36E77619R0011-005.pdf

PDF 22 MB Posted

Attached to
Construct New Radiation Oncology Suite Milwaukee VAMC (Minor)
Solicitation number
36E77619R0011
Issued by

About this file

36E77619R0011 ATTACHMENT 5 - Radiation Oncology Drawings Final 81-95.pdf

View the file

Other files

File Type Posted
36E77619R0011-0007001.pdf PDF
36E77619R0011-0007000.docx DOCX document
36E77619R0011-0006003.pdf PDF
36E77619R0011-0006000.docx DOCX document
36E77619R0011-0006001.docx DOCX document
36E77619R0011-0006002.pdf PDF
36E77619R0011-0005005.pdf PDF
36E77619R0011-0005006.pdf PDF
36E77619R0011-0005003.pdf PDF
36E77619R0011-0005002.pdf PDF
36E77619R0011-0005004.pdf PDF
36E77619R0011-0005000.docx DOCX document
36E77619R0011-0005001.docx DOCX document
36E77619R0011-0004000.docx DOCX document
36E77619R0011-0004002.pdf PDF
36E77619R0011-0004003.pdf PDF
36E77619R0011-0004001.pdf PDF
36E77619R0011-0003000.docx DOCX document
36E77619R0011-0002005.pdf PDF
36E77619R0011-0002002.pdf PDF
36E77619R0011-0002007.pdf PDF
36E77619R0011-0002010.docx DOCX document
36E77619R0011-0002000.docx DOCX document
36E77619R0011-0002001.pdf PDF
36E77619R0011-0002009.pdf PDF
36E77619R0011-0002008.pdf PDF
36E77619R0011-0002003.docx DOCX document
36E77619R0011-0002006.pdf PDF
36E77619R0011-0002004.pdf PDF
36E77619R0011-0001000.docx DOCX document
36E77619R0011-0001001.pdf PDF
36E77619R0011-000.docx DOCX document
36E77619R0011-007.pdf PDF
36E77619R0011-012.pdf PDF
36E77619R0011-003.pdf PDF
36E77619R0011-008.pdf PDF
36E77619R0011-002.pdf PDF
36E77619R0011-001.pdf PDF
36E77619R0011-009.docx DOCX document
36E77619R0011-006.pdf PDF
36E77619R0011-010.docx DOCX document
36E77619R0011-011.pdf PDF
36E77619R0011-004.pdf PDF
36E77619R0011_1.docx DOCX document
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

S

L

D

T

C

P

DL

OS

S

MO

S

SO##

C

A

B

C

A

B

D

E

E

S

S

S

(ALL SYMBOLS SHOWN MAY NOT APPEAR ON DRAWINGS)

LIGHT FIXTURE CEILING MOUNTED

LIGHT TRACK

OUTDOOR POLE MOUNTED FIXTURE -

SEE LIGHTING POLE AND FIXTURE SCHEDULE

EMERGENCY BATTERY UNIT

CEILING MOUNTED EMERGENCY BATTERY UNIT

REMOTE HEAD

EXIT LIGHT - CEILING MOUNTED

EXIT LIGHT - WALL MOUNTED

SINGLE POLE SWITCH - TOGGLE TYPE

K a

SWITCH DESIGNATION

SWITCH TYPE

(2) DOUBLE POLE

(3) 3 WAY

(4) 4 WAY

(K) KEY OPERATED

(P) WITH PILOT LIGHT INDICATION

(T) TIMER SWITCH

(D) DIMMER

INDICATES DUAL LEVEL SWITCHING - SEE DUAL LEVEL SWITCHING DETAILDLS

SINGLE POLE TOGGLE SWITCH WITH DUPLEX RECEPTACLE COMBINATION

SURGICAL LIGHT CONTROL

MOMENTARY CONTACT SWITCH

LOW VOLTAGE SWITCH STATION -

SEE LOW VOLTAGE SWITCHING STATION SCHEDULE

X

"X" DENOTES SPECIFIC UNIT

DIMMING SYSTEM CONTROL STATION - SEE DIMMING SYSTEM SCHEDULE

TIME CLOCK - SEE TIME CLOCK SCHEDULE

CONTACTOR - SEE CONTACTOR SCHEDULE

PHOTO-CELL

DAYLIGHT SENSOR

OCCUPANCY SENSOR - SEE SPECIFICATIONS FOR TYPEX

"X" DENOTES SPECIFIC TYPE

SWITCH STATION - SEE SWITCH STATION SCHEDULEX

"X" DENOTES SPECIFIC UNIT

LCP

LIGHTING CONTROL PANEL

DISCONNECT SWITCH

MOTOR STARTER - SEE EQUIPMENT SCHEDULE

T

TRANSFORMER

JUNCTION BOX

A

PANELBOARD CABINET, SURFACE MOUNTED

INDICATES DESIGNATION

A 5 6

MULTI-OUTLET ASSEMBLY (SEE DETAIL)

NUMBER OF CONDUCTORS IN A RACEWAY

#8G

INDICATES CONDUCTOR SIZE (WHEN SHOWN)

FOR PHASE AND NEUTRAL CONDUCTORS

INDICATES NUMBER OF PHASE CONDUCTORS

INDICATES NEUTRAL CONDUCTOR

INDICATES GREEN GROUND CONDUCTOR

(NUMBER INDICATES CONDUCTOR SIZE)

PUSH BUTTON SWITCH

CT

12 3

CABLE TRAY

INDICATES DEPTH (IN INCHES)

INDICATES WIDTH (IN INCHES)

SEE DETAIL SYMBOL

INDICATES DETAIL DESIGNATION

INDICATES SHEET NUMBER

KEYED NOTE SYMBOL

FB

X

(FB) FLOOR BOX

(PT) POKE-THRU

(DA) DUCT ACTIVATION

(TP) TELEPOWER POLE

INDICATES TYPE (SEE SPECIFICATION)

INDICATES QUANTITY OF DEVICES ASSOCIATED WITH UNIT

GXX

DENOTES THE FOLLOWING:

(GM) GROUND MODULE

(PG) POWER GROUND MODULE

(RI) REMOTE INDICATOR

1a,X-3b X-3b,1a 1a,3b X-3*

INDICATES FIXTURE TYPE (TYPICAL)

SECOND DESIGNATOR (TYPICAL)

FIRST DESIGNATOR (TYPICAL)

SINGLE DESIGNATOR (TYPICAL)

1 FIRST DESIGNATOR INDICATES THE CIRCUIT AND CONTROL MEANS ASSOCIATED WITH THE

OUTBOARD LAMPS.

2 SECOND DESIGNATOR INDICATES THE CIRCUIT AND CONTROL MEANS ASSOCIATED WITH THE

INBOARD LAMPS.

3 SINGLE DESIGNATOR INDICATES THE CIRCUIT AND MEANS OF CONTROL FOR THE ENTIRE

FIXTURE.

X-3b LOWER CASE LETTERS INDICATE SWITCH DESIGNATION CONTROLLING ASSOCIATED LAMP(S).

ABSENCE OF ANY LETTER INDICATES FIXTURE/LAMP(S) CONTROLLED VIA SWITCH(ES) IN THE

ASSOCIATED ROOM. UPPERCASE "U" INDICATES ASSOCIATED LAMP(S) ARE UNSWITCHED.

INDICATES THE CIRCUIT NUMBER SERVING FIXTURE/LAMP(S).

INDICATES BRANCH PANELBOARD SERVING THE DEVICE. SEE PLAN FOR AREAS SERVED BY

PANELBOARD(S).

X-3

DESIGNATOR

XX

X-3

SPECIAL OUTLET

DESIGNATOR

X-3

INDICATES THE CIRCUIT NUMBER SERVING DEVICE.

INDICATES BRANCH PANELBOARD SERVING THE DEVICE. SEE PLAN FOR

AREAS SERVED BY PANELBOARD(S).

GENERAL NOTES - NOTES THAT APPLY TO ALL DRAWINGS WITHIN THE DRAWING SET.

SHEET NOTES - NOTES THAT APPLY TO THE SHEET ON WHICH THEY APPEAR.

KEYED NOTES - NOTES THAT APPLY TO AN AREA, ITEM AND/OR DEVICE ON A FLOOR

PLAN OR DETAIL.

DETAIL NOTES - NOTES THAT APPLY TO A SPECIFIC DETAIL.

THE LIGHTING DESIGN FOR THIS PROJECT SET IS IN

COMPLIANCE WITH COMM 63.051. COMPLIANCE IS

DEMONSTRATED BY USING ASHRAE 90.1-2013

(ALL ABBREVIATIONS SHOWN MAY NOT APPEAR ON DRAWINGS)

ABV ABOVE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINAL GRADE

ALT ALTERNATE

ALT SW ALTERNATE SWITCH

ARCH ARCHITECT

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BLDG BUILDING

BOL BUILT IN OVERLOAD

BPC BOLTED PRESSURE CONTACT SWITCH

BRKR BREAKER

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

CP CONTROL PANEL

CS COMBINATION STARTER

DE DUAL ELEMENT FUSES

DIR DIRECT

DISC DISCONNECT

DN DOWN

EC ELECTRICAL CONTRACTOR

ELEV ELEVATION

EMER EMERGENCY

EMT ELECTRIC METALLIC TUBING

EOL END OF LINE RESISTOR

EP EXPLOSION PROOF

ER EXISTING REMOVE FROM SERVICE

ERL EXISTING RELOCATED

ES EXPOSED STRUCTURE

ETR EXISTING TO REMAIN

EX EXISTING

EWC ELECTRIC WATER COOLER

F FLUSH

FBO FURNISHED BY OTHERS

FDR FEEDER

FIXT FIXTURE

FLUOR FLUORESCENT

FLR FLOOR

FS FLOW SWITCH

FVNR FULL VOLTAGE NON-REVERSING

GC GENERAL CONTRACTOR

GFI GROUND FAULT INTERRUPTED

GRC GALVANIZED RIGID CONDUIT

GRD GROUND

GRDG GROUNDING

GYP GYPSUM BOARD

HOA HAND-OFF-AUTO SWITCH

HVAC HEATING, VENTILATING, & AIR CONDITIONING

HW HEAVYWALL

IL INTERLOCK

IMC INTERMEDIATE METALLIC CONDUIT

JB JUNCTION BOX

kVA KILO VOLTAMPERE

LG LAY-IN GRID

LTG LIGHTING

LV LOW VOLTAGE

LVT LINE VOLTAGE THERMOSTAT

MAG MAGNETIC STARTER

MAN MANUAL STARTER

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MLO MAIN LUGS ONLY

MSB MAIN SWITCHBOARD

MTD MOUNTED

NIC NOT IN CONTRACT

NU NEAR UNIT

OU ON UNIT

P POLE

PB PUSH BUTTON

PEND PENDANT

PC PLUMBING CONTRACTOR

PE SW PNEUMATIC SWITCH

PLBG PLUMBING

PNL PANEL

PVC POLYVINYL CHLORIDE

R RELAY

RAI REMAIN AS IS

RE/CKT RECONNECT TO EXISTING CIRCUIT

RECEPT RECEPTACLE

RM ROOM

RVS REDUCED VOLTAGE STARTING

S SPLINE

SEL SW SELECTOR SWITCH

SP SW SPEED SWITCH

SURF SURFACE

SW SWITCH

TC TIME CLOCK

TCC TEMPERATURE CONTROL CONTRACTOR

TCP TEMPERATURE CONTROL PANEL

TYP TYPICAL

UG UNDERGROUND

UNIV UNIVERSAL

USS UNIT SUBSTATION

WP WEATHERPROOF

XFMR TRANSFORMER

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

LIGHT FIXTURE, RECESSED FLUORESCENT,

2'x4' LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED FLUORESCENT,

2'x4' LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED FLUORESCENT,

1'x4' LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED FLUORESCENT,

1'x4' LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED FLUORESCENT,

1'x8' LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED FLUORESCENT,

1'x8' LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED FLUORESCENT,

2'x2' LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED FLUORESCENT,

2'x2' LETTER INDICATES TYPE.

LIGHT FIXTURE, FLUORESCENT EMERGENCY;

LETTER INDICATES TYPE.

LIGHT FIXTURE, STRIP/INDUSTRIAL FLUORESCENT; LETTER

INDICATES TYPE.

LIGHT FIXTURE, WALL MOUNTED

RECEPTACLE, DUPLEX

(IG) ISOLATED GROUND

(TD) TRIPLE DUPLEX

(TR) TAMPER RESISTANCE

(WP) WEATHERPROOF W/ GFI RECEPTACLE

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, SINGLE

RECEPTACLE, QUADRAPLEX

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE, SINGLE WITH SWITCH

RECEPTACLE, DUPLEX WITH SWITCH

DUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER BACKSPLASH

DUPLEX RECEPTACLE - MOUNTED AT SPECIAL MOUNTING HEIGHT

INDICATED ON DRAWING OR AS INDICATED IN THE ASSOCIATED

ARCHITECTURAL ELEVATION.

46"

INDICATES MOUNTING HEIGHT WHEN SHOWN.

RECEPTACLE, SPECIAL PURPOSE OR EQUIPMENT CONNECTION -

SEE EQUIPMENT SCHEDULE

ELECTRIC SWITCH - SEE EQUIPMENT SCHEDULE

A

INDICATES DESIGNATION

PANELBOARD CABINET, FLUSH MOUNTED

LIGHT FIXTURE, UNDER CABINET MOUNTED FLUORESCENT,

SIZE DEPENDANT ON TYPE, LETTER INDICATES TYPE.

LIGHT FIXTURE CEILING RECESSED

DIGITAL DISTRIBUTED IN-ROOM DIMMER SWITCH

REFER TO SEQUENCE OF OPERATIONS IN SPECIFICATIONS 26 09 29

DIGITAL DISTRIBUTED IN-ROOM SWITCH

SYMBOLS: ELECTRICAL CIRCUITING:

LIGHTING FIXTURES:

LIGHTING CIRCUITING NOTES -

DESIGNATOR DESCRIPTION:

ELECTRICAL DEVICES:

DESIGNATOR DESCRIPTION:

NOTE DESCRIPTIONS -

ABBREVIATIONS:

X

X

J

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

FULLY-SPRINKLERED

PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR

TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE

OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION

SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.

C U s e rs

\p e rm o \D o c u m e n ts

\7

.0

E

M

P e re z ri n g d u .c o m

.r v t

/2 /2

:5

:3

P

M

ES000

ELECTRICAL SYMBOLS,

ABBREVIATIONS & SHEET INDEX

CONSTRUCT NEW RADIATION

ONCOLOGY SUITE

MILWAUKEE VAMC

695-404

04 OCTOBER 2018 MGM MTP

FINAL CONSTRUCTION

DOCUMENTS BLDG 111

ELECTRICAL SHEET INDEX

No. TITLE

ES000 ELECTRICAL SYMBOLS, ABBREVIATIONS & SHEET INDEX

ES101D BASEMENT FLOOR PLAN - DEMOLITION

ES101P PARTIAL BASEMENT FLOOR PLAN - POWER

ES102P PARTIALBASEMENT FLOOR PLAN - POWER

ES121P ROOF PLAN - POWER

ES201L PARTIAL BASEMENT FLOOR PLAN - LIGHTING

ES202L PARTIAL BASEMENT FLOOR PLAN - LIGHTING

ES300 ENLARGED PLANS

ES301 ENLARGED PLANS

ES302 ENLARGED PLANS

ES303 ENLARGED PLANS

ES400 ONE LINE SYMBOLS

ES401 ONE LINE DIAGRAM

ES500 ELECTRICAL DETAILS

ES501 ELECTRICAL DETAILS

ES502 LIGHTING DETAILS

ES600 ELECTRICAL SCHEDULES

ES601 ELECTRICAL SCHEDULES

ES602 ELECTRICAL SCHEDULES

17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com

R&D Project No.:

THIS BAR IS 1" LONG.

IF IT MEASURES ANYTHING OTHER THAN 1"

ADJUST SCALE ACCORDINGLY.

217164.00Revisions: Date:

OS

J

J

J J J J J

J J

J

J

J J

J

J

J

J

J

J

J

C DB

EM

CR

GFI

EM

E M

GFI

GFI

GFI

GFI

E M

E M

E M

E M

EM

GFI

E M

B02-3

EUL-Q

EM

EM

EMTV

MO A

MO A

MO A

AUTO DOOR

CEILING

ELEC BASEBOARD

EM

ELEC BASEBOARD

EUL-CR-B02-1

6,8

ELEC BASEBOARD

ELEC BASEBOARD

EUL-CR-B02-1

2,4

B00-2

EUL-CREM

OVERHEAD AUTO DOOR ELEC BASEBOARD

B00-2

ECRT

ECRTB002

DS

EM

EM

PETMRI

DS

ELEC BASEBOARD

X28

X27

X26

X25

X24

X23

X22

X21

X20

X19

XBXCXDXEXFXG E

FG

A

CHILLER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

FULLY-SPRINKLERED

PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR

TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE

OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION

SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.

C U s e rs

\p e rm o \D o c u m e n ts

\7

.0

E

M

P e re z ri n g d u .c o m

.r v t

/2 /2

:2

:4

P

M

ES101D

BASEMENT FLOOR PLAN -

DEMOLITION

CONSTRUCT NEW RADIATION

ONCOLOGY SUITE

MILWAUKEE VAMC

695-404

04 OCTOBER 2018 MGM MTP

FINAL CONSTRUCTION

DOCUMENTS BLDG 111

1/8" = 1'-0"ES101D

1 PARTIAL FIRST FLOOR PLAN - DEMOLITION

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

EC TO REMOVE TEMPORARY LIGHTING IN

UNASSIGNED SPACE.

PET MRI CEILING HVAC UNITS FED FROM ACC

PET/MRI.

EXHAUST AND SUPPLY FAN DISCONNECTS

ARE FED FROM PANEL EUL-Q-BO2-3.

POWER CONDUITS SHOWN FEED PARKING

STRUCTURE. CONDUITS ARE EXISTING TO

REMAIN UNLESS OTHERWISE NOTED.

ROOM LOCKED DURING TIME OF SURVEY. NO

EXISTING INFORMATION AVAILABLE.

DEVICES IN ROOM ARE BASED ON TYPICAL

ADJACENT ROOMS.

(5) MULTI OUTLET ASSEMBLIES STACKED

VERTICALLY.

ELECTRIC BUSWAY FED FROM GENERATOR

ROOM IS EXISTING TO REMAIN.

LINAC CHILLER FED FROM PANEL DH-B02-1.

CHILLER TO BE RELOCATED. REFER TO ONE

LINE DIAGRAM FOR ADDITIONAL

INFORMATION.

ACC PET/MRI TRAILER FED FROM EUL-CR-

B00-2 CKT 2,4.

EXISTING PANEL TO BE DEMOLISHED. EC TO

CAPTURE REMAINING CIRCUITS AFTER

DEMOLITION AND EXTEND TO NEW PANEL

EUL-Q-B00-1.

AREA WITHIN BOUNDARY IS PART OF PHASE

4. REFER TO ARCHITECTURAL PHASING

PLANS FOR ADDITIONAL INFORMATION.

NOT TO SCALE

DEMOLITION KEY PLAN

N

N

1.

2.

3.

SHEET NOTES -

KEYED NOTES -

ALL EQUIPMENT SHOWN ON DEMOLITION

PLAN IS "EXISTING TO BE REMOVED"

UNLESS NOTED OTHERWISE.

DASHED WALLS INDICATE EXISTING

WALLS BEING REMOVED. REFER TO

ARCHITECTURAL DEMOLITION AND

PHASING PLANS FOR THE EXACT EXTENT

OF GENERAL CONSTRUCTION DEMOLITION

REQUIRED.

REFER TO DEMOLITION DRAWINGS OF

OTHER TRADES FOR ADDITIONAL

DEMOLITION BEING DONE.

17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com

R&D Project No.:

THIS BAR IS 1" LONG.

IF IT MEASURES ANYTHING OTHER THAN 1"

C DB

EXAM

B0205

EXAM

B0206

EXAM

B0209 TOILET

B0212

NURSE PRACTITIONER

B0213

LEAD PHYSICIAN

B0214

TOILET

B0217

CLEAN

B0215

ADMIN

B0216

CANCER CARE

B0228

RESEARCH

B0229

EXAM

B0211

NURSE

WORKSTATIONS

B0208

RESIDENT

WORKSTATIONS

B0227

RECEPTION

B0201

WAITING

B0200

PHYSICIST

WORKROOM

B0222

LEAD PHYSICIST

B0223

CONTROL ROOM

B0014

CONTROL ROOM

B0011

CONSULT / EXAM

B0204

VITALS

B0203

ADMIN

B0224

EXAM

B0210

PHYSICIAN

WORKSTATIONS

B0226

PROCEDURE HOLDING

BAY

B0207

CORRIDOR

C0A14

CORRIDOR

C0A13

CORRIDOR

C0A12

CORRIDOR

C0A10

MECH / ELEC

B0225

CORRIDOR

C0A17

HAC

B0218

LOCKERS

B0219

CONFERENCE ROOM

B0220

STAFF LOUNGE

B0221

ES300

B02-1

DH

CT SCANNER

B0004

CORRIDOR

C0A15

PHYSICS STORAGE

B0233

ES300

ES300

ES300

CR-7

EDH-211

EX

EX

DOSIMETRY

B0001

CONTROL ROOM

B0002

CT ENTRY ROOM

B0003

DRESSING / TOILET

B0007

DRESSING / TOILET

B0008

WAITING ROOM

B0009

DRESSING ROOM

B0010

CT EQUIPMENT

B0005

ES302

ES301

ES303

TR

NL-20

GFI

NL-20

GFI

NL-20

NL-10

NL-10

CL-2

CL-4

NL-14

CL-4 NL-14

48"

GFI

NL-6

NL-10NL-10

NL-11 NL-11

GFI

NL-6

TR

NL-3

48"

GFI

NL-35

48"

NL-10

60"

NL-51

NL-1

NL-1

RF

GFB

CL-13 NL-35

NL-33

NL-33 NL-33

NL-33

NL-11

NL-11

NL-11

NL-31

NL-31

CL-17

CL-17

NL-41

NL-41

GFI

NL-11

GFI

NL-11

CL-17

NL-31

NL-31

NL-17

NL-17

NL-17

NL-41

NL-41

NL-41

GFI

NL-39

NL-29

NL-29

NL-29

NL-27

NL-27

NL-25

NL-23NL-23NL-23

CL-11

NL-25

NL-21CL-11

CL-11

NL-21

CL-5

NL-13

NL-11

GFI

NL-19

48"

CL-5

TR

NL-3

TR

NL-3

TR

NL-3

TR

NL-3

TR

NL-3

TR

NL-3

CL-3

CL-3

CL-3

NL-7

NL-7

NL-9

NL-7

NL-43

NL-43

CL-11

NL-19 GFI

CL-9

GFI

NL-19

NL-15

NL-13

NL-15

NL-17

GFI

NL-13

NL-13

NL-13

GFI

NL-13

NL-27

NL-13

GFI

NL-15

GFI

NL-15

GFI

NL-17CL-9

NL-17

NL-19

CL-9

NL-15

GFI

CL-9

NL-15

48"

NL-35

NL-35

NL-35

FB

H1

NL-1

NL-25

CL-5

NL-19

NL-9

NL-9

ES101P

ES102P

ES101P

ES102P

UL-B02-1-41

UL-B02-1-41

CL-9

CL-5

NL-4

NL-43

NL-45

NL-4

NL-20

LINAC 1

B0013

LINAC 2

B0012

NL-6

SCHEDULERS

B0202

TV

NL-5

GFI

NL-21

EXEX

NL-3

CL-17

CL-17

NL-8

CL-17

NL-8

X28

X27

X26

X25

X24

X23

X22

X21

X20

X19

XBXCXDXEXFXG E

FG

A

CL-4

NL-12

NL-28

NL-52

CL-2

NL-12

AO

EPL-LS-11-2-7

CORRIDOR

C0A15

HRCU-B0004

NL-19

NL-1

GFI

NL-37

NL-21

NL-25

NL-6

48"

NL-6

NL-20

Q-3

EDH-304

EX

HHWP-B0225A

HHWP-B0225B

ES300

AO

CL-7

PS

CL-1

NL-8

GFI

CL-15

NL-33

NL-1

48"

NL-10

BLOCK MOLD FILM

PROCESS STORAGE

B0230

LOGISTICS - CLEAN

B0234

SOILED

B0232

LOGISTICS - DIRTY

B0235

B00-1

UL

4 45

MG

CT STORAGE

B0006

CLEAN LINENS

B0231

NL-4

NL-4

NL-43

NL-45

NL-45

CM

NL-49

WC

NL-47

NL-1

CL-17

NL-54

48"

CL-**

CORRIDOR

C0A14

NL-52 NL-28

NL-28

NL-526

AO

CL-27

AO

CL-27

AO

EPL-LS-11-2-7

SC

7 7

HCUH-C0A17

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

FULLY-SPRINKLERED

PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR

TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE

OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION

SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.

C U s e rs

\p e rm o \D o c u m e n ts

\7

.0

E

M

P e re z ri n g d u .c o m

.r v t

/2 /2

:2

:0

P

M

ES101P

PARTIAL BASEMENT FLOOR PLAN

- POWER

CONSTRUCT NEW RADIATION

ONCOLOGY SUITE

MILWAUKEE VAMC

695-404

04 OCTOBER 2018 MGM MTP

FINAL CONSTRUCTION

DOCUMENTS BLDG 111

1/8" = 1'-0"ES101P

1 PARTIAL BASEMENT FLOOR PLAN - POWER SOUTH

N

1" = 100'-0"

KEY PLAN SOUTH

N

KEYED NOTES -

1.

2.

3.

4.

5.

6.

7.

8.

EXISTING GENERATOR BUSWAY IS

EXISTING TO REMAIN. PROTECT IN PLACE

DURING CONSTRUCTION.

APPROXIMATE ROUTING OF NEW FEEDERS

TO LINACS.

EXISTING JUNCTION BOX FEEDS PARKING

STRUCTURE. BOX SIZE IS APPROXIMATE

AND SHALL BE PROTECTED IN PLACE

DURING CONSTRUCTION.

PROVIDE (2) 4" CONDUIT STUBS FOR

FUTURE EQUIPMENT MODIFICATIONS.

COORDINATE EXACT LOCATION WITH

PHYSICIST OF RECORD PRIOR TO

COMMENCING WORK.

APPROXIMATE ROUTING OF NEW FEEDER

TO CT.

MOUNT RECEPTACLE 6" ABOVE COUNTER.

EC TO REUSE SPARE CIRCUIT BREAKERS

WITHIN PANEL EPL-LS-11-2.

APPROXIMATE LOCATION OF PANEL EPL-

LS-11-2. ROOM (1167) IS LOCATED ON FIRST

FLOOR.

1.

2.

3.

4.

5.

SHEET NOTES -

EC SHALL REFER TO ARCHITECTURAL

FLOOR PLANS, REFLECTED CEILING PLANS

AND ELEVATIONS FOR EXACT LOCATIONS

AND MOUNTING HEIGHTS.

REFER TO ARCHITECTURAL PHASING

PLANS FOR EXACT EXTENT OF

CONSTRUCTION.

NORMAL BRANCH POWER CIRCUIT 'NL' IS

208/120V AND SHALL BE FED FROM PANEL

UL-B00-1, UNLESS OTHERWISE NOTED.

CRITICAL BRANCH POWER CIRCUIT 'CL' IS

208/120V AND SHALL BE FED FROM PANEL

EUL-CR-B00-1, UNLESS OTHERWISE NOTED.

CIRCUIT NUMBERS INDICATED DO NOT

REFLECT THE ACTUAL POSITION OF THE

CIRCUIT BREAKER IN THE PANEL. RATHER,

THE NUMBER INDICATES WHICH DEVICES

ARE CONNECTED TO A COMMON CIRCUIT.

EC SHALL UTILIZE SPARES, SPACES AND

CIRCUITS RELIEVED FROM DUTY TO

PROVIDE THE INDICATED NUMBER OF

CIRCUITS.

17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com

R&D Project No.:

THIS BAR IS 1" LONG.

IF IT MEASURES ANYTHING OTHER THAN 1"

ADJUST SCALE ACCORDINGLY.

217164.00

Revisions: Date:

e28

C DB

PET-MRI VESTIBULE

B0015

CORRIDOR

C0A17

CL-26

NL-48

NL-48

NL-48

ES101P

ES102P

ES101P

ES102P

HAC-B0015

WP

NL-48

CORRIDOR

C0A17

48"

WP

CL-24

PETMRI

DS

PETMRI

MLD

CL-22

MLD

CL-24

MLD

CL-22

E31

X30

X28

E

FG

A

HAC-C0A17

AS

CL-28

OD

CL-30

PL

CL-26

48"

UL-B02-1-41

UL-B02-1-41

PAC

CL-26

MECHANICAL ROOM

B0016

AO

EPL-LS-11-2-9

AO

EPL-LS-11-2-9

48"

UL-B02-1-41

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

FULLY-SPRINKLERED

PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR

TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE

OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION

SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.

C U s e rs

\p e rm o \D o c u m e n ts

\7

.0

E

M

P e re z ri n g d u .c o m

.r v t

/2 /2

:2

:1

P

M

ES102P

PARTIALBASEMENT FLOOR PLAN -

POWER

CONSTRUCT NEW RADIATION

ONCOLOGY SUITE

MILWAUKEE VAMC

695-404

04 OCTOBER 2018 MGM MTP

FINAL CONSTRUCTION

DOCUMENTS BLDG 111

1/4" = 1'-0"ES102P

1 PARTIAL BASEMENT FLOOR PLAN - POWER NORTH

1" = 100'-0"

KEY PLAN NORTH

N

N

1.

2.

3.

4.

5.

SHEET NOTES -

KEYED NOTES -

EC SHALL REFER TO ARCHITECTURAL

FLOOR PLANS, PHASING PLANS,

REFLECTED CEILING PLANS AND

ELEVATIONS FOR EXACT LOCATIONS AND

MOUNTING HEIGHTS.

REFER TO ARCHITECTURAL PHASING

PLANS FOR EXACT EXTENT OF

CONSTRUCTION.

NORMAL BRANCH POWER CIRCUIT 'NL' IS

208/120V AND SHALL BE FED FORM PANEL

UL-B00-1, UNLESS OTHERWISE NOTED.

CRITICAL BRANCH POWER CIRCUIT 'CL' IS

208/120V AND SHALL BE FED FROM PANEL

EUL-CR-B00-1, UNLESS OTHERWISE NOTED.

CIRCUIT NUMBERS INDICATED DO NOT

REFLECT THE ACTUAL POSITION OF THE

CIRCUIT BREAKER IN THE PANEL. RATHER,

THE NUMBER INDICATES WHICH DEVICES

ARE CONNECTED TO A COMMON CIRCUIT.

EC SHALL UTILIZE SPARES, SPACES AND

CIRCUITS RELIEVED FROM DUTY TO

PROVIDE THE INDICATED NUMBER OF

CIRCUITS.

1.

2.

EC TO REUSE SPARE CIRCUIT BREAKERS

WITHIN PANEL EPL-LS-11-2.

EC TO REUSE SPARE CIRCUIT BREAKERS

WITHIN PANEL UL-B02-1.

17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com

R&D Project No.:

THIS BAR IS 1" LONG.

IF IT MEASURES ANYTHING OTHER THAN 1"

File details come from the government source that posted it.