The system comprises an air handling unit with comprehensive control logic for cooling, heating, humidification, and epidemic mode operations. Key operational features include: discharge air pressure maintenance at 5" WG with critical zone reset strategy; chilled water valve modulation to maintain 55°F discharge air temperature in cooling mode; heating valve modulation when discharge air temperature drops below 52°F; outdoor air damper and return air damper modulation to maintain minimum outdoor air quantity; relief fan operation to maintain building pressurization at 0.01" WG; and enthalpy-based economizer control. The system includes humidification control with return air humidity modulation and high-limit humidity sensor at 30% relative humidity adjustable setpoint, with steam supply valve closure above 60°F outdoor air temperature. Safety controls include smoke detector integration, freeze protection with low-limit setpoint of 40°F, and high-pressure protection at 5" WG. Alarms are configured for dirty filters, temperature excursions, fan failures, excessive discharge static pressure, and condensate high level. The document also includes VAV terminal unit controls with continuous operation maintaining 75°F cooling and 70°F heating setpoints, zone damper modulation for occupied and unoccupied modes, and reheating coil valve control with high discharge air temperature limiting.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYSTEM:
CUSTOM VAV AIR HANDLER
7A-AHU-1
POINT
LEGEND
SYSTEM
OUTPUTS
BINARY
ANA-
LOG
BINARY ANALOG
SYSTEM INPUTS SYSTEM SOFTWARE/CONTROL
APPLICATION/FUNCTION
ALARM
PROCESSING
PAGE:
SYSTEM COMPONENT:
RETURN AIR TEMPERATURE
RETURN AIR HUMIDITY
MIXED AIR TEMPERATURE
PRE-HEAT TEMPERATURE
COOLING COIL TEMPERATURE
DISCHARGE AIR TEMPERATURE
DISCHARGE STATIC PRESSURE
DISCHARGE AIR HUMIDITY
OUTSIDE AIR TEMPERATURE
RELIEF FAN RF-1 STATUS
SUPPLY FAN STATUS
MIXED AIR LOW LIMIT
STATIC PRESSURE HIGH LIMIT
HUMIDITY HIGH LIMIT
SUPPLY FAN VSMC ALARM
RELIEF FAN RF-1 VSMC ALARM
DUCT SMOKE DETECTOR
RELIEF FAN RF-2 VSMC
SUPPLY FAN VSMC
RETURN AIR DAMPER
RELIEF AIR DAMPER
PREHEAT VALVE
COOLING VALVE
RELIEF FAN RF-1 START/STOP
SUPPLY FAN START/STOP
AIRFLOW MONITORING - RA
AIRFLOW MONITORING - OA
AIRFLOW MONITORING - SA
AI-1
AI-2
AI-3
AI-4
AI-5
AI-6
AI-7
AI-8
AI-9
BI-2
BI-4
BI-6
BI-7
BI-8
BI-9
BI-10
BI-12
AO-2
AO-3
AO-4
AO-5
AO-7
AO-8
BO-1
BO-3
FT-1
FT-2
FT-3
T-4
H-1
T-5
T-3
T-6
T-1
SP-1
H-2
T-2
CS-IT 1
CS-IT 3
TSL-1
SP-1
HL-1
ALA-SF
ALA-RF 1
SD
SPD-RF 2
SPD-SF
D-2
D-3
V-2
V-1
SST-RF 1
SST-SF
AF-1 / PSL
AF-2
AF-3
P O
IN
T
ID
A B
B R
E V
IA
T
IO
N
P R
IO
R
IT
Y
/A D
D A
L T E
R
-- -- -- -- -- -- --E L E
C T R
IC
D
E V
IC
E
S T A
R T /S
T O
P
O P
E N
/C L O
S E
S P
E E
D C
O M
M A
N D
V A
L V
E P
O S
IT
IO
N
D A
M P
E R
P O
S
IT
IO
N
S T A
T U
S A
L A
R M
P R
E S
S U
R E
H
IG
H H
U M
ID
IT
Y
H
IG
H S
T A
T
IC
P R
E S
S U
R E
L O
W T
E M
P E
R A
T U
R E
T E
M P
E R
A T U
R E
T I)
P R
E S
S U
R E
P O
S
IT
IO
N
F L O
W P
E R
C E
N T
S T A
T
IC
P R
E S
S U
R E
C A
R B
O N
M O
N O
X
ID
E
H U
M
ID
IT
Y
V A
C U
U M
L O
C A
L A
L A
R M
P A
N E
L
A R
E A
A L A
R M
P A
N E
L
M A
S T E
R A
L A
R M
P A
N E
L
H
IG
H L
IM
IT
L O
W L
IM
IT
S C
H E
D U
L E
S T A
R T /S
T O
P
F U
N C
T
IO
N D
U T Y
C Y C
L E
T E
M P
E
C O
N O
M
IZ
E R
E N
T H
A L P
Y E
C O
N O
M
IZ
E R
T E
M P
E R
A T U
R E
R E
S E
T
D E
M A
N D
L
IM
IT
IN
G
T E
M P
E R
A T U
R E
O V
E R
R
ID
E
S T A
T
IC
P R
E S
S U
R E
R E
S E
T
P R
E S
S U
R E
/V O
L C
O N
T R
O L
F A
IL
U
R E
M O
D E
S P
A C
E T
E M
P C
O N
T R
O L
F U
L L C
O M
M
IU
N
IC
A T
IO
N
T R
E N
D
IN
G
REMARKS
FULL COMMUNICATION
FULL COMMUNICATION
PRE-FILTER 1 BI-1 DPS-1
EF-1 STATUS
EXHAUST DAMPER POSITION
BI-5
BI-13
CS-IT 4
D-5
EF-1 START/STOP
EXHAUST DAMPER OPEN/CLOSE
BO-4
BO-5
SST EF 1
D-5
BI-17 SD-2
STEAM HUMIDIFIER
OUTSIDE AIR DAMPER
PRE-FILTER 2
AFTER FILTER
AO-9
AO-10
BI-14
BI-15
HU-1
D-1
DPS-2
DPS-3
BI-16 SD-1SMOKE DETECTOR 1
SMOKE DETECTOR 2
OUTSIDE AIR HUMIDITY AI-10 H-3
RELIEF FAN RF-2 START/STOP BO-2 SST-RF 2
RELIEF FAN RF-1 VSMC AO-1 SPD-RF 1 FULL COMMUNICATION
RELIEF FAN RF-2 VSMC ALARM BI-11 ALA-RF 2
RELIEF FAN RF-2 STATUS BI-3 CS-IT 2
RELIEF AIR DAMPER AO-6 D-4
RETURN AIR
PRESSURE SWITCH HIGH TO DISABLE
FAN WHEN HIGH PRESSURE LIMIT
SETPOINT IS REACHED (TYPICAL)
STEAM
HUMIDIFIER
STEAM PIPED FROM
ELECTRIC STEAM
HUMIDIFIER
SMOKE
DETECTOR
CHWR
CHWSV-2
LOCATE SENSORS
OUTSIDE UNDER SHIELD
OUTSIDE AIR
V-1
SUPPLY FAN
(2 FAN ARRAY)
SPS
SP-1
HHL
HL-1
HT
H-2
ZC
PSH
SD2
DPS
TT
T-1
SST
SF
HS
CS
IT-2
VFD
SPD
SF
TT
T-6
TT
T-3
TT
T-5
TSL
TSL-1
C O
IL
C O
O L
IN
G
C O
IL
P R
E H
E A
T
A F
T E
R -F
IL
T
E R
P R
E -F
IL
T
E R
-1
FT
AF-1
PSL
A F
M D
HT
H-1
TT
T4
TT
T-2
A F
M D
DPS
D-1
ZC
D-2
MT
P R
E -F
IL
T
E R
-2
DPS
ZC
D-3
FT
AF-2
RELIEF AIR
ZC
FT
AF-3
A F
M D
SUPPLY AIR TO
TERMINAL UNIT
CURRENT
TRANSMITTER FOR FAN
STATUS (TYP.)
SST
EF
VFD HS
SPD
EF
ALA
EF
COMM
IT-1
CS
1 2
HHWR
HHWS
ALA
SF
COMM
LOW PRESSURE SWITCH
SP-1 FT
AF-3
A F
M D
M
M
HT
H-3
SD1
SST
EF
VFD HS
SPD
EF
ALA
EF
COMM
IT-1
CS
RELIEF
FAN RF-1
ZC
D-4
RELIEF
FAN RF-2
RELIEF AIR
1. GENERAL FAN/TEMPERATURE CONTROL
1.1 COOLING-OCCUPIED/OVERRIDE: AHU'S WILL BE INTERLOCKED WITH ASSOCIATED AREA EXHAUST FANS, SO EACH EXHAUST FAN WILL OPERATE WHENEVER ITS ASSOCIATED AHU IS ENERGIZED. AHU SUPPLY FAN SPEED SHALL BE DETERMINED BY DISCHARGE AIR PRESSURE AND POLLING OF VAV BOX DAMPER POSITIONS. DISCHARGE AIR PRESSURE SHALL INCLUDE A "CRITICAL ZONE RESET STRATEGY" WHICH REDUCES DISCHARGE AIR PRESSURE UNTIL AT LEAST ONE ZONE VAV BOX DAMPER IS 90% OPEN. THE INITIAL AIR PRESSURE SETPOINT SHALL BE 5" WG (ADJUSTABLE). THE AHU RETURN AIR FAN SHALL BE INTERLOCKED WITH THE SUPPLY AIR FAN. THE RETURN AIR FAN SPEED OFFSET SHALL BE DETERMINED DURING THE INITIAL TAB WORK. AS SPACE PRESSURIZATION RISES ABOVE 0.01" WG, THE RELIEF AIR FAN SHALL START AND RESPECITVE DAMPER SHALL OPEN TO MAINTAIN SPACE PRESSURIZATION AT 0.01" WG (ADJUSTABLE). CHILLED WATER CONTROL VALVE SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE OF 55°F (ADJ). OUTDOOR AIR DAMPER AND RETURN AIR DAMPER SHALL MODULATE TO MAINTAIN A MINIMUM OUTDOOR AIR QUANTITY DURING OCCUPIED CYCLE AS SHOWN ON THE AIR HANDLING UNIT
SCHEDULE AS MEASURED BY AN AIRFLOW MEASURING STATION.
1.2 COOLING-UNOCCUPIED: SHALL OPERATE AS IN OCCUPIED MODE.
1.3 HEATING-OCCUPIED: AHU SUPPLY AIR FAN SHALL BE ENERGIZED AND RUN CONTINUOUSLY. OA FLOW WILL BE MAINTAINED AS DESCRIBED IN COOLING-OCCUPIED MODE ABOVE. WHEN DISCHARGE AIR TEMPERATURE DROPS BELOW 52°F, DISCHARGE AIR TEMPERATURE CONTROLLER THRU DDC CONTROL SHALL MODULATE THE HEATING VALVE TO MAINTAIN 55°F LEAVING AIR TEMPERATURE. THE CHILLED WATER VALVE SHALL BE FULLY CLOSED TO THE
COIL WHEN IN HEATING MODE.
1.4 HEATING-UNOCCUPIED: UNIT SHALL BE DE-ENERGIZED UNLESS THE AVERAGE OF THE ZONE TEMPERATURES FALLS BELOW THE SETBACK TEMPERATURE SETPOINT. THE OA AND EA DAMPER SHALL BE CLOSED.
1.5 TRANSITION FROM OCCUPIED TO UNOCCUPIED: AUTOMATICALLY THRU DDC CONTROL AND PRESET TIME SCHEDULE.
SYSTEM SHALL ALSO BE ABLE TO BE RETURNED TO OCCUPIED MODE FROM UNOCCUPIED MODE BY THE OPERATOR WORKSTATION. TRANSITION FROM COOLING TO HEATING SHALL OCCUR WHEN CHILLED WATER CONTROL VALVE IS
CLOSED AND DISCHARGE AIR TEMPERATURE FALLS BELOW 52°F.
2. HUMIDIFICATION MODE:
2.1 THE SUPPLY AIR HIGH LIMIT HUMIDITY SENSOR SETPOINT SHALL BE CAPABLE OF BEING ADJUSTED FROM EITHER THE
CENTRAL OR LOCAL ECC CONTROL PANEL.
2.2 THE RETURN AIR HUMIDITY SENSOR LOCATED IN THE RETURN AIR DUCT SHALL MODULATE THE HUMIDIFIER TO MAINTAIN THE SPACE HUMIDITY. THE HIGH LIMIT HUMIDITY SENSOR SHALL MODULATE THE HUMIDIFIER TO
MAINTAIN 30% ADJUSTABLE RELATIVE HUMIDITY IN THE SPACES.
2.3 THE OUTDOOR AIR TEMPERATURE SENSOR SHALL CLOSE OFF THE HUMIDIFIER STEAM SUPPLY VALVE WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE & OPEN THE HUMIDIFIER STEAM SUPPLY VALVE WHEN OUTSIDE AIR
TEMPERATURE IS BELOW 60°F.
3. EPIDEMIC MODE:
3.1 EPIDEMIC MODE SHALL BE MANUALLY INITIATED AT THE ECC. AHU SHALL OPERATE WITH 100% OUTDOOR AIR DURING
EPIDEMIC MODE AS FOLLOWS:
3.2 RETURN DAMPER SHALL MODULATE CLOSED WHILE THE OUTSIDE AIR DAMPER MODULATES TO FULL OPEN.
3.3 LEAD RELIEF FAN SHALL START AND MODULATE ITS SPEED TO MAINTAIN BUILDING PRESSURE TO OUTDOORS AT 0.01" W.G. PRESSURE MONITOR SHALL BE LOCATED IN SEATING 120. LAG RELIEF FAN SHALL START IF THE LEAD FAN FAILS
TO START AFTER 5 MINUTES (ADJ.).
3.4 PREHEAT COIL AND COOLING COIL VALVES SHALL MODULATE IN SEQUENCE TO MAINTAIN THE DISCHARGE AIR
TEMPERATURE FOR OCCUPIED MODE (SEE ABOVE).
4. ECONOMIZER:
4.1 A COMPARATIVE ENTHALPY ECONOMIZER STRATEGY SHALL BE UTILIZED. THE OUTSIDE AIR DAMPER SHALL MODULATE OPEN AND THE RETURN AIR DAMPER SHALL MODULATE CLOSED WHEN OA ENTHALPY IS LESS THAN
RETURN AIR ENTHALPY IN COOLING MODE.
5. SAFETY CONTROL/PROTECTION:
5.1 SMOKE DETECTOR SHALL BE PROVIDED BY FIRE ALARM CONTRACTOR. THROUGH DDC CONTROL IT SHALL DE-ENERGIZE THE ASSOCIATED AHU, ALL ASSOCIATED VAV SUPPLY AND EXHAUST FANS (INCLUDING INTERLOCKS), SIGNAL FIRE ALARM PANEL AND CLOSE THE OUTSIDE AIR DAMPER UPON THE DETECTION OF THE PRODUCTS OF
COMBUSTION.
5.2 FREEZE PROTECTION: IF HEATING WATER COIL DISCHARGE AIR TEMPERATURE FALLS BELOW 40°F DURING HEATING MODE, THE FREEZESTAT SHALL CLOSE THE OUTSIDE AIR DAMPER, DE-ENERGIZE THE AHU SUPPLY AIR FAN AND FULLY
OPEN THE PRIMARY STEAM AND CHILLED WATER VALVES TO COIL.
5.3 PRESSURE PROTECTION: A HIGH PRESSURE TRANSMITTER LOCATED AT THE SUPPLY FAN DISCHARGE SHALL
DE-ENERGIZE THE SUPPLY AIR FAN IF ITS SETPOINT, 5” WG, IS REACHED.
5.4 CONDENSATE HIGH LEVEL PROTECTION: IF CONDENSATE HIGH LEVEL SWITCH IS ACTIVATED, UNIT SHALL BE
DE-ACTIVATED AND AN ALARM INITIATED.
6. ALARMS:
6.1 ALARM FOR DIRTY FILTER WHEN PRESSURE DROP EXCEEDS 0.5” WG ABOVE INITIAL PRESSURE DROP. ALARM IF LEAVING AIR TEMPERATURE EXCEEDS 60°F IN COOLING MODE OR DROPS BELOW 50°F IN HEATING MODE. ALARM IF AHU SUPPLY OR EXHAUST AIR FAN FAILS TO START OR FAILS DURING OPERATION. ALARM IF UNIT DISCHARGE STATIC PRESSURE EXCEEDS 5” WG. ALARM IF CONDENSATE REACHES HIGH LEVEL. ALARM UPON SMOKE DETECTOR
ACTIVATION.
7. GRAPHICS AND MONITORING:
7.1 BAS FRONT END SYSTEM SHALL INCLUDE GRAPHICS SHOWING ALL HVAC SYSTEMS, ALARMS AND OTHER POINTS SHOWN ON THE DRAWINGS AND INCLUDED IN THE SPECIFICATIONS AND IN ACCORDANCE WITH VA REQUIREMENTS.
VFDS SHALL REPORT OPERATIONAL AND ALARM CONDITIONS TO THE BAS.
8. DDC PANELS:
8.1 PROVIDE NETWORK AREA CONTROL PANELS IN ACCORDANCE WITH THE SPECS TO BE LOCATED IN THE EXISTING
RESPECTIVE LOCATIONS TO SERVE AHUS, TERMINAL BOXES, AND OTHER EQUIPMENT.
DA
AO - REHEATING VALVE
HW
M
HWS HWR
T
AI - DISCHARGE AIR TEMP
AI - AIRFLOW
M
AO - ZONE DAMPER
SA
T AI - ZONE TEMP
AI - ZONE SETPOINT ADJUST
F
H AI - ZONE HUMIDITY
AI - ZONE HUMIDITYSETPOINT
VISIBLE ALARM
APPLY TO OPERATING
ROOMS ONLY
VAV TERMINAL UNIT
VARIABLE AIR VOLUME - TERMINAL UNIT
RUN CONDITIONS - CONTINUOUS:
THE UNIT SHALL RUN CONTINUOUSLY AND SHALL MAINTAIN:
• A 75°F (ADJ.) COOLING SETPOINT.
• A 70°F (ADJ.) HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER
DEFINABLE AMOUNT (ADJ.).
• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER
DEFINABLE AMOUNT (ADJ.).
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT
THE ZONE SENSOR.
PRESSURE INDEPENDENT VARIABLE VOLUME TERMINAL UNIT - FLOW CONTROL:
THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF THE
FOLLOWING:
OCCUPIED:
• WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL
MODULATE BETWEEN THE MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW
(ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE HEATING SETPOINT, THE
ZONE DAMPER SHALL MAINTAIN THE MINIMUM REQUIRED ZONE AIRFLOW (ADJ.).
• WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SETPOINT, THE CONTROLLER SHALL MODULATE
THE HEATING VALVE OPEN TO MAINTAIN THE ZONE TEMPERATURE AT ITS HEATING SETPOINT.
ADDITIONALLY, IF WARM AIR IS AVAILABLE FROM THE AHU, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM HEATING AIRFLOW (ADJ.) UNTIL
THE ZONE IS SATISFIED.
UNOCCUPIED:
• WHEN THE ZONE IS UNOCCUPIED THE ZONE DAMPER SHALL CONTROL TO ITS MINIMUM UNOCCUPIED
AIRFLOW (ADJ.).
• WHEN THE ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL
MODULATE BETWEEN THE MINIMUM UNOCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW
(ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN ZONE TEMPERATURE IS LESS THAN ITS UNOCCUPIED HEATING SETPOINT, THE CONTROLLER SHALL MODULATE THE HEATING VALVE OPEN TO MAINTAIN THE ZONE TEMPERATURE AT THE SETPOINT.
ADDITIONALLY, IF WARM AIR IS AVAILABLE FROM THE AHU, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM UNOCCUPIED AIRFLOW (ADJ.) AND THE AUXILIARY HEATING AIRFLOW (ADJ.)
UNTIL THE ZONE IS SATISFIED.
REHEATING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE REHEATING COIL VALVE
OPEN ON DROPPING ZONE TEMPERATURE TO MAINTAIN ITS HEATING SETPOINT.
REHEATING - HIGH DISCHARGE AIR TEMPERATURE LIMIT:
THE CONTROLLER SHALL MEASURE THE DISCHARGE AIR TEMPERATURE AND LIMIT HOT WATER VALVE POSITION IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 15°F (ADJ.) ABOVE THE ZONE TEMPERATURE.
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 100°F (ADJ.).
• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 50°F (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH HUMIDITY: IF THE SPACE RELATIVE HUMIDITY RISES ABOVE 60% A VISIBLE ALARM SHALL BE
INITIATED IN THE AFFECTED OR AND AT THE DDC MONITORING STATION.
POINT NAME:
ZONE TEMPERATURE
ZONE TEMPERATURE SETPOINT
AIRFLOW
DISCHARGE AIR TEMPERATURE
ZONE DAMPER
REHEATING VALVE
MAXIMUM OCCUPIED AIRFLOW SETPOINT
HEATING MODE
HEATING SETPOINT
COOLING SETPOINT
HIGH ZONE TEMPERATURE
LOW ZONE TEMPERATURE
HIGH DISCHARGE TEMPERATURE
LOW DISCHARGE TEMPERATURE
HARDWARE POINTS
AI AO
X
X
X
X
BI BO
SOFTWARE POINTS
AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
TOTAL HARDWARE (8) TOTAL SOFTWARE (21)
6 2 3
X
X
X
X
12 5 13
X
X
X
X
X
X
HIGH ZONE HUMIDITY
MINIMUM OCCUPIED AIR FLOW SETPOINT
MINIMUM UNOCCUPIED AIRFLOW SETPOINT
ZONE HUMIDITY
ZONE HUMIDITY SETPOINT
X
X
X
X
X
X
X
X
X
X
X
X X
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:3
:4
P
M C
U s e rs \w s h ip le y \D o c u m e n ts
\M P
-0
-V
A J a c k s o n -C o n s tr u c t C
L C
R w s h ip le y .r v t
M-504
MECHANICAL CONTROLS
13 15PRP
CLC RESIDENTIAL
NEIGHBORHOOD
G.V. MONTGOMERY VAMC
1500 E. WOODROW WILSON AVENUE
JACKSON, MS 39216 JUNE 23, 2025
100% CONSTRUCTION DOCUMENTS
586-40123-060
7A
WRS
Scale: No Scale
7A-AHU-1 POINTS LIST
Scale: No Scale
7A-AHU-1 SCHEMATIC
Scale: No Scale
7A-AHU-1 SEQUENCE OF OPERATIONS
Scale: No Scale
VAV TERMINAL SCHEMATIC
Scale: No Scale
VAV TERMINAL SEQUENCE OF OPERATION
Scale: No Scale
VAV TERMINAL UNIT CONTROLS
1 ADDENDUM 1 6/29/2026
Docusign Envelope ID: EC0B67D1-8783-88BA-8137-1E253E84F1B1
6/29/2026
| Sheets |
| M-503 - MECHANICAL DETAILS |
| M-504 - MECHANICAL CONTROLS |
| M-601 - MECHANICAL SCHEDULES |
| 2026-06-29T20:29:42+0000 | |
| Digitally verifiable PDF exported from www.docusign.com |
File details come from the government source that posted it. Updated .