRENHEIT
FIRE ALARM
FIRE ALARM ANNUNCIATOR
FIRE ALARM CONTROL UNIT
FLOOR BOX
FOOT-CANDLE
FAN COIL UNIT
FUSED DISCONNECT
FOUNDATION
FEEDER
FINISHED
FIXTURE
FULL LOAD AMPS
FLEXIBLE
FLOOR
FACTORY MUTUAL
FLEXIBLE METAL CONDUIT
FAN POWERED BOX
FEED THROUGH LUGS
FEET; FOOT
FEED THROUGH LUGS
FURNISHED
FULL-VOLTAGE NON-REVERSING
GROUND
GAUGE
GALVANIZED
GENERAL CONTRACTOR
GARBAGE DISPOSAL
GENERATOR
GROUND FAULT EQUIPMENT PROTECTION
GROUND FAULT CIRCUIT INTERRUPTER
HIGH
HEAVY DUTY
HIGH-DENSITY POLYETHYLENE CONDUIT
HAND-OFF-AUTO
HORIZONTAL
HORSEPOWER
HR
HT
HEAT PUMP
HEATER
HERTZ
INSIDE DIAMETER
INSTIT. OF ELECTRICAL AND ELECTRONICS ENGINEERS
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
IMPEDANCE
AC
AF
AFC
AFCI
AFF
AFG
AHU
AIC
AL
ANSI
ASYM
AT
ATS
AUX
AVG
AWG
BATT
BCP
BKR
BPS
C
CAB
CB
C/C
CD
CF
CL
CLG
CMU
COL
COMB
CONC
COND
CONN
CONT
CONST
CP
CPT
CT
CU
CUH
CYL
D
DB
DC
DED
DEMO
DIA
DIAG
DISC
DISTR
DN
DPDT
DPST
DW
DWG
EA
EC
EF
EGB
EGC
EHD
ELEC
ELEV
EM
EMT
ENCL
ENG
EO
EPO
EQ
EQUIP
ERM
EST
ETR
EWC
EWH
EXP
EX
EXT
F
FA
FAA
FACU
FB
FC
FCU
FD
FDN
FDR
FIN
FIXT
FLA
FLEX
FLR
FM
FMC
FPB
FTL
FT
FTL
FURN
FVNR
G/GND
GA
GALV
GC
GD
GEN
GFEP
GFCI
H
HD
HDPE
HOA
HORIZ
HP
HR
HT
HTP
HTR
HZ
ID
IEEE
IG
IMC
IMP
ABBREVIATIONS
IN INCH
INSULATED; INSULATION
INTERIOR; INTERNAL
INVERTED ELEVATION
JOULE
JUNCTION BOX
THOUSAND
THOUSAND CIRCULAR MILS
KIRK KEY
KNOCKOUT
KEYPAD
KILOVOLTS
KILOVOLT-AMPERES
KILOVOLT-AMPERES REACTIVE
KILOWATTS
LINEAR FEET
LENGTH; LONG
LIGHTNING ARRESTOR
LIGHT EMITTING DIODE
LIQUIDTIGHT FLEXIBLE METAL CONDUIT
LUMEN
LOCK-OUT TAG-OUT
LOCKED ROTOR AMPS
LONG-SHORT-INSTANTANEOUS
LONG-SHORT-INSTANTANEOUS-GROUND FAULT
LIGHT; LIQUIDTIGHT
LIGHTING
LOW VOLTAGE
MANUAL
MATERIAL
MAXIMUM
MECH. CONTRACTOR (DIV. 23); METAL CLAD CABLE
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOLDED CASE CIRCUIT BREAKER
MAIN DISTRIBUTION PANELBOARD
MECHANICAL
MANUFACTURING
MANUFACTURER
MANHOLE; MOUNTING HEIGHT
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
MAIN SWITCHBOARD
MOUNTED
MOUNTING
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE
MEGAVOLT AMPERES
MEGAVOLT AMPERES REACTIVE
NEUTRAL
NOT APPLICABLE
NORMALLY CLOSED
NEGATIVE (-)
NATIONAL ELECTRICAL MANUFACTURERS ASSOC.
NON-FUSED DISCONNECT SWITCH
NIGHT LIGHT
NON-METALLIC SHEATHED CABLE
NORMALLY OPEN; NUMBER
NOT TO SCALE
INSUL
INT
INV EL
J
JB
K
KCMIL
KK
KO
KP
KV
KVA
KVAR
KW
LF
L
LA
LED
LFMC
LM
LOTO
LRA
LSI
LSIG
LT
LTG
LV
MAN
MAT
MAX
MC
MCA
MCB
MCC
MCCB
MDP
MECH
MFG
MFR
MH
MIN
MISC
MLO
MOCP
MSB
MTD
MTG
MTS
MV
MVA
MVAR
N
N/A
NC
NEG
NEMA
NF
NIC
NL
NM
NO
NTS
KILOWATT-HOURSKWHR
POUNDLB
LIGHTING CONTROL RELAY PANELLCP
MEDIUMMED
MEGAWATTS; MICROWAVE OVENMW
MAIN ELECTRICAL GROUND BARMEGB
NOT IN CONTRACT
OC
OD
OH
OL
P
PB
PC
PED
PF
PH/Ø
PL
POS
PRI
PSF
PSI
PT
PUH
PVC
PWR
QTY
R
REF
REFR
REQ'D
RLA
RMC
RM
RT
RTU
RVAT
SCCR
SCHED
SCR
SEC
SF
SFB
SFL
SN
SP
SPDT
SPEC
SPST
SQ
SQ FT
SQ IN
SS
S/S
ST
STD
STP
SURF
SW
SWBD
PIV
RECEPT
SPD
SQ YD
SYM
T
TB
TCC
TCP
TR
TS
TYP
UC
UG
UL
UNFIN
UNO
VERT
UTP
UV
VAR
VFD
VG
VIF
VM
VP
VR
VUV
W
W/
W/O
WG
WP
WT
XFER
XFMR
Y
UTIL
V
VA
TC
TD
OVERCURRENT
OUTSIDE DIAMETER
OVERHEAD
OVERLOAD
POLE
PULL BOX; PUSH BUTTON
PHOTOCELL; PLUMBING CONTRACTOR (DIVISION 22)
PEDESTAL
POWER FACTOR
PHASE
PILOT LIGHT
POSITIVE (+)
PRIMARY
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POTENTIAL TRANSFORMER
PROPELLER UNIT HEATER
POLYVINYL CHLORIDE CONDUIT
POWER
QUANTITY
RESISTANCE
REFERENCE
REFRIGERATOR
REQUIRED
RUNNING LOAD AMPS
RIGID METAL CONDUIT
ROOM
RAINTIGHT
ROOF TOP UNIT
REDUCED VOLTAGE AUTOTRANSFORMER
SHORT-CIRCUIT CURRENT RATING
SCHEDULE
SHORT CIRCUIT RATING
SECONDARY
SUPPLY FAN
SUB-FEED CIRCUIT BREAKER
SUB-FEED LUGS
SOLID NEUTRAL
SINGLE-POLE
SINGLE-POLE, DOUBLE-THROW
SPECIFICATION
SINGLE-POLE, SINGLE-THROW
SQUARE
SQUARE FEET
SQUARE INCH
STAINLESS STEEL
START-STOP
SHUNT TRIP
STANDARD
SHIELDED TWISTED PAIR
SURFACE
SWITCH
SWITCHBOARD
POST INDICATOR VALVE
RECEPTACLE
SURGE PROTECTION DEVICE
SQUARE YARD
SYMMETRICAL
TEMPERATURE; TRANSFORMER
TERMINAL BLOCK
TEMPERATURE CONTROL CONTRACTOR
TEMPERATURE CONTROL PANEL
TAMPER-RESISTANT
TAMPER SWITCH
TYPICAL
UNDERCOUNTER; UNDERCABINET
UNDERGROUND
UNDERWRITERS LABORATORY
UNFINISHED
UNLESS NOTED OTHERWISE
VERTICAL
UNSHIELDED TWISTED PAIR
UNIT VENTILATOR
VOLT AMPERES REACTIVE
VARIABLE FREQUENCY DRIVE
VANDAL GUARD
VERIFY IN FIELD
VENDING MACHINE
VANDAL PROOF
VANDAL RESISTANT
VERTICAL UNIT VENTILATOR
WIDE; WIRE; WATT
WITH
WITHOUT
WIRE GUARD
WEATHERPROOF
WATERTIGHT; WEIGHT
TRANSFER
TRANSFORMER
WYE
UTILITY
VOLT
VOLT AMPERES
TIME CLOCK
TIME DELAY
FLOW SWITCHFS
MAIN FUSED SWITCHMFS
MOTOR-STARTING SWITCHMSS
FRACTIONAL HORSEPOWER MANUAL CONTROLLERFHPMC
INTEGRATED HORSEPOWER MANUAL CONTROLLERIHPMC
FIRE PROTECTION CONTRACTORFPC
SEISMIC RESTRAINTS REQUIREMENTS
SEISMIC RESTRAINTS SHALL BE PROVIDED FOR ALL
ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE
WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING
CODE AND ASCE-7.
REFERENCE THE STRUCTURAL DRAWINGS FOR SEISMIC
DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE
CALCULATIONS AND A COMPLETE LAYOUT INDICATING THE
LOCATIONS AND DETAILS OF THE PROPOSED SEISMIC
RESTRAINTS FOR REVIEW AND ACCEPTANCE BY THE
ARCHITECT AND ENGINEER. ALL MATERIALS SHALL BE BY A
SINGLE MANUFACTURER.
THE SUBMITTAL SHALL BE STAMPED AND SIGNED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF
INDIANA.
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:4
:5
A
M
C
R e v it L o c a l\
-0
.4
H B ld g
E
\2
-0
.4
H
B ld g
E s m a th is .r v t
2026-028.44H
10.28.2026
GENERAL INFORMATION
E-002
SACM
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
E -0
G E
N E
R A
L I
N F
O R
M A
T
IO
N
GENERAL REQUIREMENTS NOTES
(ALL DRAWINGS)
# NOTES
A APPLICABLE CODES:
- 2009 INDIANA ELECTRICAL CODE (2008 NEC WITH AMMENDMENTS)
- NFPA 72 - 2010
B CONTRACT DOCUMENTS CONSISTS OF BOTH A PROJECT MANUAL AND
DRAWINGS. BOTH ARE MEANT TO BE COMPLEMENTARY - ANYTHING APPEARING
ON EITHER MUST BE EXECUTED THE SAME AS IF SHOWN ON BOTH.
C THOROUGHLY EXAMINE THE WORK OF OTHER CONTRACTORS AND PROPERLY
INSTALL ALL WORK REQUIRED FOR THE PROJECT.
D REFER TO LIFE SAFETY PLAN FOR FIRE-RATING REQUIREMENTS. CONTRACTOR IS
RESPONSIBLE FOR PROVIDING FIRE-RATED DEVICES/SEALS AS SHOWN ON
ELECTRICAL DRAWINGS AND AS REQUIRED BASED ON LIFE SAFETY PLAN
INFORMATION.
E PER NEC ARTICLE 110.26(A) AND 110.26(F) THE DEDICATED ELECTRICAL SPACE
INCLUDES THE SPACE DEFINED BY EXTENDING THE FOOTPRINT OF THE
ELECTRICAL EQUIPMENT (INCLUDING BUT NOT LIMITED TO SWITCHBOARDS,
PANELBOARDS, TRANSFORMERS, MOTOR CONTROLLERS) FROM THE FLOOR TO A
HEIGHT OF 6’-0” ABOVE THE HEIGHT OF THE EQUIPMENT OR TO THE STRUCTURAL
CEILING, WHICH EVER IS LOWER. THE DEDICATED ELECTRICAL SPACE MUST BE
CLEAR OF ANY PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR EQUIPMENT
FOREIGN TO THE ELECTRICAL INSTALLATION. PLUMBING, HEATING, VENTILATION,
AND AIR-CONDITIONING PIPING, DUCTS, AND EQUIPMENT MUST BE INSTALLED
OUTSIDE THE WIDTH AND DEPTH ZONE. CONTRACTOR SHALL MAKE SURE NO
PIPING OR DUCT WORK IS INSTALLED ABOVE THE ELECTRICAL EQUIPMENT.
COORDINATE THESE REQUIREMENTS WITH ALL OTHER TRADES PRIOR TO
INSTALLATION.
F THE NUMBER OF WIRES INDICATED ON DRAWINGS, IN PANEL SCHEDULES AND
CIRCUIT SIZING SCHEDULES APPLIES TO CURRENT CARRYING CONDUCTORS
INCLUDING NEUTRALS. IN ADDITION TO THE NUMBER OF WIRES INDICATED,
PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR SIZED AS SCHEDULED OR
SIZED BY NEC 250.
G PROVIDE NO MORE THAN THREE PHASE CONDUCTORS (PLUS NEUTRALS AND
GROUND) PER CONDUIT.
H PROVIDE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS FOR ALL 120V AND
277V CIRCUITS. DO NOT SHARE NEUTRALS.
I UNLESS OTHERWISE NOTED, PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH
HAVE AN AMPACITY EQUAL TO OR GREATER THAN THE CIRCUIT OVERCURRENT
PROTECTIVE DEVICE RATING SERVING THE CIRCUIT. REFER TO CIRCUIT SIZING
SCHEDULE FOR SIZES OF FEEDERS AND BRANCH CIRCUITS.
J WHEN PROVIDING NEW AND/OR REPLACING EXISTING BREAKERS IN EXISTING
AND/OR OWNER PROVIDED EQUIPMENT, FIELD SURVEY EQUIPMENT AND MATCH
LARGEST AIC VALUE BASED ON EXISTING BREAKERS IN EQUIPMENT.
K MAKE ALL FINAL CONNECTIONS BETWEEN MOTOR CONTROLLERS, DISCONNECT
SWITCHES, ETC. AND EQUIPMENT BEING SERVED BY FEEDER OR BRANCH
CURRENT.
L WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT
PHONES) ARE INDICATED, PROVIDE MULTI-GANG OUTLET BOXES WITH GANG
BARRIERS AND A COMMON FACEPLATE FOR SIMILIAR DEVICES.
M WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING
HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS
FOUR INCHES BETWEEN ADJACENT VERTICAL EDGES.
N WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE
LOCATED IN THE SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR
CENTERLINES.
O CONNECT ALL LIGHTING FIXTURES WITHIN ROOM TO INDICATED SWITCH AND
BRANCH CIRCUIT, U.O.N.
P ALL EXIT FIXTURES AND FIXTURES INDICATED WITH "NL" SHALL BE UNSWITCHED.
Q WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR, MOUNT AS FOLLOWS: IF THE
DISTANCE BETWEEN THE TOP OF THE DOOR FRAME AND THE CEILING IS 24
INCHES OR LESS, CENTER THE EXIT SIGN BETWEEN TOP OF DOOR FRAME AND
CEILING. OTHERWISE, MOUNT BOTTOM OF EXIT SIGN 6 INCHES ABOVE TOP OF
DOOR FRAME. MOUNT OTHER WALL MOUNTED EXIT SIGNS LOCATED WITHIN THE
SAME AREA AT THE SAME HEIGHT.
R COORDINATE LOCATION OF CEILING MOUNTED FIRE ALARM DEVICES WITH
OTHER EQUIPMENT TO AVOID INTERFERENCE. LOCATE FIRE ALARM DEVICES AS
NEAR TO LOCATION INDICATED WHILE AVOIDING INTERFERENCES AND
MAINTAINING CODE REQUIREMENTS.
GENERAL FEEDER & BRANCH CIRCUIT
SCHEDULE NOTES (COPPER)
# NOTES
A PROVIDE BOTH NEW CONDUCTORS AND NEW CONDUIT FOR ALL FEEDERS AND
BRANCH CIRCUITS INDICATED WITH A 'FEEDER/BRANCH CIRCUIT LABEL'. DO NOT
REUSE ANY EXISTING CONDUCTORS AND/OR CONDUIT UNLESS SPECIFICALLY
NOTED ON DRAWINGS, ONE-LINE DIAGRAM, ETC.
B REFER TO SPECIFICATIONS FOR MINIMUM CONDUCTOR AND CONDUIT SIZES.
C REFER TO SPECIFICATIONS FOR TYPE OF RACEWAY.
D FOR ALL NEW AND EXISTING CONDUIT INSTALLATIONS, REFER TO THE NEC FOR
CONDUIT AND TUBING FILL TABLES. IN LOCATIONS WHERE EXISTING CONDUIT IS
PERMITTED TO BE REUSED, IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY
THE EXISTING CONDUIT SIZE MEETS THE NEC CONDUIT AND FILL TABLES PRIOR
TO BID. IF THE CONDUIT DOES NOT MEET THE NEC FILL TABLES, REPLACE THE
CONDUIT FOR THE FEEDER AND/OR BRANCH CIRCUIT IN IT'S ENTIRETY TO
SATISFY THE NEC CONDUIT AND TUBING FILL TABLES.
E ANY CONDUIT AND/OR CONDUCTOR SIZE DEVIATIONS FROM THIS SCHEDULE, OR
INDICATED ON DRAWINGS, MUST BE APPROVED BY THE ENGINEER IN WRITING.
F PROVIDE ROOF SUPPORTS FOR ALL CONDUITS ROUTED ON THE ROOF AND
SUPPORT A MINIMUM OF 1” ABOVE ROOF. ADJUST CONDUCTOR AND CONDUIT
SIZE AS REQUIRED PER NEC AMBIENT TEMPERATURE ADJUSTMENT TABLES.
SUBMIT TO ENGINEER FOR APPROVAL.
G ROOF PENETRATIONS: PROVIDE ROOF PENETRATIONS PER MANUFACTURER'S
RECOMMENDED DETAIL AND VERIFY PENETRATIONS DO NOT VOID ROOF'S
WARRANTY.
H VERIFY LUG SIZES AND QUANTITIES, INCLUDING BUT NOT LIMITED TO, IN
PANELBOARDS, CIRCUIT BREAKERS, MECHANICAL EQUIPMENT, PLUMBING
EQUIPMENT, ELECTRICAL EQUIPMENT, ETC. PRIOR TO PROVIDING CONDUIT
AND/OR CONDUCTORS. MODIFY LUGS AS REQUIRED FOR LARGER FEEDERS
REQUIRED FOR VOLTAGE DROP. COORDINATE FINAL LUG CAPACITY OF ALL
EQUIPMENT BASED ON FINAL SUBMITTALS PRIOR TO PROVIDING CONDUIT
AND/OR CONDUCTORS. NO EXCEPTIONS WILL BE MADE TO ACCOMMODATE
CONDUIT AND/OR CONDUCTORS INSTALLED PRIOR TO COORDINATION WITH
FINAL EQUIPMENT AND PRIOR TO NOTIFYING ENGINEER OF RECORD.
ATS
EX. FCU-1
EX. VRF FCU
EX. HRB-1
EX. FCU-1
EX. FCU-2
EX. FCU
MDF
003A
RR
STORAGE
006A
RR
OFFICE
EMERGENCY OPERATIONS
PLANNING
OFFICE
OFFICE
OFFICE
STAIR 1
ST-1-0
RISER
EX. FCU-4
EX. FCU-4
EX. FCU-4
EX. EF-4
EX. EH-3
EX. EH-3
EX. HRB-1
EX. FCU-3
EX. FCU-4
EX. HRB-1
EX. FCU-4
EX. FCU-5
EX. HRB-1
EX. SSCU-TECH
EX. RH-1 EX. RH-2
EX. RH-3
EX. RH-4CUSTODIAL
FITNESS ROOM
ADA RR
RR
GEAR ROOM
CAPTAIN'S OFFICE
OFFICE STORAGE
STOR.
STAIR 2.1
ST 2-1
APPARATUS BAY
RR
RISER
EMS STORAGE
AIR COMPRESSOR
STAIR 1
ST 1-1
TOOL ROOM
CORRIDOR
OFFICE / WATCHROOM
VESTIBULE
ELEC
EX. EF-2
EX. EH-3
1L2-S1
1L2-S2
1L1
MDP
EX. HP-1C
EX. HP-1B
EX. HP-1A
DORM
213A
BATH
213B
LOCKER
DORM
214A
DORM
215A
LOCKER
LOCKER
BATH
214B
BATH
215B
LAUNDRY
SUPPLY CLOSET
STORAGE
MECH.
JANITOR
PANTRY
PANTRY
PANTRY
BATH
220BLOCKER
LOCKER
LOCKER
LOCKER
LOCKER
BATH
217B
BATH
216B
BATH
219B
BATH
218B
DORM
216A
DORM
217A
DORM
218A
DORM
219A
DORM
220A
KITCHEN
STAIR 1
ST 1-2
STAIR 2
ST 2-2
DAY ROOM
DINING
CORRIDOR
EX. FCU-1 EX. FCU-1
1 1
EX. FCU-1
EX. FCU-1
EX. FCU-1
EX. HRB-1
EX. FCU-1
EX. HRB-1
1 1
2L1-S2 2L1-S1
EX. FCU-1
EX. FCU-5
EX. HBR-1
EX. FCU-6
EX. DOAS-1
EX. MAU-1
1 EX. FCU-4
EX. FCU-4
EX. FCU-4 EX. FCU-4
EX. HRB-1
EX. EF-1
EX. EF-3
EX. FCU-1
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:4
:5
A
M
C
R e v it L o c a l\
-0
.4
H B ld g
E
\2
-0
.4
H
B ld g
E s m a th is .r v t
2026-028.44H
10.28.2026
DEMOLITION PLAN
ED101
SACM
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
E D
D
E M
O L
IT
IO
N
P L A
N
GENERAL DEMOLITION NOTES
# NOTES
A REFER TO SHEETS E-001 AND E-002 FOR ADDITIONAL INFORMATION.
B THIS DRAWING REPRESENTS INFORMATION OBTAINED FROM ORIGINAL
CONTRACT DRAWINGS AND FIELD SURVEY. VERIFY BY ON-SITE OBSERVATION
THE EXTENT OF WORK PRIOR TO SUBMISSION OF BID.
C THE OWNER HOLDS RIGHT OF FIRST REFUSAL FOR ALL DEMOLISHED ELECTRICAL
EQUIPMENT.
D ALL ELECTRICAL ITEMS SHOWN WITH LIGHT LINEWORK ARE EXISTING TO REMAIN.
E REMOVE ALL ELECTRICAL ITEMS SHOWN WITH BOLD/DASHED LINEWORK
COMPLETE, UNLESS NOTED OTHERWISE.
F COORDINATE AND DISCONNECT ALL CIVIL, ARCHITECTURAL, MECHANICAL,
PLUMBING, AND TELECOMMUNICATION EQUIPMENT AS NOTED FOR REMOVAL BY
OTHERS. REMOVE ALL ASSOCIATED ELECTRICAL EQUIPMENT, RACEWAYS,
CONDUCTORS, ETC. SERVING THE EQUIPMENT.
G PROVIDE ALL CUTTING AND PATCHING AS REQUIRED FOR THE REMOVAL OF
EXISTING ELECTRICAL EQUIPMENT. REFER TO SPECIFICATIONS.
H PROVIDE A BLANK COVERPLATE FOR ALL EXISTING WALL OPENINGS WHERE
ELECTRICAL EQUIPMENT HAS BEEN REMOVED AND NOT REPLACED. IN AREAS
RECEIVING NEW WALL TREATMENTS, PATCH THE EXISTING OPENING.
I REFER TO A, M, P, AND T-SERIES DRAWINGS FOR AREAS WITH ABOVE CEILING
WORK AND/OR CEILING REMOVAL. TEMPORARILY SUPPORT ALL ELECTRICAL
DEVICES, FIXTURES, ETC. AS REQUIRED. RE-INSTALL ELECTRICAL ITEMS
FOLLOWING THE COMPLETION OF WORK IN THE NEW OR EXISTING CEILINGS.
J REMOVE SYSTEMS AND EQUIPMENT MADE OBSOLETE BY THIS PROJECT. THIS
INCLUDES, BUT IS NOT LIMITED TO, CONDUIT, RACEWAYS, WIREWAYS,
CONDUCTORS, JUNCTION BOXES, WIRING DEVICES, LIGHT FIXTURES, PULL
BOXES, DISCONNECTS, MOTOR STARTERS, CONTACTORS, ETC.
K REMOVE ALL DEBRIS FROM SITE AND LEGALLY DISPOSE OF SAME.
L REMOVE ALL EXISTING EQUIPMENT PADS MADE OBSOLETE. CUT OFF BELOW
FLOOR SLAB AND FILL WITH CONCRETE ALL CONDUITS WHICH ARE ABANDONED
IN OR BELOW THE FLOOR SLAB. PATCH FLOOR TO MATCH EXISTING CONDITIONS.
M REMOVE ALL EXISTING ABOVE SLAB CONDUITS MADE OBSOLETE. CUT OFF
BELOW FLOOR SLAB AND FILL WITH CONCRETE ALL CONDUITS WHICH ARE
ABANDONED IN OR BELOW THE FLOOR SLAB. PATCH FLOOR TO MATCH EXISTING
CONDITIONS.
N COORDINATE ALL EXISTING CEILING-MOUNTED DEVICES (INCLUDING POWER,
FIRE ALARM, LIGHT FIXTURES, AND LIGHTING CONTROLS) WITH NEW WORK BY
ALL DIVISIONS. TEMPORARILY SUPPORT, OR REMOVE AND REINSTALL, DEVICES
AS REQUIRED TO ACCOMMODATE NEW WORK.
DEMOLITION PLAN NOTES
NOT ALL NOTES APPLY TO EVERY SHEET.
# NOTES
1 DISCONNECT AND REMOVE EXISTING ELECTRICAL CONNECTIONS TO
DEMOLISHED MECHANICAL EQUIPMENT COMPLETE. INCLUDING, BUT NOT LIMITED
TO, RACEWAYS, ABANDONED HANGERS, SUPPORTS, JUNCTION BOXES,
CONDUCTORS, DISCONNECTS/STARTERS, DUCT DETECTORS, ETC.
1/8" = 1'-0" 5A
BASEMENT DEMOLITION PLAN
1/8" = 1'-0" 5D
MEZZANINE DEMOLITION PLAN
1/8" = 1'-0" 2C
FIRST FLOOR DEMOLITION PLAN
1/8" = 1'-0" 2A
SECOND FLOOR DEMOLITION PLAN
J J
J
J
J
J
ATS
J
J
J
MDF
003A
RR
STORAGE
006A
RR
OFFICE
EMERGENCY OPERATIONS
PLANNING
OFFICE
FACU
SS-1
RISER
CUSTODIAL
FITNESS ROOM
ADA RR
RR
GEAR ROOM
CAPTAIN'S OFFICE
OFFICE STORAGE
STOR.
STAIR 2.1
ST 2-1
APPARATUS BAY
RR
RISER
EMS STORAGE
AIR COMPRESSOR
STAIR 1
ST 1-1
TOOL ROOM
CORRIDOR
OFFICE / WATCHROOM
VESTIBULE
ELEC
MDPATS
1L1
1L2-S1
1L2-S2
ELEC
EP101
1A
1L2-S2-66
DORM
213A
BATH
213B
LOCKER
DORM
214A
DORM
215A
LOCKER
LOCKER
BATH
214B
BATH
215B
LAUNDRY
SUPPLY CLOSET
STORAGE
MECH.
JANITOR
PANTRY
PANTRY
PANTRY
BATH
220BLOCKER
LOCKER
LOCKER
LOCKER
LOCKER
BATH
217B
BATH
216B
BATH
219B
BATH
218B
DORM
216A
DORM
217A
DORM
218A
DORM
219A
DORM
220A
KITCHEN
STAIR 1
ST 1-2
STAIR 2
ST 2-2
DAY ROOM
DINING
CORRIDOR
2L1-S2 2L1-S1
RTU-2
SSCU-1
EF-5
EX. EF-1
EX. EF-3EX. MAU-1
RTU-1
DS201
MDP
F70
F70
DS203
DS202
MDP
F150F150
2L1-S2-(77,79) F30
F30
2L1-S2-61
GFCI/WP
2L1-S2-61
GFCI/WP
2L1-S2-63
2L1-S2-63
2L1-S2-65
MS202
F20
F20
F20
2L1-S2-67 F20
2L1-S2-69 F20
MS201
1L1
1L2-S2
1L2-S1
MDP
P-1
B-1
ELEC
1L2-S2-64
F20
MDP
F20
F20
1L2-S2-46
FIRST FLOOR
EXISTING MDP
208Y/120V
600A - MLO
3Ø, 4W
AIC: 65KA
EATON PRL3A
1. INTERNAL SPD
2. OL1: 200A-3P
3. 1L1: 200A-3P
4. 1L2: 200A-3P
5. 2L1: 200A-3P
6. HP-1-3: 60A-3P
7. NEW RTU-1: 70A-3P
A. DEMOLISHED: DOAS-1: 60A-3P
8. HP-1-2: 80A-3P
9. HP-1-1: 80A-3P
10. (6) 1P SPACES
11. NEW PUMP P-1: 20A-3P
A. DEMOLISHED: (3) SPACES
12. (3) 1P SPACES
13. NEW RTU-2: 150A-3P
1. DISCONNECT AND REMOVE EXISTING 60A-3P BREAKER FOR
DEMOLISHED 'DOAS-1' UNIT. REPLACE WITH NEW 70A-3P, 65kA
BREAKER TO SERVE RTU-1.
2. PROVIDE NEW 20A-3P, 65kA CIRCUIT BREAKER FOR PUMP P-1.
PROVIDE BREAKER IN THE 'SPACE' SECTION AT THE BOTTOM OF THE
PANEL. PROVIDE NEW COVER PLATES AS REQUIRED.
3. PROVIDE NEW 150A-3P, 65kA CIRCUIT BREAKER FOR RTU-2. PROVIDE
BREAKER IN THE 'SPACE' SECTION AT THE BOTTOM OF THE PANEL.
PROVIDE NEW COVER PLATES AS REQUIRED.
4. FIELD VERIFY ALL REQUIREMENTS FOR NEW BREAKERS AND
COORDINATE WITH MANUFACTURER PRIOR TO ORDERING AND
INSTALLING BREAKER.
SEISMIC RESTRAINTS REQUIREMENTS
SEISMIC RESTRAINTS SHALL BE PROVIDED FOR ALL
ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE
WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING
CODE AND ASCE-7.
REFERENCE THE STRUCTURAL DRAWINGS FOR SEISMIC
DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE
CALCULATIONS AND A COMPLETE LAYOUT INDICATING THE
LOCATIONS AND DETAILS OF THE PROPOSED SEISMIC
RESTRAINTS FOR REVIEW AND ACCEPTANCE BY THE
ARCHITECT AND ENGINEER. ALL MATERIALS SHALL BE BY A
SINGLE MANUFACTURER.
THE SUBMITTAL SHALL BE STAMPED AND SIGNED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF
INDIANA.
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:4
:5
A
M
C
R e v it L o c a l\
-0
.4
H B ld g
E
\2
-0
.4
H
B ld g
E s m a th is .r v t
2026-028.44H
10.28.2026
POWER PLAN
EP101
SACM
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
E P
P
O W
E R
P L A
N
GENERAL POWER NOTES
# NOTES
A REFER TO SHEETS E-001 AND E-002 FOR ADDITIONAL INFORMATION.
B COORDINATE ALL EXISTING CEILING-MOUNTED DEVICES (INCLUDING POWER,
FIRE ALARM, LIGHT FIXTURES, AND LIGHTING CONTROLS) WITH NEW WORK BY
ALL DIVISIONS. TEMPORARILY SUPPORT, OR REMOVE AND REINSTALL, DEVICES
AS REQUIRED TO ACCOMMODATE NEW WORK.
POWER PLAN NOTES
NOT ALL NOTES APPLY TO EVERY SHEET.
# NOTES
1 REFER TO POWER PLANS AND EQUIPMENT SCHEDULES FOR MOTOR STARTER
SIZE, LOCATION, AND WIRE SIZE SERVING EXHAUST FAN. CONNECT TO
MANUFACTURER PROVIDED DISCONNECT SWITCH IN EXHAUST FAN.
2 DISCONNECT SWITCH FOR OUTDOOR SPLIT SYSTEM. PROVIDE
INTER-CONNECTION BETWEEN OUTDOOR AND INDOOR MECHANICAL UNITS
COMPLETE. REFER TO POWER PLANS, MECHANICAL PLANS, EQUIPMENT
SCHEDULES, DETAILS, ETC. FOR MORE INFORMATION AND LOCATION OF
INTERIOR MECHANICAL UNIT.
3 CIRCUIT CONNECTION FOR MANUFACTURER PROVIDED MECHANICAL EQUIPMENT
RECEPTACLE(S). COORDINATE EXACT LOCATION WITH MANUFACTURER.
CONNECT COMPLETE. REPLACE SPARE 20A-1P WITH A 15A-1P BREAKER IN
PANELBOARD INDICATED. MATCH HIGHEST AIC RATED BREAKER IN EXISTING
PANELBOARD.
4 MOTOR STARTER FOR EXHAUST FAN. CONNECT TO MANUFACTURER PROVIDED
DISCONNECT IN EXHAUST FAN COMPLETE. CONNECT TO EXISITNG SPARE 20A-1P
CIRCUIT BREAKER IN PANELBOARD AS INDICATED.
5 DISCONNECT AND REMOVE EXISTING SPARE 20A-1P CIRCUIT BREAKERS.
REPLACE WITH NEW 30A-2P CIRCUIT BREAKER IN PANELBOARD AS INDICATED.
EXISTING PANELBOARD IS AN EATON PRL1A, 208Y/120V, 3Ø, 4W. FIELD VERIFY
AND MATCH HIGHEST AIC RATING IN PANELBOARD OR PROVIDE 65KA RATED
BREAKER.
6 CIRCUIT FOR TEMPERATURE CONTROL PANEL. CONNECT TO SPARE 20A-1P
CIRCUIT IN EXISTING PANELBOARD AS INDICATED.
7 PROVIDE NEW 15A-1P, SHUNT TRIP CIRCUIT BREAKER IN PANELBOARD AS
INDICATED. EXISTING PANELBOARD IS AN EATON PRL1A, 208Y/120V, 3Ø, 4W. FIELD
VERIFY AND MATCH HIGHEST AIC RATING IN PANELBOARD OR PROVIDE 65KA
RATED BREAKER.
8 EMERGENCY STOP BUTTON FOR BOILER(S). REFER TO SCHEMATICS FOR
ADDITIONAL INFORMATION. CONNECT TO CIRCUIT INDICATED AND SHUNT TRIP
BREAKERS SERVING NEW BOILER(S). PROVIDE NEW 20A-1P, CIRCUIT BREAKER IN
PANELBOARD AS INDICATED. EXISTING PANELBOARD IS AN EATON PRL1A,
208Y/120V, 3Ø, 4W. FIELD VERIFY AND MATCH HIGHEST AIC RATING IN
PANELBOARD OR PROVIDE 65KA RATED BREAKER.
9 CONNECT TO PUMP CONTROLLER. REFER TO RISER DIAGRAM FOR MORE
INFORMATION.
10 REMOVE AND REINSTALL EXISTING CEILING MOUNTED DEVICES AND LIGHT
FIXTURES IN NEW CEILING GRID TO ACCOMODATE ARCHITECTURAL CHANGES.
11 SPLIT SYSTEM UNIT IS POWERED BY OUTDOOR CONDENSING UNIT LOCATED ON
ROOF. PROVIDE WIRING FROM CONDENSING UNIT AND CONNECT TO SPLIT
SYSTEM UNIT COMPLETE. REFER TO ROOF PLANS, DETAILS, EQUIPMENT
SCHEDULES, M-SERIES DRAWINGS, ETC. FOR MORE INFORMATION AND
LOCATION OF OUTDOOR UNIT.
1/8" = 1'-0" 5A
BASEMENT POWER PLAN
1/8" = 1'-0" 5D
MEZZANINE POWER PLAN
1/8" = 1'-0" 2C
FIRST FLOOR POWER PLAN
1/8" = 1'-0" 2A
SECOND FLOOR POWER PLAN
1/4" = 1'-0" 1A
ENLARGED POWER PLAN - ELEC 115
NOT TO SCALE
1B
MDP ELEVATION
R D
R D
MDF
003A
RR
STORAGE
006A
RR
OFFICE
EMERGENCY OPERATIONS
PLANNING
OFFICE
OFFICE
OFFICE
STAIR 1
ST-1-0
FACU
RISER
1L2-S1
1L2-S2
1L1
ATS MDP
CUSTODIAL
FITNESS ROOM
ADA RR
RR
GEAR ROOM
CAPTAIN'S OFFICE
OFFICE STORAGE
STOR.
STAIR 2.1
ST 2-1
APPARATUS BAY
RR
RISER
EMS STORAGE
AIR COMPRESSOR
STAIR 1
ST 1-1
TOOL ROOM
CORRIDOR
OFFICE / WATCHROOM
VESTIBULE
ELEC
RTU-2
RTU-1
RTU-2
DORM
213A
BATH
213B
LOCKER
DORM
214A
DORM
215A
LOCKER
LOCKER
BATH
214B
BATH
215B
LAUNDRY
SUPPLY CLOSET
STORAGE
MECH.
JANITOR
PANTRY
PANTRY
PANTRY
BATH
220BLOCKER
LOCKER
LOCKER
LOCKER
LOCKER
BATH
217B
BATH
216B
BATH
219B
BATH
218B
DORM
216A
DORM
217A
DORM
218A
DORM
219A
DORM
220A
KITCHEN
STAIR 1
ST 1-2
STAIR 2
ST 2-2
DAY ROOM
DINING
CORRIDOR
2L1-S2
2L1-S1
RTU-1
SEISMIC RESTRAINTS REQUIREMENTS
SEISMIC RESTRAINTS SHALL BE PROVIDED FOR ALL
ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE
WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING
CODE AND ASCE-7.
REFERENCE THE STRUCTURAL DRAWINGS FOR SEISMIC
DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE
CALCULATIONS AND A COMPLETE LAYOUT INDICATING THE
LOCATIONS AND DETAILS OF THE PROPOSED SEISMIC
RESTRAINTS FOR REVIEW AND ACCEPTANCE BY THE
ARCHITECT AND ENGINEER. ALL MATERIALS SHALL BE BY A
SINGLE MANUFACTURER.
THE SUBMITTAL SHALL BE STAMPED AND SIGNED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF
INDIANA.
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:4
:5
A
M
C
R e v it L o c a l\
-0
.4
H B ld g
E
\2
-0
.4
H
B ld g
E s m a th is .r v t
2026-028.44H
10.28.2026
FIRE ALARM PLAN
EF101
SACM
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
E F
F
IR
E A
L A
R M
P L A
N
GENERAL FIRE ALARM NOTES
# NOTES
A REFER TO SHEETS E-001 AND E-002 FOR ADDITIONAL INFORMATION.
B COORDINATE ALL EXISTING CEILING-MOUNTED DEVICES (INCLUDING POWER,
FIRE ALARM, LIGHT FIXTURES, AND LIGHTING CONTROLS) WITH NEW WORK BY
ALL DIVISIONS. TEMPORARILY SUPPORT, OR REMOVE AND REINSTALL, DEVICES
AS REQUIRED TO ACCOMMODATE NEW WORK.
FIRE ALARM PLAN NOTES
NOT ALL NOTES APPLY TO EVERY SHEET.
# NOTES
1/8" = 1'-0" 5A
BASEMENT FIRE ALARM PLAN
1/8" = 1'-0" 5D
MEZZANINE FIRE ALARM PLAN
1/8" = 1'-0" 2A
FIRST FLOOR FIRE ALARM PLAN
1/8" = 1'-0" 2C
SECOND FLOOR FIRE ALARM PLAN
EF-6
EX. KEF-1
REFER TO
SECOND FLOOR
PLANS FOR
THIS AREA OF
ROOF
SEISMIC RESTRAINTS REQUIREMENTS
SEISMIC RESTRAINTS SHALL BE PROVIDED FOR ALL
ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE
WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING
CODE AND ASCE-7.
REFERENCE THE STRUCTURAL DRAWINGS FOR SEISMIC
DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE
CALCULATIONS AND A COMPLETE LAYOUT INDICATING THE
LOCATIONS AND DETAILS OF THE PROPOSED SEISMIC
RESTRAINTS FOR REVIEW AND ACCEPTANCE BY THE
ARCHITECT AND ENGINEER. ALL MATERIALS SHALL BE BY A
SINGLE MANUFACTURER.
THE SUBMITTAL SHALL BE STAMPED AND SIGNED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF
INDIANA.
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:4
:5
A
M
C
R e v it L o c a l\
-0
.4
H B ld g
E
\2
-0
.4
H
B ld g
E s m a th is .r v t
2026-028.44H
10.28.2026
ROOF PLAN
ER101
SACM
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
E R
R O
O F
P L A
N
GENERAL ROOF NOTES
# NOTES
A REFER TO SHEETS E-001 AND E-002 FOR ADDITIONAL INFORMATION.
ROOF PLAN NOTES
NOT ALL NOTES APPLY TO EVERY SHEET.
# NOTES
1 REFER TO POWER PLANS AND EQUIPMENT SCHEDULES FOR MOTOR STARTER
SIZE, LOCATION, AND WIRE SIZE SERVING EXHAUST FAN. CONNECT TO
MANUFACTURER PROVIDED DISCONNECT SWITCH IN EXHAUST FAN.
1/8" = 1'-0" 2A
ROOF PLAN
GNP
GNP
G
P
N
CONDUIT
WIRE NUT
GROUND SCREW
#10-32 X 5/8" GREEN
HEX/SLOTTED/PHILIPS
HEAD WASHER FACE
TAPPED HOLE IN BOX
INSULATED EYE TERMINAL
OUTLET BOXDEVICE YOKE
GROUNDING CONNECTIONS
SHALL BE CONTINUOUS SUCH
THAT REMOVAL OF DEVICE WILL
NOT INTERFERE WITH
CONDUCTOR CONTINUITY
BONDING JUMPER
COMBINATION CONDUIT
HANGER CLAMP
STEEL STRUCTURE
FLAT PLATE FITTING WITH
NUT AND WASHER. NUT
AND WASHER ON
BOTTOM.
THREADED ROD
SIZE AS REQUIRED
BEAM CLAMP ON TOP
OF CHORD OF JOIST
STRUT CHANNEL
CONDUIT CLAMP SIZE AS
REQUIRED (TYP.)
CONDUIT CLAMP,
SIZE AS REQUIRED
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
REFER TO PLANS
FOR QUANTITY &
SIZE OF CONDUITS
3/8" MIN GALVANIZED
THREADED ROD, TYP.
LOCKING
SQUARE WASHER
& LOCKNUT
UV-INHIBITED POLYCARBONATE
OR HIGH-DENSITY
POLYPROPYLENE PLASTIC
BLOCK, LENGTH AS REQUIRED
CORE DRILLED HOLE
EXISTING EXTERIOR
FOUNDATION / WALL
PRESSURE PLATE
STAINLESS STEEL BOLT
SLEEVE SEAL SYSTEM
CORE DRILLED HOLE
EXISTING EXTERIOR
FOUNDATION / WALL
PRESSURE PLATE
STAINLESS STEEL BOLT
SLEEVE SEAL SYSTEM
SIDE VIEW FRONT VIEW
HOT DIPPED GALVANIZED OR
STAINLESS STEEL STRUT -
TYPICAL
STRUT POST BASE
"T" FITTING FOR HORIZONTAL
STRUT CHANNEL - TYPICAL
HORIZONTAL STRUT CHANNEL
4-HOLE 90° "L"
BRACKET ATTACHED
TO FLOOR AND
STRUT CHANNEL
ANGLED STRUT
CHANNEL
ADJUSTABLE
CHANNEL BRACE
NOTES:
1. THIS DETAIL INDICATES INTENT ONLY.
2. PROVIDE ALL LENGTHS, HEIGHTS, CHANNEL SIZE/GAUGE/QUANTITIES, ETC.
AS STRUCTURALLY REQUIRED FOR EACH PROJECT SPECIFIC INSTALLATION.
3. ATTACH FRAME SECURELY TO FLOOR AND STRUCTURE ABOVE.
4. PROVIDE FASTENERS/BOLTS/SCREWS IN ALL HOLES INTENDED FOR
ATTACHING FITTINGS TO FLOOR, STRUCTURE, STRUT ETC.
5. INSTALL PANELS, DISCONNECTS, MOTOR CONTROLLERS, CONDUIT, ETC. AS
INDICATED ON THE DRAWINGS OR AS REQUIRED.
PAINT CUT ENDS OF STRUT
CHANNELS WITH COLD
GALVANIZING COMPOUND
90 DEGREE FITTING FOR
HORIZONTAL STRUT CHANNEL -
TYPICAL
PROVIDE LENGTHS AND HEIGHTS AS
REQUIRED FOR EQUIPMENT TO BE
SUPPORTED
FINISHED FLOOR
NOT TO SCALE
1A
WIRING DEVICE GROUNDING AND BONDING
DETAIL
NOT TO SCALE
2B
CONDUIT 2" AND SMALLER SUPPORT
(STEEL STRUCURE) DETAIL
NOT TO SCALE
1D
CONDUIT 2-1/2" AND LARGER SUPPORT
(STEEL STRUCTURE) DETAIL
NOT TO SCALE
2A
ROOF CONDUIT SUPPORT DETAIL
NOT TO SCALE
1B
SLEEVE SEAL SYSTEM WITH SLEEVE
DETAIL
NOT TO SCALE
4A
TYPICAL FLOOR-MOUNTED STRUT FRAME
DETAIL
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:4
:5
A
M
C
R e v it L o c a l\
-0
.4
H B ld g
E
\2
-0
.4
H
B ld g
E s m a th is .r v t
2026-028.44H
10.28.2026
GENERAL DETAILS
E-501
SACM
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
E -5
G E
N E
R A
L D
E T
A
IL
S
BASEMENT FLOOR
F R
F S
M
V H
1ST FLOOR
2ND FLOOR
EXISTING
FIRE ALARM
CONTROL
PANEL BY
HONEYWELL
EXISTING
REMOTE
ANNUNCIATOR
PANEL
EXISTING
FIRE ALARM
NAC PANEL
F R
F S
M
V H
EXISTING
FIRE ALARM
NAC PANEL
V H
EXISTING
FIRE ALARM
NAC PANEL
F
R F
S M
HVAC UNIT
MOTOR STARTER
DETECTOR WITH
RELAY BASE
RI RI
D R
D S
NOTES:
1. REFER TO SITE AND FLOOR PLANS FOR DEVICE LOCATIONS AND
QUANTITIES.
2. ALL VISUAL DEVICES AND HORN/VISUALS TO BE SYNCHRONIZED
FLASH.
3. UPGRADE / EXPAND / ADD EQUIPMENT TO EXISTING FIRE ALARM
SYSTEM AS REQUIRED BY SCOPE INDICATED ON DRAWINGS.
4. FIELD VERIFY ANY CONNECTIONS INTO EXISTING SYSTEM.
5. EXISTING NAC PANELS SHOWN ARE FOR SCHEMATIC PURPOSES
ONLY AND MAY NOT EXIST ON EACH FLOOR AS INDICATED.
6. REFER TO SPECIFICATION SECTION '284621 - ADDRESSABLE FIRE-
ALARM SYSTEMS' FOR REQUIREMENTS.
OUTDOOR
CONDENSING
UNIT
NEMA 3R FUSED DISCONNECT SWITCH.
REFER TO PLANS AND SCHEDULES
FOR ADDITIONAL INFORMATION.
PROVIDE BRANCH CIRCUIT HOME RUN
TO PANELBOARD INDICATED ON
PLANS. PROVIDE ALL REQUIRED
CONNECTIONS BETWEEN DISCONNECT
SWITCH AND CONDENSING UNIT.
INDOOR DUCTLESS
FAN COIL
(1) 3/4"C FOR POWER WIRING. REFER
TO MANUFACTURER'S REQUIREMENTS
FOR WIRING SIZE.
NOTES:
1. COORDINATE FINAL MANUFACTURER ELECTRICAL REQUIREMENTS WITH
EQUIPMENT PROVIDED BY DIVISION 23, INCLUDING, BUT NOT LIMITED TO,
OVERCURRENT PROTECTION AND CONDUCTOR SIZES.
2. PROVIDE CIRCUIT BREAKER LOCKOUT DEVICE IN PANELBOARD SERVING
THE OUTDOOR CONDENSING UNIT.
(1) 3/4"C FOR COMMUNICATION WIRING.
REFER TO MANUFACTURER'S
REQUIREMENTS FOR WIRING SIZE.
PROVIDE EQUIPMENT IDENTIFICATION LABEL INDICATING
OUTDOOR CONDENSING UNIT SERVING THE INDOOR
DUCTLESS FAN COIL AND THE BRANCH CIRCUIT SERVING THE
OUTDOOR CONDENSING UNIT.
NOTES:
1. PUSHING THE BOILER EMERGENCY POWER-OFF BUTTON WILL PROVIDE 120
VOLTS TO EACH CIRCUIT BREAKER SHUNT TRIP COIL AND TRIP THE CIRCUIT
BREAKER SERVINGS THE BURNER CONTROL POWER FOR ALL BOILERS.
2. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT, AND BOILER AND
EMERGENCY POWER-OFF PUSHBUTTON QUANTITY.
LINE
N
SHUNT TRIP
CIRCUIT BREAKER
NO
SHUNT TRIP
CIRCUIT BREAKER
SHUNT TRIP
CIRCUIT BREAKER
BOILER EPO
BUTTON(S)
REFER TO FLOOR PLAN FOR BOILER QUANTITY
EMERGENCY
POWER OFF
LIFT HERE
PUSH
YELLOW POLYCARBONATE
HOUSING
BLACK LETTERS
RED 2" DIAMETER MUSHROOM
PUSHBUTTON (TURN TO RESET)
HINGED, CLEAR
POLYCARBONATE SHIELD
BOILER
EMERGENCY
POWER-OFF
PUSHBUTTON
SIZE AS REQUIRED
LABEL WITH YELLOW
BACKGROUND WITH 1/2"
BLACK LETTERS
HINGE
NOTES:
1. INSTALL BOILER EMERGENCY POWER OFF (EPO) BUTTON AT 3'-10"
ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.
2. FOR USE IN MECHANICAL BOILER ROOMS.
3. EMERGENCY POWER OFF (EPO) PUSHBUTTON: SAFETY
TECHNOLOGY INTERNATIONAL (STI) STOPPER STATION, MODEL
SS2241PO.
WHITE LETTERS
ATTACH ENGRAVED LABEL
TO THE WALL ABOVE THE
EMERGENCY POWER OFF
PUSHBUTTON
WIRING SCHEMATIC EPO DETAIL
NO
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:4
:5
A
M
C
R e v it L o c a l\
-0
.4
H B ld g
E
\2
-0
.4
H
B ld g
E s m a th is .r v t
2026-028.44H
10.28.2026
SCHEMATICS &
SCHEDULES
E-601
SACM
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
E -6
S C
H E
M A
T
IC
S
S C
H E
D U
L E
S
262816.1 - ENCLOSED SWITCHES & CIRCUIT BREAKERS SCHEDULE
LABEL
LOCATION
EQUIPMENT
SERVED
EQUIPMENT RATINGS ACCESSORIES
REMARKSNUMBER NAME VOLTAGE POLES AMPERAGE FUSED FUSE SIZE NEMA ENCL
AUX.
CONTACTS
SOLID
NEUTRAL
DS201 RTU-1 240 V 3 100 A Yes 70 A 3R (1) N.O. / N.C. No
DS202 RTU-2 240 V 3 200 A Yes 150 A 3R (1) N.O. / N.C. No
DS203 SSCU-1 240 V 2 30 A Yes 30 A 3R (1) N.O. / N.C. No
262913/262923.1 - ENCLOSED & VARIABLE-FREQUENCY MOTOR CONTROLLERS SCHEDULE
LABEL
LOCATION EQUIPMENT
SERVED
EQUIPMENT RATINGS STARTER DISCONNECT SWITCH REMOTE
CAPACITOR REMARKSNUMBER NAME VOLTAGE PHASE HP FLA NEMA ENCL TYPE NEMA SIZE TYPE FUSE SIZE
MS201 210 MECH. EF-5 120 V 1 1/3 HP 7.2 A 1 FHPMC - - - - HORSEPOWER-RATED TOGGLE SWITCH WITH THERMAL OVERLOADS.
MS202 210 MECH. EF-6 120 V 1 1/6 HP 4.4 A 1 FHPMC - - - - HORSEPOWER-RATED TOGGLE SWITCH WITH THERMAL OVERLOADS.
NOT TO SCALE
1A
FIRE ALARM SCHEMATIC
NOT TO SCALE
3A
MINI-SPLIT WIRING SCHEMATIC
NOT TO SCALE
3B
BOILER EMERGENCY POWER-OFF WIRING
SCHEMATIC/DETAIL
| E-001 - SYMBOLS |
| E-002 - GENERAL INFORMATION |
| ED101 - DEMOLITION PLAN |
| EP101 - POWER PLAN |
| EF101 - FIRE ALARM PLAN |
| ER101 - ROOF PLAN |
| E-501 - GENERAL DETAILS |
| E-601 - SCHEMATICS & SCHEDULES |
File details come from the government source that posted it. Updated .