16-Structural - 2237 Ridge Ave.pdf

PDF 3 MB Posted

Attached to
Request for Proposal - General Contracting Services (REBID of RFP 244856)
Solicitation number
US.259879
Issued by
Philadelphia County, Dale Borough, Pennsylvania

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4130 Ridge Ave

PO Box 5621 Philadelphia, PA 19129

Structural Evaluation of Existing Storefront and Surrounding Structure

Project Address: 2237 Ridge Ave., Philadelphia, PA

To Whom it May Concern, Scope of Service

This Existing Structural Conditions Report has been prepared for the proposed storefront improvements at the above-referenced property. A site visit was conducted on March 24, 2026, and our findings are summarized herein.

The purpose of this report is to document observed structural deficiencies at the property. The scope of evaluation is limited to the front façade.

Observations were made at the front façade. No other areas or structural components were evaluated. Framing above the existing storefront was concealed at the time of the site visit and could not be observed.

The existing structure consists of rough-sawn wood framing supported by multi-wythe brick masonry bearing walls.

Summary of Key Findings

The building façade is generally in good overall condition. Observed deficiencies are localized and primarily related to minor masonry deterioration, including spalling, abandoned anchor penetrations, and isolated surface damage. These conditions are not indicative of widespread structural concerns but should be addressed to prevent water infiltration and ongoing deterioration. With routine repairs and maintenance, the façade can continue to perform as intended.

31 March 2026

PRESTONSTRUCTURAL

SOLUTIONS.COM

+1 215 701 3375

INFO@PRESTONSTRUCTURAL

SOLUTIONS.COM

Required Structural Improvements

Item #1

Location: Party Wall Condition at 2nd Floor

Deficiency: Existing brick at the interface between 2237 and 2235 exhibits signs of spalling and localized material loss.

Suggested Repair: Replace deteriorated and missing masonry at the party wall with new brick and mortar to match existing. Repoint surrounding joints as necessary to create a continuous, watertight assembly and prevent further water infiltration.

Recommended Structural Improvements (not required)

Item #2

Location: Front Façade

Deficiency: Miscellaneous voids and abandoned anchor penetrations from prior signage were observed throughout the front façade. Isolated masonry units exhibit chipping and surface deterioration.

Suggested Repair: Remove abandoned anchors and patch all masonry voids to prevent water infiltration. Replacement masonry units and mortar shall match existing and be subject to architect approval.

Assumptions, Limitations, and Reliance

This report has been prepared based on visual observations made during a site visit and on information available to Preston Structural Solutions, LLC at the time of the assessment. The evaluation was limited in nature and did not include comprehensive destructive testing, demolition, or verification of concealed or inaccessible conditions, except where limited exploratory demolition was observed in the field.

Preston Structural Solutions, LLC is not the original engineer of record for the structure and has not performed a complete review or verification of the original structural design, calculations, or construction documents, except where explicitly noted. The findings and recommendations herein shall not be interpreted as a certification of the overall structural adequacy of the building.

The existing framing above the storefront, supporting the overlying masonry, was not observable at the time of the site visit. This framing should be evaluated by the contractor once exposed. If significant deterioration is observed, or if there is uncertainty regarding the adequacy of the existing framing, Preston Structural Solutions, LLC should be notified for further evaluation.

The observations and conclusions presented herein are limited to conditions observed at the time of the site visit. Actual conditions may di6er as construction progresses or as concealed conditions are exposed.

Responsibility for construction means, methods, sequencing, temporary shoring, and job site safety remains solely with the contractor. Implementation of the recommended repairs may require temporary support, coordination with other trades, or additional engineering evaluation.

This report is intended for use by the client and project team for the purpose of evaluating and addressing the structural conditions described herein. Reliance by others, or use of this report for other purposes, is not authorized without written consent from Preston Structural Solutions, LLC.

Closing

We appreciate the opportunity to assist with the evaluation of the existing structural conditions at this project.

We are available to discuss the findings presented in this report, clarify recommended repair approaches, and assist with coordination as the project progresses.

Additional engineering services may be required during the implementation of repairs, upon exposure of concealed conditions, or as coordination with other project stakeholders advances. Further documentation and engineering design will be required as the project moves forward and as additional information becomes available.

Please contact our o6ice with any questions or to discuss next steps.

Sincerely, Ryan Preston, MS, PE

Founder & Principal Engineer

Preston Structural Solutions LLC

2026-03-31T11:08:46-0400
Ryan Preston

File details come from the government source that posted it. Updated .