36E77619R0009-0002003.pdf

PDF Posted

Attached to
ESPC IDIQ (VA-19-00001743) Federal contract opportunity
Solicitation number
36E77619R0009
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This pre-solicitation notice announces the Department of Veterans Affairs' intent to issue an indefinite delivery, indefinite quantity multiple award contract for energy savings performance contracts. The solicitation number will be 36E77619R0009 and will be posted on January 15, 2019 on FEDBIZOPPS and the VA vendor portal. The NAICS code is 236220 and the small business size standard is $36.5 million.

The IDIQ contract will utilize the Department of Energy's qualified list of energy service companies. Eligible service-disabled veteran-owned small businesses must be on the qualified ESCO list and registered in the Vendor Verification Program and SAM database. The VA estimates annual cost savings through energy conservation measures implemented by contractors at no upfront cost, with contractors paid back through a contractually determined share of savings over the term.

36E77619R0009 0002 Old PV Drawings.pdf

View the file

Other files for this federal contract opportunity

Other files attached to ESPC IDIQ (VA-19-00001743), newest first.
File Type Posted
36E77619R0009 0008.docx DOCX document
36E77619R0009-0007000.docx DOCX document
36E77619R0009-0007000.docx DOCX document
36E77619R0009-0006000.docx DOCX document
36E77619R0009-0005001.docx DOCX document
36E77619R0009-0004000.docx DOCX document
36E77619R0009-0004000.docx DOCX document
36E77619R0009-0003004.pdf PDF
36E77619R0009-0003002.pdf PDF
36E77619R0009-0003005.pdf PDF
36E77619R0009-0003004.pdf PDF
36E77619R0009-0002002.pdf PDF
36E77619R0009-0002000.docx DOCX document
36E77619R0009-0002004.pdf PDF
36E77619R0009-0002000.docx DOCX document
36E77619R0009-0002002.pdf PDF
36E77619R0009-0002003.pdf PDF
36E77619R0009-0001001.docx DOCX document
36E77619R0009-0001000.docx DOCX document
36E77619R0009-0001001.docx DOCX document
36E77619R0009-027.docx DOCX document
36E77619R0009-026.pdf PDF
36E77619R0009-023.pdf PDF
36E77619R0009-021.pdf PDF
36E77619R0009-019.pdf PDF
36E77619R0009-018.docx DOCX document
36E77619R0009-013.pdf PDF
36E77619R0009-010.pdf PDF
36E77619R0009-028.pdf PDF
36E77619R0009-022.pdf PDF
36E77619R0009-014.pdf PDF
36E77619R0009-011.pdf PDF
36E77619R0009-019.pdf PDF
36E77619R0009-004.docx DOCX document
36E77619R0009-011.pdf PDF
36E77619R0009-005.pdf PDF
36E77619R0009-020.pdf PDF
36E77619R0009-006.pdf PDF
36E77619R0009-008.pdf PDF
36E77619R0009-013.pdf PDF
36E77619R0009-010.pdf PDF
36E77619R0009-012.pdf PDF
36E77619R0009-018.docx DOCX document
36E77619R0009-027.docx DOCX document
36E77619R0009-009.pdf PDF
36E77619R0009-007.pdf PDF
36E77619R0009-028.pdf PDF
36E77619R0009-025.pdf PDF
Vendor_Portal_Instructions.pdf PDF
36E77619R0009.docx DOCX document
Show all 50

ESPC IDIQ (VA-19-00001743) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B

C

D

E

F

G

H

J

03.AS.301

03.AS.301

03.AS.301

03.AS.301

03.AS.302

03.AS.302

03.AS.202

03.AS.202

SEE - 1/03.AS.105-B SEE - 1/03.AS.105-B

A

2'-9"32'-0"32'-0" - 8 EQ PANELS32'-0" - 8 EQ PANELS32'-0" - 8 EQ PANELS32'-0" - 8 EQ PANELS32'-0" - 8 EQ PANELS32'-0" - 8 EQ PANELS28'-0"

'-9

'-0

'-0

'-0

'-0

34'-4 1/4"

252'-0"

0'

-8

/8

CLS

XX.AS.562

XX.AS.561

XX.AS.561

RS03

MP52

MP52A

MP52

MP52A

4.6

SMOKE VENT

ROOF HOOD

RE: MH DWGS

XX.AS.562

RS23

XX.AS.563

GRATING

RE: SS DWGS

DB

LSP

03.AS.105-A

179' - 5"

180' - 9"

179' - 5" 180' - 9"

179' - 5"

180' - 9"

179' - 5"

MP52A

1' -0

2'

-4

XX.AS.547

XX.AS.547

SIM

BCT

XX.AS.411

TYP

179' - 0"

180' - 0"

4'-0"4'-9 3/4"9"

1' -5

7'

-4

/8

REMOVABLE

GUARD RAIL

DN

TRIM AND SEAL

AROUND DB, TYP

XX.AS.563

OVERFLOW

SCUPPER

MP52A

MP52

9"

RD & OFD REF TO

15/XX.AS.562 AND PLUMBING DWGS

ROOFING SYSTEM LEGEND

CODE

RS01

DESCRIPTION

RUBBERIZED ASPHALT GREEN

ROOF SYSTEM

RS02

RS03

RUBBERIZED ASPHALT PAVER

ROOF SYSTEM

RUBBERIZED ASPHALT PAVER

ROOF AT PV PANELS

RS11

PVC ROOFING SYSTEM NON-

INSULATED

DAVIT BASE

RS21

DB

CLS CONTINUOUS LIFE LINE SYSTEM

BMRS BUILDING MAINTENANCE

RAIL SYSTEM

PERMANENTLY FIXED ROTATING

DAVITSDLP

PVC ROOFING SYSTEM

INSULATED ON CONCRETE DECKRS22

ROOF HATCHROH01

PVC ROOFING SYSTEM

INSULATED ON METAL DECKRS23

DUAL VERTICAL RAILS FOR

ROLLING SOCKET

SIMULATED-METAL PVC

ROOFING

RS01-A RUBBERIZED ASPHALT GREEN

ROOF SYSTEM

LSP

BCT

CONTINUOUS LIFELINE

SUPPORT PEDESTALS

BOSUN CHAIR / SAFETY

TIEBACKS

EXTENT OF SNOW MELT SYSTEM,

REFER TO 11/XX.AS.562 FOR DET

DVR

GENERAL NOTES

1. FOR ROOF PENETRATION DETAILS REFER TO DETAILS 1 THROUGH 4 ON

XX.AS.562

2. FOR BUILDING MAINTENANCE & FALL PROTECTION SYSTEM DETAILS

REFER TO DETAILS 5 THROUGH 7 ON XX.AS.562

3. FOR LIGHTNING PROTECTION ROD DETAIL REFER TO DETAIL 8 ON

XX.AS.562

4. FOR CONCOURSE STANDING SEAM LAYOUT REFER TO PARTIAL ROOF

PLAN 3 ON XX.AS.104-B

5. FOR PVC ROOFING SYSTEM PROVIDE 6" MINIMUM TAPERED INSULATION

WITH 2% MINIMUM SLOPE TO DRAIN.

6. ALL SOUTH ELEVATION SUPER-RIB WALL OPENING HEIGHT TO BE 11'-

10" (SILL HEIGHT 4' 8" FROM PENTHOUSE LEVEL), UNLESS NOTED

OTHERWISE

7. FOR LOUVER SIZES REFER TO PLANS AND ELEVATIONS. TOP HEIGHT OF

LOUVERS TO ALIGN AT 17' 6" ABOVE PENTHOUSE LEVEL, UNLESS

NOETED OTHERWISE

C

XX.AS.523

RS23

176' - 9"

176' - 7"

4'-2 7/8"6'-11"

XX.AS.563

176' - 7"

1' -1

0" 4"

EXJ02

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key PlanCONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R

ES

D

AT

IB

S

IB

N

EN

C

C

LC

C

BN

C

BC

C

BS

PS

N

PV

N

PV

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E on e ei gh th in ch o ne fo ot

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

6/ 5/

:5

4:

P M

C :\R ev it

Lo ca l F ile s\

AS

-C

EN

TR

AL

_M in ja e.

Ki m

.rv t

03.AS.105-A

ROOF LEVEL PLAN - AREA A

DIAGNOSTIC AND TREATMENT

08/31/2012

1/8" = 1'-0"1 ROOF LEVEL PLAN - AREA A

0' 4' 8' 16' 32'0' 4' 8' 16' 32'

NORTH

A

B

CDI No.12 08/31/2012 JSI No. 038 10/26/2012 JSI No. 041 11/16/2012 JSI No. 044 12/19/2012 JSI No. 084 04/24/2014 JSI No. 091 06/05/2014

1/8" = 1'-0"2 ROOF PLAN - ST1

B

C

D

E

F

G

H

7.5

03.AS.301

03.AS.301

03.AS.301

03.AS.301

03.AS.302

03.AS.302

SEE - 1/03.AS.105-A SEE - 1/03.AS.105-A

RG.5 03

RG 03

RF.5 03

RF 03

RE.5

RD.5

RC.5

RD

RC

RB.5

RB

RA

R1

A

32'-0"32'-0"32'-0"32'-0"32'-0"32'-0"28'-0"

'-0

'-0

'-0

220'-0"

CLS

XX.AS.561

XX.AS.561

XX.AS.562

MP52A

MP52A

RS03

MP52A

MP52A

MP52

03.AS.105-B

03.AS.105-B

GRATING

RE: SS DWGS

LSP

BCT

179' - 10"

180' - 9"

179' - 10"

180' - 9"

179' - 8"

BCT

XX.AS.411

TYP

REMOVABLE

GUARD RAIL

DN

TRIM AND SEAL

AROUND DAVIT BASE, TYP

DB

RD & OFD REF TO

15/XX.AS.562 AND PLUMBING DWGS

ROOFING SYSTEM LEGEND

CODE

RS01

DESCRIPTION

RUBBERIZED ASPHALT GREEN

ROOF SYSTEM

RS02

RS03

RUBBERIZED ASPHALT PAVER

ROOF SYSTEM

RUBBERIZED ASPHALT PAVER

ROOF AT PV PANELS

RS11

PVC ROOFING SYSTEM NON-

INSULATED

DAVIT BASE

RS21

DB

CLS CONTINUOUS LIFE LINE SYSTEM

BMRS BUILDING MAINTENANCE

RAIL SYSTEM

PERMANENTLY FIXED ROTATING

DAVITSDLP

PVC ROOFING SYSTEM

INSULATED ON CONCRETE DECKRS22

ROOF HATCHROH01

PVC ROOFING SYSTEM

INSULATED ON METAL DECKRS23

DUAL VERTICAL RAILS FOR

ROLLING SOCKET

SIMULATED-METAL PVC

ROOFING

RS01-A RUBBERIZED ASPHALT GREEN

ROOF SYSTEM

LSP

BCT

CONTINUOUS LIFELINE

SUPPORT PEDESTALS

BOSUN CHAIR / SAFETY

TIEBACKS

EXTENT OF SNOW MELT SYSTEM,

REFER TO 11/XX.AS.562 FOR DET

DVR

GENERAL NOTES

1. FOR ROOF PENETRATION DETAILS REFER TO DETAILS 1 THROUGH 4 ON

XX.AS.562

2. FOR BUILDING MAINTENANCE & FALL PROTECTION SYSTEM DETAILS

REFER TO DETAILS 5 THROUGH 7 ON XX.AS.562

3. FOR LIGHTNING PROTECTION ROD DETAIL REFER TO DETAIL 8 ON

XX.AS.562

4. FOR CONCOURSE STANDING SEAM LAYOUT REFER TO PARTIAL ROOF

PLAN 3 ON XX.AS.104-B

5. FOR PVC ROOFING SYSTEM PROVIDE 6" MINIMUM TAPERED INSULATION

WITH 2% MINIMUM SLOPE TO DRAIN.

6. ALL SOUTH ELEVATION SUPER-RIB WALL OPENING HEIGHT TO BE 11'-

10" (SILL HEIGHT 4' 8" FROM PENTHOUSE LEVEL), UNLESS NOTED

OTHERWISE

7. FOR LOUVER SIZES REFER TO PLANS AND ELEVATIONS. TOP HEIGHT OF

LOUVERS TO ALIGN AT 17' 6" ABOVE PENTHOUSE LEVEL, UNLESS

NOETED OTHERWISE

C

D

7.5

4" 24'-8" 7'-4"

7' -7

/8

1'

-7

4"

176' - 7" 176' - 7"

RS23

176' - 10"

XX.AS.563

SIM

EXJ02

H

6'-3 7/8" 3'-5 3/4"

'-8

/2

5'

-5

/4

RS23

170' - 0"

169' - 9"

XX.AS.563

SIM

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key PlanCONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R

ES

D

AT

IB

S

IB

N

EN

C

C

LC

C

BN

C

BC

C

BS

PS

N

PV

N

PV

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E on e ei gh th in ch o ne fo ot

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

6/ 5/

:5

5:

P M

C :\R ev it

Lo ca l F ile s\

AS

-C

EN

TR

AL

_M in ja e.

Ki m

.rv t

03.AS.105-B

ROOF LEVEL PLAN - AREA B

DIAGNOSTIC AND TREATMENT

08/31/2012

1/8" = 1'-0"1 ROOF LEVEL PLAN - AREA B

0' 4' 8' 16' 32'0' 4' 8' 16' 32'

NORTH

A

B

CDI No.12 08/31/2012 JSI No. 038 10/26/2012 JSI No. 044 12/19/2012 JSI No. 084 04/24/2014 JSI No. 091 06/05/2014

1/8" = 1'-0"3 ROOF PLAN - ELEVATOR

1/8" = 1'-0"2 ROOF PLAN - ST5

UP

UP

B

C

D

E

F

G

H

J

7.5

4.6

A

MATCHLINE AREA A

MATCHLINE AREA B

L L

1 1

L

L

TO CONCOURSE

L L L L L L L L L L L L L

L

L

LL

L

L

L L L L L

L

L

L

L

L

L

L

L

L

L

L

L

L L L L

L

L

L

L L

L L L

L

L

L

L

L

L L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L L

L

L

L

L

L

L

L

TO CONCOURSE

L

L L

L L

L

L

L

L

TO CONCOURSE

5L

L

L

L

L

L

L

L

L

L

L

LLLLLLLLL

L L L L L L L L L L L L L L L L

L L L L L L L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

03-NLP2-2,4

03-NLP7-2,4

WP

WP

WP

WPWP2WPWP

WP

WP WP

WP

03-NL37-9,11,13

03-NL35-43,45,47

WP

03-NL32-52,54,56

03-NL33-56,58,60

PHOTOVOLTAIC COLLECTOR PANEL (TYPICAL)

L L

L L

L L

L L

L L

L L

L L

L L

L L

PHOTOVOLTAIC COLLECTOR PANEL (TYPICAL)

L

L

FLAG NOTES:

PROVIDE #4/0 AWG BARE TINNED COPPER LIGHTNING

PROTECTION DOWNLEAD. REFER TO DETAILS FOR ROOF

PENETRATION AND REQUIREMENTS FOR CONNECTION TO

BUILDING STEEL.

PROVIDE U.L. MASTER LABELED LIGHTNING PROTECTION

SYSTEM WITH CLASS 2 MATERIALS PER SPECIFICATION.

NOT USED.

PROVIDE MONOCRYSTALLINE PHOTOVOLTAIC ARRAY ON THE

ROOF OF THE PENTHOUSE. THE LAYOUT SHOWN INDICATES

DESIGN INTENT ONLY. REFER TO THE SPECIFICATION FOR

MORE INFORMATION.

PROVIDE BONDING BETWEEN THE LIGHTNING PROTECTION

SYSTEM AND THE PHOTOVOLTAIC RACKING, TYPICAL FOR ALL

RACKING.

PROVIDE L15-30R INSTALLED AT CANOPY LEVEL. REFER TO

MOUNTING DETAIL ON TRACTEL SHOP DRAWINGS FOR

INSTALLATION REQUIREMENTS. PROVIDE (3-#10, 1-#10G)-3/4"C

TO CIRCUITS INDICATED.

(NOT ALL FLAG NOTES USED ON THIS SHEET)

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R E

S

D A

T

I B

S

I B

N

E N

C

C L C

C B

N

C B

C

C B

S

P S

N

P V

N

P V

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E o n e q u a rt e r in c h o n e f o o t

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

/5

/2

:5 :1

P

M D

R e v it L o c a l F ile s \2

\E

S -D

A T

N

W o n d e l.

rv t

03.ES.405-A

ROOF LEVEL ELECTRICAL PLAN

(NORTH)

DIAGNOSTIC AND TREATMENT

08/31/2012

A

B

NORTH

0' 4' 8' 16' 32' 1/8" = 1'-0"1

ROOF LEVEL POWER PLAN

(NORTH)

CDI No.12 08/31/2012

RFI No. 2503 09/17/2013

JSI No. 090 06/05/2014

R1

R2

A

B

C

D

E

F

G

H

J

RA

RB

RC

RE

RF

RH

RJ

RD

04.AS.301

04.AS.301

K

04.AS.301

04.AS.301

2' -1

0"

'-3

'-6

2'-9"12'-6"21'-7 1/2"35'-0"35'-0"35'-0"35'-0"35'-0"35'-0"35'-0"

RG

CLS

XX.AS.562

XX.AS.561

XX.AS.561

XX.AS.561

XX.AS.561

XX.AS.561

04.AS.301

04.AS.301

MP52

RS03

MP52A

MP52A

MP52A

MP52

MP52A

XX.AS.563

7" 9'-9"

'-0

'-6

RS02

SMOKE VENT

ROOF HOOD

RE: MH DWGS

179' - 11" 180' - 9"

180' - 9"

179' - 11" 180' - 9"

179' - 11" 180' - 9"

179' - 11"

REMOVABLE

GUARD RAIL

GRATING

RE: SS DWGS

RS23

9"

8' -0

2'

-0

LSP

DN

DB

TRIM AND SEAL

AROUND DB, TYP 12

XX.AS.411

TYP

5 5/8" 3 3/8"

XX.AS.563

180' - 0" 179' - 2"

OVERFLOW

SCUPPER

LOW POINT

5'-4"

1' -6

XX.AS.563

SIM

RD & OFD REF TO

15/XX.AS.562 AND PLUMBING DWGS

ROOFING SYSTEM LEGEND

CODE

RS01

DESCRIPTION

RUBBERIZED ASPHALT GREEN

ROOF SYSTEM

RS02

RS03

RUBBERIZED ASPHALT PAVER

ROOF SYSTEM

RUBBERIZED ASPHALT PAVER

ROOF AT PV PANELS

RS11

PVC ROOFING SYSTEM NON-

INSULATED

DAVIT BASE

RS21

DB

CLS CONTINUOUS LIFE LINE SYSTEM

BMRS BUILDING MAINTENANCE

RAIL SYSTEM

PERMANENTLY FIXED ROTATING

DAVITSDLP

PVC ROOFING SYSTEM

INSULATED ON CONCRETE DECKRS22

ROOF HATCHROH01

PVC ROOFING SYSTEM

INSULATED ON METAL DECKRS23

DUAL VERTICAL RAILS FOR

ROLLING SOCKET

SIMULATED-METAL PVC

ROOFING

RS01-A RUBBERIZED ASPHALT GREEN

ROOF SYSTEM

LSP

BCT

CONTINUOUS LIFELINE

SUPPORT PEDESTALS

BOSUN CHAIR / SAFETY

TIEBACKS

EXTENT OF SNOW MELT SYSTEM,

REFER TO 11/XX.AS.562 FOR DET

DVR

GENERAL NOTES

1. FOR ROOF PENETRATION DETAILS REFER TO DETAILS 1 THROUGH 4 ON

XX.AS.562

2. FOR BUILDING MAINTENANCE & FALL PROTECTION SYSTEM DETAILS

REFER TO DETAILS 5 THROUGH 7 ON XX.AS.562

3. FOR LIGHTNING PROTECTION ROD DETAIL REFER TO DETAIL 8 ON

XX.AS.562

4. FOR CONCOURSE STANDING SEAM LAYOUT REFER TO PARTIAL ROOF

PLAN 3 ON XX.AS.104-B

5. FOR PVC ROOFING SYSTEM PROVIDE 6" MINIMUM TAPERED INSULATION

WITH 2% MINIMUM SLOPE TO DRAIN.

6. ALL SOUTH ELEVATION SUPER-RIB WALL OPENING HEIGHT TO BE 11'-

10" (SILL HEIGHT 4' 8" FROM PENTHOUSE LEVEL), UNLESS NOTED

OTHERWISE

7. FOR LOUVER SIZES REFER TO PLANS AND ELEVATIONS. TOP HEIGHT OF

LOUVERS TO ALIGN AT 17' 6" ABOVE PENTHOUSE LEVEL, UNLESS

NOETED OTHERWISE

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key PlanCONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R

ES

D

AT

IB

S

IB

N

EN

C

C

LC

C

BN

C

BC

C

BS

PS

N

PV

N

PV

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E on e ei gh th in ch o ne fo ot

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

6/ 5/

:5

7:

P M

C :\R ev it

Lo ca l F ile s\

AS

-C

EN

TR

AL

_M in ja e.

Ki m

.rv t

04.AS.105

ROOF LEVEL PLAN

INPATIENT BUILDING (SOUTH)

08/31/2012

1/8" = 1'-0"1 ROOF LEVEL PLAN

0' 4' 8' 16' 32'0' 4' 8' 16' 32'

NORTH

CDI No.12 08/31/2012 JSI No. 038 10/26/2012 JSI No. 044 12/19/2012 JSI No. 084 04/24/2014

A

A

B

B

C

C

D

D

E

E

F

F

G

G

H

H

J

J

R1

R1

R2

R2

RJ

RJ

RH

RH

RG

RG

RF

RF

RE

RE

RC

RC

RB

RB

RA

RA

K

K 04

RD

RD

666 6 6

L L L L L

L L L L L L

L

L L L

L L

L

L

L

L

L

L

L

L

L

L

LLL

L

L

L

L

L L

L L

L

(TYP)

(TYP)

(TYP)

L

L

L

L

L

L

L

L

L

LL

L

L

L

L

L

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP) 4

(TYP)

(TYP)

(TYP)

(3)4"C 4

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

L

LLL

L

L

L

L

L L

(TYP)

L

LLLLLLLLLLLLLL

L L

L L

L L

L

(TYP.)

(TYP.)

L

L"04-EF-5"

"04-EF-6"

BOND TO

STACK

L

(TYP.)L

BOND TO

"04-EF-07"

STACK

"04-EF-3"

"04-EF-4"

BOND TO

STACK

L

L

"04-EF-2" L

BOND TO

STACK

L

"04-EF-08"

BOND TO

STACK

"04-EF-1"

L

L

(TYP)

04-NLP1-20

WP

WP

WP

WP

WPWPWPWP

WP

04-NLP1-22

(TYP.)

L

04-NLP1-26,28,30

12 12

04-NLP2-1,3,5

PHOTOVOLTAIC COLLECTOR PANEL (TYPICAL)

L L

L

L L

L L

L L

L L

L L

L L

L L

L

L

L

FLAG NOTES:

EXTEND CONDUIT DOWN TO P4 INVERTERS IN MAIN ELECTRICAL

ROOM LOCATED ON PENTHOUSE LEVEL. COORDINATE EXACT

LOCATION OF ROOF PENETRATION WITH EQUIPMENT PROVIDED.

NOT USED.

INSTALL AIR TERMINAL TO METAL STRUCTURE. TERMINALS AT THIS

LOCATION SHALL BE ALUMINUM TO PREVENT CORROSION BETWEEN

DISSIMILAR METALS. COORDINATE TERMINAL MATERIAL WITH

ARCHITECTURAL AND STRUCTURAL CONSTRUCTION DOCUMENTS.

ROUTE #4/0 BRAIDED CABLING ACROSS STEEL STRUCTURE TO

PENTHOUSE PERIMETER WALL AND DOWN TO AIR TERMINAL AT

PARAPET BELOW (DETAIL NOTE 7). REFER TO ARCHITECTURAL

SECTIONS AND ELEVATIONS FOR ADDITIONAL INFORMATION.

COORDINATE MATERIAL WITH STRUCTURAL BUILDING COMPONENTS

TO AVOID CORROSION BETWEEN DISSIMILAR METALS.

PROVIDE #4/0 AWG BARE TINNED COPPER DOWN LEAD. CADWELD

DOWN LEAD CONDUCTOR TO STEEL COLUMN WITH CAD WELDED

BONDING JUMPERS AT ALL COLUMN JOINTS THROUGH BUILDING TO

GRADE FOR CONNECTION TO DRIVEN GROUND RODS. INSTALL PVC

CONDUIT AT BOTTOM OF COLUMN FOR ROUTING DOWN LEAD OUT TO

GROUND ROD LOCATION TO ELECTRICAL SITE PLAN FOR GROUND

ROD LOCATIONS.

LOCATED AT PARAPET WALL BELOW ROOF STRUCTURE. REFER TO

ARCHITECTURAL SECTIONS AND ELEVATIONS FOR DETAILS.

PROVIDE U.L. MASTER LABELED LIGHTING PROTECTION SYSTEM WITH

CLASS 2 MATERIALS PER SPECIFICATIONS.

PROVIDE #4/0AWG BRAIDED BARE TINNED LIGHTING PROTECTION

MAIN CONDUCTOR. COORDINATE MATERIAL WITH STRUCTURAL

ELEMENTS TO PREVENT CORROSION OF DISSIMILAR METALS.

COPPER CONDUCTOR SHALL BE USED IN ALL AREAS WHERE

CONDUCTOR WILL NOT COME IN CONTACT WITH OTHER METALS.

PROVIDE BONDING BETWEEN THE LIGHTNING PROTECTION SYSTEM

AND THE PHOTOVOLTAIC RACKING SYSTEM (TYPICAL FOR ALL

RACKING).

PROVIDE BUILDING INTEGRATED PHOTOVOLTAIC ARRAY. THE

LAYOUT SHOWN INDICATES DESIGN INTENT ONLY. REFER TO THE

SPECIFICATIONS FOR ADDITIONAL INFORMATION/REQUIREMENTS.

NEMA L15-30P INSTALLED AT PARAPET. REFER TO MOUNTING DETAIL

ON TRACTEL SHOP DRAWINGS FOR INSTALLATION REQUIREMENTS.

PROVIDE (3-#10; 1-#10G) IN 3/4" CONDUIT TO CIRCUIT INDICATED.

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R E

S

D A

T

I B

S

I B

N

E N

C

C L C

C B

N

C B

C

C B

S

P S

N

P V

N

P V

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E o n e e ig h th i n c h o n e f o o t

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

/5

/2

:5

:5

A

M D

R e v it L o c a l F ile s \2

\E

S -I

B S

L A ra m b u la

.r v t

04.ES.405

ROOF LEVEL ELECTRICAL/LIGHTNING

PROTECTION PLAN

INPATIENT BUILDING (SOUTH)

08/31/2012

1/8" = 1'-0"1

ROOF LEVEL

ELECTRICAL/LIGHTNING

PROTECTION PLAN

NORTH

0' 4' 8' 16' 32'

CDI No.12 08/31/2012

RFI 2503 09/19/2013

D

J

H

G

F

E

D

C

B

A

RG

RH

RJ

RF

RE

RD

RC

RB

RA

R2

R1

05.AS.201

05.AS.201

05.AS.201

05.AS.301

05.AS.301

05.AS.301

05.AS.301

K

05.AS.202

2'-9"12'-6"21'-7 1/2"35'-0"35'-0"35'-0"35'-0"35'-0"35'-0"35'-0"

2' -1

0"

'-3

'-6

CLS

XX.AS.561

XX.AS.562

XX.AS.561

XX.AS.561

XX.AS.561

XX.AS.561

MP52A

RS03

MP52A

MP52A

MP52

9'-9"7"

'-0

'-7

/4

RS02

XX.AS.563

SMOKE VENT

ROOF HOOD

RE: MH DWGS

LSP

179' - 11" 180' - 9"

179' - 11" 180' - 9" 179' - 11" 180' - 9"

179' - 10"

XX.AS.411

DB

TRIM AND SEAL

AROUND DB, TYP.

GRATING

RE: SS DWGS

REMOVABLE

GUARD RAIL

DN

LSP

RS23

180' - 0"

5 5/8" 3 3/8" 9"

179' - 2"

2' -0

8'

-0

5'-4"

1' -6

LOW POINT

OVERFLOW

SCUPPER17

XX.AS.563

XX.AS.563

SIM

RD & OFD REF TO

15/XX.AS.562 AND PLUMBING DWGS

ROOFING SYSTEM LEGEND

CODE

RS01

DESCRIPTION

RUBBERIZED ASPHALT GREEN

ROOF SYSTEM

RS02

RS03

RUBBERIZED ASPHALT PAVER

ROOF SYSTEM

RUBBERIZED ASPHALT PAVER

ROOF AT PV PANELS

RS11

PVC ROOFING SYSTEM NON-

INSULATED

DAVIT BASE

RS21

DB

CLS CONTINUOUS LIFE LINE SYSTEM

BMRS BUILDING MAINTENANCE

RAIL SYSTEM

PERMANENTLY FIXED ROTATING

DAVITSDLP

PVC ROOFING SYSTEM

INSULATED ON CONCRETE DECKRS22

ROOF HATCHROH01

PVC ROOFING SYSTEM

INSULATED ON METAL DECKRS23

DUAL VERTICAL RAILS FOR

ROLLING SOCKET

SIMULATED-METAL PVC

ROOFING

RS01-A RUBBERIZED ASPHALT GREEN

ROOF SYSTEM

LSP

BCT

CONTINUOUS LIFELINE

SUPPORT PEDESTALS

BOSUN CHAIR / SAFETY

TIEBACKS

EXTENT OF SNOW MELT SYSTEM,

REFER TO 11/XX.AS.562 FOR DET

DVR

GENERAL NOTES

1. FOR ROOF PENETRATION DETAILS REFER TO DETAILS 1 THROUGH 4 ON

XX.AS.562

2. FOR BUILDING MAINTENANCE & FALL PROTECTION SYSTEM DETAILS

REFER TO DETAILS 5 THROUGH 7 ON XX.AS.562

3. FOR LIGHTNING PROTECTION ROD DETAIL REFER TO DETAIL 8 ON

XX.AS.562

4. FOR CONCOURSE STANDING SEAM LAYOUT REFER TO PARTIAL ROOF

PLAN 3 ON XX.AS.104-B

5. FOR PVC ROOFING SYSTEM PROVIDE 6" MINIMUM TAPERED INSULATION

WITH 2% MINIMUM SLOPE TO DRAIN.

6. ALL SOUTH ELEVATION SUPER-RIB WALL OPENING HEIGHT TO BE 11'-

10" (SILL HEIGHT 4' 8" FROM PENTHOUSE LEVEL), UNLESS NOTED

OTHERWISE

7. FOR LOUVER SIZES REFER TO PLANS AND ELEVATIONS. TOP HEIGHT OF

LOUVERS TO ALIGN AT 17' 6" ABOVE PENTHOUSE LEVEL, UNLESS

NOETED OTHERWISE

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key PlanCONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R

ES

D

AT

IB

S

IB

N

EN

C

C

LC

C

BN

C

BC

C

BS

PS

N

PV

N

PV

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E on e ei gh th in ch o ne fo ot

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

6/ 5/

:5

8:

P M

C :\R ev it

Lo ca l F ile s\

AS

-C

EN

TR

AL

_M in ja e.

Ki m

.rv t

05.AS.105

ROOF LEVEL PLAN

INPATIENT BUILDING (NORTH)

08/31/2012

1/8" = 1'-0"1 ROOF LEVEL PLAN

0' 4' 8' 16' 32'0' 4' 8' 16' 32'

NORTH

CDI No.12 08/31/2012 JSI No. 038 10/26/2012 JSI No. 044 12/19/2012 JSI No. 084 04/24/2014

UPUP

FLAG NOTES:

EXTEND CONDUIT DOWN TO P4 INVERTERS IN MAIN ELECTRICAL

ROOM LOCATED ON PENTHOUSE LEVEL. COORDINATE EXACT

LOCATION OF ROOF PENETRATION WITH EQUIPMENT PROVIDED.

NOT USED.

INSTALL AIR TERMINAL TO METAL STRUCTURE. TERMINALS AT

THIS LOCATION SHALL BE ALUMINUM TO PREVENT CORROSION

BETWEEN DISSIMILAR METALS. COORDINATE TERMINAL

MATERIAL WITH ARCHITECTURAL AND STRUCTURAL

CONSTRUCTION DOCUMENTS.

ROUTE #4/0 BRAIDED CABLING ACROSS STEEL STRUCTURE TO

PENTHOUSE PERIMETER WALL AND DOWN TO AIR TERMINAL AT

PARAPET BELOW (DETAIL NOTE 7). REFER TO ARCHITECTURAL

SECTIONS AND ELEVATIONS FOR ADDITIONAL INFORMATION.

COORDINATE MATERIAL WITH STRUCTURAL BUILDING

COMPONENTS TO AVOID CORROSION BETWEEN DISSIMILAR

METALS.

PROVIDE #4/0 AWG BARE TINNED COPPER DOWN LEAD. CADWELD

DOWN LEAD CONDUCTOR TO STEEL COLUMN WITH CAD WELDED

BONDING JUMPERS AT ALL COLUMN JOINTS THROUGH BUILDING

TO GRADE FOR CONNECTION TO DRIVEN GROUND RODS.

INSTALL PVC CONDUIT AT BOTTOM OF COLUMN FOR ROUTING

DOWN LEAD OUT TO GROUND ROD LOCATION TO ELECTRICAL

SITE PLAN FOR GROUND ROD LOCATIONS.

LOCATED AT PARAPET WALL BELOW ROOF STRUCTURE. REFER

TO ARCHITECTURAL SECTIONS AND ELEVATIONS FOR DETAILS.

PROVIDE U.L. MASTER LABELED LIGHTING PROTECTION SYSTEM

WITH CLASS 2 MATERIALS PER SPECIFICATIONS.

PROVIDE #4/0AWG BRAIDED BARE TINNED LIGHTING PROTECTION

MAIN CONDUCTOR. COORDINATE MATERIAL WITH STRUCTURAL

ELEMENTS TO PREVENT CORROSION OF DISSIMILAR METALS.

COPPER CONDUCTOR SHALL BE USED IN ALL AREAS WHERE

CONDUCTOR WILL NOT COME IN CONTACT WITH OTHER METALS.

PROVIDE BONDING BETWEEN THE LIGHTNING PROTECTION

SYSTEM AND THE PHOTOVOLTAIC RACKING SYSTEM (TYPICAL

FOR ALL RACKING).

PROVIDE MONOCRYSTALLINE PHOTOVOLTAIC ARRAY ON THE

ROOF OF THE PENTHOUSE. THE LAYOUT SHOWN INDICATES

DESIGN INTENT ONLY. REFER TO THE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

NEMA L15-30P INSTALLED AT PARAPET. REFER TO MOUNTING

DETAIL ON TRACTEL SHOP DRAWINGS FOR INSTALLATION

REQUIREMENTS.

(NOT ALL FLAG NOTES USED ON THIS SHEET)

A

A

B

B

C

C

D

D

E

E

F

F

G

G

H

H

J

J

R1

R1

R2

R2

RE

RE

RF

RF

RG

RG

RH

RH

RJ

RJ

RC

RC

RB

RB

RA

RA

RD

RD

K

K

(3) 4"C

L L L L L L L L L L L L L L L

6 6

(TYP)

(TYP)

L

L L

L

L

L

L

L

L

L

L

L

L

L

LL

L

L

L

L

L

L

L

L

L L L L

L

L

L

L

L

L

L

L

(TYP)

L

L

L

L

L

(TYP)

(TYP)

(TYP)

4(TYP)

11 (TYP)

L

L

L

L

L L

L

L L

L

L

L

L L L

L

L

L

L

L

L

L

L

L L L L L L L L L L L L L L

L

L

L

L

L

L

L

L

L

L

L

L

LLL

"05-EF-2"

BOND TO STACK

"05-EF-1"

(TYP)

"05-EF-4"

"05-EF-3"

"05-EF-8"

"05-EF-7"

"05-EF-6"

BOND TO STACKBOND TO STACK

10 (TYP)

11(TYP)

05-NLP1-7

WP

WP

WP

WP

WP

WP

WP

WP WP

05-NL32-88,90,92

05-NL31-84,86,88

05-NLP1-6

PHOTOVOLTAIC COLLECTOR PANEL (TYPICAL)

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R E

S

D A

T

I B

S

I B

N

E N

C

C L C

C B

N

C B

C

C B

S

P S

N

P V

N

P V

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E o n e e ig h th i n c h o n e f o o t

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

/5

/2

:1

:0

A

M D

R e v it L o c a l F ile s \2

\E

S -I

B N

L A ra m b u la

.r v t

05.ES.405

ROOF LEVEL ELECTRICAL/LIGHTNING

PROTECTION PLAN

INPATIENT BUILDING (NORTH)

08/31/2012

1/8" = 1'-0"1

ROOF LEVEL

ELECTRICAL/LIGHTNING

PROTECTION PLAN

0' 4' 8' 16' 32'

NORTH

CDI No.12 08/31/2012

RFI 2503 09/19/2013

RFI 3229a 02/24/2014

DN

DN

J J J J

J J J J

J J J J

J

J J J J

JJJ

J

2000KVA

XFMR

15KV MV15KV MV

TEMP GEN

TAP BOX

2000KVA

XFMR

GA1,GA2 GA3,GA4

XFMR

GEN #1 GEN #2

UTILITY #1

TIE

UTILITY #2

GEN #3 GEN #4

GEN #5

(FUTURE)

GB1,GB2 GB3,GB4

800 GAL. DAY

TANK

800 GAL.DAY

TANK 800 GAL. DAY

TANK

800 GAL. DAY

TANK

CONTROL

SHORE

POWER

JACKET

HEATER

JACKET

HEATER

JACKET

HEATER

JACKET

HEATER

BATTERY

CHARGER

BATTERY

CHARGER

BATTERY

CHARGER

BATTERY

CHARGER

MASTER

GRAPHIC

PANEL

GEN #1

GEN #2

GEN #3

GEN #4

FUTURE GEN

#5

F

G

H

J

K

L

M

FUTURE 800

GAL. DAY

TANK

06-HWUH-1

06-HWUH-2 06-HWUH-3 06-HWUH-5

06-HWUH-4

GEN-5

FUTURE

GEN INTAKE

LOUVER

GEN INTAKE

LOUVER

GEN INTAKE

LOUVER

GEN INTAKE

LOUVER

JACKET

HEATER

JACKET

HEATER

JACKET

HEATER

JACKET

HEATER

06 - GEN 1 06 - GEN 2 06 - GEN 3 06 - GEN 4

1 1 1 1

+40"

+40"

+40"

+40"

+40" +40"

+40"

+40"+40"

+40"

11 11 11 11 11

06-APH1106-EQL11-24

06-FCU-2

06-EQH11-8

06-FCU-5

06-EQH12-8

SUBSTATION

"06-EMDCP1"

GENERATOR

PARALLELING

GEAR

+40" +40" +40"

+40"

+40"

+40"+40"+40"+40"

+40"

+40"

+40"

+40" +40"

+40"

+40"

CONTROL

SHORE

POWER

PARALEL

SWITCHGEAR

MASTER

CONTROL

EQUIPMENT

LOAD BANK

06-APL11

06-APL11-28

06-APL11-8,10

06-APL11-7,9

06-APL11-16,18

06-APL11-15,17

06-APL11-30 06-APL11-29

06-APL11-11,13

06-APL11-12,14

06-APL11-24

06-APL11-37,39

06-APL11-23,25

06-EQL11-21

06-EQL11-20

06-HWUH-6

06-EQL11-12

06-NL11-38

06-EQL11-22,29

06-NL11-40

06-APL11-2 06-APL11-27 06-APL11-22 06-APL11-21

06-EQL12-6

06-EQL13-11

06-EQL13-12

23 23 23 23

BATT HTR BATT HTR BATT HTR BATT HTR

06-APL11-31 06-APL11-26

06-APL11-20 06-APL11-1906-11-F2-E10

GENERATOR RM 06-11-F2-E11

GENERATOR RM

06-11-F2-E12

GENERATOR RM,

FUTR

06-11-F2-E13

TAP BOX SUB

06-11-F2-E16

MECH

06-11-V3

VEST

06-11-ST3

STAIR

06-RWP-406-RWP-306-RWP-206-RWP-1

06-APH11-61,63,65

06-APH11-67,69,71 06-APH11-73,75,77

06-APH11-79,81,83

06-APH11-55,57,59

(PARTIAL)

(PARTIAL)

06-APH11-55,57,59

06-APH11-55,57,59

(PARTIAL)

(PARTIAL)

06-APH11-55,57,59

3906-APL11-33,35

06-APL11-45,47

06-APL11-38,40 06-APL11-42,44

RFI 7195 RFI 7195 RFI 7195

RFI 7195

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R E

S

D A

T

I B

S

I B

N

E N

C

C L C

C B

N

C B

C

C B

S

P S

N

P V

N

P V

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

/2

/2

:1 :3

P

M D

R e v it L o c a l F ile s \2

\E

S -E

N C

J B a rr o w

.r v t

06.ES.402-B2

LEVEL 1 ELECTRICAL POWER PLAN

(SOUTHEAST)

ENERGY CENTER

06/15/2012

1/4" = 1'-0"1

LEVEL 1 ELECTRICAL EQUIPMENT

PLAN (SOUTHEAST)

0' 2' 4' 8' 16'

NORTH

FLAG NOTES:

PROVIDE BREAK GLASS STYLE EMERGENCY POWER OFF BUTTON TO SHUT

DOWN GENERATOR IN CASE OF EMERGENCY. PROVIDE LABEL/SIGNAGE TO

INDICATE BUTTON SHUTS DOWN GENERATOR, LABEL TO BE WHITE LETTERS ON

RED BACKGROUND.

CORD-REEL RECEPTACLE, SEE DETAIL FOR ADDITIONAL REQUIREMENTS.

PROVIDE 10#14AWG CONDUCTORS AND 3 BELDON 878 CABLES FROM PARALLEL

SWITCHGEAR WITH 50'-0" OF SLACK COILED IN TAP BOX FOR CONTROLS

WIRING. PROVIDE NUMBERED LABELS ON EACH END OF CONDUCTORS.

PROVIDE CEILING MOUNTED OUTLET FOR PROJECTOR.

PROVIDE TWO (2) 125VDC SHORE BATTERY POWER CABINETS WITH INTEGRAL

DISTRIBUTION FOR POWER TO MEDIUM VOLTAGE SWITCHGEAR. UNITS SHALL

BE EQUIPPED WITH INTEGRAL 3 STAGE BATTERY CHARGER AND VRLA

BATTERIES. PROVIDE 150 AMP-HR BATTERY CAPACITY. PROVIDE #10 WIRING

FROM EACH CABINET TO EACH BREAKER IN THE SWITCHGEAR LINE-UP FOR

BEST BATTERY REDUNDANCY.

PROVIDE TEMPORARY GENERATOR TAP BOX CONNECTION, SEE DETAIL FOR

REQUIREMENTS.

PROVIDE A 120V, 20A1P ENCLOSED CIRCUIT BREAKER CAPABLE OF BEING

LOCKED IN THE OPEN POSITION FOR THE BRANCH CIRCUIT SUPPLYING THE

ELEVATOR CAB LIGHTS, RECEPTACLE, AND VENTILATION SYSTEM..

PROVIDE #4/0 AWG BARE TINNED COPPER LIGHTNING PROTECTION DOWNLEAD.

REFER TO DETAILS FOR ROOF PENETRATION AND REQUIREMENTS FOR

CONNECTION TO BUILDING.

PROVIDE U.L. MASTER LABELED LIGHTNING PROTECTION SYSTEM WITH CLASS 2

MATERIALS PER SPECIFICATION. BOND ALL ROOFTOP MECHANICAL EQUIPMENT

AND STACKS.

PROVIDE #4/0 AWG BARE TINNED COPPER LIGHTNING PROTECTION MAIN

CONDUCTOR.

PROVIDE INTEGRAL SILENCER AND CATALYTIC OXIDIZER. PROVIDE SUPER

CRITICAL SILENCER WITH 90% THC REDUCTION CATALYST OXIDIZER.

PROVIDE EMERGENCY BOILER POWER OFF SWITCH, SWITCH SHALL BE

MUSHROOM HEAD TYPE, BE CLEARLY LABELED AS "EMERGENCY BOILER

SHUTOFF" SURFACE MOUNT, BRIGHT YELLOW COLORED AND HAVE A SUITABLE

CLEAR COVER TO PROTECT FROM ACCIDENTAL SHUT-OFF. SWITCH SHALL BE

24V AND WIRED TO BOILER CONTROLLER, COORDINATE WITH MECHANICAL

CONTROLS CONTRACTOR.

REFER TO GENERATOR CONTROL WIRING DIAGRAM FOR ADDITIONAL

REQUIREMENTS.

PROVIDE CONDUIT AND WIRING TO FIRE PUMP ANNUNCIATOR IN CONTROL

ROOM, COORDINATE WITH DIV. 21 FOR REQUIREMENTS.

PROVIDE EMERGENCY CHILLER POWER OFF SWITCH, SWITCH SHALL BE

MUSHROOM HEAD TYPE, BE CLEARLY LABELED AS "EMERGENCY CHILLER

SHUTOFF" SURFACE MOUNT, BRIGHT YELLOW COLORED AND HAVE A SUITABLE

CLEAR COVER TO PROTECT FROM ACCIDENTAL SHUT-OFF. SWITCH SHALL BE

24V AND WIRED TO CHILLER CONTROLLER AND BAS FOR EQUIPMENT SHUT

DOWN IN ROOM, COORDINATE WITH MECHANICAL CONTROLS CONTRACTOR.

PROVIDE EMERGENCY CHILLER ROOM EXHAUST SWITCH, SWITCH SHALL BE

MUSHROOM HEAD TYPE, BE CLEARLY LABELED AS "EMERGENCY CHILLER FAN

CONTROL" SURFACE MOUNT, BRIGHT YELLOW COLORED AND HAVE A SUITABLE

CLEAR COVER TO PROTECT FROM ACCIDENTAL SHUT-OFF. SWITCH SHALL BE

24V AND WIRED TO EXHAUST FAN CONTROLLER, COORDINATE WITH

MECHANICAL CONTROLS CONTRACTOR.

PROVIDE POWER FOR PTZ CAMERA, COORDINATE EXACT LOCATION WITH

SECURITY DRAWINGS.

PROVIDE GROUND BAR, SEE GROUND RISER FOR ADDITIONAL REQUIREMENTS.

SEE GROUND BAR DETAILS FOR MORE INFORMATION.

PROVIDE ABOVE THE COUNTER THE FOLLOWING OUTLETS FOR TESTING

EQUIPMENT: (1) NEMA 6-20R, (1) NEMA L15-30R, (1) L5-30R, AND (2) 5-20R,

CIRCUIT AS SHOWN.

PROVIDE 3 POINTS OF CONNECTION FOR WATER TREATMENT SYSTEM

GENERATOR, MEASUREMENT MODULE, AND GAS DETECTION.

PROVIDE CONDUIT AND WIRING FOR REMOTE LOAD BANK CONTROLLER.

COORDINATE WITH LOAD BANK MANUFACTURER FOR CONTROLS WIRING.

PROVIDE CONNECTION OF AUTOMATIC TRANSFER SWITCHES TO REMOTE

MONITORING PANEL AND FIBER CONNECTION TO CAMPUS ATS CONTROL LOOP.

REFER TO CAMPUS FIBER LOOP FOR GENERATOR REMOTE MONITORING PANELS

DETAIL FOR ADDITIONAL REQUIREMENTS.

PROVIDE STRUT RACK TO MOUNT BATTERY CHARGER DIRECTLY ADJACENT TO

BATTERIES.

MOUNT ELECTRICAL COMPONENTS FOR COOLING TOWERS TO STRUCTURAL

SUPPORT. PROVIDE POWER FOR VIBRATION SWITCH AND BASIN HEATER AS

SHOWN.

PROVIDE 120V HARD WIRED CONNECTION TO ALL WATER CLOSETS,

LAVATORIES, AND/OR URINALS IN THIS ROOM.

PROVIDE 120V POWER FOR MOTORIZED VALVES IN THE CHILLER PIPING

SYSTEM, COORDINATE WITH MECHANICAL FOR EXACT REQUIREMENTS.

PROVIDE POWER AND DISCONNECT FOR COOLING TOWER SUMP IMMERSION

HEATER, 40KW.

LOCATE ELEVATOR EQUIPMENT DISCONNECT WITHIN 18” OF LATCH SIDE OF

ELEVATOR MACHINE ROOM DOOR. PROVIDE 2#10 IN 3/4” CONDUIT FROM

ELEVATOR CONTROLLER TO ASSOCIATED ATS SERVING THE ELEVATOR FOR THE

PRE-TRANSFER SIGNAL RELAY.

SUMP PUMP 06-SP-03. COORDINATE CORD AND PLUG CONNECTION WITH DIV. 22

CONTRACTOR. MOUNT RECEPTACLE AT +40" AFF. UTILIZE WEATHERPROOF

JUNCTION BOXES AND COMPRESSION CONDUIT FITTINGS TO ACCOMPLISH

WIRING IN THIS SPACE.

MOUNT RECEPTACLE AT +40" AFF AND IN CLOSE PROXIMITY TO LADDER.

UTILIZE WEATHERPROOF JUNCTION BOXES AND COMPRESSION CONDUIT

FITTINGS TO ACCOMPLISH WIRING IN THIS SPACE.

STEAM CONDENSATE PUMP ASSEMBLY. PROVIDE 120V POWER CONNECTION TO

DUPLEX CONTROLLER. WIRING 2#10, 1#10 GND IN 3/4"C. RE: PANEL SHEDULE

FOR CIRCUIT BREAKER RATING. COORDINATE ROUGH-IN LOCATION WITH

DIVISION 23 CONTRACTOR.

PROVIDE 120V CONNECTION TO ELECTRICAL ACTUATOR(S) CONTROLLING

OPERATION OF SMOKE DAMPER.

PA MASS NOTIFICATION SYSTEM UPS. PROVIDE NEMA L5-30R TWIST-LOCK

RECEPTACLE MOUNTED TO UNISTRUT RACK ABOVE CABLE TRAY. PROVIDE 2#10,

1#10G., 3/4" CONDUIT TO PANEL. FIELD COORDINATE EXACT LOCATION WITH PA

MASS NOTIFICATION INSTALLER PRIOR TO ROUGH-IN.

FUEL OIL PUMP DUPLEX CONTROLLER. CONNECT 120V POWER AS SHOWN.

BULK STORAGE FUEL TANK LEVEL MONITOR AND LEAK DETECTION SYSTEM

PANEL. CONNECT 120V POWER AS SHOWN. FIELD COORDINATE EXACT

LOCATION.

FUEL CLEANING SYSTEM CONTROLLER WITH INTEGRAL DISCONNECT SWITCH.

CONNECT 120V POWER AS SHOWN. FIELD COORDINATE EXACT LOCATION.

REMOTE FILL STATION CONTROLLER WITH INTEGRAL DISCONNECT SWITCH.

CONNECT 120V POWER AS SHOWN. FIELD COORDINATE EXACT LOCATION.

DAY TANK INCOMING POWER. CONNECT 208V SINGLE-PHASE POWER AS

SHOWN. WIRING 2#12 PHASE CONDUCTORS, 1#12 NEUTRAL CONDUCTOR AND 1#

12 GROUND IN 3/4" CONDUIT.

FUEL OIL COOLING FAN. CONNECT 480V THREE-PHASE POWER AS SHOWN.

WIRING 3#12 PHASE CONDUCTORS, 1#12 GROUND IN 3/4" CONDUIT.

(NOT ALL FLAG NOTES USED ON THIS SHEET)

CDI No.10 06/15/2012

CDI No.12 08/31/2012

JSI No. 044 12/19/2012

JSI No. 081 04/03/2014

JSI No. 118 POSTED SET 03/16/2015

RFI 7195 - ES.X517 04/28/2015

RFI 7195

By Justin Krit at 7:49 am, Apr 29, 2015 jacqueline.cipriani Cloud jacqueline.cipriani Cloud jacqueline.cipriani Arrow jacqueline.cipriani Callout

VA RFI #4535 (KT RFI 5143)

Load bank controller rack to be adjacent to generator sync gear.

jacqueline.cipriani Text Box KT RFI #3059 / VA RFI #2825 - Generator outside air louver control shall be controlled by the generators only, and not through the DDC.

jacqueline.cipriani Arrow jacqueline.cipriani Arrow jacqueline.cipriani Arrow jacqueline.cipriani Arrow jacqueline.cipriani Text Box KT RFI #3059 / VA RFI #2825 - It is acceptable to utilize the unit heater thermostat for generator room cooling in lieu of duplicating thermostats.

jacqueline.cipriani Rectangle jacqueline.cipriani Cloud jacqueline.cipriani Rectangle jacqueline.cipriani Rectangle jacqueline.cipriani Cloud jacqueline.cipriani Rectangle jacqueline.cipriani Cloud jacqueline.cipriani Callout KT RFI #05443/VA #04843: Pnl: CP-AHU-3 & PSH500A Circuit: 06-EQL13-15 jacqueline.cipriani Callout KT RFI #05443/VA #04843: Pnl: 06-SLR-1G Circuit: 06-EQL13-15 jacqueline.cipriani Callout KT RFI #05443/VA #04843: Pnl: CP-006 Circuit: 06-EQL13-14

Josh.Gruning-PTR Text Box

KT RFI #8104:

A disconnecting means is required between the DC output of the battery rack and the battery selector. Contractor to request disconnect sizes and quantities from GE Zenith Controls.

Josh.Gruning-PTR Arrow

Josh.Gruning-PTR Snapshot

Josh.Gruning-PTR Cloud

Josh.Gruning-PTR Callout RFI #7767a:

Added hydrogen detector for batteries shall be similar to an EagleEye Power Solutions Model HGD-2000 with dual relay and remote control box with connection cable.

Josh.Gruning-PTR Text Box

KT RFI #9277:

The EPO switches located at the Parallel Switchgear Master Control Equipment meet the intent of the EPO switches required exterior of the generator rooms. Secondary EPO switches in addition to these are not required.

Josh.Gruning-PTR Arrow

ENERGY CENTER

NORMAL SUBSTATION

"06-NDCP5"

FUTURE

COMMUNITY LIVING CENTER

NORMAL SUBSTATION

"07-NDCP"

SEE DRAWING 07.ES.601

S150.3G

S150.3G

S150.3G

N.O.

TO FITZSIMONS

SUBSTATION

#1 #2

SUBSTATION

TO FITZSIMONS

N.C.

52-A1

RESEARCH BUILDING

NORMAL SUBSTATION

"02-NDCP"

SEE DRAWING 02.ES.601

DIAGNOSTIC AND TREATMENT BUILDING NORTH

NORMAL SUBSTATION

"03-NDCP3"

SEE DRAWING 03.ES.601-A

DIAGNOSTIC AND TREATMENT BUILDING SOUTH

NORMAL SUBSTATION

"03-NDCP1"

SEE DRAWING 03.ES.601-B

INPATIENT BUILDING (SOUTH)

NORMAL SUBSTATION

"04-NDCP"

SEE DRAWING 04.ES.601

INPATIENT BUILDING (NORTH)

NORMAL SUBSTATION

"05-NDCP"

SEE DRAWING 05.ES.601

ENERGY CENTER

NORMAL SUBSTATION

"06-NDCP1"

SEE DRAWING 06.ES.602

ENERGY CENTER

NORMAL SUBSTATION

"06-NDCP2"

SEE DRAWING 06.ES.602

ENERGY CENTER

NORMAL SUBSTATION

"06-NDCP3"

SEE DRAWING 06.ES.602

ENERGY CENTER

NORMAL SUBSTATION

"06-NDCP4"

SEE DRAWING 06.ES.602

CLINIC BUILDING (NORTH)

NORMAL SUBSTATION

"08-NDCP"

SEE DRAWING 08.ES.601

CLINIC BUILDING (CENTER)

NORMAL SUBSTATION

"09-NDCP"

SEE DRAWING 09.ES.601

CLINIC BUILDING (SOUTH)

NORMAL SUBSTATION

"10-NDCP"

SEE DRAWING 10.ES.601

PARKING STAFF (NORTH)

NORMAL SUBSTATION

"11-NDCP"

SEE DRAWING 11.ES.601

PARKING VISITOR (NORTH)

NORMAL SUBSTATION

"12-NDCP"

SEE DRAWING 12.ES.601

PARKING VISITOR (SOUTH)

NORMAL SUBSTATION

"13-NDCP"

SEE DRAWING 13.ES.601

VAULT

EC6A

VAULT

EC4A

VAULT

EC2A

VAULT

EC4A

VAULT

EC3A

VAULT

EN2A

VAULT

EW3A

VAULT

EW3A

VAULT

EW4A

VAULT

EW1A

VAULT

EC5A

VAULT

EC6A

VAULT

EC4A

VAULT

EC3A

VAULT

EN3A

VAULT

EE2A

VAULT

EE5A

VAULT

EE6A

VAULT

EE5A

VAULT

EE3A

DIAGNOSTIC AND TREATMENT BUILDING NORTH

NORMAL SUBSTATION

"03-NDCP2"

SEE DRAWING 03.ES.601-B

VAULT

EE4A

VAULT

EC5A

52-A2

TO

PARALLELING

SWITCHGEAR

SEE DRAWING

06.ES.601

52-A3 52-A4 52-F1A 52-F2A 52-F3A 52-F4A 52-B1 52-B2 52-B3 52-B4

1200AF1200AF1200AF1200AF1200AF1200AFNO NO

NO NO

13.2KV SPLIT BUS

AUTOMATIC THROW OVER (ATO)

SWITCHGEAR, 1,200A BUS

52-U1 N.C.

52-U1

52-ATO TIE

1200AF1200AF1200AF1200AF1200AF1200AF

1200AF

1200AF 1200AF

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:1

3PT

600:5

3CT

600:1

3PT

600:5

3CT

600:1

3PT

600:1

3PT

600:1

3PT

600:1

3PT

600:1

3PT

600:1

3PT

600:5

3CT

ISCA=

3,305

CDI No.10 SCOPE

CDI No.12 SCOPE

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

G

TO MAIN GROUND BAR

XCEL METER AND DEMARCATION

EXTERIOR OF THE BUILDING

XCEL METER AND DEMARCATION

EXTERIOR OF THE BUILDING

15KV

600AT

15KV

600AT

S500.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S500.3G S500.3G S500.3G S500.3G S500.3G S500.3G S500.3G S500.3G S500.3G S500.3G

15KV

500AT

50N

51N

S500.3G

50/51

51N

15KV

500AT

50N

50/51

51N

15KV

500AT

50N

50/51

51N

15KV

500AT

50N

50/51

51N

15KV

500AT

50N

50/51

51N

15KV

500AT

50N

50/51

51N

50N

50/51

51N

50N

50/51

51N

50N

50/51

51N

50N

50/51

51N

50N

50/51

51N

50N

50/51

51N

81L/M

81L/M

51N

50N

50N

15KV

500AT

15KV

500AT

15KV

500AT

15KV

500AT

15KV

500AT

15KV

500AT

15KV

600AT

S600.3G S600.3G

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

M

R

R

M

FEEDER SCHEDULE

KEY CONDUCTORS "C

S500.3 G 3 # 1000 AL 15KV #2 G 6

S600.3 G 2 [ 3# 350 AL 15KV #3/0 G] 6

FLAG NOTES:

PROVIDE 600A, 15KV DEAD-BREAK "T" CONNECTION IN SITE ELECTRICAL

VAULT INDICATED. SEE ELECTRICAL SITE PLANS.

PRIMARY FEEDER BY XCEL ENERGY.

PROVIDE 1,200A, 15KV SPLIT BUS ATO.

PROVIDE 600A, 15KV DEAD-BREAK "T" CONNECTION IN ENERGY CENTER.

(NOT ALL FLAG NOTES USED ON THIS SHEET)

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R E

S

D A

T

I B

S

I B

N

E N

C

C L C

C B

N

C B

C

C B

S

P S

N

P V

N

P V

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

/5

/2

:0 :4

A

M D

R e v it L o c a l F ile s \2

\E

S -E

N C

L A ra m b u la

.r v t

06.ES.600

NORMAL POWER SYSTEM MEDIUM

VOLTAGE ONE-LINE DIAGRAM

ENERGY CENTER

06/15/2012

SCALE: NONE1

NORMAL POWER SYSTEM

MEDIUM VOLTAGE ONE-LINE

DIAGRAM

CDI No.10 06/15/2012

CDI No.12 08/31/2012

JSI No. 044 12/19/2012

JSI No. 064 08/30/2013

RFI 3806 05/13/2014

JSI No. 090 06/05/2014 jacqueline.cipriani Typewritten Text KT RFI #04243/VA #03806: See Revised Drawing:

jacqueline.cipriani Snapshot

Josh.Gruning-PTR Cloud

Josh.Gruning-PTR Callout KT RFI #8309: Due to the reduced size of this vault, it is acceptable to pull straight through the vault in lieu of providing splices / load breaks.

Josh.Gruning-PTR Text Box

SOUTH

Josh.Gruning-PTR Cloud

Josh.Gruning-PTR Text Box

VAULT

EC5A

Josh.Gruning-PTR Text Box

Josh.Gruning-PTR Text Box

Josh.Gruning-PTR Ellipse

Josh.Gruning-PTR Cloud

Josh.Gruning-PTR Text Box

VAULT

EE4A

Josh.Gruning-PTR Ellipse

Josh.Gruning-PTR Text Box

Josh.Gruning-PTR Text Box

Josh.Gruning-PTR Arrow

Josh.Gruning-PTR Text Box

Josh.Gruning-PTR Line

Josh.Gruning-PTR Line

Josh.Gruning-PTR Line

Josh.Gruning-PTR Line

Josh.Gruning-PTR Cloud

Josh.Gruning-PTR Arrow

Josh.Gruning-PTR Text Box

Josh.Gruning-PTR Line

Josh.Gruning-PTR Line

Josh.Gruning-PTR Line

Josh.Gruning-PTR Line

Josh.Gruning-PTR Callout

KT RFI #8192

Josh.Gruning-PTR Arrow

Josh.Gruning-PTR Callout

KT RFI #8192

Ben.Braxton Text Box KT RFI #8312 - Proceed with coordinated revised main and feeder relay setting per TCC-MV-5.2.

Ben.Braxton Snapshot

ENERGY CENTER

EMERGENCY SUBSTATION

"06-EMDCP5"

FUTURE

COMMUNITY LIVING CENTER

EMERGENCY SUBSTATION

"07-EMDCP"

SEE DRAWING 07.ES.602

FUTURE 2.0MW,13.2KV

GENERATOR

S150.3G

S150.3G

S150.3G

S150.3

2.0MW

PORTABLE

GENERATOR

TAP BOXLOAD BANK

RESISTIVE

FIXED

2.0MW

N.O.

N.C.

52-GB4

RESEARCH BUILDING

EMERGENCY SUBSTATION

"02-EMDCP"

SEE DRAWING 02.ES.602

DIAGNOSTIC AND TREATMENT BUILDING NORTH

EMERGENCY SUBSTATION

"03-EMDCP2"

SEE DRAWING 03.ES.602-A

DIAGNOSTIC AND TREATMENT BUILDING SOUTH

EMERGENCY SUBSTATION

"03-EMDCP1"

SEE DRAWING 03.ES.602-B

INPATIENT BUILDING (SOUTH)

EMERGENCY SUBSTATION

"04-EMDCP"

SEE DRAWING 04.ES.602

INPATIENT BUILDING (NORTH)

EMERGENCY SUBSTATION

"05-EMDCP"

SEE DRAWING 05.ES.602

ENERGY CENTER

EMERGENCY SUBSTATION

"06-EMDCP1"

SEE DRAWING 06.ES.603

ENERGY CENTER

EMERGENCY SUBSTATION

"06-EMDCP2"

SEE DRAWING 06.ES.603

ENERGY CENTER

EMERGENCY SUBSTATION

"06-EMDCP3"

SEE DRAWING 06.ES.604

ENERGY CENTER

EMERGENCY SUBSTATION

"06-EMDCP4"

SEE DRAWING 06.ES.604

CLINIC BUILDING (NORTH)

EMERGENCY SUBSTATION

"08-EMDCP"

SEE DRAWING 08.ES.602

CLINIC BUILDING (CENTER)

EMERGENCY SUBSTATION

"09-EMDCP"

SEE DRAWING 09.ES.602

CLINIC BUILDING (SOUTH)

EMERGENCY SUBSTATION

"10-EMDCP"

SEE DRAWING 10.ES.602

PARKING STAFF (NORTH)

EMERGENCY SUBSTATION

"11-EMDCP"

SEE DRAWING 11.ES.602

PARKING VISITOR (NORTH)

EMERGENCY SUBSTATION

"12-EMDCP"

SEE DRAWING 12.ES.602

PARKING VISITOR (SOUTH)

EMERGENCY SUBSTATION

"13-EMDCP"

SEE DRAWING 13.ES.602

TO ATO

SEE DRAWING

06.ES.600

2,500

KVA

VAULT

EE6B

VAULT

EE4B

VAULT

EE2B

VAULT

EE5B

VAULT

EE3B

VAULT

EW2B

VAULT

EW3B

VAULT

EW4B

VAULT

EW1B

VAULT

EN2B

VAULT

EC2B

VAULT

EC4B

VAULT

EC6B

VAULT

EC5B

VAULT

EC3B

VAULT

EC3B

VAULT

EC4B

VAULT

EC6B

VAULT

EC4B

VAULT

EN3B

PORTABLE

GENERATOR/LOAD

BANK UNIT SUBSTATION

2,500KVA

13.2KV/480/277V

3-PHASE, 4-WIRE

15KV PARALLELING

SWITCHGEAR 1,200A

BUS

52-GB352-GB2

1200AF1200AF1200AF

52-GB1

1200AF

52-F4GB

1200AF

N.C.

52-F3GB

1200AF

N.C.

52-F2GB

1200AF

N.C.

52-F1GB

1200AF

N.C.

52-GA4

1200AF

N.C.

52-GA3

1200AF

N.C.

52-GA2

1200AF

N.C.

52-GA1

1200AF

1200AF52-LB

52-PSG TIE

2.0MW,13.2KV

GENERATOR

200:5

3CT

200:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

150:1

3PT

200:5

3CT

(TYP ALL GENERATORS

AND TAP BOX CONNECTION)

1200AF52-G1

200:5

3CT

1200AF52-G2

200:5

3CT

1200AF52-G3

200:5

3CT

1200AF52-G4

200:5

1200AF52-G4

200:5

ISCA=

3,669

150:1

3PT

150:1

3PT

CDI No.10 SCOPE

CDI No.12 SCOPE

2.0MW,13.2KV

GENERATOR

2.0MW,13.2KV

GENERATOR

2.0MW,13.2KV

GENERATOR

3CT 3CT

1200AF

200:5

3CT

200:5 200:5

3CT 3CT

200:5

3CT

200:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

600:5

3CT

150:1

3PT

150:1

3PT

150:1

3PT

150:1

3PT

150:1

3PT

150:1

3PT

150:1

3PT

150:1

3PT

150:1

3PT

150:1

3PT

200:5

3CT

600:5

3CT

600:5

3CT

G

TO MAIN GROUND BAR

15KV

500AT

S500.3G S500.3G S500.3G S600.3 S500.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

S150.3G

LSIGZ

4,000A3P

LSIGZ

4,000A3P

LSIGZ

4,000A3P

4,000.4G 4,000.4G

S150.3

50/51

51N

50N

S150.3

15KV

500AT

50/51

51N

50N

15KV

500AT

50/51

51N

50N

15KV

500AT

50/51

51N

50N

15KV

500AT

50/51

51N

50N

S500.3G

15KV

500AT

50/51

51N

50N

S500.3G

15KV

500AT

50/51

51N

50N

S500.3G

15KV

500AT

50/51

51N

50N

S500.3G

15KV

500AT

50/51

51N

50N

S500.3G

15KV

500AT

50/51

51N

50N

15KV

500AT

50/51

51N

50N

S500.3G

15KV

500AT

50/51

51N

50N

S500.3G

S150.3 S150.3

50/51

51N

150AT

15KV

46 51GN

50GN

21 87

592427

50/51

51N

150AT

15KV

50/51

51N

150AT

15KV

50/51

51N

150AT

15KV

50/51

51N

150AT

15KV

50/51

51N

150AT

15KV

15KV

600AT

25 25252525

78 4032

G

R

R

R

G G

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

G G

R

R

RR

R RR RR R

R

R

R

R

R

R

RRR

R

R

R

R

R

R

R

R

R

R

R

R R

R

R RRRR

R RR

FEEDER SCHEDULE

KEY CONDUCTORS "C

S500.3 G 3 # 1000 AL 15KV #2 G 6

S150.3 3# 1/0 AL 15KV 4

S150.3 G 3# 1/0 AL 15KV #2 G 4

4000.4 G 11 [ 4 # 500 , 1 # 500 G 4 ]

FLAG NOTES:

PROVIDE 600A, 15KV DEAD-BREAK "T" CONNECTION IN SITE ELECTRICAL

VAULT INDICATED. SEE ELECTRICAL SITE PLANS.

PRIMARY FEEDER BY XCEL ENERGY.

PROVIDE 1,200A, 15KV SPLIT BUS ATO.

PROVIDE 600A, 15KV DEAD-BREAK "T" CONNECTION IN ENERGY CENTER.

(NOT ALL FLAG NOTES USED ON THIS SHEET)

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R E

S

D A

T

I B

S

I B

N

E N

C

C L C

C B

N

C B

C

C B

S

P S

N

P V

N

P V

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

/1

/2

:4 :0

P

M D

R e v it L o c a l P ro je c ts

\2 \E

S -E

N C c d o u g la s .r v t

06.ES.601

ESSENTIAL ELECTRICAL SYSTEM

MEDIUM VOLTAGE ONE-LINE DIAGRAM

ENERGY CENTER

06/15/2012

SCALE: NONE1

ESSENTIAL ELECTRICAL SYSTEM

MEDIUM VOLTAGE ONE-LINE

DIAGRAM

CDI No.10 06/15/2012

CDI No.12 08/31/2012

JSI No. 044 12/19/2012 lara.ceigerkansky Text Box

RFI 1234 (VA RFI 1095) -

7. PSG is shorthand notation for the "Paralleling Switchgear" and is also the same equipment shown on floor plans as "Generator Paralleling Switchgear".

lara.ceigerkansky Arrow michael.durbin Cloud michael.durbin Cloud michael.durbin Line michael.durbin Text Box S500.3G randy.wicke Cloud

Omar.AlRubaye-PTR verify pipe size See RFI 3806(KT 4243)

Omar.AlRubaye-PTR Rectangle jacqueline.cipriani Typewritten Text KT RFI #04243/VA #03806: See Revised Drawing:

jacqueline.cipriani Snapshot

Steve.Walter Callout KT RFI #03253/VA #02919: This is the current information for the correct S150.3 G feeder cable information (3# 1/0AL 15kV, #2 G).

Steve.Walter Callout KT RFI #03253/VA #02919: This is the current information for the correct S150.3 G feeder cable information (3# 1/0AL 15kV, #2 G). See Feeder Schedule.

VA.PLAN

Callout

KT RFI #2620/VA #2294:

PSG and Load Bank/Portable Gen. Substation cannot be close coupled. Will run S150.3G (3# 1/0 AL 15kV, #2 ground - 4" conduit) to connect sections

Steve.Walter Callout KT RFI #02657/VA #02398: To clarify, the 4000A rated generator tap box can be provided as designed, but ti would be a custom unit as noted. The 3200A rated installation is technically acceptable. The current 4000A cable feeser schedule shown on 06.ES.601 (4000.4.G) consisting of 11 sets of 500kcmil copper conductors (380A reach, 4180A total) can be revised to 500kcmil AL conductors (310A each, 3410A total).

Colter.Dahlstrom Snapshot

Colter.Dahlstrom Callout

KT RFI #2509/VA #2191:

Change main feeder to S500.3G

Josh.Gruning-PTR Cloud

Josh.Gruning-PTR Callout KT RFI #8309: Due to the reduced size of this vault, it is acceptable to pull straight through the vault in lieu of providing splices / load breaks.

LEVEL 1

SERVICE LEVEL

LEVEL 1

SERVICE LEVEL

1 1

SPD SPARECHILLEREQUIPMENT SPACE SPACE SPD SPARECHILLEREQUIPMENT

TO 06-ATS-EQ1

SEE

DRAWING

06.ES.603

TO 06-ATS-CH1

SEE

DRAWING

06.ES.603

TO 06-ATS-LS1

SEE

DRAWING

06.ES.603

TO 06-ATS-GEN

SEE

DRAWING

06.ES.603

TO 06-ATS-EQ2

SEE

DRAWING

06.ES.603

TO 06-ATS-CH2

SEE

DRAWING

06.ES.603

SPACESPACENORMAL

ENERGY CENTER

UNIT SUBSTATION

2,000KVA

13.2KV-480/277V

100KAIC

"06-NDCP3"

CRITICALSPD SPARECHILLEREQUIPMENT SPACE SPACE SPD SPARECHILLEREQUIPMENT

TO 06-ATS-EQ3

SEE

DRAWING

06.ES.604

TO 06-ATS-CH3

ATS SEE

DRAWING

06.ES.604

TO 06-ATS-CR1

SEE

DRAWING

06.ES.604

TO 06-ATS-EQ4

SEE

DRAWING

06.ES.604

TO 06-ATS-CH4

SEE

DRAWING

06.ES.604

SPACESPACENORMAL

TO 06-FPC-FP1

CONTROLLER SEE

DRAWING

06.ES.604

ENERGY CENTER

"06-NDCP1"

UNIT SUBSTATION

2,000KVA

13.2KV-480/277V

100KAIC

GENERATOR

APPURTENANCE

LIFE

SAFETY

TO CABLE "A2"

SEE DRAWING

06.ES.600

TO CABLE "B2"

SEE DRAWING

06.ES.600

ENERGY CENTER

"06-NDCP2"

UNIT SUBSTATION

2,000KVA

13.2KV-480/277V

100KAIC

ENERGY CENTER

"06-NDCP4"

UNIT SUBSTATION

2,000KVA

13.2KV-480/277V

100KAIC

ISCA=38,255

ISCA=38,150

ISCA=38,049ISCA=38,048

ISCA=48,908

ISCA=5,249

ISCA=4,755ISCA=4,416

ISCA=

27,400

ISCA=35,610

ISCA=4,634

ISCA=66,771

ISCA=3,420

15KV

15KV

TO CABLE "A4"

SEE DRAWING

06.ES.600

TO CABLE "B4"

SEE DRAWING

06.ES.600

ISCA=84,186

ISCA=3,420

15KV

15KV

TO CABLE "A3"

SEE DRAWING

06.ES.600

TO CABLE "B3"

SEE DRAWING

06.ES.600

ISCA=85,262

ISCA=3,419

15KV

15KV

TO CABLE "A1"

SEE DRAWING

06.ES.600

TO CABLE "B1"

SEE DRAWING

06.ES.600

ISCA=89,627

ISCA=3,421

15KV

15KV

1600AF

TO MAIN GROUND BAR TO MAIN GROUND BAR

TO MAIN GROUND BARTO MAIN GROUND BAR

N G

TO MAIN GROUND BAR

VD=0.924%

VD=0.321%

VD=0.496%

VD=1.264%

VD=0.482%

VD=0.385%

VD=1.05%

150:1

3CT

150:1

3CT

150:1

3CT

150:1

3CT

150:1

3CT

2HR RATED

CABLE ASSEMBLY

N G

TO MAIN GROUND BAR

N G

TO MAIN GROUND BAR

N G

TO MAIN GROUND BAR

FIRE PUMP

KVA

DRY TYPE

TRANSFORMER

DELTA/WYE

KVA

KVA

KVA

DRY TYPE

TRANSFORMER

DELTA/WYE

DRY TYPE

TRANSFORMER

DELTA/WYE

DRY TYPE

TRANSFORMER

DELTA/WYE

1600AF 800AF800AF3200AF800AF800AF1600AF 1600AF 800AF3200AF

1600AF 1600AF 800AF3200AF 800AF 1600AF 1600AF 800AF800AF3200AF

150:1

3CT

150:1

3CT

LSIGZ

1200AT SPD

LSIGZ

200AT

LSIGZ

MEC

LSIGZ LSIGZ

600AT

1200.4G MEC

LSIGZ

1200AT SPD

LSIGZ

MEC

LSIGZ

SPD

SPD

200.4G 600.4G 200.4G

PANEL

"06-

NHDP11"

PANEL

"06-

NH11" 100.4G

PANEL

"06-

NL11"

XFMR

XFMR

PANEL

"06-

NHS1"

50.4G

XFMR

XFMR

PANEL

"06-

NLS1"

MEC1200.4G

LSIGZ

200AT

SPD

SPD

SPD

LSIGZ

200AT

LSIGZ

MEC

MEC

LSIGZ

1200AT

LSIGZ

SPD

SPD

LSIGZ

1200AT

LSIGZ

1200.4G

SPD

LSIGZ

MEC

200.4G 200.4G

PANEL

"06-

NHDP12"

XFMR

XFMR

PANEL

"06-

NLS2"

MEC1200.4G

LSIGZ

200AT

SPD

SPD

MEC

1200AF

110AT

a

1200AF

110AT

LSIGZ

3,000AT

a

1200AF

110AT

a

1200AF

110AT

LSIGZ

3,000AT

a

1200AF

110AT

a

1200AF

110AT

LSIGZ

3,000AT

a

1200AF

110AT

a

1200AF

110AT

LSIGZ

3,000AT

a

06-TNL11

06-TNLS1

06-TNLS2

TK

M

M

R

R

R

R

M

K

K

R

R

R

R

M

K

K

R

R

R

R

M

K

K

R

R

R

R

M

K

K

TK

TK

FEEDER SCHEDULE

KEY CONDUCTORS "C

50.4 G 4 # 6 , 1 # 10 G 1 1/4

100.4 G 4 # 1 , 1 # 8 G 1 1/2

200.4 G 4 # 250 AL , 1 # 4 AL G 2 1/2

800.4 G 3 [ 4 # 400 AL , 1 # 3/0 AL G 3 ]

1200.4 G 4 [ 4 # 500 AL , 1 # 250 AL G 3 ]

SPD PER SPD MANUFACTURER

MEC SEE MECH'L EQUIPMENT SCHEDULE

XFMR SEE TRANSFORMER SCHEDULE

NOTE: ALUMINUM CONDUCTORS ARE BASED

ON TYPE XHHW-2 COMPACT 600V

TRANSFORMER SCHEDULE

KEY HV FLA LV FLA HV PROT HIGH VOLTAGE FEEDER LV PROT LOW VOLTAGE FEEDER GROUNDING DIMENSIONS WEIGHT BTUH NOTE

480 V 208 V CCT BRKR CONDUCTORS "C CCT BRKR CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP OTPT

TK13-75 90.2 208.2 110 A 3 P 3 # 1 , 1 # 6 G 1-1/2 250 A 3 P 5 # 350 AL , 1 # 1/0 AL G 3 1 # 1/0 AL 3/4 43.75 32.00 27.00 875 7749 7

NOTES: 1.) PRIMARY AND SECONDARY O.C. PROTECTION PER NEC 450.3.

2.) BONDING AND GROUNDING CONDUCTOR PER NEC 250.66.

3.) CONDUCTORS ARE COPPER UNLESS OTHERWISE NOTED. ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V.

4.) SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC.

5.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER.

6.) BRANCH CIRCUITS TO HAVE A DEDICATED NEUTRAL FOR EACH CIRCUIT ON K-RATED TRANSFORMERS.

7.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD .

FLAG NOTES:

PROVIDE SURGE PROTECTIVE DEVICE (SPD) WITH 240,000A PER

MODE (L-L,L-N,L-C) PROTECTION.

(NOT ALL FLAG NOTES USED ON THIS SHEET)

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R E

S

D A

T

I B

S

I B

N

E N

C

C L C

C B

N

C B

C

C B

S

P S

N

P V

N

P V

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

/2

/2

:2

:1

P

M D

R e v it L o c a l F ile s \2

\E

S -E

N C

C

D o u g la s .r v t

06.ES.602

NORMAL POWER SYSTEM ELECTRICAL

ONE-LINE DIAGRAM

ENERGY CENTER

06/15/2012

SCALE: NONE1

NORMAL POWER SYSTEM

ELECTRICAL ONE-LINE DIAGRAM

CDI No.10 06/15/2012

CDI No.12 08/31/2012

JSI No. 044 12/19/2012

RFI No.

This is the start of the file's text. The full file is on GovTribe.