5.4_-_Architecture.pdf

PDF 2 MB Posted

Attached to
CFD Station #344 HVAC Renovation
Solicitation number
IFB-2026-019
Issued by
Hamilton County, Indiana

About this file

This architectural document is a comprehensive set of construction drawings and specifications for the HVAC Replacement project at Carmel Fire Station #44, located at 5032 E Main St, Carmel, Indiana 46033. The project, identified as 2026-028.44H, involves replacement of the heating, ventilating, and air conditioning systems along with related electrical, controls, and ancillary work. The document includes detailed architectural abbreviations, general notes, demolition plans for basement, first, and second floors, overall floor plans showing room layouts across three levels, reflected ceiling plans with specifications for acoustical panel ceilings (APC-1, APC-2, APC-3) and gypsum wallboard (GWB) finishes, and roof plans with equipment placement details. The architectural drawings are dated October 28, 2026, and sealed bids for this project were to be received by the City of Carmel's Board of Public Works and Safety through their e-Procurement Portal at https://procurement.opengov.com/portal/carmelin, with a bid deadline of 10:00 am on Wednesday, December 16, 2026.

The scope of work encompasses extensive MEP (mechanical, electrical, plumbing) coordination with demolition of existing ceiling systems, wall modifications, floor slab cutting, and roof penetrations as required for new system installation. The contractor is responsible for field verification of all existing conditions, protection of surfaces to remain, temporary dust control, and coordination with mechanical, electrical, and plumbing drawings for penetration locations. The project includes reinstallation of existing ceiling grids and equipment with matching finishes, patching and repair of affected surfaces, and compliance with fire-rating requirements and applicable building codes. Specific finish standards require all gypsum wallboard to be 5/8" Type X unless noted otherwise, ceilings at 9'-0" AFF standard height with noted exceptions, and all exposed ductwork and piping to be painted with colors selected by the architect. The architectural drawings serve as the reference documents for detailed construction specifications and coordination with the structural, mechanical, electrical, and plumbing design series.

View the file

Other files

File Type Posted
CFD_Station_#344_HVAC_Renovation.pdf PDF
2026-028.44H_FINAL_TECH_SPECS.pdf PDF
5.7_-_Mechanical.pdf PDF
5.8_-_Plumbing.pdf PDF
5.9_-_Electrical.pdf PDF
5.3_-_Structural.pdf PDF
5.1_-_General.pdf PDF
SAMPLE_OF_MOU_FOR_E-VERIFY.pdf PDF
MAINTENANCE_BOND.pdf PDF
PAYMENT_BOND.pdf PDF
RIGHT_OF_ENTRY.pdf PDF
PERFORMANCE_BOND.pdf PDF
Exhibit_D_E-Verify-1.PDF PDF
SUBCONTRACTORS_LIST.pdf PDF
WORK_DIRECTIVE_CHANGE.pdf PDF
SCREENSHOT_INSTRUCTIONS_-_FOR_BIDS.pdf PDF
SAMPLE_AGREEMENT.pdf PDF
FIELD_ORDER.pdf PDF
NON_COLLUSION_AFFIDAVIT.pdf PDF
CONTRACT_CHANGE_ORDER.pdf PDF
CONTRACT_CHANGE_REQUEST.pdf PDF
REQUEST_FOR_PROPOSAL_CHANGE.pdf PDF
MANUFACTURERS_LIST.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

A/E

ADA

ARCHITECT/ENGINEER

AMERICANS WITH DISABILITIES ACT

ADD

ADJ

ADDENDUM

ADJACENT

ADMIN

AFF

ADMINISTRATION

ABOVE FINISHED FLOOR

ALUM

APPROX

ALUMINUM

APPROXIMATE

APC

APT

ACOUSTICAL PANEL CEILING

APARTMENT

ARCH

ASSN

ARCHITECT

ASSOCIATION

ASTM

A/V

AMERICAN SOCIETY FOR TESTING AND MATERIALS

AUDIO/VISUAL

AVG

AWI

AVERAGE

ARCHITECTURAL WOODWORKING INSTITUTE

BD

BITUM

BOARD

BITUMINOUS

BLDG

BLKHD

BUILDING

BOT

BSMT

BOTTOM

BASEMENT

BULKHEAD

CAB

CB

CABINET

CHALK BOARD

CD

CD

CONSTRUCTION DOCUMENTS

CONTRACT DOCUMENTS

CIP

CJ

CAST-IN-PLACE

CONTROL JOINT

CL

CLG

CENTER LINE

CEILING

CLO

CLR

CLOSET

CLEAR

CMU

COL

CONCRETE MASONRY UNIT

COLUMN

CONC

CONF

CONCRETE

CONFERENCE

CONST

COORD

CONSTRUCTION

COORDINATE

CORR

CPT

CORRIDOR

CARPET

CSI

CTR

CONSTRUCTION SPECIFICATIONS INSTITUTE

CENTER

CU FT

CU IN

CUBIC FEET

CUBIC INCH

CUST

CW

CUSTODIAN

CURTAINWALL

DBL

DEFS

DOUBLE

DIRECT-APPLIED FINISH SYSTEM

DEG

DEMO

DEGREE

DEMOLITION

DEPT

DET

DEPARTMENT

DETAIL

DF

DH

DRINKING FOUNTAIN

DOUBLE HUNG (DOOR, WINDOW)

DIA

DIAG

DIAMETER

DIAGONAL

DIM

DISP

DIMENSION

DISPENSER

DIV

DN

DIVISION

DOWN

DS

DWG

DOWN SPOUT

DRAWING

EA EACH

EC

EIFS

ELECTRICAL CONTRACTOR

EXTERIOR INSULATION AND FINISH SYSTEM

EJ

EL/ELEV

EXPANSION JOINT

ELEVATION

ELEC

ELEV

ELECTRIC

ELEVATOR

EOS

EPDM

EDGE OF SLAB

ETHYLENE PROPYLENE DIENE MONOMER

EQ

EQUIP

EQUAL

EQUIPMENT

EST

ETC

ESTIMATE

ET CETERA

EXIST EXISTING

FD

FE

FLOOR DRAIN

FIRE EXTINGUISHER

FEC

FIN

FIRE EXTINGUISHER CABINET

FINISH

FIN FLR

FIN GR

FINISH FLOOR

FINISH GRADE

FIXT

FLASH

FIXTURE

FLASHING

FLR

FR

FLOOR

FIRE RESISTANT

FRC

FRG

FIBER REINFORCED CONCRETE

FIBER REINFORCED GYPSUM

FRP

FRZ

FIBERGLASS REINFORCED PLASTIC

FREEZER

FT

FTG

FEET, FOOT

FOOTING

FURG FURRING

FURN

FWC

FURNITURE

FABRIC WALL COVERING

GA

GAL

GAUGE

GALLON

GALV

GC

GALVANIZED

GENERAL CONTRACTOR

GFRC

GFRG

GLASS-FIBER-REINFORCED CONCRETE

GLASS-FIBER-REINFORCED GYPSUM

GFRP GLASS-FIBER-REINFORCED PLASTER

GL BLK

GLU LAM

GLASS BLOCK

GLUE LAMINATED WOOD

GOVT

GWB

GOVERNMENT

GYPSUM WALLBOARD

HAZ

HAZ MAT

HAZARD

HAZARDOUS MATERIALS

HDBD

HDW

HEAVY DUTY HARDBOARD

HARDWARE

HM HOLLOW METAL

HORIZ

HR

HORIZONTAL

HOUR

HT

HVAC

HEIGHT

HEATING, VENTILATION, AND AIR CONDITIONING

IBC INTERNATIONAL BUILDING CODE

ID INSIDE DIAMETER

IN

INSTR

INCH/ INCHES

INSTRUMENT

INSUL

INT

INSULATION, E, (ED)

INTERIOR

JAN JANITOR

KD KNOCK DOWN

KIT

KO

KITCHEN

KNOCKOUT

LAM

LG

LAMINATE

LAMINATED GLASS

LAV

LED

LAVATORY

LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LKR RM

LRG

LOCKER ROOM

LARGE

LT

LT GA

LIGHT

LIGHT GAUGE

MAINT

MAN

MAINTENANCE

MANUAL

MATL

MAX

MATERIAL

MAXIMUM

MB

MC

MARKER BOARD

MECHANICAL CONTRACTOR

MDO

MECH

MEDIUM DENSITY OVERLAY

MECHANICAL

MED

MEMB

MEDIUM

MEMBRANE

MEP

MEZZ

MECHANICAL, ELECTRICAL, PLUMBING

MEZZANINE

MFD

MFG

MANUFACTURED

MANUFACTURING

MFR

MGT

MANUFACTURER

MANAGEMENT

MIN

MISC

MINIMUM

MISCELLANEOUS

ML

MO

METAL LATH

MASONRY OPENING

MT

MTD

MOUNT

MOUNTED

MTG

MTL

MOUNTING

METAL

MULL MULLION

NA

NIC

NOT APPLICABLE

NOT IN CONTRACT

NO

NOM

NUMBER

NOMINAL

NTS NOT TO SCALE

O/O

OC

OUT TO OUT

ON CENTER

OD

OPG

OUTSIDE DIAMETER

OPENING

OPP

ORIG

OPPOSITE

ORIGINAL

OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

PART

PBD

PARTIAL

PARTICLEBOARD

PERF

PKG

PERFORATED

PACKAGE

PLAS LAM

PLYWD

PLASTIC LAMINATE

PLYWOOD

PNL

PORC

PANEL

PORCELAIN

PR

PREFAB

PAIR

PREFABRICATED

PREFIN

PREP

PREFINISH

PREPARATION

PROJ

PT

PROJECT

PAINT

R

RCP

RADIUS

REFLECTED CEILING PLAN

RD

REBAR

ROOF DRAIN

REINFORCING STEEL BARS

RECPT

REF

RECEPTACLE

REFERENCE

REF

REINF

REFRIGERATOR

REINFORCED

REQD

REST

REQUIRED

RESTROOM

RM

RO

ROOM

ROUGH OPENING

RTG

RTU

RATING

ROOF TOP UNIT

SCHED

SCHEM

SCHEDULE

SCHEMATIC

SCWD

SECT

SOLID CORE WOOD DOOR

SECTION

SF

SHR

SQUARE FOOT (FEET)

SHOWER

SHT

SIM

SHEET

SIMILAR

SM

SPEC

SMALL

SPECIFICATION

SPKLR

SQ

SPRINKLER

SQUARE

SQ YD

SS

SQUARE YARD

STAINLESS STEEL

ST

STD

STREET

STANDARD

STL

STOR

STEEL

STORAGE

STRUCT

SURR

STRUCTURAL

SURROUND

SUSP SUSPEND

SUSP CLG SUSPENDED CEILING

SV

SVC

SHEET VINYL

SERVICE

SYS SYSTEM

T&G

T/O

TONGUE AND GROOVE

TOP OF

TB

TD

TACK BOARD

TOWEL DISPENSER

TECH

TEMP

TECHNICAL

TEMPORARY

TFF

TG

TOP OF FINISHED FLOOR

TEMPERED GLASS

THK THICKNESS

THRU THROUGH

TI

TOS

TAPERED INSULATION

TOP OF STEEL

TOM TOP OF MASONRY

TRANS TRANSOM

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

VAR

VB

VARIES

VINYL BASE

VCT

VEH

VINYL COMPOSITION TILE

VEHICLE

VERT VERTICAL

VEST VESTIBULE

VIF

VOL

VERIFY IN FIELD

VOLUME

VR VAPOR RETARDER

VWC VINYL WALL COVERING

VWF VINYL WALL FABRIC

W/ WITH

W/O

WC

WITHOUT

WALL COVERING

WD WOOD

WP WORKING POINT

WT WEIGHT

CONCRETE MASONRY UNIT

FACE BRICK

EARTH

CONCRETE

PLYWOOD

METAL/STEEL

FINISHED WOOD TRIM

WOOD BLOCKING

WOOD SHIM

INSULATION (LOOSE OR BATT.)

INSULATION (RIGID) GYPSUM BOARD / PLASTER

MATERIAL SYMBOLS

TITLE MARK

SECTION MARK

ELEVATION MARK

CUT LINE

WALL DESIGNATION WINDOW NUMBER

ROOM TAG

View Name

1/8" = 1'-0"

1t W22

ROOM NAME

404B

REFERENCE SYMBOLS

REVISION TAG

A101

SIM

A-201

1 Ref

R ef

R ef

1 Ref

SHEET REFERENCE

DETAIL REFERENCE

DOOR NUMBER

DOOR LABEL

DOOR NUMBER HARDWARE

SET

PANEL TYPE

m in

FG

H M

A

H

M

KEYNOTE LABEL

00 00 00.B9

SPECIFICATION

REFERENCE

UNIQUE

IDENTIFIER

(NOT A

REFERENCE)

UNIT MATCHLINE

UNIT A

UNIT B

DETAIL MARK

A101

SIM

COLUMN DESIGNATION

FB

FB

DATUM POINT NORTH ARROWN

A. CONTRACTOR SHALL FIELD-VERIFY ALL EXISTING CONDITIONS, DIMENSIONS,

AND ARRANGEMENTS.

B. CONTRACTOR IS RESPONSIBLE FOR PROTECTION OF ALL EXISTING SURFACES,

MATERIALS, AND COMPONENTS TO REMAIN OR BE RELOCATED. DAMAGE TO

THESE RESULTING FROM PERFORMANCE OF WORK SHALL BE REPAIRED BY

CONTRACTOR TO SATISFACTION OF OWNER AND ARCHITECT AT NO

ADDITIONAL EXPENSE TO OWNER.

C. CONTRACTOR SHALL PROVIDE TEMPORARY DUST PROTECTION AS REQUIRED

TO PREVENT CONSTRUCTION DEBRIS AND DUST FROM MIGRATING OUT OF

PROJECT AREA. OWNER/ARCHITECT SHALL CONFIRM ALL DUST PREVENTION

MEASURES/LOCATIONS AND SHALL DETERMINE CHANGES TO THESE

MEASURES.

D. ALL EXISTING EQUIPMENT AND FIXTURES SHALL REMAIN PROPERTY OF OWNER.

ALL REUSABLE ITEMS SALVAGED DURING DEMOLITION OPERATIONS SHALL BE

RETAINED FOR OWNER'S INSPECTION. ONLY ITEMS SO INSPECTED AND

REJECTED BY OWNER SHALL BE DISPOSED. ALL OTHER SUCH ITEMS SHALL BE

TURNED OVER TO OWNER FOR DISPOSITION.

E. ALL EXISTING SURFACES LOCATED ADJACENT TO, OR EXPOSED BY DEMOLITION

WORK AND SCHEDULED TO RECEIVE NEW CONSTRUCTION SHALL BE PATCHED

AND REPAIRED AS REQUIRED TO CLEANLY RECEIVE NEW WORK.

F. ALL EXISTING SURFACES LOCATED ADJACENT TO, OR EXPOSED BY DEMOLITION

WORK AND SCHEDULED TO REMAIN EXPOSED AFTER COMPLETION OF NEW

CONST. SHALL BE REPAIRED AND PATCHED AS REQUIRED TO RECEIVE NEW

FINISHES.

G. OWNER WILL BE RESPONSIBLE FOR REMOVAL/REARRANGEMENT OF ALL

EXISTING LOOSE FURNISHINGS DURING CONSTRUCTION, UNLESS NOTED

OTHERWISE.

H. REFER TO MECH./ELEC./PLUMBING DRAWINGS FOR ADDITIONAL PATCHING AND

PREPARATION WORK RELATED TO M.E.P. DEMOLITION ITEMS.

I. EXISTING SLEEVES, HOLES, AND OTHER PENETRATIONS OR NEW DAMAGE OF

EXISTING BUILDING STRUCTURE ABOVE GRADE EXPOSED BY DEMOLITION AND

REMOVAL OF PIPING, APPURTENANCES, EQUIPMENT SHALL BE PATCHED AND

REPAIRED AS PART OF THE WORK. MAINTAIN FIRE RATINGS OF ALL AND

ADJACENT CONSTRUCTION AFFECTED.

J. CAP ALL PIPING TO REMAIN OR ABANDONED IN ACCORDANCE WITH

REQUIREMENTS OF AUTHORITY HAVING JURISDICTION AND IN ACCORDANCE

WITH ALL LOCAL AND STATE PLUMBING AND HEALTH CODES. UTILIZE ONLY PRE-

MANUFACTURED AND APPROVED FITTINGS TO CAP EXISTING PIPING.

K. EACH CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION WORK REQUIRED

OR NOTED FOR INSTALLATION OF NEW WORK. DEMOLITION MAY INCLUDE

ASSOCIATED DISTRIBUTION SYSTEMS, APPURTENANCES, EQUIPMENT

SUPPORTING CONTROLS, AND MISCELLANEOUS SUPPORTS, UNLESS NOTED

OTHERWISE.

L. COORDINATE ALL DEMOLITION WITH PROJECT SEQUENCING AS DIRECTED BY

GENERAL CONTRACTOR OR CONSTRUCTION MANAGER.

GENERAL DEMOLITION NOTES

A. ALL DIMENSIONS SHOWN ARE TO FACE OF STUD OR MASONRY, UNLESS

NOTED OTHERWISE. DIMENSIONS DESIGNATED AS "CLR OR "CLEAR" INDICATE

A CLEAR DIMENSION FROM FACE OF FINISH TO FACE OF FINISH. DIMENSIONS

OF EXTERIOR WALLS ARE TO OUTSIDE EDGE OF FOUNDATION.

B. ALL OPENINGS FOR MECHANICAL, PLUMBING, FIRE PROTECTION AND

ELECTRICAL SHALL BE FIRE STOPPED AT EACH FLOOR PENETRATION.

C. PROVIDE BRACING AND BLOCKING AS REQUIRED IN WALLS SUPPORTING

CASEWORK, TACKBOARDS, MARKERBOARDS, AND RESTROOM ACCESSORIES.

D. SEAL ALL JOINTS BETWEEN DISSIMILAR MATERIALS.

E. ALL GYPSUM WALLBOARD IS 5/8" TYPE "X", UNLESS NOTED OTHERWISE.

F. WHERE NEW FLOORS MEET EXISTING FLOORS, A SMOOTH, STRAIGHT, AND

FLUSH TRANSITION SHALL BE CONSTRUCTED. VERIFY IN FIELD EXISTING

FLOOR ELEVATIONS AND CONDITIONS WHERE A NEW FLOOR SHALL BE

CONSTRUCTED ADJACENT. TRIM AND PATCH EXISTING FLOOR AS REQUIRED

TO ACHIEVE DESIRED TRANSITION.

G. HATCHING WITHIN WALLS SHOWN IN PLANS AND SECTIONS INDICATES NEW

CONSTRUCTION.

GENERAL PLAN NOTES

A. ALL CEILINGS ARE AT 9'-0" AFF, UNLESS NOTED OTHERWISE.

B. ALL BULKHEADS ARE AT 8'-10" AFF, UNLESS NOTED OTHERWISE.

C. ALL GRIDS ARE CENTERED IN ROOMS, UNLESS NOTED OTHERWISE.

D. ALL EXPOSED DUCTWORK, PIPING ETC. SHALL BE PAINTED. COLOR SELECTED

BY ARCHITECT.

E. LOCATE SPRINKLER HEADS IN CENTER OF CEILING PANEL - WHERE

APPLICABLE.

GENERAL REFLECTED CEILING

PLAN NOTES

REFLECTED CEILING PLAN

LEGEND

APC-1

2' X 2' Acoustical Panel Ceiling (09 51 13)

APC-3

2' X 2' Humidity Resistant Acoustical Panel Ceiling (09 51 13)

GWB

5/8" GWB on Grid Suspension System (09 22 16)

Walls to Deck

Light Fixture (Reference E-Series Dwgs)

Return Air (Reference M-Series Dwgs)

Supply Air (Reference M-Series Dwgs)

Exit Light (Reference E-Series Dwgs)

Recessed Light Fixture Suspended Fixture in Areas with Exposed Ceilings (Reference E-Series Dwgs)

S

SOUND SYSTEM SPEAKER

(REFERENCE E-SERIES/T-

SERIES DWGS)

APC-2

2' X 2' Acoustical Panel Ceiling (09 51 13)

A. WHERE UTILIZED, TAPERED INSULATION SHALL BE INSTALLED TO ACHIEVE

POSITIVE DRAINAGE WITH A MINIMUM RESULTANT SLOPE OF 1/4" PER FOOT,

UNLESS NOTED OTHERWISE.

B. LOW SLOPE ROOF AREAS SHALL HAVE A MINIMUM OF 4" RIGID INSULATION

OVER METAL ROOF DECK. SADDLES, CRICKETS, AND SLOPE PORTIONS OF

FLAT ROOF DECK SHALL BE FORMED BY TAPERED INSULATION. AREAS

WHERE TAPERED INSULATION IS ANTICIPATED HAVE BEEN INDICATED, BUT

SHALL NOT BE CONSIDERED ALL INCLUSIVE. IT IS CONTRACTOR'S

RESPONSIBILITY TO PROVIDE SLOPED SURFACES TO ACHIEVE PROPER

DRAINAGE.

C. ROOF PENETRATIONS AND EQUIPMENT SHOWN SHALL NOT BE CONSIDERED

ALL INCLUSIVE. COORDINATE WITH MECHANICAL, PLUMBING AND ELECTRICAL

DOCUMENTS TO CONFIRM PENETRATIONS AND EQUIPMENT LOCATIONS.

FLASH ALL ROOF PENETRATIONS IN ACCORDANCE WITH ROOFING

MANUFACTURER'S RECOMMENDATIONS. PROVIDE CRICKETS TO ALLOW FOR

PROPER DRAINAGE AROUND UNITS.

GENERAL ROOF PLAN NOTES

COMPONENT SYMBOLS

EXISTING CONSTRUCTION/DOOR

TO REMAIN

ITEMS TO BE DEMOLISHED

(DEMOLITION PLAN)

NEW DOOR

CLEARANCE

WHEELCHAIR CLEARANCE RADIUS

ADA

09 29 00.B7 - INT GWB, 5/8" TYPE X

09 22 16.C6 - INT STEEL STUD

FRAMING, 3-5/8" @ 16" O.C.

M

IN

09 51 13.A2 - CEILING FINISH, REF

ARCHITECTURAL CEILING PLANS

09 22 16.C13 - DEFLECTION TRACK

SECURE FRAMING TO DECK/STRUCTURE

ABOVE

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:3

:5

A M

C

R e v it L o c a l\

-0

.4

H

B ld g

A

\2

-0

.4

H B ld g

A tp h a n .r v t

2026-028.44H

10.28.2026

ARCHITECTURAL

GENERAL NOTES AND

ABBREVIATIONS

A-001

TP

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

A -0

A

R C

H

IT

E C

T U

R A

L G

E N

E R

A L N

O T

E S

A N

D A

B B

R E

V

IA

T

IO

N S

1 1/2" = 1'-0" 1A

S4-C' WALL TYPE

# Revision Date

UP

DN

UP

DN

DN

UP

A B C D E F GA.1 D.6

FITNESS ROOM

CAPTAIN'S OFFICE

OFFICE STORAGE

OFFICE / WATCHROOM

VESTIBULE

GEAR ROOM

ADA RR

RR

AIR COMPRESSOR

EMS STORAGE

RISER

RR

CUSTODIAL

TOOL ROOM

APPARATUS BAY

ELEC

CORRIDOR

STOR.

STAIR 1

ST 1-1

STAIR 2.1

ST 2-1

10 9

8' - 0"

10' - 0"

A B C D E F GA.1 D.6

DORM

220A

DORM

219A

DORM

218A

DORM

217A

DORM

216A

BATH

216B

BATH

217B

LOCKER

LOCKER

BATH

218B

BATH

219B

LOCKER

LOCKER

BATH

220B

LOCKER

PANTRY

PANTRY

PANTRY

JANITOR

SUPPLY CLOSET

LOCKER

DORM

215A

BATH

215B

MECH.

STORAGE

BATH

214B

DORM

214A

DORM

213A

LOCKER

BATH

213B

LAUNDRY

KITCHEN

DINING

DAY ROOM

LOCKER

CORRIDOR

STAIR 1

ST 1-2

STAIR 2

ST 2-2

1 1 1 1 1

33333

3 3

3 2 2

1 13 3

RR

RR

PLANNING

OFFICE

STORAGE

006A

EMERGENCY OPERATIONS

OFFICE

MDF

003A

STAIR 1

ST-1-0 3

OFFICE

1 1

OFFICE

A. CONTRACTOR SHALL FIELD-VERIFY ALL EXISTING CONDITIONS, DIMENSIONS,

AND ARRANGEMENTS.

B. CONTRACTOR IS RESPONSIBLE FOR PROTECTION OF ALL EXISTING SURFACES,

MATERIALS, AND COMPONENTS TO REMAIN OR BE RELOCATED. DAMAGE TO

THESE RESULTING FROM PERFORMANCE OF WORK SHALL BE REPAIRED BY

CONTRACTOR TO SATISFACTION OF OWNER AND ARCHITECT AT NO

ADDITIONAL EXPENSE TO OWNER.

C. CONTRACTOR SHALL PROVIDE TEMPORARY DUST PROTECTION AS REQUIRED

TO PREVENT CONSTRUCTION DEBRIS AND DUST FROM MIGRATING OUT OF

PROJECT AREA. OWNER/ARCHITECT SHALL CONFIRM ALL DUST PREVENTION

MEASURES/LOCATIONS AND SHALL DETERMINE CHANGES TO THESE

MEASURES.

D. ALL EXISTING EQUIPMENT AND FIXTURES SHALL REMAIN PROPERTY OF OWNER.

ALL REUSABLE ITEMS SALVAGED DURING DEMOLITION OPERATIONS SHALL BE

RETAINED FOR OWNER'S INSPECTION. ONLY ITEMS SO INSPECTED AND

REJECTED BY OWNER SHALL BE DISPOSED. ALL OTHER SUCH ITEMS SHALL BE

TURNED OVER TO OWNER FOR DISPOSITION.

E. ALL EXISTING SURFACES LOCATED ADJACENT TO, OR EXPOSED BY DEMOLITION

WORK AND SCHEDULED TO RECEIVE NEW CONSTRUCTION SHALL BE PATCHED

AND REPAIRED AS REQUIRED TO CLEANLY RECEIVE NEW WORK.

F. ALL EXISTING SURFACES LOCATED ADJACENT TO, OR EXPOSED BY DEMOLITION

WORK AND SCHEDULED TO REMAIN EXPOSED AFTER COMPLETION OF NEW

CONST. SHALL BE REPAIRED AND PATCHED AS REQUIRED TO RECEIVE NEW

FINISHES.

G. OWNER WILL BE RESPONSIBLE FOR REMOVAL/REARRANGEMENT OF ALL

EXISTING LOOSE FURNISHINGS DURING CONSTRUCTION, UNLESS NOTED

OTHERWISE.

H. REFER TO MECH./ELEC./PLUMBING DRAWINGS FOR ADDITIONAL PATCHING AND

PREPARATION WORK RELATED TO M.E.P. DEMOLITION ITEMS.

I. EXISTING SLEEVES, HOLES, AND OTHER PENETRATIONS OR NEW DAMAGE OF

EXISTING BUILDING STRUCTURE ABOVE GRADE EXPOSED BY DEMOLITION AND

REMOVAL OF PIPING, APPURTENANCES, EQUIPMENT SHALL BE PATCHED AND

REPAIRED AS PART OF THE WORK. MAINTAIN FIRE RATINGS OF ALL AND

ADJACENT CONSTRUCTION AFFECTED.

J. CAP ALL PIPING TO REMAIN OR ABANDONED IN ACCORDANCE WITH

REQUIREMENTS OF AUTHORITY HAVING JURISDICTION AND IN ACCORDANCE

WITH ALL LOCAL AND STATE PLUMBING AND HEALTH CODES. UTILIZE ONLY PRE-

MANUFACTURED AND APPROVED FITTINGS TO CAP EXISTING PIPING.

K. EACH CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION WORK REQUIRED

OR NOTED FOR INSTALLATION OF NEW WORK. DEMOLITION MAY INCLUDE

ASSOCIATED DISTRIBUTION SYSTEMS, APPURTENANCES, EQUIPMENT

SUPPORTING CONTROLS, AND MISCELLANEOUS SUPPORTS, UNLESS NOTED

OTHERWISE.

L. COORDINATE ALL DEMOLITION WITH PROJECT SEQUENCING AS DIRECTED BY

GENERAL CONTRACTOR OR CONSTRUCTION MANAGER.

GENERAL DEMOLITION NOTES

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:3

:5

A M

C

R e v it L o c a l\

-0

.4

H

B ld g

A

\2

-0

.4

H B ld g

A tp h a n .r v t

2026-028.44H

10.28.2026

OVERALL DEMOLITION

FIRST PLAN

AD101

TP

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

A D

O

V E

R A

L L D

E M

O L

IT

IO

N

F

IR

S T

P L A

N

1/8" = 1'-0" 2A

DEMOLITION FLOOR PLAN - FIRST FLOOR

1/8" = 1'-0" 2C

DEMOLITION FLOOR PLAN - SECOND FLOOR

1/8" = 1'-0" 4A

DEMOLITION FLOOR PLAN - BASEMENT

DEMOLITION PLAN NOTES

REFER TO A-001 FOR GENERAL NOTES. NOT ALL NOTES APPLY TO EVERY SHEET.

# NOTE

1 REMOVE EXISTING CEILING PADS IN THEIR ENTIRETY. TAKE DOWN CEILING GRIDS

AS REQUIRED FOR MEP WORK. PROTECT EXISTING GRIDS FOR REINSTALLATION.

CONTRACTOR TO REPLACE DAMAGED CEILING GRIDS. MATCH EXISTING. VIF.

2 CUT EXISTING GYPSUM CEILING AS REQUIRED FOR MEP WORK. PATCH, REPAIR,

AND FINISH TO MATCH EXISTING.

3 REMOVE EXISTING SUSPENDED LAY-IN PANEL CEILING SYSTEM IN ITS ENTIRETY

INCLUDING, BUT NOT LIMITED TO THE CEILING PADS, GRID, SUSPENSION WIRES,

AND ALL RELATED ANCHORS. PATCH AND REPAIR EXISTING SURFACES TO REMAIN

AND PREP FOR NEW CONSTRUCTION/FINISH.

4 REMOVE EXISTING GYPSUM BOARD CEILING SYSTEM IN ITS ENTIRETY INCLUDING,

BUT NOT LIMITED TO THE GYPSUM BOARD, SUSPENDED FRAMING AND ALL

RELATED ANCHORS/FASTENERS. PATCH AND REPAIR EXISTING SURFACES TO

REMAIN AND PREP FOR NEW CONSTRUCTION/FINISH.

5 REMOVE EXISTING INTERIOR WALL CONSTRUCTION IN ITS ENTIRETY TO LIMITS

INDICATED INCLUDING, BUT NOT LIMITED TO DOORS, FRAMES, WINDOWS AND ALL

MISCELLANEOUS FRAMING. FIELD VERIFY ALL EXISTING WALL CONSTRUCTION

PRIOR TO DEMOLITION. REFER TO ARCHITECTURAL AND INTERIOR FLOOR PLANS

FOR FINISH CONDITIONS AND DIMENSIONS. PATCH AND REPAIR EXISTING

ADJACENT SURFACES TO REMAIN AND PREP FOR NEW CONSTRUCITON.

6 EXISTING BULKHEAD TO REMAIN, PATCH AND REPAIR AS REQUIRED. MATCH

EXISTING.

7 CUT EXISTING ROOF MEMBRANE, PROTECTION BOARD, INSULATION, AND ROOF

DECK AS REQUIRED FOR NEW MEP PENETRATIONS. REF. MEP SERIES DRAWINGS

FOR PENETRATION LOCATIONS. PATCH AND REPAIR AS REQUIRED AND PREP FOR

NEW WORK. VIF EXISTING CONDITION BEFORE CUTTING.

8 SAW CUT EXISTING CONCRETE FLOOR SLAB IN ITS ENTIRETY TO LIMITS INDICATED

FOR MEP WORK. REFERENCE MEP-SERIES AND S-SERIES DRAWINGS FOR

ADDITIONAL INFORMATION. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND

EXISTING BUILDING CONDITIONS IN THE FIELD. PATCH AND REPAIR SLAB-ON-GRADE

CONCRETE FLOOR TO MATCH EXISTING, VIF.

9 REMOVE AND SALVAGE EXISTING SHELVES AND SUPPORT BRACKETS IN ITS

ENTIRETY AND ALL RELATED ANCHORS AND SEALANTS. PATCH AND REPAIR

EXISTING WALL SURFACE TO REMAIN AND PREP FOR NEW CONSTRUCTION/FINISH.

MODIFY SHELVES AS REQUIRED FOR REINSTALLATION. COORDINATE WITH OWNER

FOR LOCATION.

10 REMOVE EXISTING CARPET FLOOR FINISH IN ITS ENTIRETY INCLUDING, BUT NOT

LIMITED TO THE CARPET, ADHESIVES/TACK STRIPS, TRANSITION STRIPS AND ALL

ASSOCIATED WALL BASE TO THE LIMITS INDICATED. PATCH AND REPAIR EXISTING

SURFACES TO REMAIN AND PREP FOR NEW CONSTRUCTION/FINISH.

11 CUT EXISTING GYPSUM CEILING ABOVE CEILING GRID AS REQUIRED FOR MEP

WORK. PATCH, REPAIR, AND FINISH TO MATCH EXISTING.

12 TAKE DOWN CEILING GRIDS AND PADS AS REQUIRED FOR MEP WORK. PROTECT

EXISTING CEILING PADS AND GRIDS FOR REINSTALLATION. CONTRACTOR TO

REPLACE DAMAGED CEILING TILES AND GRIDS. MATCH EXISTING. VIF. # Revision Date

DN

UP

DN

DN

OFFICE

EMERGENCY OPERATIONS

PLANNING

OFFICE

STORAGE

006A

RR

RR

STAIR 1

ST-1-0

MDF

003A

OFFICE

CUSTODIAL

004A

ELEV.

EV-1-0

OFFICE

A B C D E F GA.1 D.6

FITNESS ROOM

CAPTAIN'S OFFICE

OFFICE STORAGE

OFFICE / WATCHROOM

VESTIBULE

GEAR ROOM

ADA RR

RR

AIR COMPRESSOR

EMS STORAGE

RISER

RR

CUSTODIAL

TOOL ROOM

APPARATUS BAY

ELEC

CORRIDOR

STOR.

STAIR 1

ST 1-1

STAIR 2.1

ST 2-1

S4-C'

M A

T C

H E

X

IS

T

IN

G V

IF

/8

ELEV.

EV-1-1

3' - 0"

S -C

1 2

1 2

A B C D E F GA.1 D.6

DORM

220A

DORM

219A

DORM

218A

DORM

217A

DORM

216A

BATH

216B

BATH

217B

LOCKER

LOCKER

BATH

218B

BATH

219B

LOCKER

LOCKER

BATH

220B

LOCKER

PANTRY

PANTRY

PANTRY

JANITOR

SUPPLY CLOSET

LOCKER

DORM

215A

BATH

215B

MECH.

STORAGE

BATH

214B

DORM

214A

DORM

213A

LOCKER

BATH

213B

LAUNDRY

KITCHEN

DINING

DAY ROOM

LOCKER

CORRIDOR

STAIR 1

ST 1-2

STAIR 2

ST 2-2

5A

AR100

S -C

2' - 4"

A. ALL DIMENSIONS SHOWN ARE TO FACE OF STUD OR MASONRY, UNLESS

NOTED OTHERWISE. DIMENSIONS DESIGNATED AS "CLR OR "CLEAR" INDICATE

A CLEAR DIMENSION FROM FACE OF FINISH TO FACE OF FINISH. DIMENSIONS

OF EXTERIOR WALLS ARE TO OUTSIDE EDGE OF FOUNDATION.

B. ALL OPENINGS FOR MECHANICAL, PLUMBING, FIRE PROTECTION AND

ELECTRICAL SHALL BE FIRE STOPPED AT EACH FLOOR PENETRATION.

C. PROVIDE BRACING AND BLOCKING AS REQUIRED IN WALLS SUPPORTING

CASEWORK, TACKBOARDS, MARKERBOARDS, AND RESTROOM ACCESSORIES.

D. SEAL ALL JOINTS BETWEEN DISSIMILAR MATERIALS.

E. ALL GYPSUM WALLBOARD IS 5/8" TYPE "X", UNLESS NOTED OTHERWISE.

F. WHERE NEW FLOORS MEET EXISTING FLOORS, A SMOOTH, STRAIGHT, AND

FLUSH TRANSITION SHALL BE CONSTRUCTED. VERIFY IN FIELD EXISTING

FLOOR ELEVATIONS AND CONDITIONS WHERE A NEW FLOOR SHALL BE

CONSTRUCTED ADJACENT. TRIM AND PATCH EXISTING FLOOR AS REQUIRED

TO ACHIEVE DESIRED TRANSITION.

G. HATCHING WITHIN WALLS SHOWN IN PLANS AND SECTIONS INDICATES NEW

CONSTRUCTION.

GENERAL PLAN NOTES

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:3

:5

A M

C

R e v it L o c a l\

-0

.4

H

B ld g

A

\2

-0

.4

H B ld g

A tp h a n .r v t

2026-028.44H

10.28.2026

OVERALL FLOOR PLANS

AF101

TP

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

A F

O

V E

R A

L L F

L O

O R

P L A

N S

1/8" = 1'-0" 4A

BASEMENT

1/8" = 1'-0" 2A

FIRST FLOOR

1/8" = 1'-0" 2C

SECOND FLOOR

FLOOR PLAN NOTES

REFER TO A-001 FOR GENERAL NOTES. NOT ALL NOTES APPLY TO EVERY SHEET.

# NOTE

1 MODIFY EXISTING FLOOR AND WALL BASE AS REQUIRED FOR NEW WALL. PROVIDE

NEW WALL BASE FOR NEW WALL. WALL BASE TO MATCH EXISTING.

2 099600.99 - NEW WALL FINISH TO MATCH EXISTING, VIF.

3 NEW SLAB-ON-GRADE INFILL. MATCH EXISTING, VIF. REF. S-SERIES DRAWINGS.

A B C D E F GA.1 D.6

2 2

A.F.F.

APC-1

12' - 0"

A.F.F.

APC-1

10' - 0"

A.F.F.

APC-2

10' - 0"

A.F.F.

APC-1

10' - 0"

A.F.F.

APC-1

10' - 0"

A.F.F.

APC-2

10' - 0"

GEAR ROOM

FITNESS ROOM

ADA RR

RR

CORRIDOR

CAPTAIN'S OFFICE

OFFICE STORAGE

OFFICE / WATCHROOM

VESTIBULE

AIR COMPRESSOR

EMS STORAGE

RISER

RR

CUSTODIAL

TOOL ROOM

ELEC

STAIR 2.1

ST 2-1

APPARATUS BAY

A.F.F.

APC-2

9' - 0"

A.F.F.

APC-1

10' - 0"

A B C D E F GA.1 D.6

RR

RR

PLANNING

OFFICE

STORAGE

006A

EMERGENCY OPERATIONS

OFFICE

MDF

003A

STAIR 1

ST-1-0

OFFICE

A.F.F.

APC-2

9' - 0"

A.F.F.

APC-1

8' - 8"

A.F.F.

APC-1

8' - 8"

4C

AC101

A.F.F.

APC-2

9' - 0"

OFFICE

A.F.F.

APC-1

8' - 8"

A.F.F.

APC-1

8' - 8"

1 1

A B C D E F GA.1 D.6

DORM

220ADORM

219A

DORM

218A

DORM

217A

DORM

216A

BATH

216B

BATH

217B

LOCKER

LOCKER

BATH

218B

BATH

219B

LOCKER

LOCKER

BATH

220B

LOCKER

PANTRY

PANTRY

PANTRY

JANITOR

SUPPLY CLOSET

LOCKER

DORM

215A

BATH

215B

MECH.

STORAGE

BATH

214BDORM

214A

DORM

213A

LOCKER

BATH

213B

LAUNDRY

KITCHEN

DINING

DAY ROOM

LOCKER

CORRIDOR

STAIR 1

ST 1-2

STAIR 2

ST 2-2

2 8

1 1 1 1 1

333 3 3

A.F.F.

APC-1

9' - 0"

A.F.F.

GWB

8' - 10"

A.F.F.

APC-2

9' - 0"

A.F.F.

GWB

8' - 0"

A.F.F.

GWB

10' - 0"

A.F.F.

GWB

10' - 0"

A.F.F.

APC-2

8' - 4"

A.F.F.

APC-2

9' - 0"

A.F.F.

APC-1

9' - 0"A.F.F.

APC-1

9' - 0"A.F.F.

APC-1

9' - 0"A.F.F.

APC-1

9' - 0"

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-1

8' - 0"

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-3

7' - 8"

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-2

9' - 0"

A.F.F.

APC-2

8' - 4"

A.F.F.

GWB

8' - 0"

7 7 7 7

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-2

9' - 0"

A.F.F.

APC-1

9' - 0" A.F.F.

APC-1

9' - 0" A.F.F.

APC-1

9' - 0" A.F.F.

APC-1

9' - 0"

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-1

8' - 0"

A.F.F.

APC-1

9' - 0"

A.F.F.

APC-3

8' - 0"

A.F.F.

APC-1

9' - 0" A.F.F.

APC-1

9' - 0" A.F.F.

APC-1

8' - 0"

1 1

REFLECTED CEILING PLAN

LEGEND

APC-1

2' X 2' Acoustical Panel Ceiling (09 51 13)

APC-3

2' X 2' Humidity Resistant Acoustical Panel Ceiling (09 51 13)

GWB

5/8" GWB on Grid Suspension System (09 22 16)

Walls to Deck

Light Fixture (Reference E-Series Dwgs)

Return Air (Reference M-Series Dwgs)

Supply Air (Reference M-Series Dwgs)

Exit Light (Reference E-Series Dwgs)

Recessed Light Fixture Suspended Fixture in Areas with Exposed Ceilings (Reference E-Series Dwgs)

S

SOUND SYSTEM SPEAKER

(REFERENCE E-SERIES/T-

SERIES DWGS)

APC-2

2' X 2' Acoustical Panel Ceiling (09 51 13)

A. ALL CEILINGS ARE AT 9'-0" AFF, UNLESS NOTED OTHERWISE.

B. ALL BULKHEADS ARE AT 8'-10" AFF, UNLESS NOTED OTHERWISE.

C. ALL GRIDS ARE CENTERED IN ROOMS, UNLESS NOTED OTHERWISE.

D. ALL EXPOSED DUCTWORK, PIPING ETC. SHALL BE PAINTED. COLOR SELECTED

BY ARCHITECT.

E. LOCATE SPRINKLER HEADS IN CENTER OF CEILING PANEL - WHERE

APPLICABLE.

GENERAL REFLECTED CEILING

PLAN NOTES

M

IN

REF. PLANS

M

IN

09 29 00.B7 - INT GWB, 5/8" TYPE X

09 22 16.C6 - INT STEEL STUD

FRAMING, 3-5/8" @ 16" O.C.

09 51 13.A2 - CEILING FINISH, REF

ARCHITECTURAL CEILING PLANS

REF. PLANS

M

IN

V

IF

EXISTING DISPLAY, VIF.

EXISTING WALL

09 51 13.A2 - CEILING FINISH, REF

ARCHITECTURAL CEILING PLANS

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:3

:0

A M

C

R e v it L o c a l\

-0

.4

H

B ld g

A

\2

-0

.4

H B ld g

A tp h a n .r v t

2026-028.44H

10.28.2026

FIRST FLOOR

REFLECTED CEILING

PLAN

AC101

TP

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

A C

F

IR

S

T F

L O

O R

R E

F L E

C T

E D

C E

IL

IN

G P

L A

N

1/8" = 1'-0" 2A

FIRST FLOOR(1)

1/8" = 1'-0"

4A

BASEMENT

1/8" = 1'-0" 2C

SECOND FLOOR(1)

REFLECTED CEILING PLAN NOTES

REFER TO A-001 FOR GENERAL NOTES. NOT ALL NOTES APPLY TO EVERY SHEET.

# NOTE

1 REINSTALL EXISTING CEILING GRIDS WITH NEW CEILING PADS. CONTRACTOR TO

REPLACE DAMAGED EXISTING CEILING GRIDS AS REQUIRED. CEILING GRID

REPLACEMENT TO MATCH EXISTING, VIF.

2 PATCH AND REPAIR GYPSUM CEILING AS REQUIRED FROM MEP WORK. FINISH TO

MATCH EXISTING.

3 NEW CEILING GRID AND PADS, MATCH EXISTING HEIGHT AND LOCATION. REINSTALL

CEILING MOUNTED EQUIPMENT/DEVICES/FIXTURES. REF. MEP SERIES DRAWINGS.

4 NEW GWB CEILING, MATCH EXISTING HEIGHT. NEW PAINT/FINISH TO MATCH

EXISTING, VIF. REINSTALL CEILING MOUNTED EQUIPMENT/DEVICES/FIXTURES. REF.

MEP SERIES DRAWINGS

5 PATCH AND REPAIR EXISTING GWB AS REQUIRED FROM MEP WORK.

REPAINT/REFINISH ENTIRE GWB CEILING, MATCH EXISTING. REINSTALL CEILING

MOUNTED EQUIPMENT/DEVICES/FIXTURES. REF. MEP SERIES DRAWINGS

6 SLOPE CEILING GRID AND TILES UP TO BE ABOVE EXISTING WALL MOUNTED

DISPLAY SCREEN.

7 NO CEILING WORK

8 REINSTALL EXISTING CEILING GRID AND PADS, MATCH EXISTING LAYOUT AND

HEIGHT. CONTRACTORS TO REPLACE ANY DAMAGED CEILING GRIDS AND PADS,

MATCH EXISTING. REINSTALL CEILING MOUNTED EQUIPMENT/DEVICES/FIXTURES.

REF. MEP SERIES DRAWINGS.

1 1/2" = 1'-0" 4D

TYPICAL BULKHEAD DETAIL

# Revision Date

3/4" = 1'-0" 4C

SLOPE CEILING

A B C D E F GA.1 D.6

2 5A

AR100

A. WHERE UTILIZED, TAPERED INSULATION SHALL BE INSTALLED TO ACHIEVE

POSITIVE DRAINAGE WITH A MINIMUM RESULTANT SLOPE OF 1/4" PER FOOT,

UNLESS NOTED OTHERWISE.

B. LOW SLOPE ROOF AREAS SHALL HAVE A MINIMUM OF 4" RIGID INSULATION

OVER METAL ROOF DECK. SADDLES, CRICKETS, AND SLOPE PORTIONS OF

FLAT ROOF DECK SHALL BE FORMED BY TAPERED INSULATION. AREAS

WHERE TAPERED INSULATION IS ANTICIPATED HAVE BEEN INDICATED, BUT

SHALL NOT BE CONSIDERED ALL INCLUSIVE. IT IS CONTRACTOR'S

RESPONSIBILITY TO PROVIDE SLOPED SURFACES TO ACHIEVE PROPER

DRAINAGE.

C. ROOF PENETRATIONS AND EQUIPMENT SHOWN SHALL NOT BE CONSIDERED

ALL INCLUSIVE. COORDINATE WITH MECHANICAL, PLUMBING AND ELECTRICAL

DOCUMENTS TO CONFIRM PENETRATIONS AND EQUIPMENT LOCATIONS.

FLASH ALL ROOF PENETRATIONS IN ACCORDANCE WITH ROOFING

MANUFACTURER'S RECOMMENDATIONS. PROVIDE CRICKETS TO ALLOW FOR

PROPER DRAINAGE AROUND UNITS.

GENERAL ROOF PLAN NOTES

SECOND FLOOR

18' - 0"

LOW ROOF FRAMING PLAN

+16'-8"

LOW ROOF FRAMING PLAN

+16'-8"

SECOND FLOOR

18' - 0"

SECOND FLOOR

18' - 0"

10 24 00 - SCREEN WALL

07 53 23 - SQUARE TUBE WRAP FLASHING

AROUND SQUARE/RECTANGULAR STEEL TUBE

PER MANUFACTURER'S RECOMMENDATION TO

TO MAINTAIN EXISTING ROOF WARRANTY.

M

IN

10 24 00 - SUB FRAMING

05 12 00.A1 - STRUCT STEEL, REF

S-SERIES DWGS

EXISTING ROOF, VIF.

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:3

:0

A M

C

R e v it L o c a l\

-0

.4

H

B ld g

A

\2

-0

.4

H B ld g

A tp h a n .r v t

2026-028.44H

10.28.2026

ROOF PLAN

AR100

TP

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

A R

R

O O

F P

L A

N

1/8" = 1'-0" 1A

OVERALL ROOF PLAN

ROOF PLAN NOTES

REFER TO A-001 FOR GENERAL NOTES. NOT ALL NOTES APPLY TO EVERY SHEET.

# NOTE

1 ROOF TOP M/E/P/T EQUIPMENT, PROVIDE ROOF CURBS AND MANUFACTURER

STANDARD FLASHING DETAIL. REFERENCE M/E/P/T SERIES DRAWINGS . PROVIDE

TAPERED INSULATION CRICKETS AS REQUIRED AROUND THE EQUIPMNET FOR

POSITIVE DRAINAGE TO DRAINS. INSTALL FLASHING AND CURB PER

MANUFACTURER'S RECOMMENDATION TO MAINTAIN EXISTING ROOF WARRANTY.

2 10 24 00 - CONTINUOUS SCREEN WALL, REF. TO S-SERIES DWGS FOR STRUCTURAL

SUPPORT LOCATIONS. PER MANUFACTURER'S RECOMMENDATION TO MAINTAIN

ROOFING WARRANTY, PROVIDE TPO CONSTRUCTED TUBE WRAPS TO WRAP

AROUND SQUARE/RECTANGULAR STEEL TUBE STRUCTURE.

3 07 53 23 - FLEXIBLE WALKWAY PAD PER MANUFACTURER'S RECOMMENDATION TO

MAINTAIN EXISTING ROOF WARRANTY.

3/4" = 1'-0" 5A

SCREEN WALL SECTION

A-001 - ARCHITECTURAL GENERAL NOTES AND ABBREVIATIONS
AD101 - OVERALL DEMOLITION FIRST PLAN
AF101 - OVERALL FLOOR PLANS
AC101 - FIRST FLOOR REFLECTED CEILING PLAN
AR100 - ROOF PLAN

File details come from the government source that posted it. Updated .