Milwaukee VAMC 11-21-2018
695-404 Construct New Radiation Oncology Suite Addendum 1
Milwaukee, WI 53295 12-01-2016
08 71 00-1
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
A. Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
A. Caulking: Section 07 92 00 JOINT SEALANTS.
B. Application of Hardware: Section 08 14 00, WOOD DOORS, Section 08 11
13, HOLLOW METAL DOORS AND FRAMES, Section 08 41 13, ALUMINUM-FRAMED
ENTRANCES AND STOREFRONTS, Section 08 71 13, AUTOMATIC DOOR OPERATORS, Section 08 71 13.11, LOW ENERGY DOOR OPERATORS, Section 13 49 00, RADIATION PROTECTION
C. Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.
D. Painting: Section 09 91 00, PAINTING.
E. Card Readers: Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS.
F. Electrical: Division 26, ELECTRICAL.
G. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.
1.3 GENERAL
A. All hardware shall comply with UFAS, (Uniform Federal Accessible
Standards) unless specified otherwise.
B. Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.
D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
E. The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
Milwaukee, WI 53295 12-01-2016
08 71 00-2
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
4. Exit devices.
5. Floor closers.
1.4 WARRANTY
A. Automatic door operators shall be subject to the terms of FAR Clause
52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
1.5 MAINTENANCE MANUALS
A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section
01 33 23. Submit 2 final copies of the final approved schedules to VAMC
Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
B. Hardware Schedule: Prepare and submit hardware schedule in the following form:
Hardware
Item
Quantity Size Reference
Publication
Type No.
Finish Mfr.
Name and
Catalog
No.
Key
Control
Symbols
UL Mark
(if fire rated and listed)
ANSI/BHMA
Finish
Designation
C. Samples and Manufacturers' Literature:
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers
Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
Milwaukee, WI 53295 12-01-2016
08 71 00-3
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
D. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
1.7 DELIVERY AND MARKING
A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to
Resident Engineer for reference purposes. Tag shall identify items by
Project Specification number and manufacturer's catalog number. These items shall remain on file in Resident Engineer's office until all other similar items have been installed in project, at which time the
Resident Engineer will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and
Hardware Manufacturer’s Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
Milwaukee, WI 53295 12-01-2016
08 71 00-4
1.9 INSTRUCTIONS
A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols.
Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.
1.10 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
B. American Society for Testing and Materials (ASTM):
F883-04.................Padlocks
E2180-07................Standard Test Method for Determining the
Activity of Incorporated Antimicrobial Agent(s)
In Polymeric or Hydrophobic Materials
C. American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA):
A156.1-06...............Butts and Hinges
A156.2-03...............Bored and Pre-assembled Locks and Latches
A156.3-08...............Exit Devices, Coordinators, and Auto Flush
Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.11-14..............Cabinet Locks
A156.12-05 .............Interconnected Locks and Latches
A156.13-05..............Mortise Locks and Latches Series 1000
A156.14-07 .............Sliding and Folding Door Hardware
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.17-04 .............Self-Closing Hinges and Pivots
A156.18-06..............Materials and Finishes
Milwaukee, WI 53295 12-01-2016
08 71 00-5
A156.20-06 .............Strap and Tee Hinges, and Hasps
A156.21-09..............Thresholds
A156.22-05..............Door Gasketing and Edge Seal Systems
A156.23-04..............Electromagnetic Locks
A156.24-03..............Delayed Egress Locking Systems
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
A156.29-07 .............Exit Locks and Alarms
A156.30-03 .............High Security Cylinders
A156.31-07 .............Electric Strikes and Frame Mounted Actuators
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
D. National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
E. Underwriters Laboratories, Inc. (UL):
Building Materials Directory (2008)
PART 2 - PRODUCTS
2.1 BUTT HINGES
A. ANSI A156.1. Provide only Hager BB1168 five-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some type of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:
1. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.
Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc.) shall be of stainless steel material.
B. Provide quantity and size of hinges per door leaf as follows:
1. Doors up to 1210 mm (4 feet) high: 2 hinges.
2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.
3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.
Milwaukee, WI 53295 12-01-2016
08 71 00-6
4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm
(4-1/2 inches x 4-1/2 inches) hinges.
5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
7. Provide heavy-weight hinges where specified.
8. At doors weighing 330 kg (150 lbs.) or more, furnish 127 mm (5 inch) high hinges.
C. See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.
2.2 CONTINUOUS HINGES
A. ANSI/BHMA A156.26, Grade 1-600.
1. Listed under Category N in BHMA's "Certified Product Directory."
2. Provide only Hager continuous hinge.
B. General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete
C. Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a
Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.
1. Base Metal for Interior Hinges: Stainless steel.
2. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.
3. Provide with non-removable pin (hospital tip option) at lockable outswing doors.
4. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.
5. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.
6. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.
7. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s
Milwaukee, WI 53295 12-01-2016
08 71 00-7 adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.
2.3 DOOR CLOSING DEVICES
A. Closing devices shall be LCN 4040 or 4040H Series.
2.4 OVERHEAD CLOSERS
A. Conform to ANSI A156.4, Grade 1.
B. Closers shall conform to the following:
1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.
4. Material of closer body shall be forged or cast.
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.
7. Closers shall have full size metal cover; plastic covers will not be accepted.
8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11. Provide parallel arm closers with heavy duty rigid arm.
Milwaukee, WI 53295 12-01-2016
08 71 00-8
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 ½” (38mm) minimum piston diameter.
2.5 DOOR STOPS
A. Conform to ANSI A156.16.
B. Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use lead expansion shields for mounting door stops.
C. Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
D. Provide floor stops Type L02141 or L02161 in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.
E. Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
F. Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.
G. Omit stops where floor mounted door holders are required and where automatic operated doors occur.
H. Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.
I. Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.
J. Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.
Milwaukee, WI 53295 12-01-2016
08 71 00-9
K. Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.
L. Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
2.6 OVERHEAD DOOR STOPS AND HOLDERS
A. Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
2.7 FLOOR DOOR HOLDERS
A. Conform to ANSI Standard A156.16. Provide extension strikes for Types
L01301 and L01311 holders where necessary.
2.8 LOCKS AND LATCHES
A. Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall be
Sargent Cylindrical and Mortise Lock Set with Medeco 7-pin interchangeable cylindrical cores (Model 22N700006). Cylinders for all locksets shall be removable core type. Cylinders shall be furnished with construction removable cores and construction master keys.
Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand Master Key System.
Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.
B. In addition to above requirements, locks and latches shall comply with following requirements:
1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be Best 45H Series, minimum Grade 2. All locksets and latchsets shall have lever handles fabricated from cast stainless
Milwaukee, WI 53295 12-01-2016
08 71 00-10 steel. Provide sectional (lever x rose) lever design matching
[__________]. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks.
Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.
2. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latchsets shall be furnished with
122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design. Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)
3. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.
4. Privacy locks in non-mental-health patient rooms shall have an inside thumbturn for privacy and an outside thumbturn for emergency entrance. Single occupancy patient privacy doors shall typically swing out; where such doors cannot swing out, provide center-pivoted doors with rescue hardware (see HW-2B).
2.9 PUSH-BUTTON COMBINATION LOCKS
A. ANSI/BHMA A156.5, Grade 1. Battery operated pushbutton entry.
B. Construction: Heavy duty mortise lock housing conforming to ANSI/BHMA
A156.13, Grade 1. Lever handles and operating components in compliance
Milwaukee, WI 53295 12-01-2016
08 71 00-11 with the UFAS and the ADA Accessibility Guidelines. Match lever handles of locks and latchsets on adjacent doors.
C. Special Features: Key override to permit a master keyed security system and a pushbutton security code activated passage feature to allow access without using the entry code.
2.10 ELECTROMAGNETIC LOCKS
A. ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product
Directory."
1. Type: Full exterior or full interior, as required by application indicated.
2. Strength Ranking: 1500 lbf (6672 N).
3. Inductive Kickback Peak Voltage: Not more than 53 V.
4. Residual Magnetism: Not more than 4 lbf (18 N) to separate door from magnet.
B. Delayed-Egress Locks: BHMA A156.24. Listed under Category G in BHMA's
"Certified Product Directory".
1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 lbf (67 N) for not more than 3 seconds, as required by NFPA 101.
2. Security Grade: Activated from secure side of door by initiating device.
3. Movement Grade: Activated by door movement as initiating device.
4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.
5. Coordinate with any requirements with Access Control and engineering drawings.
6. Exit device shall be coordinated with engineering drawings and activation shall be monitored by Johnson Controls panel and monitor at Police Desk.
2.11 ELECTRIC STRIKES
A. ANSI/ BHMA A156.31 Grade 1.
B. General: Use fail-secure electric strikes at fire-rated doors.
Milwaukee, WI 53295 12-01-2016
08 71 00-12
2.12 KEYS
A. Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:
Locks/Keys Quantity
Cylinder locks 2 keys each
Cylinder lock change key blanks
100 each different key way
Master-keyed sets 6 keys each
Grand Master sets 6 keys each
Great Grand Master set 5 keys
Control key 2 keys
2.13 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
A. Conform to ANSI Standard A156.6.
B. Provide protective plates as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates
25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
a. Armor plate side of doors;
b. Exterior side of exterior doors;
c. Closet side of closet doors;
d. Both sides of aluminum entrance doors.
4. Armor plates for doors are listed under Article "Hardware Sets".
Armor plates shall be thickness as noted in the hardware set, 875 mm
(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all
Milwaukee, WI 53295 12-01-2016
08 71 00-13
4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail.
On doors equipped with panic devices, extend armor plates to within
13 mm (1/2 inch) of panic bolt push bar.
5. Armor plates on rated doors to be UL listed to maintain required door rating.
6. Armor plates on toilet room doors to be 36” high.
2.14 EXIT DEVICES
A. Exit devices shall be Von Duprin or Sargent. Conform to ANSI Standard
A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.
B. Surface vertical rod panics shall only be provided less bottom rod;
provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.
C. Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.
D. Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.
E. At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.
F. Exit devices for fire doors shall comply with Underwriters
Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance.
G. Coordinate Access Control requirements with engineering drawings.
2.15 FLUSH BOLTS (LEVER EXTENSION)
A. Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to
ANSI A156.16, for flush bolts required on lower part of doors.
Milwaukee, WI 53295 12-01-2016
08 71 00-14
B. Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.
C. Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).
D. Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.
E. Provide extension rods for top bolt where door height exceeds 2184 mm
(7 feet 2 inches).
2.16 FLUSH BOLTS (AUTOMATIC)
A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI
A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).
B. At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than
20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
2.17 COMBINATION PUSH AND PULL PLATES
A. Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm
(1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.
2.18 COORDINATORS
A. Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for
Milwaukee, WI 53295 12-01-2016
08 71 00-15 full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
2.19 MISCELLANEOUS HARDWARE
A. Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):
Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.
B. Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur, // except as otherwise specified //. Provide cylinders to operate locking devices where specified for following partitions and doors:
1. Folding doors and partitions.
2. Wicket door (in roll-up door assemblies).
3. Slide-up doors.
4. Swing-up doors.
5. Fire-rated access doors-Engineer's key set.
6. Doors from corridor to electromagnetic shielded room.
7. Day gate on vault door.
C. Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers
Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors.
Provide 4 mutes or silencers for frames for each Dutch type door.
Provide 2 mutes for each edge of sliding door which would contact door frame.
2.20 FINISHES
A. Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.
B. 626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.
C. Miscellaneous Finishes:
Milwaukee, WI 53295 12-01-2016
08 71 00-16
1. Hinges --exterior doors: 626 or 630.
2. Hinges --interior doors: 652 or 630.
3. Pivots: Match door trim.
4. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.
5. Thresholds: Mill finish aluminum.
6. Cover plates for floor hinges and pivots: 630.
7. Other primed steel hardware: 600.
D. Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces.
E. Special Finish: Exposed surfaces of hardware for dark bronze anodized aluminum doors shall have oxidized oil rubbed bronze finish (dark bronze) finish on door closers shall closely match doors.
2.31 BASE METALS
A. Apply specified U.S. Standard finishes on different base metals as following:
Finish Base Metal
652 Steel
626 Brass or bronze
630 Stainless steel
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
A. For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA Resident Engineer for approval.
B. Hardware Heights from Finished Floor:
1. Exit devices centerline of strike (where applicable) 1024 mm (40-
5/16 inches).
2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).
3. Deadlocks centerline of strike 1219 mm (48 inches).
4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.
5. Centerline of door pulls to be 1016 mm (40 inches).
Milwaukee, WI 53295 12-01-2016
08 71 00-17
6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.
7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.
8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.
3.2 INSTALLATION
A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors except security bedroom, bathroom and anteroom doors which shall have closer installed parallel arm on exterior side of doors. At exterior doors, closers shall be mounted on interior side. Where closers are mounted on doors they shall be mounted with sex nuts and bolts; foot shall be fastened to frame with machine screws.
B. Hinge Size Requirements:
Door Thickness Door Width Hinge Height
45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)
45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)
125 mm (5 inches)
35 mm (1-3/8 inch)
(hollow core wood doors)
Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)
C. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.
D. Hinges Required Per Door:
Doors 1500 mm (5 ft) or less in height 2 butts
Doors over 1500 mm (5 ft) high and not over 2280 mm
(7 ft 6 in) high
3 butts
Doors over 2280 mm (7 feet 6 inches) high 4 butts
Dutch type doors 4 butts
Doors with spring hinges 1370 mm (4 feet 6 inches) high or less
2 butts
Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts
Milwaukee, WI 53295 12-01-2016
08 71 00-18
E. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted.
All fastenings exposed to weather shall be of nonferrous metal.
F. After locks have been installed; show in presence of Resident Engineer that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and above shall be sent
Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the Resident Engineer for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.
3.3 FINAL INSPECTION
A. Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:
1. Re-adjust hardware.
2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.
3. Identify items that have deteriorated or failed.
4. Submit written report identifying problems.
3.4 DEMONSTRATION
A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project Engineer and VA
Locksmith.
3.5 HARDWARE SETS
A. Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.
B. Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.
08 71 00-19
ELECTRIC HARDWARE ABBREVIATIONS LEGEND:
ADO = Automatic Door Operator
EMCH = Electro-Mechanical Closer-Holder
MHO = Magnetic Hold-Open (wall- or floor-mounted)
08 71 00-20
HW-1
Each Door to Have: NON-RATED
1 Continuous Hinge x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SCREWS
1 Storeroom Lock F07
1 Closer C02011/C02021
1 Armor Plate J101 x 1.275 MM (.050 INCH) THICKNESS
1 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY) , CUT: HARDWARE
1 Wall Stop L02101 CONVEX
3 Silencers L03011
HW-2
Each Door to Have: RATED
1 Continuous Hinge
1 Hospital Latch F01 x PADDELS POINTING DOWN
1 Closer C02021
1 Electric Strike E09331 (FAIL SECURE) 24VDC
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS
REQUIRED.
1 Kickplate J102
1 Wall Stop L02101 CONVEX
1 Set Self Adhesive Seals R0Y154
AUTOMATIC DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTO DOOR
OPERATORS.
08 71 00-21
HW-3
Hinges QUANITY & TYPE AS REQUIRED
1 Storeroom Lock F07
1 Closer C02021
1 Elecrtic Strike E09331 (Fail Secure) 24VDC
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS
REQUIRED.
1 Kickplate J102
1 Wall Stop L02101 CONVEX
CARD READER AND PUSH BUTTON AT RECEPTION BY DIVISION 28
HW-4
1 Office Lock F04
1 Kickplate J102
HW-5
1 Privacy Latch F02-MOD x OCCUPANCY INDICATOR
1 Kickplate J102
08 71 00-22
HW-6
Each Pair to Have: NON-RATED
1 Set Auto Flush Bolts TYPE 25 LESS BOTTOM BOLT
1 Latchset F01
1 Overlapping Astragal R0Y63
2 Armor Plates J101 x 1.25 MM (.050 INCH) THICKNESS
4 Edge Guards (@Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE
2 Wall Stops L02101 CONVEX
2 Silencers L03011
HW-7
1 Classroom Lock F05
1 Kickplate J102
HW-8
1 Privacy Latch F02-MOD x OCCUPANCY INDICATOR
1 Kickplate J102
1 Mop Plate J103
08 71 00-23
HW-9
1 Closer C02021
1 Elecrtic Strike E09331 (Fail Secure) 24VDC
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS
REQUIRED.
1 Kickplate J102
1 Wall Stop L02101 CONVEX
CARD READER BY DIVISION 28
HW-10
1 Closer C02011
1 Kickplate J102
HW-11
1 Latchset F01
1 Closer C02011
1 Kickplate J102
Milwaukee, WI 53295 12-01-2016
08 71 00-24
HW-12
1 Office Lock F04
1 Closer C02011
1 Kickplate J102
HW-13
Each Lead Lined Pair to Have: NON-RATED
2 Pivots Sets C07162 x 454KG (1000 LBS) WEIGHT CAPACITY
2 Intermediate Pivots C07311
1 Set Auto Flush Bolts TYPE 25 LESS BOTTOM BOLT x LEAD-LINED
1 Classroom Lock F08 x LEAD-LINED x PADDLES POINTING DOWN
1 Overlapping Astragal R0Y63 x R0Y154 x THRU-BOLTS x LEAD-LINED
1 Overhead Stop C01541
2 Armor Plates J101 x 1.25 MM (.050 INCH) THICKNESS
4 Edge Guards (@Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE
1 Set Self-Adhesive Seals R0Y154
HW-14
Each Pair to Have: NON-RATED
1 Set Auto Flush Bolts TYPE 25 LESS BOTTOM BOLT
1 Hospital Latch F01 x PADDELS POINTING DOWN
1 Overlapping Astragal R0Y63
2 Armor Plates J101 x 1.25 MM (.050 INCH) THICKNESS
4 Edge Guards (@Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE
08 71 00-25
HW-15
Each Lead lined Door to Have: NON-RATED
1 Pivots Set C07162 x 454KG (1000 LBS) WEIGHT CAPACITY
1 Intermediate Pivot C07311
1 Office Lock F04 x LEAD LINED
1 Closer C02011 x METAL LEAD LINED COVER
1 Kickplate J102
HW-16
1 Closer C02021
1 Kickplate J102
HW-17
1 Set Manual Flush Bolts L04081
1 Storeroom Lock F07
1 Closer C02021
1 Dust Proof Strike L04021
2 Kickplates J102
Milwaukee, WI 53295 12-01-2016
08 71 00-26
HW-18
Each Door to Have: EXTERIOR NON-RATED
1 Continuous Hinge
1 Anti-Vandal Pull
1 Exit Device TYPE 1 F03 LESS TRIM
1 Key Clinder TYPE AS REQUIRED
1 Closer C02021 x HD ARM
1 Kickplate J102
1 Floor Stop L02121 x THREE FASTNERS
1 Threshold J32120 x SILICONE GASKET
1 Door Sweep ROY416
1 Set Frame Seals R0Y164
1 Drip Guard R0Y976
HW-19
Each Rool-up Door Have: EXTERIOR NON-RATED
1 Padlock or Cylinder TYPE AS REQUIRED
BALANCE OF HARDWARE BY SECTION 08 33 00 , COILING DOORS AND GRILLS
HW-20
1 Continuous Hinges
1 Closer C02021
1 Elecrtic Strike E09331 (Fail Secure) 24VDC
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS
REQUIRED.
1 Kickplate J102
1 Wall Stop L02101 CONVEX
1 Set Self Adhesive Seals R0Y154
CARD READER BY DIVISION 28
08 71 00-27
HW-21
Each [ADO] Door to Have: RATED
1 Continuous Transfer Hinges x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SEREWS x 8-THRUWIRE
TRANSFER x IN-HINGE ACCESS PANEL
1 Continuous Transfer Hinges x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SEREWS x 4-THRUWIRE
TRANSFER x IN-HINGE ACCESS PANEL
1 Set Auto Flush Bolts TYPE 25 LESS BOTTOM BOLT
1 Classroom Hospital Lock F08 x PADDLES POINTING DOWN
1 Elecrtic Strike 310-2-3/4 OR EQUAL FAIL SECURE 24VDC
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS
REQUIRED.
1 Coordinator TYPE 21A
1 Overlapping Astragal with R0Y634 x R0Y154 x THRU-BOLTS
Self-Adhesive Seal
2 Armor Plates J101 x 1.275 MM (.050 INCH) THICKNESS
2 Edge Guards J208M / J211 (VERIFY). CUT: HARDWARE
1 Overhead Stop C01541-ADJUSTABLE
1 Wall Stop L02101 CONVEX
1 Set Self Adhesive Seals R0Y154
CARD READER BY DIVISION 28.
AUTOMATIC DOOR OPERATORS AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
POWER TRANSFERS SHARED BY ELECTRIC STRIKE AND RE-ACTIVATION SENOR WIRING
(RE-ACTIVATION SENORS PROVIDED BY SECTION 08 71 13).
08 71 00-28
HW-22
Each [ADO] Door to Have: NON-RATED
TRANSFER x IN-HINGE ACCESS PANEL
1 Continuous Transfer Hinges x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SEREWS x 4-THRUWIRE
TRANSFER x IN-HINGE ACCESS PANEL
1 Set Auto Flush Bolts TYPE 25 LESS BOTTOM BOLT
1 Hospital Latch F01 x PADDLES POINTING DOWN
1 Elecrtic Strike 310-2-3/4 OR EQUAL FAIL SECURE 24VDC
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS
REQUIRED.
1 Coordinator TYPE 21A
1 Overlapping Astragal with R0Y634 x R0Y154 x THRU-BOLTS
Self-Adhesive Seal
2 Armor Plates J101 x 1.275 MM (.050 INCH) THICKNESS
2 Edge Guards J208M / J211 (VERIFY). CUT: HARDWARE
1 Overhead Stop C01541-ADJUSTABLE
1 Wall Stop L02101 CONVEX
1 Set Self Adhesive Seals R0Y154
CARD READER BY DIVISION 28.
AUTOMATIC DOOR OPERATORS AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
HW-23
1 Kickplate J102
Milwaukee, WI 53295 12-01-2016
08 71 00-29
HW-24
1 Closer C02011 / C02021
1 Kickplate J102
1 Set Self Adhesive Seals R0Y154
HW-25
Each [ADO] Door to Have: RATED
TRANSFER x IN-HINGE ACCESS PANEL
1 Continuous Transfer Hinges x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SEREWS x 4-THRUWIRE
TRANSFER x IN-HINGE ACCESS PANEL
1 Set Auto Flush Bolts TYPE 25 LESS BOTTOM BOLT
1 Hospital Latch F01 x PADDLES POINTING DOWN
1 Elecrtic Strike 310-2-3/4 OR EQUAL FAIL SECURE 24VDC
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS
REQUIRED.
1 Coordinator TYPE 21A
1 Overlapping Astragal with R0Y634 x R0Y154 x THRU-BOLTS
Self-Adhesive Seal
2 Armor Plates J101 x 1.275 MM (.050 INCH) THICKNESS
2 Edge Guards J208M / J211 (VERIFY). CUT: HARDWARE
2 Wall Stop L02101 CONVEX
1 Set Self Adhesive Seals R0Y154
CARD READER BY DIVISION 28.
AUTOMATIC DOOR OPERATORS AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
Milwaukee, WI 53295 12-01-2016
08 71 00-30
- - - E N D - - -