5.8_-_Plumbing.pdf

PDF 7 MB Posted

Attached to
CFD Station #344 HVAC Renovation
Solicitation number
IFB-2026-019
Issued by
Hamilton County, Indiana

About this file

This is a plumbing design and specification document for the HVAC Replacement project at Carmel Fire Station #44, located at 5032 E Main Street, Carmel, Indiana 46033. The document provides comprehensive plumbing symbols, abbreviations, and detailed plans for the renovation work. The project includes plumbing demolition plans for the first floor and roof, fire protection system plans for the basement, first floor, and second floor, foundation plumbing plans, and plumbing roof plans. The specifications detail the installation of new domestic water supply and waste piping systems, sanitary waste connections, natural gas pressure regulators serving multiple appliances with a total connected load of 1,657,000 BTU/H, and fire protection sprinkler systems compliant with NFPA 13 standards. Key plumbing notes require the contractor to verify existing pipe routing prior to floor slab cutting, jet and flush existing sanitary sewers before making new connections, cap and fill abandoned underground piping with flowable fill, remove fixture rough-in piping beyond finished surfaces, remove overhead piping and hangers in remodeled areas, and permanently cap abandoned vents through the roof. The document is dated October 28, 2026, and indicates bid submission deadline of December 16, 2026, at 10:00 AM through the City's e-Procurement Portal.

The plumbing specifications include schedules for sanitary waste specialties and metering/pressure reducing valves, with specific equipment such as a Zurn Wilkins reduced pressure backflow preventer (Model #975XLS2) rated at 30 GPM with a 14.3 PSI pressure drop. Natural gas regulators are specified for various equipment including range, grills, fireplaces, domestic water heaters, and rooftop units, with inlet pressure of 2 PSIG and outlet pressures ranging from 7 to 10 inches of water column. The contractor must increase the utility supply pressure for natural gas from 10 inches of water column to 2 PSI and coordinate with utility providers. Plumbing fixture rough-ins are shown for cold water, hot water, waste, vent, and storm drainage connections throughout the building. The document emphasizes contractor responsibility for field verification, coordination with other trades, and compliance with existing architectural and design standards, with all drawings and specifications remaining the property of the architect.

View the file

Other files

File Type Posted
CFD_Station_#344_HVAC_Renovation.pdf PDF
2026-028.44H_FINAL_TECH_SPECS.pdf PDF
5.4_-_Architecture.pdf PDF
5.7_-_Mechanical.pdf PDF
5.9_-_Electrical.pdf PDF
5.3_-_Structural.pdf PDF
5.1_-_General.pdf PDF
SAMPLE_OF_MOU_FOR_E-VERIFY.pdf PDF
MAINTENANCE_BOND.pdf PDF
PAYMENT_BOND.pdf PDF
RIGHT_OF_ENTRY.pdf PDF
PERFORMANCE_BOND.pdf PDF
Exhibit_D_E-Verify-1.PDF PDF
SUBCONTRACTORS_LIST.pdf PDF
WORK_DIRECTIVE_CHANGE.pdf PDF
SCREENSHOT_INSTRUCTIONS_-_FOR_BIDS.pdf PDF
SAMPLE_AGREEMENT.pdf PDF
FIELD_ORDER.pdf PDF
NON_COLLUSION_AFFIDAVIT.pdf PDF
CONTRACT_CHANGE_ORDER.pdf PDF
CONTRACT_CHANGE_REQUEST.pdf PDF
REQUEST_FOR_PROPOSAL_CHANGE.pdf PDF
MANUFACTURERS_LIST.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AV

AW

AIR

CW

GAS

GW

HW

ABANDONED ACID-RESISTANT VENT

ABANDONED ACID-RESISTANT WASTE

ABANDONED AIR

ABANDONED COLD WATER

ABANDONED GAS

ABANDONED GREASE WASTE

ABANDONED HOT WATER

ABANDONED PIPING SYSTEMS

HWR ABANDONED HOT WATER RETURN

FP ABANDONED FIRE PROTECTION

N2 ABANDONED NITROGEN

ST ABANDONED STORM

VAC ABANDONED VACUUM

V ABANDONED VENT

W ABANDONED WASTE

GALV GALVANIZED

STP

HWR HOT WATER RETURN

STS, STR

STRUCT

HWCP

HR

HO

HD

HORIZ

HOUR

HORIZONTAL

HEAD (FT.)

HUB OUTLET

HB

GC

GPM

GT

GPH

HOSE BIB

GENERAL CONTRACTOR

GALLONS PER MINUTE

GALLONS PER HOUR

GREASE TRAP

STD

ST

SSK

SSD

SS

SPEC

SPG

SHT

SK

SH

SECT

SF

SB

SCW

FLOOR DRAIN

FIRE PROTECTION CONTRACTOR

FIRE DEPARTMENT CONNECTION

G

GAL

GA

FPC

FOV

FP

FT

FPM

FTG

GALLON

GAUGE

NATURAL GAS

FIRE PROTECTION

FUEL OIL VENT

FEET PER MINUTE

FOOTING

FOOT/FEET

FE

FHC

FH

FOS

FOR

FLR

FCO

FDC

FD

FIRE EXTINGUISHER

FUEL OIL RETURN

FUEL OIL SUPPLY

FIRE HOSE CABINET

FLOOR

FIRE HOSE

FLOOR CLEANOUT

RO

RPM

RM

RECIR

RH

RD

RCP

R

PVC

EXIST

EXP

°F

ET

EWC

EW

DEGREES FAHRENHEIT

EXPANSION

EXISTING

EXPANSION TANK

EMERGENCY EYEWASH

ELECTRIC WATER COOLER

EMER

ENCL

ES

EQUIP

EFF

ELEV

ELEC

EMERGENCY

EMERGENCY SHOWER

EQUIPMENT

ENCLOSURE

ELEVATION

ELECTRIC

EFFICIENCY

PSIG

PRESS

PRV

PSI

PREFAB

PPM

POC

PIV

PLT

PER

PI

PH

PD

PC

STORAGE TANK PUMP

STORAGE TANK SUPPLY AND RETURN

STRUCTURE(E), (AL)

SUB SURFACE (FOOTING) DRAIN

STORAGE TANK

STAINLESS STEEL

SERVICE SINK

STANDARD

SPECIFICATIONS

SPECIAL GAS

SHEET

SINK

SOFT COLD WATER (DOMESTIC)

SQUARE FOOT

SHOWER

SECTION

SITZ BATH

RODDING HOLE

REVERSE OSMOSIS WATER

REVOLUTIONS PER MINUTE

ROOM

RECIRCULAT(E), (OR), (ING)

REINFORCED CONCRETE PIPE

ROOF DRAIN

THERMAL RESISTANCE

POLYVINYL CHLORIDE

POST INDICATOR VALVE

POINT OF CONNECTION (NEW TO EXISTING)

POUNDS PER SQUARE INCH

PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH GAUGE

PRESSURE

PARTS PER MILLION

PREFABRICATED

PLASTER TRAP

PRESSURE DROP (IN OR WG AS NOTED)

PERCENT

PRESSURE INDICATOR

PHASE

PLUMBING CONTRACTOR

MISC

ECO

EC

DN

DS

DF

DWG

DWH

EXTERIOR CLEANOUT

ELECTRICAL CONTRACTOR

DRINKING FOUNTAIN

DOMESTIC WATER HEATER

DRAWING

DOWNSPOUT

DOWN

CW

D

COLD WATER (DOMESTIC)

DRAIN

P

OSD

OFOI

OFCI

OFD

OE

OA

O

NA

NO

NTS

NIC

NC

N

MTD

CONTRACTOR FURNISHED/OWNER INSTALLED

BRITISH THERMAL UNIT PER HOUR

CO

CI

CONN

CO2

CFOI

CARBON DIOXIDE

CONNECTION

CAST IRON

CLEANOUT

BT

CD

BTUH

BOP

BLDG

BATHTUB

CONDENSATE DRAIN

BOTTOM OF PIPING

BUILDING

MIN

MH

MECH

MC

MBH

MS

MB

MAX

LPC

MA

LV

LFC

LP

LEC

AREA DRAIN

AMPERE (AMP, AMPS)

A

AW

BFC

AMP

ARCH

AV

APD

APPROX

COMPRESSED AIR

BELOW FINISHED CEILING

ACID WASTE

AIR PRESSURE DROP (IN WG)

ARCHITECT (URAL)

APPROXIMAT(E), (LY)

ACID VENT

ADJ

AE

AFF

ALTER

AD

ADA

ADJUSTABLE

ABOVE FINISHED FLOOR

ANESTHESIA EVACUATION

ALTERNATE

AMERICAN DISABILITIES ACT

LBS

LAB

LA

L

KW

INV

KEC

IN

INDIC

INSUL

INT

INCL

ID

HZ

VACUUM PUMP DISCHARGE

W/O WITHOUT

MISCELLANEOUS

OWNER FURNISHED/CONTRACTOR INSTALLED

OWNER FURNISHED/OWNER INSTALLED

OPEN SITE DRAIN

PUMP

ORAL EVACUATION

OVERFLOW DRAIN

OUTSIDE AIR

OXYGEN

NOT APPLICABLE

NORMALLY CLOSED

NORMALLY OPEN

NOT TO SCALE

NOT IN CONTRACT

NITROGEN

MOUNTED

ZN

WTR

YD

WPD

WP

ZONE

WATER PRESSURE DROP

YARD DRAIN

WEATHERPROOF

WATER

THOUSANDS OF BTU PER HOUR

MECHANICAL

MINIMUM

MANHOLE

MECHANICAL CONTRACTOR

MOP SINK

MOP BASIN

MAXIMUM

LABORATORY FURNISHINGS CONTRACTOR

LABORATORY PLUMBING CONTRACTOR

LABORATORY EQUIPMENT CONTRACTOR

LABORATORY VACUUM

MEDICAL AIR

LIQUID PETROLEUM

WH

WG

W.C.

WCO

WC

W/

VV

VPD

VT

VTR

WATER CLOSET

WATER COLUMN

WALL CLEANOUT

WATER GAUGE

WALL HYDRANT

VITRIFIED TILE

VENT THROUGH ROOF

VACUUM VENT

WITH

VB

VERT

VIF

VC

VAC

VAR

VA

VACUUM BREAKER

VERIFY IN FIELD

VACUUM CLEANING

VERTICAL

VOLT AMPERE

VACUUM

VARIABLE

TEMPERATURE AND PRESSURE

THERMOSTATIC MIXING VALVE

UNLESS NOTED OTHERWISE

INVERT

KITCHEN EQUIPMENT CONTRACTOR

LABORATORY AIR

LABORATORY

POUND

KILOWATT

LAVATORY

INCH/INCHES

INSULAT(E), (ED), (ION)

INCLUD(E), (ED)

INDICATOR

INTERIOR

FREQUENCY (MEGAHERTZ)

INSIDE DIAMETER

UNO

UR

TYP.

TS

TP

URINAL

TRAP PRIMER

TAMPER SWITCH

TYPICAL

TEMP

TMV

T&P

SU

TEMPERATURE

SHOWER UNIT

ABBREVIATIONS

HW HOT WATER (DOMESTIC)

T TEMPERED WATER

DWS DOMESTIC WATER SOFTNER

HOT WATER RECIRCULATING PUMP

ABBREVIATIONS

M-301

M-501

SECTION REFERENCE

DETAIL REFERENCE

DRAWING NOTATIONS

NOTE:

ALL SYMBOLS AND ABBREVIATIONS

MAY NOT BE USED FOR THIS PROJECT

NEW TO EXISTING

DEMO TO THIS POINT

EQUIPMENT TAG - (SEE SCHEDULE SHEETS)XXX-1

XXX-1 FIXTURE TAG - (SEE SCHEDULE SHEETS)

FIRE PROTECTION SYMBOLS

A

TS

F

F

ALARM VALVE

ZONE VALVE (OS&Y)

SIDEWALL SPRINKLER HEAD

CONCEALED PENDANT SPRINKLER HEAD

UPRIGHT SPRINKLER HEAD

PENDANT SPRINKLER HEAD

DRY PENDANT SPRINKLER HEAD

FIRE DEPT. CONNECTION

POST INDICATOR VALVE

FLOW SWITCH

TAMPER SWITCH

FIRE WATER MAIN

140° HW

140° HWR

160° HW

160° HWR

AV

AW

AIR

CW

HW

HWR

FPD

FP

FPPA

FPW

G (11 in-wc)

G (2 psig)

GW

LCW

LHR

LA

LHW

LVAC

LVE

N2

PWR

PWS

RO

ROR

SCW

SHW

ST

TW

VAC

V

W

140° DOMESTIC HOT WATER

140° DOMESTIC HOT WATER RETURN

160° DOMESTIC HOT WATER

160° DOMESTIC HOT WATER RETURN

ACID RESISTANT VENT

ACID RESISTANT WASTE

AIR

DOMESTIC COLD WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER RETURN

FIRE PROTECTION DRY

FIRE PROTECTION OTHER

FIRE PROTECTION PRE-ACTION

FIRE PROTECTION WET

GAS (11" w.c.)

GAS (2 psig)

GREASE WASTE

LAB AIR

LAB COLD WATER

LAB HOT WATER

LAB HOT WATER RETURN

LAB VACUUM

LAB VACUUM EXHAUST

NITROGEN

PURE WATER RETURN

PURE WATER SUPPLY

REVERSE OSMOSIS WATER

REVERSE OSMOSIS WATER RETURN

SOFT COLD WATER

SOFT HOT WATER

STORM

TEMPERED WATER

VACUUM

VENT

WASTE

PIPING SYSTEMS

CA COMBUSTION AIR

EA EXHAUST AIR

G (6 in-wc) GAS (6" w.c.)

G (5 psig) GAS (5 psig)

RCW RAW COLD WATER

GENERAL DUTY VALVES & FITTINGS

A

CONCENTRIC REDUCER

DOMESTIC COLD WATER VALVE BOX

ECCENTRIC REDUCER

PRESSURE REDUCING VALVE

(P) = PRESSURE

VACUUM BREAKER

GAS COCK

PETE'S PLUG

PIPE EXPANSION JOINT

FLEXIBLE PIPING CONNECTOR

Y-STRAINER W/BLOWDOWN

VALVE & CAP

PIPE ANCHORS

PIPE GUIDES

THERMOMETER WELL

AUTOMATIC AIR VENT

GAUGE CONNECTION(S) & WELL

THERMOMETER & WELL

MANUAL AIR VENT

AUTOMATIC BALANCING VALVE

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

UNION

MANUAL BALANCING VALVE

ANGLE VALVE

PLUG VALVE

PRESSURE REGULATING VALVE

BUTTERFLY VALVE

VALVE - SEE SPECIFICATIONS

FOR VALVE TYPE

PIPE CONTINUED ON ANOTHER

DRAWING

CHECK VALVE

CAPPED PIPE

RISE IN PIPING

DROP IN PIPING

MEDICAL GAS SYSTEMS

CO2 CARBON DIOXIDE

LN LIQUID NITROGEN

MA

MO

MV

MEDICAL AIR

MEDICAL OXYGEN

MEDICAL VACUUM

MVE MEDICAL VACUUM EXHAUST

N NITROGEN

NO NITROUS OXIDE

WAGD WASTE ANESTHETIC GAS DISPOSAL

MEDICAL GAS SYMBOLS

MEDICAL VACUUM INLET

MEDICAL OXYGEN OUTLET

MEDICAL AIR OUTLET

CARBON DIOXIDE OUTLET

WAGD INLET

NITROUS OXIDE OUTLET

NITROUS OUTLET

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:4

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

PLUMBING SYMBOLS AND

ABBREVIATIONS

P-001

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P -0

P

L U

M B

IN

G

S Y

M B

O L S

A N

D A

B B

R E

V

IA

T

IO

N S

# Revision Date

EX. 3" G

EX. 3" G

EX. 3" G

EX. 1" G

EX. 1" G

EX. 1" G

EX. 1" G

EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

EX. 3" G

EX. 2" G EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

EX. 2" G

EX. 1 1/2" G

EX. 1 1/2" G

TO GAS RANGE

EX. 1 1/2" G

EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1 1/4" G

TO GAS GRILL AND FIRE PLACE

EX. 2" G

EX. 2" G

EX. 1 1/2" G

EX. DWH

EX. 1 1/4" G

EX. 1 1/4" G

EX. 3/4" G

EX. 1 1/4" G

EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

TO ROOF

EX. SERVICE SINK

EX. FD

EX. WMB

EX. 1 1/4" G

EX. 1/2" CW

EX. 1/2" CW

EX. 1/2" CW

EX. 3/4" CW

EX. 3/4" CW

EX. 1 1/2" CW

EX. 3/4" CW

EX. 3/4" CW

EX. NFWH

EX. 2" CWEX. 1/2" CW

EX. 2" CW

EX. 1/2" CW

EX. 2" CW

EX. 2" CW

EX. 3/4" CW

EX. 2 1/2" CW

EX. 2 1/2" CW

EX. 2 1/2" CW

INCOMING

WATER SERVICE

EX. 1 1/2" V

EX. 1 1/2" V

EX. 1 1/2" V

EX. 2" V TO SECOND FLOOR

1. EXISTING PIPE ROUTING, AS SHOWN ON DRAWINGS, IS BASED UPON RECORD

DOCUMENTS AND FIELD SURVEYS. ACTUAL ROUTE OF CONCEALED PIPING MAY

VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO

SAW CUTTING OF FLOOR SLABS.

2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS

WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.

3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN

PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.

4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN

WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT

BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH

EXISTING FINISH.

5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,

CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE

UNLESS OTHERWISE INDICATED.

6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED

IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW

ROOF FOR A WATER TIGHT SEAL.

PLUMBING RENOVATION NOTES

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:5

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

FIRST FLOOR

DEMOLITION PLUMBING

PLAN

PPD01

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P P

D F

IR

S

T F

L O

O R

D E

M O

L

IT

IO

N

P L U

M B

IN

G

P L A

N

1/4" = 1'-0" 2A

FIRST FLOOR DEMOLITION ENLARGED PLUMBING PLAN

EX. MB

EX. SERVICE SINK

1. EXISTING PIPE ROUTING, AS SHOWN ON DRAWINGS, IS BASED UPON RECORD

DOCUMENTS AND FIELD SURVEYS. ACTUAL ROUTE OF CONCEALED PIPING MAY

VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO

SAW CUTTING OF FLOOR SLABS.

2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS

WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.

3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN

PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.

4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN

WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT

BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH

EXISTING FINISH.

5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,

CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE

UNLESS OTHERWISE INDICATED.

6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED

IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW

ROOF FOR A WATER TIGHT SEAL.

PLUMBING RENOVATION NOTES

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1" G

EX. 1" G

EX. 1 1/4" G

TO EX. GAS GRILL

DEMO ABOVE ROOF DECK

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:0

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

PLUMBING DEMOLITION

ROOF PLAN

PRD01

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P R

D P

L U

M B

IN

G

D E

M O

L

IT

IO

N

R O

O F

P L A

N

1/4" = 1'-0" 2A

PLUMBING DEMOLITION ENLARGED ROOF PLAN

1. SPRINKLER SCHEDULE:

ROOMS WITHOUT CEILINGS: UPRIGHT SPRINKLERS

ROOMS WITH CEILINGS: SEMI-RECESSED SPRINKLER HEADS

WALL MOUNTING: SIDEWALL SPRINKLER HEADS

SUBJECT TO FREEZING: DRY PENDANT SPRINKLER HEADS

2. ALL SPRINKLER COVERAGE SHALL COMPLY WITH MINIMUM STANDARDS AS

ESTABLISHED BY NFPA 13, INCLUDING OFFICE SPACES.

3. WHERE APPLICABLE, INCOMING FIRE PROTECTION WATER SERVICE AND FIRE

DEPARTMENT CONNECTION MAIN FROM 5'-0" OUTSIDE OF BUILDING TO FLANGED

CONNECTION 12" ABOVE FLOOR OR FROM WALL SHALL BE PROVIDED BY

DIVISION 22.

4. WHERE MAIN ELECTRIC ROOMS HAVE A 2-HOUR RATING, DO NOT INSTALL

SPRINKLER COVERAGE.

5. DO NOT ROUTE SPRINKLER PIPING OVER ANY TELEDATA, IDF, MDF OR SIMILAR

ROOM. PROVIDE SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD

LOCATED ABOVE DOOR WHEREVER POSSIBLE.

6. DO NOT ROUTE SPRINKLER PIPING OVER ANY ELECTRICAL ROOM. PROVIDE

SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD LOCATED ABOVE

DOOR WHEREVER POSSIBLE.

FIRE PROTECTION GENERAL NOTES

ELEV.

EV-1-0

MDF

003A

RR

CUSTODIAL

004A

STORAGE

006A

RR

EMERGENCY OPERATIONS

PLANNING

OFFICE

OFFICE

OFFICE

OFFICE

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:1

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

BASEMENT FIRE

PROTECTION PLAN

FP100

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

F P

B

A S

E M

E N

T F

IR

E

P R

O T

E C

T

IO

N P

L A

N

1/4" = 1'-0" 2A

BASEMENT FIRE PROTECTION

CONTRACTOR SHALL TEMPERARILY SUPPORT SPRINKLER HEADS WHILE CEILING IS BEING

REMOVED TO ACCOUNT FOR HVAC REWORK. CONTRACTOR SHALL ADJUST SPRINKLER HEAD TO

ACCOUNT FOR CEILING INSTALL. CONTRACTOR SHALL ADJUST SPRINKLER HEADS IN NOTED

SPACE TO COMPLY WITH NFPA 13 REQUIREMENTS. CONTRACTOR TO COORDINATE WITH OTHER

TRADES AS REQUIRED.

ROOMS WITH CEILINGS: SEMI-RECESSED SPRINKLER HEADS

WALL MOUNTING: SIDEWALL SPRINKLER HEADS

SUBJECT TO FREEZING: DRY PENDANT SPRINKLER HEADS

2. ALL SPRINKLER COVERAGE SHALL COMPLY WITH MINIMUM STANDARDS AS

ESTABLISHED BY NFPA 13, INCLUDING OFFICE SPACES.

3. WHERE APPLICABLE, INCOMING FIRE PROTECTION WATER SERVICE AND FIRE

DEPARTMENT CONNECTION MAIN FROM 5'-0" OUTSIDE OF BUILDING TO FLANGED

CONNECTION 12" ABOVE FLOOR OR FROM WALL SHALL BE PROVIDED BY

DIVISION 22.

4. WHERE MAIN ELECTRIC ROOMS HAVE A 2-HOUR RATING, DO NOT INSTALL

SPRINKLER COVERAGE.

5. DO NOT ROUTE SPRINKLER PIPING OVER ANY TELEDATA, IDF, MDF OR SIMILAR

ROOM. PROVIDE SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD

LOCATED ABOVE DOOR WHEREVER POSSIBLE.

6. DO NOT ROUTE SPRINKLER PIPING OVER ANY ELECTRICAL ROOM. PROVIDE

SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD LOCATED ABOVE

DOOR WHEREVER POSSIBLE.

FIRE PROTECTION GENERAL NOTES

CUSTODIAL

ADA RR

RR

GEAR ROOM

CAPTAIN'S OFFICE

OFFICE STORAGE

ELEV.

EV-1-1

STOR.

STAIR 2.1

ST 2-1

APPARATUS BAY

RR

RISER

EMS STORAGE

AIR COMPRESSOR

STAIR 1

ST 1-1

CORRIDOR

OFFICE / WATCHROOM

VESTIBULE

TOOL ROOM

ELEC

EMERGENCY OPERATIONS

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:2

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

FIRST FLOOR FIRE

PROTECTION PLAN

FP101

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

F P

F

IR

S

T F

L O

O R

F

IR

E P

R O

T E

C T

IO

N P

L A

N

1/4" = 1'-0" 2A

FIRST FLOOR FIRE PROTECTION PLAN

CONTRACTOR SHALL TEMPERARILY SUPPORT SPRINKLER HEADS WHILE CEILING IS BEING

REMOVED TO ACCOUNT FOR HVAC REWORK. CONTRACTOR SHALL ADJUST SPRINKLER HEAD TO

ACCOUNT FOR CEILING INSTALL. CONTRACTOR SHALL ADJUST SPRINKLER HEADS IN NOTED

SPACE TO COMPLY WITH NFPA 13 REQUIREMENTS. CONTRACTOR TO COORDINATE WITH OTHER

TRADES AS REQUIRED.

ROOMS WITH CEILINGS: SEMI-RECESSED SPRINKLER HEADS

WALL MOUNTING: SIDEWALL SPRINKLER HEADS

SUBJECT TO FREEZING: DRY PENDANT SPRINKLER HEADS

2. ALL SPRINKLER COVERAGE SHALL COMPLY WITH MINIMUM STANDARDS AS

ESTABLISHED BY NFPA 13, INCLUDING OFFICE SPACES.

3. WHERE APPLICABLE, INCOMING FIRE PROTECTION WATER SERVICE AND FIRE

DEPARTMENT CONNECTION MAIN FROM 5'-0" OUTSIDE OF BUILDING TO FLANGED

CONNECTION 12" ABOVE FLOOR OR FROM WALL SHALL BE PROVIDED BY

DIVISION 22.

4. WHERE MAIN ELECTRIC ROOMS HAVE A 2-HOUR RATING, DO NOT INSTALL

SPRINKLER COVERAGE.

5. DO NOT ROUTE SPRINKLER PIPING OVER ANY TELEDATA, IDF, MDF OR SIMILAR

ROOM. PROVIDE SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD

LOCATED ABOVE DOOR WHEREVER POSSIBLE.

6. DO NOT ROUTE SPRINKLER PIPING OVER ANY ELECTRICAL ROOM. PROVIDE

SIDEWALL SPRINKLER COVERAGE FOR THE SPACE WITH HEAD LOCATED ABOVE

DOOR WHEREVER POSSIBLE.

FIRE PROTECTION GENERAL NOTES

DORM

213A

BATH

213B

LOCKER

DORM

214A

DORM

215A

LOCKER

LOCKER

BATH

214B

BATH

215B

LAUNDRY

STORAGE

MECH.

JANITOR

PANTRY

PANTRY

PANTRY

BATH

220B

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

BATH

217B

BATH

216B

BATH

219B

BATH

218B

DORM

216A

DORM

217A

DORM

218A

DORM

219A

DORM

220A

KITCHEN

STAIR 1

ST 1-2

STAIR 2

ST 2-2

DAY ROOM

DINING

SUPPLY CLOSET

CORRIDOR

CORRIDOR

CORRIDOR

ELECTRICAL

PANELS

FIRST FLOOR ROOF

PATIO

FIRST FLOOR ROOF

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:3

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

SECOND FLOOR FIRE

PROTECTION PLAN

FP102

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

F P

S

E C

O N

D F

L O

O R

F

IR

E P

R O

T E

C T

IO

N

P L A

N

1/4" = 1'-0" 2A

SECOND FLOOR FIRE PROTECTION PLAN

CONTRACTOR SHALL TEMPERARILY SUPPORT SPRINKLER

HEADS WHILE CEILING IS BEING REMOVED TO ACCOUNT FOR

HVAC REWORK. CONTRACTOR SHALL ADJUST SPRINKLER HEAD

TO ACCOUNT FOR CEILING INSTALL. CONTRACTOR SHALL

ADJUST SPRINKLER HEADS IN NOTED SPACE TO COMPLY WITH

NFPA 13 REQUIREMENTS. CONTRACTOR TO COORDINATE WITH

OTHER TRADES AS REQUIRED.

VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO

SAW CUTTING OF FLOOR SLABS.

2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS

WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.

3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN

PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.

4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN

WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT

BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH

EXISTING FINISH.

5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,

CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE

UNLESS OTHERWISE INDICATED.

6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED

IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW

ROOF FOR A WATER TIGHT SEAL.

PLUMBING RENOVATION NOTES

EX. MB

EX. DWH

EX. FD

EX. FD

EX. 2" W UP

TO WMB

EX. 2" W UP TO

SERVICE SINK

2A

P-902

3" W

1 1/2" V

FD-1

3" WFD-1

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" WEX. 3" W

EX. 2" W

EX. 3" W

EX. 2" W

EX. 4" W EX. 2" W

CONTRACTOR TO DEMO ANY

PIPE TO MAKE NEW CONNECTION

CONTRACTOR TO DEMO ANY

PIPE TO MAKE NEW CONNECTION

BASEMENT

BASEMENT

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:4

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

FOUNDATION PLUMBING

PLAN

PF101

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P F

F

O U

N D

A T

IO

N

P L U

M B

IN

G

P L A

N

PLUMBING FIXTURE ROUGH-IN LEGEND

MARK

FIXTURE CONNECTION

CW HW W V ST

FD-1 3"

# Revision Date

1/4" = 1'-0" 2A

FOUNDATION PLUMBING ENLARGED PLAN

VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO

SAW CUTTING OF FLOOR SLABS.

2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS

WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.

3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN

PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.

4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN

WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT

BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH

EXISTING FINISH.

5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,

CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE

UNLESS OTHERWISE INDICATED.

6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED

IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW

ROOF FOR A WATER TIGHT SEAL.

PLUMBING RENOVATION NOTES

B-1

UP TO ROOF

UP TO ROOF

3/4" G

3/4" G

3/4" G

GPR-3

GPR-4

GPR-2

GPR-1

GPR-5

UP TO GAS GRILL AND FIRE PLACE

GPR-9

GPR-8

1 1/4" G

1 1/2" G

1" G

2D

P-901

2D

P-901

2D

P-901

2D

P-901

2D

P-901

2D

P-901

EX. RH-4

EX. RH-3

EX. RH-1 EX. RH-2

UP TO GAS RANGE

EX. 1 1/2" G

EX. 1 1/2" G

EX. 3/4" G

EX. 3/4" G

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1 1/4" G

1 1/4" G

EX. 3/4" G

EX. 3/4" GEX. 2" G

EX. 3" G

EX. 1" G

EX. 1" G

EX. 1" G

EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

EX. 3" G

GPR-6

EX. GFUH

EX. 3/4" G

EX. 1 1/4" G

CUSTODIAL

ADA RR

RR

GEAR ROOM

CAPTAIN'S OFFICE

OFFICE STORAGE

ELEV.

EV-1-1

STOR.

STAIR 2.1

ST 2-1

APPARATUS BAY

RR

RISER

EMS STORAGE

AIR COMPRESSOR

STAIR 1

ST 1-1

CORRIDOR

OFFICE / WATCHROOM

VESTIBULE

TOOL ROOM

ELEC

FITNESS ROOM

EX. DWH

EX. 2" G

FD-1

EX. SERVICE SINK

EX. FD

EX. WMB

TOTAL CONNECTED LOAD:

1,657,000 BTU/H

2D

P-901

EX. 3/4" G

EX. 1 1/4" G

EX. 1 1/4" G

BFP-1

EX. 1/2" CW

EX. NFWH

EX. 1 1/4" G

FD-1

2A

P-902

EX. 2 1/2" CW

EX. 2 1/2" CW

EX. 2 1/2" CW

EX. 2 1/2" CW

EX. 2" CW

1 1/2" V

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:5

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

FIRST FLOOR PLUMBING

PLAN

PP101

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P P

F

IR

S

T F

L O

O R

P L U

M B

IN

G

P L A

N

1/4" = 1'-0" 2A

FIRST FLOOR PLUMBING ENLARGED PLAN

EX. MB

EX. SERVICE SINK

PLUMBING PLAN NOTES

NOT ALL NOTES APPLY TO EVERY SHEETS.

# NOTE

1 CONTRACTOR SHALL INCREASE THE ULTILITY SUPPLY PRESSURE FOR NATURAL

GAS. CONTRACTOR SHALL INCREASE PRESSURE FROM 10" W.C. TO 2 PSI.

CONTRACTOR TO COORIDINATE WITH UTILITIES AS REQUIRED.

2 MAKE UP WATER CONNECTION. REFER TO M-SERIES FOR CONTINUATION

3 MAX MOUNTING HEIGHT OF 54" AFF

PLUMBING FIXTURE ROUGH-IN LEGEND

MARK

FIXTURE CONNECTION

CW HW W V ST

FD-1 3"

INCOMING

WATER SERVICE

VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO

SAW CUTTING OF FLOOR SLABS.

2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS

WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.

3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN

PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.

4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN

WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT

BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH

EXISTING FINISH.

5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,

CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE

UNLESS OTHERWISE INDICATED.

6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED

IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW

ROOF FOR A WATER TIGHT SEAL.

PLUMBING RENOVATION NOTES

RTU-1

EX. MAU-1

RTU-2

EX. 1 1/4" G

TO EX. GAS GRILL

GPR-7

GPR-10

1 1/4" G

1 1/4" G 1/2" G

3/4" G 3/4" G

1/2" G

1/2" G

1/2" G

3/4" G

3/4" G

GPR-11

3/4" G

3/4" G

2D

P-901

2D

P-901

2D

P-901

RECONNECT ABOVE ROOF DECK

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:0

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

PLUMBING ROOF PLAN

PR101

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P R

P

L U

M B

IN

G

R O

O F

P L A

N

1/4" = 1'-0" 2A

PLUMBING ENLARGED ROOF PLAN

6" LONG HARDWOOD

BLOCK SHAPED TO

PIPE AND HANGER

INSULATION

PIPEPIPE

INSULATION

HEAVY DUTY

CLEVIS HANGER

SUPPORT NUT

LOCKING NUT

HANGER ROD

14 GUAGE ZINC

COATED SHEET STEEL

SADDLE, AT LEAST 6"

LONG

STEEL ROD

COUPLING

THREADED STEEL

HANGER ROD

UNI-STRUT

TRAPEZE

SUPPORT

STRUT PIPE CLAMP

PIPE INSULATION MATERIAL

(REFER TO SPECIFICATIONS)

SYSTEM PIPE (REFER TO

DRAWINGS FOR TYPE OF

SYSTEM AND SIZE OF PIPE)

CARRIER PIPE - (ONLY

AT CLAMP LOCATIONS)

TRAFFIC PAD

PIPESTAND

SADDLE

INSULATED PIPE

PIPE STRAP

ROOF SURFACE

M

IN

PLAN NOTES:

1.PIPESTAND MIRO MODEL NO. 3-R WITH ROLLER.

2. PROVIDE SADDLE UNDER INSULATED PIPE.

3. INSTALL PIPE STRAP USING #10 STAINLESS STEEL SCREWS PER UNIT MFR

RECOMMENDATION. PROVIDE LOOSE INSTALLATIN TO PROVIDE FREE MOVEMENT.

4.SPACE PIPESTANDS TO OBTAIN A MAX. LOAD WEIGHT OF 100 LBS. PER PIPE STAND.

MAX. SPACING SHALL BE 10'.

5. INSTALL MIRO MODEL NO. 3-R SPACERS AS REQUIRED TO PROVIDE MIN. 6"

CLEARANCE BETWEEN ROOF SURFACE AND BOTTOM OF PIPE INSULATION.

6. INSTALL TRAFFIC PAD OR MIRO DECK PLATE BELOW EACH PIPESTAND. ADJUST THE

HEIGHT OF EACH PIPE STAND TO ACHIEVE EVEN LOAD WEIGHT AT ALL PIPESTANDS.

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:1

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

PLUMBING DETAILS

P-501

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P -5

P

L U

M B

IN

G

D E

T A

IL

S

NOT TO SCALE

2A

PIPE HANGER (6" & SMALLER) DETAIL

NOT TO SCALE

2B

TYPICAL TRAPEZE PIPE SUPPORT DETAIL

NOT TO SCALE

2C

ROOFTOP PIPESTAND DETAIL

SANITARY WASTE PIPING SPECIALTIES SCHEDULE (221319)

MARK

FIXTURE W

CONNECTION ACCESSORIES NOTESMANUFACTURER MODEL DESCRIPTION

FD-1 J.R. SMITH #2005Y-F-37-U-PB DUCO CAST IRON BODY WITH FLASHING COLLAR, ADJUSTABLE ROUND STRAINER HEAD, POLISHED BRONZE STRAINER, FLUSH WITH FLOOR FUNNEL WITH ANTI-SPLASH RIM AND GRATE 3" TRAPGUARD BY PROSET, NO SUBSTITUTIONS

METERING AND PRESSURE REDUCING VALVES SCHEDULE (221119)

MARK

EQUIPMENT PLUMBING

NOTESMANUFACTURER MODEL DESCRIPTION FLOW RATE (GPM) PRESSURE DROP (PSI)

BFP-1 ZURN WILKINS #975XLS2 - 3/4" REDUCED PRESSURE BACKFLOW PREVENTER 30 14.3

EX. DWH

DIRT LEG

DIRT LEG

DIRT LEG

DIRT LEG

TO EX. GAS RANGE

TO EX. GAS GRILL

AND FIRE PLACE

1 1/4" G 1 1/2" G

GPR-8

B-1

1 1/4" G

1 1/4" G

1/2" G

1/2" G

1/2" G

GPR-7

EX. MAU-1

1/2" G

3/4" G

GPR-10

1/2" G 3/4" G

RTU-1

GPR-6

3/4" G

1" G

GPR-2

GPR-4

GPR-3

EX. RH-4

EX. GFUH

EX. RH-3

EX. RH-1

GPR-1

EX. RH-2 3/4" G

3/4" G

3/4" G

RTU-2

3/4" G

3/4" G

GPR-11

3/4" G

3/4" G

GPR-5

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1 1/4" G

EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

EX. 1 1/2" G

EX. 3/4" G

EX. 3/4" G

EX. 1 1/2" G

EX. 1 1/2" G

EX. 2" G

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1 1/4" G

EX. 1 1/2" G

EX. 2" G

EX. 3" G

EX. 2" G

EX. 3" G

EX. 1" G

EX. 1" G

EX. 3" G

EX. 3" G

EX. 3" G

EX. 3" G

EX. 1" G

EX. 1" G

EX. 3/4" G

EX. 3/4" G

EX. 3/4" G

EX. 2" G

EX. 3/4" G

EX. 3/4" G

EX. 1 1/4" G

EX. 3/4" G

EX. 1 1/4" G

1 1/4" G

TOTAL CONNECTED LOAD:

1,657,000 BTU/H

GPR-9

RECONNECT ABOVE ROOF DECK

CONTRACTOR SHALL COORDINATE

METER AND UTILITY REQUIREMENTS

WITH UTILITY PROVIDER AS REQUIRED.

CONFIRM INLET SIDE

PIPE SIZE WITH PLANS

SHUTOFF VALVE

PRESSURE GAUGE

UNION

5 TIMES PIPE DIAMETER OF STRAIGHT

PIPE ON INLET SIDE OF REGULATOR

NATURAL GAS PRESSURE REGULATOR (GPR-X)

SEE PLANS FOR LOCATION AND THIS SHEET

FOR SCHEDULE INFORMATION

UNION

10 TIMES PIPE DIAMETER OF STRAIGHT

PIPE ON OUTLET SIDE OF REGULATOR

PRESSURE GAUGE

SHUTOFF VALVE

CONFIRM OUTLET SIDE

PIPE SIZE WITH PLANS

THREADOLETTE FITTING

THREADOLETTE FITTING

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:2

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

NATURAL GAS

ISOMETRIC

P-901

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P -9

N

A T U

R A

L G

A S

I S

O M

E T

R

IC

IDENTITY DATA PRESSURE NATURAL GAS

MARK DESCRIPTION VENTING

INLET

(psig)

OUTLET (inches w.c.)

TOTAL CONNECTED

LOAD (BTU/H)

EQUIPMENT

SERVED

GPR-1 GAS PRESSURE REGULATOR VENT LIMITING 2 10 100,000 EX. RH-1 AND EX. RH-2

GPR-2 GAS PRESSURE REGULATOR VENT LIMITING 2 10 50,000 EX. RH-3

GPR-3 GAS PRESSURE REGULATOR VENT LIMITING 2 10 50,000 EX. RH-4

GPR-4 GAS PRESSURE REGULATOR VENT LIMITING 2 10 250,000 EX. RANGE

GPR-5 GAS PRESSURE REGULATOR VENT LIMITING 2 10 132,000 EX. GAS GRILL

GPR-6 GAS PRESSURE REGULATOR VENT LIMITING 2 10 30,000 EX. GFUH

GPR-7 GAS PRESSURE REGULATOR VENT TO THE OUTSIDE 2 10 60,000 EX. MAU-1

GPR-8 GAS PRESSURE REGULATOR VENT LIMITING 2 10 300,000 EX. DWH

GPR-9 GAS PRESSURE REGULATOR VENT LIMITING 2 7 285,000 B-1

GPR-10 GAS PRESSURE REGULATOR VENT TO THE OUTSIDE 2 10 150,000 RTU-1

GPR-11 GAS PRESSURE REGULATOR VENT TO THE OUTSIDE 2 10 250,000 RTU-2

NOT TO SCALE

2A

NATURAL GAS ISOMETRIC

NOT TO SCALE

2D

NATURAL GAS PRESSURE REGULATOR PIPING DIAGRAM

PLUMBING ISOMETRIC PLAN NOTES

# NOTE

1 CONTRACTOR SHALL INCREASE THE ULTILITY SUPPLY PRESSURE FOR NATURAL

GAS. CONTRACTOR SHALL INCREASE PRESSURE FROM 10" W.C. TO 2 PSI.

CONTRACTOR TO COORIDINATE WITH UTILITIES ARE REQUIRED.

VARY. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY PIPE ROUTING PRIOR TO

SAW CUTTING OF FLOOR SLABS.

2. CONTRACTOR SHALL JET AND THOROUGHLY FLUSH EXISTING SANITARY SEWERS

WHERE DOCUMENTS CALL FOR NEW WASTE PIPE CONNECTIONS.

3. ALL UNDERGROUND SANITARY OR STORM PIPING SHOWN TO BE ABANDONED IN

PLACE SHALL BE CAPPED AND FILLED WITH FLOWABLE FILL.

4. WHERE PLUMBING FIXTURE ROUGH-IN PIPING IS SHOWN TO BE ABANDONED IN

WALLS OR BELOW FLOOR SLAB, ROUGH-INS SHALL BE REMOVED TO A POINT

BEYOND THE FINISHED SURFACE AND CAPPED. PATCH SURFACE TO MATCH

EXISTING FINISH.

5. IN AREAS WHERE A FULL REMODEL IS INDICATED ON THE DRAWINGS,

CONTRACTOR SHALL REMOVE ALL OVERHEAD PIPING AND HANGERS COMPLETE

UNLESS OTHERWISE INDICATED.

6. WHERE SANITARY OR ACID VENT THROUGH ROOF IS SHOWN TO BE ABANDONED

IN PLACE, CONTRACTOR SHALL PERMANENTLY CAP PIPE ABOVE AND BELOW

ROOF FOR A WATER TIGHT SEAL.

PLUMBING RENOVATION NOTES

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 4" W

EX. 2" W

EX. 4" W

EX. 4" W

EX. 2" W

EX. 2" W

EX. 2" W

EX. 2" W

EX. 2" W

EX. 2" W

EX. DWH

EX. WMB

EX. FD

EX. FD

EX. SERVICE

SINK

EX. 2" W

EX. 2" W

EX. NFWH

EX. 3/4" CW

EX. 3/4" CW

EX. 3/4" CW

EX. 3/4" CW

UP TO LEVEL 02

UP TO LEVEL 02

UP TO LEVEL 02

EX. 1/2" CW

EX. 1/2" CW

EX. 1 1/2" CW

EX. 1 1/2" CW

EX. 2" CW

EX. 2" CW

EX. 1/2" CW

EX. 2" CW

EX. 2" CW

EX. 1/2" CW

EX. 2" CW

EX. 1/2" CW

EX. 1/2" CW

EX. 1/2" CW

EX. 2" CW

FROM INCOMING SERVICE

TO BUILDING

TO BUILDING

TO BUILDING EXIT

BFP-1

FD-1

FD-1

3" W

3" W

3" W

3" W

3" W

3" W

3/4" CW

3/4" CW

3/4" CW

MAKE UP WATER

CONNECTION.

REFER TO M-SERIES

DRAWINGS FOR

CONTINUATION

MAX MOUNTING

HEIGHT OF 54" AFF

EX. 1/2" CW

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

BALL VALVE (TYP.)

EX. 2" V TO LEVEL 02

PIPE SEGMENTS SHALL BE INSTALLED

SO THAT THEY ARE COMBINATION

DRAIN AND VENT SYSTEM.

N

123456

A

B

C

D

E

123456

A

B

C

D

E

Project No.

Project Date

Produced

These Drawings and Specifications, and all copies thereof are and shall remain the property and copyright of the Architect. They shall be used only with respect to this

Project and are not to be used on any other Project or Work without prior written permission from the Architect.

KEY PLAN

/2

/2

:5

:3

P

M

C

R e v it L o c a l\

-0

.4

H B ld g

P

\2

-0

.4

H

B ld g

P x h ic k s .r v t

2026-028.44H

10.28.2026

COMBINE DOMESTIC

WATER AND WASTE

ISOMETRIC

P-902

XJH / JJB

CITY OF CARMEL

FIRE STATION #44

HVAC

REPLACEMENT

-0

.4

H

C

IT

Y

O F

C A

R M

E L F

IR

E

S T

A T

IO

N

H

V A

C R

E P

L A

C E

M E

N T

5032 E MAIN ST

CARMEL, IN 46033

P -9

C

O M

B

IN

E D

O M

E S

T

IC

W A

T E

R A

N D

W A

S T E

I S

O M

E T

R

IC

PLUMBING FIXTURE ROUGH-IN LEGEND

MARK

FIXTURE CONNECTION

CW HW W V ST

FD-1 3"

NOT TO SCALE

2A

COMBINED DOMESTIC WATER AND WASTE ISOMETRIC

P-001-r.pdf
PPD01-r.pdf
PRD01-r.pdf
FP100-r.pdf
FP101-r.pdf
FP102-r.pdf
PF101-r.pdf
PP101-r.pdf
PR101-r.pdf
P-501-r.pdf
P-901-r.pdf
P-902-r.pdf

File details come from the government source that posted it. Updated .