36E77619R0011 ATTACHMENT 6 - Radiation Oncology Drawings Final 96-119.pdf
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
e28
C DB
HACCU-B0005
HACCH-B0012
HEF-1
HACCU-1
HRRF-2
WP
NL-54
WP
NL-52
WP
NL-52
WP
NL-54
WP
NL-52
X30
X28
X27
X26
X25
X24
X23
X22
X21
E
FG
A
HSAF-1
WP
NL-52
HACCU-B0004
WP
NL-52
HACCH-B0013
WP
NL-54
HEX-ACCH-L2
WP
NL-54
HEX-ACCH-L1
WP
NL-54
HRRF-1
HSAF-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C U s e rs
\p e rm o \D o c u m e n ts
\7
.0
E
M
P e re z ri n g d u .c o m
.r v t
/2 /2
:2
:0
P
M
ES121P
ROOF PLAN - POWER CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
1/8" = 1'-0"ES121P
1 ROOF PLAN - ELECTRICAL
1" = 100'-0"
KEY PLAN ROOF
N
N
1.
2.
3.
SHEET NOTES -
EC SHALL REFER TO ARCHITECTURAL
FLOOR PLANS, REFLECTED CEILING PLANS
AND ELEVATIONS FOR EXACT LOCATIONS
AND MOUNTING HEIGHTS.
NORMAL BRANCH POWER CIRCUIT 'NL' IS
208/120V AND SHALL BE FED FORM PANEL
UL-B00-1, UNLESS OTHERWISE NOTED.
REFER TO THE MECHANICAL EQUIPMENT
SCHEDULE ON ES601 FOR PANELS AND
BREAKERS FOR MECHANICAL EQUIPMENT
CIRCUITS.
Revisions: Date:
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OSOS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
OS
OS
OS
OS
OS
DL
OS
OS OS OS
OSOS
OS
C DB
EXAM
B0205
EXAM
B0206
EXAM
B0209
TOILET
B0212
NURSE PRACTITIONER
B0213
LEAD PHYSICIAN
B0214
TOILET
B0217
CLEAN
B0215
HAC
B0218
CONFERENCE ROOM
B0220
ADMIN
B0216
CANCER CARE
B0228
RESEARCH
B0229
BLOCK MOLD FILM
PROCESS STORAGE
B0230
EXAM
B0211
NURSE
WORKSTATIONS
B0208
RESIDENT
WORKSTATIONS
B0227
RECEPTION
B0201
WAITING
B0200
STAFF LOUNGE
B0221
PHYSICIST
WORKROOM
B0222
LEAD PHYSICIST
B0223
CONTROL ROOM
B0014
CONTROL ROOM
B0011
VITALS
B0203
LOCKERS
B0219
ADMIN
B0224
EXAM
B0210
PHYSICIAN
WORKSTATIONS
B0226
PROCEDURE HOLDING
BAY
B0207
DRESSING / TOILET
B0007
CORRIDOR
C0A15
CORRIDOR
C0A14
CORRIDOR
C0A13
CORRIDOR
C0A12
CORRIDOR
C0A10
MECH / ELEC
B0225
SCHEDULERS
B0202
CORRIDOR
C0A17
LOGISTICS - CLEAN
B0234
DRESSING ROOM
B0010
CT SCANNER
B0004
PHYSICS STORAGE
B0233
LOGISTICS - DIRTY
B0235
HAC
B0230A
LOCKER ROOM
B0240
BREAK ROOM
B0234
HAC
B0232
DOSIMETRY
B0001
DRESSING / TOILET
B0008
CONTROL ROOM
B0002
CT ENTRY ROOM
B0003
SOILED
B0232
WAITING ROOM
B0009
ES302
ES301
ES303
ES201L
ES202L
ES201L
ES202L
ETR
ETR
LINAC 1
B0013
LINAC 2
B0012
CT EQUIPMENT
B0005
CN
R-7
(LH-22)
CN
R-7
CN
R-7
CN
R-7
(LH-22)
AC
NH-10a
CD
NH-10a
AC
CH-9b
CD
NH-10a
AC
CH-9b
CQ
CH-9b
CQ
CH-9b
CQ
NH-10a
CQ
NH-10a
CQ
NH-10a
CQ
CH-9c
CQ
CH-9c
CQ
CH-9b
CQ
NH-10a
CQ
CH-9c
CQ
CH-9c
CQ
NH-10a
CQ
CH-9b
CQ
CH-9a
CQ
CH-9a
CQ
NH-10b
CQ
NH-10b
CQ
CH-9c
CQ
CH-9c
AA
CH-9
CC
NH-12
CC
NH-12
AN
CH-9a
AN
NH-10b
AA
CH-9b
AA
NH-10a
CN
NH-12a
CN
NH-12a
CN
CH-11b
CN
CH-11b
CN
CH-11b
CN
CH-11b
CN
CH-11b
AN
CH-11b
AN
CH-11b
AN
NH-12a
AN
NH-12a
AN
CH-11b
AN
NH-12a
CE
NH-12a
CE
CH-11b
CE
NH-12a
CE
CH-11b
CE
NH-12a
CE
NH-12a
CE
CH-11b
CE
NH-12a
CE
CH-11b
CE
NH-12a
CE
CH-11b
CE
NH-12a
CE
NH-12a
CE
CH-11b
CF
NH-12a
CF
CH-11b
CF
NH-12a
CF
CH-11b
ETR
ETR
ETR
ETR
ETR
ETR
CN
R-3
CN
R-3
CN
R-3
(LH-22)
CN
R-3
Mo
Mo Mo
Mo
Mo
Mo
FC
CH-9
FC
CH-9
FC
NH-10
CQ
NH-10a
CQ
CH-9a
CQ
NH-10b
CQ
CH-9a
CQ
NH-10b
CN
NH-10a
CN
CH-9b
CN
NH-10a
CN
R-7
CC
CH-9
CN
CH-9f
CN
CH-9f
CN
CH-9d
CN
CH-9d
CN
CH-9d
CN
CH-9d
CN
CH-9d
DA
NH-10c
DA
NH-10c
CN
CH-11b
CN
CH-11b
CN
NH-12a
CN
NH-12a
X28
X27
X26
X25
X24
X23
X22
X21
X20
X19
XBXCXDXEXFXG E
FG
A
CN
R-7
CN
R-7
CN
R-7
(LH-22)
CN
R-6
CN
R-6
(LH-22)
CN
R-6
CN
R-6
CN
R-6
(LH-22)
CN
R-6
CN
R-6
(LH-22)
CN
R-6
CN
R-5
(LH-22)
CN
R-5
CN
R-7
(LH-22)
CN
R-7
CD
NH-10a
AC
CH-9b
CD
NH-10a
AC
CH-9b
CD
NH-10a
AC
CH-9b
CD
NH-10a
AC
CH-9b
Mo
WA
CH-9
DA
CH-9
WA
CH-9
DA
CH-9
AC
CH-9b
AC
NH-10a
AN
CH-9a
AN
NH-10b
AN
NH-10a
AN
CH-9b
AN
NH-10a
AN
CH-9b
CQ
NH-10a
CQ
CH-9b
CN
R-3
CN
R-3
(LH-22)CN
R-5
(LH-22)
CN
R-5
CN
R-5
(LH-22)
CN
R-5
CN
R-5
CN
R-5
(LH-22)
CN
R-3
(LH-22)
CN
R-4
CN
R-4
CN
R-4
(LH-22)
CN
R-3
CN
LH-22U
CN
R-2
CN
R-2
(LH-22)
CN
R-2
CN
R-2
XA
XA
XA
XB
AN
CH-11
WA
CH-11
WA
CH-11
DA
CH-11
DA
CH-11
DA
CH-11
DA
CH-11
XA
XA
XA XA
XA
XA
XA
XAXAXA
XA
XA
XA
XA
XA
XA
CT STORAGE
B0006
CN
R-5 a b b a b a b a b a a b ba a b a b ab c d ab ab b a c c b a a b b c b a a b a b b a b a
UC
NL-39
XG
LC
R-8
LC
R-8
LV
LV
LV
LV
LV
LV
LV
LV LV
LV
b a
CN
R-3
CN
NH-12a
CN
NH-12a
CN
NH-12a
CQ
NH-10b
0.04
0.05
0.060.07
0.08
0.09
0.10 0.11
0.12
0.13
CQ
CH-9b
CQ
CH-9b
CQ
CH-9b
CQ
CH-9b
XA
XA
baabbaab a ba b
UC
NL-15
UC
NL-15
UC
NL-15
UC
NL-13
b a f
(LH-22)
(LH-22)
(LH-22)
(LH-22)
(LH-22)
DD
NH-10a
DD
NH-10a
DD
NH-10a
DD
NH-10aDD
NH-10a
DD
NH-10a
DD
NH-10a
DD
NH-10a
DD
NH-10a
DD
NH-10a
DD
NH-10a
LV0.14
LD
R-12
UC
NL-13
CORRIDOR
C0A14
UC
NL-19
CN
R-5
LD
R-11
LD
R-11
LD
R-11
LD
R-11
DB
R-3
DB
R-3
DB
R-4
DA
NH-12
DA
NH-12
DA
NH-12
DA
NH-12
LD
R-12
LD
R-12
LD
R-12
DD
NH-10a
DD
NH-10a
DD
NH-10a
DA
NH-10a
DA
NH-10a
DA
NH-10a
DA
NH-10a
DA
NH-10a
DA
NH-10a DA
NH-10a
DB
CH-9b
DB
CH-9b DB
CH-9b
DB
CH-9b
DB
CH-9b
DB
CH-9b
DB
CH-9b
DB
CH-9b
DB
CH-9b
DB
CH-9b
DB
CH-9b
DB
CH-9b
(LH-22)
CONSULT / EXAM
B0204
XA
CN
R-6
Mo
CN
R-4
CD
CH-9b
CD
NH-10a
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C
R e v it L o c a lF ile s \7
.0
E k ro c a
.r v t
/2 /2
:4
:3
A M
ES201L
PARTIAL BASEMENT FLOOR PLAN
- LIGHTING
CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
1" = 100'-0"
KEY PLAN SOUTH
N
1.
2.
3.
4.
5.
6.
7.
8.
9.
SHEET NOTES -
KEYED NOTES -
REFERENCE ARCHITECTURAL PLANS,
ELEVATIONS AND DETAILS FOR EXACT
LOCATIONS OF ALL DEVICES SHOWN.
CIRCUIT NUMBERS INDICATED DO NOT
REFLECT ACTUAL POSITION OF THE CIRCUIT
BREAKER WITHIN THE PANEL. CIRCUIT
NUMBERS SHOWN REPRESENT INTENT OF
DEVICES CONNECTED TO A COMMON
CIRCUIT.
ALL 208/120 VOLT, NORMAL BRANCH
CIRCUITS "NL" SHALL BE SERVED FROM
PANEL UL-B00-1, UNLESS OTHERWISE NOTED.
ALL 480/277 VOLT, NORMAL BRANCH
CIRCUITS "NH" SHALL BE SERVED FROM
PANEL UH-B00-1, UNLESS OTHERWISE NOTED.
ALL 480/277 VOLT, CRITICAL BRANCH
CIRCUITS "CH" SHALL BE SERVED FROM
PANEL ELH-CR-B02-1, UNLESS OTHERWISE
NOTED.
ALL 480/277 VOLT, LIFE SAFETY BRANCH
CIRCUITS "LH" SHALL BE SERVED FROM
PANEL ELH-LS-B04-1, UNLESS OTHERWISE
NOTED.
ALL EXIT SIGNS SHALL BE WIRED TO CIRCUIT
ELH-LS-B04-1-26 UNLESS OTHERWISE NOTED.
"R" AS IN "R-*" INDICATES A RELAY CONTROL
CIRCUIT FED FROM LIGHTING CONTROL
PANEL LCP/B00-1 UNLESS OTHERWISE NOTED.
REFER TO LIGHTING CONTROL PANEL
SCHEDULE FOR CIRCUIT AND CONTROL
INFORMATION.
REFER TO ARCHITECTURAL PHASING PLANS
FOR EXACT EXTENT OF CONSTRUCTION.
1.
N
1/8" = 1'-0"ES201L
1 PARTIAL BASEMENT PLAN - LIGHTING
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
MOUNT LINEAR FIXTURE 3'-0" ABOVE
BOTTOM EDGE OF SKYLIGHT.
DL
e28
C DB
PET-MRI VESTIBULE
B0015
CORRIDOR
C0A17
ES201L
ES202L
ES201L
ES202L
CN
R-1
(LH-22)
CN
R-1
CN
R-1
CN
R-1
CN
R-1
(LH-22)
CN
R-1
CN
R-1
CN
R-1
CN
R-1
(LH-22)
CN
R-1
FC
NH-12a
FC
CH-11b
E31
X30
X28
E
FGA
XA
XA
XA
XAXA
FC
NH-12a
FC
CH-11b
XA
XA
XA
3a
3a
OD
R-10
OD
R-10
OE
R-9
OE
R-9
OA
R-9
OA
R-9
OA
R-9
3b
3b
OD
R-10
OD
R-10
OD
R-10
OD
R-10
LV
LV
CN
R-2
(LH-22)
CN
R-2
CN
R-2
CN
R-2
(LH-22)
CN
R-2
(LH-22)
(LH-22) (LH-22)
0.01
LV
0.02
0.03
(LH-22)
2 2
MECHANICAL ROOM
B0016
CORRIDOR
C0A19
OD
R-10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C U s e rs
\p e rm o \D o c u m e n ts
\7
.0
E
M
P e re z ri n g d u .c o m
.r v t
/2 /2
:2
:2
P
M
ES202L
PARTIAL BASEMENT FLOOR PLAN
- LIGHTING
CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
1/4" = 1'-0"ES202L
1 PARTIAL BASEMENT PLAN - LIGHTING NORTH
SHEET NOTES -
KEYED NOTES -
1.
2.
MOUNT FIXTURE TYPE OD, AT 108'-0"
ELEVATION TO BOTTOM OF FIXTURE,
TYPICAL.
MOUNT FIXTURE, TYPE OE, ABOVE DOOR
HEADER, CENTERED BETWEEN DOOR AND
SOFFIT.
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
1.
2.
3.
4.
5.
6.
7.
8.
REFERENCE ARCHITECTURAL PLANS,
ELEVATIONS AND DETAILS FOR EXACT
LOCATIONS OF ALL DEVICES SHOWN.
CIRCUIT NUMBERS INDICATED DO NOT
REFLECT ACTUAL POSITION OF THE
CIRCUIT BREAKER WITHIN THE PANEL.
CIRCUIT NUMBERS SHOWN REPRESENT
INTENT OF DEVICES CONNECTED TO A
COMMON CIRCUIT.
ALL 480/277 VOLT, NORMAL BRANCH
CIRCUITS "NH" SHALL BE SERVED FROM
PANEL UH-B00-1, UNLESS OTHERWISE
NOTED.
ALL 480/277 VOLT, CRITICAL BRANCH
CIRCUITS "CH" SHALL BE SERVED FROM
PANEL ELH-CR-B02-1, UNLESS OTHERWISE
NOTED.
ALL 480/277 VOLT, LIFE SAFETY BRANCH
CIRCUITS "LH" SHALL BE SERVED FROM
PANEL ELH-LS-B04-1, UNLESS OTHERWISE
NOTED.
ALL EXIT SIGNS SHALL BE WIRED TO
CIRCUIT ELH-LS-B04-1-26 UNLESS
OTHERWISE NOTED.
"R" AS IN "R-*" INDICATES A RELAY
CONTROL CIRCUIT FED FROM LIGHTING
CONTROL PANEL LCP/B00-1 UNLESS
OTHERWISE NOTED. REFER TO LIGHTING
CONTROL PANEL SCHEDULE FOR CIRCUIT
AND CONTROL INFORMATION.
REFER TO ARCHITECTURAL PHASING
PLANS FOR EXACT EXTENT OF
CONSTRUCTION.
N
N
1" = 100'-0"
KEY PLAN NORTH
MECH / ELEC
B0225 B00-1
UH
B00-1
EUL-CR
B00-1
LCP
B0225
ECRT-1
B00-1
EUH-Q
B0225
EQRT-1
B00-1
EUL-Q
A
X22
X21
A
CL-15
HTCC-1
HTCC-2
HVAV-XFRMR
B04-1
ELH-LS
EX
X28
B01-1
DL
B01-1
DH
T
EX
EX
EX
X19
XC
B02-1
UL
B02-2
UL
B02-4
UL
B02-3
UL
EQT
B02-1
EUL-Q
EX
EX
EX EX EX
EX
X24
XE
B02-1
ELH-CR
B02-1
EDH-CR
X25
EX
EX
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C U s e rs
\p e rm o \D o c u m e n ts
\7
.0
E
M
P e re z ri n g d u .c o m
.r v t
/2 /2
:2
:1
P
M
ES300
ENLARGED PLANS CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
1/4" = 1'-0"ES300
1 ENLARGED ELECTRICAL ROOM B0225
1/4" = 1'-0"ES300
4 ENLARGED ELECTRICAL ROOM B0448
1/4" = 1'-0"ES300
5 ENLARGED ELECTRICAL ROOM B0114
1/4" = 1'-0"ES300
2 ENLARGED ELECTRICAL ROOM B0214
1/4" = 1'-0"ES300
3 ENLARGED ELECTRICAL ROOM B0219
KEYED NOTES -
1. EXISTING CONDUIT RISERS.
N
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
NNNN
KEYED NOTES -
1. EXISTING JUNCTION BOX FEEDS PARKING
STRUCTURE. BOX SIZE IS APPROXIMATE
AND SHALL BE PROTECTED IN PLACE
DURING CONSTRUCTION.
J
NL-26NL-26NL-26
NL-26 NL-26
L-2
MS4
MS3
L-2 L-2
MS5
MS2
MS1
TC
CL-20
TC
CL-20
L-2
NL-22CL-16 NL-22 CL-16 NL-22
NL-24
CL-18
NL-24
CL-18
ED-2
LINAC 2
B0012
CONTROL ROOM
B0011
G E
N -2
PDCU
C L
-2
CL-20
SDX
SD
MS6
CITB
SV
NL-32
SV
NL-32 SV
NL-32
C
IT
B -2
FB2-2
X28
X27
X26
FG
NL-24
ED-2
LINAC 2
B0012
CONTROL ROOM
B0011
CB
CH-11
CB
CH-11
CB
CH-11
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
AZ
CH-11c
AZ
CH-11c
DA
CH-11h
DA
CH-11e
DA
CH-11f
CN
NH-12g
CN
NH-12g
33D
D
DD
D h e f g
X28
X27
X26
E FG
XG1
Mo
UC
NL-26
UC
NL-26
DC
NH-12f
DC
NH-12f
DC
NH-12f
DC
NH-12f
DC
NH-12f
DC
NH-12f
DE
CH-11d
DE
CH-11d
DE
CH-11d
DE
CH-11d
D Da b dD
Dfc
FC
NH-12
LINAC 2
B0012
CONTROL ROOM
B0011
4 5
X28
X27
X26
E FG
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C
R e v it L o c a lF ile s \7
.0
E k ro c a
.r v t
/2 /2
:4
:3
A M
ES301
ENLARGED PLANS CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
1/4" = 1'-0"ES301
2 LINAC ROOM B0012 - POWER
N
N
KEYED NOTES -
1.
2.
3.
1.
2.
ELEKTA VERSA HD DELIVERY SYSTEM
REFERENCE DRAWING
THE ELECTRICAL CONTRACTORS SHALL
INCLUDE ALL COSTS ASSOCIATED WITH
THE INSTALLATION OF THE ELECTRICAL
EQUIPMENT AND RACEWAYS INDICATED
ON THE DOCUMENTS DEVELOPED BY
ELEKTA TITLED VERSA HD DELIVERY
SYSTEM REFERENCE DRAWING DATED
JUNE 15, 2016.
FINAL SITE SPECIFIC DRAWINGS WERE NOT
RECEIVED BEFORE SUBMISSION. ALL
CONDUITS, RACEWAYS, AND ANY
EQUIPMENT BEYOND MAIN POWER FEED
"SD" AND "SDX" SHALL BE COORDINATED
PRIOR TO ROUGH-IN.
1.
2.
3.
DRAWING COMMENTS
DRAWING E1
a. ITEM "FB2" IS EQUIPMENT
CONNECTION OUTLET FB2-2 SHOWN
ON THIS DRAWING.
b. ITEM "GEN" IS EQUIPMENT
CONNECTION OUTLET GEN-2 SHOWN
ON THIS DRAWING.
DRAWING E1a
a. CLIENT TERMINAL BOX (CITB)
FURNISHED BY ELEKTA AND
INSTALLED BY EC.
DRAWING E2
a. PROVIDE ALL OF THE CONDUITS
INDICATED IN THE "ELECTRICAL
RACEWAY PLAN." COORDINATE
EXACT LOCATIONS OF ALL
COMPONENTS PRIOR TO ROUGH IN.
b. POWER CONNECTION TO LASERS
CIRCUIT IS EQUIPMENT CONNECTION
L1 SHOWN ON THIS DRAWING.
c. ITEM "ROL" IS LIGHTING FIXTURE XG
SHOWN ON THIS DRAWING.
1/4" = 1'-0"ES301
1 LINAC ROOM B0012 - LIGHTING
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
DETAIL NOTES -
1.
2.
3.
ALL 480/277 VOLT, NORMAL BRANCH
CIRCUITS "NH" SHALL BE SERVED FROM
PANEL UH-B00-1, UNLESS OTHERWISE
NOTED.
ALL 480/277 VOLT, CRITICAL BRANCH
CIRCUITS "CH" SHALL BE SERVED FROM
PANEL ELH-CR-B02-1, UNLESS OTHERWISE
NOTED.
NORMAL POWER BRANCH CIRCUIT "NL" IS
208/120V AND SHALL BE FED FROM PANEL
UL/BO7-1.NORMAL POWER BRANCH
CIRCUIT "NL" IS 208/120V AND SHALL BE
FED FROM PANEL UL/BO7-1.
1/4" = 1'-0"ES301
3 LINAC ROOM B0012 - CONDUIT AND RACEWAY
N
KEYED NOTES -
1.
2.
3.
SWITCH SHALL BE LABELED "LASERS."
BOX MOUNTED CIRCUIT BOARD (CITB) IS
SUPPLIED BY ELEKTA AND INSTALLED BY
EC.
PROVIDE 2#12 IN 3/4" CONDUIT FROM PUSH
BUTTON TO SHUNT TRIP CIRCUIT
BREAKERS. WIRE CIRCUIT IN SERIES WITH
CIRCUIT BREAKERS SD AND SDX.
DETAIL NOTES -
1.
2.
3.
CIRCUIT NUMBERS INDICATED DO NOT
REFLECT THE ACTUAL POSITION OF THE
CIRCUIT BREAKERS IN THE PANEL. RATHER
THE NUMBER INDICATES WHICH DEVICES
ARE CONNECTED TO A COMMON CIRCUIT.
NORMAL POWER BRANCH CIRCUIT "NL" IS
208/120V AND SHALL BE FED FROM PANEL
UL/BO7-1.
CRITICAL POWER BRANCH CIRCUIT "CL" IS
208/120V AND SHALL BE FED FROM PANEL
EULCR/BO7-1
FIXTURE SHALL BE MOUNTED 6" ABOVE
DOOR HEADER, CENTERED OVER DOOR.
WIRE LIGHT FIXTURE THROUGH CITB IN
LINEAR ACCELERATOR ROOM. SEE 1/ES501
FOR WIRING SCHEMATIC.
STACK SWITCHES VERTICALLY. PROVIDE
TWO SWITCH GANGS. BOTTOM GANG
SHALL INCLUDE DIMMERS FOR SWITCH
LEGS "a", "b", AND "d". TOP SWITCH GANG SHALL INCLUDE CONTROLS FOR "c" AND "f" SWITCH LEGS.
DOWNLIGHT, TYPE DC, SHALL BE
CENTERED ON GRAPHIC PANEL. OFFSET
FROM WALL APPROXIMATELY 6 INCHES.
VERIFY FINAL LOCATION FROM
ARCHITECTURAL ELEVATIONS, PRIOR TO
ROUGH-IN, TYPICAL.
KEYED NOTES -
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
PROVIDE 4"W x 9"L GROMMETED CABLE
PASSAGE IN COVER OF FLOOR RACEWAY.
PROVIDE 12"W x 12"L x 12"D FLOOR BOX
WITH REMOVABLE 1/4" THICK STEEL
COVER PLATE, FLUSH MOUNTED FOR
TERMINATION OF UNDERSLAB 4"
CONDUITS.
PROVIDE 10"W x 10"L x 12"D FLOOR BOX, FLUSH MOUNTED WITH FINISH FLOOR. NO
COVER PLATE.
PROVIDE 12"W x 24"L x 12"D FLOOR BOX
WITH REMOVABLE 1/4" THICK STEEL
COVER PLATE, FLUSH MOUNTED FOR
TERMINATION OF UNDERSLAB 4"
CONDUITS.
12" W x MIN. 8"D FLOOR TRENCH
RACEWAY, FLUSH MOUNTED WITH 1/4"
THICK STEEL COVER PLATE.
(3) 4" CONDUITS FROM FB3 TO WJB1. DO
NOT RUN UNDER TABLE PIT. CONDUITS TO
BE WATER TIGHT.
(1) 4" CONDUITS FROM FB3 TO TO FB4.
CONDUIT TO BE WATER TIGHT.
12"W x 3 1/2"D WALL RACEWAY, SURFACE
MOUNTED, WITH REMOVABLE SCREW-
TYPE COVER PLATE.
12"H x 24"L x6"D WALL JUNCTION BOX
WITH REMOVABLE 1/4" THICK STEEL
COVER PLATE, FLUSH MOUNTED WITH
FINISH WALL FOR TERMINATION OF
UNDERSLAB 4" CONDUITS.
PROVIDE 1" CONDUIT FROM FLOOR BOX TO
TABLE PIT. CONDUIT SHALL NOT EXCEED
5'-4".
DETAIL NOTES -
1.
2.
3.
4.
5.
EC SHALL REFER TO ARCHITECTURAL
FLOOR PLANS, REFLECTED CEILING PLANS
AND ELEVATIONS FOR EXACT LOCATIONS
AND MOUNTING HEIGHTS.
COORDINATE ALL UNDERGROUND
CONDUIT ENTRANCE POINTS TO LINEAR
ACCELERATOR ROOM WITH ARCHITECT
AND STRUCTURAL DRAWINGS PRIOR TO
COMMENCING WORK.
CONDUIT ROUTES SHOWN ARE FOR
DIAGRAMMATIC PURPOSES ONLY.
ELECTRICAL CONTRACTOR SHALL
COORDINATE EXACT ROUTE WITH ALL
OTHER DISCIPLINES.
ROUTE ALL ROOM PENETRATIONS AS
PERPENDICULAR TO THE ISOCENTER AS
POSSIBLE TO AVOID RADIATION SCATTER.
VERIFY ALL ROOM PENETRATIONS WITH
THE PHYSICIST OF RECORD.
CONDUIT SHOWN IS FOR ELEKTA
EQUIPMENT REQUIREMENTS, UNLESS
OTHERWISE NOTED.
KEYED NOTES -
11.
12.
13.
14.
PROVIDE 4" x 4" x 4" CEILING JUNCTION
BOX, MOUNTED ABOVE FINISH CEILING AT
HEXAPOD CAMERA LOCATION. PROVIDE
REMOVABLE COVER FOR CABLE PASSAGE.
PROVIDE 6" x 6" WIRE CABLE TRAY
MOUNTED UNDER COUNTERTOP FOR
CABLE MANAGEMENT.
PROVIDE 6" x 6" WALL CHASE FOR
CONNECTION BETWEEN CPU CLOSET AND
CONTROL ROOM. LOCATE BELOW
COUNTERTOP. MATCH HEIGHT TO WIRE
CABLE TRAY.
PROVIDE (1) 1-1/2"C FROM FLOOR BOX TO
PDCU. REFER TO ONE LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
C DB
CONTROL ROOM
B0014
G E
N -1
PDCU
NL-34 CL-10NL-34CL-10NL-34
NL-36
N L
-3
C L
-1
N L
-3
N L
-3
N L
-3
NL-38 NL-38
C L
-1
CL-14
L-1
N L
-3
CL-12
MS6
MS4
MS3
L-1
L-1
MS5
MS2
MS1
SDX
SD
TC
CL-14
TC
CL-14
L-1
LINAC 1
B0013
S V
N L
-4
SV
NL-44
SV
NL-44
C
IT
B
-1CITB
ED-1
FB2-1
X28
X27
X26
ED-1
C DB
CONTROL ROOM
B0014
CN
NH-12k
CN
NH-12k
DA
CH-11g
DA
CH-11h
DA
CH-11j
CB
CH-11
CB
CH-11
CB
CH-11
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
AZ
CH-11c
AZ
CH-11c
33 D
DD abd
D D
D j hg
Dk
FP
NH-12
X28
X27
X26
E
XG1
D
Df c
DE
CH-11d
DE
CH-11d
DE
CH-11d
DE
CH-11d
DC
NH-12f
DC
NH-12f
DC
NH-12f
UC
NL-38
UC
NL-38
DC
NH-12f
DC
NH-12f
DC
NH-12f
C DB
CONTROL ROOM
B0014
LINAC 1
B0013
X28
X27
X26
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C
R e v it L o c a lF ile s \7
.0
E k ro c a
.r v t
/2 /2
:4
:3
A M
ES302
ENLARGED PLANS CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
1/4" = 1'-0"ES302
2 LINAC ROOM B0013 - POWER
N
DETAIL NOTES -
KEYED NOTES -
1.
2.
N
1/4" = 1'-0"ES302
1 LINAC ROOM B0013 - LIGHTING
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
1.
2.
3.
ALL 480/277 VOLT, NORMAL BRANCH
CIRCUITS "NH" SHALL BE SERVED FROM
PANEL UH-B00-1, UNLESS OTHERWISE
NOTED.
ALL 480/277 VOLT, CRITICAL BRANCH
CIRCUITS "CH" SHALL BE SERVED FROM
PANEL ELH-CR-B02-1, UNLESS OTHERWISE
NOTED.
NORMAL POWER BRANCH CIRCUIT "NL" IS
208/120V AND SHALL BE FED FROM PANEL
UL/BO7-1.
1/4" = 1'-0"ES302
4 LINAC ROOM B0013 - CONDUIT AND RACEWAY
KEYED NOTES -
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
PROVIDE 4"W x 9"L GROMMETED CABLE
PASSAGE IN COVER OF FLOOR RACEWAY.
PROVIDE 12"W x 12"L x 12"D FLOOR BOX
WITH REMOVABLE 1/4" THICK STEEL
COVER PLATE, FLUSH MOUNTED FOR
TERMINATION OF UNDERSLAB 4"
CONDUITS.
PROVIDE 10"W x 10"L x 12"D FLOOR BOX, FLUSH MOUNTED WITH FINISH FLOOR. NO
COVER PLATE.
PROVIDE 12"W x 24"L x 12"D FLOOR BOX
WITH REMOVABLE 1/4" THICK STEEL
COVER PLATE, FLUSH MOUNTED FOR
TERMINATION OF UNDERSLAB 4"
CONDUITS.
12" W x MIN. 8"D FLOOR TRENCH
RACEWAY, FLUSH MOUNTED WITH 1/4"
THICK STEEL COVER PLATE.
(3) 4" CONDUITS FROM FB3 TO WJB1. DO
NOT RUN UNDER TABLE PIT. CONDUITS TO
BE WATER TIGHT.
(1) 4" CONDUITS FROM FB3 TO TO FB4.
CONDUIT TO BE WATER TIGHT.
12"W x 3 1/2"D WALL RACEWAY, SURFACE
MOUNTED, WITH REMOVABLE SCREW-
TYPE COVER PLATE.
12"H x 24"L x6"D WALL JUNCTION BOX
WITH REMOVABLE 1/4" THICK STEEL
COVER PLATE, FLUSH MOUNTED WITH
FINISH WALL FOR TERMINATION OF
UNDERSLAB 4" CONDUITS.
PROVIDE 1" CONDUIT FROM FLOOR BOX TO
TABLE PIT.
DETAIL NOTES -
1.
2.
3.
4.
5.
EC SHALL REFER TO ARCHITECTURAL
FLOOR PLANS, REFLECTED CEILING PLANS
AND ELEVATIONS FOR EXACT LOCATIONS
AND MOUNTING HEIGHTS.
COORDINATE ALL UNDERGROUND
CONDUIT ENTRANCE POINTS TO LINEAR
ACCELERATOR ROOM WITH ARCHITECT
AND STRUCTURAL DRAWINGS PRIOR TO
COMMENCING WORK.
CONDUIT ROUTES SHOWN ARE FOR
DIAGRAMMATIC PURPOSES ONLY.
ELECTRICAL CONTRACTOR SHALL
COORDINATE EXACT ROUTE WITH ALL
OTHER DISCIPLINES.
ROUTE ALL ROOM PENETRATIONS AS
PERPENDICULAR TO THE ISOCENTER AS
POSSIBLE TO AVOID RADIATION SCATTER.
VERIFY ALL ROOM PENETRATIONS WITH
THE PHYSICIST OF RECORD.
CONDUIT SHOWN IS FOR ELEKTA
EQUIPMENT REQUIREMENTS, UNLESS
OTHERWISE NOTED.
N
KEYED NOTES -
1.
2.
3.
SWITCH SHALL BE LABELED "LASERS."
BOX MOUNTED CIRCUIT BOARD (CITB) IS
SUPPLIED BY ELEKTA AND INSTALLED BY
EC. REFER TO DETAIL 1/ES501 FOR WIRING
PROVIDED BY EC.
PROVIDE 2#12 IN 3/4" CONDUIT FROM PUSH
BUTTON TO SHUNT TRIP CIRCUIT
BREAKERS. WIRE CIRCUIT IN SERIES WITH
CIRCUIT BREAKERS SD AND SDX.
DETAIL NOTES -
1.
2.
3.
CIRCUIT NUMBERS INDICATED DO NOT
REFLECT THE ACTUAL POSITION OF THE
CIRCUIT BREAKERS IN THE PANEL. RATHER
THE NUMBER INDICATES WHICH DEVICES
ARE CONNECTED TO A COMMON CIRCUIT.
NORMAL POWER BRANCH CIRCUIT "NL" IS
208/120V AND SHALL BE FED FROM PANEL
UL/BO7-1.
CRITICAL POWER BRANCH CIRCUIT "CL" IS
208/120V AND SHALL BE FED FROM PANEL
EULCR/BO7-1
FIXTURE SHALL BE MOUNTED 6" ABOVE
DOOR HEADER, CENTERED OVER DOOR.
WIRE LIGHT FIXTURE THROUGH CITB IN
LINEAR ACCELERATOR ROOM. SEE 1/ES501
FOR WIRING SCHEMATIC.
STACK SWITCHES VERTICALLY. PROVIDE
TWO SWITCH GANGS. BOTTOM GANG
SHALL INCLUDE DIMMERS FOR SWITCH
LEGS "a", "b", AND "d". TOP SWITCH GANG SHALL INCLUDE CONTROLS FOR "c" AND "f" SWITCH LEGS.
1.
2.
ELEKTA VERSA HD DELIVERY SYSTEM
REFERENCE DRAWING
THE ELECTRICAL CONTRACTORS SHALL
INCLUDE ALL COSTS ASSOCIATED WITH
THE INSTALLATION OF THE ELECTRICAL
EQUIPMENT AND RACEWAYS INDICATED
ON THE DOCUMENTS DEVELOPED BY
ELEKTA TITLED VERSA HD DELIVERY
SYSTEM REFERENCE DRAWING DATED
JUNE 15, 2016.
FINAL SITE SPECIFIC DRAWINGS WERE NOT
RECEIVED BEFORE SUBMISSION. ALL
CONDUITS, RACEWAYS, AND ANY
EQUIPMENT BEYOND MAIN POWER FEED
"SD" AND "SDX" SHALL BE COORDINATED
PRIOR TO ROUGH-IN.
1.
2.
3.
DRAWING COMMENTS
DRAWING E1
a. ITEM "FB2" IS EQUIPMENT
CONNECTION OUTLET FB2-1 SHOWN
ON THIS DRAWING.
b. ITEM "GEN" IS EQUIPMENT
CONNECTION OUTLET GEN-1 SHOWN
ON THIS DRAWING.
DRAWING E1a
a. CLIENT TERMINAL BOX (CITB)
FURNISHED BY ELEKTA AND
INSTALLED BY EC.
DRAWING E2
a. PROVIDE ALL OF THE CONDUITS
INDICATED IN THE "ELECTRICAL
RACEWAY PLAN." COORDINATE
EXACT LOCATIONS OF ALL
COMPONENTS PRIOR TO ROUGH IN.
b. POWER CONNECTION TO LASERS
CIRCUIT IS EQUIPMENT CONNECTION
L1 SHOWN ON THIS DRAWING.
c. ITEM "ROL" IS LIGHTING FIXTURE XG
SHOWN ON THIS DRAWING.
KEYED NOTES -
11.
12.
13.
14.
PROVIDE 4" x 4" x 4" CEILING JUNCTION
BOX, MOUNTED ABOVE FINISH CEILING AT
HEXAPOD CAMERA LOCATION. PROVIDE
REMOVABLE COVER FOR CABLE PASSAGE.
PROVIDE 6" x 6" WIRE CABLE TRAY
MOUNTED UNDER COUNTERTOP FOR
CABLE MANAGEMENT.
PROVIDE 6" x 6" WALL CHASE FOR
CONNECTION BETWEEN CPU CLOSET AND
CONTROL ROOM. LOCATE BELOW
COUNTERTOP. MATCH HEIGHT TO WIRE
CABLE TRAY.
PROVIDE (1) 1-1/2"C FROM FLOOR BOX TO
PDCU. REFER TO ONE LINE DIAGRAM FOR
ADDITIONAL INFORMATION.
J
J
J
J
D
CT SCANNER
B0004
CONTROL ROOM
B0002
CT ENTRY ROOM
B0003
CT STORAGE
B0006
SPD
PDC
DD
GFI
CL-6
UL-B00-1-18
C L
-6
UL-B00-1-18
UL-B00-1-18
UL-B00-1-16 UL-B00-1-16
UL-B00-1-16
C L
-6EPO
EPO
EPO
X26
X25
X24
X23
E FG
HRACU-B0004
UL-B00-1-18
48"
UL-B00-1-20
CT EQUIPMENT
B0005
UL-B00-1-16
UL-B00-1-18
CL-8
CL-8
CL-8
L-3
L-3
L-3
MP
UL-B00-1-16
D
CT SCANNER
B0004
CONTROL ROOM
B0002
CT ENTRY ROOM
B0003
CN
NH-12l CN
NH-12l
CN
NH-12l
AA
CH-11
DA
CH-11m
DA
CH-11n
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
CB
NH-12a
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
DE
CH-11b
AZ
CH-11c
AZ
CH-11c
3 D DDl m n
Dp CH-11p
DA
3l
DD cba
X
X25
X24
X23
E FG
Mo Mo
XG
DC
NH-12c
DC
NH-12c
DC
NH-12c
DC
NH-12c
UC
NL-18
UC
NL-18
AA
NH-12
AA
NH-12
AA
NH-12
AA
NH-12
AA
NH-12
Dd
CT STORAGE
B0006
CT EQUIPMENT
B0005
D
X26
X25
X24
X23
E FG
CT SCANNER
B0004
CONTROL ROOM
B0002
CT ENTRY ROOM
B0003
CT STORAGE
B0006
VD1
CT EQUIPMENT
B0005
DRESSING ROOM
B0010
MP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C U s e rs
\p e rm o \D o c u m e n ts
\7
.0
E
M
P e re z ri n g d u .c o m
.r v t
/2 /2
:2
:5
P
M
ES303
ENLARGED PLANS CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
1/4" = 1'-0"ES303
2 CT SCAN ROOM B0004 - POWER
N
1.
2.
SIEMENS SOMATOM CONFIDENCE
TYPICAL FINAL DRAWING SET
KEYED NOTES -
THE ELECTRICAL CONTRACTORS SHALL
INCLUDE ALL COSTS ASSOCIATED WITH
THE INSTALLATION OF THE ELECTRICAL
EQUIPMENT AND RACEWAYS INDICATED
ON THE DOCUMENTS DEVELOPED BY
SIEMENS' TITLED SOMATOM CONFIDENCE
TYPICAL FINAL DRAWING SET.
FINAL SITE SPECIFIC DRAWINGS WERE NOT
RECEIVED BEFORE SUBMISSION. ALL
CONDUITS, RACEWAYS, AND ANY
EQUIPMENT BEYOND MAIN POWER FEED
"MP" SHALL BE COORDINATED PRIOR TO
ROUGH-IN.
1.
2.
DISCONNECT ENCLOSURE "MP" AS
INDICATED ON SHEET E-101 & E-102 OF
MANUFACTURERS TYPICAL SITE
DRAWINGS.
EPO'S MUST HAVE FAIL SAFE DESIGN AND
MECHANICAL LATCHING MECHANISM.
N
DETAIL NOTES -
1.
DRAWING COMMENTS
DRAWINGS E-101
a. INSTALL ALL OF THE CONDUITS
INDICATED IN THE "ELECTRICAL
RACEWAY PLAN." COORDINATE
EXACT LOCATIONS OF ALL
COMPONENTS PRIOR TO ROUGH IN.
b. ALL 120VOLT CIRCUITS ARE SHOWN
ON THE ELECTRICAL/TECHNOLOGY
DRAWINGS.
c. REFER TO ELECTRICAL ONE LINE
DIAGRAM AND PANEL SCHEDULE FOR
ADDITIONAL INFORMATION ON MAIN
PANEL "MP."
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
1.
2.
3.
ALL 480/277 VOLT, NORMAL BRANCH
CIRCUITS "NH" SHALL BE SERVED FROM
PANEL UH-B00-1, UNLESS OTHERWISE
NOTED.
ALL 480/277 VOLT, CRITICAL BRANCH
CIRCUITS "CH" SHALL BE SERVED FROM
PANEL ELH-CR-B02-1, UNLESS OTHERWISE
NOTED.
NORMAL POWER BRANCH CIRCUIT "NL" IS
208/120V AND SHALL BE FED FROM PANEL
UL-B00-1.
1/4" = 1'-0"ES303
1 CT SCAN ROOM B0004 - LIGHTING
1/4" = 1'-0"ES303
3 CT SCAN ROOM B0004 - CONDUITS AND RACEWAY
KEYED NOTES -
1.
2.
3.
4.
PROVIDE PULL BOX MOUNTED FLUSH WITH
FINISHED WALL PROVIDED WITH 2"Ø
OPENING IN FINISHED COVER. LOCATE THE
SPD WITHIN 3 FEET CABLE RUN FROM
CIRCUIT BREAKER. VERIFY HEIGHT WITH
OWNER PRIOR TO INSTALL.
PROVIDE 10" x 3-1/2" VERTICAL
ELECTRICAL DUCT WITH FINISHED,
REMOVABLE COVERS MOUNTED FLUSH
WITH FINISHED WALL. DUCT SHALL
EXTEND FROM FROM FLOOR LINE TO END
ABOVE FINISHED CEILING. DIVIDE DUCT
INTO TWO SECTIONS WITH METAL
DIVIDERS.
PROVIDE 10" x 3-1/2" HORIZONTAL
ELECTRICAL DUCT SURFACE MOUNTED AT
THE FLOOR LINE. DIVIDE DUCT INTO TWO
SECTIONS WITH METAL DIVIDERS.
PROVIDE 10"X4" OPENING WHERE KEYED
NOTE IS SHOWN.
APPROXIMATE CONDUIT ROUTE BETWEEN
EPO'S. PROVIDE 2#12 & 1#12 GND IN
3/4"CONDUIT BETWEEN EPO'S.
DETAIL NOTES -
1.
2.
3.
4.
EC SHALL REFER TO ARCHITECTURAL
FLOOR PLANS, REFLECTED CEILING PLANS
AND ELEVATIONS FOR EXACT LOCATIONS
AND MOUNTING HEIGHTS.
CONDUIT ROUTES SHOWN ARE FOR
DIAGRAMMATIC PURPOSES ONLY.
ELECTRICAL CONTRACTOR SHALL
COORDINATE EXACT ROUTE WITH ALL
OTHER DISCIPLINES.
CONDUIT SHOWN IS FOR SIEMENS
EQUIPMENT REQUIREMENTS, UNLESS
OTHERWISE NOTED.
EC SHALL LEAVE A MINIMUM OF 10 FEET
OF WIRE TAILS AT ALL OUTLET POINTS
WITH WIRE IDENTIFICATION TAGGED AT
BOTH ENDS FOR FINAL CONNECTION.
DETAIL NOTES -
1.
2.
3.
CIRCUIT NUMBERS INDICATED DO NOT
REFLECT THE ACTUAL POSITION OF THE
CIRCUIT BREAKERS IN THE PANEL. RATHER
THE NUMBER NUMBERS INDICATE WHICH
DEVICES ARE CONNECTED TO A COMMON
CIRCUIT.
NORMAL POWER BRANCH CIRCUIT "NL" IS
208/120V AND SHALL BE FED FROM PANEL
UL-B00-1.
CRITICAL POWER BRANCH CIRCUIT "CL" IS
208/120V AND SHALL BE FED FROM PANEL
EUL-CR-B00-1
N
KEYED NOTES -
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
PROVIDE PULL BOX MOUNTED ABOVE
FINISH CEILING. SIZE BOX AS REQUIRED
FOR CONDUIT TERMINATIONS.
PROVIDE PULL BOX MOUNTED FLUSH WITH
FINISHED WALL. SIZE BOX AS REQUIRED
FOR CONDUIT TERMINATIONS.
PROVIDE 12" x 2-1/2" ELECTRICAL DUCT
MOUNTED FLUSH WITH FINISHED FLOOR.
DUCT SHALL HAVE WATERPROOF
REMOVABLE COVERS WITH FINISHES TO
MATCH FLOORING. DIVIDE DUCT INTO
TWO SECTIONS WITH METAL DIVIDERS.
PROVIDE (2) 12" X 5" RACEWAY OPENINGS
FLUSH WITH THE FINISHED FLOOR.
PROVIDE 12" X 8" RACEWAY OPENINGS
FLUSH WITH THE FINISHED FLOOR.
PROVIDE (1) 3/4" CONDUIT FROM DUCT TO
DOOR SWITCH.
APPROXIMATE CONDUIT ROUTE BETWEEN
"MP" AND PDC. REFER TO ONE LINE
DIAGRAM FOR ADDITIONAL INFORMATION.
PROVIDE 2-1/2" CONDUIT FROM VERDICAL
DUCT VD1 TO VD2.
PROVIDE 3" CONDUIT FROM PULL BOX TO
VERTICAL DUCT.
PROVIDE 1" CONDUIT INBETWEEN LASER
JUNCTION BOXES.
CONDUIT LEGEND
ABOVE ACCESSIBLE CEILING
BENEATH FLOOR SLAB
KEYED NOTES -
1.
2.
FIXTURE SHALL BE MOUNTED 6" ABOVE
DOOR HEADER, CENTERED OVER DOOR.
DOWNLIGHT, TYPE DC, SHALL BE
CENTERED ON GRAPHIC PANEL. OFFSET
FROM WALL APPROXIMATELY 6 INCHES.
VERIFY FINAL LOCATION FROM
ARCHITECTURAL ELEVATIONS, PRIOR TO
ROUGH-IN, TYPICAL.
XX
XX
MANUAL OR AUTOMATIC
PANELBOARD - REFER TO PANEL
OVERLOAD
ENCLOSURE
EQUIPMENT CONNECTION -
ENGINE GENERATOR
TRANSFORMER
XX
XX
SURGE SUPPRESSION
DENOTES
LA = LIGHTNING ARRESTORS
SPD = SURGE PROTECTIVE DEVICE
FEEDER CONTINUATION CONNECTION #
FEEDER CONTINUED ON SHEET INDICATED
DEVICE UPSTREAM OR DOWNSTREAM
(CAP)
(ATS)
CAPACITOR
AUTOMATIC TRANSFER SWITCH
KEY INTERLOCKING - KEY #
KEY NORMALLY REMOVED
SEE EQUIPMENT SCHEDULE
"AF" - DENOTES AMP FRAME
"XXX" - DENOTES AMP RATING
GP - GROUND FAULT PROTECTION - PERSONNEL
UVT - UNDER VOLTAGE TRIP
ST - SHUNT TRIP
MC - MOLDED CASE CIRCUIT BREAKER
SS - SOLID STATE MOLDED CASE CIRCUIT BREAKER
IC - INSULATED CASE CIRCUIT BREAKER
PC - LOW VOLTAGE POWER CIRCUIT BREAKER
GE - GROUND FAULT PROTECTION - EQUIPMENT
ALS - ALARM SWITCH
AXS - AUXILIARY SWITCH
EOP - ELECTRIC OPERATOR
AF - ARC FAULT CIRCUIT INTERRUPTER (RESIDENTIAL ONLY)
CL - CURRENT LIMITING
(XX) DEVICE DESIGNNATION
DENOTES THE FOLLOWING:
DENOTES THE FOLLOWING:
(CB) CIRCUIT BREAKER
(CON) CONTACTOR
(DS) DISCONNECT SWITCH
(VM)
(AM)
VOLTMETER
AMMETER
DENOTES THE FOLLOWING:
(VS) VOLTMETER SWITCH
(AS) AMMETER SWITCH
(M) KWHR METER
(DM) DIGITAL METER
XX
(XX) DEVICE DESIGNATION TYPE -
DENOTES THE FOLLOWING:
SEE SPECIFICATION
-SEE SCHEDULE & DETAILS
"AS" - DENOTES AMP SENSOR
"AT" - DENOTES AMP TRIP
GS - GROUND FAULT SENSING / ALARM
HC - HEATING, COOLING, AIR CONDITIONING, REFRIGERATION - HCAR
HM - HIGH MAGNETIC - HID, MOTORS
MS - MOLDED CASE SWITCH
MP - MOTOR CIRCUIT PROTECTOR
L1 - LONG TIME / INSTANTANEOUS - LI
L2 - LONG TIME / SHORT TIME / INSTANTANEOUS - LSI
L3 - LONG TIME / SHORT TIME / INSTANTANEOUS / GROUND FAULT TRIP - LSIG
L4 - LONG TIME / SHORT TIME / INSTANTANEOUS / GROUND FAULT SENSING - LSIA
SC - SYSTEM COMMUNICATION
SD - SYSTEM DIAGNOSTICS
SM - SYSTEM MONITORING
ZS - ZONE SELECTIVE INTERLOCKING
"XXX" - DENOTES AMP RATING
VW - VIEWING WINDOW
AXS - AUXILIARY SWITCH
DL - DOUBLE LUGS
PL - PILOT LIGHT
DS - UNFUSED DISCONNECT SWITCH
EDS - ELEVATOR DISCONNECT SWITCH
"AS" - DENOTES AMP SWITCH
"AF" - DENOTES AMP FUSE
AR - ARC FLASH REDUCTION
LOW VOLTAGE
LOW VOLTAGE FUSED
LOW VOLTAGE
LOW VOLTAGE
LOW VOLTAGE
FUSE
DISCONNECT SWITCH
DISCONNECT SWITCH
CIRCUIT BREAKER
DRAWOUT
LOW VOLTAGE
DRAWOUT POWER
CIRCUIT BREAKER
CIRCUIT BREAKER
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
CAPACITOR
GROUND
G
JUNCTION BOX
KEY INTERLOCKING - KEY #
KEY NORMALLY INSERTED
-SEE SCHEDULE & DETAILS
TRANSFER SWITCH
NORMALLY CLOSED
CONTACTOR
NORMALLY OPEN
CONTACTOR
CONTROL SWITCH
FLOAT SWITCH
LIGHT FIXTURE
NO
NC
NO
FR - FULLY RATED (100%)
1.
NEW.
2.
ARE EXISTING TO REMAIN.
3.
BELOW ARE EXISTING TO BE REMOVED.
4.
BELOW ARE TYPICAL EQUIPMENT DIVISIONS.
5.
FUTURE.
6.
BE KEPT TO AN ABSOLUTE MINIMUM.
7.
DIAGRAM SHALL BE PROTECTED FROM AVAILABLE FAULT CURRENT
SHOWN BY EITHER OF THE FOLLOWING METHODS:
- PROVIDE BREAKERS WITH A MINIMUM AIC RATING GREATER THAN
INDICATED
- THE SERIES RATING METHOD IS NOT ACCEPTABLE
1 - NON VENTILATED ENCLOSURE
2 - INTEGRAL STRIP HEATER
3 - WEATHER SHIELD
OPTIONS
TEMPERATURE RISE
SECONDARY VOLTAGE
PRIMARY VOLTAGE
kVA
TRANSFORMER ID
RATING
TYPE
DT - DRY TYPE
LF - LIQUID FILLED
DP - DRY TYPE PAD MOUNT
LP - LIQUID FILLED PAD MOUNT
GP - GENERAL PURPOSE
K-# - K-RATED
EE - ENERGY EFFICIENT
4 - NEMA 3R
5 - STAINLESS STEEL
CR - CAST RESIN
EC - ENCAPSULATED CORE
N - NORMAL BRANCH
LS - LIFE SAFETY BRANCH
CR - CRITICAL CARE BRANCH
BRANCH
EQ - EQUIPMENT BRANCH
EM - EMERGENCY BRANCH
TRANSFER SWITCH ID
ES - ESSENTIAL SYSTEMS
NES - NON ESSENTIAL SYSTEMS
AMPS
VOLTAGE
CLOSING & WITHSTAND AIC RATING
TRANSFER
AUTO - AUTOMATIC
MAN - MANUAL
POLES
TRANSFER SWITCH TYPE
OPTIONS
1 - LOAD SHED RELAY
2 - BLOCK TRANSFER RELAY
3 - SYNCH CHECK RELAY
4 - PEAK READING AMMETER
5 - STANDARD METER
6 - VOLTMETER
7 - COMPRESSION LUGS
8 - ELEVATOR INTERFACE RELAY
BYPASS
NON BYPASS
FIRE PUMP
TRANSITION
OPEN TRANSITION
CLOSED TRANSITION
DELAYED TRANSITION
TYPE
OPTIONS
1 - UNIT STATUS INDICATORS
2 - AUDIBLE ALARM
3 - TRANSIENT COUNTER
4 - REMOTE MONITOR PANEL
5 - SERVICE DISCONNECT SWITCH
6 - SUMMARY ALARM RELAY CONTACTS
7 - HIGH PERFORMANCE INTERCONNECT CABLE
SE - 125 kA - SERVICE ENTRANCE BP - 80 kA - BRANCH PANEL VOLTAGE
SPD ID
BYPASS ISOLATION
TRANSFER SWITCH
MOUNTING TYPE
8 - MASTERMIND MONITORING
(JB) JUNCTION BOX
(MTS) MANUAL TRANSFER SWITCH
(T) TRANSFORMER
(SS) SURGE SUPPRESSION
(UPS) UNINTERRUPTIBLE POWER SUPPLY
(WW) WIREWAY
(FS) FUSIBLE SWITCH
(F) FUSE
(MVF) MEDIUM VOLTAGE FUSE
(MVFS) MEDIUM VOLTAGE FUSIBLE SWITCH
(MVS) MEDIUM VOLTAGE SWITCH
(MVT) MEDIUM VOLTAGE CABLE TERMINATION
(PLC) POWER LINE CONDITIONER
(MVC) MEDIUM VOLTAGE FUSED CUTOUT
(EDP) ELEVATOR DISTRIBUTION PANEL
(EDS) ELEVATOR DISCONNECT SWITCH
MD - MODIFIED DIFFERENTIAL GROUND FAULT
(BW) BUS WAY
BUS
COPPER
ALUMINUM
TYPE
INDOOR
OUTDOOR
CYCLE CLOSING & WITHSTAND RATING
3 CYCLE
30 CYCLE
9 - OVERLAPPING NEUTRAL CONTACTS
10 - DIGITAL METERING
ALL ITEMS INDICATED BY A DARK SOLID LINE AS SHOWN BELOW ARE
ALL ITEMS INDICATED BY A LIGHT DASHED LINE AS SHOWN BELOW
ALL ITEMS INDICATED BY A DARK DASH-DOT-DASH LINE AS SHOWN
ALL ITEMS INDICATED BY A LIGHT DASH-DOT-DASH LINE AS SHOWN
ALL ITEMS INDICATED BY A LIGHT SOLID LINE AS SHOWN BELOW ARE
ALL DOWNTIME SHALL BE SCHEDULED WITH THE OWNER AND SHALL
THE PANELS AND SWITCHBOARDS INDICATED ON THE ONE LINE
FS - FUSED DISCONNECT SWITCHLABELING SCHEME FOR DESIGNATIONS
XX
XXX
XXX
XX
XXXXX
XXXAF
XXXAS
XXXAT
3P
FS XXX
XXXAS
XXXAF
3P K#
K#
X
X
EXX
XXX/XX
X
XX
X
XXX kVA
/ X / X
P: XXX
S: XXX
XXX XXX
X / X / X / X / X
XXX
XXX
XXX
XXX XXX
XXXXXX
XXX
XXX
XXX
X / X / X / X
XXX
XXXXXX
XXXXXX
DS XXX
XXXAS
XXXAF
3P
XXXXXX
XXXXXX
MIN AIC RATING =
XXX VOLTS 3Ø 4W
RMS SYM @ XXX VOLTS
XXXk AMPS
XXX AMPS @
XXX XXXBUS: TYPE:
XXX
CIRCUIT BREAKER INFORMATION
CIRCUIT BREAKER ACCESSORIES
CIRCUIT BREAKER TYPE
ONE-LINE SYMBOLS
CIRCUIT BREAKER OPTIONS
LOW VOLTAGE DISCONNECT SWITCH INFORMATION
DISCONNECT SWITCH ACCESSORIES
DISCONNECT SWITCH TYPE
PANEL LABELING SCHEME
GENERAL NOTES -
T
TRANSFORMER INFORMATION
ATS
TRANSFER SWITCH INFORMATION
SPD
SURGE PROTECTIVE DEVICE
BW/
BUS WAY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C U s e rs
\p e rm o \D o c u m e n ts
\7
.0
E
M
P e re z ri n g d u .c o m
.r v t
/2 /2
:2
:4
P
M
ES400
ONE LINE SYMBOLS CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00Revisions: Date:
RMS SYM @ 240 VOLTS
208/120 VOLTS 3Ø 4W
POWER PANEL CONSTRUCTION
INDIVIDUAL FIXED
65k AMPS
GROUP MOUNTED
RMS SYM @ 480 VOLTS
480/277 VOLTS 3Ø 4W
POWER PANEL CONSTRUCTION
____k AMPS
GROUP MOUNTED
RMS SYM @ 480 VOLTS
480 VOLTS 3Ø 3W
POWER PANEL CONSTRUCTION
GROUP MOUNTED
65k AMPS
GROUP MOUNTED
SS
P: 480V DELTA
S: 208Y/120V
DT 75 kVA
MC
1-1/4"C.
#3 &3
#8 GRD1
COPPER
MC
2"C.
#1/0 &4
#6 GRD1
COPPER
RMS SYM @ 480 VOLTS
480/277 VOLTS 3Ø 4W
POWER PANEL CONSTRUCTION
GROUP MOUNTED
65k AMPS
GROUP MOUNTED
MC
MC
RMS SYM @ 480 VOLTS
480/277 VOLTS 3Ø 4W
POWER PANEL CONSTRUCTION
INDIVIDUAL FIXED
65k AMPS
GROUP MOUNTED
P: 480V DELTA
S: 208Y/120V
EE 150°C
DT 45 kVA
FLOOR
DSDS
2"C.
SS
L2
MC
MC
MC
2-1/2"C.
#1/0 &4
#1/0 GRD1
COPPER
SS
L2
2-1/2"C.
#1 &4
#1 GRD1
COPPER
1"C.
#10 &4
#10 GRD1
COPPER
ST ST
2"C.
#3 &4
#3 GRD1
COPPER
1-1/2"C.
#6 &4
#6 GRD1
COPPER
1-1/2"C.
#6 &4
#6 GRD1
COPPER
1-1/2"C.
#4 &4
#4 GRD1
COPPER
MC
MC
MC
3"C.
#1/0 &4
#1/0 GRD1
COPPER
MC ST ST
3"C.
#1/0 &4
#1/0 GRD1
COPPER
1-1/2"C.
#6 &4
#6 GRD1
COPPER
1-1/2"C.
#6 &4
#6 GRD1
COPPER
1-1/2"C.
#4 &4
#4 GRD1
COPPER
P: 480V DELTA
S: 208Y/120V
EE 150°C
DT 45 kVA
2"C.
#2/0 &4
#6 GRD1
COPPER
DS
2-1/2"C.
#3/0 &4
#6 GRD1
COPPER
2-1/2"C.
#3/0 &4
#6 GRD1
COPPER
SS
L2
2-1/2"C.
#4/0 &3
#4 GRD1
COPPER
1"C.
#6 &3
#10 GRD1
COPPER
P: 480V DELTA
S: 208Y/120V
EE 150°C
DT 30 kVA
1-1/2"C.
#2 &4
#6 GRD1
COPPER
RMS SYM @ 480 VOLTS
480/277 VOLTS 3Ø 4W
POWER PANEL CONSTRUCTION
65k AMPS
GROUP MOUNTED
MC
2-1/2"C.
#4/0 &4
#4 GRD1
COPPER
SS
L2
P: 480V DELTA
S: 208Y/120V
DT 300 kVA
FLOOR
SS
DS DS
2-1/2"C.
#1 &4
#1 GRD1
COPPER
ECRT
B002
DS
PETMRI
DS
PDCU
SD
SDX
PDCU
SD
SDX
DS
PETMRI
8 8
10 10 10 10
1. POWER CONDITIONING DISTRIBUTION UNIT FURNISHED BY OTHERS
AND INSTALLED BY CONTRACTOR. GROUND TO BUILDING
STEEL.
2. FEEDER NOT TO EXCEED 20FT. PROVIDE A 6' PIGTAIL AT THE XVI
GENERATOR.
3. PROVIDE A 6' PIGTAIL AT THE END OF EXIT FB2.
4. PROVIDE ALL NECESSARY MOUNTING HARDWARE AND
ACCESSORIES TO RETROFIT NEW BREAKER INTO EXISTING PANEL.
5. 200A 3PH 480/277V ELECTRIC RECEPTACLE.
6. EPO CIRCUIT TO BE NORMALLY CLOSED, WIRED IN SERIES,
CONNECTED TO CT PDC UPS ONLY.
7. EXISTING CHILLERS TO BE RELOCATED. REFER TO NEW ROOF PLAN
FOR APPROXIMATE LOCATION.
8. EC TO VERIFY EXISTING CONDUCTOR TYPE AND SIZE AND EXTEND
TO NEW LOCATION.
9. PROVIDE 3 #10 ROM ACCELERATOR UNIT TO PDC FOR ION PUMP.
10. PROVIDE OVERSIZED LUGS FOR CONDUCTOR SIZE SHOWN AND A
MINIMUM AIC RATING OF 65K AMPS.
1200AMPS @
MAIN SECTION:
DISTRIBUTION SECTION:
MIN AIC RATING =
EATON POW-R-LINE PRL4B
200AF
200AT
3P
UL
B02-3
UL
BO2-4
400AMPS @
MAIN SECTION:
DISTRIBUTION SECTION:
MIN AIC RATING =
CUTLER-HAMMER PRL4
ELHCR
BO2-1
1200AMPS @
MAIN SECTION:
DISTRIBUTION SECTION:
MIN AIC RATING =
400AF
100AT
3P
EULQ
BO2-1
FED FROM SG-3EQ 100AF
90AT
3P
150AT
3P
UL
B00-1
1200AMPS @
MAIN SECTION:
DISTRIBUTION SECTION:
MIN AIC RATING =
WESTINGHOUSE CDP-3PH-4W
FED FROM SG-3N
50AT
3P
CHILLER
70AT
3P
70AT
3P
800AMPS @
MAIN SECTION:
DISTRIBUTION SECTION:
MIN AIC RATING =
CUTLER-HAMMER PRL4
200AT
3P
FED FROM SG-2CR
EULCR
B00-2
60AS
3P
200AS
3P
EULQ
BO2-3
1200AF
1200AS
1200AT
3P
200AF
40AT
3P
40AT
3P
125AT
3P
PDC
150AF150AF225AF
800AF
800AT
3PEDH-212-CR-2
FED FROM EDH-9
MP
SPD
FB2-1
GEN-1
70AT
3P
70AT
3P
40AT
3P
40AT
3P
150AF150AF
FB2-2
GEN-2
EUL-CR
B00-1
200AS
3P
400AF
225AT
3P
EUH-Q
B00-1
EUL-Q
B00-1
PETMRI
4 4 4 4 4
1200AMPS @
MAIN SECTION:
DISTRIBUTION SECTION:
MIN AIC RATING =
EATON POW-R-LINE PRL4B
FED FROM SWB-2
150AT
3P
UH
B00-1
1200AF
1200AS
1200AT
3P
200AF
600AT
3P
600AF
___AS
3P
HEX-ACCH-L1
35AT
3P
CHILLER
___AS
3P
HEX-ACCH-L2
9 9
150AT 150AT 150AT 150AT
DL-B01-1
EDH-CR-B02-1
EDH-304-Q-3
ET/7
DH-BO2-1
EDH-211-CR-7
ECRT-B00-2
KEYED NOTES -
ECRT-1-B0225
EQRT-1-B0225
DH-B01-1
T/2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C U s e rs
\p e rm o \D o c u m e n ts
\7
.0
E
M
P e re z ri n g d u .c o m
.r v t
/2 /2
:2
:1
P
M
ES401
ONE LINE DIAGRAM CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
NOT TO SCALEES401
1 ONE LINE DIAGRAM
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
2" 1/4"
-1
/2
OUTLET VOICE/DATA
3/4" CONDUIT
3/4" CONDUIT
V D
DD
RECEPTACLE
INFO
CIRCUIT
INFO
CIRCUIT
INFO
REQUIRED LABELS FOR ALL RECEPTACLES:
FIRST PART OF LABEL INDICATES RECEPTACLE
INFORMATION SUCH AS RECEPTACLE ID NO, TYPE,
VOLTS, AMPS, PHASE, PANEL BOARD, CIRCUIT NO,
PANEL BOARD ROOM NO.
SECOND PART OF CIRCUIT INDICATES CIRCUIT
INFORMATION SUCH AS IDENTITIY OF RECEPTACLES
ON THE SAME CIRCUIT, PANEL BOARD, AND CIRCUIT
I.D. PROVIDE SECOND LABEL AS REQUIRED.
ALL LABELS TO BE 1/16" PHENOLIC PLASTIC,
RECEPTACLES ON EMERGENCY POWER TO USE RED
PLASTIC WITH WHITE LETTERING. RECEPTACLES ON
NORMAL POWER TO USE BLACK PLASTIC WITH WHITE
LETTERING TO BE 3/16" HIGH. LOCATION OF LABELS
AS SHOWN OR AS DIRECTED BY COR. SCREW LABELS
TO WALL WITH #6 X3/4" LENGTH SCREW, SET IN PLASTIC
DRYWALL TYPE
ANCHORS.
TYPICAL
RECEPTACLE
LENGTH AS REQUIRED
DETAIL NOTES -
KEYED NOTES -
1.
2.
3.
1.
2.
3.
4.
5.
6.
METAL CHANNEL STRUT SUPPORT LONGER THAN 36"
SHALL BE INSTALLED WITH A CENTER SUPPORT ROD.
FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 0533, RACEWAYS AND
BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT
CONDITIONS.
FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER
TO SPECIFICATION SECTION 10 05 41, SEISMIC
RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
3/8" MIN GALVANIZED THREADED ROD, TYP.
LOCKING SQUARE WASHER & LOCKNUT
INTEGRAL GALVANIZED LIPPED STEEL MOUNTING
CHANNEL
WASHER & LOCKNUT
REFER TO PLANS FOR QUANTITY & SIZE OF CONDUITS
CONDUIT CLAMP. SIZE AS REQUIRED
KEYED NOTES -
3/8" MAX
[10mm]
1.
2.
3.
4.
5.
6.
7.
8.
9.
FLOOR SLAB, TYPICAL
FIRESTOP SEALANT PER SECTION 07 84 00,
FIRESTOPPING
CONDUIT, TYPICAL
MINERAL WOOL (FIRMLY PACKED)
INTEGRAL GALVANIZED LIPPED STEAL MOUNTING
CHANNEL, TYPICAL
STEEL EXPANSION ANCHOR, TYPICAL
CONDUIT COMPRESSION FITTING, TYPICAL
SPRING NUT, TYPICAL
JUNCTION BOX (SIZE AS REQUIRED)
DETAIL NOTES -
KEYED NOTES -
1.
2.
3.
4.
8 9
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
MAINTAIN A MINIMUM CLEARANCE OF 12" [308mm] ON ALL
SIDES OF ROOF PENETRATION FROM WALLS, CURBS,
AND OTHER PROJECTIONS TO FACILITATE PROPER
FLASHING.
FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT
OR OVERLAPPED.
VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
COORDINATE FLASHING INSTALLATION WITH ROOFING
CONTRACTOR TO ENSURE PROPER METHODS &
MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.
STAINLESS CLAMP, TYP.
PREFABRICATED RUBBER BOOT CAP WITH GRADUATED
STEPS & WEATHER-PROOF PRESSURE SEAL TO COLLAR
SEALANT AT PENETRATION TO MEMBRANE JUNCTURE BY
ROOFING CONTRACTOR
ROOF MEMBRANE
ROOF
WATER CUT-OFF MASTIC COMPATIBLE WITH ROOF
MEMBRANE
CONDUIT CLAMP. SIZE AS REQUIRED
SEAL-OFF FITTING, TYP.
CONDUIT, TYP.
BATT INSULATION
PREFABRICATED FORMED 0.06" THICK ALUMINUM
FLASHING ROUND COLLAR WITH MIN. 3" WIDE FLANGE.
ATTACH TO ROOF PER MANUFACTURER'S INSTRUCTIONS
MULTIPLE MEMBRANE STRIPPING PLIES FEATHERED AT
FIELD OF ROOF BY ROOFING CONTRACTOR. PRIME
FLANGE BEFORE STRIPPING.
STEEL EXPANSION ANCHOR
3/8" MIN GALVANIZED THREADED ROD, TYP.
LOCKING SQUARE WASHER & LOCKNUT
CONDUIT CLAMP. SIZE AS REQUIRED
INTEGRAL GALVANIZED LIPPED STEEL MOUNTING
CHANNEL
M A
X
[3 m m
M A
X
[4 m m
A
A
SECTION "A-A"
ELEVATION
KEYED NOTES -
1.
2.
3.
4.
5.
CAST METAL "WHILE-IN-USE" WP COVER(S) &
RECEPTACLE(S).
RIGID STEEL CONDUIT FOR SUPPORT PER N.E.C. ART.
RIGID STEEL CONDUIT FOR WIRING
ROOF PENETRATION AND CONDUIT SUPPORT PER
SD260533-04
CAST METAL, 2-GANG, NEMA 3R JUNCTION BOX WITH
THREADED HUBS.
(1)#6 3/4" C.
INDIVIDUAL PATIENT
CARE VICINITY "A"
INDIVIDUAL PATIENT
CARE VICINITY "B"
120V &/OR 277V
OTHER
BRANCH(ES)
120V &/OR 277V
CRITICAL CARE
BRANCH
120V &/OR 277V
NORMAL
POWER
BRANCH
120V &/OR 277V
CRITICAL CARE
BRANCH
120V &/OR
277V OTHER
BRANCH(ES)
DETAIL NOTES -
KEYED NOTES -
(1)#6 3/4" C.
(1)#6 3/4" C.
(1)#6 3/4" C.
2 2 2 2
1 1
IF THIS IS A REMODEL OF AN EXISTING SPACE, THE EC
SHALL VERIFY THAT THE EXISTING PANELBOARDS
SERVING ALL INDIVIDUAL PATIENT VICINITIES WITHIN
THE CONSTRUCTION LIMITS OF THIS PROJECT ARE
BONDED WITH A MINIMUM OF A #6 INSULATED COPPER
CONDUCTOR. IF THEY ARE NOT, THE EC SHALL
PROVIDE PANELBOARD BONDING AS DESCRIBED
HEREIN.
SEE NEC 517-3 FOR THE DEFINITION OF A PATIENT
VICINITY.
ALL PANELBOARDS SERVING LIGHTING FIXTURES THAT
FALL WITHIN THE FOOTPRINT OF THE PATIENT VICINITY
SHALL BE INCLUDED IN THE PANELBOARD BONDING
SYSTEM.
1.
2.
3.
CIRCUITS SERVING A COMMON INDIVIDUAL PATIENT
VICINITY.
PROVIDE BONDING CONDUCTOR BETWEEN THE
GROUND BUSSES OF ALL PANELS SERVING A COMMON
INDIVIDUAL PATIENT VICINITY AS REQUIRED BY NEC
517-14 AND AS DEFINED HEREIN. EACH CONDUCTOR
SHALL BE BONDED TO THE RACEWAY AT BOTH ENDS.
EXAMPLE OF PANELS BONDED TOGETHER FOR
INDIVIDUAL PATIENT VICINITY "A".
EXAMPLE OF PANELS BONDED TOGETHER FOR
INDIVIDUAL PATIENT VICINITY "B".
PANELBOARD GROUND BUS. TYPICAL.
1.
2.
3.
4.
5.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C U s e rs
\p e rm o \D o c u m e n ts
\7
.0
E
M
P e re z ri n g d u .c o m
.r v t
/2 /2
:2
:4
P
M
ES500
ELECTRICAL DETAILS CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
NOT TO SCALEES500
1 CONDUIT TRAPEZE MOUNTING DETAIL
NOT TO SCALEES500
2 FLOOR SLAB PENETRATION DETAIL
NOT TO SCALEES500
4 ROOF PENETRATION DETAIL
NOT TO SCALEES500
5 RECEPTACLE ROOF MOUNTING DETAIL
NOT TO SCALEES500
3 PANELBOARD BONDING DETAIL
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
NOT TO SCALEES500
6 RECEPTACLE DETAIL
D
D
D
D
D
SDX
SD
PDCUGEN
CLIENT INTERFACE TERMINAL BOX (CITB) SCHEMATIC
CITB
CUSTOMER VAULT DOOR
DOOR 1 SWITCH - D1A
15 24 VAC FROM MACHINE
24 VAC FROM MACHINE
CUSTOMER FASCIA DOOR
DOOR 2B SWITCH
CUSTOMER FASCIA DOOR
DOOR 2B SWITCH
24 VAC FROM MACHINE
24 VAC FROM MACHINE
24 VAC FROM MACHINE
24 VAC FROM MACHINE
MAXIMUM PERMISSIBLE
VOLTAGE DROP ACROSS
0.25 V AT 5 AMPS
ANY TWO TERMINALS
CUSTOMER FASCIA DOOR
DOOR 2A SWITCH
CUSTOMER FASCIA DOOR
DOOR 2A SWITCH
24 VAC FROM MACHINE
24 VAC FROM MACHINE
24 VAC FROM MACHINE
24 VAC FROM MACHINE
MOTION STOP SWITCHES, NUMBER AS
REQUIRED (SERIES CONNECTION)
24 VAC FROM MACHINE
24 VAC RETURN TO MACHINE
MAX PERMISSIBLE VOLT DROP
1V AT 5 AMPS
L
N
TO CITB POWER SUPPLY
VOLTAGE CURRENT
TO MACHINE
CHILLER
START
REMOTE
SUPPLY SYSTEM
CHILLED WATER
RELAY
(RELAY BY
CONTRACTOR)
28 28
FROM…