Structural Evaluation of Existing Storefront and Surrounding Structure

Project Address: 2223 Ridge Ave, Philadelphia, PA

To Whom it May Concern, Scope of Service

This Existing Structural Conditions Report has been prepared for the proposed storefront improvements at the above-referenced property. A site visit was conducted on March 24, 2026, and our findings are summarized herein.

The purpose of this report is to document observed structural deficiencies at the property. The scope of evaluation is limited to the front façade.

Observations were made at the front façade. The foundation wall at the building perimeter beneath the storefront was not observed. We were not able to access the inside of the building. No other areas or structural components were evaluated. Framing above the existing storefront was concealed at the time of the site visit and could not be observed.

The existing structure consists of rough-sawn wood framing supported by multi-wythe brick masonry bearing walls.

Summary of Key Findings

The building is generally in good overall condition, with no significant structural deficiencies observed at the time of our site visit. The primary structural elements appear to be performing as intended. Observed concerns are limited to localized conditions, including out-of-plumb parapets and typical façade weathering such as mortar deterioration, minor masonry damage, and remnants of previous alterations. While the parapet conditions warrant attention due to potential safety concerns, the remaining items are not indicative of systemic structural issues.

Overall, the noted deficiencies are manageable and consistent with the age and exposure of the building. Recommended repairs are generally straightforward and focused on stabilization, maintenance, and restoration of the building envelope. Addressing these items in a timely manner will help prevent further deterioration, improve long-term durability, and maintain a safe condition for occupants and the public.

31 March 2026

PRESTONSTRUCTURAL

SOLUTIONS.COM

+1 215 701 3375

INFO@PRESTONSTRUCTURAL

SOLUTIONS.COM

Required Structural Improvements

Item #1

Location: Parapet Along Ridge Ave

Deficiency: The existing front parapet appears out of plumb and may present a safety hazard to pedestrians and tenants below.

Suggested Repair: Reset the masonry parapet to a plumb condition. Install a steel channel or angle diagonal kicker at the rear of the parapet to provide lateral bracing under wind loads. The kicker should be anchored to the parapet with a baseplate and adhesive anchors and connected to the roof framing with wood over framing/curbs to distribute load, blocking and thru bolts. Provide appropriate flashing at the roof to maintain a watertight assembly.

Item #2

Location: Parapet Along Cecil B. Moore

Deficiency: The existing rear parapet appears out of plumb and may present a safety hazard to pedestrians and tenants below.

Suggested Repair: Reset the masonry parapet to a plumb condition. Install a steel channel or angle diagonal kicker at the rear of the parapet to provide lateral bracing under wind loads. The kicker should be anchored to the parapet with a baseplate and adhesive anchors and connected to the roof framing with wood over framing/curbs to distribute load, blocking and thru bolts. Provide appropriate flashing at the roof to maintain a watertight assembly.

Recommended Structural Improvements (not required)

Item #3

Location: Several Locations at Facades along Ridge and Cecil B. Moore

Deficiency: The front and rear façades exhibit general signs of weathering, including prior patching, remnant signage anchors, chipping of masonry units, and mortar deterioration resulting in localized gaps. Vegetation growth, including roots, was observed within the façade along Cecil B. Moore Avenue. These conditions do not appear to present an immediate structural concern but may contribute to ongoing deterioration if not addressed.

Suggested Repair: Although non-structural, we recommend repairing these conditions to restore the storefront. Replacement masonry units and mortar should match the existing and be reviewed by the architectural team. Vegetation and roots should be removed, and deteriorated mortar joints should be repointed to mitigate water infiltration.

Assumptions, Limitations, and Reliance

This report has been prepared based on visual observations made during a site visit and on information available to Preston Structural Solutions, LLC at the time of the assessment. The evaluation was limited in nature and did not include comprehensive destructive testing, demolition, or verification of concealed or inaccessible conditions, except where limited exploratory demolition was observed in the field.

Preston Structural Solutions, LLC is not the original engineer of record for the structure and has not performed a complete review or verification of the original structural design, calculations, or construction documents, except where explicitly noted. The findings and recommendations herein shall not be interpreted as a certification of the overall structural adequacy of the building.

The existing framing above the storefront, supporting the overlying masonry, was not observable at the time of the site visit. This framing should be evaluated by the contractor once exposed. If significant deterioration is observed, or if there is uncertainty regarding the adequacy of the existing framing, Preston Structural Solutions, LLC should be notified for further evaluation.

The observations and conclusions presented herein are limited to conditions observed at the time of the site visit. Actual conditions may di9er as construction progresses or as concealed conditions are exposed.

Responsibility for construction means, methods, sequencing, temporary shoring, and job site safety remains solely with the contractor. Implementation of the recommended repairs may require temporary support, coordination with other trades, or additional engineering evaluation.

This report is intended for use by the client and project team for the purpose of evaluating and addressing the structural conditions described herein. Reliance by others, or use of this report for other purposes, is not authorized without written consent from Preston Structural Solutions, LLC.

Closing

We appreciate the opportunity to assist with the evaluation of the existing structural conditions at this project.

We are available to discuss the findings presented in this report, clarify recommended repair approaches, and assist with coordination as the project progresses.

Additional engineering services may be required during the implementation of repairs, upon exposure of concealed conditions, or as coordination with other project stakeholders advances. Further documentation and engineering design will be required as the project moves forward and as additional information becomes available.

Please contact our o9ice with any questions or to discuss next steps.

Sincerely, Ryan Preston, MS, PE

Founder & Principal Engineer

Preston Structural Solutions LLC