106 Gay Street

Unit 305 Philadelphia, PA 19127

Structural Evaluation of Existing Storefront and Surrounding Structure

Project Address: 2323 Ridge Ave, Philadelphia, PA

To Whom it May Concern, Scope of Service

This Existing Structural Conditions Report has been prepared for the proposed storefront improvements at the above-referenced property. A site visit was conducted on July 29th, 2026, and our findings are summarized herein.

The purpose of this report is to document observed structural deficiencies that may impact the proposed storefront improvements. The scope of evaluation is limited to the existing front and side facades, their supporting structural elements, and immediately adjacent areas.

Observations were made at the front and side facade. No other areas or structural components were evaluated. Framing above the existing storefront was concealed at the time of the site visit and could not be observed.

The existing structure generally consists of CMU bearing walls with steel bar joists supporting the roof. Based on exterior observations, there did not appear to be a basement at the property.

Summary of Key Findings

Overall, the portions of the existing building observed during our site visit appeared to be in good structural condition. No visible signs of significant structural distress, excessive movement, or deterioration were observed at the primary building structure within the areas included in our evaluation. The building interior was not accessed or evaluated as part of this assessment.

Two localized items were identified for consideration as part of the proposed storefront improvements:

1. Existing Freestanding Sign Structure: The existing steel sign structure exhibits cracking and corrosion consistent with deterioration and fatigue. If new freestanding signage is proposed, an allowance should be carried for complete removal and replacement of the existing sign structure, including new foundations.

2. Columns at Side Facade: The columns adjacent to the garage entries exhibit signs of water intrusion and deterioration of the exterior stucco finish, most notably at the column furthest from Ridge Avenue. No visible corrosion of the underlying structural steel was observed. An allowance should be carried for removal and replacement of the deteriorated stucco, with the understanding that concealed structural deterioration may become evident once the existing finish is removed.

Based on the conditions observed, no other structural repairs are anticipated as part of the proposed storefront improvements. This conclusion is limited to the exterior areas and structural components that were visible and accessible at the time of our site visit.

16 August 2026

PRESTONSTRUCTURAL

SOLUTIONS.COM

+1 215 701 3375

INFO@PRESTONSTRUCTURAL

SOLUTIONS.COM

Required Structural Improvements

Item #1

Location: Existing Freestanding Sign Structure

Deficiency: The existing freestanding steel sign structure exhibits signs of deterioration and fatigue. Hairline cracks are visible in the structural steel tubes near the tops and bases of the posts. Significant corrosion is also present at the tops of the posts, and the lack of protective column caps has allowed the interiors of the tubes to remain exposed to weather. Based on the observed conditions, the existing structure should not be relied upon for support of new signage.

Suggested Repair: If new freestanding signage is proposed at this location, an allowance should be carried for complete removal and replacement of the existing sign structure, including new posts and foundations. Costs associated with demolition of the existing structure and installation of the new structure should be included in the project budget.

Item #2

Location: Columns at Side Facade

Deficiency: The columns adjacent to the garage entries exhibit signs of water intrusion and deterioration of the exterior stucco finish.

The column furthest from Ridge Avenue exhibits more significant signs of prolonged water intrusion. No visible signs of corrosion of the underlying structural steel were observed at the time of the survey.

Suggested Repair: An allowance should be carried to remove and replace the deteriorated stucco finish and restore the protective exterior surface of the columns. The contractor should be aware that concealed deterioration or corrosion of the underlying structural elements may become evident once the existing stucco is removed. Any concealed structural deterioration should be evaluated prior to completing the repairs.

Assumptions, Limitations, and Reliance

This report has been prepared based on visual observations made during a site visit and on information available to Preston Structural Solutions, LLC at the time of the assessment. The evaluation was limited to readily visible and accessible conditions at the front and side facades and immediately adjacent exterior areas.

The building interior was not accessed or evaluated as part of this assessment.

The evaluation did not include destructive testing, exploratory demolition, or verification of concealed or inaccessible conditions. Conditions concealed by stucco, finishes, roofing, signage, or other construction were not evaluated.

Preston Structural Solutions, LLC is not the original engineer of record for the structure and has not performed a complete review or verification of the original structural design, calculations, or construction documents. The findings and recommendations herein shall not be interpreted as a certification of the overall structural adequacy of the building.

The observations and conclusions presented herein are limited to conditions observed at the time of the site visit. Actual conditions may di8er as construction progresses or as concealed conditions are exposed. In particular, removal of the existing stucco at the side facade columns may reveal concealed deterioration not visible at the time of our assessment. If structural deterioration is observed upon removal of the existing finishes, Preston Structural Solutions, LLC should be notified for further evaluation.

Responsibility for construction means, methods, sequencing, temporary shoring, and job site safety remains solely with the contractor. Implementation of the recommended repairs may require temporary support, coordination with other trades, or additional engineering evaluation.

This report is intended for use by the client and project team for the purpose of evaluating and addressing the structural conditions described herein in connection with the proposed storefront improvements. Reliance by others, or use of this report for other purposes, is not authorized without written consent from Preston

Structural Solutions, LLC.

Closing

We appreciate the opportunity to assist with the evaluation of the existing structural conditions at this project.

We are available to discuss the findings presented in this report, clarify recommended repair approaches, and assist with coordination as the project progresses.

Additional engineering services may be required during the implementation of repairs, upon exposure of concealed conditions, or as coordination with other project stakeholders advances. Further documentation and engineering design will be required as the project moves forward and as additional information becomes available.

Please contact our o8ice with any questions or to discuss next steps.

Sincerely, Ryan Preston, MS, PE

Founder & Principal Engineer

Preston Structural Solutions LLC