MAIN RUN BRANCH RUN
ALLOWABLE J-HOOK ARRANGEMENTS LVC TO SELECT AS CONSTRUCTION DICTATEES
MAIN RUN WALL RUN
DETAIL NOTES -
KEYED NOTES -
ATR SUPPORTWALL
SUPPORT
WASHER & NUTWASHER & NUT
2 1 2
J HOOK SHALL BE SIZED FOR CABLE SIZE AND LOAD.
SPACING BETWEEN J HOOKS 4 FEET ON CENTER.
INSTALL ADDITIONAL J HOOKS AS REQUIRED.
1.
2.
3.
THIS HOOK IS DEDICATED FOR VOICE CABLING.
THIS HOOK IS DEDICATED FOR DATA CABLING.
THIS HOOK IS DEDICATED FOR TV CABLING.
NOT USED.
CONCRETE FLOOR
WORK AREA OUTLET (TYPICAL)
CONDUIT TO ABOVE LAY-IN CEILING
WALL SLEEVE
FLOOR ABOVE
HANGER SUPPORTED FROM STRUCTURE OF FLOOR
ABOVE - OR WALL
LAY-IN CEILING
J-HOOK (TYPICAL)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
ALL DEVICES SHOWN MAY NOT APPLY TO ALL DOORS. THE
DEVICES INDICATED ARE TYPICAL DEVICES REQUIRING
WORK BY THIS ELECTRICAL CONTRACTOR. THE EC SHALL
REFERENCE THE ARCHITECTURAL DOOR HARDWARE
SCHEDULE AND SPECIFICATION FOR ALL EQUIPMENT
ASSOCIATED WITH EACH DOOR HARDWARE GROUP.
ASSUME A SINGLE GANG JUNCTION BOX SHALL BE
FURNISHED BY THE EC FOR EACH DOOR HARDWARE
DEVICE FOR BIDDING. THE EC SHALL COORDINATE WITH
THE GC AND DOOR HARDWARE VENDOR PRIOR TO THE
START OF DOOR HARDWARE ROUGH-IN WORK. EC SHALL
PROVIDE JUNCTION BOXES AS DEFINED IN THE DOOR
HARDWARE VENDOR'S WIRING DIAGRAM.
EC SHALL PROVIDE THE 120V CIRCUIT, BOXES AND
RACEWAYS FOR EACH TYPICAL DOOR TYPE AS SHOWN
ABOVE. DOOR HARDWARE EQUIPMENT INSTALLATION WILL
BE BY OTHERS.
REFER TO ET101 AND ET102 FOR CARD READER
LOCATIONS.
THE DOOR HARDWARE VENDOR SHALL PROVIDE A JOB
SPECIFIC WIRING DIAGRAM INDICATING THE WIRING OF ALL
DEVICES ASSOCIATED WITH EACH DOOR HARDWARE
GROUP. THIS INCLUDES DEVICES PROVIDED BY THE DOOR
HARDWARE VENDOR, SECURITY INTERFACES, AND FIRE
ALARM INTERFACES. IF THIS WIRING DIAGRAM IS NOT
PROVIDED AT THE TIME OF DOOR HARDWARE ROUGH-IN,
THE EC SHALL CONTACT THE ARCHITECT/GC.
THE SIZE AND AMOUNT OF WIRING INDICATED IN THIS
DETAIL FOR EACH DEVICE IS PROVIDED FOR BIDDING, AND
IS A REASONABLE ESTIMATE ONLY. THE EC SHALL PROVIDE
THE SIZE AND QUANTITY OF WIRING AS DEFINED IN THE
DOOR HARDWARE VENDOR'S WIRING DIAGRAM.
THE EC SHALL BE RESPONSIBLE FOR WIRING EACH DEVICE
AS INDICATED IN THE DOOR HARDWARE VENDOR'S WIRING
DIAGRAMS. THIS INCLUDES TERMINATION AT THE DEVICE,
POWER SUPPLY, ANCILLARY DEVICES, AND TERMINATION
AT THE TERMINAL STRIP IN THE JUNCTION BOX ABOVE THE
CEILING.
AUTO DOOR OPENER PUSH PADDLES ARE SHOWN ON
ARCHITECTURAL PLANS. REFER TO ARCHITECTURAL PLANS,
DETAILS AND SCHEDULES FOR EXACT QUANTITIES AND
LOCATIONS.
DOUBLE DOOR SINGLE DOOR
DETAIL NOTES -
1/2"C.
STRUCTURE
CEILING
1/2"C. 1/2"C. 1/2"C.3/4"C.3/4"C.
STRUCTURE
CEILING
1/2"C. 1/2"C.1/2"C.
RM
EL EL
CR
DC
CR
DC
ES
DCES
DCDC
EL
EL
RM
HW-22 HW-20
S S
S
S S S S
S
SSS
S
S
D D
RM
S
1/2"C.
RM
S
DCS
DOUBLE DOOR
STRUCTURE
EL
HW#
S
S
S
D
DC
DC
ES
ES
S
ACCESS CONTROL DEVICES ARE SERVED FROM NEW
ACCESS CONTROL PANEL AS NOTED ON SHEET ET101.
EC SHALL PROVIDE JUNCTION BOX LOCATED ABOVE AN
ACCESSIBLE CEILING, ABOVE THE DOOR CONTROLLED.
JUNCTION BOX SHALL HAVE A MINIMUM SIZE OF 8"X8"X4".
WHEN BOTH DOOR HARDWARE COMPONENTS AND
SECURITY DEVICES ARE INSTALLED ON A DOOR, THIS
JUNCTION BOX SHALL BE SHARED WITH THE SECURITY
SYSTEM. SEE THE SECURITY ACCESS AND DOOR CONTROL
WIRING DETAIL FOR MORE INFORMATION.
EC SHALL PROVIDE A 20 POSITION TERMINAL STRIP FOR
DOOR HARDWARE WIRING, AND MOUNT WITHIN JUNCTION
BOX DEFINED IN KEYED NOTE #1 ABOVE DOOR.
SPECIAL OUTLET SHOWN FOR THE POWER SUPPLY SHALL
PROVIDE 120V POWER FOR ALL POWER SUPPLIES AT THIS
DOOR. SEE FLOOR PLAN FOR EXACT CIRCUIT INFORMATION.
FIRE ALARM CONTROL MODULE SHALL PROVIDE A SET OF
NORMALLY OPEN CONTACTS THAT WILL CLOSE UPON AN
ALARM CONDITION IN THE FIRE ALARM SYSTEM. THE
CLOSURE OF THESE CONTACTS SHALL RELEASE ANY
LOCKING MECHANISMS SECURING THIS DOOR FOR EGRESS
PURPOSES.
DEVICE IS A SECURITY DEVICE. ROUTE CABLING TO NEW
ACCESS CONTROL PANEL, SIMILAR TO THE CARD READER.
KEYED NOTES -
1/2"C.1/2"C. 3/4"C.3/4"C.
EL EL
DCSDCS
EL
S
D
PT
D
PT
D
PT
D
PT
1/2"C.
2 #18
1/2"C.
4 #12 4 #18
AO
CM
XX
JUNCTION
BOX
ABOVE
CEILING
PSD
F5
6 6
6 #18 2 #18 2 #18 6 #18 6 #18 2 #18 2 #18 2 #18 6 #18 6 #18
1/2"C.
2 #18
1/2"C.
4 #12 4 #18
AO
XX
JUNCTION
BOX
ABOVE
CEILING
PSD
F5
6 6
DD D
D
D
6 #18 2 #18 2 #18 2 #18
1.
2.
3.
4.
5.
6.
1.
2.
3.
4.
5.
6.
7.
8.
DOUBLE DOOR
1/2"C.
STRUCTURE
CEILING
1/2"C. 1/2"C.3/4"C.
INACTIVE LEAF
CR
DC
DCDC
HW#
S S
S
S
D
DCS
ES
ES
S
D
PT
2 #18 2 #18 2 #18 6 #18
D
SINGLE DOOR
STRUCTURE
CEILING
ES
HW-2
S
D
1/2"C.
2 #18
1/2"C.
4 #12 4 #18
AO
XX
JUNCTION
BOX
ABOVE
CEILING
PSD
F5
1/2"C.
EMD
4 #18 1/2"C.
EM D
4 #18
HW-9DHW-3D
1/2"C.
ES
S
2 #18
HW-21D HW-25D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
FULLY-SPRINKLERED
PHASING IS DEFINED IN PROJECT SPECIFICATIONS AND PHASING PLANS. CONTRACTOR
TO COORDINATE THE FULL SCOPE OF WORK TO BE PHASED SO AS TO NOT IMPACT THE
OPERATION OF SURROUNDING SPACES OR PREVIOUS PHASES. SPECIFIC COORDINATION
SHOULD BE GIVEN FOR DEMOLITION, UTILITY ROUTING AND SHUTDOWNS.
C U s e rs
\p e rm o \D o c u m e n ts
\7
.0
E
M
P e re z ri n g d u .c o m
.r v t
/2
/2
:4
:4
A
M
ET500
TECHNOLOGY DETAILS CONSTRUCT NEW RADIATION
ONCOLOGY SUITE
MILWAUKEE VAMC
695-404
04 OCTOBER 2018 MGM MTP
FINAL CONSTRUCTION
DOCUMENTS BLDG 111
17400 West Capitol Drive, Brookfield, WI 53045 Phone: 414.778.1700 / Fax: 414.778.2360 / r-d@ringdu.com
R&D Project No.:
THIS BAR IS 1" LONG.
IF IT MEASURES ANYTHING OTHER THAN 1"
ADJUST SCALE ACCORDINGLY.
217164.00
NOT TO SCALEET500
2 TYPICAL CABLE SUPPORTS
NOT TO SCALEET500
ARCHITECTURAL DOOR HARDWARE INSTALLATION
GUIDELINES1
Revisions: Date:
ADDENDUM 1 02/22/2019
| Sheets |
| ET101 - PARTIAL BASEMENT FLOOR PLAN - TECHNOLOGY |
| ET500 - TECHNOLOGY DETAILS |
| ET600 - TECHNOLOGY SCHEDULES |