This document is a Mechanical Schedules drawing (M-601) for 100% Construction Documents associated with a federal construction project at the G.V. Montgomery VA Medical Center in Jackson, Mississippi. The project, identified as VA Project Number 23-060 (ACG Project Number 586-401), is dated June 23, 2025, and prepared by Apogee Consulting Group, P.A. for the U.S. Department of Veterans Affairs Office of Construction and Facilities Management.
The mechanical schedules detail comprehensive specifications for the CLC Residential Neighborhood building systems, including: one primary air handling unit (7A-AHU-1) with 7,600 CFM supply capacity and redundant supply fans with variable frequency drives; multiple VAV (variable air volume) terminal units (101-123) with 5-degree deadband controls serving 104 spaces; three air-cooled heat recovery heat pump chiller-heaters operating with 30% propylene glycol; heating and chilled water circulation pumps with variable speed drives; expansion tanks and buffer tanks for both heating and chilled water systems; pre-filtration, after-filtration, and final filtration with MERV 16 capability; hot water heating and chilled water cooling coils; a steam humidifier; supply, relief, and exhaust fan systems with specified static pressures and motor requirements; and air distribution devices including supply registers, return grilles, and exhaust grilles. Additional schedules specify equipment electrical requirements (primarily 208V and 460V three-phase, 60Hz), control sequences, and installation notes requiring manufacturer compliance. The pressurization map indicates neutral pressure maintenance with 0.01" water gauge positive and negative thresholds.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
0.01" WG NEGATIVE
0.01" WG POSITIVE
NEUTRAL PRESSURE
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:3
:4
P
M C
U s e rs \w s h ip le y \D o c u m e n ts
\M P
-0
-V
A J a c k s o n -C o n s tr u c t C
L C
R w s h ip le y .r v t
M-601
MECHANICAL SCHEDULES
15 15PRP
CLC RESIDENTIAL
NEIGHBORHOOD
G.V. MONTGOMERY VAMC
1500 E. WOODROW WILSON AVENUE
JACKSON, MS 39216 JUNE 23, 2025
100% CONSTRUCTION DOCUMENTS
586-40123-060
7A
WRS
NOTES:
1. ALL SELECTIONS ARE BASED ON AN ALTITUDE OF 331 FT.
2. PROVIDE VARIABLE SPEED CONTROLLER.
3. PROVIDE WITH ALUMINUM BACKDRAFT DAMPER.
4. SUPPLY FANS ARE 100% REDUNDANT, PROVIDE SHUTOFF DAMPER AT EACH FAN, CLOSED WHEN FAN IS NOT OPERATING.
5. SPRING VIBRATION ISOLATOR HANGERS.
6. PROVIDE FAN SPEED CONTROLLER.
NOTES:
1. PROVIDE DUAL SUPPLY FANS EACH CAPABLE OF HANDLING TOTAL AIR VOLUME AND STATIC PRESSURE, SECOND FAN IS STANDBY. PROVIDE MOTORIZED SHUTOFF DAMPERS AT EACH FAN INLET. PROVIDE A VARIABLE FREQUENCY DRIVE (VFD) FOR
EACH FAN FOR BALANCING AND CONTROL.
2. PROVIDE 8" HIGH BASE RAIL, FANS ON 2" DEFLECTION SPRING ISOLATORS, TOP DISCHARGE OUTLET, TOP RETURN INLET, AND ACCESS SPACE BETWEEN COILS FOR HIMIDIFIER DISPERSION TUBE.
3. TOTAL FAN STATIC SHALL INCLUDE EXTERNAL STATIC PRESSURE PLUS ALL COMPONENTS AND FILTER PRESSURE DROP AT MID-LIFE CONDITION.
4. PROVIDE BASE RAIL MINIMUM 8" HIGH.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE DAMPER IN BRANCH DUCT AS SHOWN ON PLANS.
NOTES:
1. PROVIDE PRE-INSULATED BUFFER TANK WITH FOUR FLANGED CONNECTIONS, DRAIN, THERMOSTAT AND 12" HIGH PAINTED STEEL STAND. SIMILAR TO CEMLINE MODEL V300SEB.
2. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
7A-AHU-1 104 CLC CUSTOM MODULAR VAV 7600 [ 3600 ] 2600 [ 1200 ] 5000 [ 2400 ] 1-SF5 1-RF5 1-EF5 1-PF5 1-AF5 1-FF5 N/A 1-PHC5 1-CC5 AT TU 1-H5 1, 2, 3
CFM [L/s] CFM [L/s] CFM [L/s]
SUPPLY MIN OA RETURNMARK LOCATION AREA AND/OR BLDG SERVED TYPE AIR FLOW
AIR FLOW
SUPPLY FAN MARK RETURN OR RELIEF FAN MARK EXHAUST FAN MARK PREFILTER MARK AFTER FILTER MARK FINAL FILTER MARK HEAT RECOVERY MARK PREHEAT COIL MARK COOLING COIL MARK REHEAT COIL HUMIDIFIER MARK REMARKS
AIR HANDLING UNIT SCHEDULE
7A-AF-1 SUPPLY BUILDING 1 7A-AHU1 13 10000 [ 4700 ] 0.75 [ 19 ] 1.5 [ 38 ] SIDE 18 24 x 24 x 12 [ 600 x 600 x 300 ] 6 WIDE BY 3 HIGH FILTER RACK SHALL BE CAPABLE TO HOLD MERV 16 FILTERS
7A-PF-2 SUPPLY BUILDING 1 7A-AHU1 11 10000 [ 4700 ] 0.5 [ 13 ] 1 [ 25 ] SIDE 18 24 x 24 x 12 [ 600 x 600 x 300 ] 6 WIDE BY 3 HIGH ----
7A-PF1 SUPPLY BUILDING 1 7A-AHU1 8 10000 [ 4700 ] 0.17 [ 4 ] 0.7 [ 18 ] SIDE 18 24 x 24 x 2 [ 600 x 600 x 50 ] 6 WIDE BY 3 HIGH -----
CFM [L/s] IN [mm] IN [mm] IN [mm]
INITIAL CHANGEOVER
SIZE
ARRANGEMENT REMARKS
MARK LOCATION AREA AND/OR BLDG SERVED SYSTEM AND/OR SERVICE MERV RATING
AIR FLOW
APD
HOUSING TYPE
CARTRIDGES
AIR FILTER SCHEDULE
7A-TU-123 123 6 7A-AHU-1 215 [ 100 ] 65 [ 31 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 1022 TWO-WAY 1
7A-TU-122 122 8 7A-AHU-1 460 [ 220 ] 255 [ 120 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 3951 TWO-WAY 1
7A-TU-121 121 6 7A-AHU-1 100 [ 47 ] 100 [ 47 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 1024 TWO-WAY 1
7A-TU-120 120 8 7A-AHU-1 450 [ 210 ] 280 [ 130 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 4314 TWO-WAY 1
7A-TU-119 119 6 7A-AHU-1 110 [ 52 ] 110 [ 52 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 594 TWO-WAY 1
7A-TU-118 118 6 7A-AHU-1 70 [ 33 ] 70 [ 33 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 387 TWO-WAY 1
7A-TU-117 117 8 7A-AHU-1 495 [ 230 ] 355 [ 170 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 5189 TWO-WAY 1
7A-TU-114 114 6 7A-AHU-1 255 [ 120 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 3029 THREE-WAY 1
7A-TU-113 113 6 7A-AHU-1 225 [ 110 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2632 TWO-WAY 1
7A-TU-112 112 6 7A-AHU-1 225 [ 110 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2636 TWO-WAY 1
7A-TU-111 111 6 7A-AHU-1 225 [ 110 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2560 TWO-WAY 1
7A-TU-110 110 6 7A-AHU-1 225 [ 110 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2629 TWO-WAY 1
7A-TU-109 109 6 7A-AHU-1 225 [ 110 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2551 TWO-WAY 1
7A-TU-108 108 6 7A-AHU-1 225 [ 110 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2597 TWO-WAY 1
7A-TU-107 107 6 7A-AHU-1 225 [ 110 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2584 TWO-WAY 1
7A-TU-106 106 6 7A-AHU-1 225 [ 110 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2592 TWO-WAY 1
7A-TU-105 105 6 7A-AHU-1 220 [ 100 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 2499 TWO-WAY 1
7A-TU-104 104 6 7A-AHU-1 560 [ 260 ] 165 [ 78 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 2.5 10846 TWO-WAY 1
7A-TU-103 103 8 7A-AHU-1 610 [ 290 ] 375 [ 180 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 .5 6087 TWO-WAY 1
7A-TU-101 101 12 7A-AHU-1 1510 [ 710 ] 1370 [ 650 ] VAV 5 DEGREE DEADBAND 2 60 85 110 85 1 18800 TWO-WAY 1
CFM [L/s] CFM [L/s] ROWS EAT (°F) LAT (°F) EWT (°F) LWT (°F) FLOW (GPM) CAPACITY (BTUH)
MAX MINMARK LOCATION DUCT INLET
SYSTEM AIR
HANDLING
AIR FLOW
CONTROL
TYPE
CONTROL SEQUENCE
HOT WATER HEATING COIL CONTROL
VALVE TYPE
REMARKS
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE
7A-DHP-2 104 CLC DOM WATER HTR SOURCE WATER IN-LINE 30% PROPELYNE GLYCOL 30 [ 2 ] 25 [ 400 ] 90 [ 32 ] 50 0.5 [ ] 1 120 1800 CONSTANT ----
7A-DHP-1 104 CLC DOM WATER HTR SOURCE WATER IN-LINE 30% PROPELYNE GLYCOL 30 [ 2 ] 25 [ 400 ] 90 [ 32 ] 50 0.5 [ ] 1 120 1800 CONSTANT ----
7A-CHW-P2 104 CLC CHILLED WATER END SUCTION 30% PROPELYNE GLYCOL 130 [ 8 ] 40 [ 640 ] 45 [ 7 ] 50 3 [ 2 ] 3 208 1800 VARIABLE ----
7A-CHW-P1 104 CLC CHILLED WATER END SUCTION 30% PROPELYNE GLYCOL 130 [ 8 ] 40 [ 640 ] 45 [ 7 ] 50 3 [ 2 ] 3 208 1800 VARIABLE ----
7A-HHW-P2 104 CLC HEATING WATER END SUCTION 30% PROPELYNE GLYCOL 111 [ 7 ] 55 [ 880 ] 110 [ 43 ] 50 3 [ 2 ] 3 208 2000 VARIABLE ----
7A-HHW-P1 104 CLC HEATING WATER END SUCTION 30% PROPELYNE GLYCOL 111 [ 7 ] 55 [ 880 ] 110 [ 43 ] 50 3 [ 2 ] 3 208 2000 VARIABLE ----
GPM [L/s] FT [kPa] °F [°C] HP [kW]
FLUID
FLOW HEAD TEMPERATURE NOMINAL POWER
PHASE VOLT MAX RPM SPEED CONTROL REMARKS
MARK LOCATION AREA AND/OR BLDG SERVED SYSTEM AND/OR SERVICE TYPE
CIRCULATING FLUID
MIN % EFF
ELECTRICAL MOTOR
PUMP SCHEDULE
7A-HRCH-3 MODULAR (1 MODULE) SCROLL 2 PER MODULE 96.4 54 44 34 86.84 17.4 19.63 23.2 95 110 338 47.44 4.97 2.5 460/3/60 74 100
7A-HRCH-2 MODULAR (1 MODULE) SCROLL 2 PER MODULE 96.4 54 44 34 86.84 17.4 19.63 23.2 95 110 338 47.44 4.97 2.5 460/3/60 74 100
7A-HRCH-1 MODULAR (1 MODULE) SCROLL 2 PER MODULE 96.4 54 44 34 86.84 17.4 19.63 23.2 95 110 338 47.44 4.97 2.5 460/3/60 74 100
°F °F °F TONS GPM FT H2O BTU/Wh °F °F °F MBH GPM FT H2O AMPS AMPS
TYPE #
AMBIENT AIR TEMP EWT LWT CAPACITY FLOW WPD IPLV AMBIENT AIR TEMP EWT LWT CAPACITY FLOW WPD COP V/PH/Hz
MCA MOCPMARK TYPE
COMPRESSOR COOLING HEATING ELECTRICAL
REMARKS
AIR-COOLED HEAT RECOVERY HEAT PUMP CHILLER-HEATER SCHEDULE
7A-ET-2 104 CHILLED WATER VERTICAL / BLADDER 700 [ 2600 ] 40 [ 4 ] 80 [ 27 ] 12 [ 83 ] 30 [ 210 ] 8 [ 30 ] 7 [ 26 ] 0.75 [ 19 ] 0.75 [ 19 ]
7A-ET-1 104 HEATING WATER VERTICAL / BLADDER 400 [ 1500 ] 40 [ 4 ] 140 [ 60 ] 12 [ 83 ] 30 [ 210 ] 23 [ 87 ] 23 [ 87 ] 0.75 [ 19 ] 0.75 [ 19 ]
GAL [L] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] GAL [L] GAL [L] IN [mm] IN [mm]
MIN MAXMARK LOCATION SYSTEM AND/OR SERVICE TYPE
APPROX SYSTEM VOLUME
SYSTEM TEMPERATURE RANGE
INITIAL PRESSURE IN TANK MAX OPERATING PRESSURE MIN VOLUME TANK MIN ACCEPTANCE VOLUME PIPE SIZE TO TANK COLD WATER FILL SIZE
REMARKS
EXPANSION TANK SCHEDULE
7A-HBT-2 HEATING HOT... 80 120 125 300 4" 36" 85" 2700 1, 2
7A-HBT-1 HEATING HOT... 80 120 125 300 4" 36" 85" 2700 1, 2
7A-CBT-2 CHILLED WATER 42 65 125 300 4" 36" 85" 2700 1, 2
7A-CBT-1 CHILLED WATER 42 65 125 300 4" 36" 85" 2700 1, 2
MIN TEMP MAX...
MARK SYSTEM
TANK... MAX OPERATING PRESSURE
(PSI)
TANK VOLUME
(GAL)
TANK CONNECTION
(FLANGED)
TANK
DIAMETER
TANK
HEIGHT
WEIGHT
(OPERATING)
NOTES
BUFFER TANK SCHEDULE
7A-CWCC-1 107 CLC AHU-1 10000 [ 4700 ] 450 [ 2 ] 0.72 [ 180 ] 80 [ 27 ] 67 [ 19 ] 55 [ 13 ] 54 [ 12 ] 384 [ 110 ] 276 [ 81 ] 55.2 [ 4 ] 44 [ 7 ] 54 [ 12 ] 3.95 [ 1 ] -----
CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] °F [°C] °F [°C] MBH [kW] MBH [kW] GPM [L/s] °F [°C] °F [°C] FT [M]
Db Wb Db Wb FLOW EWT LWT WPDMARK LOCATION AREA AND/OR BLDG SERVED SYSTEM AND/OR SERVICE
AIR FLOW MAX FACE VELOCITY APD
EAT LAT TOTAL
CAPACITY
SENSIBLE CAPACITY
CHILLED WATER
REMARKS
CHILLED WATER COOLING COIL SCHEDULE
7A-HC-1 104 CLC AHU-1 PREHEAT 10000 [ 4700 ] 400 [ 2 ] 0.25 [ 63 ] 23.2 [ -5 ] 55 [ 13 ] 350 [ 1200 ] 38 [ 2 ] 110 [ 43 ] 95 [ 35 ] ---
CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW] GPM [L/s] °F [°C] °F [°C]
EAT LAT FLOW EWT LWTMARK
LOCATIO
N
AREA AND/OR BLDG
SERVED
SYSTEM AND/OR
SERVICE
APPLICATIO
N
AIR FLOW
MAX FACE
VELOCITY
APD
TEMPERATURES TOTAL MIN
CAPACITY
HOT WATER
REMARKS
HOT WATER HEATING COIL SCHEDULE
7A-VFD-SF2 104 1-SF-2 20 460 NEMA 1, WITH BYPASS
7A-VFD-SF1 104 1-SF-1 20 460 NEMA 1, WITH BYPASS
7A-VFD-RF2 104 1-RF-2 2 460 NEMA 1, WITH BYPASS
7A-VFD-RF1 104 1-RF-1 2 460 NEMA 1, WITH BYPASS
7A-VFD-CP2 104 CHW-P2 3 208 NEMA 1, WITH BYPASS
7A-VFD-CP1 104 CHW-P1 3 208 NEMA 1, WITH BYPASS
7A-VFD-HP2 104 HHW-P2 3 208 NEMA 1, WITH BYPASS
7A-VFD-HP1 104 HHW-P1 3 208 NEMA 1, WITH BYPASS
HP VOLTA...MARK
LOCATIO
N
EQUIPMENT
SERVED
ELECTRICAL
REMARKS
VFD SCHEDULE
7A-AS-2 104 CHILLED WATER FULL FLOW TANGENTIAL 3 [ 75 ] 130 [ 8 ] 1 [ 3 ] NO 1
7A-AS-1 104 HEATING WATER FULL FLOW TANGENTIAL 3 [ 75 ] 110 [ 7 ] 1 [ 3 ] NO 1
IN [mm] GPM [L/s] FT [kPa]
SIZE IN FLOW WPD
BUILT-IN STRAINER REQ'D
MARK LOCATION SYSTEM AND/OR SERVICE TYPE
AIR SEPARATOR
REMARKS
AIR SEPARATOR SCHEDULE
SD-6 LINEAR SLOT 140 [ 66 ] 500 [ 240 ] 0.270 [ 68 ] CEILING 24 x 5 [ 600 x 127 ] 10 ø [254 ø] 41 NONE --- 1, 2
SD-5 SUPPLY REGISTER 80 [ 38 ] 160 [ 76 ] 0.090 [ 23 ] DUCT 12 x 8 [ 600 x 600 ] 10 x 6 [406 ø ] 25 NONE WHITE 1, 2
SD-4 LOUVERED FACE 220 [ 100 ] 640 [ 300 ] 0.090 [ 23 ] CEILING 24 x 24 [ 600 x 600 ] 14 ø [356 ø ] 21 NONE WHITE 1, 2
SD-3 LOUVERED FACE 160 [ 76 ] 470 [ 220 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 12 ø [305 ø ] 19 NONE WHITE 1, 2
SD-2 LOUVERED FACE 110 [ 52 ] 380 [ 180 ] 0.090 [ 23 ] CEILING 24 x 24 [ 600 x 600 ] 10 ø [254 ø] 22 NONE WHITE 1, 2
SD-1 LOUVERED FACE 70 [ 33 ] 280 [ 130 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 8 ø [203 ø] 20 NONE WHITE 1, 2
CFM [L/s] CFM [L/s] IN WG [Pa]
MIN MAX
IN x IN [mm x mm] IN [mm ]
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKS
AIR DEVICE SCHEDULE (SUPPLY)
RG-5 PERFORATED 420 [ 200 ] 700 [ 330 ] 0.090 23.000 CEILING 24 x 24 [ 600 x 600 ] 16 DIAM [ 406 DIAM ] 16 NONE WHITE 1, 2
RG-4 PERFORATED 320 [ 150 ] 500 [ 240 ] 0.090 23.000 CEILING 24 x 24 [ 600 x 600 ] 14 DIAM [ 356 DIAM ] 14 NONE WHITE 1, 2
RG-3 PERFORATED 240 [ 110 ] 400 [ 190 ] 0.090 23.000 CEILING 24 x 24 [ 600 x 600 ] 12 DIAM [ 305 DIAM ] 12 NONE WHITE 1, 2
RG-2 PERFORATED 170 [ 80 ] 250 [ 120 ] 0.090 23.000 CEILING 24 x 24 [ 600 x 600 ] 10 DIAM [ 254 DIAM ] 14 NONE WHITE 1, 2
RG-1 PERFORATED 60 [ 28 ] 100 [ 47 ] 0.070 18.000 CEILING 24 x 24 [ 600 x 600 ] 6 DIAM [ 152 DIAM ] 13 NONE WHITE 1, 2
CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]
MIN MAXMARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKS
AIR DEVICE SCHEDULE (RETURN)
EG-2 PERFORATED 100 [ 47 ] 170 [ 80 ] 0.090 23.000 CEILING 24 x 24 [ 600 x 600 ] 8 DIAM [ 203 DIAM ] 13 NONE WHITE 1, 2
EG-1 PERFORATED 60 [ 28 ] 100 [ 47 ] 0.070 18.000 CEILING 24 x 24 [ 600 x 600 ] 6 DIAM [ 152 DIAM ] 13 NONE WHITE 1, 2
CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]
MIN MAXMARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKS
AIR DEVICE SCHEDULE (EXHAUST)
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE DAMPER IN BRANCH DUCT AS SHOWN ON PLANS.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE DAMPER IN BRANCH DUCT AS SHOWN ON PLANS.
7A-EF-1 ROOF CLC GENERAL EXHAUST 1100 [ 520 ] 0.5 [ 130 ] SINGLE WIDTH SINGLE INLET BACKWARD INCLINED I ARR 4, CW ROTATION, TH DISCHARGE 12 [ 300 ] 42% DIRECT 1770 0.25 0.25 [ ] 1 115 1000 CONSTANT 1, 3, 6
7A-SF-2 104 CLC 1-AHU-1 7600 [ 3600 ] 7.5 [ 1900 ] DOUBLE WIDTH DOUBLE INLET AIRFOIL II ARR 3, CW ROTATION, TH DISCHARGE 20 [ 500 ] 75% DIRECT 3600 17.9 20 [ 15 ] 3 460 1800 VARIABLE 1, 2, 4
7A-SF-1 104 CLC 1-AHU-1 7600 [ 3600 ] 7.5 [ 1900 ] DOUBLE WIDTH DOUBLE INLET AIRFOIL II ARR 3, CW ROTATION, TH DISCHARGE 20 [ 500 ] 75% DIRECT 3600 17.9 20 [ 15 ] 3 460 1800 VARIABLE 1, 2, 4
7A-RF-2 104 CLC RELIEF AIR 7600 [ 3600 ] 1.5 [ 380 ] INLINE CENTRIFUGAL BACKWARD INCLINED II ARR 9, INLINE, HORIZ. DISCHARGE 24.5 [ 610 ] 53% BELT 1063 3.5 5 [ 4 ] 3 460 820 VARIABLE 1, 2, 5
7A-RF-1 104 CLC RELIEF AIR 7600 [ 3600 ] 1.5 [ 380 ] INLINE CENTRIFUGAL BACKWARD INCLINED II ARR 9, INLINE, HORIZ. DISCHARGE 24.5 [ 610 ] 53% BELT 1063 3.6 5 [ 4 ] 3 460 820 VARIABLE 1, 2, 5
CFM [L/s] IN [Pa] IN [mm] BHP HP [kW]
TYPE WHEEL CLASS ARRANGEMENT, ROTATION, AND DISCHARGE
DIAMETER
MIN % EFF DRIVE FAN MAX RPM
NOMINAL POWER
PHASE VOLT RPM SPEED CONTROL
MARK LOCATION AREA AND/OR BLDG SERVED SYSTEM AND/OR SERVICE
AIR FLOW TSP
FAN MOTOR ELECTRICAL
CONTROL SEQUENCE REMARKS
FAN SCHEDULE
7A-HU-1 MECHANICAL ROOM 1-AHU1 ELEC-STEAM 9635 RO WATER 0.35 [0.02] 65 [18] 64.2 460 3 178 [ 500 ] 1
CFM GPM [L/s] °F [°C] KW VOLTS PHASE LBS/HR [kg/HR]
FLOW EWTMARK LOCATION SYSTEM AND/OR SEVICE HUMIDIFIER TYPE
AIR FLOW
SOURCE OF MAKEUP WATER
WATER CONDITIONS
ELECTRICAL HUMIDIFIER CAPACITY
REMARKS
STEAM HUMIDIFER SCHEDULE
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
NOTES:
1. THE COOLING COIL FIN SPACING SHALL NOT EXCEED 132 FINS PER FOOT [400 FINS PER METER].
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
Scale: No Scale
PRESSURIZATION MAP
1 ADDENDUM 1 6/29/2026
Docusign Envelope ID: EC0B67D1-8783-88BA-8137-1E253E84F1B1
6/29/2026
| Sheets |
| M-503 - MECHANICAL DETAILS |
| M-504 - MECHANICAL CONTROLS |
| M-601 - MECHANICAL SCHEDULES |
| 2026-06-29T20:29:42+0000 | |
| Digitally verifiable PDF exported from www.docusign.com |
File details come from the government source that posted it. Updated .