This is a plumbing design and specification document for the HVAC Replacement project at Carmel Fire Station #44, located at 5032 E Main Street, Carmel, Indiana 46033. The document provides comprehensive plumbing symbols, abbreviations, and detailed plans for the renovation work. The project includes plumbing demolition plans for the first floor and roof, fire protection system plans for the basement, first floor, and second floor, foundation plumbing plans, and plumbing roof plans. The specifications detail the installation of new domestic water supply and waste piping systems, sanitary waste connections, natural gas pressure regulators serving multiple appliances with a total connected load of 1,657,000 BTU/H, and fire protection sprinkler systems compliant with NFPA 13 standards. Key plumbing notes require the contractor to verify existing pipe routing prior to floor slab cutting, jet and flush existing sanitary sewers before making new connections, cap and fill abandoned underground piping with flowable fill, remove fixture rough-in piping beyond finished surfaces, remove overhead piping and hangers in remodeled areas, and permanently cap abandoned vents through the roof. The document is dated October 28, 2026, and indicates bid submission deadline of December 16, 2026, at 10:00 AM through the City's e-Procurement Portal.
The plumbing specifications include schedules for sanitary waste specialties and metering/pressure reducing valves, with specific equipment such as a Zurn Wilkins reduced pressure backflow preventer (Model #975XLS2) rated at 30 GPM with a 14.3 PSI pressure drop. Natural gas regulators are specified for various equipment including range, grills, fireplaces, domestic water heaters, and rooftop units, with inlet pressure of 2 PSIG and outlet pressures ranging from 7 to 10 inches of water column. The contractor must increase the utility supply pressure for natural gas from 10 inches of water column to 2 PSI and coordinate with utility providers. Plumbing fixture rough-ins are shown for cold water, hot water, waste, vent, and storm drainage connections throughout the building. The document emphasizes contractor responsibility for field verification, coordination with other trades, and compliance with existing architectural and design standards, with all drawings and specifications remaining the property of the architect.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AV
AW
AIR
CW
GAS
GW
HW
ABANDONED ACID-RESISTANT VENT
ABANDONED ACID-RESISTANT WASTE
ABANDONED AIR
ABANDONED COLD WATER
ABANDONED GAS
ABANDONED GREASE WASTE
ABANDONED HOT WATER
ABANDONED PIPING SYSTEMS
HWR ABANDONED HOT WATER RETURN
FP ABANDONED FIRE PROTECTION
N2 ABANDONED NITROGEN
ST ABANDONED STORM
VAC ABANDONED VACUUM
V ABANDONED VENT
W ABANDONED WASTE
GALV GALVANIZED
STP
HWR HOT WATER RETURN
STS, STR
STRUCT
HWCP
HR
HO
HD
HORIZ
HOUR
HORIZONTAL
HEAD (FT.)
HUB OUTLET
HB
GC
GPM
GT
GPH
HOSE BIB
GENERAL CONTRACTOR
GALLONS PER MINUTE
GALLONS PER HOUR
GREASE TRAP
STD
ST
SSK
SSD
SS
SPEC
SPG
SHT
SK
SH
SECT
SF
SB
SCW
FLOOR DRAIN
FIRE PROTECTION CONTRACTOR
FIRE DEPARTMENT CONNECTION
G
GAL
GA
FPC
FOV
FP
FT
FPM
FTG
GALLON
GAUGE
NATURAL GAS
FIRE PROTECTION
FUEL OIL VENT
FEET PER MINUTE
FOOTING
FOOT/FEET
FE
FHC
FH
FOS
FOR
FLR
FCO
FDC
FD
FIRE EXTINGUISHER
FUEL OIL RETURN
FUEL OIL SUPPLY
FIRE HOSE CABINET
FLOOR
FIRE HOSE
FLOOR CLEANOUT
RO
RPM
RM
RECIR
RH
RD
RCP
R
PVC
EXIST
EXP
°F
ET
EWC
EW
DEGREES FAHRENHEIT
EXPANSION
EXISTING
EXPANSION TANK
EMERGENCY EYEWASH
ELECTRIC WATER COOLER
EMER
ENCL
ES
EQUIP
EFF
ELEV
ELEC
EMERGENCY
EMERGENCY SHOWER
EQUIPMENT
ENCLOSURE
ELEVATION
ELECTRIC
EFFICIENCY
PSIG
PRESS
PRV
PSI
PREFAB
PPM
POC
PIV
PLT
PER
PI
PH
PD
PC
STORAGE TANK PUMP
STORAGE TANK SUPPLY AND RETURN
STRUCTURE(E), (AL)
SUB SURFACE (FOOTING) DRAIN
STORAGE TANK
STAINLESS STEEL
SERVICE SINK
STANDARD
SPECIFICATIONS
SPECIAL GAS
SHEET
SINK
SOFT COLD WATER (DOMESTIC)
SQUARE FOOT
SHOWER
SECTION
SITZ BATH
RODDING HOLE
REVERSE OSMOSIS WATER
REVOLUTIONS PER MINUTE
ROOM
RECIRCULAT(E), (OR), (ING)
REINFORCED CONCRETE PIPE
ROOF DRAIN
THERMAL RESISTANCE
POLYVINYL CHLORIDE
POST INDICATOR VALVE
POINT OF CONNECTION (NEW TO EXISTING)
POUNDS PER SQUARE INCH
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH GAUGE
PRESSURE
PARTS PER MILLION
PREFABRICATED
PLASTER TRAP
PRESSURE DROP (IN OR WG AS NOTED)
PERCENT
PRESSURE INDICATOR
PHASE
PLUMBING CONTRACTOR
MISC
ECO
EC
DN
DS
DF
DWG
DWH
EXTERIOR CLEANOUT
ELECTRICAL CONTRACTOR
DRINKING FOUNTAIN
DOMESTIC WATER HEATER
DRAWING
DOWNSPOUT
DOWN
CW
D
COLD WATER (DOMESTIC)
DRAIN
P
OSD
OFOI
OFCI
OFD
OE
OA
O
NA
NO
NTS
NIC
NC
N
MTD
CONTRACTOR FURNISHED/OWNER INSTALLED
BRITISH THERMAL UNIT PER HOUR
CO
CI
CONN
CO2
CFOI
CARBON DIOXIDE
CONNECTION
CAST IRON
CLEANOUT
BT
CD
BTUH
BOP
BLDG
BATHTUB
CONDENSATE DRAIN
BOTTOM OF PIPING
BUILDING
MIN
MH
MECH
MC
MBH
MS
MB
MAX
LPC
MA
LV
LFC
LP
LEC
AREA DRAIN
AMPERE (AMP, AMPS)
A
AW
BFC
AMP
ARCH
AV
APD
APPROX
COMPRESSED AIR
BELOW FINISHED CEILING
ACID WASTE
AIR PRESSURE DROP (IN WG)
ARCHITECT (URAL)
APPROXIMAT(E), (LY)
ACID VENT
ADJ
AE
AFF
ALTER
AD
ADA
ADJUSTABLE
ABOVE FINISHED FLOOR
ANESTHESIA EVACUATION
ALTERNATE
AMERICAN DISABILITIES ACT
LBS
LAB
LA
L
KW
INV
KEC
IN
INDIC
INSUL
INT
INCL
ID
HZ
VACUUM PUMP DISCHARGE
W/O WITHOUT
MISCELLANEOUS
OWNER FURNISHED/CONTRACTOR INSTALLED
OWNER FURNISHED/OWNER INSTALLED
OPEN SITE DRAIN
PUMP
ORAL EVACUATION
OVERFLOW DRAIN
OUTSIDE AIR
OXYGEN
NOT APPLICABLE
NORMALLY CLOSED
NORMALLY OPEN
NOT TO SCALE
NOT IN CONTRACT
NITROGEN
MOUNTED
ZN
WTR
YD
WPD
WP
ZONE
WATER PRESSURE DROP
YARD DRAIN
WEATHERPROOF
WATER
THOUSANDS OF BTU PER HOUR
MECHANICAL
MINIMUM
MANHOLE
MECHANICAL CONTRACTOR
MOP SINK
MOP BASIN
MAXIMUM
LABORATORY FURNISHINGS CONTRACTOR
LABORATORY PLUMBING CONTRACTOR
LABORATORY EQUIPMENT CONTRACTOR
LABORATORY VACUUM
MEDICAL AIR
LIQUID PETROLEUM
WH
WG
W.C.
WCO
WC
W/
VV
VPD
VT
VTR
WATER CLOSET
WATER COLUMN
WALL CLEANOUT
WATER GAUGE
WALL HYDRANT
VITRIFIED TILE
VENT THROUGH ROOF
VACUUM VENT
WITH
VB
VERT
VIF
VC
VAC
VAR
VA
VACUUM BREAKER
VERIFY IN FIELD
VACUUM CLEANING
VERTICAL
VOLT AMPERE
VACUUM
VARIABLE
TEMPERATURE AND PRESSURE
THERMOSTATIC MIXING VALVE
UNLESS NOTED OTHERWISE
INVERT
KITCHEN EQUIPMENT CONTRACTOR
LABORATORY AIR
LABORATORY
POUND
KILOWATT
LAVATORY
INCH/INCHES
INSULAT(E), (ED), (ION)
INCLUD(E), (ED)
INDICATOR
INTERIOR
FREQUENCY (MEGAHERTZ)
INSIDE DIAMETER
UNO
UR
TYP.
TS
TP
URINAL
TRAP PRIMER
TAMPER SWITCH
TYPICAL
TEMP
TMV
T&P
SU
TEMPERATURE
SHOWER UNIT
ABBREVIATIONS
HW HOT WATER (DOMESTIC)
T TEMPERED WATER
DWS DOMESTIC WATER SOFTNER
HOT WATER RECIRCULATING PUMP
ABBREVIATIONS
M-301
M-501
SECTION REFERENCE
DETAIL REFERENCE
DRAWING NOTATIONS
NOTE:
ALL SYMBOLS AND ABBREVIATIONS
MAY NOT BE USED FOR THIS PROJECT
NEW TO EXISTING
DEMO TO THIS POINT
EQUIPMENT TAG - (SEE SCHEDULE SHEETS)XXX-1
XXX-1 FIXTURE TAG - (SEE SCHEDULE SHEETS)
FIRE PROTECTION SYMBOLS
A
TS
F
F
ALARM VALVE
ZONE VALVE (OS&Y)
SIDEWALL SPRINKLER HEAD
CONCEALED PENDANT SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
PENDANT SPRINKLER HEAD
DRY PENDANT SPRINKLER HEAD
FIRE DEPT. CONNECTION
POST INDICATOR VALVE
FLOW SWITCH
TAMPER SWITCH
FIRE WATER MAIN
140° HW
140° HWR
160° HW
160° HWR
AV
AW
AIR
CW
HW
HWR
FPD
FP
FPPA
FPW
G (11 in-wc)
G (2 psig)
GW
LCW
LHR
LA
LHW
LVAC
LVE
N2
PWR
PWS
RO
ROR
SCW
SHW
ST
TW
VAC
V
W
140° DOMESTIC HOT WATER
140° DOMESTIC HOT WATER RETURN
160° DOMESTIC HOT WATER
160° DOMESTIC HOT WATER RETURN
ACID RESISTANT VENT
ACID RESISTANT WASTE
AIR
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
FIRE PROTECTION DRY
FIRE PROTECTION OTHER
FIRE PROTECTION PRE-ACTION
FIRE PROTECTION WET
GAS (11" w.c.)
GAS (2 psig)
GREASE WASTE
LAB AIR
LAB COLD WATER
LAB HOT WATER
LAB HOT WATER RETURN
LAB VACUUM
LAB VACUUM EXHAUST
NITROGEN
PURE WATER RETURN
PURE WATER SUPPLY
REVERSE OSMOSIS WATER
REVERSE OSMOSIS WATER RETURN
SOFT COLD WATER
SOFT HOT WATER
STORM
TEMPERED WATER
VACUUM
VENT
WASTE
PIPING SYSTEMS
CA COMBUSTION AIR
EA EXHAUST AIR
G (6 in-wc) GAS (6" w.c.)
G (5 psig) GAS (5 psig)
RCW RAW COLD WATER
GENERAL DUTY VALVES & FITTINGS
A
CONCENTRIC REDUCER
DOMESTIC COLD WATER VALVE BOX
ECCENTRIC REDUCER
PRESSURE REDUCING VALVE
(P) = PRESSURE
VACUUM BREAKER
GAS COCK
PETE'S PLUG
PIPE EXPANSION JOINT
FLEXIBLE PIPING CONNECTOR
Y-STRAINER W/BLOWDOWN
VALVE & CAP
PIPE ANCHORS
PIPE GUIDES
THERMOMETER WELL
AUTOMATIC AIR VENT
GAUGE CONNECTION(S) & WELL
THERMOMETER & WELL
MANUAL AIR VENT
AUTOMATIC BALANCING VALVE
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
UNION
MANUAL BALANCING VALVE
ANGLE VALVE
PLUG VALVE
PRESSURE REGULATING VALVE
BUTTERFLY VALVE
VALVE - SEE SPECIFICATIONS
FOR VALVE TYPE
PIPE CONTINUED ON ANOTHER
DRAWING
CHECK VALVE
CAPPED PIPE
RISE IN PIPING
DROP IN PIPING
MEDICAL GAS SYSTEMS
CO2 CARBON DIOXIDE
LN LIQUID NITROGEN
MA
MO
MV
MEDICAL AIR
MEDICAL OXYGEN
MEDICAL VACUUM
MVE MEDICAL VACUUM EXHAUST
N NITROGEN
NO NITROUS OXIDE
WAGD WASTE ANESTHETIC GAS DISPOSAL
MEDICAL GAS SYMBOLS
MEDICAL VACUUM INLET
MEDICAL OXYGEN OUTLET
MEDICAL AIR OUTLET
CARBON DIOXIDE OUTLET
WAGD INLET
NITROUS OXIDE OUTLET
NITROUS OUTLET
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:4
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
PLUMBING SYMBOLS AND
ABBREVIATIONS
P-001
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P -0
P
L U
M B
IN
G
S Y
M B
O L S
A N
D A
B B
R E
V
IA
T
IO
N S
# Revision Date
EX. 3" G
EX. 3" G
EX. 3" G
EX. 1" G
EX. 1" G
EX. 1" G
EX. 1" G
EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
EX. 3" G
EX. 2" G EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
EX. 2" G
EX. 1 1/2" G
EX. 1 1/2" G
TO GAS RANGE
EX. 1 1/2" G
EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1 1/4" G
TO GAS GRILL AND FIRE PLACE
EX. 2" G
EX. 2" G
EX. 1 1/2" G
EX. DWH
EX. 1 1/4" G
EX. 1 1/4" G
EX. 3/4" G
EX. 1 1/4" G
EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
TO ROOF
EX. SERVICE SINK
EX. FD
EX. WMB
EX. 1 1/4" G
EX. 1/2" CW
EX. 1/2" CW
EX. 1/2" CW
EX. 3/4" CW
EX. 3/4" CW
EX. 1 1/2" CW
EX. 3/4" CW
EX. 3/4" CW
EX. NFWH
EX. 2" CWEX. 1/2" CW
EX. 2" CW
EX. 1/2" CW
EX. 2" CW
EX. 2" CW
EX. 3/4" CW
EX. 2 1/2" CW
EX. 2 1/2" CW
EX. 2 1/2" CW
INCOMING
WATER SERVICE
EX. 1 1/2" V
EX. 1 1/2" V
EX. 1 1/2" V
EX. 2" V TO SECOND FLOOR
1. EXISTING PIPE ROUTING, AS SHOWN ON DRAWINGS, IS BASED UPON RECORD
DOCUMENTS AND FIELD SURVEYS. ACTUAL ROUTE OF CONCEALED PIPING MAY
VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO
SAW CUTTING OF FLOOR SLABS.
2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS
WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.
3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN
PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.
4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN
WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT
BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH
EXISTING FINISH.
5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,
CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE
UNLESS OTHERWISE INDICATED.
6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED
IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW
ROOF FOR A WATER TIGHT SEAL.
PLUMBING RENOVATION NOTES
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:5
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
FIRST FLOOR
DEMOLITION PLUMBING
PLAN
PPD01
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P P
D F
IR
S
T F
L O
O R
D E
M O
L
IT
IO
N
P L U
M B
IN
G
P L A
N
1/4" = 1'-0" 2A
FIRST FLOOR DEMOLITION ENLARGED PLUMBING PLAN
EX. MB
EX. SERVICE SINK
1. EXISTING PIPE ROUTING, AS SHOWN ON DRAWINGS, IS BASED UPON RECORD
DOCUMENTS AND FIELD SURVEYS. ACTUAL ROUTE OF CONCEALED PIPING MAY
VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO
SAW CUTTING OF FLOOR SLABS.
2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS
WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.
3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN
PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.
4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN
WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT
BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH
EXISTING FINISH.
5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,
CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE
UNLESS OTHERWISE INDICATED.
6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED
IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW
ROOF FOR A WATER TIGHT SEAL.
PLUMBING RENOVATION NOTES
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1" G
EX. 1" G
EX. 1 1/4" G
TO EX. GAS GRILL
DEMO ABOVE ROOF DECK
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:0
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
PLUMBING DEMOLITION
ROOF PLAN
PRD01
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P R
D P
L U
M B
IN
G
D E
M O
L
IT
IO
N
R O
O F
P L A
N
1/4" = 1'-0" 2A
PLUMBING DEMOLITION ENLARGED ROOF PLAN
1. SPRINKLER SCHEDULE:
ROOMS WITHOUT CEILINGS: UPRIGHT SPRINKLERS
ROOMS WITH CEILINGS: SEMI-RECESSED SPRINKLER HEADS
WALL MOUNTING: SIDEWALL SPRINKLER HEADS
SUBJECT TO FREEZING: DRY PENDANT SPRINKLER HEADS
2. ALL SPRINKLER COVERAGE SHALL COMPLY WITH MINIMUM STANDARDS AS
ESTABLISHED BY NFPA 13, INCLUDING OFFICE SPACES.
3. WHERE APPLICABLE, INCOMING FIRE PROTECTION WATER SERVICE AND FIRE
DEPARTMENT CONNECTION MAIN FROM 5'-0" OUTSIDE OF BUILDING TO FLANGED
CONNECTION 12" ABOVE FLOOR OR FROM WALL SHALL BE PROVIDED BY
DIVISION 22.
4. WHERE MAIN ELECTRIC ROOMS HAVE A 2-HOUR RATING, DO NOT INSTALL
SPRINKLER COVERAGE.
5. DO NOT ROUTE SPRINKLER PIPING OVER ANY TELEDATA, IDF, MDF OR SIMILAR
ROOM. PROVIDE SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD
LOCATED ABOVE DOOR WHEREVER POSSIBLE.
6. DO NOT ROUTE SPRINKLER PIPING OVER ANY ELECTRICAL ROOM. PROVIDE
SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD LOCATED ABOVE
DOOR WHEREVER POSSIBLE.
FIRE PROTECTION GENERAL NOTES
ELEV.
EV-1-0
MDF
003A
RR
CUSTODIAL
004A
STORAGE
006A
RR
EMERGENCY OPERATIONS
PLANNING
OFFICE
OFFICE
OFFICE
OFFICE
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:1
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
BASEMENT FIRE
PROTECTION PLAN
FP100
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
F P
B
A S
E M
E N
T F
IR
E
P R
O T
E C
T
IO
N P
L A
N
1/4" = 1'-0" 2A
BASEMENT FIRE PROTECTION
CONTRACTOR SHALL TEMPERARILY SUPPORT SPRINKLER HEADS WHILE CEILING IS BEING
REMOVED TO ACCOUNT FOR HVAC REWORK. CONTRACTOR SHALL ADJUST SPRINKLER HEAD TO
ACCOUNT FOR CEILING INSTALL. CONTRACTOR SHALL ADJUST SPRINKLER HEADS IN NOTED
SPACE TO COMPLY WITH NFPA 13 REQUIREMENTS. CONTRACTOR TO COORDINATE WITH OTHER
TRADES AS REQUIRED.
ROOMS WITH CEILINGS: SEMI-RECESSED SPRINKLER HEADS
WALL MOUNTING: SIDEWALL SPRINKLER HEADS
SUBJECT TO FREEZING: DRY PENDANT SPRINKLER HEADS
2. ALL SPRINKLER COVERAGE SHALL COMPLY WITH MINIMUM STANDARDS AS
ESTABLISHED BY NFPA 13, INCLUDING OFFICE SPACES.
3. WHERE APPLICABLE, INCOMING FIRE PROTECTION WATER SERVICE AND FIRE
DEPARTMENT CONNECTION MAIN FROM 5'-0" OUTSIDE OF BUILDING TO FLANGED
CONNECTION 12" ABOVE FLOOR OR FROM WALL SHALL BE PROVIDED BY
DIVISION 22.
4. WHERE MAIN ELECTRIC ROOMS HAVE A 2-HOUR RATING, DO NOT INSTALL
SPRINKLER COVERAGE.
5. DO NOT ROUTE SPRINKLER PIPING OVER ANY TELEDATA, IDF, MDF OR SIMILAR
ROOM. PROVIDE SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD
LOCATED ABOVE DOOR WHEREVER POSSIBLE.
6. DO NOT ROUTE SPRINKLER PIPING OVER ANY ELECTRICAL ROOM. PROVIDE
SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD LOCATED ABOVE
DOOR WHEREVER POSSIBLE.
FIRE PROTECTION GENERAL NOTES
CUSTODIAL
ADA RR
RR
GEAR ROOM
CAPTAIN'S OFFICE
OFFICE STORAGE
ELEV.
EV-1-1
STOR.
STAIR 2.1
ST 2-1
APPARATUS BAY
RR
RISER
EMS STORAGE
AIR COMPRESSOR
STAIR 1
ST 1-1
CORRIDOR
OFFICE / WATCHROOM
VESTIBULE
TOOL ROOM
ELEC
EMERGENCY OPERATIONS
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:2
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
FIRST FLOOR FIRE
PROTECTION PLAN
FP101
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
F P
F
IR
S
T F
L O
O R
F
IR
E P
R O
T E
C T
IO
N P
L A
N
1/4" = 1'-0" 2A
FIRST FLOOR FIRE PROTECTION PLAN
CONTRACTOR SHALL TEMPERARILY SUPPORT SPRINKLER HEADS WHILE CEILING IS BEING
REMOVED TO ACCOUNT FOR HVAC REWORK. CONTRACTOR SHALL ADJUST SPRINKLER HEAD TO
ACCOUNT FOR CEILING INSTALL. CONTRACTOR SHALL ADJUST SPRINKLER HEADS IN NOTED
SPACE TO COMPLY WITH NFPA 13 REQUIREMENTS. CONTRACTOR TO COORDINATE WITH OTHER
TRADES AS REQUIRED.
ROOMS WITH CEILINGS: SEMI-RECESSED SPRINKLER HEADS
WALL MOUNTING: SIDEWALL SPRINKLER HEADS
SUBJECT TO FREEZING: DRY PENDANT SPRINKLER HEADS
2. ALL SPRINKLER COVERAGE SHALL COMPLY WITH MINIMUM STANDARDS AS
ESTABLISHED BY NFPA 13, INCLUDING OFFICE SPACES.
3. WHERE APPLICABLE, INCOMING FIRE PROTECTION WATER SERVICE AND FIRE
DEPARTMENT CONNECTION MAIN FROM 5'-0" OUTSIDE OF BUILDING TO FLANGED
CONNECTION 12" ABOVE FLOOR OR FROM WALL SHALL BE PROVIDED BY
DIVISION 22.
4. WHERE MAIN ELECTRIC ROOMS HAVE A 2-HOUR RATING, DO NOT INSTALL
SPRINKLER COVERAGE.
5. DO NOT ROUTE SPRINKLER PIPING OVER ANY TELEDATA, IDF, MDF OR SIMILAR
ROOM. PROVIDE SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD
LOCATED ABOVE DOOR WHEREVER POSSIBLE.
6. DO NOT ROUTE SPRINKLER PIPING OVER ANY ELECTRICAL ROOM. PROVIDE
SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD LOCATED ABOVE
DOOR WHEREVER POSSIBLE.
FIRE PROTECTION GENERAL NOTES
DORM
213A
BATH
213B
LOCKER
DORM
214A
DORM
215A
LOCKER
LOCKER
BATH
214B
BATH
215B
LAUNDRY
STORAGE
MECH.
JANITOR
PANTRY
PANTRY
PANTRY
BATH
220B
LOCKER
LOCKER
LOCKER
LOCKER
LOCKER
BATH
217B
BATH
216B
BATH
219B
BATH
218B
DORM
216A
DORM
217A
DORM
218A
DORM
219A
DORM
220A
KITCHEN
STAIR 1
ST 1-2
STAIR 2
ST 2-2
DAY ROOM
DINING
SUPPLY CLOSET
CORRIDOR
CORRIDOR
CORRIDOR
ELECTRICAL
PANELS
FIRST FLOOR ROOF
PATIO
FIRST FLOOR ROOF
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:3
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
SECOND FLOOR FIRE
PROTECTION PLAN
FP102
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
F P
S
E C
O N
D F
L O
O R
F
IR
E P
R O
T E
C T
IO
N
P L A
N
1/4" = 1'-0" 2A
SECOND FLOOR FIRE PROTECTION PLAN
CONTRACTOR SHALL TEMPERARILY SUPPORT SPRINKLER
HEADS WHILE CEILING IS BEING REMOVED TO ACCOUNT FOR
HVAC REWORK. CONTRACTOR SHALL ADJUST SPRINKLER HEAD
TO ACCOUNT FOR CEILING INSTALL. CONTRACTOR SHALL
ADJUST SPRINKLER HEADS IN NOTED SPACE TO COMPLY WITH
NFPA 13 REQUIREMENTS. CONTRACTOR TO COORDINATE WITH
OTHER TRADES AS REQUIRED.
VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO
SAW CUTTING OF FLOOR SLABS.
2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS
WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.
3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN
PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.
4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN
WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT
BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH
EXISTING FINISH.
5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,
CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE
UNLESS OTHERWISE INDICATED.
6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED
IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW
ROOF FOR A WATER TIGHT SEAL.
PLUMBING RENOVATION NOTES
EX. MB
EX. DWH
EX. FD
EX. FD
EX. 2" W UP
TO WMB
EX. 2" W UP TO
SERVICE SINK
2A
P-902
3" W
1 1/2" V
FD-1
3" WFD-1
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" WEX. 3" W
EX. 2" W
EX. 3" W
EX. 2" W
EX. 4" W EX. 2" W
CONTRACTOR TO DEMO ANY
PIPE TO MAKE NEW CONNECTION
CONTRACTOR TO DEMO ANY
PIPE TO MAKE NEW CONNECTION
BASEMENT
BASEMENT
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:4
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
FOUNDATION PLUMBING
PLAN
PF101
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P F
F
O U
N D
A T
IO
N
P L U
M B
IN
G
P L A
N
PLUMBING FIXTURE ROUGH-IN LEGEND
MARK
FIXTURE CONNECTION
CW HW W V ST
FD-1 3"
# Revision Date
1/4" = 1'-0" 2A
FOUNDATION PLUMBING ENLARGED PLAN
VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO
SAW CUTTING OF FLOOR SLABS.
2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS
WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.
3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN
PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.
4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN
WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT
BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH
EXISTING FINISH.
5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,
CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE
UNLESS OTHERWISE INDICATED.
6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED
IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW
ROOF FOR A WATER TIGHT SEAL.
PLUMBING RENOVATION NOTES
B-1
UP TO ROOF
UP TO ROOF
3/4" G
3/4" G
3/4" G
GPR-3
GPR-4
GPR-2
GPR-1
GPR-5
UP TO GAS GRILL AND FIRE PLACE
GPR-9
GPR-8
1 1/4" G
1 1/2" G
1" G
2D
P-901
2D
P-901
2D
P-901
2D
P-901
2D
P-901
2D
P-901
EX. RH-4
EX. RH-3
EX. RH-1 EX. RH-2
UP TO GAS RANGE
EX. 1 1/2" G
EX. 1 1/2" G
EX. 3/4" G
EX. 3/4" G
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1 1/4" G
1 1/4" G
EX. 3/4" G
EX. 3/4" GEX. 2" G
EX. 3" G
EX. 1" G
EX. 1" G
EX. 1" G
EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
EX. 3" G
GPR-6
EX. GFUH
EX. 3/4" G
EX. 1 1/4" G
CUSTODIAL
ADA RR
RR
GEAR ROOM
CAPTAIN'S OFFICE
OFFICE STORAGE
ELEV.
EV-1-1
STOR.
STAIR 2.1
ST 2-1
APPARATUS BAY
RR
RISER
EMS STORAGE
AIR COMPRESSOR
STAIR 1
ST 1-1
CORRIDOR
OFFICE / WATCHROOM
VESTIBULE
TOOL ROOM
ELEC
FITNESS ROOM
EX. DWH
EX. 2" G
FD-1
EX. SERVICE SINK
EX. FD
EX. WMB
TOTAL CONNECTED LOAD:
1,657,000 BTU/H
2D
P-901
EX. 3/4" G
EX. 1 1/4" G
EX. 1 1/4" G
BFP-1
EX. 1/2" CW
EX. NFWH
EX. 1 1/4" G
FD-1
2A
P-902
EX. 2 1/2" CW
EX. 2 1/2" CW
EX. 2 1/2" CW
EX. 2 1/2" CW
EX. 2" CW
1 1/2" V
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:5
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
FIRST FLOOR PLUMBING
PLAN
PP101
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P P
F
IR
S
T F
L O
O R
P L U
M B
IN
G
P L A
N
1/4" = 1'-0" 2A
FIRST FLOOR PLUMBING ENLARGED PLAN
EX. MB
EX. SERVICE SINK
PLUMBING PLAN NOTES
NOT ALL NOTES APPLY TO EVERY SHEETS.
# NOTE
1 CONTRACTOR SHALL INCREASE THE ULTILITY SUPPLY PRESSURE FOR NATURAL
GAS. CONTRACTOR SHALL INCREASE PRESSURE FROM 10" W.C. TO 2 PSI.
CONTRACTOR TO COORIDINATE WITH UTILITIES AS REQUIRED.
2 MAKE UP WATER CONNECTION. REFER TO M-SERIES FOR CONTINUATION
3 MAX MOUNTING HEIGHT OF 54" AFF
PLUMBING FIXTURE ROUGH-IN LEGEND
MARK
FIXTURE CONNECTION
CW HW W V ST
FD-1 3"
INCOMING
WATER SERVICE
VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO
SAW CUTTING OF FLOOR SLABS.
2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS
WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.
3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN
PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.
4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN
WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT
BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH
EXISTING FINISH.
5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,
CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE
UNLESS OTHERWISE INDICATED.
6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED
IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW
ROOF FOR A WATER TIGHT SEAL.
PLUMBING RENOVATION NOTES
RTU-1
EX. MAU-1
RTU-2
EX. 1 1/4" G
TO EX. GAS GRILL
GPR-7
GPR-10
1 1/4" G
1 1/4" G 1/2" G
3/4" G 3/4" G
1/2" G
1/2" G
1/2" G
3/4" G
3/4" G
GPR-11
3/4" G
3/4" G
2D
P-901
2D
P-901
2D
P-901
RECONNECT ABOVE ROOF DECK
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:0
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
PLUMBING ROOF PLAN
PR101
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P R
P
L U
M B
IN
G
R O
O F
P L A
N
1/4" = 1'-0" 2A
PLUMBING ENLARGED ROOF PLAN
6" LONG HARDWOOD
BLOCK SHAPED TO
PIPE AND HANGER
INSULATION
PIPEPIPE
INSULATION
HEAVY DUTY
CLEVIS HANGER
SUPPORT NUT
LOCKING NUT
HANGER ROD
14 GUAGE ZINC
COATED SHEET STEEL
SADDLE, AT LEAST 6"
LONG
STEEL ROD
COUPLING
THREADED STEEL
HANGER ROD
UNI-STRUT
TRAPEZE
SUPPORT
STRUT PIPE CLAMP
PIPE INSULATION MATERIAL
(REFER TO SPECIFICATIONS)
SYSTEM PIPE (REFER TO
DRAWINGS FOR TYPE OF
SYSTEM AND SIZE OF PIPE)
CARRIER PIPE - (ONLY
AT CLAMP LOCATIONS)
TRAFFIC PAD
PIPESTAND
SADDLE
INSULATED PIPE
PIPE STRAP
ROOF SURFACE
M
IN
PLAN NOTES:
1.PIPESTAND MIRO MODEL NO. 3-R WITH ROLLER.
2. PROVIDE SADDLE UNDER INSULATED PIPE.
3. INSTALL PIPE STRAP USING #10 STAINLESS STEEL SCREWS PER UNIT MFR
RECOMMENDATION. PROVIDE LOOSE INSTALLATIN TO PROVIDE FREE MOVEMENT.
4.SPACE PIPESTANDS TO OBTAIN A MAX. LOAD WEIGHT OF 100 LBS. PER PIPE STAND.
MAX. SPACING SHALL BE 10'.
5. INSTALL MIRO MODEL NO. 3-R SPACERS AS REQUIRED TO PROVIDE MIN. 6"
CLEARANCE BETWEEN ROOF SURFACE AND BOTTOM OF PIPE INSULATION.
6. INSTALL TRAFFIC PAD OR MIRO DECK PLATE BELOW EACH PIPESTAND. ADJUST THE
HEIGHT OF EACH PIPE STAND TO ACHIEVE EVEN LOAD WEIGHT AT ALL PIPESTANDS.
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:1
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
PLUMBING DETAILS
P-501
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P -5
P
L U
M B
IN
G
D E
T A
IL
S
NOT TO SCALE
2A
PIPE HANGER (6" & SMALLER) DETAIL
NOT TO SCALE
2B
TYPICAL TRAPEZE PIPE SUPPORT DETAIL
NOT TO SCALE
2C
ROOFTOP PIPESTAND DETAIL
SANITARY WASTE PIPING SPECIALTIES SCHEDULE (221319)
MARK
FIXTURE W
CONNECTION ACCESSORIES NOTESMANUFACTURER MODEL DESCRIPTION
FD-1 J.R. SMITH #2005Y-F-37-U-PB DUCO CAST IRON BODY WITH FLASHING COLLAR, ADJUSTABLE ROUND STRAINER HEAD, POLISHED BRONZE STRAINER, FLUSH WITH FLOOR FUNNEL WITH ANTI-SPLASH RIM AND GRATE 3" TRAPGUARD BY PROSET, NO SUBSTITUTIONS
METERING AND PRESSURE REDUCING VALVES SCHEDULE (221119)
MARK
EQUIPMENT PLUMBING
NOTESMANUFACTURER MODEL DESCRIPTION FLOW RATE (GPM) PRESSURE DROP (PSI)
BFP-1 ZURN WILKINS #975XLS2 - 3/4" REDUCED PRESSURE BACKFLOW PREVENTER 30 14.3
EX. DWH
DIRT LEG
DIRT LEG
DIRT LEG
DIRT LEG
TO EX. GAS RANGE
TO EX. GAS GRILL
AND FIRE PLACE
1 1/4" G 1 1/2" G
GPR-8
B-1
1 1/4" G
1 1/4" G
1/2" G
1/2" G
1/2" G
GPR-7
EX. MAU-1
1/2" G
3/4" G
GPR-10
1/2" G 3/4" G
RTU-1
GPR-6
3/4" G
1" G
GPR-2
GPR-4
GPR-3
EX. RH-4
EX. GFUH
EX. RH-3
EX. RH-1
GPR-1
EX. RH-2 3/4" G
3/4" G
3/4" G
RTU-2
3/4" G
3/4" G
GPR-11
3/4" G
3/4" G
GPR-5
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1 1/4" G
EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
EX. 1 1/2" G
EX. 3/4" G
EX. 3/4" G
EX. 1 1/2" G
EX. 1 1/2" G
EX. 2" G
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1 1/4" G
EX. 1 1/2" G
EX. 2" G
EX. 3" G
EX. 2" G
EX. 3" G
EX. 1" G
EX. 1" G
EX. 3" G
EX. 3" G
EX. 3" G
EX. 3" G
EX. 1" G
EX. 1" G
EX. 3/4" G
EX. 3/4" G
EX. 3/4" G
EX. 2" G
EX. 3/4" G
EX. 3/4" G
EX. 1 1/4" G
EX. 3/4" G
EX. 1 1/4" G
1 1/4" G
TOTAL CONNECTED LOAD:
1,657,000 BTU/H
GPR-9
RECONNECT ABOVE ROOF DECK
CONTRACTOR SHALL COORDINATE
METER AND UTILITY REQUIREMENTS
WITH UTILITY PROVIDER AS REQUIRED.
CONFIRM INLET SIDE
PIPE SIZE WITH PLANS
SHUTOFF VALVE
PRESSURE GAUGE
UNION
5 TIMES PIPE DIAMETER OF STRAIGHT
PIPE ON INLET SIDE OF REGULATOR
NATURAL GAS PRESSURE REGULATOR (GPR-X)
SEE PLANS FOR LOCATION AND THIS SHEET
FOR SCHEDULE INFORMATION
UNION
10 TIMES PIPE DIAMETER OF STRAIGHT
PIPE ON OUTLET SIDE OF REGULATOR
PRESSURE GAUGE
SHUTOFF VALVE
CONFIRM OUTLET SIDE
PIPE SIZE WITH PLANS
THREADOLETTE FITTING
THREADOLETTE FITTING
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:2
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
NATURAL GAS
ISOMETRIC
P-901
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P -9
N
A T U
R A
L G
A S
I S
O M
E T
R
IC
IDENTITY DATA PRESSURE NATURAL GAS
MARK DESCRIPTION VENTING
INLET
(psig)
OUTLET (inches w.c.)
TOTAL CONNECTED
LOAD (BTU/H)
EQUIPMENT
SERVED
GPR-1 GAS PRESSURE REGULATOR VENT LIMITING 2 10 100,000 EX. RH-1 AND EX. RH-2
GPR-2 GAS PRESSURE REGULATOR VENT LIMITING 2 10 50,000 EX. RH-3
GPR-3 GAS PRESSURE REGULATOR VENT LIMITING 2 10 50,000 EX. RH-4
GPR-4 GAS PRESSURE REGULATOR VENT LIMITING 2 10 250,000 EX. RANGE
GPR-5 GAS PRESSURE REGULATOR VENT LIMITING 2 10 132,000 EX. GAS GRILL
GPR-6 GAS PRESSURE REGULATOR VENT LIMITING 2 10 30,000 EX. GFUH
GPR-7 GAS PRESSURE REGULATOR VENT TO THE OUTSIDE 2 10 60,000 EX. MAU-1
GPR-8 GAS PRESSURE REGULATOR VENT LIMITING 2 10 300,000 EX. DWH
GPR-9 GAS PRESSURE REGULATOR VENT LIMITING 2 7 285,000 B-1
GPR-10 GAS PRESSURE REGULATOR VENT TO THE OUTSIDE 2 10 150,000 RTU-1
GPR-11 GAS PRESSURE REGULATOR VENT TO THE OUTSIDE 2 10 250,000 RTU-2
NOT TO SCALE
2A
NATURAL GAS ISOMETRIC
NOT TO SCALE
2D
NATURAL GAS PRESSURE REGULATOR PIPING DIAGRAM
PLUMBING ISOMETRIC PLAN NOTES
# NOTE
1 CONTRACTOR SHALL INCREASE THE ULTILITY SUPPLY PRESSURE FOR NATURAL
GAS. CONTRACTOR SHALL INCREASE PRESSURE FROM 10" W.C. TO 2 PSI.
CONTRACTOR TO COORIDINATE WITH UTILITIES ARE REQUIRED.
VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO
SAW CUTTING OF FLOOR SLABS.
2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS
WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.
3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN
PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.
4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN
WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT
BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH
EXISTING FINISH.
5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,
CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE
UNLESS OTHERWISE INDICATED.
6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED
IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW
ROOF FOR A WATER TIGHT SEAL.
PLUMBING RENOVATION NOTES
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 4" W
EX. 2" W
EX. 4" W
EX. 4" W
EX. 2" W
EX. 2" W
EX. 2" W
EX. 2" W
EX. 2" W
EX. 2" W
EX. DWH
EX. WMB
EX. FD
EX. FD
EX. SERVICE
SINK
EX. 2" W
EX. 2" W
EX. NFWH
EX. 3/4" CW
EX. 3/4" CW
EX. 3/4" CW
EX. 3/4" CW
UP TO LEVEL 02
UP TO LEVEL 02
UP TO LEVEL 02
EX. 1/2" CW
EX. 1/2" CW
EX. 1 1/2" CW
EX. 1 1/2" CW
EX. 2" CW
EX. 2" CW
EX. 1/2" CW
EX. 2" CW
EX. 2" CW
EX. 1/2" CW
EX. 2" CW
EX. 1/2" CW
EX. 1/2" CW
EX. 1/2" CW
EX. 2" CW
FROM INCOMING SERVICE
TO BUILDING
TO BUILDING
TO BUILDING EXIT
BFP-1
FD-1
FD-1
3" W
3" W
3" W
3" W
3" W
3" W
3/4" CW
3/4" CW
3/4" CW
MAKE UP WATER
CONNECTION.
REFER TO M-SERIES
DRAWINGS FOR
CONTINUATION
MAX MOUNTING
HEIGHT OF 54" AFF
EX. 1/2" CW
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
BALL VALVE (TYP.)
EX. 2" V TO LEVEL 02
PIPE SEGMENTS SHALL BE INSTALLED
SO THAT THEY ARE COMBINATION
DRAIN AND VENT SYSTEM.
N
123456
A
B
C
D
E
123456
A
B
C
D
E
Project No.
Project Date
Produced
These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this
Project and are not to be used on any other Project or Work without prior written permission from the Architect.
KEY PLAN
/2
/2
:5
:3
P
M
C
R e v it L o c a l\
-0
.4
H B ld g
P
\2
-0
.4
H
B ld g
P x h ic k s .r v t
2026-028.44H
10.28.2026
COMBINE DOMESTIC
WATER AND WASTE
ISOMETRIC
P-902
XJH / JJB
CITY OF CARMEL
FIRE STATION #44
HVAC
REPLACEMENT
-0
.4
H
C
IT
Y
O F
C A
R M
E L F
IR
E
S T
A T
IO
N
H
V A
C R
E P
L A
C E
M E
N T
5032 E MAIN ST
CARMEL, IN 46033
P -9
C
O M
B
IN
E D
O M
E S
T
IC
W A
T E
R A
N D
W A
S T E
I S
O M
E T
R
IC
PLUMBING FIXTURE ROUGH-IN LEGEND
MARK
FIXTURE CONNECTION
CW HW W V ST
FD-1 3"
NOT TO SCALE
2A
COMBINED DOMESTIC WATER AND WASTE ISOMETRIC