MECHANICAL EQUIPMENT SCHEDULE
FEED FROM OCPD BRANCH WIRING MOTOR CONTROLLER DISCONNECT SWITCH CONNECTION REQUIREMENTS SEE
NO. SERVING LOC. VOLT/ HP FLA KW PANEL CKT BRNH TYPE SIZE POLE NO. SIZE GRD COND GRD FURN INST WIRE LOC. TYPE OPTIONS FURN INST WIRE LOC. OPTIONS NEMA TYPE OPTIONS MTG HEIGHT NOTE
PHASE (Y/N) SIZE BY BY BY BY BY BY
HSAF-1 SUPPLY FAN ROOF 480/3 20 - - EUH-Q-B00-1 1,3,5 EQ CB 60 3 3 10 Y 1 10 EC EC EC B0225 VFD - EC EC EC NU 4,6 - 3 - -
HSAF-2 SUPPLY FAN ROOF 480/3 20 - - EUH-Q-B00-1 2,4,6 EQ CB 60 3 3 10 Y 1 10 EC EC EC B0226 VFD - EC EC EC NU 4,6 - 3 - -
HRRF-1 RETURN-RELIEF FAN ROOF 480/3 8 - - EUH-Q-B00-1 7,9,11 EQ CB 25 3 3 12 Y 1/2 12 EC EC EC B0225 VFD - EC EC EC NU 4,6 - 3 - -
HRRF-2 RETURN-RELIEF FAN ROOF 480/3 8 - - EUH-Q-B00-1 8,10,12 EQ CB 25 3 3 12 Y 1/2 12 EC EC EC B0226 VFD - EC EC EC NU 4,6 - 3 - -
HEF-1 GENERAL EXHAUST FAN ROOF 120/1 1/4 - - UL-B00-1 2 N CB 15 1 2 12 Y 3/4 12 MFR MFR EC IU VFD - MFR MFR MFR NU 6 - 3 - -
HACCU-1 AIR COOLED CHILLER ROOF 480/3 - 88 MCA - UH-B00-1 38,40,42 N CB 100 3 3 3 Y 1 1/4 8 MFR MFR EC IU - - EC EC EC NU 4,6 - 3 - -
HACCU-B0004 AC UNIT - OUTDOOR SFP 208/1 - 25 MCA - EUL-Q-B00-1 2,4 EQ CB 35 2 2 10 Y 1 10 MFR MFR EC IU - - EC EC EC NU 4,6 - 3 - 1
HRCU-B0004 AC UNIT - INDOOR SFP 208/1 - - - - - - - - - 2 10 Y 1 10 MFR MFR EC IU - - EC EC EC NU 4 - 3 - 1
HACCU-B0005 AC UNIT - OUTDOOR SFP 208/1 - 10 MCA - EUL-Q-B00-1 1,3 EQ CB 15 2 2 12 Y 3/4 12 MFR MFR EC IU - - EC EC EC NU 4,6 - 3 - 1
HRCU-B005 AC UNIT - INDOOR SFP 208/1 - - - - - - - - - 2 12 Y 3/4 12 MFR MFR EC IU - - EC EC EC NU 4 - 3 - 1
HACCH-B0012 AIR COOLED CHILLER ROOF 480/3 - 8 - UH-B00-1 1,3,5 N CB 20 3 3 12 Y 3/4 12 MFR MFR EC IU - - EC EC EC NU 4,6 - 3 - -
HACCH-B0013 AIR COOLED CHILLER ROOF 480/3 - 8 - UH-B00-1 7,9,11 N CB 20 3 3 12 Y 3/4 12 MFR MFR EC IU - - EC EC EC NU 4,6 - 3 - -
HEX-ACCH-L1 AIR COOLED CHILLER ROOF 480/3 - 23 MCA - SD SD SD SD SD SD SD SD SD SD SD MFR MFR EC IU - - EC EC EC NU 4,6 - 3 - -
HEX-ACCH-L2 AIR COOLED CHILLER ROOF 480/1 - 26 MCA - SD SD SD SD SD SD SD SD SD SD SD MFR MFR EC IU - - EC EC EC NU 4,6 - 3 - -
HHWP-B0225A CIRCULATING PUMP - HEATING COIL B0225 480/3 1 2.1 - EUH-Q-B00-1 25,27,29 EQ CB 15 3 3 12 Y 3/4 12 EC EC EC NU CS - EC EC EC NU 4 - 3 - -
HHWP-B0225B CIRCULATING PUMP - HEATING COIL B0225 480/3 1 2.1 - EUH-Q-B00-1 25,27,29 EQ CB 15 3 3 12 Y 3/4 12 EC EC EC NU CS - EC EC EC NU 4 - 3 - -
HAC-C0A17 HOT WATER AIR CURTAIN C0A17 480/3 - - UH-B00-1 2,4,6 N CB 15 3 3 12 Y 3/4 12 EC EC EC NU CS - - - - - - - 3 - -
HAC-B0015 HOT WATER AIR CURTAIN B0015 480/3 - - EUH-Q-B00-1 14,16,18 EQ CB 15 3 3 12 Y 3/4 12 EC EC EC NU CS - - - - - - - 3 - -
HVAV-XFRMR VAV BOX TRANSFORMER PANEL B0225 120/1 - - 0.5 EUL-Q-B00-1 6 EQ CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 3 - -
HTCC-1 TEMPERATURE CONTROL PANEL B0225 120/1 - - 0.5 EUL-Q-B00-1 5 EQ CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 3 - -
HTCC-2 TEMPERATURE CONTROL PANEL B0225 120/1 - - 0.5 EUL-Q-B00-1 7 EQ CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 3 - -
PAC PRE ACTION SYSTEM COMPRESSOR C018 120/1 - - 1 EPL-LS-11-2 8 LS CB 20 1 2 12 Y 3/4 12 MFR MFR EC NU - - - - - - - 3 - 2
HCUH-C0A17 CABINET UNIT HEATER C017 120/1 - - - UL-B02-1 - N CB 20 1 2 12 Y 3/4 12 MFR MFR EC NU CS - - - - - - - 3 - 3
ABBREVIATIONS:
N = NORMAL BRANCH CB = AMPERE RATED CIRCUIT BREAKER MFR = MANUFACTURER 2SP = 2 SPEED MAGNETIC CONTROLLER SFS = SEE FOOD SERVICE PLANS SA = SEE ARCHITECTURAL DETAILS LS = LIFE SAFETY BRANCH F = AMPERE RATED FUSES PC = PLUMBING CONTRACTOR VFD = VARIABLE FREQUENCY DRIVE SD = SEE ONELINE DIAGRAM CR = CRITICAL CARE BRANCH OCPD = OVERCURRENT PROTECTIVE DEVICE MAN = MANUAL CONTROLLER IU = IN UNIT BOL = BUILT-IN OVERLOAD EQ = EQUIPMENT SYSTEM EC = ELECTRICAL CONTRACTOR MAG = MAGNETIC CONTROLLER NU = NEAR UNIT WP = WEATHER PROOF EM = EMERGENCY SYSTEM FSEC = FOOD SERVICE EQUIP. CONTRACTOR CS = COMBINATION CONTROLLER OU = ON UNIT FD = FUSIBLE DISCONNECT
ES = ESSENTIAL SYSTEM MC = MECHANICAL CONTRACTOR RVS = REDUCE VOLTAGE CONTROLLER SFP = SEE FLOOR PLANS LMRS = LOCKABLE MOTOR RATED SWITCH
OPTIONS:
1 = SINGLE RECEPTACLE 4 = NON FUSIBLE DISCONNECT 7 = LOCKABLE 10 = VERIFY WITH MANUFACTURER PRIOR TO INSTALLATION 13 = GFI RECEPTACLE
2 = DUPLEX RECEPTACLE 5 = FUSIBLE DISCONNECT 8 = CONCEALED 11 = SURFACE MOUNTED 14 = FED FROM UPSTREAM GFI BREAKER
3 = DIRECT CONNECTION 6 = WEATHERPROOF 9 = TOGGLE SWITCH 12 = FLUSH MOUNTED
MECHANICAL EQUIPMENT SCHEDULE NOTES:
1. INDOOR UNIT IS FED FROM THE OUTDOOR UNIT. CONFIRM CONFIGURATION WITH APPROVED SHOP DRAWINGS PRIOR TO INSTALLATION. WIRE PER MANUFACTURER'S INSTALLATION MANUAL.
2. FINAL INFORMATION NOT PROVIDED DURING TIME OF DESIGN. EC TO COORDINATE FINAL MOTOR SIZE AND WIRING REQUIREMENTS WITH FIRE PROTECTION CONTRACTOR. EC TO REUSE SPARE CIRCUIT BREAKERS WITHIN EXISTING LIFE SAFETY PANEL.
3. REUSE SPARE EXISTING CIRCUIT BREAKER FROM PANEL UL-B02-1.
MEDICAL EQUIPMENT SCHEDULE
FEED FROM OCPD BRANCH WIRING MOTOR CONTROLLER DISCONNECT SWITCH CONNECTION REQUIREMENTS SEE
NO. SERVING LOC. VOLT/ HP FLA KW PANEL CKT BRNH TYPE SIZE POLE NO. SIZE GRD COND GRD FURN INST WIRE LOC. TYPE OPTIONS FURN INST WIRE LOC. OPTIONS NEMA TYPE OPTIONS MTG HEIGHT NOTE
PHASE (Y/N) SIZE BY BY BY BY BY BY
CITB-1 CLIENT INTERFACE TERMINAL BOX B0013 120/1 - - 0.5 EUL-CR-B00-1 19 CR CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 3 - -
CITB-2 CLIENT INTERFACE TERMINAL BOX B0012 120/1 - - 0.5 EUL-CR-B00-1 21 CR CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 3 - -
ED-1 PUSH BUTTON B0014 120/1 - - - UL-B00-1 42 N CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 4 - -
ED-2 PUSH BUTTON B0011 120/1 - - - UL-B00-1 30 N CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 5 - -
FB2-1 ACCELERATOR UNIT B0013 480/277 - - 45 SD SD N SD SD SD SD SD SD SD SD - - - - - - SD SD SD SD SD - 3 - 1
FB2-2 ACCELERATOR UNIT B0012 480/277 - 45 SD SD N SD SD SD SD SD SD SD SD - - - - - - SD SD SD SD SD - 3 - 1
GEN-1 X-RAY GENERATOR B0013 480/277 - - 40 SD SD N SD SD SD SD SD SD SD SD - - - - - - SD SD SD SD SD - 3 - 1
GEN-2 X-RAY GENERATOR B0012 480/277 - - 40 SD SD N SD SD SD SD SD SD SD SD - - - - - - SD SD SD SD SD - 3 - 1
L-1 LASER SFP 120/1 - - - UL-B00-1 40 N CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 2 - 2
L-2 LASER SFP 120/1 - - - UL-B00-1 28 N CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 2 - 2
L-3 CT LASER B0004 120/1 - - - UL-B00-1 50 N CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - - -
MLD MIDGET LOCKING DEVICE SFP 120/1 - - - SFP SFP CR CB 15 1 2 12 Y 3/4 12 - - - - - - - - - - - ML-2R 6 - -
PETMRI PETMRI TRAILER SFP 480/277 - - - SD SD CR SD SD SD SD SD SD SD SD - - - - - - SD SD SD SD 6 - 6,10 - 3
PDC POWER DISTRIBUTION CABINET B0005 480/277 - - - SD SD N SD SD SD SD SD SD SD SD - - - - - - SD SD SD SD SD - 3 - 1
SPD SURGE PROTECTIVE DEVICE B0004 480/277 - - - SD SD N SD SD SD SD SD SD SD SD - - - - - - SD SD SD SD SD - 3 - 1
TC CAMERA OUTLETS SFP 120/1 - - - SFP SFP CR CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 2 - 4
ABBREVIATIONS:
N = NORMAL BRANCH CB = AMPERE RATED CIRCUIT BREAKER MFR = MANUFACTURER 2SP = 2 SPEED MAGNETIC CONTROLLER SFS = SEE FOOD SERVICE PLANS SA = SEE ARCHITECTURAL DETAILS LS = LIFE SAFETY BRANCH F = AMPERE RATED FUSES PC = PLUMBING CONTRACTOR VFD = VARIABLE FREQUENCY DRIVE SD = SEE ONELINE DIAGRAM CR = CRITICAL CARE BRANCH OCPD = OVERCURRENT PROTECTIVE DEVICE MAN = MANUAL CONTROLLER IU = IN UNIT BOL = BUILT-IN OVERLOAD EQ = EQUIPMENT SYSTEM EC = ELECTRICAL CONTRACTOR MAG = MAGNETIC CONTROLLER NU = NEAR UNIT WP = WEATHER PROOF EM = EMERGENCY SYSTEM FSEC = FOOD SERVICE EQUIP. CONTRACTOR CS = COMBINATION CONTROLLER OU = ON UNIT FD = FUSIBLE DISCONNECT
ES = ESSENTIAL SYSTEM MC = MECHANICAL CONTRACTOR RVS = REDUCE VOLTAGE CONTROLLER SFP = SEE FLOOR PLANS LMRS = LOCKABLE MOTOR RATED SWITCH
OPTIONS:
1 = SINGLE RECEPTACLE 4 = NON FUSIBLE DISCONNECT 7 = LOCKABLE 10 = VERIFY WITH MANUFACTURER PRIOR TO INSTALLATION 13 = GFI RECEPTACLE
2 = DUPLEX RECEPTACLE 5 = FUSIBLE DISCONNECT 8 = CONCEALED 11 = SURFACE MOUNTED 14 = FED FROM UPSTREAM GFI BREAKER
3 = DIRECT CONNECTION 6 = WEATHERPROOF 9 = TOGGLE SWITCH 12 = FLUSH MOUNTED
MEDICAL EQUIPMENT SCHEDULE NOTES:
1. REFER TO ONE LINE DIAGRAMS AND FLOOR PLANS FOR ADDITIONAL INFORMATION.
2. WIRE PER MANUFACTURS SITE SPECIFIC DRAWINGS. REFER TO SHEET E1a OF ELEKTA VERSA HD REF DRAWING.
3. PROVIDE A THOMAS & BETTS (T&B) DF2504FRAB0 RECEPTACLE OR EQUIVALENT.
4. 120VAC CONVENIENCE OUTLET PROVIDING POWER TO CCTV CAMERAS (FLUSH MOUNTED IN WALL RECESS).
LIGHT FIXTURE SCHEDULE
FIXTURE LIGHT SOURCE BALLASTS/DRIVERS INPUT
VOLT MOUNT
SURFACE FIXTURE FIXTURE SPECIFICATION AND ACCEPTABLE MANUFACTURERS
OPTIONS
SEE
ID DESCRIPTION TYPE NO. DESCRIPTION WATTS K CRI (MIN.) TYPE CONTROL NO. WATTS TYPE DEPTH MANUFACTURER CATALOG SERIES NOTE
AA
2X4 TROFFER 4000 LITHONIA 2TL
PRISMATIC LENS FROST OVERLAY LED - DELIVERED 31 4000 80 DR DM10 1 31 277 R LG <5" 1,2 1B
LUMENS
AC
2X4 TROFFER 7200 LITHONIA GTL
PRISMATIC LENS FROST OVERLAY LED - DELIVERED 53 4000 80 DR DM1 1 53 277 R LG <5" 1,2 1B
LUMENS
AN
2X4 VOLUMETRIC TROFFER 3000 LITHONIA 2VTL
CURVED CENTER LENS W/ LINEAR PRISMATIC LED - DELIVERED 26 4000 80 DR DM10 1 26 277 R LG <5" 1 1B
LUMENS
AZ
2X4 IMAGE PANEL LUMINAIRE FAIL SAFE CV-LEL-4B
LED - IN UNIT 20 6000 80 XFMR DM1 1 20 277 R LG <1" NEWSTAR AGG24 28 3,4
PRIOR APPROVED EQUAL
CB
2X2 TROFFER 4000 LITHONIA 2TL
PRISMATIC LENS FROST OVERLAY LED - DELIVERED 35 4000 80 DR DM10 1 35 277 R LG <5" 1,2 1B
LUMENS
CC
2X2 TROFFER 2000 LITHONIA 2TL
PRISMATIC LENS FROST OVERLAY LED - DELIVERED 17 4000 80 DR DM10 1 17 277 R LG <5" 1,2 1B
LUMENS
CD
2X2 TROFFER 4000 LITHONIA 2GTL
PRISMATIC LENS FROST OVERLAY LED - DELIVERED 34 4000 80 DR DM10 1 34 277 R LG <5" 1,2 1B
LUMENS
CE
2X4 CLEANROOM TROFFER 3000 LITHONIA SRTL
SEALED AND GASKETED LED - DELIVERED 27 4000 80 DR DM1 1 27 277 R LG <5" 1,17,71 1B
LUMENS
CF
2X4 CLEANROOM TROFFER 5000 LITHONIA SRTL
SEALED AND GASKETED LED - DELIVERED 42 4000 80 DR DM1 1 42 277 R LG <5" 1,17,71 1B
LUMENS
CN
2X2 VOLUMETRIC TROFFER 2000 LITHONIA 2VTL
CURVED CENTER LENS W/ LINEAR PRISMATIC LED - DELIVERED 18 4000 80 DR DM10 1 18 277 R LG <5" 1 1B
LUMENS
CQ
2X2 VOLUMETRIC TROFFER 3300 LITHONIA 2VTL
CURVED CENTER LENS W/ LINEAR PRISMATIC LED - DELIVERED 30 4000 80 DR DM10 1 30 277 R LG <5" 1 1B
LUMENS
DA
4" DIA APERTURE DOWNLIGHT 700 GOTHAM EVO4
WIDE BEAM DISTRIBUTION LED - DELIVERED 10 4000 80 DR DM10 1 10 277 R V <8" 41 1C
LUMENS
DB
4" DIA APERTURE DOWNLIGHT 2000 GOTHAM EVO4
WIDE BEAM DISTRIBUTION LED - DELIVERED 24 4000 80 DR DM10 1 24 277 R V <8" 41 1C
LUMENS
DC
2" DIA APERTURE DOWNLIGHT 860
R LG <5"
ALPHABET 624 RD
40 DEGREE DISTRIBUTION LED - DELIVERED 12 3500 80 DR DM1 1 12 277 41 1C
DIFFUSED LENS LUMENS
DD
3" DIA DECORATIVE DOWNLIGHT 700
R DW <5"
LIGHTOLIER C2L R02
ACRYLIC WITH CENTER CUTOUT LED - DELIVERED 10 4000 80 DR DM10 1 10 277 FOCAL POINT FLS2D
LUMENS PATHWAY 4VLFL2XG GSW
DE
6"DIA APERTURE DOWNLIGHT 1500 FAILAFE FFLD6A/OR
SEALED AND GASKETED SURGICAL FIXT. LED - DELIVERED 23 4000 80 DR DM1 1 23 277 R V <8" 16,41 1E
FLUSH LENS LUMENS
FC
4' STRIPLIGHT 3000 LITHONIA CLX
CURVED LENS SHIELDING LED - DELIVERED 35 4000 80 DR SW 1 35 277 SUSP. ES - 1,33 1B
CHAIN MOUNTING LUMENS
FP
4' CLOSET LIGHT ** LITHONIA WL4
CURVED LENSED SHIELDING LED - DELIVERED 40 4000 80 DR SW 1 40 277 S W - 1,55 1B
INTEGRAL PIR MOTION SENSOR LUMENS
LC
2IN W X 6FT L LINEAR BEAM FIXTURE 375 L/FT 5 5
S SKYLGT. -
FOCAL POINT FSM1BW DCFL
WALL MOUNT. DIRECT DISTRIBUTION LED - DELIVERED WATTS 4000 80 DR DM10 AR WATTS 277 AXIS SCWDI 28 6
FLUSH LENS. WHITE FINISH LUMENS PER FT. PER FT. FINELITE / LITECONTROL HP2 / MOD2
LD
4IN WIDE RECESSED LINEAR 625 L/FT 8.5 8.5
R LG <5"
FOCAL POINT FSM4AL
WALL WASH DISTRIBUTION LED - DELIVERED WATTS 4000 80 DR DM10 NO. WATTS 277 AXIS BBRLED ASO 43 6
FROSTED LENS LUMENS PER FT. PER FT. FINELITE / LITECONTROL HP4 / MOD4 RL ASYM
LIGHTING CONTROL PANEL SCHEDULE - BASEMENT LEVEL
CONTROL
PANEL PANEL RELAY CIRCUIT LOAD BRANCH RELAY LOW VOLTAGE SWITCH DAYLIGHT PHOTOCELL TIMECLOCK BLINK SEE
DESIGNATION LOCATION NUMBER CONTROLLED DESCRIPTION SOURCE TYPE CONTROL SENSOR WARNING NOTE
LCP-B00-1
MECH/ELEC
B0225
1 UH-B00-1-8 CORRIDOR N 0-10V ON / OFF / OVERRIDE DIM 1,3
2 UH-B00-1-8 CORRIDOR N 0-10V ON / OFF / OVERRIDE 1
3 UH-B00-1-8 CORRIDOR N 0-10V ON / OFF / OVERRIDE 1
4 UH-B00-1-8 CORRIDOR N 0-10V ON / OFF / OVERRIDE DIM 1,3
5 UH-B00-1-8 CORRIDOR N 0-10V ON / OFF / OVERRIDE 1,
6 UH-B00-1-8 CORRIDOR N 0-10V ON / OFF / OVERRIDE 1
7 UH-B00-1-8 CORRIDOR N 0-10V ON / OFF / OVERRIDE 1
8 UH-B00-1-8 SKYLIGHT N 0-10V ASTRONOMIC ON / OFF 2
9 UH-B00-1-8 EXTERIOR-DOORS N ON / OFF ON / OFF
10 UH-B00-1-8 EXTERIOR N ON / OFF ON / OFF
11 UH-B00-1-8 CORRIDOR WALL WASH N 0-10V DIM AUTO ON / OFF
12 UH-B00-1-8 CORRIDOR WALL WASH N 0-10V DIM AUTO ON / OFF
13 SPARE ON / OFF
14 SPARE ON / OFF
15 SPARE ON / OFF
16 SPARE ON / OFF
BRANCH SOURCE: N = NORMAL E = EMERGENCY C = CRITICAL LS = LIFE SAFETY
E = 700 LEGALLY REQUIRED EMERGENCY S1 = 701 LEGALLY REQUIRED STANDBY S2 = 702 STANDBY
LIGHTING CONTROL PANEL GENERAL NOTES:
1. PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE AND OPERATING SYSTEM.
2. PROVIDE HIGH VOLTAGE BARRIERS AS NECESSARY TO SEPARATE DIFFERENT BRANCH SOURCES.
3. VERIFY ALL PROGRAMMING PARAMETERS WITH OWNER PRIOR TO FINAL COMMISSIONING.
4. REFER TO LOW VOLTAGE SWITCH STATION SCHEDULE FOR MORE INFORMATION.
LIGHTING CONTROL PANEL SCHEDULE NOTES:
1. EGRESS FIXTURES SHOWN ON PLAN, FED BY RELAY, SHALL UTLIZE UL924 DEVICE. REFER TO DETAILS ON ES502 FOR WIRING DIAGRAM. EC TO VERIFY COMPATIBLE TYPE.
2. PROGRAM RELAY TO TURN ON AT SUNSET AND OFF AT SUNRISE. OWNER SHALL VERIFY IF RELAY SHALL BE SET TO A DIMMED LEVEL.
3. LOCAL DAYLIGHT SENSOR SHALL CONTINUOUSLY DIM FIXTURES IN DAYLIGHT ZONE BUT NEVER TURNING THEM OFF. IN CORRIDORS, MAINTAIN 15 FOOTCANDLES (FC) AT FLOOR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C
R e v it L o c a lF ile s \7
.0
E c k ro llG T
Z L J .r v t
/2
/2
:5
:4
P
M
ES601
ELECTRICAL SCHEDULES CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 Checker MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
LIGHT FIXTURE SCHEDULE CONTINUED ON ES603
Revisions: Date:
ADDENDUM 1 02/22/2019
| Sheets |
| ES601 - ELECTRICAL SCHEDULES |
| ES602 - ELECTRICAL SCHEDULES |