Structural Evaluation of Existing Storefront and Surrounding Structure

Project Address: 1754 N 27th Street, Philadelphia, PA

To Whom it May Concern, Scope of Service

This Existing Structural Conditions Report has been prepared for the proposed storefront improvements at the above-referenced property. A site visit was conducted on July 29th, 2026, and our findings are summarized herein.

The purpose of this report is to document observed structural deficiencies at the property. The scope of evaluation is limited to the front façade, storm doors, and foundation walls beneath the façade.

Observations were made at the front and side façades. The foundation wall at the building perimeter beneath the storefront was also observed. No other areas or structural components were evaluated. Framing above the existing storefront was concealed at the time of the site visit and could not be observed.

The existing structure consists of rough-sawn wood framing supported by multi-wythe brick masonry bearing walls.

Summary of Key Findings

Based on our visual observations, the following key structural conditions were identified within the areas included in this assessment:

• Front Façade Masonry Movement: Localized movement was observed at the leftmost second- and third-floor window openings, including displaced masonry headers and sills and cracking between the openings. The cause of the movement could not be confirmed because the structural framing above the storefront was concealed. The existing framing should be exposed and evaluated during construction, as deterioration of the supporting steel or other framing may be contributing to the observed façade movement.

• Front Sidewalk / Former Storm Door: A deteriorated and uneven portion of the front sidewalk appears to correspond with a former basement storm door or opening. The sidewalk presents a tripping hazard, and the condition of the underlying infill could not be verified.

The a3ected concrete should be removed and replaced, with the underlying area evaluated and properly backfilled as necessary before placement of the new sidewalk.

16 August 2026

PRESTONSTRUCTURAL

SOLUTIONS.COM

+1 215 701 3375

INFO@PRESTONSTRUCTURAL

SOLUTIONS.COM

Required Structural Improvements

Item #1

Location: Front Façade

Deficiency: The front façade is exhibiting signs of localized masonry movement at the leftmost second- and third-floor window openings. The windows appear to have settled toward the center of the front façade of the building, and the masonry headers above the openings have visibly shifted. The masonry sills below the leftmost second- and third-floor windows are also visibly out of level and appear deteriorated when observed from the street. A crack was observed in the masonry between the left side of these window openings, extending between the second and third floors.

Suggested Repair: The observed conditions indicate localized movement of the front façade, the cause of which could not be determined based on visual observations alone. At a minimum, install Simpson Strong-Tie helical masonry ties across the crack between the second- and third-floor window openings in accordance with the manufacturer’s requirements. The existing masonry headers and sills at the a3ected windows should also be reset, repaired, and repointed as required to close existing gaps and limit continued water intrusion.

The observed façade movement may be indicative of deterioration or corrosion of the existing steel transfer beam or other structural framing supporting the masonry façade above the storefront. During construction, the contractor should expose the existing framing above the storefront along the front elevation and notify

Preston Structural Solutions, LLC if corrosion, section loss, displacement, or other deterioration is observed. If deterioration is present, repair or replacement of the existing supporting framing may be required and should be evaluated once exposed.

Item #2

Location: Front Sidewalk

Deficiency: A portion of the concrete sidewalk appears to have been replaced more recently than the surrounding sidewalk. The concrete in this area is deteriorated, with soil deposits and vegetation growth visible within the a3ected area.

Based on the location and configuration, this area appears to correspond with a former basement storm door or similar opening that was previously removed and infilled.

The deteriorated and uneven concrete currently presents a tripping hazard. Additionally, the condition of the underlying infill is unknown, and it could not be verified whether the former opening was properly backfilled prior to placement of the sidewalk. Improperly backfilled former basement openings are commonly encountered at similar properties and can result in localized settlement or collapse of the overlying sidewalk.

Suggested Repair: At a minimum, remove and replace the deteriorated concrete sidewalk within the a3ected area. During removal, the contractor should verify that the former storm door or basement opening has been properly infilled and that competent, adequately compacted material is present beneath the sidewalk. Any voids, loose material, or inadequate backfill encountered should be removed and properly filled and compacted prior to placement of the new concrete sidewalk.

Assumptions, Limitations, and Reliance

This report has been prepared based on visual observations made during a site visit and on information available to Preston Structural Solutions, LLC at the time of the assessment. The evaluation was limited in nature and did not include comprehensive destructive testing, demolition, or verification of concealed or inaccessible conditions, except where limited exploratory demolition was observed in the field.

Preston Structural Solutions, LLC is not the original engineer of record for the structure and has not performed a complete review or verification of the original structural design, calculations, or construction documents, except where explicitly noted. The findings and recommendations herein shall not be interpreted as a certification of the overall structural adequacy of the building.

The existing framing above the storefront, supporting the overlying masonry, was not observable at the time of the site visit. This framing should be evaluated by the contractor once exposed. If significant deterioration is observed, or if there is uncertainty regarding the adequacy of the existing framing, Preston Structural Solutions, LLC should be notified for further evaluation.

The conditions beneath the apparent former storm door at the front sidewalk were not observable at the time of the site visit. The presence of voids and the adequacy of the existing backfill should be verified by the contractor when the deteriorated sidewalk is removed.

The observations and conclusions presented herein are limited to conditions observed at the time of the site visit. Actual conditions may di3er as construction progresses or as concealed conditions are exposed.

Responsibility for construction means, methods, sequencing, temporary shoring, and job site safety remains solely with the contractor. If conditions encountered during construction di3er materially from those described herein, Preston Structural Solutions, LLC should be notified for further evaluation.

This report is intended for use by the client and project team for the purpose of evaluating and addressing the structural conditions described herein. Reliance by others, or use of this report for other purposes, is not authorized without written consent from Preston Structural Solutions, LLC.

Closing

We appreciate the opportunity to assist with the evaluation of the existing structural conditions at this project.

We are available to discuss the findings presented in this report, clarify recommended repair approaches, and assist with coordination as the project progresses.

Additional engineering services may be required during the implementation of repairs, upon exposure of concealed conditions, or as coordination with other project stakeholders advances. Further documentation and engineering design will be required as the project moves forward and as additional information becomes available.

Please contact our o3ice with any questions or to discuss next steps.

Sincerely, Ryan Preston, MS, PE

Founder & Principal Engineer

Preston Structural Solutions LLC