5.3_-_Structural.pdf
PDF 856 KB Posted
- Attached to
- CFD Station #344 HVAC Renovation
- Solicitation number
- IFB-2026-019
- Issued by
- Hamilton County, Indiana
About this file
This is a structural drawing document for the City of Carmel Fire Station #44 HVAC Replacement project located at 5032 E Main Street, Carmel, Indiana 46033. The document comprises detailed structural plans and specifications for the renovation work, including First Floor Slab and Framing Plan (SF101), Second Floor and Low Roof Framing Plan (SF102), Sections and Details (S-501), and Structural Notes (S-600). The project involves modifications to the existing steel frame structure to accommodate new HVAC equipment, including roof opening frames, floor opening frames, rooftop equipment support details, and slab-on-grade infill work. The plans specify existing wide-flange steel beams (W12x19 through W30x191), roof deck systems, and structural modifications required for mechanical unit installation. The sealed bid submission deadline is 10:00 a.m. on Wednesday, December 16, 2026, via the City's e-Procurement Portal at https://procurement.opengov.com/portal/carmelin.
The structural drawings establish design criteria in accordance with the 2014 Indiana Building Code (2012 International Building Code with amendments), AISC 360 standards, and ACI 318 concrete specifications. The design incorporates ultimate wind speeds of 120 miles per hour (nominal 93 mph), seismic design category C with a mapped spectral response acceleration (Ss) of 0.145g, and gravity loads including roof snow loads of 16.8 PSF and minimum roof live loads of 20 PSF. All structural steel shall comply with ASTM A992 (Fy=50 ksi) for wide-flange members and ASTM A572 Grade 50 for plates and angles. The contractor is responsible for field verification of existing conditions, temporary bracing and shoring during construction, compliance with all safety requirements, and submission of shop drawings to the Structural Engineer of Record for review prior to fabrication. Concrete requirements specify 4,000 PSI compressive strength for foundation and slab work with water-reducing admixtures and standard reinforcement per ASTM A615 Grade 60.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B
B
A.1 C
C
D
D
E
E
F
F
G
G
1.1
2 2
3 3
4 4
4.9
FLOOR OPENING FRAMES
PER 2 & 3/S-501
E X
. W x1
-0 '-6
E X
. W x1
-0 '-6
EX. W16x45
-0'-6"
EX. W16x45
-0'-6"
EX. W16x45
-0'-6"
E X
. W x1
-0 '-6
E X
. W x2
-0 '-6
E X
. W x2
-0 '-6
E X
. W x2
-0 '-6
E X
. W x2
-0 '-6
E X
. W x2
-0 '-6
E X
. W x1
-0 '-6
E X
. W x1
-0 '-6
E X
. W x1
-0 '-6
E X
. W x1
-0 '-6
E X
. W x1
-0 '-6
E X
. W x1
-0 '-6
FLOOR OPENING FRAME
PER 2 & 3/S-501
REMOVE SLAB ON GRADE AS REQUIRED FOR NEW
DRAIN INSTALLATION. INFILL SLAB ON GRADE PER
8/S-501. TAKE CARE NOT TO DAMAGE EXISTING
COLUMN FOOTING DURING SLAB DEMOLITION.
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
FIRST FLOOR
/2
/2
:5
:3
A
M
C
U s e rs
\n ri te n o u r\
D e s k to p \P ro je c ts
\2
C a rm e l F
S
H
V A
C R e p la c e m e n t\
-0
.4
H
B ld g
S
C e n tr a l.
rv t
2026-028.44H
10.28.2026
FIRST FLOOR SLAB AND
FRAMING PLAN
SF101
NRR RMD
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E S
T A
T
IO
N
H V
A C
R E
P L A
C E
M E
N T
B
ID
S
E T
5032 E MAIN ST
CARMEL, IN 46033
S F
F
IR
S T
F L O
O R
S L
A B
A N
D F
R A
M
IN
G P
L A
N
SCALE: 1/4" = 1'-0"SF101
1 FIRST FLOOR SLAB AND FRAMING PLAN
# Revision Date
B
B
A.1 C
C
D
D
E
E
F
F
G
G
D.6
1.1
2 2
3 3
4 4
4.9
RTU
6' -6
2'
-0
3"
(2) MC6x15.1 x 18'-6"
LAID ON TOP OF DECK
TOES DOWN IN FLUTES
VERIFY w/ RTU LOCATION
RTU
3' -5
3" 3'
-0
6' -6
VERIFY w/ RTU LOCATION(3) MC6x15.1 x 13'-0"
LAID ON TOP OF DECK
TOES DOWN IN FLUTES
ROOF OPENING FRAMES
PER 4 & 5/S-501
E X
. W x3
+1 6'
-8
E X
. W x3
+1 6'
-8
E X
. W x8
+1 7'
-6
E X
. W x8
+1 7'
-6
EX. W14x22
+16'-8"
EX. W16x31
+16'-8"
EX. W16x31
+16'-8"
EX. W16x31
+16'-8"
EX. W14x22
+16'-8"
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8 "E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x2
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
EX. W14x22
+16'-8"
EX. W14x22
+16'-8"
EX. W14x22
+16'-8"
EX. W16x40
+16'-8"
EX. W14x22
+16'-8"
EX. W16x31
+16'-8"
EX. W24x55
+17'-6"
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
EX. W27x84
+17'-6"
EX. W16x31
+17'-6"
EX. W16x31
+17'-6"
EX. W16x31
+17'-6"
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x2
+1 6'
-8
EX. W16x31
+17'-6"
EX. W24x55
+17'-6"
EX. W24x55
+17'-6"
EX. W14x109
+16'-8"
E X
. W x1
+1 6'
-8
E X
. W x1
+1 7'
-6
E X
. W x1
+1 6'
-8
E X
. W x1
+1 7'
-6
E X
. W x1
+1 6'
-8
E X
. W x1
+1 7'
-6
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x1
+1 6'
-8
E X
. W x3
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 6'
-8
E X
. W x1
+1 7'
-6
E X
. W x5
+1 7'
-6
SCREENWALL PER ARCH DWGS
L2.5x2.5x3/8 BRACE
PER 6/S-501 (TYP)
6' -6
3'
-0
E X
. W x8
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x2
+1 7'
-6
E X
. W x1
+1 7'
-6
EX. W14x22
+17'-6"
EX. W16x40
+17'-6"
EX. W16x40
+17'-6"
EX. W16x40
+17'-6"
E X
. W x5
+1 7'
-6
EX. W16x31
+17'-6"
E X
. W x2
+1 7'
-6
EX. W16x40
+17'-6"
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
EX. W12x19
+17'-6"
E X
. W x1
+1 7'
-6
EX. W16x31
+17'-6"
E X
. W x5
+1 7'
-6
EX. W12x19
+17'-6"
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
EX. W16x31
+17'-6"
EX. W16x45
+17'-6"
EX. W16x45
+17'-6"
EX. W16x45
+17'-6"
EX. W16x31
+17'-6"
E X
. W x8
+1 7'
-6
E X
. W x8
+1 7'
-6
E X
. W x3
+1 7'
-6
E X
. W x3
+1 7'
-6
EX. W14x22
+17'-6"
E X
. W x2
+1 7'
-6
E X
. W x2
+1 7'
-6
EX. W12x19
+17'-6"
EX. W12x19
+17'-6"
EX. W12x19
+17'-6"
EX. W12x19
+17'-6"
EX. W12x19
+17'-6"
EX. W12x19
+17'-6"
E X
. W x2
+1 7'
-6
E X
. W x1
+1 7'
-6
E X
. W x1
+1 7'
-6
EX. W12x19
+17'-6"
EX. W12x19
+17'-6"
FLOOR OPENING FRAME
PER 2 & 3/S-501
ROOF OPENING FRAME
PER 4 & 5/S-501
ROOF OPENING FRAMES
PER 4 & 5/S-501.
NOTE: THESE FRAMES TO
BE LOCATED AT
PENETRATIONS IN HIGH
ROOF (PLAN NOT SHOWN)
L2.5x2.5x3/8 BRACES
PER 6/S-501
S-501
SEE DETAIL 6/S-501 FOR
SMALL ROOF OPENING
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
SECOND FLOOR
/2
/2
:5
:3
A
M
C
U s e rs
\n ri te n o u r\
D e s k to p \P ro je c ts
\2
C a rm e l F
S
H
V A
C R e p la c e m e n t\
-0
.4
H
B ld g
S
C e n tr a l.
rv t
2026-028.44H
10.28.2026
SECOND FLOOR AND
LOW ROOF FRAMING
PLAN
SF102
NRR RMD
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E S
T A
T
IO
N
H V
A C
R E
P L A
C E
M E
N T
B
ID
S
E T
5032 E MAIN ST
CARMEL, IN 46033
S F
S E
C O
N D
F L
O O
R A
N D
L O
W R
O O
F F
R A
M
IN
G P
L A
N
SCALE: 1/4" = 1'-0"SF102
1 SECOND FLOOR AND LOW ROOF FRAMING PLAN
2-L2x2x3/16 ADDNL. DIAGONALS
REF. TYPICAL DETAILS
(NOT APPLICABLE AT STEEL BEAMS)
STEEL JOIST OR BEAM
1 1/2" STEEL ROOF DECK
5/16
INSPECT
MECHANICAL CURB OR POST
COORD. w/ MECH. CONTRACTOR
NOTE: USE C12x20.7 WHEN WIDTH OF
CURB OR POST IS TOO WIDE FOR MC6
MC6x15.1 TOES DOWN IN DECK FLUTES
SUPPORTED BY JOISTS AT BOTH ENDS
COPE VERTICAL LEGS OF
ANGLES WITHIN 1" OF EDGE
OF JOIST CHORD OR BEAM
FLANGE
ANGLES TO BEAR A MIN. OF
3" ON JOIST TOP CHORD OR
BEAM TOP FLANGE NOTE: PROVIDE SIMILAR DETAIL FOR
ROOF ACCESS HATCH. COORD. SIZE OF
OPENING W/ ROOF HATCH MFR. COORD.
LOC'N. W/ ARCH. DWGS.
ROOF OPENING-COORD. SIZE &
LOC'N. W/ MECHANICAL TRADES
STEEL JOIST OR BEAM-
SIZE & SPACING PER PLAN
L4x4x1/4 ANGLE FRAME
PROVIDE FOR ALL
OPENINGS W/ MAX.
DIMENSION EXCEEDING 12"
1.
3.
2.
NOTES:
PROVIDE ANGLE FRAME AS SHOWN FOR ALL
ROOF OPENINGS IN 1 1/2 WIDE-RIB DECK WITH
MAXIMUM DIMENSION EXCEEDING 1'-0".
COORDINATE LOCATION OF ROOF OPENINGS WITH
MECHANICAL AND ARCHITECTURAL DRAWINGS.
USE: L4 x 4 x 1/4 TYPICAL.
MAINTAIN COPE OF VERTICAL LEG WITHIN 1" OF
EDGE OF JOIST CHORD OR BEAM FLANGE
COORD. W/ MECH.
L4x4x1/4 FRAME
COORD. W/ MECH.
ROOF OPENING
1 1/2" WIDE RIB
ROOF DECK
S E
E P
LA
N
F O
R S
P A
C
IN
G
L4x4x1/4 FRAME
ROOF OPENING-
COORD. SIZE W/
MECH. CONTR.
STEEL JOIST OR BEAM-SIZE &
SPACING PER PLAN
STEEL JOIST OR BEAM-SIZE PER PLAN
STEEL JOIST OR BEAM-SIZE PER PLAN
1"
ANGLES TO BEAR A MIN. OF
3" ON JOIST TOP CHORD OR
BEAM TOP FLANGE
SECTION
PLAN
W
ID
E F
LA
N
G E
S
TE
E L
B E
M
S
IZ
E
P E
R P
LA
N
G R
E A
TE
R
T H
A N
2"
L7x4x3/8 x 0'-8 W/ MIN. 3" BRG. ON
STEEL BEAM OR GIRDER
COORD. W/ M.C.
1/4" x 8" x CONT. PL POUR STOP
STEEL BEAM-
SIZE PER PLAN
COORD. W/ M.C.
SEE PLAN FOR SPACING
C6x8.2 FRAME
FLOOR OPENING
NOTE: C6 FRAME ONLY REQUIRED FOR
OPENINGS OVER 12" WIDE
PERPENDICULAR TO DECK SPAN
#4 x 1'-6" IN SLAB @ EACH
CORNER OF OPNG. FOR
CRACK CONTROL
FLOOR OPENING-
COORD. SIZE w/
GENERAL CONTR.
CLIP L7x4x3/8 x
0'-8" TYPICAL
C6x8.2 FRAME
2' -0
M
IN
M A
X
NOTE: IF THE OPENING IS POST-
INSTALLED AFTER THE SLAB IS POURED,
THE CLIP ANGLES MAY BE OMITTED AND
THE CHANNLES MAY BE CONNECTED
DIRECTLY TO THE BEAM WEB.
W
ID
E F
LA
N
G E
S
TE
E L
B E
M
IZ
E
P E
R P
LA
N
M A
X
2' -0
M
IN
NOTE: POUR STOP PLATE NOT
SHOWN FOR CLARITY
C6x8.2 CHANNEL FRAME PROVIDE FOR ALL OPENINGS w/
MAX. DIMENSION EXCEEDING 18"
FLOOR OPENING-COORD. SIZE &
LOCATION w/ MECHANICAL TRADES
CLIP L7x4x3/8 LLV x 0'-8" w/
MIN. 3" BRG. ON JOIST
CHORD OR BEAM FLANGE
STEEL JOIST OR BEAM-SIZE
& SPACING PER BEAM
NOTE: THIS PROJECT DOES NOT
INCLUDE STEEL BAR JOISTS. ALL
SUPPORTING MEMBERS ARRE WIDE-
FLANGE BEAMS AS DEFINED ON PLAN.
EX. STEEL ROOF DECK
EX. STEEL BEAM PER ROOF FRAMING PLAN
SIZE VARIES & T/S VARIES
BEAM
GALV. HSS5X5X3/8 SCREENWALL SUPPORT POST
3/8" GALV. CAP PLATE AT EACH POST
SEAL WELDED ALL AROUND
POST
VERIFY IN FIELD 6"
SCREENWALL PER ARCH. DWGS.
GALV. HSS5X5X3/8 SCREENWALL SUPPORT GIRT W/
3/8" FILLET SEAL-WELDED ALL AROUND
TO HSS POST BOTH ENDS
GALV. HSS5X5 SCREENWALL SUPPORT GIRT W/
3/8" FILLET SEAL-WELDED ALL AROUND
TO HSS POST BOTH ENDS
CUT ROOF DECK ONLY AS REQUIRED.
DO NOT OVERCUT!
(2) L4X4X1/2 X 1'-1" FIELD WELDED ALL AROUND
AT ALL CONTACTS W/ 3/8" FILLET
(I.E. ONE EACH SIDE OF HSS POST)
(2) 1/2" X 7 1/2" W. X 4" H. PL's W/ CHAMFERED CORNER
FIELD WELDED ALL AROUND AT ALL CONTACTS W/ 3/8" FILLET
(I.E. ONE EACH SIDE OF HSS POST)
3/8" X 3 1/2" X 3 1/2" PL W/ CHAMFERED CORNER
FIELD WELDED ALL AROUND AT ALL CONTACTS W/ 1/4" FILLET
L2.5X2.5X3/8 DIAGONAL KICKER FIELD WELDED
BOTH ENDS AT ALL CONTACTS W/ 1/4" FILLET
(NOTE: LENGTH VARIES - VIF)
BEAM
5' -0
2'
-4
1' -8
9' -0
" T O
TA
L
S C
R E
E N
W A
LL
P
O S
T H
E
IG
H T
GALV. 16 GA. COVER PLATE FOR
OPENINGS GREATER THAN 6" &
LESS THAN 12" (SQUARE OR
ROUND)
NOTE: HOLES LESS THAN 6" IN WIDTH (ONE
RIB REMOVED) DO NOT REQUIRE
REINFORCEMENT. REF. TYPICAL ROOF
OPENING FRAME DETAIL FOR OPENINGS w/
MAX. DIMENSION EXCEEDING 12"
#8 TEK SCREWS - FASTEN
TO EACH RIB
NOTE: PROVIDE SIMILAR COVER
PLATE DETAIL COVER PLATE
DETAIL FOR SINGLE DAMAGED
RIB - CONSULT ENGINEER FOR
DIRECTION WHERE MORE THAN
ONE ADJ. RIB IS DAMAGED
STEEL ROOF DECK
PER PLAN
#4 x 1'-6" LONG DOWELS @ 18" O.C. W/
6" EMBEDMENT INTO EXISTING SLAB
W/ HILTI HIT HY 200 ADHESIVE USING
HILTI SAFE-SET SYSTEM
NEW SLAB ON GRADE INFILL
EXISTING SLAB-ON-GRADE
TO REMAIN
F.F.E. (MATCH EXISTING)
MATCH EX. SLAB THICKNESS
(MIN. THICKNESS OF SLAB INFILL = 4")
SCALE: 3/4" = 1'-0"S-501
1 ROOFTOP EQUIPMENT SUPPORT DETAIL
SCALE: 3/4" = 1'-0"S-501
4 ROOF OPENING FRAME DETAIL (1 1/2" DECK)
SCALE: 3/4" = 1'-0"S-501
5 ROOF OPENING FRAME PERSPECTIVE (1 1/2" DECK)
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:3
A
M
C
U s e rs
\n ri te n o u r\
D e s k to p \P ro je c ts
\2
C a rm e l F
S
H
V A
C R e p la c e m e n t\
-0
.4
H
B ld g
S
C e n tr a l.
rv t
2026-028.44H
10.28.2026
SECTIONS AND DETAILS
S-501
NRR RMD
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E S
T A
T
IO
N
H V
A C
R E
P L A
C E
M E
N T
B
ID
S
E T
5032 E MAIN ST
CARMEL, IN 46033
S -5
S E
C T
IO
N
S A
N D
D E
T A
IL
S
SCALE: 3/4" = 1'-0"S-501
2 FLOOR OPENING FRAME DETAIL
SCALE: 3/4" = 1'-0"S-501
3 FLOOR OPENING FRAME PERSPECTIVE
SCALE: 1 1/2" = 1'-0"S-501
7 SECTION
SCALE: 3/4" = 1'-0"S-501
6 SMALL ROOF OPENING DETAIL
# Revision Date
SCALE: 1" = 1'-0"S-501
8 SLAB ON GRADE INFILL DETAIL
GENERAL NOTES
1. The Contractor shall be responsible for complying with all safety precautions and regulations during the work. The Structural Engineer of Record (SER) will not advise on nor issue direction as to safety precautions and programs.
2. The structural drawings herein represent the finished structure and in the completed state will provide global stability, local stability of the individual components, and resist the loading defined. The SER analyzed and designed the structure in this finished state and did not evaluate any partially completed stages of construction.
3. The Contractor is responsible for the stability and strength of the structure during all construction stages. The Contractor shall provide all temporary guying, bracing, and shoring required to erect and hold the structure in proper alignment until all structural work has been completed. The investigation, design, safety, adequacy, and inspection of this guying, bracing, shoring, and temporary supports, etc.
is the sole responsibility of the Contractor. The Contractor shall considering hiring an engineer licensed in the jurisdiction of the project location to ensure that this responsibility is adequately met until the structure is finished.
4. Any temporary guying, bracing, shoring, and supports shall be removed by the contractor after they are no longer required.
5. The SER shall not be responsible for the methods, techniques, and sequences of procedures to perform the work. The supervision of the work is the sole responsibility of the Contractor.
6. Loading applied to the structure during the process of construction shall not exceed the safe load-carrying capacity of the structural members. The live loading used in the design of this structure is indicated in the Design Criteria. Do not apply any construction loads until the structural framing is properly connected together and until all permanent bracing is in place.
7. Shop drawings and other items shall be submitted to the SER for review prior to fabrication. Work shall not be started prior to the Contractor receiving appropriate reviewed submittals by the SER.
Work that is performed without reviewed shop drawings will be subject to removal and replacement at the contractor's expense. All shop drawings shall be reviewed by the Contractor & Construction Manager, if applicable, before being submitted to the SER. The SER's review shall be for conformance with the design concept and general compliance with the relevant contract documents.
The SER's review does not relieve the Contractor of the sole responsibility to review, check, and coordinate the shop drawings prior to submission. The Contractor remains solely responsible for errors and omissions associated with the preparation of shop drawings as they pertain to member sizes, details, dimensions, quantities, etc.
8. Submit shop drawings in electronic PDF format. In no case shall reproductions of the Contract Documents be used as shop drawings. As a minimum, submit the following items for review.
A. Structural steel shop drawings.
9. Resubmitted shop drawings: Resubmitted shop drawings are reviewed only for responses to comments made in the previous submittal. Changes on resubmitted shop drawings should be clearly tracked by the Contractor such that the SER can easily review.
10. When calculations are included in the submittals for components of work designed and certified by a Specialty Structural Engineer (SSE), the review by the SER shall be for conformance with the relevant contract documents. The SER's review does not relieve the SSE from responsibility for the design of the system and the coordination with the elements of the structure under the certification of the SER, or other SSE's. The SER's review does not constitute a warranty of the accuracy or completeness of the SSE's design.
11. When modifications are proposed to structural elements under the design and certification of a Specialty Structural Engineer (SSE), written authorization by the SSE must be obtained and submitted to the Structural Engineer of Record for review, prior to performing the proposed modification.
12. Contractors shall visit the site prior to bid to ascertain conditions which may adversely affect the work or cost thereof.
13. No structural member may be cut, notched, or otherwise reduced in strength without written direction from the SER.
EXISTING CONSTRUCTION
1. The Contractor shall field verify the dimensions, elevations, etc. necessary for the proper construction and alignment of the new portions of the work to the existing work. The Contractor shall make all necessary measurements for fabrication and erection of the structural members. Any discrepancy shall be immediately brought to the attention of the SER.
2. Before proceeding with any work within the existing facility, the Contractor shall become familiar with existing structural and other conditions. Any shoring shown or noted on the plans is a partial and schematic representation of that required. It shall be the Contractor's responsibility to provide all necessary bracing, shoring, and other safeguards to maintain all parts of the work in a safe condition during the progress of demolition and construction, and to protect from damage those portions of the existing work which are to remain. Shoring shall remain in place until the structural work is complete, has been inspected by the Testing Agency, and is certified to be in substantial compliance with the contract documents.
3. When required by the Specifications or by plan note, the Contractor shall submit for the SER's review, a "Proposed Shoring Plan," including, but not limited to: plans, sections, details, notes, description of proposed sequence of work, and calculations prepared by, or under the supervision of a SSE.
4. Welding to and within an existing facility presents potential hazards including:
A. Fire Hazard - Due to the existing construction and building contents.
B. Structural Liquefaction - Due to welding across the full section of the structural members.
Recommendations to prevent these hazards include:
A. Fire hazard - Protect existing combustibles prior to welding. Keep a separate watchman and several fire extinguishers on hand.
B. Structural liquefaction - weld in small increments. Allow welds to harden before continuing to the next increment.
C. Do not leave the site until satisfied that no fire hazard exists.
D. Preference should be given to the use of beam clamps, mechanical fasteners, or bolted connections in lieu of welding within existing facilities, whenever possible. Do not field-drill existing structural members without the written permission of the SER.
COORDINATION WITH OTHER TRADES
1. The Contractor shall coordinate and check all dimensions relating to architectural finishes, mechanical equipment and openings, elevator shafts and overrides, etc. and notify the Architect/Engineer of any discrepancies before proceeding with any work in the area under question.
2. The structural drawings shall be used in conjunction with the drawings of all other disciplines and the specifications. The Contractor shall verify the requirements of other trades as to sleeves, chases, hangers, inserts, anchors, holes, and other items to be placed or set in the structural work.
3. There shall be no vertical or horizontal sleeves set, or holes cut or drilled in any beam or column unless shown on the structural drawings or approved in writing by the SER.
4. Mechanical and electrical openings through supported slabs and walls, 8" diameter or larger, not shown on the structural drawings, must be approved by the SER. Openings less than 8" in diameter shall have at least 1'-0" clear between openings, unless approved in writing by the SER.
5. Verify locations and dimensions of mechanical and electrical openings through supported slabs and walls shown on the structural drawings with the mechanical and electrical contractors.
6. Do not install conduit in supported slabs, slabs on grade, or concrete walls unless explicitly shown or noted on the structural drawings.
7. Do not suspend any items, such as ductwork, mechanical or electrical fixtures, ceilings, etc. from steel roof deck or wood roof sheathing.
8. The mechanical contractor shall verify that mechanical units supported by the steel framing are capable of spanning the distance between the supporting members indicated on the structural drawings. The mechanical contractor shall supply additional support framing as required. The mechanical contractor is also responsible in providing adequate attachment of any units to the structure.
9. If drawings and specifications are in conflict, the most stringent restrictions and requirements shall govern.
DESIGN CRITERIA
1. DESIGN STANDARDS: The intended design standards, codes, and/or criteria are as follows:
General The 2014 Indiana Building Code (2012 International Building Code (IBC) with Indiana Amendments)
Concrete ACI 318 Masonry ACI 530/TMS402 Steel AISC 360 Steel Joists/Girders Steel Joist Institute Steel Deck Steel Deck Institute Cold-Formed Metal AISI Wood Framing NDS Wood Trusses TPI Glu-Lam Construction AITC All referenced standards and codes, as well as ASTM numbers, are for the editions of these publications referenced in the building code listed above, unless otherwise noted.
2. DEAD LOADS: Gravity dead loads used in the design of the structure are as computed for the materials of construction incorporated into the building, including but not limited to walls, floors, ceilings, stairways, fixed partitions, finishes, cladding, and other similar architectural and structural items, as well as mechanical, electrical and plumbing equipment and fixtures, and material handling and fixed service equipment, including the weight of cranes.
3. LIVE LOADS: Gravity live loads used in the design of the structure meet or exceed the values based on Table 1607.1 from the IBC:
OCCUPANCY OR USE UNIFORM (PSF) CONCENTRATED (LB)
A. FLOOR LIVE LOAD 100 2000
B. CORRIDORS AT FIRST FLOOR 100
C. CORRIDORS ABOVE FIRST FLOOR 80
D. STAIRWAYS 100 300
E. MECHANICAL AREAS 125
4. LIVE LOAD REDUCTION: Not Used.
5. PARTITION ALLOWANCE: a uniform partition allowance of 15 PSF has been used to account for the load of all floors where partition locations are subject to change, unless the specified live load exceeds
80 PSF.
6. COLLATERAL LOAD: Unless otherwise noted, a minimum uniform collateral load of 10 PSF has been used to account for ductwork, ceilings, sprinklers, lighting, etc. The collateral load is in addition to the weight of mechanical units, larger piping (greater than 4" diameter) and suspended fixtures or equipment that have been specifically accounted for in the design.
7. COLLATERAL LOAD ABOVE CORRIDORS & MECHANICAL ROOMS: A minimum uniform collateral load of 20 PSF has been used to account for large ductwork, sprinkler mains, concentrations of piping, and electrical distribution above corridors and mechanical rooms. The collateral load is in addition to the weight of mechanical units and larger piping (greater than 4" diameter) and suspended fixtures or equipment that have been specifically accounted for in the design.
8. CONCENTRATED LOADS:
A. All single panel points of the lower chord of exposed roof trusses or any point along the primary structural members supporting roofs over manufacturing, commercial storage and warehousing, and commercial garage floors shall be capable of carrying safely a suspended concentrated load of not less than 2000 LBS in addition to dead load.
B. All single panel points of the lower chord of exposed roof trusses or any point along the primary structural members supporting roofs over all other occupancies shall be capable of carrying safely a suspended concentrated load of not less than 200 LBS in addition to dead load, unless noted.
9. HANDRAILS AND GUARDS
A. Handrail Assemblies and Guards 50 PLF applied in any direction 200 LB concentrated load applied in any direction (non-concurrent with 50 PLF load)
B. Components, Intermediate Rails, 50 LBS horizontally applied normal load Balusters, Fillers, Etc. on an area not to exceed 1 square foot not superimposed with those of handrail assemblies.
10. ROOF LIVE/SNOW LOADS: Gravity Live Loads used in the design of the roof structure meet or exceed the following table:
A. Snow Load
Ground Snow Load, Pg 20 PSF Flat Roof Snow Load, Pf 16.8 PSF Low Slope Minimum Snow Load, Pm 24 PSF Exposure Factor, Ce 1.0 Risk Category (IBC Table 1604.5) IV Snow Importance Factor, Is 1.2 Thermal Factor, Ct 1.0
B. Minimum Roof Live Load 20 PSF C. Overhang Eaves & Projections 33.6 PSF D. Sloped roof snow loads calculated in accordance with Section 7.4, ASCE 7.
E. Unbalanced roof snow loads calculated in accordance with Section 7.6, ASCE 7. Specialty
Structural Engineers must consider unbalanced snow loads in the design of pre-engineered trusses, frames, skylights, curtain walls, cold-formed metal framing, canopies, etc.
F. Drift loads calculated in accordance with Section 7.7, ASCE 7.
G. Roofs used for roof gardens or assembly purposes have been designed for a minimum live load of 100 PSF.
11. LATERAL LOADS: Lateral loads were computed using the following criteria:
A. Wind Load Ultimate Design Wind Speed, Vult 120 MPH Nominal Design Wind Speed, Vasd 93 MPH Wind Exposure Category B Risk Category (IBC Table 1604.5) IV Internal Pressure Coefficient, GCpi ± 0.18
B. Seismic Load Site Classification D Risk Category (IBC Table 1604.5) IV Seismic Importance Factor, Ie 1.5 Mapped Spectral Response Acceleration, Ss 0.145g Mapped Spectral Response Acceleration, S1 0.081g Design Spectral Response Acceleration, Sds 0.155g Design Spectral Response Acceleration, Sd1 0.129g Seismic Design Category, SDC C Response Modification Coefficient, R 2 Seismic Response Coefficient, Cs 0.116 Design Base Shear, V 142 kips Analysis Procedure Equivalent Lateral Force Base Seismic Force-Resisting System B-18: Building Frame System with (ASCE 7-10, Table 12.2-1) Ordinary Reinforced Masonry Shear Walls
12. SAFETY FACTORS: This structure has been designed with 'Safety Factors' in accordance with accepted principles of structural engineering. The fundamental nature of the 'Safety Factor' is to compensate for uncertainties in the design, fabrication, and erection of structural building components. It is intended that ' Safety Factors' be used such that the load-carrying capacity of the structure does not fall below the design load and that the building will perform under design load without distress. While the use of 'Safety Factors' implies some excess capacity beyond design load, such excess capacity cannot be adequately predicted and SHALL NOT BE RELIED UPON.
STRUCTURAL STEEL NOTES
1. Structural steel construction shall conform to the American Institute of Steel Construction
"Specification for Structural Steel Buildings".
2. All wide flange and channel members shall be ASTM A992, Fy=50 ksi
3. All plates, bars, angles, and rods shall be ASTM A572 Gr 50, Fy=50 ksi, unless noted.
4. All structural tube members shall be ASTM A500, Grade C, Fy = 50 ksi unless noted.
5. All structural pipe members shall be ASTM A53,Grade B, Fy=35 ksi unless noted.
6. Details for design, fabrication and erection of all structural steel shall be in accordance with the latest
AISC Standards, unless otherwise noted or specified.
7. Provide temporary erection guying and bracing as required.
8. Unless otherwise shown or noted on the Drawings, provide 8" minimum bearing each end for all loose lintels and beams.
9. For loose lintels, masonry shelf angles and other such items generally not shown on the Structural
Drawings, refer to the Architectural Drawings. See general notes on lintels this sheet for sizes, reinforcing, etc.
10. Steel columns below grade shall be encased in a minimum of 4" concrete or painted with 2 coats of asphaltum paint, unless otherwise shown.
11. Fabricate simple span beams not specifically noted to receive camber so that after erection, any minor camber due to rolling or shop assembly be upward.
12. Refer to the Division 5 Structural Steel Specification of the Project Manual for structural steel surface preparations and prime painting requirements.
13. The Erector shall shim between parallel roof beams and joists with differential mill and induced cambers for level deck bearing.
14. Provide cap plates/end plates to close off exposed, open ends of all tubular members, unless noted.
Seal weld with partial penetration square groove welds for watertight condition.
CAST IN PLACE CONCRETE
1. Details of fabrication of reinforcement, handling and placing of the concrete, construction of forms and placement of reinforcement not otherwise covered by the Plans and Specifications, shall comply with the ACI Code requirements of the latest revised date.
2. Cold weather concreting shall be in accordance with ACI 306. Cold weather is defined as a period when for more than 3 successive days the average daily air temperature drops below 40F and stays below 50F. The Contractor shall maintain a copy of this publication on site.
3. Hot weather concreting shall be in accordance with ACI 305. Hot weather is defined as any combination of the following conditions that tends to impair the quality of the freshly mixed or hardened concrete: high ambient temperature, high concrete temperature, low relative humidity, wind speed, or solar radiation The Contractor shall maintain a copy of this publication on site.
4. A certified Testing Agency shall be retained to perform industry standard testing including measurement of slump, air temperature, concrete cylinder testing, etc. to ensure conformance with the Contract Documents. Submit reports to Architect/Engineer.
5. Finishing of Slabs: After screeding, bull floating and floating operations have been completed, apply final finish as indicated below, and as described in the Division 3 Cast In Place Concrete Specification of the Project Manual.
A. Floor Slabs Hard Trowel Finish B. Ramps, Stairs, & Sidewalks Broom Finish C. Surfaces to Receive Topping Slab Float Finish D. Surfaces to Receive Thick-Set Mortar Float Finish
Beds or Similar Cementitious Materials E. Driving Surfaces Rough Swirl Finish
Sample Finishes: See Specifications for sample and mockup requirements, if any.
Floor Tolerances: See the Specifications for specified Ff and Fl tolerances. Ff and Fl testing shall be performed by the Testing Agency in accordance with ASTM E-1155. Results, including acceptance or rejection of the work will be provided to the Contractor and the Architect/Engineer within 48 hours after data collection. Remedies for out-of-tolerance work shall be in accordance with the Specifications. When approved by the Structural Engineer of Record, measurement of the gaps beneath a 10-foot straight edge may be used in lieu of Ff and Fl testing. Approval must be obtained in writing prior to the beginning of concrete operations.
6. Finishing of Formed Surfaces: Finish formed surfaces as indicated below, and as described in the Division 3 Cast In Place Concrete Specification of the Project Manual.
A. Sides of Footings & Pile Caps Rough Form Finish B. Sides of Grade Beams Rough Form Finish C. Surfaces not exposed to public view Rough Form Finish D. Surfaces exposed to public view Rough Form Finish
7. The Contractor shall consult with the Structural Engineer of Record before starting concrete work to establish a satisfactory placing schedule and to determine the location of construction joints so as to minimize the effects of shrinkage in the floor system.
8. Sawn or tooled control/contraction joints shall be provided in all slabs on grade. For a framed structure, joints shall be located on all column lines. If the column spacing exceeds 20'-0", provide intermediate joints. Exterior slabs, and interior slabs without column shall have joints spaced a maximum of 15'-0" apart. Layout joints so that maximum aspect ratio (ratio of long side to short side) does not exceed 1.5.
9. Where vinyl composition tile, vinyl sheets goods, thin-set epoxy terrazzo, or other similar material is the specified finish floor material, the Contractor shall coordinate the locations of control/contraction and construction joints with the Finish Flooring Contractor. Submit a dimensioned plan showing joint locations and proposed sequence of floor pours.
10. Unless specifically noted on the Plans, composite and non-composite supported slabs on metal deck, and supported cast-in-place concrete slabs do not require sawn control joints.
11. Joints in slabs to receive a finished floor may remain unfilled, unless required by the finish flooring contractor. All exposed slabs shall be filled with sealant specified in Division 7, or as follows: All slabs in industrial, manufacturing, or warehouse applications subject to wheeled traffic shall be filled with specified epoxy resin sealant, all other joints shall be filled with specified elastometric sealant. Defer filling of joints as long as possible, preferably a minimum of 4 to 6 weeks after the slab has been cured. Prior to filling, remove all debris from the slab joints, the fill in accordance with the manufacturer's recommendations.
12. Refer to the Architectural Drawings for locations and details of reveals (1" maximum depth) in exposed walls.
13. Refer to the Architectural Drawings for chamfer requirements for corners of concrete. Where not indicated, provide 3/4" chamfers on exposed corners of concrete, except those abutting masonry.
14. Refer to the Architectural Drawings for exact locations and dimensions of recessed slabs, ramps, stairs, thickened slabs, etc. Slope slabs to drains where shown on the Architectural and Plumbing Drawings.
15. Sidewalks, drives, exterior retaining walls, and other site concrete are not indicated on the Structural Drawings. Refer to the Site/Civil and Architectural Drawings for locations, dimensions, elevations, jointing, and finish details.
CONCRETE REINFORCING
1. Reinforcing steel shall conform to ASTM A615, Grade 60, unless noted.
2. Welded wire fabric shall conform to ASTM A1064, unless noted.
3. Where hooks are indicated, provide standard hooks per ACI and CRSI for all bars unless other hook dimensions are shown on the plans or details.
4. Reinforcement in footings, walls and beams shall be continuous.
5. Reinforcement shall be supported and secured against displacement in accordance with the CRSI
'Manual of Standard Practice'.
6. Details of reinforcing steel fabrication and placement shall conform to ACI 315 'Details and Detailing of
Concrete Reinforcement' and ACI 315R 'Manual of Engineering and Placing Drawings for Reinforced Concrete Structures', unless otherwise indicated.
7. Spread reinforcing steel around small openings and sleeves in slabs and walls, where possible, and where bar spacing will not exceed 1.5 times the normal spacing. Discontinue bars at all large openings where necessary, and provide an area of reinforcement, equal to the interrupted reinforcement, in full length bars, distributing one-half each side of the opening. Where shrinkage and temperature reinforcement is interrupted, add (2) #5 x opening dimension + 4'-0" on each side of the opening. Provide #5 x 4'-0" long diagonal bars in both faces, at each corner of openings larger than 12" in any direction.
8. Provide standees for the support of top reinforcement for footings, pile caps, and mats.
9. Provide individual high chairs with support bars, as required for the support of top reinforcement for supported slabs. Do NOT provide standees.
10. Provide snap-on plastic space wheels to maintain required concrete cover for vertical wall reinforcement.
11. Where walls sit on column footings, provide dowels for the wall. Dowels shall be the same size and spacing as the vertical wall reinforcement, unless noted otherwise, with lab splices as shown on the application sections. Install dowels in the footing forms before concrete is placed. Do NOT stick dowels into footings after concrete is placed.
12. Field bending of reinforcing steel is prohibited, unless noted on drawings.
13. Development length/ lap splice length shall be as follows:
1. Schedule above is based on the following:
A. Class B Tension Splice B. Case 1 condition. Case 1 occurs when both a. and b. are met:
a. Clear cover ≥ bar diameter
b. Center to center bar spacing ≥ 3 * bar diameter
C. 4,000 psi concrete D. 60 ksi, uncoated and deformed reinforcing bars
2. Where the above is not met, notify EOR for guidance.
14. Minimum concrete cover over reinforcing steel shall be as follows, unless noted otherwise on plan, section or note:
BAR SIZE TOP BARS OTHER BARS
DEVELOPMENT/LAP SPLICE SCHEDULE
#3 25" 19"
#4 33" 25"
#5 41" 31"
#6 49" 37"
#7 71" 54"
#8 81" 62"
#9 91" 70"
#10 102" 79"
#11 114" 87"
CONCRETE MIXES
CONCRETE: FOOTINGS, FOUNDATION WALLS, PIERS, & GRADE BEAMS
COMPRESSIVE STRENGTH 4000 PSI
MAXIMUM WATER/CEMENT RATIO 0.45
AIR CONTENT 0 - 3 PERCENT
WATER-REDUCING ADMIXTURE REQUIRED
SLUMP 5" TO 6 1/2"
CONCRETE: INTERIOR CONCRETE SLABS
COMPRESSIVE STRENGTH 4000 PSI
MINIMUM CEMENTITIOUS MATERIAL CONTENT 517 LB/CU YD
AIR CONTENT 0 - 3 PERCENT
WATER-REDUCING ADMIXTURE REQUIRED
SLUMP 5" TO 6 1/2"
CONCRETE: LEAN CONCRETE FILL
COMPRESSIVE STRENGTH 2000 PSI
MAXIMUM WATER/CEMENT RATIO 0.65
AIR CONTENT OPTIONAL
WATER-REDUCING ADMIXTURE NOT REQUIRED
SLUMP 4" TO 7"
1. Slump:
A. Mixes containing Type A WRDA 5" Maximum B. Mixes containing Mid-Range WRDA 5 - 6 1/2" C. Mixes containing High-Range WRDA 5-8"
2. Specified minimum cementitious material contents are based on the use of water reducing admixtures.
3. Include an air-entraining admixture for all concrete exposed to freezing and thawing in service and for all concrete exposed to cold weather during construction, before attaining its specified design compressive strength. Ref. ACI 306 for definition of cold weather.
4. Class C fly ash may be used as a cement substitute with a maximum 20% substitution rate on a pound-per-pound basis.
5. Proportion concrete mixes to provide workability and consistency to permit concrete to be worked readily into the corners and angles of the forms and around reinforcement by the methods of placement and consolidation to be employed, without segregation and excessive bleeding.
6. Adjustments to the approved mix designs may be requested by the contractor when job conditions, weather, test results, or other circumstances warrant. These revised mix designs shall be submitted to the architect/engineer for approval prior to use.
MINIMUM COVER FOR REINFORCEMENT
SUSPENDED SLABS AND JOISTS
MINIMUM COVER
TOP & BOTTOM BARS FOR DRY CONDITIONS:
#11 BARS & SMALLER
#14 & #18 BARS
3/4"
1 1/2"
FORMED CONCRETE SURFACES EXPOSED TO EARTH, WATER, OR WEATHER,
AND OVER OR IN CONTACT WITH SEWAGE AND FOR BOTTOMS BEARING ON
WORK MAT, OR SLABS SUPPORTING EARTH COVER:
#5 BARS & SMALLER
#6 THROUGH #18 BARS 2"
1 1/2"
BEAMS & COLUMNS, FORMED
FOR DRY CONDITIONS:
STIRRUPS, SPIRALS & TIES
PRINCIPAL REINFORCEMENT
1 1/2"
2"
EXPOSED TO EARTH, WATER, SEWAGE, OR WEATHER:
STIRRUPS & TIES
PRINCIPAL REINFORCEMENT
2"
2 1/2"
WALLS
FOR DRY CONDITIONS:
#11 BARS & SMALLER
#14 & #18 BARS
3/4"
1 1/2"
FORMED CONCRETE SURFACES EXPOSED TO EARTH,
WATER, SEWAGE, WEATHER, OR IN CONTACT WITH GROUND
2"
FOOTINGS & BASE SLABS
AT FORMED SURFACES & BOTTOMS BEARING ON
CONCRETE WORK MAT
2"
3"
AT UNFORMED SURFACES & BOTTOMS IN CONTACT
WITH EARTH
TOP OF FOOTINGS SAME AS SLABS
OVER TOP OF PILES 2"
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:4
A
M
C
U s e rs
\n ri te n o u r\
D e s k to p \P ro je c ts
\2
C a rm e l F
S
H
V A
C R e p la c e m e n t\
-0
.4
H
B ld g
S
C e n tr a l.
rv t
2026-028.44H
10.28.2026
STRUCTURAL NOTES
S-600
Designer Author
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4 H
C
IT
Y
O F
C A
R M
E L
F
IR
E S
T A
T
IO
N
H V
A C
R E
P L A
C E
M E
N T
B
ID
S
E T
5032 E MAIN ST
CARMEL, IN 46033
S -6
S T
R U
C T
U R
A L N
O T
E
| SF101 - FIRST FLOOR SLAB AND FRAMING PLAN |
| SF102 - SECOND FLOOR AND LOW ROOF FRAMING PLAN |
| S-501 - SECTIONS AND DETAILS |
| S-600 - STRUCTURAL NOTES |
File details come from the government source that posted it. Updated .