5.9_-_Electrical.pdf

PDF 1009 KB Posted

Attached to
CFD Station #344 HVAC Renovation
Solicitation number
IFB-2026-019
Issued by
Hamilton County, Indiana

About this file

This electrical design document file (5.9_-_Electrical.pdf) supports the City of Carmel Fire Station #44 HVAC Renovation project located at 5032 E Main Street, Carmel, Indiana 46033. The project involves comprehensive replacement of the heating, ventilating, and air conditioning systems, together with related electrical, controls, and ancillary work. The electrical scope includes demolition and removal of existing HVAC-related electrical infrastructure, installation of new power distribution and motor control systems, fire alarm system upgrades and expansions, and associated wiring and conduit work. Sealed bids for the overall project are due on Wednesday, December 16, 2026, at 10:00 a.m., submitted via the City's e-Procurement Portal at https://procurement.opengov.com/portal/carmelin. The project is managed by the Board of Public Works and Safety for the City of Carmel, Hamilton County, Indiana. The electrical documentation establishes detailed specifications for equipment including new circuit breakers, motor starters, disconnect switches, fire alarm devices, receptacles, lighting controls, and support infrastructure, with mounting heights, conductor sizing schedules, and seismic restraint requirements in accordance with the 2009 Indiana Electrical Code (2008 NEC with Amendments) and NFPA 72.

The electrical work requires coordination with mechanical, plumbing, and architectural divisions to ensure proper installation of HVAC-related components, emergency shutdown systems, and building modifications. Specific power requirements include new disconnect switches and circuit breakers serving RTU-1 (70A-3P), RTU-2 (150A-3P), and other mechanical equipment, along with new 20A-3P breaker for a pump controller. The contractor must provide all cutting, patching, grounding connections, seismic restraints, and conduit support systems as detailed in the specifications. Existing electrical equipment has right of first refusal to the owner. All materials and calculations for seismic restraints must be submitted by a professional engineer registered in Indiana and approved by the architect and engineer prior to installation. No pricing information, set-asides, or contract award dates are specified in this technical electrical document.

View the file

Other files

File Type Posted
CFD_Station_#344_HVAC_Renovation.pdf PDF
2026-028.44H_FINAL_TECH_SPECS.pdf PDF
5.4_-_Architecture.pdf PDF
5.7_-_Mechanical.pdf PDF
5.8_-_Plumbing.pdf PDF
5.3_-_Structural.pdf PDF
5.1_-_General.pdf PDF
SAMPLE_OF_MOU_FOR_E-VERIFY.pdf PDF
MAINTENANCE_BOND.pdf PDF
PAYMENT_BOND.pdf PDF
RIGHT_OF_ENTRY.pdf PDF
PERFORMANCE_BOND.pdf PDF
Exhibit_D_E-Verify-1.PDF PDF
SUBCONTRACTORS_LIST.pdf PDF
WORK_DIRECTIVE_CHANGE.pdf PDF
SCREENSHOT_INSTRUCTIONS_-_FOR_BIDS.pdf PDF
SAMPLE_AGREEMENT.pdf PDF
FIELD_ORDER.pdf PDF
NON_COLLUSION_AFFIDAVIT.pdf PDF
CONTRACT_CHANGE_ORDER.pdf PDF
CONTRACT_CHANGE_REQUEST.pdf PDF
REQUEST_FOR_PROPOSAL_CHANGE.pdf PDF
MANUFACTURERS_LIST.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL LEGEND & SYMBOLS

• EXIT SIGN

• DIRECTIONAL ARROWS AS INDICATED

• SHADING INDICATES ILLUMINATED

FACE

• CONNECT TO UNSWITCHED BRANCH

CIRCUIT INDICATED

• END / WALL / CEILING

• LIGHTING FIXTURE

• TYPE AS INDICATED

• POLE MOUNTED LIGHT FIXTURE

• TYPE AS INDICATED

• EMERGENCY BATTERY WALL PACK

• TYPE AS INDICATED

• SHADING INDICATES EMERGENCY

FIXTURE CONNECTED TO BATTERY

INVERTER OR GENERATOR

• CONNECT BATTERY INVERTER TO

UNSWITCHED SOURCE IN ADDITION TO

SWITCHING INDICATED

• TRACK AND TRACK LIGHT FIXTURE

• LIGHT FIXTURE

• TYPE AS INDICATED

• WALL MOUNTED FIXTURE

• TYPE AS INDICATED

LIGHTING

SUBSCRIPTS FOR LIGHTING FIXTURES INDICATE THE FOLLOWING, U.O.N.

NL - NIGHT LIGHT, PANEL SWITCHED, U.O.N.

POWER DISTRIBUTION

• POWER DISTRIBUTION PANELBOARD

• 208Y/120V; 3Ø, 4W

• FLOOR / SURFACE

• BRANCH CIRCUIT PANELBOARD

• 208Y/120V OR 480Y/277V; 3Ø, 4W

• FLUSH / SURFACE

• TERMINAL CABINET, TYPE AS NOTED

ON DRAWINGS

• FLUSH / SURFACE

• DRY- TYPE TRANSFORMER, RATING AS

INDICATED

• HOUSEKEEPING PAD

• SWITCHBOARD W/MAIN CIRCUIT

BREAKER SECTION

• HOUSEKEEPING PAD

• AUTOMATIC TRANSFER SWITCH

• WORKING CLEARANCE ABOUT

ELECTRICAL EQUIPMENT

• ELECTRIC MANHOLE

• GROUND ROD

• MOTOR - "M" INDICATES HORSEPOWER

• HEAVY-DUTY, NON-FUSED DISCONNECT

SWITCH (DS-#)

• HEAVY-DUTY, FUSED DISCONNECT

SWITCH (DS-#)

• COMBINATION MOTOR STARTER AND

DISCONNECT SWITCH (MS-#)

• VARIABLE FREQUENCY DRIVE (MS-#)

• FRACTIONAL HOURSEPOWER MANUAL

CONTROLLER WITH THERMAL

OVERLOADS (MS-#)

• EMERGENCY POWER OFF BUTTON

• SIMPLEX RECEPTACLE

• NEMA 5-20R, 125V, 20A

WIRING DEVICES

SUBSCRIPTS FOR RECEPTACLES, JUNCTION BOXES AND OTHER DEVICES INDICATE THE

FOLLOWING, U.O.N:

F - FLUSH IN FLOOR

GFCI - GROUND FAULT CIRCUIT

INTERRUPTER

H - HORIZONTALLY MOUNTED

IG - ISOLATED GROUND

L - LOCKING TYPE

R - RECESS IN EXISTING WALL (CUT/PATCH)

S - SURFACE MOUNTED

TR - TAMPER RESISTANT

WP - WEATHERPROOF IN-USE

X - MOUNTED IN EXISTING OUTLET BOX

• DUPLEX RECEPTACLE

• NEMA 5-20R,125V, 20A

• DOUBLE DUPLEX (QUADRAPLEX) RECEPTACLE

• NEMA 5-20R,125V, 20A

• DUPLEX RECEPTACLE

• EMERGENCY CIRCUIT

• NEMA 5-20R, 125V, 20A

• DOUBLE DUPLEX (QUADRAPLEX) RECEPTACLE

• EMERGENCY CIRCUIT

• NEMA 5-20R, 125V, 20A

• SPECIAL RECEPTACLE

• NEMA CONFIGURATION AS INDICATED ON

DRAWING

• JUNCTION BOX

• DIRECT CONNECTION TO EQUIPMENT

• PULLBOX

• PROVIDE PULLBOXES INDICATED AS A

MINIMUM

• PROVIDE ADDITIONAL PULLBOXES, SIZED

PER NEC, AS REQUIRED

• FLUSH JUNCTION BOX WITH FURNITURE FEED

ADAPTING CONNECTOR MOUNTED AT 6" A.F.F.

• SURFACE-MOUNTED RACEWAY

• RECEPTACLES IN LOCATIONS INDICATED

• WIREWAY

• WALL MOUNTED U.O.N.

• FLOOR BOX

• SINGLE POLE SWITCH

• THREE-WAY SWITCH

• THREE-WAY SWITCH WITH PILOT LIGHT

• FOUR-WAY SWITCH

• SINGLE POLE SWITCH W/ PILOT LIGHT

• KEY OPERATED SINGLE POLE SWITCH

• KEY OPERATED THREE-WAY SWITCH

M EMH

ATS

J J

FB

M

J

MS-#

• PUSH BUTTON CONTROL STATION

PB

P

3P

K

3K

MCB

D

PANELBOARD NAMING

1 2 A 1

BRANCH PANELBOARDS

SEQUENTIAL PANEL NUMBER

FLOOR PLAN UNIT

A - UNIT A

B - UNIT B

VOLTAGE

2 - 208Y/120V 4 - 480Y/277V

FLOOR NUMBER

B - BASEMENT

1 - 1ST FLOOR

2 - 2ND FLOOR

1 2 A DP 1

POWER DISTRIBUTION PANELBOARDS

SEQUENTIAL PANEL NUMBER

"DISTRIBUTION PANELBOARD"

FLOOR PLAN UNIT

A - UNIT A

B - UNIT B

VOLTAGE

2 - 208Y/120V 4 - 480Y/277V

FLOOR NUMBER

B - BASEMENT

1 - 1ST FLOOR

2 - 2ND FLOOR

LIGHTING CONTROL DEVICES

OS1

O1

• MANUAL CONTROLS & AUTO-ON / AUTO-OFF

• 1000 SQFT COVERAGE

• TWO RELAYS IN POWER PACK

SYMBOL MOUNTING

WALL

DIMMING

TYPE

0-10V

OCCUPANCY

SENSOR TYPE

SWITCH/

BUTTONS

CONTROL DESCRIPTION

• (1) MANUAL SWITCH ON (TO SELECTED LIGHT LEVEL)/OFF

• (1) MANUAL LIGHT LEVEL WITH SLIDER

(1)N/A

D

DS

WALL 0-10V • (1) MANUAL SWITCH ON (TO SELECTED LIGHT LEVEL)/OFF

• (1) MANUAL LIGHT LEVEL WITH SLIDER

• MANUAL ON / AUTO OFF

(1)DUAL TECH.

D

DL

WALL LINE VOLT. • (1) MANUAL SWITCH ON (TO SELECTED LIGHT LEVEL)/OFF

• (1) MANUAL LIGHT LEVEL WITH SLIDER

(1)N/A

WALL N/A DUAL TECH.

(1)

OS2

WALL N/A DUAL TECH.

(1) • (1) MANUAL SWITCH ON/OFF

• MANUAL ON / AUTO OFF

OS3

WALL N/A DUAL TECH.

(2) • (2) MANUAL SWITCH ON/OFF

• MANUAL ON / AUTO OFF

CEILING N/A DUAL TECH. N/A

O2

• AUTO-ON / AUTO-OFF ONLY

• 1000 SQFT COVERAGE

• TWO RELAYS IN POWER PACK

CEILING N/A DUAL TECH. N/A

O3

• MANUAL CONTROLS & AUTO-ON / AUTO-OFF

• 1000 SQFT COVERAGE

• TWO RELAYS IN POWER PACK

• PLUG-LOAD CONTROL OF RECEPTACLES INDICATED IN

ROOM, U.O.N.

CEILING N/A DUAL TECH. N/A

D

DMX

WALL DMX N/A MULTI. • DMX COLOR CHANGING CONTROLLER

• NICOLAUDIE STICK-CU4

HB

• MANUAL CONTROLS & AUTO-ON / AUTO-OFF

• TWO RELAYS IN POWER PACK

• HIGHBAY COVERAGE

CEILING N/A PIR N/A

• (1) MANUAL SWITCH ON/OFF

• AUTO ON / AUTO OFF

DH

• DAY-LIGHT HARVESTING CONTROLLER W/AUTO DIMMINGCEILING N/A N/A N/A

• DUPLEX RECEPTACLE

• SPLIT-WIRE

• NEMA 5-20R, 125V, 20A

• DUPLEX RECEPTACLE

• PLUG-LOAD CONTROLLED

• NEMA 5-20R, 125V, 20A

• DOUBLE DUPLEX (QUADRAPLEX) RECEPTACLE

• PLUG-LOAD CONTROLLED

• NEMA 5-20R, 125V, 20A

HALF

CONTROLLED

FULLY

CONTROLLED

CONDUIT & FEEDER

• OVERHEAD ELECTRICAL SERVICE

• UNDERGROUND ELECTRICAL

SERVICE

• CONDUIT - TURNED UP

• CONDUIT - TURNED DOWN

• HOMERUN TO PANEL WITH CIRCUIT

NUMBER(S) AS INDICATED

• GROUND CONDUCTOR

• PHASE CONDUCTOR

• NEUTRAL CONDUCTOR

• ONE-LINE DIAGRAM

• EXISTING FEEDER & CONDUIT

• ONE-LINE DIAGRAM

• DEMOLISHED FEEDER & CONDUIT

• ONE-LINE DIAGRAM

• NEW (NORMAL) FEEDER & CONDUIT

• ONE-LINE DIAGRAM

• NEW (EMERGENCY) FEEDER & CONDUIT

• ONE-LINE DIAGRAM & FLOOR PLANS

• NEW FEEDER & CONDUIT SIZE

• REFER TO 'FEEDER & BRANCH

CIRCUIT SCHEDULE (COPPER)' OR

'FEEDER SCHEDULE (ALUMINUM)'

BASED ON SPECIFICATIONS AND

PROVIDE BOTH FEEDER AND

CONDUIT SIZE INDICATED

F###

• FIRE ALARM CONTROL UNIT

• FLUSH / SURFACE

FIRE ALARM SYSTEM

SUBSCRIPTS FOR FIRE ALARM SYSTEM DEVICES INDICATE THE FOLLOWING, U.O.N:

S - SURFACE MOUNTED

R - RECESS IN EXISTING WALL (CUT/PATCH)

• REMOTE FIRE ALARM CONTROL UNIT

• FLUSH / SURFACE

• FIRE ALARM ANNUNCIATOR UNIT

• FLUSH / SURFACE

• MANUAL PULL STATION

• SPEAKER

• WALL / CEILING

• VISUAL STROBE

• WALL / CEILING

• BELL WITH VISUAL INDICATOR

• WALL

• DUCT DETECTOR - SUPPLY DUCT

• DUCT DETECTOR - RETURN DUCT

• DOOR HOLD RELEASE DEVICE

• SUPPLIED BY DIVISION 8

• SPRINKLER SYSTEM TAMPER SWITCH

• SPRINKLER SYSTEM FLOW SWITCH

• POST INDICATOR VALVE

• SPEAKER/STROBE

• WALL / CEILING

• HORN

• WALL / CEILING

M

S

S

H

H

V

B

R

TS

FS

P

S F

R F

S D

R D

FACU FACU

RACU RACU

FAA FAA

AR

• ADDRESSABLE RELAY MODULE FOR

CONTROL / MONITORING

• SPRINKLER SYSTEM PRESSURE SWITCH

PS

• HORN/STROBE

• WALL / CEILING

• SMOKE DETECTOR

• CEILING

• HEAT DETECTOR

• CEILING

SR

F

• COMBINATION SMOKE / HEAT DETECTOR

• CEILING

S

S

H

H

V

• POWER DISTRIBUTION PANELBOARD

• 480Y/277V; 3Ø, 4W

• FLOOR / SURFACE

HALF

CONTROLLED

FULLY

CONTROLLED

SYMBOL MOUNTING HEIGHT ABOVE FINISHED FLOOR (U.O.N.)

• +18" TO CENTER OF RECEPTACLE

• +6" ABOVE TOP OF COUNTERTOP TO BOTTOM OF

RECEPTACLE

• +46" TO CENTER OF LIGHT SWITCH / CONTROLSOS1, OS2, OS3,

3, 4, P, 3P, K, 3K

D

• +46" TO CENTER OF DIMMER / CONTROLSD1, D2, D3, DMX

• COORDINATE MOUNTING HEIGHT WITH EQUIPMENT IF

NOT INDICATED ON DRAWING

• +46" TO CENTER OF MOTOR STARTER TOGGLE SWITCHMS

• +46" TO CENTER OF EMERGENCY SHUT-OFF

B H H S S V

• +80" TO BOTTOM OF WALL MOUNTED FIRE ALARM DEVICE

M

• +46" TO CENTER OF MANUAL PULL STATION

• REFER TO SPECIFICATIONS AND 'GENERAL SYMBOLS &

ABBREVIATIONS NOTES (ALL DRAWINGS)'

• +90" TO TOP OF POWER DISTRIBUTION PANELBOARD'S

TRIM

• +72" TO TOP OF PANELBOARD'S TRIM

• +72" TO TOP OF EQUIPMENT

• +72" TO TOP OF EQUIPMENT

• +18" TO CENTER OF RECEPTACLE

• +6" ABOVE TOP OF COUNTERTOP TO BOTTOM OF

RECEPTACLE

• FLUSH TO CEILING

MOUNTING HEIGHTS

ANNOTATION SYMBOLS

• CIRCUIT TAG

PANEL-CKT

• ROOM CIRCUIT TAG

PANEL-CKT

• CIRCUIT NUMBER NOMENCLATURE BASED

ON # OF POLES

1P OR SWITCHBOARD: PANEL-CKT

2P: PANEL-(X,Y)

3P: PANEL-(X,Y,Z)

WP - WEATHERPROOF

X - MOUNTED IN EXISTING OUTLET BOX

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:4

:5

A

M

C

R e v it L o c a l\

-0

.4

H B ld g

E

\2

-0

.4

H

B ld g

E s m a th is .r v t

2026-028.44H

10.28.2026

SYMBOLS

E-001

SACM

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4 H

C

IT

Y

O F

C A

R M

E L

F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

E -0

S Y

M B

O L S

GENERAL ROUGH-IN MOUNTING HEIGHT NOTES

# NOTES

A COMPLETE COMPLIANCE WITH ALL ASPECTS OF ADA STANDARDS FOR ACCESSIBLE

DESIGN AND ICC/ANSI A117.1 IS REQUIRED OF ALL PROJECTS AND ACTIVITIES.

B MOUNTING HEIGHTS INDICATED ARE FOR TYPICAL DEVICES, UNLESS NOTED OR SPECIFIED

OTHERWISE.

C COORDINATE MOUNTING HEIGHTS OF ANY DEVICES WHICH ARE NOT INDICATED BY

ARCHITECT OR AND/OR ENGINEER.

D REFERENCE DIVISIONS 8, 10, 14, 22, 23, AND 27 FOR ADDITIONAL MOUNTING HEIGHTS.

# Revision Date

F20 12 12 3/4"

1P,1N,1G 2P,1G

2P,1N,1G 3P,1G

3P,1N,1G 3P,1N

EQUIP/SERV

GROUND

FEEDER/BRANCH

CIRCUIT LABEL

CONDUCTOR SIZE PER

CONDUIT

CONDUIT SIZE & QUANTITY

FEEDER & BRANCH CIRCUIT SCHEDULE (COPPER)

3P,2N,1G 3P,3N,1G 3P,1N,2G

PHASE &

NEUTRAL

3/4" 3/4" 3/4" 3/4" 3/4"

F30 10 10 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"

F40 8 10 3/4" 3/4" 1" 1" 1" 1"

F50 6 10 1" 1" 1" 1-1/4" 1-1/4" 1"

F60 4 10 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4"

F70 4 8 1" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 1-1/4"

F80 3 8 1" 1-1/4" 1-1/4" 1-1/2" 1-1/2" 1-1/4"

F90 2 8 1" 1-1/4" 1-1/2" 1-1/2

2" 1-1/2"

F100 1 8 1-1/4" 1-1/2" 1-1/2" 2" 2" 2"

F110 1 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"

F125 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"

F150 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"

F175 2/0 6 1-1/2" 2" 2" 2-1/2" 2-1/2" 2"

F200 3/0 6 1-1/2" 2" 2" 2-1/2" 3" 2-1/2"

F225 4/0 4 2" 2" 2-1/2" 3" 2-1/2"

F250 250 4 2" 2-1/2" 3" 3" 3"

F300 350 4 2" 2-1/2" 3" 3-1/2" 3"

F350 500 3 2-1/2" 3" 3-1/2" 4" 3-1/2"

F400 3/0 3 (2) 1-1/2" (2) 2" (2) 2-1/2" (2) 2-1/2" (2) 2-1/2"

F450 4/0 2 (2) 2" (2) 2" (2) 2-1/2" (2) 3" (2) 2-1/2"

F500 250 2 (2) 2" (2) 2-1/2" (2) 3" (2) 3" (2) 3"

F600 350 1 (2) 2-1/2" (2) 3" (2) 3" (2) 3-1/2" (2) 3"

F700 500 1/0 (2) 2-1/2" (2) 3" (2) 3-1/2" (2) 4" (2) 3-1/2"

F800 350 2/0 (3) 2-1/2" (3) 3" (3) 3" (3) 3-1/2" (3) 3"

F900 350 2/0 (3) 2-1/2" (3) 3" (3) 3" (3) 3-1/2"

F1000 500 2/0 (3) 2-1/2" (3) 3" (3) 3-1/2" (3) 4"

F1200 350 3/0 (4) 2-1/2" (4) 3" (4) 3" (4) 3-1/2"

F1600 500 4/0 (5) 3" (5) 3" (5) 3-1/2" (5) 4"

F2000 500 250 (6) 3" (6) 3" (6) 3-1/2" (6) 4"

F2500 500 350 (7) 4" (7) 3-1/2" (7) 3-1/2" (7) 4"

F3000 500 500 (8) 4" (8) 4" (8) 4"

CONDUCTOR

SIZE

SINGLE PHASE

MAXIMUM BRANCH CIRCUIT CONDUCTOR LENGTHS (FEET)

#12

#8

#6

#4

#3

#2

#1

BRANCH CIRCUIT BREAKER SIZE

#10

120 VOLT

20A-1P 30A-1P

N/A

208 VOLT

20A-2P 30A-2P

N/A

277 VOLT

20A-1P 30A-1P

N/A

480 VOLT

20A-2P 30A-2P

N/A

CONDUCTOR

SIZE

THREE PHASE

#12

#8

#6

#4

#3

#2

#1

BRANCH CIRCUIT BREAKER SIZE

#10

208 VOLT

20A-3P 30A-3P

N/A

480 VOLT

20A-3P 30A-3P

N/A

NOTES:

1. MAINTAIN A MAXIMUM VOLTAGE DROP OF 3%. ADJUST CONDUCTOR SIZE PER MAXIMUM

BRANCH CIRCUIT LENGTH.

2. BRANCH CIRCUIT LENGTHS ARE BASED ON CONDUCTOR DISTANCE FROM PANELBOARD TO

LOAD.

3. PROVIDE JUNCTION BOX TO MAKE WIRE TRANSITION FOR FINAL TERMINATION ON DEVICE,

FIXTURE, EQUIPMENT, ETC.

4. CALCULATIONS BASED ON COPPER CONDUCTORS, 80% LOADING OF BRANCH CIRCUIT

BREAKER, AND 0.95 POWER FACTOR.

A AMPERE

ALTERNATING CURRENT; ARMORED CABLE

AMP SIZE OF CIRCUIT BREAKER FRAME/FUSED SWITCH

ABOVE FINISHED COUNTERTOP

ARC FAULT CIRCUIT INTERRUPTER

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

ALUMINUM

AMERICAN NATIONAL STANDARDS INSTITUTE

ASYMMETRICAL

AMP TRIP SIZE CIRCUIT BREAKER/FUSED SWITCH

AUTOMATIC TRANSFER SWITCH

AUXILIARY

AVERAGE

AMERICAN WIRE GAUGE

BATTERY

BRANCH CIRCUIT PANELBOARD

BREAKER

BOLTED PRESSURE SWITCH

CONDUIT; CELSIUS

CABINET

CIRCUIT BREAKER

CENTER TO CENTER

CANDELA

CUBIC FEET

CENTERLINE

CEILING

CONCRETE MASONRY UNIT

COLUMN

COMBINATION

CONCRETE

CONDUCTOR

CONNECTION

CONTINUOUS; CONTINUED

CONSTRUCTION

CONTROL PANEL

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

COPPER; CONDENSING UNIT

CABINET UNIT HEATER

CYLINDER

DEEP; DEPTH

DIRECT BURIED

DIRECT CURRENT

DEDICATED DEVICE ON INDIVIDUAL BRANCH CIRCUIT

DEMOLISH; DEMOLITION

DIAMETER

DIAGONAL

DISCONNECT

DISTRIBUTION

DOWN

DOUBLE-POLE, DOUBLE-THROW

DOUBLE-POLE, SINGLE-THROW

DISHWASHER

DRAWING

EACH

ELECTRICAL CONTRACTOR; DIVISIONS 26-28

EXHAUST FAN

ELECTRICAL GROUND BAR

ELECTRICAL GROUNDING CONDUCTOR

ELECTRIC HAND DRYER

ELECTRICAL

ELEVATOR; ELEVATION

EMERGENCY

ELECTRICAL METALLIC TUBING

ENCLOSURE

ENGINE

ELECTRICALLY OPERATED

EMERGENCY POWER OFF

EQUAL

EQUIPMENT

ENERGY REDUCTION MAINTENANCE SWITCH

ESTIMATED

EXISTING TO REMAIN

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EXPOSED

EXISTING

EXTERIOR

FUSED; FAHRENHEIT

FIRE ALARM

FIRE ALARM ANNUNCIATOR

FIRE ALARM CONTROL UNIT

FLOOR BOX

FOOT-CANDLE

FAN COIL UNIT

FUSED DISCONNECT

FOUNDATION

FEEDER

FINISHED

FIXTURE

FULL LOAD AMPS

FLEXIBLE

FLOOR

FACTORY MUTUAL

FLEXIBLE METAL CONDUIT

FAN POWERED BOX

FEED THROUGH LUGS

FEET; FOOT

FEED THROUGH LUGS

FURNISHED

FULL-VOLTAGE NON-REVERSING

GROUND

GAUGE

GALVANIZED

GENERAL CONTRACTOR

GARBAGE DISPOSAL

GENERATOR

GROUND FAULT EQUIPMENT PROTECTION

GROUND FAULT CIRCUIT INTERRUPTER

HIGH

HEAVY DUTY

HIGH-DENSITY POLYETHYLENE CONDUIT

HAND-OFF-AUTO

HORIZONTAL

HORSEPOWER

HR

HT

HEAT PUMP

HEATER

HERTZ

INSIDE DIAMETER

INSTIT. OF ELECTRICAL AND ELECTRONICS ENGINEERS

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

IMPEDANCE

AC

AF

AFC

AFCI

AFF

AFG

AHU

AIC

AL

ANSI

ASYM

AT

ATS

AUX

AVG

AWG

BATT

BCP

BKR

BPS

C

CAB

CB

C/C

CD

CF

CL

CLG

CMU

COL

COMB

CONC

COND

CONN

CONT

CONST

CP

CPT

CT

CU

CUH

CYL

D

DB

DC

DED

DEMO

DIA

DIAG

DISC

DISTR

DN

DPDT

DPST

DW

DWG

EA

EC

EF

EGB

EGC

EHD

ELEC

ELEV

EM

EMT

ENCL

ENG

EO

EPO

EQ

EQUIP

ERM

EST

ETR

EWC

EWH

EXP

EX

EXT

F

FA

FAA

FACU

FB

FC

FCU

FD

FDN

FDR

FIN

FIXT

FLA

FLEX

FLR

FM

FMC

FPB

FTL

FT

FTL

FURN

FVNR

G/GND

GA

GALV

GC

GD

GEN

GFEP

GFCI

H

HD

HDPE

HOA

HORIZ

HP

HR

HT

HTP

HTR

HZ

ID

IEEE

IG

IMC

IMP

ABBREVIATIONS

IN INCH

INSULATED; INSULATION

INTERIOR; INTERNAL

INVERTED ELEVATION

JOULE

JUNCTION BOX

THOUSAND

THOUSAND CIRCULAR MILS

KIRK KEY

KNOCKOUT

KEYPAD

KILOVOLTS

KILOVOLT-AMPERES

KILOVOLT-AMPERES REACTIVE

KILOWATTS

LINEAR FEET

LENGTH; LONG

LIGHTNING ARRESTOR

LIGHT EMITTING DIODE

LIQUIDTIGHT FLEXIBLE METAL CONDUIT

LUMEN

LOCK-OUT TAG-OUT

LOCKED ROTOR AMPS

LONG-SHORT-INSTANTANEOUS

LONG-SHORT-INSTANTANEOUS-GROUND FAULT

LIGHT; LIQUIDTIGHT

LIGHTING

LOW VOLTAGE

MANUAL

MATERIAL

MAXIMUM

MECH. CONTRACTOR (DIV. 23); METAL CLAD CABLE

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOLDED CASE CIRCUIT BREAKER

MAIN DISTRIBUTION PANELBOARD

MECHANICAL

MANUFACTURING

MANUFACTURER

MANHOLE; MOUNTING HEIGHT

MINIMUM

MISCELLANEOUS

MAIN LUGS ONLY

MAXIMUM OVERCURRENT PROTECTION

MAIN SWITCHBOARD

MOUNTED

MOUNTING

MANUAL TRANSFER SWITCH

MEDIUM VOLTAGE

MEGAVOLT AMPERES

MEGAVOLT AMPERES REACTIVE

NEUTRAL

NOT APPLICABLE

NORMALLY CLOSED

NEGATIVE (-)

NATIONAL ELECTRICAL MANUFACTURERS ASSOC.

NON-FUSED DISCONNECT SWITCH

NIGHT LIGHT

NON-METALLIC SHEATHED CABLE

NORMALLY OPEN; NUMBER

NOT TO SCALE

INSUL

INT

INV EL

J

JB

K

KCMIL

KK

KO

KP

KV

KVA

KVAR

KW

LF

L

LA

LED

LFMC

LM

LOTO

LRA

LSI

LSIG

LT

LTG

LV

MAN

MAT

MAX

MC

MCA

MCB

MCC

MCCB

MDP

MECH

MFG

MFR

MH

MIN

MISC

MLO

MOCP

MSB

MTD

MTG

MTS

MV

MVA

MVAR

N

N/A

NC

NEG

NEMA

NF

NIC

NL

NM

NO

NTS

KILOWATT-HOURSKWHR

POUNDLB

LIGHTING CONTROL RELAY PANELLCP

MEDIUMMED

MEGAWATTS; MICROWAVE OVENMW

MAIN ELECTRICAL GROUND BARMEGB

NOT IN CONTRACT

OC

OD

OH

OL

P

PB

PC

PED

PF

PH/Ø

PL

POS

PRI

PSF

PSI

PT

PUH

PVC

PWR

QTY

R

REF

REFR

REQ'D

RLA

RMC

RM

RT

RTU

RVAT

SCCR

SCHED

SCR

SEC

SF

SFB

SFL

SN

SP

SPDT

SPEC

SPST

SQ

SQ FT

SQ IN

SS

S/S

ST

STD

STP

SURF

SW

SWBD

PIV

RECEPT

SPD

SQ YD

SYM

T

TB

TCC

TCP

TR

TS

TYP

UC

UG

UL

UNFIN

UNO

VERT

UTP

UV

VAR

VFD

VG

VIF

VM

VP

VR

VUV

W

W/

W/O

WG

WP

WT

XFER

XFMR

Y

UTIL

V

VA

TC

TD

OVERCURRENT

OUTSIDE DIAMETER

OVERHEAD

OVERLOAD

POLE

PULL BOX; PUSH BUTTON

PHOTOCELL; PLUMBING CONTRACTOR (DIVISION 22)

PEDESTAL

POWER FACTOR

PHASE

PILOT LIGHT

POSITIVE (+)

PRIMARY

POUNDS PER SQUARE FOOT

POUNDS PER SQUARE INCH

POTENTIAL TRANSFORMER

PROPELLER UNIT HEATER

POLYVINYL CHLORIDE CONDUIT

POWER

QUANTITY

RESISTANCE

REFERENCE

REFRIGERATOR

REQUIRED

RUNNING LOAD AMPS

RIGID METAL CONDUIT

ROOM

RAINTIGHT

ROOF TOP UNIT

REDUCED VOLTAGE AUTOTRANSFORMER

SHORT-CIRCUIT CURRENT RATING

SCHEDULE

SHORT CIRCUIT RATING

SECONDARY

SUPPLY FAN

SUB-FEED CIRCUIT BREAKER

SUB-FEED LUGS

SOLID NEUTRAL

SINGLE-POLE

SINGLE-POLE, DOUBLE-THROW

SPECIFICATION

SINGLE-POLE, SINGLE-THROW

SQUARE

SQUARE FEET

SQUARE INCH

STAINLESS STEEL

START-STOP

SHUNT TRIP

STANDARD

SHIELDED TWISTED PAIR

SURFACE

SWITCH

SWITCHBOARD

POST INDICATOR VALVE

RECEPTACLE

SURGE PROTECTION DEVICE

SQUARE YARD

SYMMETRICAL

TEMPERATURE; TRANSFORMER

TERMINAL BLOCK

TEMPERATURE CONTROL CONTRACTOR

TEMPERATURE CONTROL PANEL

TAMPER-RESISTANT

TAMPER SWITCH

TYPICAL

UNDERCOUNTER; UNDERCABINET

UNDERGROUND

UNDERWRITERS LABORATORY

UNFINISHED

UNLESS NOTED OTHERWISE

VERTICAL

UNSHIELDED TWISTED PAIR

UNIT VENTILATOR

VOLT AMPERES REACTIVE

VARIABLE FREQUENCY DRIVE

VANDAL GUARD

VERIFY IN FIELD

VENDING MACHINE

VANDAL PROOF

VANDAL RESISTANT

VERTICAL UNIT VENTILATOR

WIDE; WIRE; WATT

WITH

WITHOUT

WIRE GUARD

WEATHERPROOF

WATERTIGHT; WEIGHT

TRANSFER

TRANSFORMER

WYE

UTILITY

VOLT

VOLT AMPERES

TIME CLOCK

TIME DELAY

FLOW SWITCHFS

MAIN FUSED SWITCHMFS

MOTOR-STARTING SWITCHMSS

FRACTIONAL HORSEPOWER MANUAL CONTROLLERFHPMC

INTEGRATED HORSEPOWER MANUAL CONTROLLERIHPMC

FIRE PROTECTION CONTRACTORFPC

SEISMIC RESTRAINTS REQUIREMENTS

SEISMIC RESTRAINTS SHALL BE PROVIDED FOR ALL

ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE

WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING

CODE AND ASCE-7.

REFERENCE THE STRUCTURAL DRAWINGS FOR SEISMIC

DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE

CALCULATIONS AND A COMPLETE LAYOUT INDICATING THE

LOCATIONS AND DETAILS OF THE PROPOSED SEISMIC

RESTRAINTS FOR REVIEW AND ACCEPTANCE BY THE

ARCHITECT AND ENGINEER. ALL MATERIALS SHALL BE BY A

SINGLE MANUFACTURER.

THE SUBMITTAL SHALL BE STAMPED AND SIGNED BY A

PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF

INDIANA.

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:4

:5

A

M

C

R e v it L o c a l\

-0

.4

H B ld g

E

\2

-0

.4

H

B ld g

E s m a th is .r v t

2026-028.44H

10.28.2026

GENERAL INFORMATION

E-002

SACM

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4 H

C

IT

Y

O F

C A

R M

E L

F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

E -0

G E

N E

R A

L I

N F

O R

M A

T

IO

N

GENERAL REQUIREMENTS NOTES

(ALL DRAWINGS)

# NOTES

A APPLICABLE CODES:

- 2009 INDIANA ELECTRICAL CODE (2008 NEC WITH AMMENDMENTS)

- NFPA 72 - 2010

B CONTRACT DOCUMENTS CONSISTS OF BOTH A PROJECT MANUAL AND

DRAWINGS. BOTH ARE MEANT TO BE COMPLEMENTARY - ANYTHING APPEARING

ON EITHER MUST BE EXECUTED THE SAME AS IF SHOWN ON BOTH.

C THOROUGHLY EXAMINE THE WORK OF OTHER CONTRACTORS AND PROPERLY

INSTALL ALL WORK REQUIRED FOR THE PROJECT.

D REFER TO LIFE SAFETY PLAN FOR FIRE-RATING REQUIREMENTS. CONTRACTOR IS

RESPONSIBLE FOR PROVIDING FIRE-RATED DEVICES/SEALS AS SHOWN ON

ELECTRICAL DRAWINGS AND AS REQUIRED BASED ON LIFE SAFETY PLAN

INFORMATION.

E PER NEC ARTICLE 110.26(A) AND 110.26(F) THE DEDICATED ELECTRICAL SPACE

INCLUDES THE SPACE DEFINED BY EXTENDING THE FOOTPRINT OF THE

ELECTRICAL EQUIPMENT (INCLUDING BUT NOT LIMITED TO SWITCHBOARDS,

PANELBOARDS, TRANSFORMERS, MOTOR CONTROLLERS) FROM THE FLOOR TO A

HEIGHT OF 6’-0” ABOVE THE HEIGHT OF THE EQUIPMENT OR TO THE STRUCTURAL

CEILING, WHICH EVER IS LOWER. THE DEDICATED ELECTRICAL SPACE MUST BE

CLEAR OF ANY PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR EQUIPMENT

FOREIGN TO THE ELECTRICAL INSTALLATION. PLUMBING, HEATING, VENTILATION,

AND AIR-CONDITIONING PIPING, DUCTS, AND EQUIPMENT MUST BE INSTALLED

OUTSIDE THE WIDTH AND DEPTH ZONE. CONTRACTOR SHALL MAKE SURE NO

PIPING OR DUCT WORK IS INSTALLED ABOVE THE ELECTRICAL EQUIPMENT.

COORDINATE THESE REQUIREMENTS WITH ALL OTHER TRADES PRIOR TO

INSTALLATION.

F THE NUMBER OF WIRES INDICATED ON DRAWINGS, IN PANEL SCHEDULES AND

CIRCUIT SIZING SCHEDULES APPLIES TO CURRENT CARRYING CONDUCTORS

INCLUDING NEUTRALS. IN ADDITION TO THE NUMBER OF WIRES INDICATED,

PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR SIZED AS SCHEDULED OR

SIZED BY NEC 250.

G PROVIDE NO MORE THAN THREE PHASE CONDUCTORS (PLUS NEUTRALS AND

GROUND) PER CONDUIT.

H PROVIDE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS FOR ALL 120V AND

277V CIRCUITS. DO NOT SHARE NEUTRALS.

I UNLESS OTHERWISE NOTED, PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH

HAVE AN AMPACITY EQUAL TO OR GREATER THAN THE CIRCUIT OVERCURRENT

PROTECTIVE DEVICE RATING SERVING THE CIRCUIT. REFER TO CIRCUIT SIZING

SCHEDULE FOR SIZES OF FEEDERS AND BRANCH CIRCUITS.

J WHEN PROVIDING NEW AND/OR REPLACING EXISTING BREAKERS IN EXISTING

AND/OR OWNER PROVIDED EQUIPMENT, FIELD SURVEY EQUIPMENT AND MATCH

LARGEST AIC VALUE BASED ON EXISTING BREAKERS IN EQUIPMENT.

K MAKE ALL FINAL CONNECTIONS BETWEEN MOTOR CONTROLLERS, DISCONNECT

SWITCHES, ETC. AND EQUIPMENT BEING SERVED BY FEEDER OR BRANCH

CURRENT.

L WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT

PHONES) ARE INDICATED, PROVIDE MULTI-GANG OUTLET BOXES WITH GANG

BARRIERS AND A COMMON FACEPLATE FOR SIMILIAR DEVICES.

M WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING

HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS

FOUR INCHES BETWEEN ADJACENT VERTICAL EDGES.

N WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE

LOCATED IN THE SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR

CENTERLINES.

O CONNECT ALL LIGHTING FIXTURES WITHIN ROOM TO INDICATED SWITCH AND

BRANCH CIRCUIT, U.O.N.

P ALL EXIT FIXTURES AND FIXTURES INDICATED WITH "NL" SHALL BE UNSWITCHED.

Q WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR, MOUNT AS FOLLOWS: IF THE

DISTANCE BETWEEN THE TOP OF THE DOOR FRAME AND THE CEILING IS 24

INCHES OR LESS, CENTER THE EXIT SIGN BETWEEN TOP OF DOOR FRAME AND

CEILING. OTHERWISE, MOUNT BOTTOM OF EXIT SIGN 6 INCHES ABOVE TOP OF

DOOR FRAME. MOUNT OTHER WALL MOUNTED EXIT SIGNS LOCATED WITHIN THE

SAME AREA AT THE SAME HEIGHT.

R COORDINATE LOCATION OF CEILING MOUNTED FIRE ALARM DEVICES WITH

OTHER EQUIPMENT TO AVOID INTERFERENCE. LOCATE FIRE ALARM DEVICES AS

NEAR TO LOCATION INDICATED WHILE AVOIDING INTERFERENCES AND

MAINTAINING CODE REQUIREMENTS.

GENERAL FEEDER & BRANCH CIRCUIT

SCHEDULE NOTES (COPPER)

# NOTES

A PROVIDE BOTH NEW CONDUCTORS AND NEW CONDUIT FOR ALL FEEDERS AND

BRANCH CIRCUITS INDICATED WITH A 'FEEDER/BRANCH CIRCUIT LABEL'. DO NOT

REUSE ANY EXISTING CONDUCTORS AND/OR CONDUIT UNLESS SPECIFICALLY

NOTED ON DRAWINGS, ONE-LINE DIAGRAM, ETC.

B REFER TO SPECIFICATIONS FOR MINIMUM CONDUCTOR AND CONDUIT SIZES.

C REFER TO SPECIFICATIONS FOR TYPE OF RACEWAY.

D FOR ALL NEW AND EXISTING CONDUIT INSTALLATIONS, REFER TO THE NEC FOR

CONDUIT AND TUBING FILL TABLES. IN LOCATIONS WHERE EXISTING CONDUIT IS

PERMITTED TO BE REUSED, IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY

THE EXISTING CONDUIT SIZE MEETS THE NEC CONDUIT AND FILL TABLES PRIOR

TO BID. IF THE CONDUIT DOES NOT MEET THE NEC FILL TABLES, REPLACE THE

CONDUIT FOR THE FEEDER AND/OR BRANCH CIRCUIT IN IT'S ENTIRETY TO

SATISFY THE NEC CONDUIT AND TUBING FILL TABLES.

E ANY CONDUIT AND/OR CONDUCTOR SIZE DEVIATIONS FROM THIS SCHEDULE, OR

INDICATED ON DRAWINGS, MUST BE APPROVED BY THE ENGINEER IN WRITING.

F PROVIDE ROOF SUPPORTS FOR ALL CONDUITS ROUTED ON THE ROOF AND

SUPPORT A MINIMUM OF 1” ABOVE ROOF. ADJUST CONDUCTOR AND CONDUIT

SIZE AS REQUIRED PER NEC AMBIENT TEMPERATURE ADJUSTMENT TABLES.

SUBMIT TO ENGINEER FOR APPROVAL.

G ROOF PENETRATIONS: PROVIDE ROOF PENETRATIONS PER MANUFACTURER'S

RECOMMENDED DETAIL AND VERIFY PENETRATIONS DO NOT VOID ROOF'S

WARRANTY.

H VERIFY LUG SIZES AND QUANTITIES, INCLUDING BUT NOT LIMITED TO, IN

PANELBOARDS, CIRCUIT BREAKERS, MECHANICAL EQUIPMENT, PLUMBING

EQUIPMENT, ELECTRICAL EQUIPMENT, ETC. PRIOR TO PROVIDING CONDUIT

AND/OR CONDUCTORS. MODIFY LUGS AS REQUIRED FOR LARGER FEEDERS

REQUIRED FOR VOLTAGE DROP. COORDINATE FINAL LUG CAPACITY OF ALL

EQUIPMENT BASED ON FINAL SUBMITTALS PRIOR TO PROVIDING CONDUIT

AND/OR CONDUCTORS. NO EXCEPTIONS WILL BE MADE TO ACCOMMODATE

CONDUIT AND/OR CONDUCTORS INSTALLED PRIOR TO COORDINATION WITH

FINAL EQUIPMENT AND PRIOR TO NOTIFYING ENGINEER OF RECORD.

ATS

EX. FCU-1

EX. VRF FCU

EX. HRB-1

EX. FCU-1

EX. FCU-2

EX. FCU

MDF

003A

RR

STORAGE

006A

RR

OFFICE

EMERGENCY OPERATIONS

PLANNING

OFFICE

OFFICE

OFFICE

STAIR 1

ST-1-0

RISER

EX. FCU-4

EX. FCU-4

EX. FCU-4

EX. EF-4

EX. EH-3

EX. EH-3

EX. HRB-1

EX. FCU-3

EX. FCU-4

EX. HRB-1

EX. FCU-4

EX. FCU-5

EX. HRB-1

EX. SSCU-TECH

EX. RH-1 EX. RH-2

EX. RH-3

EX. RH-4CUSTODIAL

FITNESS ROOM

ADA RR

RR

GEAR ROOM

CAPTAIN'S OFFICE

OFFICE STORAGE

STOR.

STAIR 2.1

ST 2-1

APPARATUS BAY

RR

RISER

EMS STORAGE

AIR COMPRESSOR

STAIR 1

ST 1-1

TOOL ROOM

CORRIDOR

OFFICE / WATCHROOM

VESTIBULE

ELEC

EX. EF-2

EX. EH-3

1L2-S1

1L2-S2

1L1

MDP

EX. HP-1C

EX. HP-1B

EX. HP-1A

DORM

213A

BATH

213B

LOCKER

DORM

214A

DORM

215A

LOCKER

LOCKER

BATH

214B

BATH

215B

LAUNDRY

SUPPLY CLOSET

STORAGE

MECH.

JANITOR

PANTRY

PANTRY

PANTRY

BATH

220BLOCKER

LOCKER

LOCKER

LOCKER

LOCKER

BATH

217B

BATH

216B

BATH

219B

BATH

218B

DORM

216A

DORM

217A

DORM

218A

DORM

219A

DORM

220A

KITCHEN

STAIR 1

ST 1-2

STAIR 2

ST 2-2

DAY ROOM

DINING

CORRIDOR

EX. FCU-1 EX. FCU-1

1 1

EX. FCU-1

EX. FCU-1

EX. FCU-1

EX. HRB-1

EX. FCU-1

EX. HRB-1

1 1

2L1-S2 2L1-S1

EX. FCU-1

EX. FCU-5

EX. HBR-1

EX. FCU-6

EX. DOAS-1

EX. MAU-1

1 EX. FCU-4

EX. FCU-4

EX. FCU-4 EX. FCU-4

EX. HRB-1

EX. EF-1

EX. EF-3

EX. FCU-1

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:4

:5

A

M

C

R e v it L o c a l\

-0

.4

H B ld g

E

\2

-0

.4

H

B ld g

E s m a th is .r v t

2026-028.44H

10.28.2026

DEMOLITION PLAN

ED101

SACM

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4 H

C

IT

Y

O F

C A

R M

E L

F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

E D

D

E M

O L

IT

IO

N

P L A

N

GENERAL DEMOLITION NOTES

# NOTES

A REFER TO SHEETS E-001 AND E-002 FOR ADDITIONAL INFORMATION.

B THIS DRAWING REPRESENTS INFORMATION OBTAINED FROM ORIGINAL

CONTRACT DRAWINGS AND FIELD SURVEY. VERIFY BY ON-SITE OBSERVATION

THE EXTENT OF WORK PRIOR TO SUBMISSION OF BID.

C THE OWNER HOLDS RIGHT OF FIRST REFUSAL FOR ALL DEMOLISHED ELECTRICAL

EQUIPMENT.

D ALL ELECTRICAL ITEMS SHOWN WITH LIGHT LINEWORK ARE EXISTING TO REMAIN.

E REMOVE ALL ELECTRICAL ITEMS SHOWN WITH BOLD/DASHED LINEWORK

COMPLETE, UNLESS NOTED OTHERWISE.

F COORDINATE AND DISCONNECT ALL CIVIL, ARCHITECTURAL, MECHANICAL,

PLUMBING, AND TELECOMMUNICATION EQUIPMENT AS NOTED FOR REMOVAL BY

OTHERS. REMOVE ALL ASSOCIATED ELECTRICAL EQUIPMENT, RACEWAYS,

CONDUCTORS, ETC. SERVING THE EQUIPMENT.

G PROVIDE ALL CUTTING AND PATCHING AS REQUIRED FOR THE REMOVAL OF

EXISTING ELECTRICAL EQUIPMENT. REFER TO SPECIFICATIONS.

H PROVIDE A BLANK COVERPLATE FOR ALL EXISTING WALL OPENINGS WHERE

ELECTRICAL EQUIPMENT HAS BEEN REMOVED AND NOT REPLACED. IN AREAS

RECEIVING NEW WALL TREATMENTS, PATCH THE EXISTING OPENING.

I REFER TO A, M, P, AND T-SERIES DRAWINGS FOR AREAS WITH ABOVE CEILING

WORK AND/OR CEILING REMOVAL. TEMPORARILY SUPPORT ALL ELECTRICAL

DEVICES, FIXTURES, ETC. AS REQUIRED. RE-INSTALL ELECTRICAL ITEMS

FOLLOWING THE COMPLETION OF WORK IN THE NEW OR EXISTING CEILINGS.

J REMOVE SYSTEMS AND EQUIPMENT MADE OBSOLETE BY THIS PROJECT. THIS

INCLUDES, BUT IS NOT LIMITED TO, CONDUIT, RACEWAYS, WIREWAYS,

CONDUCTORS, JUNCTION BOXES, WIRING DEVICES, LIGHT FIXTURES, PULL

BOXES, DISCONNECTS, MOTOR STARTERS, CONTACTORS, ETC.

K REMOVE ALL DEBRIS FROM SITE AND LEGALLY DISPOSE OF SAME.

L REMOVE ALL EXISTING EQUIPMENT PADS MADE OBSOLETE. CUT OFF BELOW

FLOOR SLAB AND FILL WITH CONCRETE ALL CONDUITS WHICH ARE ABANDONED

IN OR BELOW THE FLOOR SLAB. PATCH FLOOR TO MATCH EXISTING CONDITIONS.

M REMOVE ALL EXISTING ABOVE SLAB CONDUITS MADE OBSOLETE. CUT OFF

BELOW FLOOR SLAB AND FILL WITH CONCRETE ALL CONDUITS WHICH ARE

ABANDONED IN OR BELOW THE FLOOR SLAB. PATCH FLOOR TO MATCH EXISTING

CONDITIONS.

N COORDINATE ALL EXISTING CEILING-MOUNTED DEVICES (INCLUDING POWER,

FIRE ALARM, LIGHT FIXTURES, AND LIGHTING CONTROLS) WITH NEW WORK BY

ALL DIVISIONS. TEMPORARILY SUPPORT, OR REMOVE AND REINSTALL, DEVICES

AS REQUIRED TO ACCOMMODATE NEW WORK.

DEMOLITION PLAN NOTES

NOT ALL NOTES APPLY TO EVERY SHEET.

# NOTES

1 DISCONNECT AND REMOVE EXISTING ELECTRICAL CONNECTIONS TO

DEMOLISHED MECHANICAL EQUIPMENT COMPLETE. INCLUDING, BUT NOT LIMITED

TO, RACEWAYS, ABANDONED HANGERS, SUPPORTS, JUNCTION BOXES,

CONDUCTORS, DISCONNECTS/STARTERS, DUCT DETECTORS, ETC.

1/8" = 1'-0" 5A

BASEMENT DEMOLITION PLAN

1/8" = 1'-0" 5D

MEZZANINE DEMOLITION PLAN

1/8" = 1'-0" 2C

FIRST FLOOR DEMOLITION PLAN

1/8" = 1'-0" 2A

SECOND FLOOR DEMOLITION PLAN

J J

J

J

J

J

ATS

J

J

J

MDF

003A

RR

STORAGE

006A

RR

OFFICE

EMERGENCY OPERATIONS

PLANNING

OFFICE

FACU

SS-1

RISER

CUSTODIAL

FITNESS ROOM

ADA RR

RR

GEAR ROOM

CAPTAIN'S OFFICE

OFFICE STORAGE

STOR.

STAIR 2.1

ST 2-1

APPARATUS BAY

RR

RISER

EMS STORAGE

AIR COMPRESSOR

STAIR 1

ST 1-1

TOOL ROOM

CORRIDOR

OFFICE / WATCHROOM

VESTIBULE

ELEC

MDPATS

1L1

1L2-S1

1L2-S2

ELEC

EP101

1A

1L2-S2-66

DORM

213A

BATH

213B

LOCKER

DORM

214A

DORM

215A

LOCKER

LOCKER

BATH

214B

BATH

215B

LAUNDRY

SUPPLY CLOSET

STORAGE

MECH.

JANITOR

PANTRY

PANTRY

PANTRY

BATH

220BLOCKER

LOCKER

LOCKER

LOCKER

LOCKER

BATH

217B

BATH

216B

BATH

219B

BATH

218B

DORM

216A

DORM

217A

DORM

218A

DORM

219A

DORM

220A

KITCHEN

STAIR 1

ST 1-2

STAIR 2

ST 2-2

DAY ROOM

DINING

CORRIDOR

2L1-S2 2L1-S1

RTU-2

SSCU-1

EF-5

EX. EF-1

EX. EF-3EX. MAU-1

RTU-1

DS201

MDP

F70

F70

DS203

DS202

MDP

F150F150

2L1-S2-(77,79) F30

F30

2L1-S2-61

GFCI/WP

2L1-S2-61

GFCI/WP

2L1-S2-63

2L1-S2-63

2L1-S2-65

MS202

F20

F20

F20

2L1-S2-67 F20

2L1-S2-69 F20

MS201

1L1

1L2-S2

1L2-S1

MDP

P-1

B-1

ELEC

1L2-S2-64

F20

MDP

F20

F20

1L2-S2-46

FIRST FLOOR

EXISTING MDP

208Y/120V

600A - MLO

3Ø, 4W

AIC: 65KA

EATON PRL3A

1. INTERNAL SPD

2. OL1: 200A-3P

3. 1L1: 200A-3P

4. 1L2: 200A-3P

5. 2L1: 200A-3P

6. HP-1-3: 60A-3P

7. NEW RTU-1: 70A-3P

A. DEMOLISHED: DOAS-1: 60A-3P

8. HP-1-2: 80A-3P

9. HP-1-1: 80A-3P

10. (6) 1P SPACES

11. NEW PUMP P-1: 20A-3P

A. DEMOLISHED: (3) SPACES

12. (3) 1P SPACES

13. NEW RTU-2: 150A-3P

1. DISCONNECT AND REMOVE EXISTING 60A-3P BREAKER FOR

DEMOLISHED 'DOAS-1' UNIT. REPLACE WITH NEW 70A-3P, 65kA

BREAKER TO SERVE RTU-1.

2. PROVIDE NEW 20A-3P, 65kA CIRCUIT BREAKER FOR PUMP P-1.

PROVIDE BREAKER IN THE 'SPACE' SECTION AT THE BOTTOM OF THE

PANEL. PROVIDE NEW COVER PLATES AS REQUIRED.

3. PROVIDE NEW 150A-3P, 65kA CIRCUIT BREAKER FOR RTU-2. PROVIDE

BREAKER IN THE 'SPACE' SECTION AT THE BOTTOM OF THE PANEL.

PROVIDE NEW COVER PLATES AS REQUIRED.

4. FIELD VERIFY ALL REQUIREMENTS FOR NEW BREAKERS AND

COORDINATE WITH MANUFACTURER PRIOR TO ORDERING AND

INSTALLING BREAKER.

SEISMIC RESTRAINTS REQUIREMENTS

SEISMIC RESTRAINTS SHALL BE PROVIDED FOR ALL

ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE

WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING

CODE AND ASCE-7.

REFERENCE THE STRUCTURAL DRAWINGS FOR SEISMIC

DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE

CALCULATIONS AND A COMPLETE LAYOUT INDICATING THE

LOCATIONS AND DETAILS OF THE PROPOSED SEISMIC

RESTRAINTS FOR REVIEW AND ACCEPTANCE BY THE

ARCHITECT AND ENGINEER. ALL MATERIALS SHALL BE BY A

SINGLE MANUFACTURER.

THE SUBMITTAL SHALL BE STAMPED AND SIGNED BY A

PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF

INDIANA.

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:4

:5

A

M

C

R e v it L o c a l\

-0

.4

H B ld g

E

\2

-0

.4

H

B ld g

E s m a th is .r v t

2026-028.44H

10.28.2026

POWER PLAN

EP101

SACM

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4 H

C

IT

Y

O F

C A

R M

E L

F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

E P

P

O W

E R

P L A

N

GENERAL POWER NOTES

# NOTES

A REFER TO SHEETS E-001 AND E-002 FOR ADDITIONAL INFORMATION.

B COORDINATE ALL EXISTING CEILING-MOUNTED DEVICES (INCLUDING POWER,

FIRE ALARM, LIGHT FIXTURES, AND LIGHTING CONTROLS) WITH NEW WORK BY

ALL DIVISIONS. TEMPORARILY SUPPORT, OR REMOVE AND REINSTALL, DEVICES

AS REQUIRED TO ACCOMMODATE NEW WORK.

POWER PLAN NOTES

NOT ALL NOTES APPLY TO EVERY SHEET.

# NOTES

1 REFER TO POWER PLANS AND EQUIPMENT SCHEDULES FOR MOTOR STARTER

SIZE, LOCATION, AND WIRE SIZE SERVING EXHAUST FAN. CONNECT TO

MANUFACTURER PROVIDED DISCONNECT SWITCH IN EXHAUST FAN.

2 DISCONNECT SWITCH FOR OUTDOOR SPLIT SYSTEM. PROVIDE

INTER-CONNECTION BETWEEN OUTDOOR AND INDOOR MECHANICAL UNITS

COMPLETE. REFER TO POWER PLANS, MECHANICAL PLANS, EQUIPMENT

SCHEDULES, DETAILS, ETC. FOR MORE INFORMATION AND LOCATION OF

INTERIOR MECHANICAL UNIT.

3 CIRCUIT CONNECTION FOR MANUFACTURER PROVIDED MECHANICAL EQUIPMENT

RECEPTACLE(S). COORDINATE EXACT LOCATION WITH MANUFACTURER.

CONNECT COMPLETE. REPLACE SPARE 20A-1P WITH A 15A-1P BREAKER IN

PANELBOARD INDICATED. MATCH HIGHEST AIC RATED BREAKER IN EXISTING

PANELBOARD.

4 MOTOR STARTER FOR EXHAUST FAN. CONNECT TO MANUFACTURER PROVIDED

DISCONNECT IN EXHAUST FAN COMPLETE. CONNECT TO EXISITNG SPARE 20A-1P

CIRCUIT BREAKER IN PANELBOARD AS INDICATED.

5 DISCONNECT AND REMOVE EXISTING SPARE 20A-1P CIRCUIT BREAKERS.

REPLACE WITH NEW 30A-2P CIRCUIT BREAKER IN PANELBOARD AS INDICATED.

EXISTING PANELBOARD IS AN EATON PRL1A, 208Y/120V, 3Ø, 4W. FIELD VERIFY

AND MATCH HIGHEST AIC RATING IN PANELBOARD OR PROVIDE 65KA RATED

BREAKER.

6 CIRCUIT FOR TEMPERATURE CONTROL PANEL. CONNECT TO SPARE 20A-1P

CIRCUIT IN EXISTING PANELBOARD AS INDICATED.

7 PROVIDE NEW 15A-1P, SHUNT TRIP CIRCUIT BREAKER IN PANELBOARD AS

INDICATED. EXISTING PANELBOARD IS AN EATON PRL1A, 208Y/120V, 3Ø, 4W. FIELD

VERIFY AND MATCH HIGHEST AIC RATING IN PANELBOARD OR PROVIDE 65KA

RATED BREAKER.

8 EMERGENCY STOP BUTTON FOR BOILER(S). REFER TO SCHEMATICS FOR

ADDITIONAL INFORMATION. CONNECT TO CIRCUIT INDICATED AND SHUNT TRIP

BREAKERS SERVING NEW BOILER(S). PROVIDE NEW 20A-1P, CIRCUIT BREAKER IN

PANELBOARD AS INDICATED. EXISTING PANELBOARD IS AN EATON PRL1A,

208Y/120V, 3Ø, 4W. FIELD VERIFY AND MATCH HIGHEST AIC RATING IN

PANELBOARD OR PROVIDE 65KA RATED BREAKER.

9 CONNECT TO PUMP CONTROLLER. REFER TO RISER DIAGRAM FOR MORE

INFORMATION.

10 REMOVE AND REINSTALL EXISTING CEILING MOUNTED DEVICES AND LIGHT

FIXTURES IN NEW CEILING GRID TO ACCOMODATE ARCHITECTURAL CHANGES.

11 SPLIT SYSTEM UNIT IS POWERED BY OUTDOOR CONDENSING UNIT LOCATED ON

ROOF. PROVIDE WIRING FROM CONDENSING UNIT AND CONNECT TO SPLIT

SYSTEM UNIT COMPLETE. REFER TO ROOF PLANS, DETAILS, EQUIPMENT

SCHEDULES, M-SERIES DRAWINGS, ETC. FOR MORE INFORMATION AND

LOCATION OF OUTDOOR UNIT.

1/8" = 1'-0" 5A

BASEMENT POWER PLAN

1/8" = 1'-0" 5D

MEZZANINE POWER PLAN

1/8" = 1'-0" 2C

FIRST FLOOR POWER PLAN

1/8" = 1'-0" 2A

SECOND FLOOR POWER PLAN

1/4" = 1'-0" 1A

ENLARGED POWER PLAN - ELEC 115

NOT TO SCALE

1B

MDP ELEVATION

R D

R D

MDF

003A

RR

STORAGE

006A

RR

OFFICE

EMERGENCY OPERATIONS

PLANNING

OFFICE

OFFICE

OFFICE

STAIR 1

ST-1-0

FACU

RISER

1L2-S1

1L2-S2

1L1

ATS MDP

CUSTODIAL

FITNESS ROOM

ADA RR

RR

GEAR ROOM

CAPTAIN'S OFFICE

OFFICE STORAGE

STOR.

STAIR 2.1

ST 2-1

APPARATUS BAY

RR

RISER

EMS STORAGE

AIR COMPRESSOR

STAIR 1

ST 1-1

TOOL ROOM

CORRIDOR

OFFICE / WATCHROOM

VESTIBULE

ELEC

RTU-2

RTU-1

RTU-2

DORM

213A

BATH

213B

LOCKER

DORM

214A

DORM

215A

LOCKER

LOCKER

BATH

214B

BATH

215B

LAUNDRY

SUPPLY CLOSET

STORAGE

MECH.

JANITOR

PANTRY

PANTRY

PANTRY

BATH

220BLOCKER

LOCKER

LOCKER

LOCKER

LOCKER

BATH

217B

BATH

216B

BATH

219B

BATH

218B

DORM

216A

DORM

217A

DORM

218A

DORM

219A

DORM

220A

KITCHEN

STAIR 1

ST 1-2

STAIR 2

ST 2-2

DAY ROOM

DINING

CORRIDOR

2L1-S2

2L1-S1

RTU-1

SEISMIC RESTRAINTS REQUIREMENTS

SEISMIC RESTRAINTS SHALL BE PROVIDED FOR ALL

ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE

WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING

CODE AND ASCE-7.

REFERENCE THE STRUCTURAL DRAWINGS FOR SEISMIC

DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE

CALCULATIONS AND A COMPLETE LAYOUT INDICATING THE

LOCATIONS AND DETAILS OF THE PROPOSED SEISMIC

RESTRAINTS FOR REVIEW AND ACCEPTANCE BY THE

ARCHITECT AND ENGINEER. ALL MATERIALS SHALL BE BY A

SINGLE MANUFACTURER.

THE SUBMITTAL SHALL BE STAMPED AND SIGNED BY A

PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF

INDIANA.

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:4

:5

A

M

C

R e v it L o c a l\

-0

.4

H B ld g

E

\2

-0

.4

H

B ld g

E s m a th is .r v t

2026-028.44H

10.28.2026

FIRE ALARM PLAN

EF101

SACM

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4 H

C

IT

Y

O F

C A

R M

E L

F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

E F

F

IR

E A

L A

R M

P L A

N

GENERAL FIRE ALARM NOTES

# NOTES

A REFER TO SHEETS E-001 AND E-002 FOR ADDITIONAL INFORMATION.

B COORDINATE ALL EXISTING CEILING-MOUNTED DEVICES (INCLUDING POWER,

FIRE ALARM, LIGHT FIXTURES, AND LIGHTING CONTROLS) WITH NEW WORK BY

ALL DIVISIONS. TEMPORARILY SUPPORT, OR REMOVE AND REINSTALL, DEVICES

AS REQUIRED TO ACCOMMODATE NEW WORK.

FIRE ALARM PLAN NOTES

NOT ALL NOTES APPLY TO EVERY SHEET.

# NOTES

1/8" = 1'-0" 5A

BASEMENT FIRE ALARM PLAN

1/8" = 1'-0" 5D

MEZZANINE FIRE ALARM PLAN

1/8" = 1'-0" 2A

FIRST FLOOR FIRE ALARM PLAN

1/8" = 1'-0" 2C

SECOND FLOOR FIRE ALARM PLAN

EF-6

EX. KEF-1

REFER TO

SECOND FLOOR

PLANS FOR

THIS AREA OF

ROOF

SEISMIC RESTRAINTS REQUIREMENTS

SEISMIC RESTRAINTS SHALL BE PROVIDED FOR ALL

ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE

WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING

CODE AND ASCE-7.

REFERENCE THE STRUCTURAL DRAWINGS FOR SEISMIC

DESIGN CRITERIA. THE CONTRACTOR SHALL PROVIDE

CALCULATIONS AND A COMPLETE LAYOUT INDICATING THE

LOCATIONS AND DETAILS OF THE PROPOSED SEISMIC

RESTRAINTS FOR REVIEW AND ACCEPTANCE BY THE

ARCHITECT AND ENGINEER. ALL MATERIALS SHALL BE BY A

SINGLE MANUFACTURER.

THE SUBMITTAL SHALL BE STAMPED AND SIGNED BY A

PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF

INDIANA.

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:4

:5

A

M

C

R e v it L o c a l\

-0

.4

H B ld g

E

\2

-0

.4

H

B ld g

E s m a th is .r v t

2026-028.44H

10.28.2026

ROOF PLAN

ER101

SACM

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4 H

C

IT

Y

O F

C A

R M

E L

F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

E R

R O

O F

P L A

N

GENERAL ROOF NOTES

# NOTES

A REFER TO SHEETS E-001 AND E-002 FOR ADDITIONAL INFORMATION.

ROOF PLAN NOTES

NOT ALL NOTES APPLY TO EVERY SHEET.

# NOTES

1 REFER TO POWER PLANS AND EQUIPMENT SCHEDULES FOR MOTOR STARTER

SIZE, LOCATION, AND WIRE SIZE SERVING EXHAUST FAN. CONNECT TO

MANUFACTURER PROVIDED DISCONNECT SWITCH IN EXHAUST FAN.

1/8" = 1'-0" 2A

ROOF PLAN

GNP

GNP

G

P

N

CONDUIT

WIRE NUT

GROUND SCREW

#10-32 X 5/8" GREEN

HEX/SLOTTED/PHILIPS

HEAD WASHER FACE

TAPPED HOLE IN BOX

INSULATED EYE TERMINAL

OUTLET BOXDEVICE YOKE

GROUNDING CONNECTIONS

SHALL BE CONTINUOUS SUCH

THAT REMOVAL OF DEVICE WILL

NOT INTERFERE WITH

CONDUCTOR CONTINUITY

BONDING JUMPER

COMBINATION CONDUIT

HANGER CLAMP

STEEL STRUCTURE

FLAT PLATE FITTING WITH

NUT AND WASHER. NUT

AND WASHER ON

BOTTOM.

THREADED ROD

SIZE AS REQUIRED

BEAM CLAMP ON TOP

OF CHORD OF JOIST

STRUT CHANNEL

CONDUIT CLAMP SIZE AS

REQUIRED (TYP.)

CONDUIT CLAMP,

SIZE AS REQUIRED

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

REFER TO PLANS

FOR QUANTITY &

SIZE OF CONDUITS

3/8" MIN GALVANIZED

THREADED ROD, TYP.

LOCKING

SQUARE WASHER

& LOCKNUT

UV-INHIBITED POLYCARBONATE

OR HIGH-DENSITY

POLYPROPYLENE PLASTIC

BLOCK, LENGTH AS REQUIRED

CORE DRILLED HOLE

EXISTING EXTERIOR

FOUNDATION / WALL

PRESSURE PLATE

STAINLESS STEEL BOLT

SLEEVE SEAL SYSTEM

CORE DRILLED HOLE

EXISTING EXTERIOR

FOUNDATION / WALL

PRESSURE PLATE

STAINLESS STEEL BOLT

SLEEVE SEAL SYSTEM

SIDE VIEW FRONT VIEW

HOT DIPPED GALVANIZED OR

STAINLESS STEEL STRUT -

TYPICAL

STRUT POST BASE

"T" FITTING FOR HORIZONTAL

STRUT CHANNEL - TYPICAL

HORIZONTAL STRUT CHANNEL

4-HOLE 90° "L"

BRACKET ATTACHED

TO FLOOR AND

STRUT CHANNEL

ANGLED STRUT

CHANNEL

ADJUSTABLE

CHANNEL BRACE

NOTES:

1. THIS DETAIL INDICATES INTENT ONLY.

2. PROVIDE ALL LENGTHS, HEIGHTS, CHANNEL SIZE/GAUGE/QUANTITIES, ETC.

AS STRUCTURALLY REQUIRED FOR EACH PROJECT SPECIFIC INSTALLATION.

3. ATTACH FRAME SECURELY TO FLOOR AND STRUCTURE ABOVE.

4. PROVIDE FASTENERS/BOLTS/SCREWS IN ALL HOLES INTENDED FOR

ATTACHING FITTINGS TO FLOOR, STRUCTURE, STRUT ETC.

5. INSTALL PANELS, DISCONNECTS, MOTOR CONTROLLERS, CONDUIT, ETC. AS

INDICATED ON THE DRAWINGS OR AS REQUIRED.

PAINT CUT ENDS OF STRUT

CHANNELS WITH COLD

GALVANIZING COMPOUND

90 DEGREE FITTING FOR

HORIZONTAL STRUT CHANNEL -

TYPICAL

PROVIDE LENGTHS AND HEIGHTS AS

REQUIRED FOR EQUIPMENT TO BE

SUPPORTED

FINISHED FLOOR

NOT TO SCALE

1A

WIRING DEVICE GROUNDING AND BONDING

DETAIL

NOT TO SCALE

2B

CONDUIT 2" AND SMALLER SUPPORT

(STEEL STRUCURE) DETAIL

NOT TO SCALE

1D

CONDUIT 2-1/2" AND LARGER SUPPORT

(STEEL STRUCTURE) DETAIL

NOT TO SCALE

2A

ROOF CONDUIT SUPPORT DETAIL

NOT TO SCALE

1B

SLEEVE SEAL SYSTEM WITH SLEEVE

DETAIL

NOT TO SCALE

4A

TYPICAL FLOOR-MOUNTED STRUT FRAME

DETAIL

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:4

:5

A

M

C

R e v it L o c a l\

-0

.4

H B ld g

E

\2

-0

.4

H

B ld g

E s m a th is .r v t

2026-028.44H

10.28.2026

GENERAL DETAILS

E-501

SACM

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4 H

C

IT

Y

O F

C A

R M

E L

F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

E -5

G E

N E

R A

L D

E T

A

IL

S

BASEMENT FLOOR

F R

F S

M

V H

1ST FLOOR

2ND FLOOR

EXISTING

FIRE ALARM

CONTROL

PANEL BY

HONEYWELL

EXISTING

REMOTE

ANNUNCIATOR

PANEL

EXISTING

FIRE ALARM

NAC PANEL

F R

F S

M

V H

EXISTING

FIRE ALARM

NAC PANEL

V H

EXISTING

FIRE ALARM

NAC PANEL

F

R F

S M

HVAC UNIT

MOTOR STARTER

DETECTOR WITH

RELAY BASE

RI RI

D R

D S

NOTES:

1. REFER TO SITE AND FLOOR PLANS FOR DEVICE LOCATIONS AND

QUANTITIES.

2. ALL VISUAL DEVICES AND HORN/VISUALS TO BE SYNCHRONIZED

FLASH.

3. UPGRADE / EXPAND / ADD EQUIPMENT TO EXISTING FIRE ALARM

SYSTEM AS REQUIRED BY SCOPE INDICATED ON DRAWINGS.

4. FIELD VERIFY ANY CONNECTIONS INTO EXISTING SYSTEM.

5. EXISTING NAC PANELS SHOWN ARE FOR SCHEMATIC PURPOSES

ONLY AND MAY NOT EXIST ON EACH FLOOR AS INDICATED.

6. REFER TO SPECIFICATION SECTION '284621 - ADDRESSABLE FIRE-

ALARM SYSTEMS' FOR REQUIREMENTS.

OUTDOOR

CONDENSING

UNIT

NEMA 3R FUSED DISCONNECT SWITCH.

REFER TO PLANS AND SCHEDULES

FOR ADDITIONAL INFORMATION.

PROVIDE BRANCH CIRCUIT HOME RUN

TO PANELBOARD INDICATED ON

PLANS. PROVIDE ALL REQUIRED

CONNECTIONS BETWEEN DISCONNECT

SWITCH AND CONDENSING UNIT.

INDOOR DUCTLESS

FAN COIL

(1) 3/4"C FOR POWER WIRING. REFER

TO MANUFACTURER'S REQUIREMENTS

FOR WIRING SIZE.

NOTES:

1. COORDINATE FINAL MANUFACTURER ELECTRICAL REQUIREMENTS WITH

EQUIPMENT PROVIDED BY DIVISION 23, INCLUDING, BUT NOT LIMITED TO,

OVERCURRENT PROTECTION AND CONDUCTOR SIZES.

2. PROVIDE CIRCUIT BREAKER LOCKOUT DEVICE IN PANELBOARD SERVING

THE OUTDOOR CONDENSING UNIT.

(1) 3/4"C FOR COMMUNICATION WIRING.

REFER TO MANUFACTURER'S

REQUIREMENTS FOR WIRING SIZE.

PROVIDE EQUIPMENT IDENTIFICATION LABEL INDICATING

OUTDOOR CONDENSING UNIT SERVING THE INDOOR

DUCTLESS FAN COIL AND THE BRANCH CIRCUIT SERVING THE

OUTDOOR CONDENSING UNIT.

NOTES:

1. PUSHING THE BOILER EMERGENCY POWER-OFF BUTTON WILL PROVIDE 120

VOLTS TO EACH CIRCUIT BREAKER SHUNT TRIP COIL AND TRIP THE CIRCUIT

BREAKER SERVINGS THE BURNER CONTROL POWER FOR ALL BOILERS.

2. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT, AND BOILER AND

EMERGENCY POWER-OFF PUSHBUTTON QUANTITY.

LINE

N

SHUNT TRIP

CIRCUIT BREAKER

NO

SHUNT TRIP

CIRCUIT BREAKER

SHUNT TRIP

CIRCUIT BREAKER

BOILER EPO

BUTTON(S)

REFER TO FLOOR PLAN FOR BOILER QUANTITY

EMERGENCY

POWER OFF

LIFT HERE

PUSH

YELLOW POLYCARBONATE

HOUSING

BLACK LETTERS

RED 2" DIAMETER MUSHROOM

PUSHBUTTON (TURN TO RESET)

HINGED, CLEAR

POLYCARBONATE SHIELD

BOILER

EMERGENCY

POWER-OFF

PUSHBUTTON

SIZE AS REQUIRED

LABEL WITH YELLOW

BACKGROUND WITH 1/2"

BLACK LETTERS

HINGE

NOTES:

1. INSTALL BOILER EMERGENCY POWER OFF (EPO) BUTTON AT 3'-10"

ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.

2. FOR USE IN MECHANICAL BOILER ROOMS.

3. EMERGENCY POWER OFF (EPO) PUSHBUTTON: SAFETY

TECHNOLOGY INTERNATIONAL (STI) STOPPER STATION, MODEL

SS2241PO.

WHITE LETTERS

ATTACH ENGRAVED LABEL

TO THE WALL ABOVE THE

EMERGENCY POWER OFF

PUSHBUTTON

WIRING SCHEMATIC EPO DETAIL

NO

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:4

:5

A

M

C

R e v it L o c a l\

-0

.4

H B ld g

E

\2

-0

.4

H

B ld g

E s m a th is .r v t

2026-028.44H

10.28.2026

SCHEMATICS &

SCHEDULES

E-601

SACM

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4 H

C

IT

Y

O F

C A

R M

E L

F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

E -6

S C

H E

M A

T

IC

S

S C

H E

D U

L E

S

262816.1 - ENCLOSED SWITCHES & CIRCUIT BREAKERS SCHEDULE

LABEL

LOCATION

EQUIPMENT

SERVED

EQUIPMENT RATINGS ACCESSORIES

REMARKSNUMBER NAME VOLTAGE POLES AMPERAGE FUSED FUSE SIZE NEMA ENCL

AUX.

CONTACTS

SOLID

NEUTRAL

DS201 RTU-1 240 V 3 100 A Yes 70 A 3R (1) N.O. / N.C. No

DS202 RTU-2 240 V 3 200 A Yes 150 A 3R (1) N.O. / N.C. No

DS203 SSCU-1 240 V 2 30 A Yes 30 A 3R (1) N.O. / N.C. No

262913/262923.1 - ENCLOSED & VARIABLE-FREQUENCY MOTOR CONTROLLERS SCHEDULE

LABEL

LOCATION EQUIPMENT

SERVED

EQUIPMENT RATINGS STARTER DISCONNECT SWITCH REMOTE

CAPACITOR REMARKSNUMBER NAME VOLTAGE PHASE HP FLA NEMA ENCL TYPE NEMA SIZE TYPE FUSE SIZE

MS201 210 MECH. EF-5 120 V 1 1/3 HP 7.2 A 1 FHPMC - - - - HORSEPOWER-RATED TOGGLE SWITCH WITH THERMAL OVERLOADS.

MS202 210 MECH. EF-6 120 V 1 1/6 HP 4.4 A 1 FHPMC - - - - HORSEPOWER-RATED TOGGLE SWITCH WITH THERMAL OVERLOADS.

NOT TO SCALE

1A

FIRE ALARM SCHEMATIC

NOT TO SCALE

3A

MINI-SPLIT WIRING SCHEMATIC

NOT TO SCALE

3B

BOILER EMERGENCY POWER-OFF WIRING

SCHEMATIC/DETAIL

E-001 - SYMBOLS
E-002 - GENERAL INFORMATION
ED101 - DEMOLITION PLAN
EP101 - POWER PLAN
EF101 - FIRE ALARM PLAN
ER101 - ROOF PLAN
E-501 - GENERAL DETAILS
E-601 - SCHEMATICS & SCHEDULES

File details come from the government source that posted it. Updated .