This notice provides details for an energy savings performance contract solicitation for the Department of Veterans Affairs Medical Center Orlando. The solicitation will seek energy conservation measures across four campuses, including boiler and chiller plant improvements, HVAC upgrades, lighting retrofits, electric motor replacements, renewable energy systems, and commissioning. Eligible energy service companies must be on the Department of Energy's Qualified List by the closing date. The solicitation will be issued on March 22, 2018 via the VA Vendor Acquisition Portal under request for proposal number 36E77618R0005. It will remain open for approximately 60 calendar days and is set aside for service-disabled veteran owned small businesses. Questions may be submitted to the point of contact by email only.
36E77618R0005 00001 Q3 Lake Baldwin One Line Diagram- Exisitng conditions.pdf
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TAG # CONDUIT CONDUCTORS GROUND LENGTH
1 PVC 3#500KCMIL EPR CU (15KV) 750'
2 PVC 3#500KCMIL EPR CU (15KV) 315'
3 PVC 3#500KCMIL EPR CU (15KV) 15'
4 4" PVC 3#4/0 AL (15KV) #4 CU 900'
5 6" PVC 3#4/0 AL (15KV) 100'
6 PVC 3#500KCMIL XLP AL (15KV) 300'
7 PVC 3#500KCMIL EPR CU (15KV) 30'
8 PVC 3#500KCMIL EPR CU (15KV) 15'
9 PVC 3#500KCMIL CU (15KV) 25'
10 PVC 3#500KCMIL EPR CU (15KV) 40'
11 NOT USED
12 PVC 3#500KCMIL EPR CU (15KV) 305'
13 4" PVC 3#4/0 AL (15KV) #4 CU 40'
14 PVC 3#500KCMIL EPR CU (15KV) 600'
15 PVC 3#4/0 AL (15KV) 30'
16 PVC 3#4/0 AL (15KV) 15'
17 PVC 3#4/0 AL (15KV) 15'
18 6" RGS 3#4/0 AL (15KV) 15'
19 6" PVC 3#4/0 AL (15KV) 15'
20 6" PVC 3#4/0 AL (15KV) 15'
21 4" PVC UNKNOWN 355'
22 PVC UNKNOWN 495'
23 (5) 4" PVC (5) 4#500KCMIL 2#4/0 15'
24 (5) 3 1/2" RGS (5) 4#500KCMIL CU 15'
25 (4) 4" RMC (4) 4#500KCMIL THHN-2 CU 15'
26 (4) PVC (4) 4#750KCMIL XLPE AL 20'
27 (2) 4" PVC (2) 4#600KCMIL THHN CU 130'
28 (2) 4" PVC (2) 4#350KCMIL THW CU 80'
29 (5) 4" PVC (5) 4#600KCMIL CU 45'
30 (4) PVC (4) 3#750KCMIL THHN-THWN AL, #4/0 N 160'
31 (6) PVC (6) 3#600KCMIL THHN-THWN AL, #4/0 N 290'
32 4" PVC 4#500KCMIL THHN CU #4/0 THHN CU 175'
33 NOT USED
34 NOT USED
35 (6) PVC (6) 3#750KCMIL THHN-THWN AL, #4/0 N 160'
36 NOT USED
37 NOT USED
38 NOT USED
39 NOT USED
40 NOT USED
41 NOT USED
42 NOT USED
43 NOT USED
44 NOT USED
45 NOT USED
46 NOT USED
47 NOT USED
48 NOT USED
49 NOT USED
50 NOT USED
FEEDER SCHEDULE
VHAORLRiqueD Rectangle
VHAORLRiqueD Text Box All power will be lost fed from ATS 4 and MWS 4. No other areas will be affected.